rev. 03 08-01-2014 Control Narrative Logic for the new "CRUDE OIL MAIN PUMP" item D8-PAX60122B DS-8 CRUDE EXPORT SYSTEM DESCRIPTION The Crude Export System at DS-8 is comprised of four (4) Booster Pumps and four (4) Crude Oil Main Pumps. The Booster Pumps and Main Pumps operate in series. The Crude Oil Main Pumps are connected in parallel. The pumps have been divided into two groups, an East Station and a West Station: The pumps arrangement is presented diagrammatically below: All four (4) of the Booster Pumps and three (3) of the Crude Oil Main Pumps are existing units. The existing units are controlled by an existing relay based logic control system. The 4 th Crude Oil Main Pump, D8-PAX601022B, is new and will be controlled by a new PLC based system. This PLC based system will be housed in a new Main Control Panel, OIP601022, and associated unit

description

pump control

Transcript of 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

Page 1: 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

rev. 03 08-01-2014

Control Narrative Logic for the new

"CRUDE OIL MAIN PUMP" item D8-PAX60122B

DS-8 CRUDE EXPORT SYSTEM DESCRIPTION The Crude Export System at DS-8 is comprised of four (4) Booster Pumps and four (4) Crude Oil Main Pumps. The Booster Pumps and Main Pumps operate in series. The Crude Oil Main Pumps are connected in parallel. The pumps have been divided into two groups, an East Station and a West Station: The pumps arrangement is presented diagrammatically below:

All four (4) of the Booster Pumps and three (3) of the Crude Oil Main Pumps are existing units. The existing units are controlled by an existing relay based logic control system. The 4th Crude Oil Main Pump, D8-PAX601022B, is new and will be controlled by a new PLC based system. This PLC based system will be housed in a new Main Control Panel, OIP601022, and associated unit

Page 2: 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

rev. 03 08-01-2014

control panel ACP601022B. A control cabinet has been provided to allow future conversion of the control system for D8-PAX601022A should that be desired. The Control Narratives described herein relate strictly to 4th Crude Oil Main Pump, D8-PAX601022B.

DS‐8CRUDEEXPORTSYSTEMOPERATION A number of potential operating scenarios have been included in the design:

1. Booster Pumps Only 2. East Station and/or West Station Independent Operation 3. Combined Mode

Booster Pumps Only In this arrangement no Crude Oil Main Pumps are in operation. From 1 to 4 Booster Pumps may operate to ship the crude. Station Basis In this arrangement the Booster Pump(s) from the respective Station feed only their respective Crude Oil Main Pump(s). The manual Isolation Valve is “Closed” in this case. The number of Booster Pumps must equal the number of Crude Oil Main Pumps in operation at each station, either 1 or 2 pump sets at each Station. Common Basis In this arrangement all operating Booster Pump(s) feed a common suction header for the Crude Oil Main Pump(s). The manual Isolation Valve is “Open” in this case. The number of Booster Pumps must equal the number of Crude Oil Main Pumps in operation, from 1 to 4 pump sets.

Page 3: 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

rev. 03 08-01-2014

DESCRIPTION OF OPERATION "CRUDE OIL MAIN" PAX60122B Pls refer to: - 084488_P&ID piping & instrument diagram. - 084488_LCP local control panel lay-out & wiring diagram. - 084488_MCP_1 main control panel lay-out. - 084488_MCP-2 main control panel wiring diagram. - 084488_LOG logic diagram. - 084488_HMI HMI Operating Procedure (EMB A4-C139-752). LCP = Local Control Panel tag IQD8-LCP601022B MCP = Main Control Panel tag ACP601022B HMI = Human Main Interface (Touch-screen display) on the MCP tag OIP601022 A) - NORMAL START-UP

1. Pre-Set the Pump for Start-Up

Place OFF/LOCAL/AUTO key Selector Switch "HS-601022B-10" on LCP to “AUTO” position. Note that if in the "OFF" position the pump cannot be started. Indication of this switch position is provided at the MCP on HMI "XL-601022B-24" LOCAL and "XL-601022B-25" AUTO.

Note that when main pump D8-PAX601022B is operating it will be not stopped if OFF/LOCAL/AUTO selector switch "HS-601022B-10" is switched from LOCAL to AUTO position, and vice versa. The pump will stop if the Selector switch is positioned to "OFF".

2. Select The Operating Mode

Select "Booster Pumps - Station Basis or Common Basis” via software selector switch "HS-601022A/B-22" on HMI (common page for all main pumps D8-PAX601022A, D8-PAX601022B & D8-PAX6012A, D8-PAX6012B).

“Station Basis”: It is assumed that the manual “Isolation Valve” is closed and that the Booster Pump(s) are providing flow only to their respective Crude Oil Main Pump(s). In order for D8-PAX601022B to receive a Start permissive signal, there must be one more dedicated Booster Pump operating than Crude Oil Main Pump operating. If D8-PAX601022A is not operating then either D8-PAX601021A or D8-PAX601021B must be running. If D8-PAX601022A is operating then both D8-PAX601021A and D8-PAX601021B must be running to permit the 4th Crude Oil Main Pump to start.

“Common Basis”: It is assumed that the “Isolation Valve” is open and that the Booster Pump(s) are providing flow to the suction header to the Crude Oil Main Pump(s). In order for D8-PAX601022B to receive a Start permissive signal, there must be one more dedicated Booster Pump operating than Crude Oil Main Pumps operating.

Page 4: 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

rev. 03 08-01-2014

The selection of “Station Basis” or “Common Basis” is indicated at the HMI, "XL-601022A/B-22" or "XL-601022A/B-23", and the LCP, "XL-601022B-15" or "XL-601022B-16", respectively.

3. Set the time of timer "TIM-601022B-07" which controls the delay time for stop the main

pump, after dedicated booster pump is stopped.

4. Place LOCAL/OFF/REMOTE selector switch located on suction motor-driven valve "MOV-601022B-01" in REMOTE position.

With the switch on "REMOTE" the opening and the closure of the valve is automatic according to the logic described below.

5. Select LOCAL/OFF/REMOTE selector switch located on discharge motor-driven

valve "MOV-601022B-02" in REMOTE position. With the switch on "REMOTE" the opening and the closure of the valve is automatic according to the logic described below.

Note that with the switch in "LOCAL" for either "MOV-601022B-01" "MOV-601022B-02" it's possible to initiate the opening or the closure of the valve using push buttons on the electric actuator; this function will only be utilized in the case of a “Manual Start-up”.

If OFF/LOCAL/AUTO key Selector Switch "HS-601022B-10" is in “AUTO” then

both MOV’s must be set to “AUTO” in order for the normal start sequence to proceed.

6. Reset all shut-down conditions using Reset push-button "PB-601022B-15" on LCP. Should bearing temperatures, seal failure or motor failure conditions exceed the shutdown limits the start sequence will be inhibited.

7. The start-up sequence (motor-pump) is then initiated by pressing the Start push button

"PB-601022B-12" on LCP. Note that a Start push button "PB-601022B-02" has been provided on the MCP to facilitate remote starting but this pushbutton has been disabled. The start sequence will proceed automatically as follows:

7-1 The software timer "TIM-601022B-01" (PLC) which controls the time for start-up sequence is activated. At the end of the time, if the Main Pump is not in operation and the discharge valve is not open, the start-up sequence is interrupted.

7-2 The control system will check that the discharge valve "MOV-601022B-02" is in “Closed” position via "ZSL-601022B-02"; if the valve is not closed, then the control system will close it via a signal to the MOV.

Simultaneously with close command, the control system will insert software timer "TIM-601022B-02" (PLC). At the end of the time, if the discharge valve is not close, the start-up sequence is interrupted.

oliver.hermosa
Oval
oliver.hermosa
Typewritten Text
REMOTE
Page 5: 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

rev. 03 08-01-2014

7-3 The control system will check that the suction valve "MOV-601022B-01" is “Open” via "ZSH-601022B-01". If it is not opened, the control system will open it via a signal to the MOV.

Simultaneously with open command, the control system will insert software timer "TIM-601022B-03" (PLC). At the end of the time, if the discharge valve is not close, the start-up sequence is interrupted.

7-4 After confirmation is received that the suction valve is “Open” via "ZSH-601022B-01" , with the suction pressure > = 4,5 kg/cm2 via "PIT-601022B-01" (suction pressure non-low) and that the discharge valve is "Close" via "ZSL-601022B-02", the control system will send a signal to the electric motor of the pump to start.

7-5 Simultaneously with electric motor start command, the control system will insert software timer "TIM-601022B-04" (PLC) to override the interlock signal from pump bearings housing vibration "XAHH-601022B-01" & "XAHH-601022B-02" and from discharge pressure high "PAH-601022B-02".

7-6 When the motor starts a “Motor Running” signal will be provided from the Motor Control Center (MCC) which is located elsewhere. This signal will provide Status at the MCP and LCP, "XL-601022B-01" or "XL-601022B-11", respectively.

7-7 When the discharge pressure rises above 28,5 kg/cm2 via "PIT-601022B-02", the control system will open the discharge motor-driven valve "MOV-601022B-02".

Simultaneously with open command, the control system will insert software timer "TIM-601022B-05" (PLC). At the end of the time, if the discharge valve is not open, the start-up sequence is interrupted.

7-8 Once the discharge valve is “Open” via "ZSH-601022B-02" and TIM-601022B-04" (PLC) has timed out, if there are no vibration or discharge pressure alarms the system will generate a "PUMP CONTINUE RUNNING" signal.

7-9 All timers are internal to the PLC and are adjustable via software tools. Preliminary settings anticipated for the durations are indicated below:

TIMER (PLC) DURATION

TIM-601022B-01 140 sec

TIM-601022B-02 70 sec

TIM-601022B-03 70 sec

TIM-601022B-04 60 sec

TIM-601022B-05 70 sec

TIM-601022B-06 24 hour

TIM-601022B-07 5 sec

TIM-601022B-08 300 sec

oliver.hermosa
Oval
oliver.hermosa
Typewritten Text
SUCTION
oliver.hermosa
Rectangle
oliver.hermosa
Typewritten Text
PLEASE REVIEW THIS LINE. FROM 084488_LDG REV.2, THE PIT-02 DOES NOT HAVE ANY INPUT TO THE MOV-2 OPEN COMMAND. EXISTING CONTROL IS FOR MOV-2 TO CONTINUE TO OPEN AFTER PUMP START COMMAND PROVIDED AND WILL HAVE A SHUTDOWN IF NOT FULLY OPENED AFTER LAPSE OF TIM-05.
oliver.hermosa
Line
Page 6: 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

rev. 03 08-01-2014

7-10 The "Sequence Reset" pushbutton "PB-601022B-14", is used to close suction & discharge valves (initial position for start-up) with the following conditions: - Main Pump not running. - OFF/LOCAL/AUTO key Selector Switch "HS-601022B-10" on LCP to “OFF.”

- LOCAL/OFF/REMOTE selector switches located on suction & discharge motor- driven valves in "REMOTE" position.

B) - MANUAL PUMP START-UP

1. Pre-Set the Pump for Start-Up Place OFF/LOCAL/AUTO key Selector Switch "HS-601022B-10" on LCP to “LOCAL” position.

2. Select The Operating Mode Select "Booster Pumps - Station Basis or Common Basis” via software selector switch "HS-601022A/B-22" on HMI. See discussion under the Normal Start-up section.

3. Place LOCAL/AUTO selector switch located on suction motor-driven valve "MOV-

601022B-01" in LOCAL position and open the valve using the pushbuttons on the MOV.

4. Select LOCAL/AUTO selector switch located on discharge motor-driven valve "MOV-601022B-02" in LOCAL position. Close the valve to suit, using the pushbuttons on the MOV.

5. Reset all shut-down conditions using Reset push-button "PB-601022B-15" on LCP. Should bearing temperatures, seal failure or motor failure conditions exceed the shutdown limits the start sequence will be inhibited.

6. Set the time of timer "TIM-601022B-08" which controls the time for override position of discharge valve, for pump start-up sequence.

7. Press the Discharge Valve Override push button "PB-601022B-19" on LCP for insertion timer "TIM-601022B-08". Note: If the timer is activated, it's possible to start the pump with the discharge valve closed or open.

8. With suction valve open, suction pressure not low and discharge valve close or open, the start-up sequence (motor-pump) is then initiated by pressing the Start push button "PB-601022B-12" on LCP. After that, all automatic control protective devices will be active. Note that the control system will not override the motor protective circuit.

oliver.hermosa
Rectangle
oliver.hermosa
Typewritten Text
PLEASE CHECK THIS SETTING. FROM 084488_LDG, REV. 2, SHOULDN'T THIS BE "AUTO"?
oliver.hermosa
Line
oliver.hermosa
Oval
oliver.hermosa
Typewritten Text
REMOTE
oliver.hermosa
Oval
oliver.hermosa
Typewritten Text
REMOTE
Page 7: 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

rev. 03 08-01-2014

9. With main pump running, if the discharge valve is close, open the valve using the pushbuttons on the "MOV-601022B-02"

C) - MANUAL PUMP SHUTDOWN

1. The pump "PAX-601022B" may be manually stopped from the LCP, via "PB-601022B-13", or from the MCP, via "PB-601022B-03". The provision to manually stop "PB-601022B-30" the pump from a future/other remote location has also been provided. With these commands, we have: - Stop main motor. - Suction valve "MOV" closing command & Discharge valve "MOV" closing command. Note: After stop, is possible to re-start again the pump.

2. The pump "PAX-601022B" may be manually shut-down using "Emergency Stop Pushbutton" in the LCP, via Emergency "PB-601022B-11", or from the MCP, via "PB-601022B-01". With these command, we have: - Stop main motor - Suction valve & discharge valve "MOV" opening & closing inhibition. Note: After stop, start-up of the pump, is possible only after Shut-Down Reset via "PB-601022B-15", and Sequence Reset via "PB-601022B-14" from LCP.

D) - AUTOMATIC (INTERLOCK) PUMP SHUTDOWN

The pump "PAX-601022B" will automatically shut-down via the control system under the following conditions:

D1) - DISCHARGE VALVE POSITION - "MOV-601022B-02"

After the start sequence has successfully completed if the discharge vale is not open "ZSH-601022B-02".

D2) - SUCTION VALVE POSITION - "MOV-601022B-01"

After the start sequence has successfully completed if the discharge vale is not open "ZSH-601022B-01".

D3) - PUMP CASING TEMPERATURE

When the pump casing temperature "TIT-601022B-02". D4) - SUCTION LINE LOW PRESSURE

If the suction pressure is LOW (< 4,5 kg/cm2) via "PIT-601022B-01".

oliver.hermosa
Oval
oliver.hermosa
Oval
oliver.hermosa
Typewritten Text
VALVE
oliver.hermosa
Typewritten Text
SUCTION VALVE
Page 8: 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

rev. 03 08-01-2014

D5) - DISCHARGE LINE LOW PRESSURE

After the start sequence has successfully completed if the discharge pressure is LOW (< 24 kg/cm2) via "PIT-601022B-02".

D6) - DISCHARGE LINE HIGH PRESSURE

After the start-up sequence has successfully completed if the discharge pressure is still HIGH (> 30 kg/cm2) via "PIT-601022B-02".

D7) - PLAN 65 SEAL LEAKAGE DETECTOR (N.D.E. and D.E.)

After the start-up sequence has successfully completed if either level switch "LSH-601022B-01" or "LSH-601022B-02" trips after an adjustable time "TIM-601022B-06" delay of 0 to 24 hours . The Restriction Orifice, RO-601022B-01/ 02, is sized to allow a maximum of xx ml/minute to drain from the system without building level and activating the LSH.

D8) - PUMP BEARING TEMPERATURE

When the pump bearing temperature is too high (> 95 °C) "TIT-601022B-01" or "TIT-601022B-03".

D9) - MOTOR BEARING TEMPERATURE

When the motor bearing temperature is too high (> 100 °C) "TE-601022B-12" or "TE-601022B-13".

D10) - MOTOR WINDING TEMPERATURE

When the motor winding temperature is too high (> 155 °C) "TE-601022B-14 A/B/C/D/E/F".

D11) - PUMP BEARING HOUSING VIBRATION

After the start-up sequence has successfully completed if the vibration is still HIGH (> 8,5 mm/s RMS) via "XT-601022B-01" or "XT-601022B-02".

D12) – MOTOR FAILURE

Should the electric motor experience a problem it is protected by settings in its own Motor Control Center (MCC) which is located elsewhere. Should the motor shutdown or lock itself out to preclude subsequent start attempts, a signal will be provided at the MCP and LCP, "XL-601022B-03" or "XL-601022B-13", respectively.

Page 9: 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

rev. 03 08-01-2014

General Notes Applicable To All Shut-Downs

When the Crude Oil Main Pump PAX-601022B stops (due to a control interlock or manual pushbutton) indication is provided at the LCP and MCP, "XL-601022B-14" and "XL-601022B-04", respectively. When the Crude Oil Main Pump PAX-601022B stops (due to a control interlock or manual pushbutton) or the start-up sequence is interrupted, the closure of the suction valve "MOV-601022B-01" and the closure of discharge valve "MOV-601022B-02" automatically occurs if the LOCAL/AUTO selector switches located on suction/discharge motor-driven valve "MOV-601022B-01/02" is in AUTO position. All manual “Stop” pushbuttons are functional regardless of the position of “HS-601022B-10" on LCP, whether it is in “Local” or “AUTO” position. Note that when any working Crude Oil Main Pump stops there is no provision to automatically start another Crude Oil Main Pump. Should an operating Booster Pump stop there is no provision to automatically start another Booster Pump or to directly shutdown an operating Crude Oil Main Pump. Individual Crude Oil Main Pumps may shutdown in response to Low Suction Pressure (PIT-601022B-01in the case of the 4th Pump). It is suggested that the PIT on the suction of each of the Crude Oil Main Pumps have staggered settings to allow for sequential shutdown of Crude Oil Main Pumps should a Booster Pump(s) be lost during operation. Note: For main crude oil pumps "PAX-601022A" & "PAX-601022B" sequential shutdown, is determined by the setting of timer "TIM-601022A-07" or "TIM-601022B-07"

E) ALARMS & SHUTDOWNS INDICATION

All of the following will generate both audible and visual alarms in the Main Control Room and at the pump package:

Shut-Down Indications

- LOW suction pressure "PAL-601022B-01" on HMI and "PAL-601022B-03" on LCP. (see interlock ref. D4).

- LOW discharge pressure "PAL-601022B-02" on HMI and "PAL-601022B-04" on LCP. (see interlock ref. D5).

- HIGH discharge pressure "PAH-601022B-02" on HMI and "PAH-601022B-04" on LCP. (see interlock ref. D6).

- HIGH-HIGH temperature pump casing "TAHH-601022B-02" on HMI. (see interlock ref. D3)

- HIGH-HIGH temperature D.E. pump bearing "TAHH-601022B-01" on HMI. (see interlock ref. D8)

- HIGH-HIGH temperature N.D.E. pump bearing "TAHH-601022B-03" on HMI. (see interlock ref. D8)

oliver.hermosa
Oval
oliver.hermosa
Oval
oliver.hermosa
Typewritten Text
REMOTE
oliver.hermosa
Line
oliver.hermosa
Line
oliver.hermosa
Typewritten Text
ON BOTH LCP AND ON THE MOV'S
oliver.hermosa
Line
oliver.hermosa
Rectangle
oliver.hermosa
Typewritten Text
PLS. CHECK. IN 084488_LDG, REV. 2. TIM-07 CURRENTLY IS USED FOR OK TO START SIGNAL FOR BOOSTER PUMPS.
Page 10: 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

rev. 03 08-01-2014

- HIGH-HIGH temperature D.E. motor bearing "TAHH-601022B-12" on HMI. (see interlock ref. D9)

- HIGH-HIGH temperature N.D.E. motor bearing "TAHH-601022B-13" on HMI. (see interlock ref. D9).

- HIGH-HIGH temperature motor winding "TAHH-601022B-14 A/B/C/D/E/F" on HMI. (see interlock ref. D10), and common signal "TAH-601022B-18" on LCP.

- HIGH-HIGH vibration D.E. pump bearing housing "XAHH-601022B-01" on HMI. (see interlock ref. D11).

- HIGH-HIGH vibration N.D.E. pump bearing housing "XAHH-601022B-02" on HMI. (see interlock ref. D11).

- Seal Leakage D.E. "LAH-601022B-01" on HMI and "LAH-601022B-03" on LCP. (see interlock ref. D7)

- Seal Leakage N.D.E. "LAH-601022B-02" on HMI and "LAH-601022B-04" on LCP. (see interlock ref. D7) - MOV not OK position "VAX-601022B-26" on HMI. - Any of the above signals as well as the activation of any manual pump shutdown

pushbuttons will cause the Main Pump Shutdown indicator to be illuminated, "XL-601022B-04" on HMI and "XL-601022B-14" on LCP.

Alarm Indications

- HIGH temperature pump casing (> 65 °C) "TAH-601022B-02" on HMI and "TAH-601022B-05" on LCP. - HIGH temperature D.E. pump bearing (> 87 °C) "TAH-601022B-01" on HMI and "TAH-601022B-04" on LCP. - HIGH temperature N.D.E. pump bearing (> 87 °C) "TAH-601022B-03" on HMI and "TAH-601022B-06" on LCP. - HIGH vibration D.E. pump bearing housing (> 5,4 mm/s RMS) "XAH-601022B-01" on HMI and "XAH-601022B-03" on LCP. (during the motor start-up alarm bypassed). - HIGH vibration N.D.E. pump bearing housing (> 5,4 mm/s RMS) "XAH-601022B-02" on

HMI and "TAH-601022B-04" on LCP. (during the motor start-up alarm bypassed). - HIGH temperature D.E. motor bearing (> 90 °C) "TAH-601022B-12" on HMI and "TAH-601022B-16” on LCP. - HIGH temperature N.D.E. motor bearing (> 90 °C) "TAH-601022B-13" on HMI and "TAH-601022B-17” on LCP. - HIGH temperature motor winding (> 145 °C) "TAH-601022B-14 A/B/C/D/E/F" on HMI.

Page 11: 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

rev. 03 08-01-2014

- Common 24VDC Power Supply Failure "IAL-601022B-21" on HMI and Common 24VDC Power Supply Failure "XL-601022B-17" on LCP.

- MCP cabinet High Temperature "TAH-601022B-20" on HMI.

F) CONTROLS AND SIGNALS

The following controls & signals are available on the HMI (touch-screen) and/or LCP.

- MOV suction valve "MOV-601022B-01" position signals. Closed "ZLL-601022-01" on HMI, "ZLL-601022B-03" on LCP. Opened "ZLH-601022B-01" on HMI, "ZLH-6012B-03" on LCP.

- MOV discharge valve "MOV-601022B-02" position signals.

Closed "ZLL-601022-02" on HMI, "ZLL-601022B-04" on LCP. Opened "ZLH-601022B-02" on HMI, "ZLH-6012B-04" on LCP.

- Booster pumps running signals. Booster pump "D8-PAX601021A" running "XL-601021A-01" on HMI.

Booster pump "D8-PAX601021B" running "XL-601021B-01" on HMI. Booster pump "D8-PAX601011A" running "XL-601011A-01" on HMI. Booster pump "D8-PAX601011B" running "XL-601011B-01" on HMI.

- Main pumps running signals. Main pump "D8-PAX601022A" running "XL-601022A-01" on HMI.

Main pump "D8-PAX601012A" running "XL-601012A-01" on HMI. Main pump "D8-PAX601012B" running "XL-601012B-01" on HMI.

- Motor failure signal from MCC "XL-6010122B-31" on MCP and "XL-601022B-13" on

LCP. - Motor trouble signal from MCC "XL-6010122B-03" on LCP. - Alarm & Trip acknowledge push button "PB-601022B-18" on LCP and "PB-601022B-20"

on HMI. (for acknowledge horns "ALH-601022B-02" & "ALH-601022B-01). - Alarm & Trip signal reset push button "PB-601022B-17" on LCP and "PB-601022B-21" on

HMI. (for reset annunciator ISA sequence).

- Lamp Test push button "PB-601022B-16" on LCP and "PB-601022B-04" on HMI.

oliver.hermosa
Oval
oliver.hermosa
Typewritten Text
-03
oliver.hermosa
Oval
oliver.hermosa
Typewritten Text
-31
oliver.hermosa
Typewritten Text
AND "XL-601022B-32" ON MCP.
Page 12: 084488_CN.rev 03 Control Narrative Logic Pump Item PAX60122B_OMH

rev. 03 08-01-2014

G) VARIABLE INDICATION (ANALOG SIGNALS)

The following signals are displayed on the HMI (touch-screen).

- Pump Suction pressure range 0÷10 kg/cm2 - "PI-601022B-01"

- Pump discharge pressure range 0÷40 kg/cm2 - "PI-601022B-02"

- Pump D.E. bearing temperature range 0÷150 °C - "TI-601022B-01"

- Pump casing temperature range 0÷150 °C - "TI-601022B-02"

- Pump N.D.E. bearing temperature range 0÷150 °C - "TI-601022B-03"

- Pump D.E. bearing housing vibration range 0÷10 mm/s RMS - "XI-601022B-01"

- Pump N.D.E. bearing housing vibration range 0÷10 mm/s RMS - "XI-601022B-02"

- Motor D.E. bearing temperature range 0÷150 °C - "TI-601022B-12"

- Motor N.D.E. bearing temperature range 0÷150 °C - "TI-601022B-13"

- Motor winding temperature range 0÷200 °C - "TI-601022B-14 A/B/C/D/E/F"