1 HVACR415 – Mechanical for Air Conditioning System Recovery.

31
1 HVACR415 – Mechanical for Air Conditioning System Recovery

Transcript of 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

Page 1: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

1

HVACR415 – Mechanical for Air Conditioning

HVACR415 – Mechanical for Air Conditioning

System RecoverySystem Recovery

Page 2: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

2

RecoveryRecovery

• All recovery machines are different. Make sure you read the operation manual for the machine you are using.

• Using a machine in the wrong manner can cause equipment damage and personal injury.

• Safety glasses must be worn at all times.

• All recovery machines are different. Make sure you read the operation manual for the machine you are using.

• Using a machine in the wrong manner can cause equipment damage and personal injury.

• Safety glasses must be worn at all times.

Page 3: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

3

THE 3 R’STHE 3 R’S

• The three R’s of protecting the environment are:– Recovery– Recycling– Reclamation

• The three R’s of protecting the environment are:– Recovery– Recycling– Reclamation

Page 4: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

4

Recovery GuidelinesRecovery Guidelines

• Refrigerant should be recovered from a system as a liquid.– This is quicker and easier.– Recovering as a vapor will take considerably

longer.

• Refrigerant hoses should be good quality and have good sealing gaskets.

• Refrigerant should be recovered from a system as a liquid.– This is quicker and easier.– Recovering as a vapor will take considerably

longer.

• Refrigerant hoses should be good quality and have good sealing gaskets.

Page 5: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

5

Recovery GuidelinesRecovery Guidelines

• Some recovery units may require a warm-up period of up to 10 minutes.

• Read all information regarding the recovery units you are using.

• Some recovery units may require a warm-up period of up to 10 minutes.

• Read all information regarding the recovery units you are using.

Page 6: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

6

RecoveryRecovery

• Recovery is defined by the EPA as:– To remove refrigerant in any condition from a

system and store it in an external container without necessarily testing or processing it in any way.

• Refrigerant recovered can be re-used in the same system.

• Refrigerant recovered can be re-used in a different system if owned by the same owner.

• Recovery is defined by the EPA as:– To remove refrigerant in any condition from a

system and store it in an external container without necessarily testing or processing it in any way.

• Refrigerant recovered can be re-used in the same system.

• Refrigerant recovered can be re-used in a different system if owned by the same owner.

Page 7: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

7

RecoveryRecovery

• Per the EPA refrigerant that has been recovered can not be sold to another customer unless it meets new refrigerant specifications under ARI-700.

• Per the EPA refrigerant that has been recovered can not be sold to another customer unless it meets new refrigerant specifications under ARI-700.

Page 8: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

8

RecyclingRecycling

• Recycling Refrigerant is defined as:– To clean the refrigerant by oil separation and

single or multiple passes through devices such as replaceable core filter dryers.

• The filter dryers reduce moisture, acid, and particulate matter.

• Recycling means to clean up the refrigerant.

• Recycling Refrigerant is defined as:– To clean the refrigerant by oil separation and

single or multiple passes through devices such as replaceable core filter dryers.

• The filter dryers reduce moisture, acid, and particulate matter.

• Recycling means to clean up the refrigerant.

Page 9: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

9

ReclaimReclaim

• Reclaiming refrigerant is defined as:– Processing refrigerant to new product

specifications by means that may include distillation.

• This requires chemical analysis of the refrigerant.

• The refrigerant is processed to new refrigerant standards.

• Reclaiming refrigerant is defined as:– Processing refrigerant to new product

specifications by means that may include distillation.

• This requires chemical analysis of the refrigerant.

• The refrigerant is processed to new refrigerant standards.

Page 10: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

10

ReclaimReclaim

• Refrigerant that is reclaimed may be sold without hefty excise taxes. This is an incentive to save and reclaim old refrigerant.

• Refrigerant that is reclaimed may be sold without hefty excise taxes. This is an incentive to save and reclaim old refrigerant.

Page 11: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

11

Recovery TechniquesRecovery Techniques

• Active Recovery– Uses a dedicated compressor in the machine to

move the refrigerant.– Can be done on a system with a bad or missing

compressor.

• Active Recovery– Uses a dedicated compressor in the machine to

move the refrigerant.– Can be done on a system with a bad or missing

compressor.

Page 12: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

12

Recovery TechniquesRecovery Techniques

• Passive Recovery– System dependent - systems compressor must

be operational.– Passive recovery uses the systems compressor

to move the refrigerant.

• Passive Recovery– System dependent - systems compressor must

be operational.– Passive recovery uses the systems compressor

to move the refrigerant.

Page 13: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

13

Recovery TechniquesRecovery Techniques

• Piercing Valves– You are required to recover refrigerant even in a

hermetic (sealed) system with no access valves or fittings.

– When servicing a sealed system you can not just cut the pipe and let the refrigerant out.

• Piercing Valves– You are required to recover refrigerant even in a

hermetic (sealed) system with no access valves or fittings.

– When servicing a sealed system you can not just cut the pipe and let the refrigerant out.

Page 14: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

14

Page 15: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

15

Recovery TechniquesRecovery Techniques

• Piercing Valves (cont)– A piercing valve will clamp onto the line and

allow you to recover refrigerant so the system can be serviced.

– Piercing valves are temporary and can not be left on a system as they leak.

– Install a permanent valve while system is empty.

• Piercing Valves (cont)– A piercing valve will clamp onto the line and

allow you to recover refrigerant so the system can be serviced.

– Piercing valves are temporary and can not be left on a system as they leak.

– Install a permanent valve while system is empty.

Page 16: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

16

Recovery StepsRecovery Steps

• Step 1:– Get all equipment together.– You need:

• Gauges• Extra hose• Recovery Cylinder• Scale• Recovery Machine

• Step 1:– Get all equipment together.– You need:

• Gauges• Extra hose• Recovery Cylinder• Scale• Recovery Machine

Page 17: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

17

Recovery StepsRecovery Steps

• Step 1 (Continued)– Net Refrigerant is found with the following

formula:

W.C.___X 0.8 = ____80% Liquid level                       +____ T.W.                 ____ Total Capacity weight

– W.C. and T.W. is stamped on the handle of the cylinder

– Do not overfill. These cylinders can explode.

• Step 1 (Continued)– Net Refrigerant is found with the following

formula:

W.C.___X 0.8 = ____80% Liquid level                       +____ T.W.                 ____ Total Capacity weight

– W.C. and T.W. is stamped on the handle of the cylinder

– Do not overfill. These cylinders can explode.

Page 18: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

18

Page 19: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

19

Recovery StepsRecovery Steps

• Step 2:– Connect your gauges to the equipment.– Red Hose (High Side) goes to the high side of the

equipment (Liquid Line)– Blue Hose (Low Side) goes to the low side of the

equipment (Suction Line)– Make sure all gauge valves are closed.

• Step 2:– Connect your gauges to the equipment.– Red Hose (High Side) goes to the high side of the

equipment (Liquid Line)– Blue Hose (Low Side) goes to the low side of the

equipment (Suction Line)– Make sure all gauge valves are closed.

Page 20: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

20

Recovery StepsRecovery Steps

• Step 3– Connect the recovery machine.– Middle hose (yellow) from your gauge manifold

will connect to the inlet port of the recovery machine.

– Additional hose from the recovery machine will go to the liquid side of the recovery cylinder.

• Step 3– Connect the recovery machine.– Middle hose (yellow) from your gauge manifold

will connect to the inlet port of the recovery machine.

– Additional hose from the recovery machine will go to the liquid side of the recovery cylinder.

Page 21: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

21

Recovery StepsRecovery Steps

• Step 4– Starting from the hoses connected to the

equipment you are recovering from purge all the air out of the hoses.

– Once you get to the gauges open both side handles and the valve that goes to the white hose. If you have an extra hose, leave that one closed.

• Step 4– Starting from the hoses connected to the

equipment you are recovering from purge all the air out of the hoses.

– Once you get to the gauges open both side handles and the valve that goes to the white hose. If you have an extra hose, leave that one closed.

Page 22: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

22

Recovery StepsRecovery Steps

• Step 4 (Continued)– At the recovery machine turn the inlet valve to

ON and the discharge valve to ON.– Bleed the air out of the line at the recovery

cylinder.– Open the valve on the recovery cylinder.

• Step 4 (Continued)– At the recovery machine turn the inlet valve to

ON and the discharge valve to ON.– Bleed the air out of the line at the recovery

cylinder.– Open the valve on the recovery cylinder.

Page 23: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

23

Recovery StepsRecovery Steps

• Step 5:– Turn the recovery machine ON and wait until all

the gauges show 0 PSI. (can go as low as 5 inches vacuum).

– Close the gauges and wait a few minutes to see if the pressure doesn’t rise from residual liquid in the system.

• Step 5:– Turn the recovery machine ON and wait until all

the gauges show 0 PSI. (can go as low as 5 inches vacuum).

– Close the gauges and wait a few minutes to see if the pressure doesn’t rise from residual liquid in the system.

Page 24: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

24

Recovery StepsRecovery Steps

• Step 6:– Once system is empty then:– Close all gauge handles.– Purge the recovery machine if it has that

feature.– Turn off recovery machine.– Turn off recovery cylinder valve.

• Step 6:– Once system is empty then:– Close all gauge handles.– Purge the recovery machine if it has that

feature.– Turn off recovery machine.– Turn off recovery cylinder valve.

Page 25: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

25

Recovery StepsRecovery Steps

• Step 7:– Disconnect recovery cylinder and machine – put

them aside.– Weigh the recovery cylinder – record the weight

and the net refrigerant recovered.

• Step 7:– Disconnect recovery cylinder and machine – put

them aside.– Weigh the recovery cylinder – record the weight

and the net refrigerant recovered.

Page 26: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

26

Recovery RulesRecovery Rules

• Recovered refrigerant can not change ownership.

• Refrigerant must be reclaimed to change ownership.

• The refrigerant is the property of the person who owns the equipment.

• Recovered refrigerant can not change ownership.

• Refrigerant must be reclaimed to change ownership.

• The refrigerant is the property of the person who owns the equipment.

Page 27: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

27

Recovery RulesRecovery Rules

• Recovered refrigerant can not be mixed.

• Recovery containers must be DOT (department of transportation) approved and color coded gray with a yellow top.

• Recovered refrigerant can not be mixed.

• Recovery containers must be DOT (department of transportation) approved and color coded gray with a yellow top.

Page 28: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

28

Recovery RulesRecovery Rules

• All newly manufactured recovery and recycling machines must be certified by an EPA approved organization to meet the requirements of the evacuation table (standards).

• Always evacuate the machine before each use.

• All newly manufactured recovery and recycling machines must be certified by an EPA approved organization to meet the requirements of the evacuation table (standards).

• Always evacuate the machine before each use.

Page 29: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

29

Recovery RulesRecovery Rules

• When recovering R134A use a machine dedicated to that refrigerant.– The oil requirements are different.

• Recover as a liquid when possible. – Most recovery machines will first get the liquid

and then the vapor on their own.

• When recovering R134A use a machine dedicated to that refrigerant.– The oil requirements are different.

• Recover as a liquid when possible. – Most recovery machines will first get the liquid

and then the vapor on their own.

Page 30: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

30

Recovery RulesRecovery Rules

• Make sure that you replace all the caps from the unit and the equipment.

• Caps on the recovery unit keep out contaminants.

• Make sure that you replace all the caps from the unit and the equipment.

• Caps on the recovery unit keep out contaminants.

Page 31: 1 HVACR415 – Mechanical for Air Conditioning System Recovery.

31

Do your repair workDo your repair work

• Now the system is empty. You can do whatever repair work you need to accomplish.

• Make sure that you do not leave any leaks or braze near your gauges while they are connected.

• Remove any schraeder cores while you are brazing. They have rubber seals and they will melt.

• Now the system is empty. You can do whatever repair work you need to accomplish.

• Make sure that you do not leave any leaks or braze near your gauges while they are connected.

• Remove any schraeder cores while you are brazing. They have rubber seals and they will melt.