Digital Meters - Power Quality Monitoring and AnalysisJohn Levine, P.E.Levine Lectronics and Lectric
![Page 2: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/2.jpg)
2
Contents
• Effects of power quality • Power Quality definitions revisited• What is needed for PQ monitoring ?• Summary
Monitor and Analyze Power Disturbances, Disruptions & Harmonics
![Page 3: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/3.jpg)
3
PQ is a Business Problem
Power Quality issues cause business problems such as:
• Lost productivity, idle people and equipment
• Lost orders, good will, customers and profits
• Lost transactions and orders not being processed
• Revenue and accounting problems
• Customer and/or management dissatisfaction
• Overtime required to make up for lost work time
According to Electric Light and Power Magazine, 30 to 40 Percent of All Business Downtime Is Related to Power Quality Problems.
![Page 4: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/4.jpg)
4
Is Power Quality Such a Big Problem?
![Page 5: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/5.jpg)
5
Why PQ is such a Big Problem?• The sensitivity of today’s electronic equipment
makes it susceptible to power disturbances • For some devices, a momentary disturbance can
cause o scrambled datao interrupted communicationso a frozen mouse o system crashes and equipment failure
![Page 6: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/6.jpg)
6
PQ Problems are Expensive
• Berkeley Lab Study Estimates $80 Billion Annual Cost of Power Interruptions … Research News, Berkeley Lab, February 2, 2005
• $50 billon per year in the USA is lost as a results of power quality breakdowns …. Bank of America Report
• A manufacturing company lost more than $3 million one day last summer in Silicon Valley when the “lights went out.” … New York Times January 2000
• “A voltage sag in a paper mill can waste a whole day of production - $250,000 loss” … Business Week, June 17,, 1996
• Half of all computer problems and one-third of all data loss can be traced back to the power line … Contingency Planning Research, LAN Times
![Page 7: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/7.jpg)
7
Who is Affected?
• Lost production• Scrap• Costs to restart• Labor costs• Equipment damage and repair• Other costs
• High Cost Facilitieso Semiconductor plantso Pharmaceuticalso Data centers
• Medium Cost FacilitiesoAutomotive
manufacturingoGlass plantsoPlastics & ChemicalsoTextiles
![Page 8: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/8.jpg)
8
PQ Definitions RevisitedIEEE CategoriesStd 1159-1995
Short Duration Variations
Typical Duration
Instantaneous Sag 0.5 – 30 cycles
Momentary Sag 30 cycles – 3 sec
Temporary Sag 3 sec – 1 min
![Page 9: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/9.jpg)
9
PQ Definitions RevisitedIEEE CategoriesStd 1159-1995
Short Duration Variations
Typical Duration
Instantaneous Sag 0.5 – 30 cycles
Momentary Sag 30 cycles – 3 sec.
Temporary Sag 3 sec – 1 min.
Instantaneous Swell 0.5 – 30 cycles
Momentary Swell 30 cycles – 3 sec.
Temporary Swell 3 sec – 1 min.
![Page 10: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/10.jpg)
10
PQ Definitions RevisitedIEEE CategoriesStd 1159-1995
Short Duration Variations
Typical Duration
Instantaneous Sag 0.5 – 30 cycles
Momentary Sag 30 cycles – 3 sec.
Temporary Sag 3 sec – 1 min.
Instantaneous Swell 0.5 – 30 cycles
Momentary Swell 30 cycles – 3 sec.
Temporary Swell 3 sec – 1 min.
Momentary Interruptions
0.5 – 30 cycles
Temporary Interruptions
30 cycles – 3 sec.
![Page 11: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/11.jpg)
11
PQ Definitions RevisitedIEEE CategoriesStd 1159-1995
Long Duration Variations
Typical Duration
Sustained interruptions
> 1 min
Under voltages > 1 min
Over voltages > 1 min
![Page 12: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/12.jpg)
12
PQ Definitions RevisitedIEEE CategoriesStd 1159-1995
Long Duration Variations
Typical Duration
Sustained interruptions
> 1 min
Under voltages > 1 min
Over voltages > 1 min
Voltage imbalance Steady state
Waveform Distortion
![Page 13: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/13.jpg)
13
PQ Definitions RevisitedIEEE CategoriesStd 1159-1995
Long Duration Variations
Typical Duration
Sustained interruptions
> 1 min
Under voltages > 1 min
Over voltages > 1 min
Voltage imbalance Steady state
Waveform Distortion
DC offset Steady state
Harmonics Steady state
Inter harmonics Steady state
For Electric Utilities Control of Voltage and Prevention of Outages is Power Quality
![Page 14: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/14.jpg)
14
Sources of PQ ProblemsUtility Sources
• Lightning
• PF Correction Equipment
• Faults
• Switching
Internal Sources
•Individual Loads –Lighting, Elevators, Coolers, HVAC
•Uninterruptible Power Supplies
•Variable Frequency Drives
•Battery Chargers
•Large Motors During Startup
•Electronic Dimming Systems
•Lighting Ballasts (esp. Electronic)
•Arc Welders, and Other Arc Devices
•Medical Equipment, e.g. MRIs and X-Ray Machines
•Office Equipment and Computers
•Wiring
![Page 15: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/15.jpg)
15
PQ Problems and Possible CausesTypical problems Disturbance Type Possible Causes
Overheated neutralIntermittent lock-upsFrequency deviations
Steady-state Shared neutralsImproper or inadequate wiringHigh source impedanceSCR/Rectifiers and notchingHarmonics
![Page 16: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/16.jpg)
16
PQ Problems and Possible CausesTypical problems Disturbance Type Possible Causes
Overheated neutralIntermittent lock-upsFrequency deviations
Steady-state Shared neutralsImproper or inadequate wiringHigh source impedanceSCR/Rectifiers and notchingHarmonics
InterruptionGarbled dataRandom increase in harmonics levels
Utility faultsInrush currentsInadequate wiring
![Page 17: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/17.jpg)
17
PQ Problems and Possible CausesTypical problems Disturbance Type Possible Causes
Overheated neutralIntermittent lock-upsFrequency deviations
Steady-state Shared neutralsImproper or inadequate wiringHigh source impedanceSCR/Rectifiers and notchingHarmonics
InterruptionGarbled dataRandom increase in harmonics levels
Utility faultsInrush currentsInadequate wiring
Intermittent lock-upsLights flickerGarbled data
Sags/Swell Source voltage variationsInrush/surge currentsInadequate wiring
![Page 18: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/18.jpg)
18
PQ Problems and Possible CausesTypical problems Disturbance Type Possible Causes
Overheated neutralIntermittent lock-upsFrequency deviations
Steady-state Shared neutralsImproper or inadequate wiringHigh source impedanceSCR/Rectifiers and notchingHarmonics
InterruptionGarbled dataRandom increase in harmonics levels
Utility faultsInrush currentsInadequate wiring
Intermittent lock-upsLights flickerGarbled data
Sags/Swell Source voltage variationsInrush/surge currentsInadequate wiring
Component failureDielectric breakdownLock-upsGarbled dataWavy CRTs
ImpulsesEMI/RFI
LightningLoad switchingCapacitor switchingStatic dischargeHand-held radiosLoose wiring/arcing
![Page 19: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/19.jpg)
19
PQ Problems and Possible CausesTypical problems Disturbance Type Possible Causes
Overheated neutralIntermittent lock-upsFrequency deviations
Steady-state Shared neutralsImproper or inadequate wiringHigh source impedanceSCR/Rectifiers and notchingHarmonics
InterruptionGarbled dataRandom increase in harmonics levels
Utility faultsInrush currentsInadequate wiring
Intermittent lock-upsLights flickerGarbled data
Sags/Swell Source voltage variationsInrush/surge currentsInadequate wiring
Component failureDielectric breakdownLock-upsGarbled dataWavy CRTs
ImpulsesEMI/RFI
LightningLoad switchingCapacitor switchingStatic dischargeHand-held radiosLoose wiring/arcing
Overheated transformers and motorsVoltage and current distortionsGarbled dataLock-ups
Harmonics Electronic loadsSCR/rectifier
![Page 20: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/20.jpg)
20
Major PQ Problems
Source: EPRI, 1994
Spikes, 7%
Sags, 56%
Outages,
6%
Swells,
31%
Sags (Dips)
Associated with system faults
Switching of heavy loads
Starting of large motors
Swells
System fault conditions
Switching on a large capacitor bank
Switching off a large load
![Page 21: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/21.jpg)
21
Cost of Voltage Sags
Textile Industry
Plastics Industry
Glass Industry
Process Industry
Semiconductors
$1k $10k
$100k $1M $10M
Losses per Voltage Sag Event
Source: EPRI “The Economics of Custom Power”, IEEE T&D Show 2003
![Page 22: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/22.jpg)
22
Cost of Momentary Outages
Momentary Outages create problems when computers and clocks reset, equipment stalls, and work stops.
Category Minimum MaximumIndustrialSemiconductor Manufacturing $20.0 $60.0Electronics $8.0 $12.0Automobile Manufacturing $5.0 $7.5Pharmaceutical $5.0 $50.0Glass $4.0 $6.0Rubber and Plastics $3.0 $4.5Petrochemical $3.0 $5.0Food Processing $3.0 $5.0Textile $2.0 $4.0Metal Fabrication $2.0 $4.0Mining $2.0 $4.0Paper $1.5 $2.5Printing(Newspapers) $1.0 $2.0
CommercialHospitals, banks, civil service $2.0 $3.0Communications, information processing $1.0 $10.0Resturants, bars, hotels $0.5 $1.0
Commercial shops $0.1 $0.5Source: EPRI “The Economics of Custom Power”, IEEE T&D 2003
Cost of Momentary Interuption($/kW Demand)
![Page 23: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/23.jpg)
23
High Speed Waveform Capture
High Speed Waveform Capture Is the Most Important PQ Troubleshooting Tool
![Page 24: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/24.jpg)
24
Benefits of Continuous PQ Monitoring
Continuous PQ Monitoring Detects, Records, and Leads to the Prevention of PQ Problems
• Power Quality monitoring provides a continuous “Health Check” of a facility’s power system … for example:
o Harmonic interaction between loads and power conditioning equipment spotted
o High Inrush currents from equipment startup detected
o Transients from load switching are seen
• It provides data to see, diagnose and avert looming problems – “like squeaky brakes on a car”
o Trends can be detected
o JIT equipment maintenance programs can be established
• It acts like a “Black Box” on an airplane to tell you what, when, and where a Power Quality event occurred … to prevent it from reoccurring
![Page 25: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/25.jpg)
25
What is needed for PQ Monitoring?PQ Monitors must detect and record the 7 types of PQ problems
•Transients•Interruptions•Sag/Under Voltage•Swell/Over Voltage•Waveform Distortion•Voltage Fluctuations•Frequency Variations
These include Flicker and Compliance to ITI(CBEMA), IEEE and ISO Standards
Plus they must …
• Be easy to use• Be Suitable for continuously
monitoring indoors and outdoors
• Interface with standard PQ analysis Software…PQDif format
• Be fast enough to capture high speed events that produce equipment problems
• Have enough storage to save the waveforms you need
• Have PQ analysis tools that produce usable, actionable recommendations
ITI: Information Technology Industry Council (Computer & Business Equipment Manufacturer’s Association)
![Page 26: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/26.jpg)
26
Real Time Field Recorded Events
Source: AGA Brazil
Meter: EPM9650
Period: Jan 2005 – Dec 2005
Continuous Monitoring of the Station for PQ Problems
![Page 27: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/27.jpg)
27
PQ Meter ITI Capture
Equipment Interrupting Voltage Sags as Recorded
Damage Inducing Voltage Surges as Recorded
ITI Acceptable Power Disturbance Envelope
ITI: Information Technology Industry Council (Computer & Business Equipment Manufacturer’s Association)
![Page 28: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/28.jpg)
28
Instantaneous Sag Event
![Page 29: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/29.jpg)
29
Instantaneous Swell Event
![Page 30: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/30.jpg)
30
Harmonic & Interharmonic Spectrum
![Page 31: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/31.jpg)
31
Flicker Recording
![Page 32: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/32.jpg)
32
Flicker Recording
![Page 33: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/33.jpg)
33
Summary
GE Multilin provides the necessary tools for a successful PQ disturbance analysis and allows users to take remedial actions
Accurate Measurement to determine actual
state
Examinations
Remedial actionsRemedy
Feels the pulse of the power system network
Symptoms
High resolution recordings for longer
durationsGE Communicator
software
Diagnosis
![Page 34: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/34.jpg)
34
Finally…
If You Can’t Measure it You Can’t Manage it
If You Can Measure it You Can Manage it
![Page 35: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/35.jpg)
35
Proper Phasors
![Page 36: 1 Digital Meters - Power Quality Monitoring and Analysis John Levine, P.E. Levine Lectronics and Lectric.](https://reader036.fdocuments.in/reader036/viewer/2022062421/56649d6f5503460f94a50bfc/html5/thumbnails/36.jpg)
36
Proper Phasors