1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean University Chapter Objectives: Know the difference between instantaneous power and average power Learn the AC version of maximum power transfer theorem Learn about the concepts of effective or Rms value Learn about the complex power, apparent power and power factor Understand the principle of conservation of AC power Learn about power factor correction

Transcript of 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of...

Page 1: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

1EENG 224

Chapter 11AC Power Analysis

Huseyin BilgekulEeng224 Circuit Theory II

Department of Electrical and Electronic Engineering Eastern Mediterranean University

Chapter Objectives: Know the difference between instantaneous power and average

power Learn the AC version of maximum power transfer theorem Learn about the concepts of effective or Rms value Learn about the complex power, apparent power and power

factor Understand the principle of conservation of AC power Learn about power factor correction

Page 2: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

2EENG 224

Power Factor Correction The design of any power transmission system is very sensitive to the magnitude of the

current in the lines as determined by the applied loads.

Increased currents result in increased power losses (by a squared factor since P = I2R) in the transmission lines due to the resistance of the lines.

Heavier currents also require larger conductors, increasing the amount of copper needed for the system, and they require increased generating capacities by the utility company.

Since the line voltage of a transmission system is fixed, the apparent power is directly related to the current level.

In turn, the smaller the net apparent power, the smaller the current drawn from the supply. Minimum current is therefore drawn from a supply when S = P and QT = 0.

The process of introducing reactive elements to bring the power factor closer to unity is called power-factor correction. Since most loads are inductive, the process normally involves introducing elements with capacitive terminal characteristics having the sole purpose of improving the power factor.

Page 3: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

3EENG 224

Power Factor Correction

Original Inductive Load Inductive Load with improved power factor correction

Effect of capacitor on total current Power triangle of power factor correction

Increasing the power factor without altering the voltage or current to the load is called Power Factor Correction

Page 4: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

4EENG 224

Power Factor Correction

Qc = Q1 – Q2

= P (tan θ1 - tan θ2)

= ωCVrms2

P = S1 cos θ1 Q2 = P tan θ2

c 1 22 2rms rms

Q P (tan θ tan θ )C

ωV ω V

Q1 = S1 sin θ1 = P tan θ1

Increasing the power factor without altering the voltage or current to the load is called Power Factor Correction.

Page 5: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

5EENG 224

Power Factor Correction The process of increasing the power factor without altering the voltage or current to the original load is called power factor correction.

Power factor correction is necessary for economic reasons.

1 2

1 1 1 1 1 1 2 2

Real power stays same

cos sin tan ta

n

P P P

P S Q S P Q P

1 2 1 2(tan tan )CQ Q Q P

1 22 2

(tan tan )C

rms rms

Q PC

V V

2rms

L

VL

Q

• The capacitance value needed to change the pf angle from 1 to 2 .

• Similarly the inductance value needed to change the pf angle from 1 to 2 for a capacitive load.

Page 6: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

6EENG 224

Power Factor

Correction

Page 7: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

7EENG 224

Power Factor

Correction

Page 8: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

8EENG 224

Power Factor Correction

Page 9: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

9EENG 224

Practice Problem 11.15: Find the value of the capacitance needed to correct a load of 140 kVAR at 0.85 lagging pf to unity pf. The load is supplied by a 110 Volt (rms), 60 Hz line.

Page 10: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

10EENG 224

Wattmeter is the instrument for measuring the average power. Two coils are used, the high impedance Voltage coil and the low impedance Current coil. Wattmeter measures the average power given by:

ApplicationsPower Measurement

Wattmeter Wattmeter connected to the load

12 cos( ) cos( )m m v i Rms Rms v iP V I V I

Page 11: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

11EENG 224

Page 12: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

12EENG 224

Page 13: 1 EENG 224 Chapter 11 AC Power Analysis Huseyin Bilgekul Eeng224 Circuit Theory II Department of Electrical and Electronic Engineering Eastern Mediterranean.

13EENG 224

Problem 11-74