(1) Ct Vt Parameters

70
CT & VT PARAMETERS By SUDHIR PATHAK

Transcript of (1) Ct Vt Parameters

Page 1: (1) Ct Vt Parameters

CT & VT PARAMETERS

By SUDHIR PATHAK

Page 2: (1) Ct Vt Parameters

Profile Passed B.Tech in Electrical Engg.(with honors) from IT-

BHU, Varanasi in 1994. Worked with Telco,Jamshedpur from July 1994 till

Dec’95. Joined NTPC in Dec’95. Worked in Electrical Erection and carried out erection of

Switchyard & Generator Protection, Switchyard Equipments, Excitation system, Generator Bus-Duct for two and half years from year Jan ’97 till July’99 at NTPC Unchahar.

Carried out commissioning & maintenance of Switchyard & Generator Protection, Switchyard Equipments, Excitation system for about four years from Aug’99 till April’03 at NTPC Unchahar.

Working in the Protection Group at NTPC,EOC since May’03

Page 3: (1) Ct Vt Parameters

CT PARAMETERS

Page 4: (1) Ct Vt Parameters

FUNDAMENTALS

WHAT IS CT? WHEN IS CT REQUIRED ? WHY IS CT REQUIRED? HOW IS CT CONNECTED? WHERE IS CT CONNECTED? WHICH CT IS CONNECTED?

Page 5: (1) Ct Vt Parameters

WHAT IS CT?

IT’S AN INSTRUMENT TRANSFORMER WHICH TRANSFORMS CURRENT FROM ONE LEVEL TO ANOTHER LEVEL SUCH AS 1000/1 (CT RATIO) i.e. TRANSFORMS CURRENT OF THE LEVEL OF 1000 AMPS INTO CURRENT OF 1 AMP LEVEL.

back

Page 6: (1) Ct Vt Parameters

WHEN IS CT REQUIRED ?

ELECTRICAL SYSTEMS IN WHICH LARGE AMOUNT OF CURRENT ( TO THE TUNE OF 100AMPS OR MORE) FLOWS , DIRECT MEASUREMENT OF THAT CURRENT IS NOT POSSIBLE AS DEVICES USED FOR MEASUREMENT OF CURRENT ARE NOT DESIGNED TO HANDLE SUCH HUGE AMOUNT OF CURRENT.

back

Page 7: (1) Ct Vt Parameters

WHY IS CT REQUIRED? THE SYSTEM WHICH CARRIES CURRENT

MEANS THERE IS A SOURCE WHICH INJECTS THE CURRENT INTO THE SYSTEM AND THERE IS A LOAD WHICH CONSUMES THE CURRENT (OR POWER/ENERGY).SUCH A SYSTEM HAS TWO BASIC REQUIREMENTS: METERING OF ENERGY SOURCED OR

CONSUMED. PROTECTION OF THE ELECTRICAL

SYSTEM FROM FAULTS AND DISTURBANCES. back

Page 8: (1) Ct Vt Parameters

HOW IS CT CONNECTED?

CT HAS A PRIMARY AND ONE OR MORE SECONDARY WINDINGS. SECONDARY WINDING IS WOUND AROUND THE MAGNETIC CORE. METERING AND PROTECTION DEVICES ARE CONNECTED TO THE SECONDARIES OF THE CT.

Page 9: (1) Ct Vt Parameters

HOW IS CT CONNECTED?contd

M/R

PRIMARY

Ip

Ψ

Is

back

P1

P2

S1

S2

Page 10: (1) Ct Vt Parameters

WHERE IS CT CONNECTED?

FOR METERING AND PROTECTION OF A FEEDER, CT IS CONNECTED AT THE BEGINNING OF THE FEEDER.

Page 11: (1) Ct Vt Parameters

WHERE IS CT CONNECTED?

contd

Power Station to be protected

back

Unit prot

Unitprot

Non-unitprot

meter meterprot meterDistprot

One prim one sec

One prim two or more sec

Page 12: (1) Ct Vt Parameters

WHICH CT IS CONNECTED? METERING: IF WE WANT TO MEASURE

CURRENT FOR METERING PURPOSE, WE DESIRE THAT: WHATEVER CURRENT WE MEASURE, THAT

SHOULD BE VERY ACCURATE AS THE METERED DATA MAY BE USED FOR TARIFF PURPOSE i.e. MONEY EXCHANGE IS INVOLVED AMONG VARIOUS PARTIES. MOREOVER, THE DATA IS USED FOR DECISION MAKING SUCH AS DECISION ON RAISING/LOWERING OF POWER OUTPUT etc.

Page 13: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd metering

WHAT IS INACCURACY? THE SECONDARY CURRENT WHICH WE

GET IS NOT TRUE REFLECTION OF ITS PRIMARY CURRENT. FOR EXAMPLE, FOR A CT WITH CT RATIO OF 1000/1AMPS, IF WE GET 0.99 AMPS IN SECONDARY LEADING PRIMARY CURRENT BY 15 MINUTES FOR PRIMARY CURRENT OF 1000AMPS, SO THE CT HAS RATIO ERROR OF (0.99-1)/1 x 100=-1% AND PHASE ERROR OF 15 MINUTES.

Page 14: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd metering

CURRENT OR RATIO ERROR AS PER IEC IS:

Page 15: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd metering

NOW SECOND QUERY WHICH COMES IN MIND IS WHY AT ALL CTS ARE INACCURATE?

THE CULPRIT IS CORE LOSS AND MAGNETISING CURRENT, WHICH INTRODUCES RATIO AS WELL AS PHASE ERROR.

Page 16: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd metering

Ip

Ic

Ie

Is”ImIs

VsEsEp

L

Zs+ZL= Rs+jXs

Page 17: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd metering

Im

Ic Ie

Is”

Ip

Ie

θ

Ep

Ψ

Is

Es IsRs

IsXs

Vs

Page 18: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd metering

THE INTRUMENT CONNECTED TO THE SECONDARY ESPECIALLY ANALOG INDICATING METER SHOULD NOT GET DAMAGED DURING PRIMARY FAULT CONDITION. FOR THIS INSTRUMENT SECURITY FACTOR (FS) IS DEFINED WHICH IS RATIO OF MINIMUM PRIMARY CURRENT AT WHICH COMPOSITE ERROR OF THE CT (AT RATED BURDEN) IS EQUAL TO OR GREATER THAN 10% OF RATED PRIMARY CURRENT.

THE TYPICAL VALUES ARE 5,10 etc.

Page 19: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?contd

COMPOSITE ERROR:

Page 20: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?contd

IEC60044-1 HAS LAID DOWN STANDARDS ON THIS:

25 25 25

Page 21: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd metering

FOR ACHIEVING ABOVE, A CT IS CHOSEN HAVING VERY HIGH PERMEABILITY AND HIGH REMANENCE

Page 22: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd metering

HYSTERISIS CURVE OF METERING CORE

H

Ψs

Ψr∆Ψ

Page 23: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd metering

THE ABOVE CT PARAMETERS ARE THEREFORE SPECIFIED AS FOR EXAMPLE: CTR:1000/1,0.2FS5 ,30VA etc.

IN NTPC, WE TYPICALLY SPECIFY, CTR: 2000/1, 0.2,FS 5, 20VA

Page 24: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?contd

PROTECTION CLASS:

HERE, MAIN REQUIREMENT IS ABILITY OF CT TO FAITHFULLY TRANSFORM THE PRIMARY CURRENT DURING FAULT CONDITION.

Page 25: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PR

DURING FAULT CONDITION, VALUE OF PRIMARY CURRENT MAY BE 10 TO 20 TIMES THE RATED PRIMARY CURRENT. PROTECTIVE RELAY BURDEN IS CONNECTED TO THE CT SECONDARY. AT SUCH HIGH LEVEL OF PRIMARY CURRENT, IF CT IS NOT PROPERLY DESIGNED, IT MAY SATURATE AND RELAY WILL RECEIVE VERY LESS CURRENT AND, THEREFORE, DOES NOT TAKE RIGHT DECISION.

Page 26: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PR

FOR NON-UNIT TYPE PROTECTION SUCH AS O/C TYPE OF PROTECTION, CLASS PR TYPE CTs ARE USED.

THE PARAMETERS THAT ARE DEFINED FOR THE CT ARE:

STANDARD ACCURACY LIMIT FACTOR(SALF):

= RATED ACC. LIMIT PRIMARY CURR. RATED CURRENT

Page 27: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PR

WHEREAS, RATED ACCURACY LIMIT PRIMARY CURRENT IS THE VALUE OF THE PRIMARY CURRENT UPTO WHICH CT WILL COMPLY WITH THE REQUIREMENT OF COMPOSITE ERROR.

STANDARD VALUES OF SALF ARE 5,10,15,20,30

Page 28: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PR

ACCURACY CLASS: TELLS ABOUT %AGE COMPOSITE ERROR LIMIT AT SALF ,RATED FREQUENCY AND RATED BURDEN CONNECTED (at 0.8 pf). STANDARD VALUES ARE 5,10.

Page 29: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PR

RATED BURDEN: DEPENDING ON THE LOAD (VA) CONNECTED TO THE CT, RATED VA BURDEN (AT 0.8Pf) IS DEFINED.

REMANENCE FACTOR FIXED TO 10%.

PROTECTION CLASS CTs HAVE LOW REMANENCE. AS HIGH REMANENCE CTs WILL SATURATE FASTER.

Page 30: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PR

Ψs

Ψr

∆Ψ

H

HYSTERISIS CURVE FOR PROTECTION CTs

Page 31: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PR

Page 32: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PR

THE ABOVE CT PARAMETERS ARE THEREFORE SPECIFIED AS FOR EXAMPLE: CTR:1000/1, 5PR20 @ 30VA etc.

IN NTPC, FOR GENERATOR PROTECTION WE TYPICALLY SPECIFIY CTR 10000A/5A,5PR20 @ 75VA

Page 33: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection

FOR UNIT TYPE PROTECTION:

HERE , REQUIREMENTS ARE RATHER STRINGENT AS WE COMPARE CURRENT OF TWO OR MORE CTS AND RELY ON THE THEIR MUTUAL FAITHFULL-NESS. MOREOVER, OUR AIM IS THAT THE PROTECTION MUST BE STABLE FOR EVEN WORST THROUGH FAULT AND FAST ACTING FOR INTERNAL FAULT.

Page 34: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PX

Internal Fault

Substation to be protected

External/Through Fault

Page 35: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PX

I1 I1

i1 i1’

i1 – i1’

Equipment to be protectedI2

i2i1 + i2Stabilising

Resistance

Operating relay

UNIT PROTECTION

Page 36: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PX

FOR THIS PX CLASS OF CTs ARE NEEDED (THESE CTs ARE SIMILAR IN ALL RESPECTS TO CLASS PS OF IS-2705 AND CLASS-X OF BS-3938 WITH SOME ADDITIONAL FEATURES)

Page 37: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PX

THE PARAMETERS WHICH ARE DEFINED IN THIS CT ARE: KNEE POINT VOLTAGE (KPV):

That minimum sinusoidal voltage (r.m.s.) at rated power frequency when applied to the secondary terminals of the transformer, all the terminals being open-circuited, which when increased by 10% causes the r.m.s. exciting current to increase by no more than 50%.

Page 38: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PX

Ie

V

Page 39: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PX

Ie

V

∆V

∆Ie

KPV

Page 40: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PX

FOR WORST THROUGH FAULT, CTs SHOULD NOT GET SATURATED.WHEN ONE OF THE CTs GETS SATURATED, LARGE AMOUNT OF CURRENT MAY FLOW THROUGH DIFFERENTIAL CIRCUIT AND RESULT IN OPERATION OF RELAY.HOWEVER, IF RELAY IS SET ABOVE THIS VALUE

i.e. Iset= Ifx (Rct+2xRl), Rstab

Page 41: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PX

I1 I1

i1 i1’

i1 – i1’

Equipment to be protectedI2

Stabilising Resistance

Operating relay

UNIT PROTECTION (HIGH IMPEDANCE)

SATURATED CT

Page 42: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PX

THEN, RELAY MAY NOT OPERATE FOR INTERNAL FAULT IF ONE OF THE CT GETS SATURATED FOR INTERNAL FAULT. THEREFORE, KNEE POINT VOLTAGE IS DEFINED.FOR HIGH IMPEDANCE UNIT PROTECTION, THIS IS USUALLY TAKEN AS:

KPV=2x If (Rct+2xRl)

Page 43: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?contd protection PX

FOR LOW IMPEDANCE UNIT PROTECTION:

KPV=Kx In (Rct+2xRl), WHERE Kx IS THE DIMENSIONING FACTOR

WELL, THESE ARE RELAY APPLICATION AND SYSTEM X/R SPECIFIC.

Page 44: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?contd protection PX

Eqpt to be protected

UNIT PROTECTION (HIGH IMPEDANCE)

Page 45: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?contd protection PX

MAGNETISING CURRENT AT KPV OR %AGE THEREOF:

TWO OR MORE CTs USED FOR UNIT PROTECTION SHOULD WORK LIKE CLONE BROTHERS i.e. FOR THROUGH FAULT CONDITION, THE SPILL CURRENT SHOULD BE IDEALLY ZERO. BUT PRACTICALLY, THIS IS NOT THE CASE.

Page 46: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?contd protection PX

IF TWO CTs HAVE DIFFERENT

MAGNETISING CURRENT AND HIGH LEAKAGE REACTANCE, IT WILL INTRODUCE HIGH CURRENT AS WELL AS PHASE ERROR.THUS, RESULTANT CURRENT OF THESE CT SECONDARIES MAY LEAD TO HIGH SPILL(DIFFERENTIAL) CURRENT DURING THROUGH FAULT.THIS MAY LEAD TO PROTECTION OPERATION DURING THROUGH FAULT.

Page 47: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd protection PX

CT DC RESISTANCE AT 75 deg C(Rct): THIS VALUE IS VERY IMPORTANT FROM THE

POINT OF VIEW OF KPV CALCULATION AS IT IS ONE OF THE LIMITING FACTORS TO THIS. THEREFORE, IT IS DEFINED.

TURN RATIO ERROR: LIMITED TO 0.25%.

Page 48: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?contd

THE ABOVE CT PARAMETERS ARE THEREFORE SPECIFIED AS FOR EXAMPLE:

CTR: 1000/1 ,PX , KPV=1000V, Ie=30mAmp @ KPV/2, Rct< 5OHMS @75 deg C etc. (TYPICAL TO NTPC)

Page 49: (1) Ct Vt Parameters

VT PARAMETERS

Page 50: (1) Ct Vt Parameters

FUNDAMENTALS

WHAT IS VT? WHEN IS VT REQUIRED ? WHY IS VT REQUIRED? HOW IS VT CONNECTED? WHERE IS VT CONNECTED? WHICH VT IS CONNECTED?

Page 51: (1) Ct Vt Parameters

WHAT IS VT?

IT’S AN INSTRUMENT TRANSFORMER WHICH TRANSFORMS VOLTAGE FROM ONE LEVEL TO ANOTHER LEVEL SUCH AS 400KV/√3:110V/√3 (VT RATIO) i.e. TRANSFORMS VOLTAGE OF THE LEVEL OF 400KV/√3 INTO VOLTAGE OF 110V/√3 LEVEL.

back

Page 52: (1) Ct Vt Parameters

WHEN IS VT REQUIRED ?

ELECTRICAL SYSTEM WHICH HAS HIGH LEVEL OF VOLTAGE ( TO THE TUNE OF 3.3KV OR MORE) , DIRECT MEASUREMENT OF THAT VOLTAGE IS NOT POSSIBLE AS DEVICES USED FOR MEASUREMENT OF VOLTAGE ARE NOT DESIGNED TO HANDLE SUCH HIGH LEVEL OF VOLTAGE.

back

Page 53: (1) Ct Vt Parameters

WHY IS VT REQUIRED?

THE SYSTEM WHICH CARRIES VOLTAGE AND CURRENT MEANS THERE IS A SOURCE WHICH INJECTS THE POWER INTO THE SYSTEM AND THERE IS A LOAD WHICH CONSUMES POWER/ENERGY.SUCH A SYSTEM HAS TWO BASIC REQUIREMENTS: METERING OF ENERGY SOURCED OR

CONSUMED. PROTECTION OF THE ELECTRICAL

SYSTEM FROM FAULTS AND DISTURBANCES.

Page 54: (1) Ct Vt Parameters

WHY IS VT REQUIRED? Contd

FAULTS CAN BE MANY KINDS. SOME FAULTS SUCH AS O/C CAN BE DETECTED SOLELY ON CURRENT MEASUREMENT, BUT CURRENT DOES NOT PROVIDE DISCRETION ABOUT NATURE AND LOCATION OF THE FAULT. FOR HIGHLY INTERCONNECTED ELECTRICAL SYSTEM CARRYING HUGE AMOUNT OF POWER, SUB-SYSTEM ISOLATION SELECTIVITY IS IMMENSLY DESIRABLE.

Page 55: (1) Ct Vt Parameters

WHY IS VT REQUIRED? Contd

• THEREFORE, WHEN VOLTAGE IS ALSO MEASURED ALONGWITH CURRENT DURING FAULT, WE CAN IN A WAY COMPUTE POWER OR IMPEDANCE OF SYSTEM ALONGWITH ITS DIRECTION.

• MOREOVER, O/V,U/V, O/F AND U/F PROTECTIONS ARE ALSO CONFIGURED FROM VTs.

back

Page 56: (1) Ct Vt Parameters

HOW IS VT CONNECTED?

VT HAS A PRIMARY AND ONE OR MORE SECONDARY WINDINGS.

METERING AND PROTECTION DEVICES ARE CONNECTED TO THE SECONDARIES OF THE VT.

Page 57: (1) Ct Vt Parameters

HOW IS VT CONNECTED?contd

M

P

P

INDUCTIVE VOLTAGE TRANSFORMER

Page 58: (1) Ct Vt Parameters

HOW IS VT CONNECTED? contd

back

M

P

P

CAPACITIVE VOLTAGE TRANSFORMER

Page 59: (1) Ct Vt Parameters

WHERE IS VT CONNECTED?

FOR METERING AND PROTECTION OF A FEEDER, VT IS CONNECTED AT THE BEGINING OF THE FEEDER.

Page 60: (1) Ct Vt Parameters

WHERE IS VT CONNECTED?

contd

Power Station to be protected

back

Page 61: (1) Ct Vt Parameters

WHICH VT IS CONNECTED?

AS STATED FOR CT, WE NEED IT FOR

METERING: VOLTAGE MEASUREMENT, ENERGY, POWER MEASUREMENT.

PROTECTION: FOR DISTANCE PROTECTION, O/V,U/V, O/F AND U/F PROTECTIONS, FIELD FAILURE, OVER-FLUXING,etc.

Page 62: (1) Ct Vt Parameters

WHICH VT IS CONNECTED?contd

FOR METERING VTs WE NEED HIGH ACCURACY IN THE VOLTAGE MEASUREMENT DURING STABLE CONDITIONS i.e 80% TO 120% OF NOMINAL SYSTEM VOLTAGE WITH BURDENS FROM 25% TO 100% OF RATED BURDEN AT POWER FACTOR OF 0.8. IN VTs ALSO AS IN CTs, RATIO AS WELL AS PHASE ERRORS ARE THERE.

Page 63: (1) Ct Vt Parameters

WHICH VT IS CONNECTED?contd

Ip

Ic

Ie

Is”ImIs

VsEsEp

L

Zs+ZL= Rs+jXs

Vp

Zp=Rp+jXp

Page 64: (1) Ct Vt Parameters

WHICH CT IS CONNECTED?Contd metering

Im

Ic Ie

Is”

Ip

Ie

θ

Ep

Ψ

Is

Es IsRs

IsXs

Vs

IpRp

IpXpVp

Page 65: (1) Ct Vt Parameters

WHICH VT IS CONNECTED?Contd metering

IEC 60044-2 AND 60044-5 DEFINES THIS AS :

Page 66: (1) Ct Vt Parameters

WHICH VT IS CONNECTED?Contd metering

THE ABOVE VT PARAMETERS ARE THEREFORE SPECIFIED AS FOR EXAMPLE: PTR: 400KV/√3:110V/√3,0.2, 50VA etc (TYPICAL TO NTPC)

Page 67: (1) Ct Vt Parameters

WHICH VT IS CONNECTED?contd

FOR PROTECTION VTs WE NEED FAITHFULNESS OF VOLTAGE MEASUREMENT IN THE HIGHER RANGE OF VOLTAGE SUCH AS FROM VALUE AS LOW AS 2% OF NOMINAL VOLTAGE TO THE RATED VOLTAGE MULTIPLIED BY RATED VOLTAGE FACTORS SUCH AS 1.2,1.5,1.9 WITH BURDEN OF 25% TO 100% OF RATED BURDEN AT 0.8pf LAGGING.

Page 68: (1) Ct Vt Parameters

WHICH VT IS CONNECTED?contd protection

IEC 60044-2 AND 60044-5 DEFINES THIS AS :

Page 69: (1) Ct Vt Parameters

WHICH VT IS CONNECTED?Contd protetcion

THE ABOVE VT PARAMETERS ARE THEREFORE SPECIFIED AS FOR EXAMPLE: PTR: 400KV/√3:110V/√3,3P, 50VA etc (TYPICAL TO NTPC)

Page 70: (1) Ct Vt Parameters

THANKS