09-PowerFactor
Transcript of 09-PowerFactor
-
8/7/2019 09-PowerFactor
1/20
Improvement of Power Factor & EnsuringBetter Understanding
bySh.Jitendra K. Rathod,
Jalaram Consultancy & Technical Services, Raipur
-
8/7/2019 09-PowerFactor
2/20
Power Factor (PF) is the ratio between the
active power (kW) and apparent power (kVA).Trigonometrically is the Cosine of Angle
between the Reference Voltage vector and the
Current vector.
What is power factor?
-
8/7/2019 09-PowerFactor
3/20
VoltageVector
CurrentVector
Angle
1
Direction of Rotation
-
8/7/2019 09-PowerFactor
4/20
Voltage Vector
CurrentVector
Angle1
Vectors and Angle between them
-
8/7/2019 09-PowerFactor
5/20
Active Current
Measured Current
ReactiveCurrent
Angle 1
Current and Components
-
8/7/2019 09-PowerFactor
6/20
Active Power
Apparent Power
ReactivePower
Angle 1
Power Diagram
-
8/7/2019 09-PowerFactor
7/20
Active Energy
Apparent Energy
ReactiveEnergy
Angle 1
Energy Diagram
-
8/7/2019 09-PowerFactor
8/20
Glass containing Frothand Beer
-
8/7/2019 09-PowerFactor
9/20
Glass containing lot of Froth and
small quantity of Beer
-
8/7/2019 09-PowerFactor
10/20
kW
kVA1
kVAR2
Angle 1
kVA2
Angle2
kVAR1
Situation Before and Afterapplication of Capacitors
-
8/7/2019 09-PowerFactor
11/20
IACTIVE
IAPPARENT 1
IREACTIVE 2
Angle 1
IAPPARENT 2
Angle2
IREACTIVE 1
Current values before and afterCapacitor Application
-
8/7/2019 09-PowerFactor
12/20
Being a Right Angled Triangle, existing Currentcomponents shall follow Pythagoras theorem:-
IACTIVE
2 + IREACTIVE-1
2 = IAPPARENT-1
2
Being a Right Angled Triangle, the New Currentcomponents shall follow Pythagoras theorem:-
IACTIVE2 + IREACTIVE-2
2 = IAPPARENT-22
Relation between Current Values
-
8/7/2019 09-PowerFactor
13/20
It is considered as Lagging. Existing power factor are
taken as PF1 and improved power factor as PF2.
Old and New Power Factor
-
8/7/2019 09-PowerFactor
14/20
Reactive Current Switched ON = IREACTIVE-3 (IR3). We can easily measure;
this being output from the capacitors connected to the circuit.
Original Reactive component of Current = IREACTIVE-1 (IR1)
Reduced Reactive component of Current = IREACTIVE-2 (IR2)
Balance Uncompensated Reactive Current IREACTIVE-2 (IR2) = IREACTIVE-1
(IR1) - IREACTIVE-3 (IR3)
Active Current IACTIVE remains constant and hence Same Amperes.
Original Apparent Current = IAPPARENT-1 = IAPP-1= I1. We can easily measure
Reduced Apparent Current = IAPPARENT-2 = IAPP-2= I2 We can easily measure
Reduction in Apparent Current = IAPPARENT- 3 = IAPP 3 = I3. We can calculate.
Reduction in Apparent Current IAPP-3 = I3 = (I1 - I2). We can calculate.
% Reduction in Apparent Current = (I3/ I1) * 100. We can calculate.
Or, % Reduction in Apparent Current = (I1 - I2) / I1 * 100
Or, % Reduction in Apparent Current = {1 (I2/ I1)}* 100
% Reduction in Copper Loss = {1 (I2/ I1)2}* 100
Nomenclature of Current and Reduction in Load and also
reduction in Copper Losses
-
8/7/2019 09-PowerFactor
15/20
Existing Angle is in Degrees 1
Existing power factor in % = PF1 Cos 1
Reactive Power Switched ON kVAR3 MVAR3
New Angleis in Degrees 2
Improved power factor in % = PF2 Cos 2
New (Balance) Reactive Power kVAR2
MVAR2
New Apparent Power kVA2 MVA2
Improvement of Power Factor = PF1-PF2 Cos 1 - Cos 2
Reduction in Apparent Power kVA3 = kVA1 - kVA2
Addition of Capacitors kVAR3 = kVAR1kVAR2
Trignometrical Review
-
8/7/2019 09-PowerFactor
16/20
Apparent Power 325 kVA1 Existing Values Improved Values
Power Factor in % Cos 1 = 76% Cos 2 = 90%
Angle is in Degrees 1 = 40.54 2 = 25.84
Same Active Power kW = 247.000
Apparent Power kVA1 = 325.000 kVA2 = 274.444
Current at 440 Volts, in Amp. I1 = 426.452 I2 = 360.115
Reactive Power kVAR1 = 211.225 kVAR2 = 119.628
Capacitors applied kVAR3 = 211.225 kVAR1 - 119.628
kVAR2 =91.597
91.597 kVAR3/ 325 kVA1 = 0.28184
% Reduction in Apparent Power = (1 - 274.444 kVA2/
325 kVA1) =
15.56% Refer Table3
E.C. i.e. % Reduction in Copper Losses = 1 - (360.115 I2/
426.452 I1)2 =
28.69% Refer Table4
Numerical Values Before and After Capacitor
Application
-
8/7/2019 09-PowerFactor
17/20
kW
kVA1
kVAR2
Angle 1
kVA2
Angle2
kVAR1
Reduction of Current
-
8/7/2019 09-PowerFactor
18/20
RESULT
Reduction in Apparent Power i.e. kVA3 = kVA1 - kVA2
Addition of Reactive Power i.e. kVAR3 = kVAR1 - kVAR2
Being a Right Angled Triangle, existing power shallfollow Pythagoras theorem:-
kW2 + kVAR12 = kVA1
2
Being a Right Angled Triangle, the New Power triangle
shall also follow Pythagoras theorem:-kW2 + kVAR2
2 = kVA22
Components of Power & Inter-
relationship
-
8/7/2019 09-PowerFactor
19/20
S. No. Rating of individual Induction motor in . KVAR rating of LT capacitors
1 3 and above up to 5 1 KVAR
2 Above 5 to 7.5 2 KVAR
3 Above 7.5 to 10 3 KVAR
4 Above 10 to 15 4 KVAR
5 Above 15 to 20 5 KVAR
6 Above 20 to 30 6 KVAR
7 Above 30 to 40 7 KVAR
8 Above 40 to 50 8 KVAR
9 Above 50 to 100 9 KVAR
CSEB suggested values
-
8/7/2019 09-PowerFactor
20/20