09-PowerFactor

download 09-PowerFactor

of 20

Transcript of 09-PowerFactor

  • 8/7/2019 09-PowerFactor

    1/20

    Improvement of Power Factor & EnsuringBetter Understanding

    bySh.Jitendra K. Rathod,

    Jalaram Consultancy & Technical Services, Raipur

    [email protected]

  • 8/7/2019 09-PowerFactor

    2/20

    Power Factor (PF) is the ratio between the

    active power (kW) and apparent power (kVA).Trigonometrically is the Cosine of Angle

    between the Reference Voltage vector and the

    Current vector.

    What is power factor?

  • 8/7/2019 09-PowerFactor

    3/20

    VoltageVector

    CurrentVector

    Angle

    1

    Direction of Rotation

  • 8/7/2019 09-PowerFactor

    4/20

    Voltage Vector

    CurrentVector

    Angle1

    Vectors and Angle between them

  • 8/7/2019 09-PowerFactor

    5/20

    Active Current

    Measured Current

    ReactiveCurrent

    Angle 1

    Current and Components

  • 8/7/2019 09-PowerFactor

    6/20

    Active Power

    Apparent Power

    ReactivePower

    Angle 1

    Power Diagram

  • 8/7/2019 09-PowerFactor

    7/20

    Active Energy

    Apparent Energy

    ReactiveEnergy

    Angle 1

    Energy Diagram

  • 8/7/2019 09-PowerFactor

    8/20

    Glass containing Frothand Beer

  • 8/7/2019 09-PowerFactor

    9/20

    Glass containing lot of Froth and

    small quantity of Beer

  • 8/7/2019 09-PowerFactor

    10/20

    kW

    kVA1

    kVAR2

    Angle 1

    kVA2

    Angle2

    kVAR1

    Situation Before and Afterapplication of Capacitors

  • 8/7/2019 09-PowerFactor

    11/20

    IACTIVE

    IAPPARENT 1

    IREACTIVE 2

    Angle 1

    IAPPARENT 2

    Angle2

    IREACTIVE 1

    Current values before and afterCapacitor Application

  • 8/7/2019 09-PowerFactor

    12/20

    Being a Right Angled Triangle, existing Currentcomponents shall follow Pythagoras theorem:-

    IACTIVE

    2 + IREACTIVE-1

    2 = IAPPARENT-1

    2

    Being a Right Angled Triangle, the New Currentcomponents shall follow Pythagoras theorem:-

    IACTIVE2 + IREACTIVE-2

    2 = IAPPARENT-22

    Relation between Current Values

  • 8/7/2019 09-PowerFactor

    13/20

    It is considered as Lagging. Existing power factor are

    taken as PF1 and improved power factor as PF2.

    Old and New Power Factor

  • 8/7/2019 09-PowerFactor

    14/20

    Reactive Current Switched ON = IREACTIVE-3 (IR3). We can easily measure;

    this being output from the capacitors connected to the circuit.

    Original Reactive component of Current = IREACTIVE-1 (IR1)

    Reduced Reactive component of Current = IREACTIVE-2 (IR2)

    Balance Uncompensated Reactive Current IREACTIVE-2 (IR2) = IREACTIVE-1

    (IR1) - IREACTIVE-3 (IR3)

    Active Current IACTIVE remains constant and hence Same Amperes.

    Original Apparent Current = IAPPARENT-1 = IAPP-1= I1. We can easily measure

    Reduced Apparent Current = IAPPARENT-2 = IAPP-2= I2 We can easily measure

    Reduction in Apparent Current = IAPPARENT- 3 = IAPP 3 = I3. We can calculate.

    Reduction in Apparent Current IAPP-3 = I3 = (I1 - I2). We can calculate.

    % Reduction in Apparent Current = (I3/ I1) * 100. We can calculate.

    Or, % Reduction in Apparent Current = (I1 - I2) / I1 * 100

    Or, % Reduction in Apparent Current = {1 (I2/ I1)}* 100

    % Reduction in Copper Loss = {1 (I2/ I1)2}* 100

    Nomenclature of Current and Reduction in Load and also

    reduction in Copper Losses

  • 8/7/2019 09-PowerFactor

    15/20

    Existing Angle is in Degrees 1

    Existing power factor in % = PF1 Cos 1

    Reactive Power Switched ON kVAR3 MVAR3

    New Angleis in Degrees 2

    Improved power factor in % = PF2 Cos 2

    New (Balance) Reactive Power kVAR2

    MVAR2

    New Apparent Power kVA2 MVA2

    Improvement of Power Factor = PF1-PF2 Cos 1 - Cos 2

    Reduction in Apparent Power kVA3 = kVA1 - kVA2

    Addition of Capacitors kVAR3 = kVAR1kVAR2

    Trignometrical Review

  • 8/7/2019 09-PowerFactor

    16/20

    Apparent Power 325 kVA1 Existing Values Improved Values

    Power Factor in % Cos 1 = 76% Cos 2 = 90%

    Angle is in Degrees 1 = 40.54 2 = 25.84

    Same Active Power kW = 247.000

    Apparent Power kVA1 = 325.000 kVA2 = 274.444

    Current at 440 Volts, in Amp. I1 = 426.452 I2 = 360.115

    Reactive Power kVAR1 = 211.225 kVAR2 = 119.628

    Capacitors applied kVAR3 = 211.225 kVAR1 - 119.628

    kVAR2 =91.597

    91.597 kVAR3/ 325 kVA1 = 0.28184

    % Reduction in Apparent Power = (1 - 274.444 kVA2/

    325 kVA1) =

    15.56% Refer Table3

    E.C. i.e. % Reduction in Copper Losses = 1 - (360.115 I2/

    426.452 I1)2 =

    28.69% Refer Table4

    Numerical Values Before and After Capacitor

    Application

  • 8/7/2019 09-PowerFactor

    17/20

    kW

    kVA1

    kVAR2

    Angle 1

    kVA2

    Angle2

    kVAR1

    Reduction of Current

  • 8/7/2019 09-PowerFactor

    18/20

    RESULT

    Reduction in Apparent Power i.e. kVA3 = kVA1 - kVA2

    Addition of Reactive Power i.e. kVAR3 = kVAR1 - kVAR2

    Being a Right Angled Triangle, existing power shallfollow Pythagoras theorem:-

    kW2 + kVAR12 = kVA1

    2

    Being a Right Angled Triangle, the New Power triangle

    shall also follow Pythagoras theorem:-kW2 + kVAR2

    2 = kVA22

    Components of Power & Inter-

    relationship

  • 8/7/2019 09-PowerFactor

    19/20

    S. No. Rating of individual Induction motor in . KVAR rating of LT capacitors

    1 3 and above up to 5 1 KVAR

    2 Above 5 to 7.5 2 KVAR

    3 Above 7.5 to 10 3 KVAR

    4 Above 10 to 15 4 KVAR

    5 Above 15 to 20 5 KVAR

    6 Above 20 to 30 6 KVAR

    7 Above 30 to 40 7 KVAR

    8 Above 40 to 50 8 KVAR

    9 Above 50 to 100 9 KVAR

    CSEB suggested values

  • 8/7/2019 09-PowerFactor

    20/20