1 Static vs. Dynamic Contact Resistance
Transcript of 1 Static vs. Dynamic Contact Resistance
Page 1
Static vs. Dynamic Contact [email protected]
© OMICRON
1
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
According to IEC 62271-100 and ANSI C37.100-1992 a circuit breaker is a mechanical switching device,
capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying
for a specified time and breaking currents under specified abnormal conditions such as short circuit.
Page 2
What is a circuit breaker?
Definition of a circuit breaker
Automatically operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit
Basic function: immediately discontinues electrical flow
Page 2
Ideal switch
making carrying breaking
© OMICRON
© OMICRON Academy
01-Introduction-CBR-testing
The main task of a circuit breaker is to interrupt operational + fault currents and to isolate faulty parts such as
overhead lines, cables, transformers, generators, etc. from the system. Hence a circuit breaker has a dynamic
behavior (breaking and making operational and fault currents) and a static behavior (carry operational currents
and insulating HV parts to ground).
In regards to the current the wording "break" and "make" is used whereas in regards to the action "open" and
"close" is used.
A circuit breaker is controlled by the protection device of the corresponding asset and the SCADA system
which allows controlling the grid by remote.
Page 3
What is a circuit breaker?
Static behavior
Carry operational currents
Insulating HV parts to ground
Isolating faulted parts to the grid (in case the breaker is open)
Dynamic behavior
Breaking and making operational currents
Breaking and making fault currents (fault clearance)
Page 3
© OMICRON
© OMICRON Academy
01-Introduction-CBR-testing
Depending on location of in the electrical network, network design and region several design of circuit
breakers are common – which is discussed in later more in detail. All of them consist of following three main
components
Interrupter unit(s)
Support insulator
Operating mechanism & control unit
Page 4
Overview components
Example: Live-Tank circuit breaker
Page 4
Interrupter unit(s)
Breaking chamber, interrupter chamber, interrupter housing, etc.
Contains interrupter, interrupting medium
Support insulator
Line-to-ground insulator
Contains insulated pull-rod, mechanical linkage, insulating medium
Operating mechanism & control
Stored energy, secondary wiring
© OMICRON
© OMICRON Academy
01-Introduction-CBR-testing
The trip or close command from any control device is forwarded to the circuit breakers' main contacts via the
functional chain. The functional chain consists of the following parts:
Control: This is the control device of the circuit breaker, e.g. the protection device. For HV circuit breakers this
part is not included directly in the circuit breaker. But some MV breakers are equipped with the protection
device itself.
Operating mechanism: Coils, armatures and the drive itself (spring, hydraulic, pneumatic, magnetic)
Mechanical linkage: Linkage between the drive and the interrupter. In order to obtain synchronicity of the
breaker's main contacts the mechanical linkage can be tuned via screws.
Interrupter: Main contacts of the circuit breaker
Page 5
Circuit breaker components
Components
Page 5
ControlIn
terr
up
ter
Mech
an
ical
lin
kag
e
Operating
mechanism
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
Page 6
Typical test on circuit breakers?
Performance of control circuits
Coil current profile analysis
Under- & overvoltage tests
Pick-up tests
Page 6
Control
Inte
rru
pte
rM
ech
an
ical
lin
kag
e
Operating
mechanism
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
Page 7
Typical test on circuit breakers?
Test performance of charging motor
Motor current analysis
Current trace
Inrush current
Charging time
Under- & overvoltage tests
Page 7
Control
Inte
rru
pte
rM
ech
an
ical
lin
kag
e
Operating
mechanism
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
Page 8
Typical test on circuit breakers?
Test performance of kinematic chain
Timing of main and auxiliary contacts
Contact travel (motion) of main contacts
Page 8
Control
Inte
rru
pte
rM
ech
an
ical
lin
kag
e
Operating
mechanism
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
Page 9
Typical test on circuit breakers?
Identify contact wear and tear of main and arcing contacts
Static Contact Resistance
Dynamic Contact Resistance
Page 9
Control
Inte
rru
pte
rM
ech
an
ical
lin
kag
e
Operating
mechanism
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
One very common and “simple” test is the static contact resistance test.
It is done to check the status of the main contact (and/or also bus bar junctions)
The test is done when breaker is closed using the four-point resistance measurement method. This is done to
exclude the resistance from test leads in the end value.
For the analysis, the resistance value is checked against the manufacturer specifications, comparing the
values between the phases and with the previous results if available.
Page 10
Contact wear and tear of main contacts
Static Contact Resistance
Page 10
© OMICRON
Motivation
Check the status of the main contact/bus bar junctions
The ability to carry the rated current without big losses
Analysis
Resistance value
Typical value between 10 to 100 [µΩ]
Comparing to previous results
High variations between phases
Measurement done
Using the four-point resistance measurement method
Injection current level
50[A] (IEC)
100[A] (ANSI)
© OMICRON Academy
04a-Methods-MV-HV-breakers
Principle
The principle of contact resistance measurement (µΩ meter test) is to measure the resistance in static
position: breaker closed.
A high current is injected between the breaking elements (direction of line) and measure the voltage drop
(line-ground). As the contact resistance is in µΩ- range a 4-wire measurement has to be applied, as otherwise
the resistance of the test leads (mΩ- range) falsify the results.
Conventional method
Disadvantage of using conventional units is the confusingly wiring effort for breakers with several interrupting
units. Connection mistakes are highly possible. Furthermore the measurement can be affected due to long
connection leads → inductive loop (antenna).
Method with CIBANO
The usage of contact modules CB MC2 reduces the effort and complexity of wiring. The screened Ethernet
cables for power supply (Power over Ethernet = PoE) and data communication to CIBANO 500 main unit are
not affected by noise.
Page 11
Contact wear and tear of main contacts
Static/contact resistance test (µΩ)
Micro-ohm (µΩ) meter
Validates resistance of primary path
Ensures low losses of load current
Can be used for circuit breakers, bus bar joints, etc.
Measurement method
Inject a high current
Measure small voltage in a noisy environment
Use 4-wire technique for connection
Unique CIBANO 500 features
Same wiring setup as for the timing test
Short lightweight high-current cables
Eliminate capacitive interference
Allow easy wiring setup
Page 11
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
Page 12
Performance of trip and close components
Dynamic Contact Resistance (DRM)/Timing test
Page 12
© OMICRON
Motivation
Check the timing to ensure a safe and reliable circuit breaker operation
Checking the arcing contact wear
Often together with contact travel
Check misalignment and/or wrong assembly in the interrupter
Analysis
Operating times & Synchronicity
per phase and between phases
Resistance curves
Comparing to previous results
Contact wipe
Arcing contact length
Comparing to previous results
Measurement done
Using four-point resistance measurement method
Different sequences possible
O, C
OC (reclose)
CO (trip-free)
O-CO (auto-reclosing)
© OMICRON Academy
04a-Methods-MV-HV-breakers
What are arguments for performing a Dynamic Resistance Measurement (DRM) instead of a conventional
Static Contact Resistance measurement? Well it may become quite obvious comparing the sequences of a
circuit breaker operation with the jump of a motocross racer in the picture shown above.
Static Contact Resistance does only provide us an insight of the main contacts condition (resistance) in
defined open and close state. Represented by picture 1 = takeoff (open) and picture 9 = landing (close).
Dynamic Contact Resistance allows us to have a better insight of the main contacts condition (resistance)
during whole process of the movement. This allows us to see the condition of the arcing but also main
contacts providing information of resistance, timing and motion/travel (represented by picture 1+ picture 2 + ...
picture 9).
Page 13
Contact wear and tear of main contacts
Why Dynamic contact resistance (DRM)?
Static Resistance Measurement = pic 1 + pic 9
Dynamic Resistance Measurement = pic 1 + pic 2 + ..... + pic 9
Page 13
2
3456
78
91
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
A dynamic contact resistance measurement is a commonly used method, because it determines the contact
length without having to disassemble the circuit breaker.
When the arcing contact becomes shorter than the minimum requirement specified by the circuit breaker
manufacturer, a safe operation can no longer be guaranteed and the interrupter unit needs to be maintained
properly.
In order to apply that method it is important to know the components of an SF6 circuit breaker interrupter unit
and how the current is interrupted during an open operation
Principle
The principle of Dynamic Resistance measurement (DRM) is to combine all information contact resistance,
timing, coil currents and travel (motion) into one diagram for the different operations. Thereby the whole
operation can be analyzed to find out arcing problems (e.g. bouncing), contact finger problems.
Method with CIBANO
For DRM measurement CIBANO 500 main unit, contact modules CB MC2 and transducer note CB TN3 is
used. No re-wiring needed!
Page 14
Contact wear and tear of main contacts
Dynamic contact resistance (DRM)
Records contact resistance during breaker operation (resistance over time)
Combination of contact resistance, timing and travel measurements
Use DRM to find outThe arcing contact length
Contact finger problems
Lubrication problems
ProcedureInject high current
Start recording current and voltage
Operate circuit breaker
Calculate resistance
Page 14
Contact travel
Main contact
Arcing contact length
Separation of
main contact
Arcing contact
is seperated
Resistance
Start of
contact travel
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
Analyze the conductive integrity of the main contacts in closed position.
When the circuit breaker is and stays in the closed position, the current injected flows through the main
contact because it has an ohmic resistance, most of the times, lower than 100μΩ. However the arcing contact
has an ohmic resistance much higher than 100μΩ.
Page 15
Contact wear and tear of main contacts
Dynamic contact resistance (DRM)
Page 15
Closed position Arcing Open position
7 Stationary main contact2 Stationary arcing contact
3 Moving arcing contact 8 Moving main contact
Idc R<100μΩ R>>100μΩ
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
When the main contact is already opened but the arcing contact stays closed, the current injected will flow
through the arcing contact.
Tungsten copper (WCu) materials are used for arcing contacts in SF6 circuit breakers for high and medium
voltage applications. At the heart of the switching chamber, WCu arcing contacts are exposed to extreme
mechanical and thermal stresses, with temperatures ≥ 20,000 K being reached during arcing.
Tungsten-copper has unique material properties. A high level of temperature resistance is one of the most
important advantages of tungsten, while the copper content increases the electrical and thermal conductivity.
Page 16
Contact wear and tear of main contacts
Dynamic contact resistance (DRM)
Page 16
Closed position Arcing Open position
7 Stationary main contact2 Stationary arcing contact
3 Moving arcing contact 8 Moving main contact
Idc R<100μΩ R>>100μΩ
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
Above example shows a Dynamic Resistance Measurement on Open [O] operation. Overlaying the
information of contact resistance and travel (motion) over time allows to refer to the arcing contact length.
Page 17
Contact wear and tear of main contacts
Dynamic contact resistance (DRM)
Page 17
Source: SIEMENS
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
Animated Open [O sequence
Circuit breaker in closed position. The trip (open) command is send and energizing the coil (black).
Once the energy is enough the latch hits the trigger, releasing the stored energy in the spring and the
armature starts to move. Until here the main contact is still is still carrying the operational currents. In the
same time SF6 is compressed in the puffer volume
Until the main contact is separated and the arcing contacts is taking over. The arcing contacts separate and
arcing is taking place and the arc and the arc extinguishing process starts. The arcing can be easily seen in
the resistance recorded over time as the resistance value is no more stable.
The arcing is taking as long the arc is fully extinguished. The measured resistance is now very high
impendent. The coil current is interrupted by the auxiliary contact and the armature moves until it’s end
position.
Page 18
Contact wear and tear of main contacts
Dynamic contact resistance (DRM)
Page 18
Source: SIEMENS
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
Same sequence explained on a cutaway example.
Page 19
Contact wear and tear of main contacts
Dynamic contact resistance (DRM)
Page 19
© OMICRON
© OMICRON Academy
04a-Methods-MV-HV-breakers
With CIBANO 500, OMICRON has introduced the first ever 3-in-1 test system that can be used to test all
types of circuit breakers: medium- and high-voltage breakers with live- or dead-tank design. CIBANO 500
is unique in that it combines a micro-ohmmeter, timing analyzer, and circuit breaker supply in just one system.
This enables both standard tests, such as contact resistance measurement and switching time
analysis, as well as advanced tests, such as motion analysis and dynamic resistance measurement, to be
carried out with ease.
Thanks to the integrated circuit breaker supply, the user is able to freely adjust DC voltage with CIBANO 500
as well as simulate a circuit breaker supply with undervoltage without having to change the cabling. Thus it is
possible to test the circuit breaker during the commissioning of switchgear systems where no station battery is
available.
Page 20
CIBANO 500: 3-in-1 circuit breaker test system
Multi-channel timing and travel analyzer
Checks the mechanical performance
Detects problems during coil actuation
Reveals defects of the trip or close coils
High-accuracy micro-ohm (µ) meter
Assesses the condition of the main and arcing contacts and resistor switches
Powerful coil and motor supply of 2.4 kW
Applies a stable DC voltage level to the breaker, even if a station battery is not available
Page 20
Timing and travel analyzer
Digital micro-ohm-meter
Coil and motor supply of 2.4 kW
© OMICRON
07a-Hardware-CIBANO-500+accessories
© OMICRON Academy
The accessories main contact module CB MC2 and transducer node CB TN3 are powered via PoE+ (Power
over Ethernet) by the main device CIBANO 500. Over the EtherCAT® interface power supply and data
commination realized where a number of units can be connected as the based on serial bus technology.
Page 21
Functional scheme
CIBANO 500 Hardware OverviewPage 21
© OMICRON
CB
MC
2
Digital
transmission
CIBANO 500
© OMICRON Academy
07a-Hardware-CIBANO-500+accessories
The idea of main contact module CB MC2 is too minimize the wiring effort by using one module for each
phase of circuit breaker. By having 2 current output and 2 voltage measurement inputs using short cables can
be used to measure contact resistance, dynamic resistance measurement and timing tests.
The main advantage is that for all test no re-wiring is required and all wires are clearly visible arranged.
Page 22
Main contact module CB MC2
2 high-current outputs and 2 sensitive voltage measurement channels
Output power source: powerful “super-capacitor”
Same wiring set-up for all circuit breaker tests: no time-consuming rewiring necessary
Overall wiring minimized and clearly arranged
Short high-current cables: easier and faster measuring set-up
Light-weight digital connection cables between CB MC2 modules and CIBANO 500: transmission of measuring results without interference
Powered via PoE+ (Power over Ethernet)
Page 22
© OMICRON
© OMICRON Academy
07a-Hardware-CIBANO-500+accessories
Current output 1x 200A in case of a connecting to a CB with one interrupter unit
2x 100A in case of connecting of a connecting to a CB with two interrupter
unit
Voltage input 2x voltage input, one for each interrupter unit of a CB with two interrupter
units
Visualization LED Indicating the status to identify which unit connected to which phase
EtherCAT® interface power supply and data communication with CIBANO 500 main device
Page 23
Main contact module CB MC2Page 23
2x 100 A DC
current output to
interrupting unit
2x voltage/
binary input
voltage inputs
Visualization LED
status indication
EtherCAT® with PoE+
to CIBANO 500 main unit
© OMICRON
© OMICRON Academy
07a-Hardware-CIBANO-500+accessories
Here a standard connection example of 3-phase SF6 Live-Tank Circuit breaker (ganged operation) shown.
Important: first always ground all interrupter units from both sides (to busbar and asset to be protected). For
each phase (with two interrupter units) on CB MC2 is connected. Use one CB TN3 and connect all 3
transducers (rotary/linear).
Connections of trip/close coils, motor and auxiliary has to be done depending on the wiring diagram of the
circuit breaker control.
Page 24
Connection concept
Live-Tank circuit breaker
Grounding on both sides of the interrupter unit
CIBANO 500 + 3 x CB MC2 : all tests on 3-phase circuit breakers with one or two interrupters
© OMICRON
Page 24
Page 24
CIBANO 500
CB MC2
CB MC2
CB MC2CB MC2
06a-Performing-MV-HV-breakers
© OMICRON Academy
Page 25
Case study – NorwaySF6 Live tank CB, condition assessmentTime-optimized circuit breaker diagnostics with CIBANO 500
© OMICRON
25
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
Inspection was scheduled for this 315kV Live-tank SF6 breaker during maintenance. Both measurement files
are in the chapter 10. Practical exercises:
2014-09-10_DRM-Norway-before-maintenance.ptm
2014-09-15_DRM-Norway-after-maintenance.ptm
Page 26
Details about breaker
315 kV Live-tank SF6 breaker
Manufacturing year 1986
Rated current 3,15 kA
Rated s.c. current 40,0 kA
Pole operation ganged
Operating mechanismpneumatic
Page 26
© OMICRON
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
Page 27
Function principle
Interrupter unit – cutaway view
Page 27
© OMICRON
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
The results of contact resistance measurement doesn’t provided much insight in the condition of the main &
arcing contacts. Just a deviation of the resistances in close position observed between the phases L1, L2, L3.
But no further assumptions can be made based on this results.
Page 28
Condition assessment // 2014-09-10
Contact resistance measurement
Page 28
© OMICRON
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
First timing measurement for Close operation doesn’t provide much information so far.
Page 29
Condition assessment // 2014-09-10Page 29
© OMICRON
Timing Close [C]
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
Same for timing measurement in open cycle.
Page 30
Condition assessment // 2014-09-10
Timing Open [O]
Page 30
© OMICRON
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
Another DRM measurement on open sequence indicates that the second interrupter unit in shows
discontinuity of the arcing contacts which would lead to heavy arcing.
Page 31
Condition assessment // 2014-09-10
DRM Open [O] – resistances
Page 31
© OMICRON
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
As a result of the DRM results it was decided to take the interrupter unit to the workshop for inspection and
maintenance. Especially on the right picture heavy arcing can be observed on the main contacts at the
location of the contact fingers.
Page 32
Before maintenance
Main contacts
Page 32
© OMICRON
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
As well the female arcing contact showed heavy wear.
Page 33
Before maintenancePage 33
© OMICRON
Arcing contact
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
Main contact was completely renewed and the arcing contact polished.
Page 34
After maintenance
Main and arcing contact
Page 34
© OMICRON
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
After re-building the interrupter units and assembling back the breaker the measurement was repeated. The
contact resistance measurement shows now equal resistance in close positon after maintenance in all 3 poles.
Page 35
After maintenance // 2014-09-15
Contact resistance measurement
Page 35
© OMICRON
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
Repeating the DRM measurements in open position show proper performance when the arcing contact is
taking over the current flow from the main contact. No interruption any more!
Page 36
After maintenance // 2014-09-15Page 36
© OMICRON
DRM Open [O] – resistances
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
Same measurement with view of currents over time instead of contact resistance.
Page 37
After maintenance // 2014-09-15
DRM Open [O] – currents
Page 37
© OMICRON
© OMICRON Academy
12a-Case-study-DRM-HV-breaker
© OMICRON Academy Page 38
Assessment examplesTime-optimized circuit breaker diagnostics with CIBANO 500
© OMICRON
38
09-Assessment-CBR-measurements
Page 39
Case study 1 – Assessment Timing vs DRM Page 39
© OMICRON
© OMICRON Academy
09-Assessment-CBR-measurements
Page 40
Case study 1 – Assessment Timing vs DRMPage 40
© OMICRON
© OMICRON Academy
09-Assessment-CBR-measurements
This dynamic resistance measurement during opening of the circuit breaker shows that the main contact could
have something. Normally when the movement starts there will be a small change in the resistance due to
friction and a bigger increase of the resistance when the transaction from main contact to arcing contact takes
place, but in this case the bigger change is taking place immediately when the contact travel starts. This
indicates that there is either a contact problem i.e. loose main contacts (fingers) or the main contact has
contamination on the surface due to wear. But it could also be that the clamps are not correct mounted and
are moving due to the vibration during operation.
Page 41
Case study 1 – Assessment Timing vs DRMPage 41
© OMICRON
Start of contact travel
Main contact is separated
© OMICRON Academy
09-Assessment-CBR-measurements
Page 42
Case study 2 – Assessment Timing vs DRMPage 42
© OMICRON
© OMICRON Academy
09-Assessment-CBR-measurements
The dynamic resistance measurement during closing of the circuit breaker shows that the contamination of the
main contact surface can be excluded as the behavior is continuing also after that the main contact has reach
it end position. This indicates more in direction loose main contacts (fingers) or badly mounted clamps.
Page 43
Case study 2 – Assessment Timing vs DRMPage 43
© OMICRON
© OMICRON Academy
09-Assessment-CBR-measurements
This dynamic resistance measurement during opening of the circuit breaker shows that the main contact for
phase LB has something. In this measurement the resistance change is small when the contact travel starts
(due to friction), which is okay, but when the transaction from main contact to arcing contact takes place the
resistance value starts to have high peaks until the arcing contact is opened. This indicates that there is
probably a contact problem e.g. arcing contact in bad condition due to wear. The next slides shows the same
even clearer when the current trace is enabled instead.
Page 44
Case study 2 – Assessment with DRMPage 44
© OMICRON
Phase B: worn out arcing contact?
© OMICRON Academy
09-Assessment-CBR-measurements
Above DRM measurement on a SF6 MV Circuit breaker shows a good example of discontinuity of one phase.
For a short moment the main contact losses continuity before the arcing contact is taking over which can lead
to serious arcing and heavy wear off the main contacts.
Measurement of contact resistance in both states open-close would show any problem.
09 - Assessment examples Page 46
Case study 3 – Assessment with DRM
Example 1: SF6 MV CB – discontinuity of main contact
Page 46
Source: Schneider Electric
discontinuity
on red phase
© OMICRON
09-Assessment-CBR-measurements
Above shows the same before on an Open sequence and corresponding DRM measurement but just
animated.
09 - Assessment examples Page 47
Case study 3 – Assessment with DRM
Example 1: SF6 MV CB – discontinuity of main contact
Page 47
coil current (A)
travel (mm)
DRM (Ω)
Video: Schneider Electric
© OMICRON
09-Assessment-CBR-measurements