09 12 GEI Service Manual

download 09 12 GEI Service Manual

of 70

Transcript of 09 12 GEI Service Manual

  • 7/30/2019 09 12 GEI Service Manual

    1/70

    ACP-09CH25GEI

    ACP-12CH35GEI

    RoHS

    Service

    manual

    ENG

  • 7/30/2019 09 12 GEI Service Manual

    2/70

  • 7/30/2019 09 12 GEI Service Manual

    3/70

    2

    COOLING HEATING COOLING HEATING

    730 800 1300/1110 1330/1175

    1360 1390 1430 1470

    3.53 3.86 5.95 6.39

    3.20/3.42 2.88/3.38 3.00/3.21 3.38/3.40Model of Indoor Unit

    Fan Motor Speed (r/min) (H/M/L)

    Output of Fan Motor (w)

    Input of Heater (w)

    Fan Motor Capacitor (uF)

    Fan Motor RLA(A)

    Fan Type-Piece

    Diameter-Length (mm)

    Evaporator

    Pipe Diameter (mm)

    Row-Fin Gap(mm)

    Coi l length (l ) x height (H) x coi l width

    (L)

    Swing Motor Model

    Output of Swing Motor (W)

    Fuse (A)

    Sound Pres sure Level dB (A) (H/M/L)

    Sound Power Level dB (A) (H/M/L)

    Dimension (W/D/H)( mm)

    Dimens ion of Package (W/D/H)( mm)

    Net Weight /Gross Weight (kg)

    52 / 49 / 48

    830189285

    900265385

    11/15

    Controller3.15 transformer0.2

    42 / 39 / 38

    4500/40003900/3560

    2-1.4

    681324.338.1

    MP28EA

    2

    Cross flow fan

    92.1616

    Aluminum fin-copper tube

    7

    20

    None

    1

    0.152

    770X180X250

    855X272X336

    8.5/12.5

    GWHD12A6NK3DA

    1Ph 220~240V

    50Hz

    550

    1.6

    GWHD12A6NK3DA/I

    1250 / 1100 / 1050

    2

    Controller3.15 transformer0.2

    40 / 36 / 33

    50 / 46 / 43

    7

    2-1.4

    580X228.6X25.4

    MP24GA

    Indoor

    unit

    GWHD09A3NK3DA/I

    1160 /1010 /780

    14

    None

    1

    0.14

    Cross flow fan

    97-583

    Aluminum fin-copper tube

    450

    Dehumidifying Volume (l/h) 1.2

    C.O.P / EER (W/W) (High/Normal)

    Power Input (W) (High/Normal)

    Rated Input (W) (High/Normal)

    Rated Current (A) (High/Norma)

    Air Flow Volume (m3/h) (H/M/L)

    Rated Frequency 50Hz

    Total Capacity (W)

    (High/Normal )3200/2500 4000/2700

    Model GWHD09A3NK3DA

    Function

    Rated Voltage 1Ph 220~240V

    Specifications and Technical Parameters

  • 7/30/2019 09 12 GEI Service Manual

    4/70

    Model of Outdoor Unit GWHD12A6NK3DA/O

    Compressor Model EU1011DV

    Compressor Type Scroll

    L.R.A. (A) 33.5

    Compressor RLA(A) 4

    Compressor Power Input(W) 628

    Overload Protector 4CYC11233

    Throttling Method Capillary throttling

    Starting Method Transducer starting

    Working Temp Range () -10T43

    Condenser Aluminum fin-copper tube

    Pipe Diameter (mm) 9.52

    Rows-Fin Gap(mm) 2-1.4

    Coil length (l) x height (H) x coil

    width (L)64550844

    Fan Motor Speed (rpm) (H/M/L) 83020

    Output of Fan Motor (W) 30

    Fan Motor RLA(A) 0.3

    Fan Motor Capacitor (uF) 2.5

    Air Flow Volume of Outdoor Unit /

    Fan Type-Piece Axial fan-1

    Fan Diameter (mm) 400

    Defrosting Method Auto defrost

    Climate Type T1

    Isolation I

    Mois ture Protection IP24

    Permissible Excessive Operating

    Pressure for the Discharge

    Side(MPa)

    3.8

    Permissible Excessive Operating

    Pressure for the Suction

    Side(MPa)

    1.2

    Sound Pressure Level dB (A)

    (H/M/L)54

    Sound Power Level dB (A) (H/M/L) 64

    Dimension (W/D/H)( mm) 848X260X540

    Dimension of Package (W/D/H)(

    mm )878X360X610

    Net Weight /Gross Weight (kg) 45/50

    Refrigerant Charge (kg) R410A / 1.2

    Length (m) 4

    6(1/4) 6(1/4) 6(1/4)

    12(1/2) 12(1/2) 12(1/2)

    5 5 5

    10 10 10

    64

    R410A / 1.2

    45/50

    878X360X610

    848X260X540

    Outdoor

    unit

    Connecti

    on Pipe

    Outer Diameter

    Max Distance

    54

    1.2

    3.8

    IP24

    I

    T1

    Auto defrost

    400

    64550844

    2-1.4

    Axial fan-1

    /

    2.5

    0.3

    GWHD09A3NK3DA/O

    Capillary throttling

    4CYC11233

    628

    4

    4

    Scroll

    33.5

    EU1011DV

    9.52

    Aluminum fin-copper tube

    -10T43

    Transducer s tarting

    30

    83020

    The above data is subject to change without notice. Please refer to the nameplate of the unit.

  • 7/30/2019 09 12 GEI Service Manual

    5/70

    COOLING HEATING COOLING HEATING

    730 800 1300/1110 1330/1175

    1360 1390 1430 1470

    3.53 3.86 5.95 6.39

    3.20/3.42 2.88/3.38 3.00/3.21 3.38/3.40

    Model of Indoor UnitFan Motor Speed (r/min) (H/M/L)

    Output of Fan Motor (w)

    Input of Heater (w)

    Fan Motor Capacitor (uF)

    Fan Motor RLA(A)

    Fan Type-Piece

    Diameter-Length (mm)

    Evaporator

    Pipe Diameter (mm)

    Row-Fin Gap(mm)

    Coi l length (l ) x height (H) x coi l

    width (L)

    Swing Motor Model

    Output of Swing Motor (W)

    Fuse (A)Sound Pressure Level dB (A)

    H/M/LSound Power Level dB (A)

    (H/M/L)

    Dimension (W/D/H)( mm)

    Dimension of Package (W/D/H)(

    mm )Net Weight /Gross Weight (kg)

    830189285

    998364370

    16/20

    Aluminum fin-copper tube

    2

    Controller3.15 transformer0.2

    42 / 39 / 38

    52 / 49 / 48

    7

    2-1.4

    681324.338.1

    MP28EA

    Cross flow fan

    92.1616

    3900/3560 4500/4000

    20

    None

    1

    0.152

    770X190X250

    960X335X365

    40 / 36 / 33

    50 / 46 / 43

    7

    2-1.4

    580X228.6X25.4

    MP24GA

    8.5/12.5

    GWHD12A6NK3DB

    220V-240V~

    50Hz

    550

    1.6

    GWHD12A6NK3DB/I1250 / 1100 / 1050

    2

    Controller3.15 transformer0.2

    Indoor

    unit

    GWHD09A3NK3DB/I1160/1010 /780

    14

    None

    1

    0.14

    Cross flow fan

    97-583

    Aluminum fin-copper tube

    450

    Dehumidifying Volume (l/h) 1.2

    C.O.P / EER (W/W) (High/Normal)

    Power Input (W) (High/Normal)

    Rated Input (W) (High/Normal)

    Rated Current (A) (High/Normal )

    Air Flow Volume (m3/h) (H/M/L)

    Rated Frequency 50Hz

    Total Capacity (W)

    (High/Normal )3200/2500 4000/2700

    Model GWHD09A3NK3DB

    Function

    Rated Voltage 1Ph 220~240V

  • 7/30/2019 09 12 GEI Service Manual

    6/70

    Model of Outdoor Unit GWHD12A6NK3DB/O

    Compressor Model EU1011DV

    Compressor Type Scroll

    L.R.A. (A) 33.5

    Compressor RLA(A) 4

    Compressor Power Input(W) 628

    Overload Protector 4CYC11233

    Throttling Method Capillary throttling

    Starting Method Transducer starting

    Working Temp Range () -10T43

    Condenser Aluminum fin-copper tube

    Pipe Diameter (mm) 9.52

    Rows-Fin Gap(mm) 2-1.4

    Coil length (l) x height (H) x coil width (L) 64550844

    Fan Motor Speed (rpm) (H/M/L) 83020

    Output of Fan Motor (W) 30

    Fan Motor RLA(A) 0.3

    Fan Motor Capacitor (uF) 2.5

    Air Flow Volume of Outdoor Uni t /

    Fan Type-Piece Axial fan-1

    Fan Diameter (mm ) 400

    Defrosting Method Auto defrost

    Climate Type T1

    Isolation I

    Mois ture Protection IP24

    Perm is sible Exces sive Operating

    Pressure for the Discharge Side(MPa)

    3.8

    Perm is sible Exces sive Operating

    1.2

    Sound Pres sure Level dB (A) (H/M/L) 54

    Sound Power Level dB (A) (H/M/L) 64

    Dimens ion (W/D/H)( mm ) 848X260X540

    Dimens ion of Package (W/D/H)( mm) 878X360X610

    Net Weight /Gross Weight (kg) 45/50

    Refrigerant Charge (kg) R410A / 1.25

    Length (m) 4

    6(1/4) 6(1/4) 6(1/4)

    12(1/2) 12(1/2) 12(1/2)

    5 5 510 10 10

    EU1011DV

    GWHD09A3NK3DB/O

    4

    628

    4

    33.5

    Scroll

    -10T43

    Capillary throttling

    Transducer starting

    4CYC11233

    64550844

    9.52

    2-1.4

    Aluminum fin-copper tube

    /

    0.3

    2.5

    83020

    30

    T1

    I

    Auto defrost

    Axial fan-1

    400

    1.2

    54

    3.8

    IP24

    Outdoor

    unit

    Connecti

    on Pipe

    Outer Diameter

    Max Distance

    R410A / 1.25

    45/50

    878X360X590

    64

    848X320X540

    The above data is subject to change without notice. Please refer to the nameplate of the unit.

  • 7/30/2019 09 12 GEI Service Manual

    7/70

    COOLING HEATING COOLING HEATING

    3200/2550 4000/2900 4100/3500 4300/3850

    1200/730 1400/820 1500/1084 1500/1067

    1360 1400 1600 1650

    6 6.2 7 7.2

    2.67/3.49 2.86/3.54 2.73/3.23 2.87/3.61

    Model of Indoor Unit

    Fan Motor Speed (r/min) (H/M/L)

    Output of Fan Motor (w)

    Input of Heater (w)

    Fan Motor Capacitor (uF)

    Fan Motor RLA(A)

    Fan Type-Piece

    Diameter-Length (mm)

    Evaporator

    Pipe Diameter (mm)

    Row-Fin Gap(mm)

    Coil length (l) x height (H) x coil width

    (L)

    Swing Motor Model

    Output of Swing Motor (W)

    Fuse (A)Sound Pressure Level dB (A) (H/M/L)

    Sound Power Level dB (A) (H/M/L)

    Dimension (W/D/H)( mm)

    Dimension of Package (W/D/H)( mm)

    Net Weight /Gross Weight (kg)

    zH05ycneuqerFdetaR

    Total Capacity (W)

    Model ACP-09CH25GEI

    FunctionV042~022hP1egatloVdetaR

    Power Input (W) (High/Normal)

    Rated Input (W) (High/Normal)

    Rated Current (A) (High/Norma)

    Air Flow Volume (m3/h) (H/M/L) 450

    2.1)h/l(emuloVgniyfidimuheD

    C.O.P / EER (W/W) (High/Normal)

    Indoor

    unit

    ACP-09CH25GEI/I

    1160 /1010 /780

    14

    None

    1

    0.14

    Cross flow fan

    97-583

    Aluminum fin-copper tube

    7

    2-1.4

    580X228.6X25.4

    MP24GA

    2

    Controller3.15 transformer0.240 / 36 / 33

    50 / 46 / 43

    770X180X250

    855X272X330

    8.5/12.5

    ACP-12CH35GEI

    1Ph 220~240V

    50Hz

    550

    1.6

    ACP-12CH35GEI/I

    1250 / 1100 / 1050

    20

    None

    1

    0.152

    Cross flow fan

    92.1616

    Aluminum fin-copper tube

    7

    Controller3.15 transformer0.242 / 39 / 38

    2-1.4

    681324.338.1

    MP28EA

    2

    52 / 49 / 48

    830189285

    900265385

    11/14

  • 7/30/2019 09 12 GEI Service Manual

    8/70

    Model of Outdoor Unit ACP-12CH35GEI/O

    BA1H290ZR6-CledoMrosserpmoC

    yrotorniwTepyTrosserpmoC

    L.R.A. (A) 33

    29.3)A(ALRrosserpmoC

    069)W(tupnIrewoProsserpmoC

    33211CYC4rotcetorPdaolrevO

    gnilttorhtyrallipaCdohteMgnilttorhT

    gnitratsrecudsnarTdohteMgnitratS

    Working Temp Range ( 51-) T 43

    ebutreppoc-nifmunimulAresnednoC

    25.9)mm(retemaiDepiP

    4.1-2)mm(paGniF-swoR

    Coil length (l) x height (H) x coil

    width (L)64550844

    02038)L/M/H()mpr(deepSrotoMnaF

    03)W(rotoMnaFfotuptuO

    Fan Motor RLA(A) 0.35.2)Fu(roticapaCrotoMnaF

    /tinUroodtuOfoemuloVwolFriA

    Fan Type-Piece Axial fan-1

    004)mm(retemaiDnaF

    tsorfedotuAdohteMgnitsorfeD

    Climate Type T1

    Isolation I

    42PInoitcetorPerutsioM

    Permissible Excess ive Operating

    Pressure for the Discharge

    Side(MPa)

    3.8

    Permissible Excessive Operating

    Pressure for the SuctionSide(MPa)

    1.2

    Sound Pressure Level dB (A)

    (H/M/L)55

    Sound Power Level dB (A) (H/M/L) 65

    045X062X848)mm()H/D/W(noisnemiD

    Dimension of Package (W/D/H)(

    mm)878X360X610

    44/04)gk(thgieWssorG/thgieWteN

    72.1/A014R)gk(egrahCtnaregirfeR

    Length (m) 4

    6(1/4)

    12(1/2)

    5

    10

    6(1/4)

    12(1/2)

    5

    10

    64

    R410A / 1.2

    40/44

    878X360X590

    848X320X540

    Outdoor

    unit

    Connecti

    on Pipe

    Outer Diameter

    Max Distance

    54

    1.2

    3.8

    IP24

    I

    T1

    Auto defrost

    400

    64550844

    2-1.4

    Axial fan-1

    /

    2.50.3

    ACP-09CH25GEI/O

    Capillary throttling

    Int11l-3979

    960

    3.92

    4

    Twin rotory

    33

    C-6RZ092H1AB

    9.52

    Aluminum fin-copper tube

    -15 T 43

    Transducer starting

    30

    83020

    The above data is subject to change without notice. Please refer to the nameplate of the unit.

  • 7/30/2019 09 12 GEI Service Manual

    9/70

    COOLING HEATING COOLING HEATING

    3300/2500 4000/2700 4100/3500 4300/3850

    1250/730 1400/845 1500/1160 1560/1270

    1360 1480 1600 1650

    6.1 6.7 7 7.2

    2.64/3.42 2.70/3.20 2.73/3.02 2.76/3.03

    Model of Indoor Unit

    Fan Motor Speed (r/min) (H/M/L)

    Output of Fan Motor (w)

    Input of Heater (w)

    Fan Motor Capacitor (uF)

    Fan Motor RLA(A)

    Fan Type-Piece

    Diameter-Length (mm)

    Evaporator

    Pipe Diameter (mm)

    Row-Fin Gap(mm)

    Coil length (l ) x height (H) x coi l width

    (L)

    Swing Motor Model

    Output of Swing Motor (W)

    Fuse (A)Sound Pressure Level dB (A) (H/M/L)

    Sound Power Level dB (A) (H/M/L)

    Dimension (W/D/H)( mm)

    Dimens ion of Package (W/D/H)( mm)

    Net Weight /Gross Weight (kg)

    52 / 49 / 48

    830189285

    998364370

    16/20

    Controller3.15 transformer0.242 / 39 / 38

    2-1.4

    681324.338.1

    MP28EA

    2

    Cross flow fan

    92.1616

    Aluminum fin-copper tube

    7

    20

    None

    1

    0.152

    770X190X250

    960X335X365

    8.5/12.5

    GWHD12A6NK3DD

    1Ph 220~240V

    50Hz

    550

    1.6

    GWHD12A6NK3DD /I

    1250 / 1100 / 1050

    2

    Controller3.15 transformer0.240 / 36 / 33

    50 / 46 / 43

    7

    2-1.4

    580X228.6X25.4

    MP24GA

    Indoor

    unit

    GWHD09A3NK3DC/I

    1160 /1010 /780

    14

    None

    1

    0.14

    Cross flow fan

    97-583

    Aluminum fin-copper tube

    490

    Dehumidifying Volume (l/h) 1.2

    C.O.P / EER (W/W) (High/Normal)

    Power Input (W) (High/Normal)

    Rated Input (W) (High/Normal)

    Rated Current (A) (High/Norma)

    Air Flow Volume (m3/h) (H/M/L)

    Rated Frequency 50Hz

    Total Capacity (W)

    Model GWHD09A3NK3DC

    FunctionRated Voltage 1Ph 220~240V

  • 7/30/2019 09 12 GEI Service Manual

    10/70

    Model of Outdoor Unit GWHD12A6NK3DD/O

    Compressor Model C-6RZ092H1AB

    Compressor Type Twin rotory

    L.R.A. (A) 33

    Compressor RLA(A) 3.92

    Compressor Power Input(W) 960

    Overload Protector Int11l-3979

    Throttling Method Capillary throttling

    Starting Method Transducer starting

    Working Temp Range () -10T43Condenser Aluminum fin-copper tube

    Pipe Diameter (mm) 9.52

    Rows-Fin Gap(mm) 2-1.4

    Coil length (l) x height (H) x coil

    width (L)64550844

    Fan Motor Speed (rpm) (H/M/L) 83020

    Output of Fan Motor (W) 30

    Fan Motor RLA(A) 0.3Fan Motor Capacitor (uF) 2.5

    Air Flow Volume of Outdoor Unit /

    Fan Type-Piece Axial fan-1

    Fan Diameter (mm) 400

    Defrosting Method Auto defrost

    Climate Type T1

    Isolation I

    Moisture Protection IP24

    Permissible Excess ive Operating

    Pressure for the Discharge

    Side(MPa)

    3.8

    Permissible Excess ive Operating

    Pressure for the SuctionSide(MPa)

    1.2

    Sound Pressure Level dB (A)

    (H/M/L)55

    Sound Power Level dB (A) (H/M/L) 65

    Dimension (W/D/H)( mm) 848X260X540

    Dimension of Package (W/D/H)(

    mm )878X360X590

    Net Weight /Gross Weight (kg) 40/45

    Refrigerant Charge (kg) R410A / 1.27

    Length (m) 4

    6(1/4)

    12(1/2)

    5

    10

    4

    Twin rotory

    33

    C-6RZ092H1AB

    9.52

    Aluminum fin-copper tube

    -10T43

    Transducer s tarting

    30

    83020

    GWHD09A3NK3DC/O

    Capillary throttling

    Int11l-3979

    960

    3.92

    64550844

    2-1.4

    Axial fan-1

    /

    2.50.3

    I

    T1

    Auto defrost

    400

    54

    1.2

    3.8

    IP24

    Outdoor

    unit

    Connecti

    on Pipe

    Outer Diameter

    Max Distance

    64

    R410A / 1.2

    40/44

    878X360X590

    848X320X540

    6(1/4)

    12(1/2)

    5

    10

    The above data is subject to change without notice. Please refer to the nameplate of the unit.

  • 7/30/2019 09 12 GEI Service Manual

    11/70

    3

    Component Name

    Indoor unit

    Outdoor Unit

    panelAir inlet Display

    Wrapping Tape

    Power

    Guide Louver Air out let

    Display window

    Remote

    plug

    controllerset temperature

    Air inlet

    Air outlet

    Connecting pipe

    Connecting wire

    Drainage Pipe

    received windowremote control

    coolingheating

    power/run

    fan

    auto

    Dehumidify

  • 7/30/2019 09 12 GEI Service Manual

    12/70

    4 Overall and Installing Dimension

    Overall and Installing Dimension of Indoor Unit

    Air inlet grill

    Left Tube-exit SignRight Tube-exit SignTop View

    Rear View

    Ceiling

  • 7/30/2019 09 12 GEI Service Manual

    13/70

    Overall and Installing Dimension of Indoor Unit

    Air inlet grill

    Left Tube-exit Sign Right Tube-exit SignTop View

    Rear View

    Ceiling

  • 7/30/2019 09 12 GEI Service Manual

    14/70

    Overall and Installing Dimension of Outdoor Unit

    Handle

    Bolt

    Nut

    Wrench

    Over 600 Over 500

    Over 300

    Over 500

    Unit: mm

  • 7/30/2019 09 12 GEI Service Manual

    15/70

    55555 Electrical Diagram

  • 7/30/2019 09 12 GEI Service Manual

    16/70

  • 7/30/2019 09 12 GEI Service Manual

    17/70

    ACP-09CH25GEI

  • 7/30/2019 09 12 GEI Service Manual

    18/70

    +

    -

    L

    0

    0

    0

    +-

    L

    0

    0

    0

    ACP-12CH35GEI

  • 7/30/2019 09 12 GEI Service Manual

    19/70

    66666

    Remote Control ler Function Manual and Operating Instructions

    Remote Control ler Function Manual

    This function manual is for D C Inverter LGW Series:

    6.1.1 Temperature Parameters

    Indoor preset temperature (Tpreset)

    Indoor ambient temperature (Tamb.)

    6.1.2 Basic Functions

    Once energized, the compressor should in no way be restarted unless after 3-minute time interval at least.

    6.1.2.1 Cooling Mode

    6.1.2.1.1 Working Conditions and Process of Cooling

    When Tamb.Tpreset COOL mode will act, the compressor and outdoor fan will run, and the indoor fan will run at the set speed.

    When Tamb Tpreset-2 , the compressor will stop, the outdoor fan will delay 30 seconds to stop, and the indoor fan willrun at the set speed.

    When Tpreset-2 Tamb Tpreset ,the unit will maintain its original operating status.Under this mode, the 4-way valve will be de-energized and the temperature can be set within a range from 16 to

    30.The unit will adjust the running frequency of the compressor automatically according to the change of ambient temperature.

    Stop cooling

    Start cooling

    Original operating status

    Tamb

    Tpreset

    Tpreset

    Preset speed

    Run Stop

    Compressor

    Outdoor fan

    Indoor fan

    3min.

    6.1.2.1.2 Protection

    Ant if reeze Protect ion

    Under dehumidifying and cooling mode,after the compressor has run for about 10 minutes, if it is detected that the evaporator

    tube temperature is too low, the compressor will stop, the outdoor fan will stop after 30s delay, the indoor fan and swing

    motor will maintain their original operating status while under cooling mode, when under dehumidifying, the indoor fan will

    run at low speed and the swing motor will maintain its original operating status. When antifreeze protection is released

    and the compressor has stopped for 3 minutes, the complete unit will resume its original operating status.During antifreeze protection

    Compressor

    Outdoor fan

    Indoor fan

    Run Stop

    3min.

    Overcurrent Protection

    If total current is high, the compressor will run in limited or dropped frequency. When total current goes on rising over the

    specified value, the compressor will stop, the outdoor fan will delay 30 seconds to stop.

    6.1.2.2 Dehumidifying Mode6.1.2.2.1 Working Conditions and Process of Dehumidifying

    When T amb.> Tpreset the unit will run under dehumidifying mode, in which case the compressor and outdoor fan will startto run, the indoor fan will run at low speed.

    When Tpreset -2 T amb.Tpreset , the unit will maintain its original operating status.When Tamb.< Tpreset-2, the compressor will stop ,the outdoor fan will stop after 30s delay and the indoor fan will run at low speed.

    Under this mode, the reversal valve will be de-energized and the temperature can be set within a range from 16 to

    30.The unit will adjust the running frequency of the compressor automatically according to the change of ambient temperature.

  • 7/30/2019 09 12 GEI Service Manual

    20/70

    Stop

    Dehumidifying

    Original operating status

    Compressor

    Outdoor fan

    Indoor fan

    Compressor

    Outdoor fanIndoor fan

    Tpreset

    TpresetTamb

    low speed

    Run

    Run Stop6.1.2.2.2 ProtectionProtection is the sme as that under cooling mode.

    6.1.2.3 Heating Mode6.1.2.3.1 Working Conditi ons and Process of HeatingWhen T amb.Tpreset +2 , the unit will run under heating mode, in which case the reversal valve, compressor andoutdoor fan will be simultaneously started, and the indoor fan will be started after2 minutes the latest.When Tpreset +2

  • 7/30/2019 09 12 GEI Service Manual

    21/70

    6.1.2.5 AUTO modeIn this mode, the system selects COOL, HEAT and FAN mode automatically according to the change of ambient temperature.

    The protection function is the same with that of COOL/HEAT mode.

    The unit will adjust the running frequency of the compressor automatically according to the change of ambient temperature.

    6.1.3 Other control6.1.3.1 ON / OFF

    Each time the On/Off button of the remote controller is pressed, the On/Off state will switch once.

    6.1.3.2 MODE selection

    Press the MODE button on the remote controller to select and display the following modes:

    AUTO, COOL, DRY, FAN, HEAT,AUTO.

    6.1.3.3 TEMP. setting button

    Each time TEMP + or TEMP - button is pressed, the set temperature will be increased or decreased by 1 .Adjusting range

    is 16~30 . In AUTO mode, this button does not function.

    6.1.3.4 AUTO key

    When the unit is stop, press AUTO key,the unit will run under AUTO mode and the swing motor starts. If there is remote

    When the unit is running, press AUTO key,the unit will be stopped.

    control signal, the main unit will run according to the signal.

    6.1.3.5 Timer control

    The unit is turned on or off according to the timer set by the remote controller.

    Set the Temperature Tpreset

    Setting SLEEP function under HEAT mode, the preset temperature will automatically decrease by 1 after 1hour and

    decrease by another 1 after 2 hours. Preset temperature will decrease by 2 in total within 2 hours. After that, the

    unit will run at this preset temperature.

    Set the Temperature Tpreset

    Setting SLEEP function under COOL or DEHUMIDIFY mode, the preset temperature will automatically rise by 1 after 1

    hour and rise by another 1 after 2 hours. Preset temperature will rise by 2 in total within 2 hours. After that, the unit will

    run at this preset temperature.

    If set sleep function under fan or auto mode, the

    set temperature will remain unchanged.

    6.1.3.6 Sleep Function

    Tpreset

    Tpreset +2

    Tpreset +1

    1 hour 2 hours Over 2 hours

    Tpreset

    Tpreset -1

    Tpreset -2

    1 hour 2 hours Over 2 hours

    Once the sleep function is set, the indoor fan will

    run at low speed.

    6.1.3.7 Indoor fan control

    Use the remote controller to set the indoor fan running at HIGH, MED or LOW speed. At this time the fan will run

    at high, medium or low speed. It can also be set to AUTO and the indoor fan will select fan speed(HIGH, MED or

    LOW) automatically according to ambient temperature.

    The indoor fan, once running at one speed, will not turn to another speed within 3.5 minutes.

  • 7/30/2019 09 12 GEI Service Manual

    22/70

    6.1.3.8 Power supply for outdoor unitThe power supply for outdoor unit is turned on in AUTO, COOL, HEAT andDehumidify mode under turn-on state.

    The power supply for outdoor unit will delay 3 minutes to turn off under turn-off state or in the FAN mode under turn-on state.

    Use the SWING button of the wireless remote control to control SWING On and Off. Swing will only act when the indoor fan

    6.1.3.9 Swing control

    is running. After power on, the up/down swing motor will turn the guide louver back to 0 position to close the air outlet vent;after

    the unit is turned on, if the swing function has set, the guide louver will stop at current position synchronously as the indoor

    stop. When the indoor fan start to run, the guide louver will resume swing status.

    When the unit is power on or receives remote control signal or the auto key be pressed,the buzzer will give out a beep.

    6.1.3.10 Buzzer control

    Mode; Swing; Set fan speed, Set temperature.

    6.1.3.11 Power-off memory function

    6.1.4Common protection function6.1.4.1Overload pretection

    When Ttube is detected higher, the compressor will run in limited frequency.When Ttube is detected too high, the compressor will stop and

    the outdoor fan will delay 30s to stop; under AUTO HEAT or HEAT mode, indoor fan will blow 60s at low fan speed and then stop, under

    other mode, the indoor fan will run at set speed.

    (Ttube: at cooling,it detects the temp. of outdoor heat exchanger,at heating,it detects the temp. of indoor heat exchanger. )

    6.1.4.2 Compressor discharge temperature protection

    When discharge temperature is too high to over the specified value, the compressor will stop,the outdoor fan will delay 30s

    to stop; under AUTO HEAT or HEAT mode, indoor fan will blow 60s at low fan speed and then stop, under other mode, the

    indoor fan will run at set speed. When discharge temperature resume normal and the compressor has stopped for 3 mins,

    the unit will resume its original operating status.

    6.1.4.3 Communication malfunctionThere is communication malfunction if it can not receiving correct signal for 3 minutes continuously, in which case, the unit

    will stop as meeting the set temperature.

    6.1.4.4 Module protection

    6.1.4.5 Indoor Indicator

    During running, press the swing key two times continuously within 1s can turn on/off the light. Under normal running, the

    power indicator, mode indicator, fan indicator and set temperature indicator will display the current status. when receives

    remote control signal, the set temperature will display in blinking for 10s while at other time, the set temperature indicator

    displays the ambient temperature .

    When module is in protection, the compressor will be stopped ,after it has stopped for 3 minutes,the compressor will

    resume to running. During module protection period, the indoor unit displays H5 and stops as meeting the set temperature.

  • 7/30/2019 09 12 GEI Service Manual

    23/70

    Remote Contro ller Function Manual

    This function manual is forDD, DC Model

    6.2.1 Temperature Parameters

    Indoor preset temperature (Tpreset)Indoor ambient temperature (Tamb.)

    6.2.2 Basic Functions

    Once energized, the compressor should in no way be restarted unless after 3-minute time interval at least.

    6.2.2.1 Cooling Mode

    6.2.2.1.1 Working Conditions and Process of Cooling

    When Tamb.Tpreset COOL mode will act, the compressor and outdoor fan will run, and the indoor fan will run at the set speed.

    When Tamb Tpreset-2 , the compressor will stop, the outdoor fan will delay 30 seconds to stop, and the indoor fan willrun at the set speed.

    When Tpreset-2 Tamb Tpreset ,the unit will maintain its original operating status.Under this mode, the 4-way valve will be de-energized and the temperature can be set within a range from 16 to

    30.The unit will adjust the running frequency of the compressor automatically according to the change of ambient temperature.

    Stop cooling

    Start cooling

    Original operating status

    Tamb

    preset

    Tpreset

    Preset speed

    Run Stop

    Compressor

    Outdoor fan

    Indoor fan

    3min.

    6.2.2.1.2 Protection

    Ant if reeze Protect ion

    Under dehumidifying and cooling mode, after the compressor has run for about 10 minutes, if it is detected that the evaporator

    tube temperature is too low, the compressor will stop, the outdoor fan will stop after 30s delay, the indoor fan and swingmotor will maintain their original operating status while under cooling mode, when under dehumidifying, the indoor fan will

    run at low speed and the swing motor will maintain its original operating status. When antifreeze protection is released

    and the compressor has stopped for 3 minutes, the complete unit will resume its original operating status.

    During antifreeze protection

    Compressor

    Outdoor fan

    Indoor fan

    Run Stop

    3min.

    Overcurrent Protection

    If total current is high, the compressor will run in limited or dropped frequency. When total current goes on rising over the

    specified value, the compressor will stop, the outdoor fan will delay 30 seconds to stop.

    6.1.2.2 Dehumidifying Mode6.1.2.2.1 Working Conditions and Process of Dehumidifying

    When T amb.> Tpreset the unit will run under dehumidifying mode, in which case the compressor and outdoor fan will startto run, the indoor fan will run at low speed.

    When Tpreset -2 T amb.Tpreset , the unit will maintain its original operating status.When Tamb.< Tpreset-2, the compressor will stop ,the outdoor fan will stop after 30s delay and the indoor fan will run at low speed.

    Under this mode, the reversal valve will be de-energized and the temperature can be set within a range from 16 to

    30.The unit will adjust the running frequency of the compressor automatically according to the change of ambient temperature.

  • 7/30/2019 09 12 GEI Service Manual

    24/70

    Stop

    Dehumidifying

    Original operating status

    Compressor

    Outdoor fan

    Indoor fan

    Tpreset

    TpresetTamb

    low speed

    Run Stop6.2.2.2.2 Protection

    Protection is the sme as that under cooling mode.

    6.2.2.3 Heating Mode(cooling only un it has not this function)6.2.2.3.1 Working Conditi ons and Process of Heating

    Compressor

    Outdoor fan

    Indoor fan

    Run

    When T amb.Tpreset +2 , the unit will run under heating mode, in which case the reversal valve, compressor andoutdoor fan will be simultaneously started, and the indoor fan will be started after2 minutes the latest.When Tpreset +2

  • 7/30/2019 09 12 GEI Service Manual

    25/70

    6.2.3Common protection function6.2.3.1Overload pretection

    When Ttube is detected higher, the compressor will run in limited frequency. When Ttube goes on rising over the specifiedvalue, the compressor will stop ; under AUTO HEAT or HEAT mode, indoor fan will blow 60s at set speed and then stop,

    under other mode, the indoor fan will run at set speed.

    (Ttube: at cooling,it detects the temp. of outdoor heat exchanger,at heating,it detects the temp. of indoor heat exchanger. )

    6.2.3.2 Compressor discharge temperature protection

    When discharge temperature is too high to over the specified value, the compressor will stop, When discharge temperatureresume normal and the compressor has stopped for 3 mins,the unit will resume its original operating status.

    6.2.3.3 Communication malfunctionThere is communication malfunction if it can not receiving correct signal for 3 minutes continuously, in which case, the

    outdoor unit will stop, the indoor unit will stop as meeting the set temperature.6.2.3.4 Module protectionWhen module is in protection, the compressor will stop, after the compressor has stopped for 3 minutes, it will resume

    to running. During module protection period, the indoor unit displays malfunction and the whole unit stops .

    6.2.4 Other control6.2.4.1 ON / OFFEach time the On/Off button of the remote controller is pressed, the On/Off state will switch once.

    6.2.4.2 MODE selection

    Press the MODE button on the remote controller to select and display the following modes:AUTO, COOL, DRY, FAN, HEAT,AUTO.

    6.2.4.3 TEMP. setting button

    Each time TEMP + or TEMP - button is pressed, the set temperature will be increased or decreased by 1 .Adjusting range

    is 16~30 . In AUTO mode, this button does not function.

    6.2.4.4 AUTO key

    When the unit is stop, press AUTO key,the unit will run under AUTO mode and the swing motor starts.When the unit is running, press AUTO key,the unit will be stopped.

    6.2.4.5 Timer control

    The unit is turned on or off according to the timer set by the remote controller.

    Set the Temperature Tpreset

    Setting SLEEP function under HEAT mode, the preset temperature will automatically decrease by 1 after 1hour and

    decrease by another 1 after 2 hours. Preset temperature will decrease by 2 in total within 2 hours. After that, the

    unit will run at this preset temperature.(cooling only unit has not this function)

    Set the Temperature Tpreset

    Setting SLEEP function under COOL or DEHUMIDIFY mode, the preset temperature will automatically rise by 1 after 1

    hour and rise by another 1 after 2 hours. Preset temperature will rise by 2 in total within 2 hours. After that, the unit will

    run at this preset temperature.

    If set sleep function under fan or auto mode, the

    set temperature will remain unchanged.

    6.2.4.6 Sleep Function

    Tpreset

    Tpreset +2

    Tpreset +1

    1 hour 2 hours Over 2 hours

    Tpreset

    Tpreset -1

    Tpreset -2

    1 hour 2 hours Over 2 hours

    6.2.4.7 Indoor fan controlUse the remote controller to set the indoor fan running at HIGH, MED or LOW speed. At this time the fan will run

    at high, medium or low speed. It can also be set to AUTO and the indoor fan will select fan speed(HIGH, MED orLOW) automatically according to ambient temperature.

  • 7/30/2019 09 12 GEI Service Manual

    26/70

    The indoor fan, once running at one speed, will not turn to another speed within 3.5 minutes.

    6.2.4.8 Power supply for outdoor unitThe power supply for outdoor unit is turned on in AUTO, COOL, HEAT and Dehumidify mode under turn-on state.

    The power supply for outdoor unit will delay 3 minutes to turn off under turn-off state or in the FAN mode under turn-on state.

    6.2.4.9 Swing controlUse the SWING button of the wireless remote control to control SWING On and Off. Swing will only act when the indoor fan

    is running. After power on, the swing motor will reset to close the air outlet vent;after the unit is turned on,if

    the swing function has not set, the guide louver will first turn to D1, then turn back to L on standby under

    cooling ; while under heating, it will stop at D1. If the swing function has set, the guide louver will swing

    between L1 and D1.When the unit is turned off, the guide louver will swing back to 0 position.

    When the unit is power on or receives remote control signal or the auto key be pressed,the buzzer will

    6.2.4.10 Buzzer control

    give out a beep.

    6.2.4.11 Power-off memory functionMemory contents: Mode, Swing, Set temp, Set fan speed and Timer,etc. If the unit is running before de-energization, after

    re-energized, it needs at least 3 minutes for the outdoor unit be powered on by indoor unit, if the unit is stop beforede-energization, after re-energization, the outdoor unit will be powered on by indoor unit immediately .

    6.2.4.12 Delay Protection for CompressorUnder Cool, Dehumidify , Heat mode, there must be 3minutes delay befor each time the compressor starts.

    6.2.4.13 Outdoor Unit Electric Heating Strip ControlIf the outdoor ambient sensor is malfunction, the compressor heating strip and condenser heating strip will stop working

    or work according to below logic control:

    1). If the outdoor ambient temperature is lower and the compressor do not start, the compressor heating strip will work,

    if the compressor is running or the compressor is not running but the outdoor ambient temperature is higher then thespecified value, the compressor heating strip will not work. If the compressor is not running and the outdoor ambienttemperature is within the specified value, the compressor heating strip will maintain its original operating status.

    2). If the outdoor ambient temperature is lower , the condenser heating strip will work,if the outdoor ambient temperature

    is higher then the specified value, the condenser heating strip will not work. If the outdoor ambient temperature is withinthe specified value, the condenser heating strip will maintain its original operating status.

    6.2.4.14 Outdoor Indicator

    Meaning1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    Red Yellow Greenblink 1 time

    blink 1 time

    blink2 times

    blink ing

    blink2 times

    blink3times

    blink3 times

    blink4times

    blink5times

    blink6times

    blink7times

    blink8times

    blink4times

    blink5times

    blink6times

    blink7times

    blink8times

    compressor starts

    defrost

    Antifreeze Protection

    IPM Protection

    overcurrent protection

    overload stop protection

    discharge stop protection

    compressor overload

    limited frequency(current)

    malfunction

    (Antifreeze)outdoor Ttube senor

    meeting the temp. for start

    Communication normal

    protection

    dropped frequency(discharge)

    dropped frequency

    limited frequency(overload)

    malfunctionoutdoor Tamb senor

    malfunctionoutdoor Tdischargesenor

  • 7/30/2019 09 12 GEI Service Manual

    27/70

    77777 Disassembly and Assembly Procedures

    Disassembly Process of Indoor Unit

    Operating Procedures / Photos

    Disassemble Front Panel and

    Pull open the front panel, unscrew the screw

    fixing the receiving window, remove the guardboard, pull out the connecting terminal,unscrew

    the fixing screws on the elextric box top cover,

    remove the top cover,then pull out the panel alone

    the fixing groove on front case.

    (refer to Fig.7-1)

    Fig.7-1

    elextric box

    panel

    screwconnectionterminal top coverguard board

    groove

    Disassemble Filter

    Pull the filterupward a little and then push it

    inward to remove the filter.

    (refer to Fig.7-2)Filter

    Fig.7-2

    Fig.7-3

    Guide Louver

    Disassemble Guide Louver

    Manually bend the guide louver to loosen the

    clasp on it and then remove the guide louver.

    (refer to Fig.7-3)

    clasp

  • 7/30/2019 09 12 GEI Service Manual

    28/70

    Operating Procedures / Photos

    Disassemble Front Case

    Unclench the three screw covers,unscrew the three

    screws fixing the front case, pull open the clasp on front

    case and pull backward to remove the front case.

    (refer to Fig. 7-4)Screw Cover

    Fig. 7-4

    Screwclasp front case

    Disassemble Cover of Electric Box

    Loosen the three clasps, lift upward and remove

    the cover of electric box.

    clasps

    Fig. 7-5

    (refer to Fig. 7-5)

    cover of electric box

    Disassemble Water Tray

    claspWater Tray

    Unscrew the fixing screw on water tray, loose the

    clasp at the other side, and disconnect the terminal

    of the stepping motor and lift the water tray upward

    to remove it.

    terminal

    Fig. 7-6

    (refer to Fig. 7-6;7-7)Screw

  • 7/30/2019 09 12 GEI Service Manual

    29/70

    Operating Procedures / Photos

    Disassemble Electric Box

    Remove the breakwater film.

    Remove the grounding wire on the evaporator.

    Take out the tube sensor.

    Pull out the plugging connector of the indoor motor

    (refer to Fig. 7-7)

    Tube sensor

    and unscrew the fixing screw on electric box to

    remove it.

    grounding wireRoom sensor

    breakwater film.

    Fig. 7-7

    screw

    plugging connector

    screw

    rear pipe clamp

    Disassemble Evaporator

    Evaporator

    Unscrew the screw fixing the rear pipe clamp to

    remove it.

    (refer to Figure 7-8)

    Unscrew the screws fixing the evaporator, two on the

    left and two on the right (note: one of the screws is

    under the sponge,you should rive off the sponge first.)Manually lift the evaporator,and release the side

    clasp of the evaporator from the groove.

    Carefully take out the evaporator and pay attention

    to protect the connecting pipe.

    (refer to Fig. 7-9, 7-10)

    Fig. 7-8

    Fig. 7-9

    Screw

  • 7/30/2019 09 12 GEI Service Manual

    30/70

    Operating Procedures / Photos

    Evaporator

    Screw clasp sponge

    Fig. 7-10

    Screw

    Use screwdriver to unscrew the two screws fixing

    the motor clamp, and remove the motor clamp.

    Unscrew the three holding screws at the shaft

    sleeve, and remove the motor.

    (refer to Fig. 7-11, 7-12)

    motor clamp

    Disassemble Motor

    Fig. 7-11

    Screw

    motor

    Cross Flow FanFig. 7-12

  • 7/30/2019 09 12 GEI Service Manual

    31/70

    Operating Procedures / Photos

    Disassemble Cross Flow Fan

    Unscrew the screw fixing the bearing holder, remove

    the bearing holder, then remove the cross flow fan.

    Cross Flow Fan

    Bearing Holder

    Screw

    Fig. 7-13

    (refer to Fig. 7-13)

  • 7/30/2019 09 12 GEI Service Manual

    32/70

    Operating Procedures / Photos

    Disassemble Top Cover and Handle

    Use screwdriver to unscrew the fixing screw at the

    handle, push down and remove the handle. Unscrew

    the three screws around the top cover, and remove

    the top cover.

    (refer to Figure 7-14)

    Top Cover Handlescrew screw

    Figure 7-14

    Disassemble Rear Grill

    Screw out the 4 self tapping screws on rear side

    plate and chassis of valve supporter and side

    plate of condenser can take off rear grill.

    screw

    Grill

    Figure 7-15

    (refer to Figure 7-15)

    Disassemble Components of Panel

    Screw out the 5 tapping screws on panel and

    chassis of valve supporter and side plate of

    condenser can take off components of panel.screw

    Panel

    (refer to Figure 7-16)

    Figure 7-16

    Disassembly Procedures for Outdoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    33/70

    Operating Procedures / Photos

    Disassemble electric install plate

    Screw out the 3 bolts that fixing on electric install

    plate, plug out lead inserter of compressor and

    fan motor to take off electric install plate.

    (refer to Figure 7-17)bolts

    Figure 7-17

    electric install plate

    Disassemble Right Side Plate

    Screw out the 5 bolts on rear side plate can take

    off components of right side plate.

    (refer to Figure 7-18)

    bolts

    tighten nut

    axial-flow vane

    Loosen tighten nut by spanner to take off nuts,

    spring washer, flat washer, and take off axial-flow

    vane forcibly.(refer to Figure7-19)

    Disassemble axial-flow vane

    Figure 7-19

    Figure 7-18

  • 7/30/2019 09 12 GEI Service Manual

    34/70

    Operating Procedures / Photos

    Disassemble Motor and Motor Support

    Unscrew the four tapping screws fixing the motor,

    and remove the motor. Unscrew the two tapping

    screws fixing the motor support, and lift the motor

    support to remove it.

    Motor Support

    tapping screws

    Motor(refer to Figure 7-20)

    Figure 7-20

    Disassemble 4-Way Valve

    Screw off the holding nut of the 4-way valve coil

    and remove the coil. Use wet cotton cloth to wrap

    the 4-way valve, unsold the four soldering points

    connecting the 4-way valve, and remove the

    4-way valve. Be quick during the unsoldering

    process, pay attention to keep the wrapping clothwet and do not allow the soldering flame to burn

    the compressor lead-out cable.

    4-way valve

    soldering points

    holding nut

    (Note: only after discharging all freon).

    (refer to Figure 7-21)

    Figure 7-21

    Disassemble Capillary Subassembly

    Unsolder the soldering points connecting the

    capillary subassembly and the other pipelines, and

    remove the capillary subassembly.

    Capillary Subassembly

    Figure 7-22

    (refer to Figure 7-22)

  • 7/30/2019 09 12 GEI Service Manual

    35/70

    Operating Procedures / Photos

    Disassemble Valves

    Small Valves

    Unscrew the two screws fixing the big valve,

    unsolder the soldering point between the big

    valve and the return-air duct and remove the big

    valve.

    (Note: when unsoldering the soldering point, use

    wet cloth to completely wrap the big valve to

    prevent valve body from being harmed by high

    temperature.)Unscrew the two screws fixing the small valve,

    unsolder the soldering point connecting the small

    valve and the fork type pipe, and remove the small

    valve.

    (refer to Figure 7-23)

    bolts

    Big Valves

    Figure 7-23

    Unscrew the three nuts with washers at the foot of

    the compressor. Unsolder the soldering points at

    the suction and the discharge pipes of the compressor,carefully remove the pipes and take out the

    compressor.

    (refer to Figure 7-24) compressor boltFigure 7-34

    Disassemble Compressor

    Figure 7-24

  • 7/30/2019 09 12 GEI Service Manual

    36/70

    Operating Procedures / Photos

    Disassembly Procedures for Outdoor Unit

    Disassemble Top Cover and Handle

    Use screwdriver to unscrew the fixing screw at the

    handle, push down and remove the handle. Unscrew

    the three screws around the top cover, and remove

    the top cover.

    (refer to Figure 7-25)

    Top Cover Handlescrew screw

    Figure 7-25

    Disassemble Rear Grill

    Screw out the 4 self tapping screws on rear side

    plate and chassis of valve supporter and side

    plate of condenser can take off rear grill.

    screw

    Grill(refer to Figure 7-26)

    Figure 7-26

    Figure 7-27

    Disassemble Components of Panel

    Screw out the 5 tapping screws on panel and

    chassis of valve supporter and side plate of

    condenser can take off components of panel.screw

    Panel

  • 7/30/2019 09 12 GEI Service Manual

    37/70

    Operating Procedures / Photos

    Disassemble Right Side Plate

    Screw out the 7 bolts on rear side plate can take

    off components of right side plate.

    (refer to Figure 7-28)

    bolts

    right side plate

    Figure 7-28

    Figure 7-29

    Figure 7-30

    Disassembling the reactor box

    and electric box

    Unscrew the 2 screws on the cover of electric box

    and remove the cover.Unscrew the 2 screws that fix

    the reactor box, take off the sensor support and take

    out the reactor box.Unscrew the 4 screws that fix the

    reactor to take out the reactor.

    Unscrew the 2 screws that fix the electric box,

    loosen each wire bundle and unplug the

    connection wire to take off the electric box.

    (refer to Figure 7-29,7-30)

    screws

    electric box

    cover of electric box

    screws

  • 7/30/2019 09 12 GEI Service Manual

    38/70

    Operating Procedures / Photos

    Disassemble axial-flow vane

    tighten nut

    axial-flow vane

    Loosen tighten nut by spanner to take off nuts,

    spring washer, flat washer, and take off axial-flow

    vane forcibly.

    (refer to Figure7-31)

    Figure 7-31

    Unscrew the 4 screws fixing the motorand remove

    the motor , unscrew the 2 screws fixing the motor

    (refer to Figure 7-32)Screw

    Motor Support

    Screw

    support, and motor support.

    Figure 7-32

    Screw off the holding nut of the 4-way valve coil

    and remove the coil. Use wet cotton cloth to wrap

    the 4-way valve, unsold the four soldering points

    connecting the 4-way valve, and remove the

    4-way valve. Be quick during the unsoldering

    process, pay attention to keep the wrapping clothwet and do not allow the soldering flame to burn

    the compressor lead-out cable.

    4-way valve

    soldering points

    4-way valve coil(Note: only after discharging all freon).

    (refer to Figure 7-33)Figure 7-33

    Disassemble Motor and Motor Support

    Disassemble Motor and Motor Support

    Disassemble 4-way valve

  • 7/30/2019 09 12 GEI Service Manual

    39/70

    Operating Procedures / Photos

    Disassemble Capillary

    Unsolder the soldering points ofthe capillary

    subassembly and remove the capillary. Make

    sure that do not let any welding dregs to block

    Capillary subassembly

    the capillary.

    (refer to Figure 7-34)

    (refer to Figure 7-35)

    compressor

    Figure 7-34

    Figure 7-35

    Figure 7-36

    Small Valves

    Unscrew the two screws fixing the big valve,

    unsolder the soldering point between the bigvalve and the return-air duct and remove the big

    valve.

    (Note: when unsoldering the soldering point, use

    wet cloth to completely wrap the big valve to

    prevent valve body from being harmed by high

    temperature.)

    Unscrew the two screws fixing the small valve,

    unsolder the soldering point connecting the small

    valve and the fork type pipe, and remove the small

    valve.

    bolts

    Big Valves

    Disassemble Valves

    Disassemble Compressor

    Unscrew the three nuts at the foot ofthe compressor.

    Unsolder the soldering points at the suction and the

    discharge pipes of the compressor,carefully remove

    the pipes and take out the compressor.

    (refer to Figure 7-36)

    foot nut

  • 7/30/2019 09 12 GEI Service Manual

    40/70

    8

    40

    Exploded View and Components and Parts List

    Exploded View of Components and Parts of Indoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    41/70

    GWHD09A3NK3DA/I ACP-09CH25GEI/I1 Wall-Mounting Frame 01252220 01252220

    2 Rear Case 222020012 222020012

    3 Evaporator Assy 01002070 01002070

    4 Cross Flow Fan 10352001 10352001

    5 Ring of Bearing 76512203 76512203

    6 Fan Bearing 76512210 76512210

    7 Drainage Pipe 05232411 05232411

    8 Water Tray 201820272 201820272

    9 Swing Louver 10512080 10512080

    10 Swing Linkage 1 10582002 10582002

    11 Swing Linkage 2 10582003 10582003

    12 Front Case 20002211 20002211

    13 Screw Cover 24252006 24252006

    14 Filter 11122002 11122002

    15 Remote Control Y812A 30518001 30518001

    16 Receiver Board 30545702 30545702

    17 Decorate Piece 68012019 68012019

    18 Front Panel 20002209 20002209

    19 Guide Louver 2 10512034 10512034

    20 Guide Louver 1 10512033 10512033

    21 Motor MP28VA 15212110 15212110

    Motor Clamp A 26112023 26112023

    Motor Clamp 26112014 /

    Motor FN14A 15012108 /

    Motor FN14G 150121081 15012108124 Electric Box Cover 22242030 22242030

    25 Terminal Board T4B3A 42011233 42011233

    26 Covering Plate 201220061 201220061

    27 Electric Box 20102178 20102178

    28 Main PCB B9M823AJ 30039802 30039046

    29 Transformer 48X26G 43110233 43110233

    30 Wire Clamp 71010103 71010103

    31 Rear Clamp 24242001 24242001

    32 Connecting Cable 400205235 400205235

    33 Power Cord 400204643 40020389

    34 Room Sensor 15K 390000451 390000451

    35 Tube Sensor 20K 390000591 390000591

    36 swing louver clamp 10582409 10582409

    37 swing louver 10582408 10582408

    38 swing louver(up) 10542004 10542004

    39 swing louver(down) 10542005 10542005

    No Description

    1

    1

    Qty

    1

    1

    1

    1

    1

    1

    12

    1

    1

    1

    3

    2

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    11

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    Part Code

    22

    23

    1

    1

    1

    1

    1

    41

    Components and Parts List of Indoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    42/70

    Exploded View of Components and Parts of Indoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    43/70

    GWHD12A6NK3DA/I ACP12CH35GEI/I

    1 Wall-Mounting Frame 01252384

    2 Rear Case 22202050

    3 Evaporator Assy 010020212

    4 Cross Flow Fan 10352005

    5 Ring of Bearing 76712015

    6 Fan Bearing 76512210

    7 Drainage Pipe 05232411

    8 Water Tray 201820392

    9 Swing Louver 10512041

    10Swing Linkage 10582439

    11 Front Case 20002295

    12 Screw Cover 24252007

    13 Filter 11122440

    14 Remote Control YB1B4 30511005

    15 Decorate Piece 68012019

    16 Receiver Board 30545552

    17 Front Panel 20002292

    18 Guide Louver 26112043

    19 Guide Louver 26112042

    20 Motor MP28EA 15212105

    21 Cold Plasma Device 111400051 22 Cold Plasma Device Cover 22262005

    23 Right Motor Clamp 26112429

    24 Bearing Holder 26152423

    25 Motor FN20G 15012058

    26 Electric Box Cover 22242017

    27 Terminal Board T4B3A 42011233

    28 Covering Plate 20102123

    29 Electric Box 20102108

    30 Main PCB B9H823J 30039801

    31 Transformer 57X25C 43110237

    32 Wire Clamp 71010103 /

    32 Wire Clamp 71010003

    33 Rear Clamp 26112430

    34 Connecting Cable 40020538

    35 Power Cord 400204643

    36 Room Sensor 15K 390000451

    37 Tube Sensor 20K 390000591

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    12

    1

    1

    1

    1

    1

    3

    2

    1

    1

    1

    12

    1

    1

    1

    1

    1

    No Description

    1

    1

    Qty

    Part Code

    Components and Parts List of Indoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    44/70

    Exploded View of Components and Parts of Indoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    45/70

    GWHD09A3NK3DB/I ACP-09CH25GEI/I

    1 Wall-Mounting Frame 01252220 01252220 1

    2 Rear Case 222020012 222020012 1

    3 Evaporator Assy 01002511 01002511 1

    4 Cros s Flow Fan 10352001 10352001 1

    5 Ring of Bearing 76512203 76512203 1

    6 Fan Bearing 76512210 76512210 1

    7 Drainage Pipe 05232411 05232411 1

    8 Water Tray 201820272 201820272 1

    9 Swing Louver 10512080 10512080 12

    10 Swing Linkage 1 10582002 10582002 1

    11 Swing Linkage 2 10582003 10582003 112 Front Case 20002210 20002210 1

    13 Screw Cover 24252006 24252006 3

    14 Filter 11122002 11122002 2

    15 Remote Control Y812A 30518001 30518001 1

    16 Decorate Piece 68012019 68012019 1

    17 Receiver Board 30545702 30545702 1

    18 Front Panel 20002209 20002209 1

    19 Guide Louver 2 10512034 10512034 1

    20 Guide Louver 1 10512033 10512033 1

    21 Motor MP28VA 15212110 15212110 1

    22 Motor Clamp A 26112017 26112017 122 Motor Clamp 26112014 26112014 1

    23 Motor FN14A 15012108 15012108 1

    23 Motor FN14G 150121081 150121081 1

    24 Electric Box Cover 22242030 22242030 1

    25 Terminal Board T4B3A 42011233 42011233 1

    26 Covering Plate 201220061 201220061 1

    27 Electric Box 20102178 20102178 1

    28 Main PCB 9M82 30039046 30039046 1

    29 Room Sensor 15K 390000451 390000451 1

    30 Tube Sensor 20K 390000591 390000591 1

    31 Transformer 48X26G 43110233 43110233 1

    32 Wire Clamp 71010103 71010103 1

    32 Wire Clamp 71010003 71010003 1

    33 Rear Clam p 24242001 24242001 1

    34 Connecting Cable 40020531 40020531 1

    35 Soft Pipe Assy 05232030 05232030 1

    36 Power Cord 400204643 400204643 1

    37 swing louver clamp 10582409 10582409 1

    38 swing louver 10582408 10582408 1

    39 swing louver(up) 10542004 10542004 1

    40 swing louver(down) 10542005 10542005 1

    No Description Qty

    Part Code

    Components and Parts List of Indoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    46/70

    Exploded View of Components and Parts of Indoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    47/70

    GWHD12A6NK3DB/I GWHD12A6NK3DD/I

    1 Wall-Mounting Frame 01252384 01252384 1

    2 Rear Case 22202050 22202050 1

    3 Evaporator Assy 010021971 010021971 1

    4 Cros s Flow Fan 10352005 10352005 1

    5 Ring of Bearing 76712015 76712015 1

    6 Fan Bearing 76512210 76512210 1

    7 Drainage Pipe 05232411 05232411 1

    8 Water Tray 201820392 201820392 1

    9 Swing Louver 10512041 10512041 12

    10 Swing Linkage 10582439 10582439 1

    11 Front Case 20002295 20002295 112 Screw Cover 24252007 24252007 3

    13 Filter 11122440 11122440 2

    14 Remote Control Y812A 30518001 30518001 1

    15 Decorate Piece 68012019 68012019 1

    16 Receiver Board 30545552 30545552 1

    17 Front Panel 20002292 20002292 1

    18 Guide Louver 26112043 26112043 1

    19 Guide Louver 26112042 26112042 1

    20 Motor MP28VA 15212105 15212105 1

    21 Cold Plasma Device 111400051 111400051 1

    22 Cold Plasma Device Cover 22262005 22262005 223 Right Motor Clamp 26112429 26112429 1

    24 Bearing Holder 26152423 26152423 1

    25 Motor FN20G 15012058 15012058 1

    26 Electric Box Cover 22242017 22242017 1

    27 Terminal Board T4B3A 42011233 42011233 1

    28 Covering Plate 20102123 20102123 1

    29 Electric Box 20102108 20102108 1

    30 Main PCB 9H82 30039085 30039085 1

    31 Room Sensor 15K 390000451 390000451 1

    32 Tube Sensor 20K 390000591 390000591 1

    33 Transformer 57X25C 43110237 43110237 1

    34 Wire Clamp 71010103 / 1

    34 Wire Clamp 71010003 71010003 1

    35 Rear Clam p 26112430 26112430 1

    36 Connecting Cable 400205311 400205311 1

    37 Soft Pipe Assy 052320301 052320301 1

    38 Power Cord 400204643 40020389 1

    No Description Qty

    Part Code

    Components and Parts List of Indoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    48/70

    Exploded View of Components and Parts of Outdoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    49/70

    QtyGWHD09A3NK3DA/O GWHD12A6NK3DA/O

    1 Front Panel 01533005 01533005 12 Clapboard 01233381 01233381 12 Clapboard parts 01233014 01233014 13 Reactor Box C 01413504 01413504 14 Reactor 1 43130165 43130165 15 Metal Base 01203358 01203358 16 Compressor EU1011DV 00100125 00100125 17 One Way Valve 07130103 07130103 18 Bolt 70212014 70212014 39 Nut 70310014 70310014 310 Valve Support 01713041 01713041 111 Right Side Plate 01303048 01303048 112 Valve 1/2" 07100006 07100006 1

    13 Valve 1/4" 07100003 07100003 114 4-Way Valve 430004032 430004032 115 Big Handle 26233433 26233433 116 4-way valve coil 430004002 430004002 117 Wire Clap 71010103 71010103 117 Wire Clamp 71010003 71010003 118 Insulation Piece D 70410525 70410525 119 Terminal Board 42011113 42011113 120 Electric Box 2 01413051 01413051 121 Capacitor 1 33010054 33010057 122 Capacitor 2 33310054 33310054 123 Electric Box A 20103501 201035011 124 PCB W923HB 30039243 30039244 124 PCB WB9235A 30039251 30039250 125 RoomTemperature Sensor 3900012123 3900012123 126 Tube Temperature Sensor 390002068 39000071 127 Exhaust Gas Temperature 39000016 39000016 128 Electric Box Cover 01413048 01413048 129 Power Module 32210096 32210093 130 Rectifier S25VB60 46010601 46010602 231 Radiator 49010212 49010212 132 Rear Grill 01473030 01473030 133 Condenser Assy 011035072 011035073 134 Top Cover 01253443 01253443 135 Motor Support 01703391 01703391 136 Reactor 2 43130169 43130169 137 Reactor Box B 01413503 01413503 138 Motor FW25K 15013067 15013067 139 Axial Flow Fan 10333413 10333413 1

    40 Nut M6 70310131 70310131 141 Front Grill 22413431 22413431 142 4-way rever -sing valve 03023234 03023234 143 Capillary Assy 03003618 03003867 144 Overload Protector 145 Sensor Insert 42020063 42020063 146 Drainage Connecter 06123401 06123401 147 Compressor Gasket 348 Capacitor 3 33010803 33010803 149 Capacitor 33010026 33010026 150 Heater 1 76510004 76510004 151 Heater 2 76513501 76513501 1

    No Des cription

    Part Code

    Components and Parts List of Outdoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    50/70

    Exploded View of Components and Parts of Outdoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    51/70

    GWHD09A3NK3DB/O

    1 Front Panel 01533005 1

    2 Clapboard parts 01233014 1

    3 Reactor Box C 01413504 1

    4 Reactor 1 43130165 1

    5 Drainage Connecter 06123401 1

    6 Metal Base 01203358 1

    7 Overload Protector 00180039 1

    8 Compressor EU1011DV 00100125 1

    9 Freon Charge Nozzle 06120010 1

    10 Compressor Gasket 3

    11 Bolt 70212014 3

    12 Nut 70310014 3

    13 Valve Support 01703081 114 Right Side Plate Assy 01303086 1

    15 Quick Connector (Male) 06393002 1

    16 Capillary Assy 03003618 1

    17 4-Way Valve 430004032 1

    18 4-way rever -sing valve 03023666 1

    19 Big Handle 26233433 1

    20 4-way valve coil 430004002 1

    21 Wire Clap 71010103 1

    21 Wire Clamp 71010003 1

    22 Insulation Piece D 70410525 1

    23 Electric Box 2 01413051 1

    24 Capacitor 3 33010803 1

    25 Capacitor 1 33010054 126 Capacitor 2 33310054 1

    27 Electric Box A 201035011 1

    28 PCB W923HAA 30039243 1

    28 PCB WB9235 30039251 1

    29 RoomTemperature Sensor 390002061 1

    30 Tube Temperature Sensor 390002068 1

    31 Exhaust Gas Temperature 39000016 1

    32 Electric Box Cover 01413048 1

    33 Power Module 32210096 1

    34 Rectifier S15VB60 46010601 2

    35 Sensor Insert 42020063 1

    36 Radiator 49010212 1

    37 Rear Grill 01473030 1

    38 Condenser Assy 011035072 1

    39 Top Cover 01253443 1

    40 Motor Support 01703084 1

    41 Reactor 2 43130169 1

    42 Reactor Box B 01413503 1

    43 Motor FW25K 15013067 1

    44 Axial Flow Fan 10333413 1

    45 Nut M6 70310131 1

    46 Front Grill 22413431 1

    47 Heater 1 76510004 1

    48 Heater 2 76513501 1

    No Des criptionPart Code

    QtyGWHD12A6NK3DB/O

    01533005

    01233014

    01413504

    43130165

    06123401

    01203358

    00180039

    00100125

    06120010

    70212014

    70310014

    0170308101303086

    06393002

    03003867

    430004032

    03023666

    26233433

    430004002

    71010103

    71010003

    70410525

    01413051

    33010803

    3301005433310054

    201035011

    30039244

    390001781

    39000071

    39000016

    01413048

    32210093

    46010602

    42020063

    49010212

    01473030

    011035073

    01253443

    76513501

    30039250

    10333413

    70310131

    22413431

    76510004

    01703084

    43130169

    01413503

    15013067

    Components and Parts List of Outdoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    52/70

    Exploded View of Components and Parts of Outdoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    53/70

    1 Front Panel 1

    2 Clap Board 1

    3 Reactor Box C 1

    4 PFC Inductance 0.8mH/20A 1

    5 Drainage Connecter 1

    6 Reactor Support 1

    7 Overload Protector 1

    8Compressor C-

    6RZ092H1AB1

    9 One Way Valve 1

    10 Compressor Gasket 3

    11 Bolt 3

    12 Nut 3

    13 Heating cable 1

    14 Valve Support 1

    15 Right Side Plate 116 Valve 1/2" 1

    17 Valve 1/4" 1

    18 Capillary Assy 1

    19 4-Way Valve 1

    204-way Rever-sing Valve

    Component1

    21 Big Handle 1

    22 4-way Valve Coil 1

    23 Wire Clap 1

    24 Insulation Piece D 1

    25 Terminal Board A 1

    26 Electric Box 2 1

    27 Electric Box 1 127 Electric Box 1

    28 PCB W9M32 1

    28 PCB W9M32B 1

    29RoomTemperature Sensor

    15K1

    29 Temperature Sensor 1

    30 Sensor 20K 1

    31Exhaust Gas Temperature

    Sensor 50K1

    32 Electric Box Cover 1

    33 Rectifier S25VB60 2

    33 Rectifier S25VB60 1

    34 Sensor Insert 1

    35 Radiator 1

    36 Rear Grill 1

    37 Condenser Assy 1

    38 Top Cover 1

    38 Top Cover Assy 1

    39 Motor Support 1

    40 Motor FW30K 1

    41 Axial Flow Fan 1

    42 Nut 1

    43 Front Grill 1

    44 Heating cable chassis 1

    No Description QtyPart Code

    01533005

    01233012

    01413504

    99070120

    06123401

    01203524

    00183003

    00102004

    07130103

    76710236

    70210007

    70310011

    76513004

    01713041

    0130200407100006

    07100003

    03103186

    430004032

    03023670

    26233433

    430004002

    71010003

    70410525

    42011113

    01413025

    2010350120113001

    30039053

    30039154

    390001781

    3900012123

    39000071

    39000016

    01413048

    46010602

    46010602

    42020063

    49010213

    01473030

    70310131

    22413431

    76510004

    ACP-09CH25GEI/O

    01703084

    150130671

    011035077

    01253448

    01253261

    10333413

  • 7/30/2019 09 12 GEI Service Manual

    54/70

    Exploded View of Components and Parts of Outdoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    55/70

    1 Front Panel 1

    2 Clap Board 1

    3 Heating cable chassis 1

    4 Reactor Box C 1

    5 PFC Inductance 0.8mH/20A 1

    6 Drainage Connecter 1

    7 Reactor Support Assy 1

    8 Overload Protector 1

    9Compressor C-

    6RZ092H1AB1

    10 Heating cable 1

    11 Compressor Gasket 3

    12 Bolt 3

    13 Nut 3

    14 Valve Support 1

    15 Right Side Plate 116 Valve 1/2" 1

    17 Valve 1/4" 1

    18 Capillary Assy 1

    19 One Way Valve 1

    20 4-Way Valve 1

    214-way Rever-sing Valve

    Component1

    22 Big Handle 1

    23 4-way Valve Coil 1

    24 Wire Clap 1

    25 Insulation Piece D 1

    26 Terminal Board A 1

    27 Electric Box 2 128 Electric Box 1

    29 PCB W9M32C 1

    30Temperature Sensor

    15K1

    31 Sensor 20K 1

    32Exhaust Gas Temperature

    Sensor 50K1

    33 Electric Box Cover 1

    34 Rectifier S25VB60 1

    35 Sensor Insert 1

    36 Radiator 1

    37 Rear Grill 1

    38 Condenser Assy 1

    39 Top Cover Assy 1

    40 Motor Support 1

    41 Motor FW25K 1

    42 Axial Flow Fan 1

    43 Nut 1

    44 Front Grill 1

    No Description QtyPart Code

    01533005

    01233012

    76510004

    01413504

    99070120

    06123401

    01203524

    00183003

    00102004

    76513004

    76710236

    70210007

    70310011

    01713041

    0130304807100006

    07100003

    03103301

    07130103

    430004032

    03023670

    26233433

    430004002

    71010003

    70410525

    42011113

    0141302520113001

    46010602

    42020063

    49010213

    30039153

    3900012123

    39000071

    39000016

    ACP-12CH35GEI/O

    22413431

    150130671

    10333413

    70310131

    01473030

    0110350713

    01253261

    01703084

    01413048

  • 7/30/2019 09 12 GEI Service Manual

    56/70

    Exploded View of Components and Parts of Outdoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    57/70

    1 Front Panel 1

    2 Clap Board 1

    3 Reactor Box C 1

    4 PFC Inductance 0.8mH/20A 1

    5 Drainage Connecter 1

    6 Reactor Support 1

    7 Overload Protector 1

    8Compressor C-

    6RZ092H1AB1

    9 Freon Charge Nozzle 1

    10 Compressor Gasket 3

    11 Bolt 3

    12 Nut 3

    13 Heating cable 1

    14 Valve Support 1

    15 Right Side Plate 116 Quick Connector (Male) 1

    17 One Way Valve 1

    18 Capillary Assy 1

    19 4-Way Valve 1

    204-way Rever-sing Valve

    Component1

    21 Big Handle 1

    22 4-way Valve Coil 1

    23 Wire Clap 1

    24 Insulation Piece D 1

    25 Electric Box 2 1

    26 Electric Box 1 1

    26 Electric Box 127 PCB W9M32 1

    27 PCB W9M32B 1

    28RoomTemperature Sensor

    15K1

    28 Temperature Sensor 1

    29 Sensor 20K 1

    30Exhaust Gas Temperature

    Sensor 50K1

    31 Electric Box Cover 1

    32 Rectifier S25VB60 2

    32 Rectifier S25VB60 1

    33 Sensor Insert 1

    34 Radiator 1

    35 Rear Grill 1

    36 Condenser Assy 1

    37 Top Cover 1

    37 Top Cover Assy 1

    38 Motor Support 1

    39 Motor FW25K 1

    40 Axial Flow Fan 1

    41 Nut 1

    42 Front Grill 1

    44 Heating cable chassis 1

    No Description QtyPart Code

    GWHD09A3NK3DC/O

    01533005

    01233012

    01413504

    99070120

    06123401

    01203524

    00183003

    00102004

    06120010

    76710236

    70210007

    70310011

    76513004

    01703081

    0130308606393002

    07130103

    03103279

    430004032

    03023715

    26233433

    430004002

    71010003

    70410525

    01413025

    20103501

    2011300130039053

    01413048

    46010602

    46010602

    30039154

    390001781

    3900012123

    39000071

    39000016

    150130671

    01253448

    01253261

    01703084

    42020063

    49010213

    01473030

    0110350712

    10333413

    70310131

    22413431

    76510004

  • 7/30/2019 09 12 GEI Service Manual

    58/70

    Exploded View of Components and Parts of Outdoor Unit

  • 7/30/2019 09 12 GEI Service Manual

    59/70

    1 Front Panel 1

    2 Clap Board 1

    3 Reactor Box C 1

    4 PFC Inductance 0.8mH/20A 1

    5 Drainage Connecter 1

    6 Reactor Support 1

    7 Overload Protector 1

    8Compressor C-

    6RZ092H1AB1

    9 Freon Charge Nozzle 1

    10 Compressor Gasket 3

    11 Bolt 3

    12 Nut 3

    13 Valve Support 1

    14 Right Side Plate 1

    15 Quick Connector (Male) 116 One Way Valve 1

    17 Capillary Assy 1

    18 4-Way Valve 1

    194-way Rever-sing Valve

    Component1

    20 Big Handle 1

    21 4-way Valve Coil 1

    22 Wire Clap 1

    23 Insulation Piece D 1

    24 Electric Box 2 1

    25 Electric Box 1

    26 PCB W9M32C 1

    27 Temperature Sensor 128 Sensor 20K 1

    29Exhaust Gas Temperature

    Sensor 50K1

    30 Electric Box Cover 1

    31 Rectifier S25VB60 1

    32 Sensor Insert 1

    33 Radiator 1

    34 Rear Grill 1

    35 Condenser Assy 1

    36 Top Cover Assy 1

    37 Motor Support 1

    38 Motor FW25K 1

    39 Axial Flow Fan 1

    40 Nut 1

    41 Front Grill 1

    42 Heating cable chassis 1

    43 Heating cable 1

    No Description QtyPart Code

    GWHD12A6NK3DD/O

    01533005

    01233012

    01413504

    99070120

    06123401

    01203524

    00183003

    00102004

    06120010

    76710236

    70210007

    70310011

    01703081

    01303086

    0639300207130103

    0310330101

    430004032

    03023715

    26233433

    430004002

    71010003

    70410525

    01413025

    49010213

    20113001

    30039153

    390001212339000071

    39000016

    01413048

    46010602

    42020063

    22413431

    76510004

    76513004

    01473030

    0110350714

    01253261

    01703084

    150130671

    10333413

    70310131

  • 7/30/2019 09 12 GEI Service Manual

    60/70

    99999 Troubleshooting

    Common section

    Notice

    Air

    conditi

    onercannot

    start up

    Breaker trippedor fuse burnt out

    Air conditionerdoes not responseafter powered on.(The buzzer doesnot sound after the

    plug is connectedand the unit doesnot response afterthe remotecontroller is usedto turn it on)

    When the breaker is set ON, it will

    trip at once

    Remotecontroller doesnot receive signal(When poweredon, the buzzer

    will send out asound, unless it is

    broken)

    When the unit is turned on, the

    breaker will trip in a few minutes

    No power supply

    The power plug is not or poorlyconnected

    Controller fuse is burnt out

    Loose or poor contact of transformer

    connection, or transformer malfunction

    The controller is broken

    Batteries of remote controller are low

    Malfunction of remote controller

    Loose or poor connection of receivinghead

    Receiving head is broken

    Measure the insulating resistancefor grounding to confirm whetherthere is electrical leakage or shortcircuit in the unit

    Insulation malfunction of line or componenin the air conditioner. Insulation breakdowoccurs after radiation, which causes shorcircuit or electricity leakage. Measureinsulating resistance or use one-by-onelimination method;Malfunction of fuse. Replace it.

    Check power supply circuit

    Check and plug well plug, makeloosen contact firm

    Change control fuse

    Secure the wire connection: measurethe output voltage of the transformerand replace it if the value is wrong

    Re lace the controller

    Chan e batter

    First press the "AUTO" button of themanual switch. If there is no response,

    check according to the above method;if it is normal after the button is

    pressed, check if the installationlocation and wire connection of thereceiving head are correct. If correct,replace the receiving head, or theremote controller.

    When repairing, before the voltage between module PN is measured below 50V, do not touch any terminal

    to avoid electric shock.

  • 7/30/2019 09 12 GEI Service Manual

    61/70

    Improper setting of temperature

    Whether cooling (heating) load

    is ro er

    Adjust the set temperature

    Check the estimated load of cooling (heating)

    Leakage or shortage of refrigerant

    Leakage occurs between high andlow pressure inside compressor

    Malfunction of four-way valve

    Partial blockage of capillary

    Blockage of cooling system

    Replace the compressor

    Replace the four-way valve

    Replace the capillary

    Use the method of observing condensationon the evaporator and pressure value ofhigh pressure manometer to see whetherthe system is blocked and carry outcorresponding handling on the system

    Vacuumize after leakage detection

    and leakage repair. Charge refrigerant

    according to specification.

    Malfunction of

    refrigerant flow

    Poor thermal insulation of connecting

    i e of indoor and outdoor unit

    Ensure that both thick pipe and thin pipe are insulatedwell. The exposed part of the connector and copper pipe

    must be insulated as well.

    Heat exchanger of outdoor unit

    is blocked

    Air filters are blocked

    Fan speed is set too slow

    Fan speed turns low

    Improper installation location

    for outdoor unit

    Outdoor unit should be installed in a

    place with well ventilation

    Set the fan speed to high or medium

    s eed

    Clean the filter

    Clean the dust accumulated on thesurface of the heat exchan er

    Air circulation

    is insufficientamage o

    capacitordamaged

    Damage ofmotor

    Replace thecapacitor

    Replace the motor

    Flashing or awning can be installed appropriately. If themax. cooling capacity cannot be satisfied, replacement ofthe air conditioner is recommended.

    Maintain a certain degree of indoor sealability. Try not to

    use appliance with high amount of heat.

    Outdoor temperature is too high

    Indoor sealability is inadequate; too many

    people go in and out frequently; there is

    heating unit in the room.

    Poorcooling

    (heating)effect

  • 7/30/2019 09 12 GEI Service Manual

    62/70

    When unit iscooling orheating, bothcompressor andoutdoor fan don'trun

    When unit iscooling orheating, thecompressor runs

    but outdoor fandoesn't run

    When cooling orheating, outdoor

    fan runs, but

    compressor

    doesn't run.

    When cooling or

    heating, outdoor

    fan runs, butcompressor

    doesn't run.

    Fan doesn't runwhen FAN modeis set

    Abnormal power supply of outdoor unit

    Damage of outdoor main control board

    Breakage of outdoor power module

    Improper setting of temperature

    Breakage of outdoor fan motor

    Wrong wire connection

    Breakage of outdoor main control board

    Breakage of outdoor fan capacitor

    Malfunction of compressor

    Poor contact of connection between the

    main control board and module

    Abnormal input of power module

    Abnormal output of power module

    Compressor temperature is too high

    Wrong wiring

    Damage of outdoor main control board

    Check the circuit according to circuit diagram

    Replace the main control board

    Replace the power module

    Adjust the set temperature

    Replace the fan motor

    Wire according to the circuit diagram

    Replace the main control board

    Replace the fan capacitor

    Replace the compressor

    Re-fasten the connection

    Check if input is 320V. If not, replace the

    rectifier

    Replace the power module

    Cool the compressor for 30 min before running

    Wire according to the circuit diagram

    Replace the outdoor main control board

    Burn-out or broken wire of indoor fan

    motor

    Wrong wiring

    Circuit break or damage of fan motor

    ca acitor

    Repair or change the fan motor

    Wire according to the circuit diagram

    Replace the indoor main control board

  • 7/30/2019 09 12 GEI Service Manual

    63/70

    Water leakage

    Wrap of refrigerant pipe connector is

    Blockage or breakage of drainage hose

    not tight enough

    Replace the drainage hose

    Re-wrap and make it tight

    A

    bnormalsoundandshake

    Fan of indoor unit contacts other parts Adjust fan location

    There is foreign substance in indoor unit

    Compressor shakes too much

    Touch of pipeline of outdoor unit

    Touch of inner plates

    Touch of outdoor unit fan blade with

    Abnormal sound inside compressor

    Abnormal electromagnetic sound inside

    four-way valve when heating

    outer case

    Take out the foreign substance

    Adjust support washer of the compressor and

    Separate the touched pipeline

    tighten loose bolts

    Tighten connecting screws

    Stick shock-absorbing clay between plates

    Adjust fan position

    Short circuit inside electromagnetic valve.

    Replace compressor

    Replace the electromagnetic valve

    Compressor reverse;abnormal soundlike metal crash Turn the connection of the two of U; V; W

    Indoor unit is mounted in the thin wall

    cause syntonic sound

    window directly .Avoid to mount the indoor unit on the steel

    To mount the indoor unit in the strong andand thick wall

    Adopt some steps to damp vibration

  • 7/30/2019 09 12 GEI Service Manual

    64/70

    Compressor too hot, the stop often occur

    Compressor too hot,

    Ambient temperature is too high For safe use

    or directly under sunlight

    Change the mounting position

    once, or the stop

    just start and stop at

    often occur

    Check whether the outdoor unit is not mountedproperly such as outlet blockage; bad ventilation

    yes

    no

    yes

    yes

    yes

    yes

    yes

    yes

    yes

    yes

    yes

    no

    no

    no

    no

    no

    no

    no

    no

    Clean themCheck if the filter or the outdoor condenser dirty

    Check if the indoor and outdoor fans do not runor run too slowly and whether the outlet airflow

    is normal

    Check if the cooling system blockage, the frost

    on the capillary don't meltReplace blockage component

    Check if the power supply circuit for

    motor on the controller is normal or

    replace the motor

    The power is abnormal Add voltahe regulator,etc.

    Check if the system operating pressure is normal

    1.6-2.4 MPa for heating system)

    to confirm whether the refrigerant is leakage or mix

    with air (normal: 0.4-0.6MPa for cooling system, Recharge refrigerant

    Check the breadboards of indoor and outdoor units

    and the power supply circuit assembly Change the assembly or main PCB

    Change the power module

    Change the compressor

    Check the U ;V; W output of the outdoor powermodule for detail, see "Power Module protection"

    Check if the compressor is jammed or the

    wire-wound resistance is open or short circuit

  • 7/30/2019 09 12 GEI Service Manual

    65/70

    9.2 Malfunction display section

    Linge Wind D.C. Variable Frequency Series

    When malfunction or protection occurs in the air conditioner, corresponding code will be displayed on the screenof the indoor unit and the indicator of outdoor unit will blink accordingly as well. When protection or malfunction

    is eliminated, display will be back to normal

    Display code andmalfunction

    description of

    indoor unit

    (Mainboard) Yellow light blinks 1 time

    (Mainboard) Yellow light blinks 2 times

    (Mainboard) Yellow light blinks 3 times

    (Mainboard) Yellow light blinks 4 times

    (Mainboard) Yellow light blinks 5 times

    (Mainboard) Yellow light blinks 6 times

    (Mainboard) Yellow light blinks 7 times

    (Mainboard) Yellow light blinks 8 times

    (Mainboard) Red light blinks 1 time

    (Mainboard) Red light blinks 2 times

    Compressor is running (this is normal condition

    and the display of indoor unit is normal)

    Defrosting (display H1)

    Antifreezing protection (display of indoor unit

    displays is normal)

    IPM module protection (corresponds to H5 of

    indoor unit)

    Overcurrent protection (corresponds to E5 of

    indoor unit)

    Overload protection (corresponds to H4 of

    indoor unit)

    Discharge protection (corresponds to E4 of

    indoor unit)

    Compressor overload protection (corresponds toH3 of indoor unit)

    Dropped frequency (Discharge)

    Indicator display

    of outdoor unit

    E4: Compressor discharge protectionE5: Low voltage overcurrent protection

    E6: Communication malfunction

    F1: Indoor environmental sensor open or short circuit (the malfunction is detected for 30s

    continuously)

    F2: Indoor evaporator sensor open or short circuit (the malfunction is detected for 30s continuously)

    F3: Outdoor environmental sensor open or short circuit (the malfunction is detected for 30scontinuously)

    F4: Outdoor condenser sensor open or short circuit (the malfunction is detected for 30scontinuously)

    F5: Outdoor discharge sensor open or short circuit (after the compressor runs for 3 min, themalfunction is detected for 3s continuously)

    H3: Compressor overload protection

    H4: System malfunction (i.e. overload protection)

    H5: IPM module protection

    H1: Defrosting

    Limited frequency(current)

  • 7/30/2019 09 12 GEI Service Manual

    66/70

    Analysis or handling of some of the malfunction display:

    1. Compressor discharge protection (E4):

    Possible reasons: shortage of refrigerant; blockage of air filter; poor ventilation or air flow short passfor condenser; the system has noncondensing gas (such as air, water etc.); blockage of capillary assy(including filter); leakage inside four-way valve causes incorrect operation; malfunction ofcompressor; malfunction of protection relay; malfunction of discharge sensor; outdoor temperature toohigh.

    Handling method: refer to the malfunction analysis in the above section.

    2. Low voltage overcurrent protection (E5):

    Possible reason: Sudden drop of supply voltage.

    3. Communication malfunction (E6):

    Handling method: Check if communication signal cable is connected reliably

    4 Sensor open or short circuit (F1, F2, F3, F4, F5):

    Handling method: Check whether sensor is normal, connected with the corresponding position on thecontroller and if damage of lead wire is found

    5. Compressor overload protection (H3):

    Possible reasons: insufficient or too much refrigerant; blockage of capillary and increase of suction temp.;improper running of compressor, burning in or stuck of bearing, damage of discharge valve;

    malfunction of protector.Handling method: adjust refrigerant amount; replace the capillary; replace the compressor; useuniversal meter to check if the contactor of compressor is fine when it is not overheated, if not replacethe protector.

    6. System malfunction (H4):

    i.e. overload protection. When tube temperature (Check the temperature of outdoor heat exchangerwhen cooling and check the temperature of indoor heat exchanger when heating) is too high,

    protection will be activated.

    Possible reasons: Outdoor temperature is too high when cooling; insufficient outdoor air circulation;refrigerant flow malfunction.

    please refer to the malfunction analysis in the previous section for handling method .

    (Mainboard) Red light blinks 3 times

    (Mainboard) Red light blinks 4 times

    (Mainboard) Red light blinks 5 times

    (Mainboard) Red light blinks 6 times

    (Mainboard) Red light blinks 7 times

    (Mainboard) Red light blinks 8 times

    (Mainboard) Green light blinks

    Limited frequency(overload)

    Dropped frequency (Antifreeze Protection)

    Malfunction of outdoor tube sensor

    Malfunction of outdoor environmental sensor

    Malfunction of outdoor discharge sensor

    Starting temperature is reached. This is normal

    condition and display of indoor unit is normal

    Communication is normal

    Indicator display

    of outdoor unit

    Note: Malfunction display : blind 0.5s; stop 0.5s, there is 2s' interval between two malfunction displays

  • 7/30/2019 09 12 GEI Service Manual

    67/70

    7. Module protection (H5):

    Handling method:

    Check if the voltage between power module P and N is too low andif the current is too high. In normal condition, voltage between P and

    N should be about 320V.

    Normal

    Abnormal

    Check power supply circuit of outdoor unit (if PTC resistance

    rectifying bridge, reactor, capacitance etc. is ok).

    Temperature of power module is too high,which causes overheating protection

    Protection is still displayed

    Confirm the setting status of outdoor unit (cooling)

    Normal

    Confirm if outdoor fan motor is running; unplug the

    three connecting wires between U, V, W of compressor

    and power module. Turn on the unit to see if outdoorfan runs normally (about 1