08-Bay Control IED REC670

33
© ABB Power Technologies AB, 2005 2006-03-30 Substation Automation Products Training 1 Substation Automation Products Training REC 670 Bay Control IED

description

BAY CONTROL UNIT INTELLIGENT ELECTRONIC DEVICE

Transcript of 08-Bay Control IED REC670

Page 1: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 1

Substation Automation Products

Training

REC 670 Bay Control IED

Page 2: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 2

Contents Main features Configuration alternatives Control functions Apparatus control Interlocking Reservation function Event handling Measurements Synchrocheck Autorecloser Hardware Summary

Page 3: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 3

Local and Remote (Station/SCADA) control Control functionality for up to totally 30 controllable apparatuses allocated in up

to 6 bays For all voltage levels and all types of busbar arrangements Pre-defined interlocking modules for single, double and 1 1/2 circuit breaker

arrangements Reservation function to prevent simultaneous operations Synchro- and energizing-check function Autoreclosing function for single-/ two-/ three-phase reclosing programs Measuring functions U, I, P, Q, f and power factor Metering through pulse inputs from energy meters mA inputs for connection of external transducers Protection functions like BFP, TOC, TEF, TUV, TOV Possibility to include several instances of protection functions e.g. breaker

failure protections for a whole 1 1/2 circuit breaker diameter Extensive configuration possibilities and expandable hardware design to meet

specific user requirements

Main features

Page 4: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 4

Local HMI - Human Machine Interface

Large size HMI Easy navigation with easy to

understand push-buttons 15 LEDs freely programmable

Flashing or permanent light Signal following Latched mode

Single line diagram for control and supervision

Settings Disturbance information Self supervision Standard RJ45 connector to PC

with toolbox (with indication of communication.

Page 5: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 5

REC670

REC670 REC

670

Single circuit breaker Double circuit breaker 1½ circuit breaker

1U

1U

3U

3I

1U

1U

3U

3I3I

1U

1U

3U

3I

3I

3U

Configuration alternatives

3I

Page 6: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 6

Control functions

Apparatus control for single bay,max 8 app. (1 CB) incl. interlocking 1

Apparatus control for single bay,max 15 app. (2 CBs) incl. interlocking 1

Apparatus control for 6 bays,max 30 app. (6 CBs) incl. interlocking 1

Synchrocheck and energizing check,single, double or 1 1/2 circuit breaker 6

Autorecloser for 1-, 2-, and/or 3-phase,single, double or 1 1/2 circuit breaker 6

Max no. of instances

Page 7: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 7

Apparatus Control Application

Control of primary apparatuses in a substation

Station HSI

IED HMI

Page 8: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 8

Apparatus Control Operator workplaces

Station HSI

Gateway

Control Center

ApparatusControl

REC670

I/O

Backup panel

IEC 61850-8-1

breakers

disconnectors

earthing switches

ApparatusControl

REC670

I/OAlternative:

Remote

Station

Local

Page 9: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 9

Apparatus Control

Operation of primary apparatuses Select-before-operate principle to give

high security Selection and reservation function to

prevent simultaneous operation Selection and supervision of operator

place Command supervision Block/deblock of operation Block/deblock of updating of position

indications Substitution of position indications Overriding of interlocking functions Overriding of synchrocheck Pole discordance supervision Operation counter

Features

Page 10: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 10

SXCBRSCSWIQCBAY

SCILO

SXCBRSXCBR

SCSWI

SCILO

SXSWI

-QA1

-QB1

-QB9

IEC 61850

Apparatus Control Function blocks

Page 11: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 11

Disconnectors shall not be

opened or closed on-load

Earthing switches shall not be

closed onto voltage

CB:s shall not be closed when

surrounding disconnectors are in

intermediate positions

CB opening is only interlocked at

a bus-coupler bay, if a busbar

transfer is in progress

Basic principles - Interlocking

Installed to prevent maloperations of disconnectors and earthing switches

Page 12: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 12

Data exchange example between modules

Disc QB1 and QB2 closed

WA1 not earthedWA2 not earthedWA1 and WA2 interconn

Disc QB1 and QB2 closed

WA1 not earthedWA2 not earthedWA1 and WA2 interconn . . . . .

Station bus

QB1

WA1

WA2

Bay 1 Bay n Bus couplerWA1 unearthedWA1 unearthed

WA1 and WA2 interconn

WA1 and WA2 interconn in other bay

Interlocking

QB2

QA1

QB9

QB1 QB2

QA1

QB9

QB2QB1

QA1

QC1 QC2

Page 13: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 13

Data to be sent to other IEDs are defined in an engineering tool(a module in PCM600)

IEC 61850-8-1

GOOSE

IntlReceiveGR01-

BLOCKINSTNAME

RESREQ

RESRENAMRESGRANT

RESGRNAM

APP1NAMEAPP2NAME

APP15NAM

APP1_OPAPP1_CLAPP1VALAPP2_OPAPP2_CLAPP2VAL

APP15_OPAPP15_CLAPP15VALDATA_VALCOM_VAL

An IED sends information by multicasting

Only IEDs which are subscribers receive this message

Horizontal communication GOOSE

Generic Object Oriented Substation Event

Page 14: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 14

Interlockingmodule

Interlockingmodules inother bays

Apparatus controlmodules

SCSWI SXSWISCILO

Apparatus controlmodules

Apparatus controlmodules

Interlocking module on bay level

SCSWI SXCBRSCILO

SCSWI SXSWISCILO

Interlocking

Page 15: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 15

Interlocking modules

Function block ABC_LINE Line bay in arrangements

with single, double, and bypass busbars

Function block ABC_BC Bus coupler in arrangements

with single, double, and bypass busbars

QB1 QB2

QC1

QA1

QC2

QB9

QC9

WA1 (A)

WA2 (B)

WA7 (C)

QB7

QB1 QB2

QC1

QA1

WA1 (A)

WA2 (B)

WA7 (C)

QB7QB20

QC2

Page 16: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 16

Interlocking modules

Function block AB_TRAFO Transformer bay in

arrangements with single and double busbar

QC

Function block BB_ES Busbar earthing switch on

any busbar part

QB1 QB2QC1

QA1

QC2

WA1 (A)

WA2 (B)

QA2

QC3

T

QC4

QB4QB3

QA2 and QC4 are notused in this interlocking

AB_TRAFO

Page 17: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 17

Interlocking modules

Function block A1A2_BS Bus section coupler between bus

sections A1 and A2

Function block A1A2_DC Bus section disconnector between

bus sections A1 and A2

QA1

WA1 (A1)

QB2

QC4

QB1

QC3

WA2 (A2)

WA1 (A1) WA2 (A2)QB

Page 18: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 18

Interlocking modules

Function blocks

DB_BUS_A, DB_BUS_B Bus links of a double

breaker bay

DB_LINE Line connection of a

double breaker bay

WA1 (A)

WA2 (B)

QB1

QC1

QA1

QC2

QC9

QB61

QB9

QB2

QC4

QA2

QC5

QC3

QB62

DB_BUS_B

DB_LINE

DB_BUS_A

Page 19: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 19

Interlocking modules

Function blocks

BH_LINE_A, BH_LINE_B Line connections of a

breaker and a half diameter

BH_CONN Connection between two

lines of a breaker and a half diameter

WA1 (A)

WA2 (B)

QB1QC1

QA1

QC2

QC9

QB6

QB9

QB2QC1

QA1

QC2

QC3

QB6

QC3

QB62QB61 QA1

QC1 QC2

QC9

QB9

BH_LINE_A BH_LINE_B

BH_CONN

Page 20: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 20

Reservation

The purpose of the Reservation method is:

To prevent simultaneous operation (manual operation)

To ensure that interlocking information is correct at the time of operation

Page 21: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 21

REC670

REC670

Station bus

Positions1) CloseDisconnector

2) OpenBreaker

Application example

Reservation

Station HMI

Control center

Gateway

Page 22: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 22

REC670

REC670

Station bus

1) CloseDisconnector

4) OpenBreaker

The solution

3) Positions + Ackn

2) Reserve

Reservation

Gateway

Station HMI

Control center

Page 23: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 23

The configuration over station bus

SCSWI

RES_RQ

RES_GRT

REC670REC670

From otherSCSWI inthe bay

EXCH_OUT

RESIN

EXCH_OUT

RESIN

RES_DATA

QCRSVRES_RQ1

.

.RES_RQ8

RES_GRT1..

RES_GRT8EXCH_IN

To otherSCSWI inthe bay

3

3 2

Station bus. . .

. . .

. . .

Reservation

Provides high security

Page 24: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 24

Reservation

SCSWI

SELECTED

RES_EXT

REC670REC670

1Other SCWI inthe bay

Station bus. . .

SPGGIOIN

RESGRANT

IntlReceive

. . .

. . .

RESGRANT

IntlReceive

Simplified configuration over station bus

Provides high availability

Page 25: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 25

The configuration with external wiring

SCSWI

SELECTED

RES_EXT

+

REC670

BI BO

REC670

BI BO

1Other SCWI in the bay

Reservation

Page 26: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 26

Event handling

PHPIOCIOC1-

BLOCKIDSMPL1IDSMPL2IDSMPL3

TRIPTRL1TRL2TRL3

SPGGIO

SP01-

IN& 1

&

SCSWI

CS01-

BLOCK

PSTO

L_SEL

L_OPEN

L_CLOSE

AU_OPEN

AU_CLOSE

BL_CMD

RES_GRT

RES_EXT

SY_INPRO

SYNC_OK

EN_OPEN

EN_CLOSE

XPOS1

XPOS2

XPOS3

EXE_OP

EXE_CL

SELECTED

RES_RQ

START_SY

POSITION

OPENPOS

CLOSEPOS

POLEDISC

L_CAUSE

XOUT

Op.generalOp.phsAOp.phsBOp.phsC

Pos.stValPos.qPos.tPos.stSeld

stVal, q, tIE

C 6

18

50-8

-1

Event handling for IEC 61850 is included in the function and ”hidden” for the user.

REx670

Page 27: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 27

Measurements AC quantities

For each value:.mag (magnitude of reported value).range (normal |high|low |high-high |low-low)

IEC

61

850

-8-1

PQSI

Uf

cos

CVMMXU

SVRx-

IL1

IL2

IL3

3I0

Izs

Ins

CMMXU

CPx-

UL1L2

UL2L3

UL3L1

3U0

Uzs

Uns

VMMXU

VPx-

RANGE_XP

XPx-

HIGHHIGHHIGH

NORMALLOW

LOWLOWAIM Preproc

AIM Preproc

AIM Preproc

REx670

Page 28: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 28

Measurements DC quantities (mA)

IEC

61

850

-8-1

RANGE

MVGGIO

MVx-

CH1CH2CH3CH4CH5CH6

MIM

MIx-

RANGE_XP

XPx-

HIGHHIGHHIGH

NORMALLOW

LOWLOW

IN

For each channel:

.mag (magnitude of reported value)

.range (normal|high|low |high-high|low-low)

mA input module (MIM)

REx670

Page 29: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 29

Synchrocheck function

BLOCK

U-Line U-Bus

SYNC

Line referencevoltageFuse fail

U-Bus

Energizing checkHigh voltage U> 50-120% of UbaseLow voltage U< 10- 80% of UbaseOperate time 80 ms (typical)

Paralleling (Synchronism) CheckFrequency difference f < 3-1000 mHzVoltage difference U < 2 - 50 % of UbasePhase difference < 5 - 90o

Operate time 80 ms (typical)

Accuracy of frequency measurement about 0,5 mHz!!

U

Page 30: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 30

Start Quick AR without synchrocheck

Auto-Reclosing – new in REx670

Put AR on hold e.g. waiting for Thermal relays to reset to have less sag before reclosing

Skip a step and continue with next (at multiple shots)

Page 31: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 31

19” rack, 6U high

I/O-modules can comprise:• The sum of BOM and MIM must be 4

• max 4 BOM• max 1 MIM

• BIM and IOM up to totally 11/14 modulesmax 11 I/O-modules with 2 AIMmax 14 I/O-modules with 1 AIM

Hardware Structure

Analogue Input Module 6I+6U, 9I+3U, 6I, 12I TRM1, TRM2 (option)

AD-converter module AD1,AD2 (option)

OEM Communication module for IEC 61850-8-1 on AD1 module

SLM Communication module for SPA, LON, IEC 60870-5-103 on NUM module

Central Processing Module NUM

Binary Input /Output modules BIM, BOM, IOM, MIM

Power supply module PSM

NU

M

BIM

IOM

BO

M

PS

MAIM 2AIM 1

REC670

Page 32: 08-Bay Control IED REC670

©A

BB

Po

we

r T

ech

nolo

gie

s A

B,

200

5

2006-03-30 Substation Automation Products Training 32

Summary REC670 vs REC 561

LCD panel with single line diagram for control and supervision

Standard station communication with IEC 61850-8-1

Improved Apparatus control modules following IEC 61850

Improved performance and simplified engineering of the synchrocheck

Simplified engineering of the reservation method

More analog inputs with more flexibility

Several instances of protection functions

Ready-to-use configurations Authorization handling

Page 33: 08-Bay Control IED REC670