    Loadline Z Frame ACB

    Energy Division

  • 7/23/2019 07_09_ACB Z Frame

    2/66

    Loadline Z Frame ACB

    Dorman Smith Loadline Z Frame ACB is the result of an intensive market research program whichtook into account the requirements of switchboard builders, consultants and end users. Loadline ZFrame ACB is one of the smallest in the market with a 1 second rating (Icw).

    InnovationsNew design of built-in UVT that eliminates the need for the controller to be mounted on the sideof the ACB.

    New Protection AGR-B Range Relay. The new AGR-B range relay will have an improved LCDdisplay, which will include additional features such as an Ammeter, Zone Interlocking andMulti/Power Meter capabilities. This will also mean some changes to previous closing circuitconfigurations.

    Contents Page

    Section 1 - ACBs and Over-current Releases

    Features 2 - 10

    Appearance and Internal Construction 11

    Ratings 12 - 13

    Types of Mounting 14 - 15

    Spring Charge Operation 16

    Over-current Releases (OCRs) 17 - 23

    ACB Catalogue Number Selection Chart 24 - 25

    Section 2 - Factory Fitted Accessories

    Drawout Accessories (Fitted as Standard) 26 - 28

    Factory Fitted Accessories (Optional) 29 - 35

    Factory Fitted Order Codes Chart 36 - 37

    Section 3 - Accessories Supplied Loose 38 - 43

    Section 4 - Dimensions and Circuit Diagrams 44 - 59

    Section 5 - Technical and Application Data 60 - 64

    Based Standards

    IEC60947-2 InternationalElectrotechnical Commission

    EN60947-2 European Standard

    AS 3947-2 Australian Standard

    NEMA PUB NO.SG3 NationalElectrical Manufacturers Association

    ANSI C37.13 American NationalStandard Institute

    JIS C8372 Japanese IndustrialStandard

    Certification and Authorisation

    ASTA, UK ASTA CertificationServices

  • 7/23/2019 07_09_ACB Z Frame

    3/66

    Features

    The Ultimate in Compactness and

    Operational Capability

    Icw,1s = Ics for all Loadline Z Frame ACBs

    Loadline Z Frame is the worlds first DoubleBreak ACB, having two breakingcontacts per phase. The expressly designed pole structure means that the shorttime withstand rating (Icw, 1sec) is equal to the service short-circuit breakingcapacity (Ics) for all models. Full selectivity is warranted up to the full system faultlevel. Loadline Z Frame ACBs have one of the worlds smallest depth resulting inspace saving in switchboards.

    More than twenty design patents have been registered for the ACB.

    The height and depth dimensions are identical in all sizes up to 3200A. There aretwo common widths or frame size, from 800-2000A and from 2500-3200A for thestandard series. The panel cut-out size is the same for all types of Loadline ZFrame, which makes it easy to arrange the ACBs in switchboards. Maximum powerfrom minimum volume was central to the design specification. With a depth of290mm for the fixed type and 345mm for draw-out, it is one of the smallest ACBsin the world. ACBs with front connections are available off-the-shelf.

    Front connections are especially suitable for smaller-depth switchboards.

    2

    Section 1

    Standard series 800-2000A

    High fault series 1250-2000A

    2500-3200A

    1600-3200A

    4000A

  • 7/23/2019 07_09_ACB Z Frame

    4/66

    Increased Accessibility from the Front

    Enhances ease of installation, operation, and maintenance.

    The double insulated design ensures that most accessories can be safely and easily,installed by the user. Control, auxiliary and position switch terminals are mountedat the front on the ACB body for easy access. Horizontal, vertical and frontterminal connections, can also be changed by the user for any last minutealterations. Due to the increased level of harmonics within the distribution network,

    the neutral phase is fully rated as standard.

    No extra arc space required, vertical stacking permitted

    The Loadline Z Frame ACB dissipates all arc energy within its unique DoubleBreakarc chamber. The internal energy dissipation within the ACB allows the clearancedistance of the ACB to nearby earthed metal to be zero. This will assist inminimising switchboard height and costs.

    Replacement of the main contacts

    The fixed and moving main contacts can easily be replaced in the field, thusprolonging the life of the circuit breaker. Changing each pole takes around15 minutes.

    Connection to themain circuit (forfront connections)

    Connection to the control circuit

    Manual operation

    Breaker fixingbolts(optional)

    Draw-outoperation

    Accessory fitting(Removing thefront coverenablesreplacement ofinternal parts)

    No extraarcspacerequired

    3

  • 7/23/2019 07_09_ACB Z Frame

    5/66

    4

    A High Performance and Reliability

    Very fast interruption by DoubleBreak system

    The DoubleBreak main contact system ensures extremely fast interruption ofshort circuit currents and substantially reduces main contact wear. The internallysymmetrical DoubleBreak structure means the moving contact is isolated fromthe supply voltage even when the ACB is reverse connected. The neutral polesof all Loadline Z Frame ACBs are of early make/late break design. This eliminatesthe risk of abnormal line to neutral voltages, which may damage sensitive

    electronic equipment.

    DoubleBreak contacts increase service life - electrical and mechanical enduranceratings are the best available and exceed the requirements of IEC 60947-2.

    No clamp screws used for the main circuit contact units

    There are no clamp screws or flexible leads in the main circuit contact units.This substantially enhances the durability of the main circuit contact units and

    improves the reliability in ON-OFF operation.

    Easy maintenance

    Design of Loadline Z Frame incorporates its isolating clusters and main contacts

    on the ACB body allowing for quick easy maintenance of the main electricalcontact points and for maintenance to be completed without having to isolatethe switchboard.

  • 7/23/2019 07_09_ACB Z Frame

    6/66

    5

    Enhanced Selectivity

    Protection relays have LSI characteristics as standard

    This provides an adjustable time delay on overload (L) and also the l2t rampcharacteristic (S).

    As shown, these are essential to provide selectivity when grading with otherprotective devices such as downstream fuses and upstream relays.

    The standard LSI curve provides more than five million combinations of timecurrent characteristics. Zone selective interlocking is available to provide zero timedelay selectivity. As the rated breaking capacity is identical to the rated short-timewithstand current, full selectivity can be achieved.

    Rated breaking With INST functioncurrent (at AC440V) With ST delay trip function

    Without INST/MCR functions

    Rated short-time withstandcurrent (for 1 sec)

    Frame size andrated current

    Performance

    Z2 Z2800A1250A1600A

    2000A

    1250A

    1600A2000A

    Z4Z3 2500A3200A

    Z3 1600A2000A2500A

    3200A

    4000A

    65kA(std)

    80kA(high)

    85kA(std)

    100kA(high)

    100kA(std)

    A substantial improvement in life cycles

    The Loadline Z Frame series has achieved very high life cycles.

  • 7/23/2019 07_09_ACB Z Frame

    7/66

    Loadline Z Frame ACB Provides Positive Protection forElectric Power Systems

    6

    The Loadline Z Frame ACB series is equipped with anRMS sensing over-current release (OCR) having awide range of protection functions and capabilities.

    For general feeder circuits (L-characteristic)

    The DoubleBreak main contact system ensures extremely fast interruption ofshort circuit currents and substantially reduces main contact wear. The internallysymmetrical DoubleBreak structure means the moving contact is isolated fromthe supply voltage even when the ACB is reverse connected. The neutral polesof all Loadline Z Frame ACBs are of early make/late break design. This eliminatesthe risk of abnormal line to neutral voltages, which may damage sensitiveelectronic equipment.

    DoubleBreak contacts increase service life - electrical and mechanical enduranceratings exceed the requirements of IEC 60947-2.

    Overload protectionAdjustable from 40100% of rated current. True rms detection up to the 19thharmonic. Neutral protection for all those Triple-N harmonics such as 3rd, 9thand 15th. Also a thermal memory is available on the AGR21B/31B.

    A B C

    Standard OCR withadjustment dial TypeAGR-11BL

    Standard OCR with LCD-Ammeter Type AGR-21BL

    Enhanced OCR with LCD-Analyser Type AGR-31BL

    Backlit LCD installed

  • 7/23/2019 07_09_ACB Z Frame

    8/667

    For full details refer to the tables on page 21

    N-phase protection function (optional)

    In three-phase, four-wire systems that contain harmonic distortion, the 3rdharmonic may cause large currents to flow through the neutral conductor. TheN-phase protection function prevents the neutral conductor from sustainingdamage or burnout due to these large currents. Available in all OCRs.

    Ground fault trip function (optional)

    This function eliminates external relays to provide a ground fault protection toTN-C or TN-S power distribution systems on the load side (unrestricted). Groundfault protection on the line side is also available as an option. (restricted).

    Earth leakage trip function (optional)

    Used in conjunction with an externally mounted Zero-phase Current Transformer(ZCT), this function provides protection against leakage to earth of very smalllevels of current. Trip or alarm indication and contact output is available to

    enhance the level of system protection.

    Phase rotation protection function (optional)

    This function detects the negative-phase current occurring due to reverse phaseor phase loss and prevents burnout of a motor or damage to equipment.

    Advanced LCD display, over-current relay

    The AGR-31B OCR comes standard with an LCD display. It can monitor andindicate phase currents, voltages, power, energy, power factor, frequency, andmore. For features refer to page 20.

    Remote communications protocols (optional)

    Data communications via Modbus protocol, an open network, are supported.

    Energy MeasurementI, V, kW, MWh, kVar, cos, frequency

    Intelligent Fault AnalysisStatus, fault type, fault size, tripping time, fault history

    Maintenance InformationTrip circuit supervision, contact temperature monitoring.

    For details please refer to page 10. For other protocols please contactTyco Electronics.

    Contact temperature monitoring function (optional)

    This function monitors the temperature of the ACBs main contacts. An alarmindicates when the temperature exceeds 155C. Continuous monitoring of thecontact temperature provides valuable input for preventative and predictivemaintenance programs.

    Zone Interlocking (optional)

    In many conventional discrimination systems, short time delays are used to allowa short-circuit current to be tripped by the circuit breaker nearest the fault. Thedisadvantage of this type of system is during a fault; considerable thermal andmechanical stresses are placed on the entire system. With the Loadline Z FrameZone Interlock system the breaker nearest the fault (irrespective of the short timedelay setting) will trip first.

    Example of operation:

    If a fault occurs in Zone 2, only Zone Interlock A will sense any fault current fault,a no fault signal will be sent by Zone Interlock B & C, consequently ZoneInterlock A trips the ACB immediately, overriding its short time delay.

  • 7/23/2019 07_09_ACB Z Frame

    9/668

    Double opening and closing coils

    Double opening and closing coils provide extended control system redundancyto an ACB. Double coils allow designers to implement back-up tripping andclosing systems.

    It provides the end user with ultimate reliability on critical UPS circuits connected

    to critical loads.

    Protection relay performance

    Ensure that the ACB you specify suffers no loss of performance when tripped by

    an external protection relay!

    The Loadline Z Frame ACB suffers no loss in performance when tripped throughan external protection relay.

    Some competitors ACBs have reduced breaking performance when an external

    protection relay is used.

    Inform

    Inform Selectivity Analysis Software is shaped around the extensive range of DormanSmith circuit breakers, but also includes a large number of complimentary protectivedevices such as high and low voltage fuses to BS88/IEC269, IDMT Relays to BS142/IEC255. As a result, Inform can assist in protection device grading from thetransformer primary to the point of final distribution, giving the facility to produce

    over-current and earth fault studies.

    65kA 85kA 100kA

    ExternalRelay

    100kA

    Loadline Z frame ACB.With internal or externalprotection relay.

  • 7/23/2019 07_09_ACB Z Frame

    10/66

    Meeting customer requirements

    Loadline Z Frame ACB provides solutions to satisfycustomer needs

    Switchboard builder

    Compact size for high packing density

    No extra arc space required for clearance

    Low temperature dissipation

    Built in trip supervision circuit

    Fully rated neutral as standard

    Terminal connections and accessories are field changeable

    Uniform panel cut out size

    Consultant

    Restricted and unrestricted ground fault protection in one relay

    LSI characteristic curves as standard

    True rms protection

    Integral reverse power protection and load shedding relay

    End user

    Self checking protection relay and tripping coil

    Built in relay tester available on AGR21B/22B/31B can check on line withouttripping the ACB

    Contact temperature monitoring

    Fault diagnosis - type of fault, magnitude, tripping time and trip history

    High making capacity for operator safety

    Communication via BMS or SCADA system

    Main contacts can be changed within around 15 minutes per pole

    9

  • 7/23/2019 07_09_ACB Z Frame

    11/66

    10

    Communication facility added to Loadline Z Frame ACB

    Loadline Z Frame is equipped with a communication interface unit that allows data exchange with a host PC via a Modbus opennetwork. Data communicated includes measurements, fault log, maintenance information, ON/OFF status, settings and control(ON/OFF/RESET) signals.

    Fault log

    Item Modbus

    Transmission standard RS-485

    Transmission method 2-wire half-duplex

    Topology Multi-drop bus

    Transmission rate 19.2 kbps max.

    Transmission distance 1.2 km max. (at 19.2 kbps)

    Data format Modbus-RTU or ASCII

    Max. number of nodes 132

    Cause Whichever trip function, LTD, STD, INST,or GF, is activated is then transmitted.

    Fault current The fault current at which the breakertripped open is transmitted.

    Trip pickup time The trip pickup time is transmitted.

    Maintenance informationTripping circuit The tripping coil is always monitored formonitoring disconnection. If the breaker is not open

    within approx. 300 ms of a trip signaldelivered from the OCR, an alarm signalis generated.

    Data measurementPhase current The phase current I1, I2, I3, IN, Ig and max.

    current Imax are measured andtransmitted.

    Line-to-line voltage V12, V23 and V31 are measured.

    Active power The 3-phase power, reverse power andmax. power are measured.

    Demand active power The demand active power is measured.

    Accumulated power The accumulated power is measured.

    Power factor The circuit power factor is measured.

    Frequency The frequency is measured.

    Network interface I/Ospecifications

    On-screen PC monitor

    Communication network

    Modbus

    Up to 31 units can be connected per system

  • 7/23/2019 07_09_ACB Z Frame

    12/66

    11

    Appearance and Internal Construction

    Internal Construction

    Appearance

    ON-OFFcycle counter(optional)

    Position switchterminals (optional)

    Auxiliary switchterminals

    Control

    circuitterminals

    Draw-outcradle

    Springchargeindicator

    Springcharginghandle

    ON button

    Draw-outhandleinsertion

    hole

    Position

    indicator

    ON-OFFindicator

    OFF button

    Breakingfixing bolts(optional)

    Key locklocation

    (optional)

    Positionpadlock

  • 7/23/2019 07_09_ACB Z Frame

    13/66

    Ratings

    Standard Series

    12

    Frame size Z2 Z3 Z4

    Ampere rating(A) 800 1250 1600 2000 2500 3200 4000

    Rated current (max.) [I/n](A) IEC, EN, AS 800 1250 1600 2000 2500 3200 4000

    JIS 800 1250 1600 2000 2500 3200 3700

    NEMA, ANSI 800 1250 1540 2000 2500 3200 3700

    Marine 800 1250 1600 2000 2500 3200 4000

    Neutral pole Amperes frame (A) 800 1250 1600 2000 2500 3200 4000

    Number of poles 3 4 3 4 3 4 3 4 3 4 3 4 3 4

    Rated primary current of over-current 800 1250 1600 2000 2500 3200 4000

    Release [I/CT](A)

    for general feeder circuit use

    AC rated insulations voltage [Ui](V.50/60Hz) 1000 1000 1000 1000 1000 1000 1000

    Rated operational voltage [Ue](V.50/60Hz) 690 690 690 690 690 690 690

    AC rated breaking cap [kA sym rms]/making

    cap [kA peak ac 690V 50/105 50/105 50/105 50/105 65/143 65/143 75/165

    [Ics=Icu] 440V 65/143 65/143 65/143 65/143 85/187 85/187 100/220NEMA ac 600V 42/96.6 42/96.6 42/96.6 42/96.6 50/115 50/115 65/149.5

    480V 50/115 50/115 50/115 50/115 65/149.5 65/149.5 75/172.5240V 65/149.5 65/149.5 65/149.5 65/149.5 85/195.5 85/195.5 100/230

    JIS ac 550V 50/105 50/105 50/105 50/105 65/143 65/143 75/165460V 65/143 65/143 65/143 65/143 85/195.5 85/195.5 100/230220V 65/143 65/143 65/143 65/143 85/195.5 85/195.5 100/230

    dc 600V 40/40 40/40 40/40 40/40 40/40 40/40 40/40250V 40/40 40/40 40/40 40/40 40/40 40/40 40/40

    NK ac 690V 50/115 50/115 50/115 50/115 65/153 65/153 75/179450V 65/153 65/153 65/153 65/153 85/201 85/201 100/245

    LR, AB ac 690V 50/115 50/115 50/115 50/115 65/153 65/153 75/179GL, BV 450V 65/153 65/153 65/153 65/153 85/201 85/201 100/245

    Rated impulse withstand voltage [Uimp](kV) 12 12 12 12 12 12 12

    Rated short time withstand 1s 65 65 65 65 85 85 100current[Icw][kA rms] 3s 50 50 50 50 65 65 85

    Latching current (kA) 65 65 65 65 85 85 100

    Total breaking time (s) 0.03 0.03 0.03 0.03 0.03 0.03 0.03

    Closing operation time

    Spring charging time (s) max. 10 10 10 10 10 1010

    Close time (s) max. 0.08 0.08 0.08 0.08 0.08 0.08 0.08

    No. of operating cycles

    Mechanical life with maintenance 30000 30000 30000 25000 20000 20000 15000without maintenance 15000 15000 15000 12000 10000 10000 8000

    Electrical life without maintenance AC460V 12000 12000 12000 10000 7000 7000 5000AC690V 10000 10000 10000 7000 5000 5000 2500

    Weight (Kg) draw-out type 73 86 73 86 76 90 79 94 105 125 105 125 139 176

    Outline dimension (mm)

    Fixed type a 360 445 360 445 360 445 360 445 466 586 466 586 - -

    b 460 460 460 460 460 460 -

    c 290 290 290 290 290 290 -

    d 75 75 75 75 75 75 -

    Draw-out type a 354 439 354 439 354 439 354 439 460 580 460 580 631 801

    b 460 460 460 460 460 460 460

    c 345 345 345 345 345 345 375

    d 40 40 40 40 40 40 53

    1

    2

    3

    4

    5

    8

    11

    10

    7

    9

    9

    6 6 6 6 6 6

    6 6 6 6 6 6

    6 6 6 6 6 6

    Values in open air at 40C (45C for marine applications).

    For double-pole ACBs use outside poles of three-pole

    ACB.

    Rated insulation voltage depends on applied standard:

    1000V ac according to IEC 60947-2.

    Rated operational voltage depends on applied standard:

    690V according to IEC 60947-2.

    Cannot apply IT earthing system, ie, insulated from earth.

    For 500V ac.

    Please contact Tyco Electronics for dc application.

    Three-poles in series should be applied for 600V dc.

    Applicable to only three-pole ACBs.

    For vertical terminals or horizontal terminals.

    For more information see page 60.

    1

    6

    7

    8

    9

    10

    11

    2

    3

    4

    5

  • 7/23/2019 07_09_ACB Z Frame

    14/6613

    High Fault Series

    Frame size Z2 Z3

    Ampere rating(A) 1250 1600 2000 1600 2000 2500 3200

    Rated current (max.) [I/n](A) IEC, EN, AS 1250 1600 2000 1600 2000 2500 3200

    JIS 1250 1600 2000 1600 2000 2500 3200NEMA, ANSI 1250 1600 2000 1600 2000 2500 3200

    Marine 1250 1600 2000 1600 2000 2500 3200

    Neutral pole Amperes frame (A) 1250 1600 2000 1600 2000 2500 3200

    Number of poles 3 4 3 4 3 4 3 4 3 4 3 4 3 4

    Rated primary current of over-current 1250 1600 2000 1600 2000 2500 3200

    Release [I/CT](A)

    for general feeder circuit use

    AC rated insulations voltage [Ui](V.50/60Hz) 1000 1000 1000 1000 1000 1000 1000

    Rated operational voltage [Ue](V.50/60Hz) 690 690 690 690 690 690 690

    AC rated breaking cap [kA sym rms]/making

    cap [kA peak ac 690V 55/121 55/121 55/121 85/187 85/187 85/187 85/187

    [Ics=Icu] 440V 80/176 80/176 80/176 100/220 100/220 100/220 100/220NEMA ac 600V 42/96.6 42/96.6 42/96.6 50/115 50/115 50/115 65/149.5

    480V 65/149.5 65/149.5 65/149.5 80/184 80/184 80/184 80/184240V 80/184 80/184 80/184 100/230 100/230 100/230 100/230

    JIS ac 550V 55/121 55/121 55/121 85/196 85/196 85/196 85/196460V 80/176 80/176 80/176 100/230 100/230 100/230 100/230220V 80/176 80/176 80/176 100/230 100/230 100/230 100/230

    dc 600V 40/40 40/40 40/40 40/40 40/40 40/40 40/40250V 40/40 40/40 40/40 40/40 40/40 40/40 40/40

    NK ac 690V 55/128 55/128 55/128 85/201 85/201 85/201 85/201

    450V 80/186 80/186 80/186 100/233 100/233 100/233 100/233

    LR, AB ac 690V 55/128 55/128 55/128 85/201 85/201 85/201 85/201GL, BV 450V 80/186 80/186 80/186 100/233 100/233 100/233 100/233

    Rated impulse withstand voltage [Uimp](kV) 12 12 12 12 12 12 12

    Rated short time withstand 1s 80 80 80 100 100 100 100current[Icw][kA rms] 3s 55 55 55 75 75 75 75

    Latching current (kA) 65 65 65 85 85 85 85

    Total breaking time (s) 0.03 0.03 0.03 0.03 0.03 0.03 0.03

    Closing operation time

    Spring charging time (s) max. 10 10 10 10 10 1010

    Close time (s) max. 0.08 0.08 0.08 0.08 0.08 0.08 0.08

    No. of operating cycles

    Mechanical life with maintenance 30000 30000 30000 25000 20000 20000 20000without maintenance 15000 15000 15000 12000 10000 10000 10000

    Electrical life without maintenance AC460V 12000 12000 12000 10000 7000 7000 7000AC690V 10000 10000 1000 7000 5000 5000 5000

    Weight (Kg) draw-out type 79 94 79 94 79 94 105 125 105 125 105 125 105 125

    Outline dimension (mm)

    Draw-out type a 354 439 354 439 354 439 460 580 460 580 460 580 460

    580 b 460 460 460 460 460 460 460

    c 345 345 345 345 345 345 345

    d 40 40 40 40 40 40 40

    1 2

    3 4

    5

    6

    7

    14

    9

    13

    8

    10 11

    10 11

    Values in open air at 40C (45C for marine applications).

    Values for draw-out type with vertical terminals.

    For double-pole ACBs use outside poles of three-pole

    ACB.

    Four-pole ACBs without Neutral phase protection can not

    be applied to IT earthing systems.

    Rated insulation voltage depends on applied standard:

    1000V according to IEC 60947-2.

    Rated operational voltage depends on applied standard:

    690V according to IEC 60947-2.

    Contact Tyco Electronics for details.

    Please contact Tyco Electronics for dc application.

    Three-poles in series should be applied for 600V dc.

    Will apply soon.

    Applicable to only three-pole ACBs.

    For vertical terminals.

    For more information see page 60.

    1

    8

    9

    10

    12

    11

    13

    2

    3

    4

    5

    6

    7

    12

    When the ACB is used without Instantaneous trip function MCR should be set to work. The rated breaking capacity will reduce to the level of the latching current without

    MCR function.

  • 7/23/2019 07_09_ACB Z Frame

    15/6614

    Types of Mounting

    Draw-out typeThis type of ACB consists of a breaker body and a draw-out cradle. The breaker bodycan be moved within or removed from the draw-out cradle that is fixed in theswitchboard There are four breaker body positions: CONNECTED, TEST ISOLATED,and WITHDRAWN. The switchboard panel door can be kept closed in theCONNECTED, TEST, and ISOLATED positions (shut-in three positions).

    Connected position

    Both the main and control circuits are connected for normal service.

    Test position

    The main circuit is isolated and the control circuits are connected. This positionpermits operation tests without the need for opening the switchboard panel door.

    Isolated position

    Both the main and control circuits are isolated. The switchboard panel door doesnot need to be opened.

    Withdrawn position

    The breaker body is fully withdrawn from the draw-out cradle.

  • 7/23/2019 07_09_ACB Z Frame

    16/6615

    Fixed type (standard series only)This type of ACB has no draw-out cradle and is designed to be directly mounted in

    the switchboard.

    Connection methods

    Main circuit terminals

    Three types of main circuit terminal arrangements are available: vertical terminals,horizontal terminals and front connections. Different types of terminal

    arrangements can be specified for the line and load sides.

    Control circuit terminalsControl circuit terminals are front located to allow easy wiring/access.

    The terminal blocks (for auxiliary switches, position switches, and control circuits)are positioned on the top of the ACB front panel and can be accessed from thefront for wiring.

    M4 screw terminals are standard.

    Horizontal terminals

    Vertical terminals

    Front connections

  • 7/23/2019 07_09_ACB Z Frame

    17/6616

    Spring Charged OperationManual charging typeFor this type of ACB, the closing springs are charged by means of the springcharging handle. ON/OFF operation of the ACB is performed by means ofON/OFF buttons on the ACB.

    Charging the closing springsPumping the spring charging handle by hand charges the closing springs.

    Closing the ACBPressing the ON button on the ACB closes the ACB.

    Opening the ACBPressing the OFF button on the ACB opens the ACB.The ACB cannot be closed as long as the OFF button is pressed.

    Motor charging typeFor this type of ACB, the closing springs are charged by means of a motor.ON/OFF operation of the ACB can be performed remotely. A manual chargingmechanism is also fitted to facilitate inspection or maintenance work.

    Charging the closing springsA motor is used to charge the closing springs.When the closing springs are released to close the ACB, they are automaticallycharged again by the motor for the next ON operation.

    Closing the ACBTurning on remote ON switch enables the ACB to be remotely closed. Anti-pumping mechanism Even if the ON switch is kept on, ACB closing

    operation is performed only once.To close the ACB again, remove the ON signal to reset the anti-pumpingmechanism and then reapply the ON signal.

    If ON and OFF signals are simultaneously given to the ACB, the ON signalis ignored.

    Opening the ACBFor opening the ACB remotely, specify the shunt trip device (See P. 30) or theunder-voltage trip (See P. 34).

    Operation power supply

    Rated voltage Applicable voltage range (V) Operation power supply ratings

    (V) CHARGE/ OFF operation Motor inrush Motor steady-state Closing command

    ON operation (Note1) current (peak) (A) current (A) current (peak) (A)

    AC 100 85-110 7 1.1 0.48

    AC 110 94-121 7 1.1 0.39

    AC 120 102-132 7 1.1 0.37

    AC 200 170-220 4 0.7 0.24

    AC 220 187-242 4 0.7 0.19

    AC 240 204-264 4 0.7 0.18

    DC 24 20-26 14 4 1.65

    DC 48 41-53 10 1.6 0.86

    DC 100 85-110 6 0.8 0.39

    DC 110 94-121 6 0.8 0.37

    DC 125 106-138 6 0.8 0.31

    DC 200 170-220 4 0.5 0.19

    DC 220 187-242 4 0.5 0.18

    Note 1: For the ratings refer to the shunt trip device of page 30.

  • 7/23/2019 07_09_ACB Z Frame

    18/66

    Over-current Releases (OCRs)The AGR series of over-current releases (OCRs) featuring high reliability andmultiple protection capabilities is available for Loadline Z Frame. Controlled byan internal 16-bit microprocessor, the OCR provides reliable protection againstover-current.

    The OCR L-characteristic is for general feeder applications.

    The range consists of:

    Type AGR-11BL: Standard OCR with adjustment dialType AGR-21BL: Standard OCR with LCD

    Type AGR-31BL: Enhanced OCR with backlit LCD

    Optional protection functions of the OCR include those against ground fault, earthleakage, under-voltage and reverse power.

    Pretrip alarm function can also be installed.

    Protective functions

    1 Adjustable long time-delay trip function LT

    RMS sensing is used to accurately read through distorted waveforms.

    HOT start mode (applicable to L-characteristic of AGR-21BL,31BL)

    HOT or COLD start mode is user-selectable.

    In HOT start mode, the OCR operates faster than in COLD start mode in responseto an overload. The HOT start mode gives protection, taking account of thebehaviour of loads under heat stress.

    2 Adjustable short time-delay trip function ST

    The ST delay trip function has a definite time delay characteristic and a rampcharacteristic. These characteristics are switch-selectable.

    The ramp characteristic provides close selectivity with downstream circuitbreakers or fuses.

    The definite time characteristic operates when the load current reaches 1000% ormore of the rated current [In].

    The ST trip function is factory set to the definite time characteristic.

    17

  • 7/23/2019 07_09_ACB Z Frame

    19/66

    3 Adjustable instantaneous trip function INST/MCR

    The INST trip function trips the ACB when the short circuit current exceeds thepickup current setting, irrespective of the state of the ACB.

    The making current release (MCR) trips the ACB when the short circuit currentexceeds the pickup current setting during closing operation. After the ACB isclosed, the MCR is locked and kept inoperative.

    The INST and MCR are switch-selectable for AGR-21BL and 31BL. (AGR-11BL is

    INST only, MCR is not selectable) Note: The MCR needs the control power. If thecontrol power is lost, the MCR provides the INST trip function only.

    4 Adjustable pretrip alarm function PTA

    The pretrip alarm function provides an alarm signal via the alarm contact(1a-contact) when the load current exceeding a predetermined value lasts fora predetermined time.

    The pretrip alarm is automatically reset when the load current drops to thepredetermined value.

    Note that this function needs the control power.

    5 Ground fault trip function GFThe peak value sensing is used (the residual current of each phase is detected).

    The GF pickup current can be set between 10% and 100% of the CT rated primarycurrent [ICT].

    The ramp and definite time characteristics are switch selectable. The GF tripfunction comes into operation with the definite time characteristic when the loadcurrent reaches 100% or more of the CT rated primary current [ICT].

    The GF trip function is factory set to the definite time characteristic.

    When using a three-pole ACB in a three-phase, four-wire system, a separateneutral CT must be used (supplied).

    6 Earth leakage trip function ELT (For AGR-31BL only.)

    In conjunction with an external Zero phase Current Transformer (ZCT), the ELTfunction provides protection against earth leakage.

    The ELT pickup current can be set at 0.2, 0.3, 0.5 and 1A (medium sensitivity) or3 and 5A (low sensitivity).

    This function needs the control power.

    Note 1: For details on specifications of the external ZCT, contactTyco Electronics.

    Note 2: The ELT function comes usually with operation indications. If youneed nothing but earth leakage indications without earth leakage

    tripping operation, please specify at the time of ordering.Note 3: The ELT function is available up to 2500A rated current [In]

    7 N-phase protection function NP

    This NP function is available on four-pole ACBs and prevents the neutralconductor from suffering damage or burnout due to over-current.

    The NP trip pickup current can be set between 40% and 100% of the OCR ratedprimary current.

    It is factory set to a value specified at the time of ordering.

    Note 1: The NP trip function comes usually with operation indications. TheNP trip pickup current setting is shared by the LT trip function.

    Note 2: The HOT start mode is available for AGR-21BL and AGR-31BL. Theoperating time for the NP trip function is linked to that for the LTtrip function.

  • 7/23/2019 07_09_ACB Z Frame

    20/6619

    NON setting and fail-safe feature

    1 Non settingSetting a trip pick up current function to NON allows you to render thecorresponding protection function inoperative.

    Functions having the NON option include LT, ST, INST/MCR, and GF.

    Appropriate NON setting will be a useful means for optimum selectivity.

    2 Fail-safe featureThe OCR has a fail-safe mechanism in case protection functions are improperly setto NON.

    If the ST and INST trip pick up current functions are both set to NON, the fail-safe mechanism will activate the INST trip function to trip the ACB when a faultcurrent equal to or more than 16 times the rated current [In] flows throughthe ACB.

    If the ST and MCR trip pick up current functions are both set to NON, the fail safemechanism will activate the ST delay trip function to trip the ACB when a faultcurrent equal to or more than 10 times (5 times for generator protection) therated current [In] flows through the ACB.

    Field test facility

    Type AGR-21BL and 31BL OCRs are equipped with a field test function to verify the

    long time delay, short time delay, instantaneous and ground fault trip featureswithout the need for tripping of the ACB.

    To check type AGR-11BL, use the type ANU-1 OCR checker (optional).

    Operation indication function

    1 Indication via single-contact (AGR-11BL)

    When the LT, ST, INST or GF trip function is activated, an output is generated via1a-contact.

    The 1a-contact will turn off after 40 ms or more.

    A self-hold circuit is needed.

    2 Indication via individual contacts (AGR-21BL & 31BL)

    When the LT trip, ST trip, INST/MCR trip, GF trip, ELT, NS, REF, UVT, pretrip alarm,or contact temperature monitoring function is activated, LCD will indicate theiroperation individually and output is generated via the corresponding contact. TheOCR also has a self-diagnostic feature that monitors the internal tripping circuits. Ifdetecting any fault in the circuits, this feature turns on the system alarm indicator.The control power is needed.

    Operation indicationsO: Self-hold (Note 1)X: Auto-reset

    : status indication: Not applicable

    Protective characteristic L characteristic

    Function LCD Contact

    LT NP O OST O

    INST/MCR O

    GF (Ground fault) or O OELT (Earth leakage)

    OH (Contact

    temperature monitoring) O O

    (Note 2) NS (Reverse phase) O O

    REF (Line side GF) O O

    Trip indication *1

    PTA (Pretrip alarm) X X

    (Note 3) UV (Under-voltage alarm) OSpring charge indication

    System alarm O O

    O (note 4)

    Note 1: To reset the motionindication, press the resetbutton.

    Note 2: Only one function can beselected from OH, NS, REFor trip indication.

    Selection of two or more functionsinvolves manual connection of theircontrol circuits (customconfiguration). Contact Tyco

    Electronics for details.Note 3: Only one function can be

    selected from UV or springcharge indication.

    Selection of two functions involvesmanual connection of their controlcircuits (custom configuration).Contact Tyco Electronics for details.

    Note 4: Motion indication contactsare commonly used for STand INST/MCR.

    *1: A switch is used to indicate theACB has been tripped. This switchis activated whenever the off

    button, the over-current tripdevice, shunt trip device or under-voltage trip device is activated.

    (Note 3)

  • 7/23/2019 07_09_ACB Z Frame

    21/66

    Voltage Switch contact ratings (A)

    (V) Resistive load Inductive

    AC 250 3 3250 0.1 0.1125 0.5 0.530 3 3

    3 -1 Contact ratings of trip indicator and spring charge indicator

    DC

    Voltage Current (A)

    (V) 1 Single contact 2 Individual contacts

    Resistive load Inductive load Resistive load Inductive load

    AC 250 8 3 0.5 0.2250 0.3 0.15 0.27 0.04125 0.5 0.25 0.5 0.230 5 3 2 0.7

    3 -2 Contact ratings for other contacts

    DC

    OCR with advanced LCD display, type AGR-31B

    (contact Tyco Electronics for details)

    1 Monitoring various data on LCD

    OCR can monitor,

    Phase current (A) of I1, I2, I3 and their max. peak current

    Current (A) of IN, Ig

    Line voltage (V) of V12, V23, V31 and their max. peak voltage (or phase voltage(V) of V1N, V2N, V3N and their peak voltage)

    Active power max. (kW)

    Demand active power max. (kW)

    Power factor (cos )

    Electric energy (kWh/ MWh/ GWh)

    Frequency (Hz)

    Trip history

    Fault current is monitored and the operation cause is indicated on LCD and viaindividual contacts.

    Note 1: The supply voltage to the OCR for indicating the main circuit voltage orpower must not exceed 250V ac. If the main circuit voltage exceed 250V ac, astep-down power transformer is needed. When ordering the ACB, state the step-down ratio of the transformer you will use.

    2 Gives the system alarm with number on the LCD for the followingabnormal function.

    Trip function fail

    MHT circuit break

    20

  • 7/23/2019 07_09_ACB Z Frame

    22/66

    21

    OCR specifications

    Protection

    characteristicsProtection relay Protection Functions

    Standard protection

    Standard protection relays

    Long

    time

    Short

    time

    Instantaneous Unrestricted Restricted N-phase

    protection

    N-phase Indication and monitoring

    Indication

    Single

    contact

    Individual

    contacts

    Ammeter Energy

    analyser

    Monitoring

    Ground fault

    S REF NPUREFL

    Over-current

    releace (OCR)

    Available as standard

    Available as option Not available

    2 Only one function can be selected from OH, NS, REF or trip indication.Selection of two or more functions involves manual connection of their controlcircuits (special specification). Contact Tyco Electronics for details.

    3 Only one function can be selected from UV or spring charge indication.Selection of two or more functions involves manual connection of their controlcircuits (special specification). Contact Tyco Electronics for details.

    For full operational information see pages 17 to 20

    If the control power is not supplied or is lost, each function operates as follows:

    LT, ST, INST Operates normally

    GF Operates normally

    When the CT rated primary current [ICT] is less than 800A and the GF

    pick up current is set to 10%, the GF becomes inoperativeMCR Operates as INST

    PTA 1-channel PTA Is inoperative

    ELT Is inoperative

    LED indicator on OCRs with Is on momentarily or offsingle-contact indication

    Contact output from OCRs with Turns off after 40 ms or moresingle-contact indication

    Contact output from OCRs with Is inoperativeindividual contact indication

    LCD No display

    Field test facility Is inoperative

    Protection

    characteristicsProtection relay

    Standard protection relays

    Over-current

    releace (OCR)

  • 7/23/2019 07_09_ACB Z Frame

    23/6622

    L-characteristic for general feeder circuits (Type AGR-11BL, 21BL, 31BL)

    Setting range of protection functions

    Protection functions Setting range

    Adjustable long time-delay trip characteristics

    LT

    Pick up current [IR] (A) [In]X(0.80.850.90.951.0NON); 6 graduations

    Non tripping when load current ([IR]X1.05). Tripping when ([IR]X1.05)< load current ([IR]X1.2)

    Time-delay [tR] (s) (0.51.252.551015202530) at 600% of [IR]; 9 graduations

    Time-delay setting tolerance (%) 15% +150ms0ms

    Adjustable short time-delay trip characteristics

    ST

    Pick up current [Isd] (A) [In]X(11.522.5346810 NON); 10 graduations

    Current setting tolerance (%) 15%

    Time-delay [tsd] (ms) Relay time 50 100 200 400 600 800; 6 graduations

    Resettable time (ms) 25 75 175 375 575 775

    Max. total clearing time (ms) 120 170 270 470 670 870

    Adjustable instantaneous trip characteristics

    INST or MCR (For AGR-11B, INST only)

    Pick up current [Ii] (A) [In]X(246810121416 NON); 9 graduations

    Current setting tolerance (%) 20%

    Adjustable pretrip alarm characteristics [In]X(0.750.80.850.90.951.0); 6 graduations

    Pick up current [IP1] (A) 7.5%

    Current setting tolerance (%) (5101520406080120160200) at [IP1] or more; 10 graduations

    Time-delay [tP1] (s) 15% +100ms 0ms

    Time-delay setting tolerance (%)

    Adjustable ground fault trip characteristics

    GF N ote: Set [Ig] to 1200A or less

    Pick up current [Ig] (A) [ICT]X(0.10.20.30.40.60.81.0NON); 8 graduations

    Current setting tolerance (%) 20%

    Time-delay [tg] (ms) Relay time 100 200 300 500 1000 200 ; 6 graduations

    Resettable time (ms) 75 175 275 475 975 1975

    Max. total clearing time (ms) 170 270 370 570 1070 2070

    Ground fault trip characteristics on line side

    REF (AGR-21B, 31B only)

    Pick up current [IRE F] (A) [ICT]X(0.10.20.30.40.60.81.0NON); 8 graduationsCurrent setting tolerance (%) 20%

    Time-delay (s) Inst

    N-phase protection characteristics

    NP

    Pick up current [IN] (A) [ICT]X(0.40.50.630.81.0); Factory set to a user-specified value Non tripping

    when load current ([IN]X1.05) Tripping when ([IN]X1.05)< load current ([In]X1.2)

    Time-delay [tN] (s) Tripping at 600% of [IN] with LT time-delay [tR]

    Time-delay setting tolerance (%) 15% +150ms 0ms

    Reverse phase protection characteristics

    NS (AGR-21B, 31B only)

    Pick up current [INS ] (A) [In]X(0.20.30.40.50.60.70.80.91.0); 9 graduations

    Current setting tolerance (%) 10%

    Time-delay [tNS ] (s) 0.40.81.21.622.42.83.23.64; 10 graduations

    Time-delay setting tolerance (%) 20% +150ms0ms

    Adjustable earth leakage trip characteristics

    ELT (AGR-31B only)

    Pick up current [IR] (A) 0.20.30.51 (Medium sensitivity) or 35 (Low sensitivity)

    Current setting tolerance Non operate below 50% of [IR], Operate between 50% and 100% of [IR]

    Time-delay [tR] (ms) Relay time 100 200 300 500 1000 2000 ; 6 graduations

    Resettable time (ms) 50 150 250 450 950 1950

    Max. total clearing time (ms) 250 350 450 600 1150 2150

    Under-voltage alarm characteristics

    UV (AGR-31B only)

    Recovery setting voltage (V) [Vn]X(0.80.850.90.95); 4 graduations

    Setting voltage (V) [Vn]X(0.40.60.8); 3 graduations

    Time-delay (s) 0.10.51251015203036; 10 graduations

    Control power AC100120V DC100125V

    AC200240V DC200250V

    DC48V

    DC24V

    Power consumption: 5 VA

    Common Common)

    Common)

    )

  • 7/23/2019 07_09_ACB Z Frame

    24/66

    Values of [ICT] and [In]

    Type Applicable Rated current [In](A)

    [ICT] [ICT] [ICT] [ICT] [ICT](A) X0.5 X0.63 X0.8 X1.0

    800 400 500 630 8001250 630 800 1000 12501600 800 1000 1250 1600

    Type Applicable Rated current [In](A)

    [ICT] [ICT] [ICT] [ICT] [ICT](A) X0.5 X0.63 X0.8 X1.0

    Z2 (STD) 2000 1000 1250 1600 2000Z3 (STD) 2500 1250 1600 2000 2500Z3 (STD) 3200 1600 2000 2500 3200Z4 (STD) 4000 2000 2500 3200 4000

    Type Applicable Rated current [In](A)

    [ICT] [ICT] [ICT] [ICT] [ICT](A) X0.5 X0.63 X0.8 X1.0

    Z2 (HIGH) 1250 630 800 1000 1250Z2 (HIGH) 1600 800 1000 1250 1600Z2 (HIGH) 2000 1000 1250 1600 2000Z3 (HIGH) 1600 800 1000 1250 1600Z3 (HIGH) 2000 1000 1250 1600 2000Z3 (HIGH) 2500 1250 1600 2000 2500Z3 (HIGH) 3200 1600 2000 2500 3200

    Protection characteristics

    23

    Z2(STD)

  • 7/23/2019 07_09_ACB Z Frame

    25/6624

    Loadline Z-Frame ACB Selection Chart

    Example: Drawout ACB, three-Pole, 65kA, 1600A with horizontal terminals and manual charging.21BL OCR with LSIG protection, Pretrip alarm and 240V ac control voltage.

    11BL 31BL No OCR

    ACB frame size

    Standard ACB

    breaking capacity

    High Series ACBbreaking capacity

    Z2 Frame

    Fixed Drawout

    4-Pole 3-Pole 4-Pole 3-Pole 4-Pole

    Fixed Drawout Drawout

    Z3 Frame Z4 Frame

    AC Controlvoltage

    200-240Vacor none on 11BL

    AC Controlvoltage

    110-120Vac

    DC Controlvoltage

    200-250Vdc

    DC Controlvoltage

    100-125Vdc

    DC Controlvoltage48Vdc

    DC Controlvoltage24Vdc

    3-Pole

    21BL

    PG

    (LSIG

    +PT)

    Items supplied as standard on all ACBs1. IP31 door flange2. 4 NO AB auxiliary switches3. Mechanical indication of spring status4. Mechanical open and close buttons and indicators5. Open and close button padlock facility6. Test report for ACB and OCR (when fitted)

    7. Operation manual

    Items supplied with draw-out ACB1. Draw-out handle2. Draw-out portion indication3. Draw-out portion position padlock facility4. Fixed portion main safety shuttles padlockable5. Fixed portion control circuits socket shutters

    Factory fitted accessories1. Castell/cylinder lock/padlock facility2. Shunt trip3. UVR fixed4. Aux switches5. Position switches (draw-out only)6. Mechanical Interlocks

    7. Spring charged indicator switch8. Auto spring discharge device

    (draw-out only)9. Under-voltage alarm10. Remotely tripped indicator switch11. Restricted ground fault12. Contact temperature monitoring13. Phase rotation protection

  • 7/23/2019 07_09_ACB Z Frame

    26/6625

    21BL

    Z2 Frame

    Drawout

    3-Pole

    65kA

    1600A

    Horz terms

    Manual charging

    PG (LSIG+PT)

    AC Control Voltage

    200 - 240Vac

    Order Codes

    Example

    Selected

    Example

    Order Code

    Z2

    Z2D

    Z2D3

    Z2D3J

    Z2D3J16

    Z2D3J16H

    Z2D3J16H0

    Z2D3J16H0K

    Z2D3J16H0KD

    Z2D3J16H0ADA

    Frame Size

    Z2 = Z2 Frame Z3 = Z3 Frame Z4 = Z4 Frame

    Body Type

    D = Drawout F = Fixed

    Number of Poles

    3 = 3-pole 4 = 4-pole

    Breaking capacity

    J = 60 - 65kA K = 80 - 85kA L = 100kA

    08 = 800A

    12 = 1250A

    16 = 1600A

    20 = 2000A

    25 = 2500A

    32 = 3200A

    40 = 4000A

    Terminal typeH = Horizontal top and bottomV = Vertical top and bottomF = Front top and bottom

    HV = Horizontal top, vertical bottomHF = Horizontal top, front bottomVH = Vertical top, horizontal bottomVF = Vertical top, front bottomFH = Front top, horizontal bottomFV = Front top, vertical bottom

    Charging type0 = Manual1 = 240V ac2 = 220V ac3 = 200V ac

    4 = 120V ac5 = 110V ac6 = 100V ac7 = 24V dc

    8 = 48V dc9 = 100V dc10= 110V dc11 = 125V dc

    12 = 200V dc13 = 220V dc

    9. Lifting plates10. Control circuits terminal cover11. IP55 cover12. OCR checker13. Motor step-down transformer

    (220V ac motor to be specified)14. Capacitor trip device

    (48V dc shunt trip to be specified)15. Mechanical interlock cables

    Loosegear accessories1. Shutter padlocking device (pair)2. Fixing bolts (draw-out only)3. Mal insertion device (draw-out only)4. Test jumper cable 5 meters5. ACB lifters6. Spare draw-out handle

    7. Terminal barrier8. Cycle counter

    OCR Control VoltageA = None on 11BL or200-240V acB = 200-250V dcC = 48V dc

    D = 100-120V acE = 100-125V dcF = 24V dc

    OCR type

    Order No OCR 11BL 21BL 31BL +Modbus +Zone +EarthCode Comms Interlock Leakage

    D

    J K L M N P Q R S T U

    OCR functions

    Order OCR LT ST INST/ PTA GF NPCode Type Function MCR

    ABCDFGHJ

    11BL

    21BL or31BL

    AlGL

    PSPG

    AL + NPGL + NP

    PS + NPPG + NP

    11BL

    21BL or31BL

    Current rating

  • 7/23/2019 07_09_ACB Z Frame

    27/66

    Section 2

    26

    Draw-Out Accessories(Fitted as standard)Main circuit safety shutters

    The main circuit safety shutters automatically conceal the main circuit contacts onthe draw-out cradle when the ACB is drawn out.

    The top and bottom shutters operate independently and can be separatelypadlocked in the closed position.

    Up to three padlocks (with 6 hasp) can be installed on each side usingpadlocking unit. (Padlock not supplied).

    In the closed position, the shutters are locked to the extent that they cannot beeasily unlocked by hand. They can be unlocked and held open if required for the

    purpose of inspection or maintenance.

    Control circuit safety shutter

    The control circuit safety shutter covers the control circuit contacts, ensuring safety.

    Position padlock lever

    Using the position padlock lever prevents the breaker body from inadvertently beingdrawn out. The position padlock lever in the pulled-out position locks the breakerbody in the CONNECTED, TEST or ISOLATED position. Up to three padlocks (with

    6 hasp) can be installed.

  • 7/23/2019 07_09_ACB Z Frame

    28/6627

    Current transformer for neutral line (separate type)

    When using a three-pole ACB with the ground fault protection function to protecta three-phase, four-wire system against ground fault, this current transformer (CT)should be fitted to the neutral line of the system.

    This CT is supplied a standard with all three-pole ACBs with ground fault OCRs.

    For the four-pole ACB, a measuring CT instead of the neutral line CT is already

    built into the neutral phase of the ACB when the ground fault protection is fitted.

    Outline dimension of CT for neutral line

    Restricted ground fault

    The over-current trip device of Loadline Z Frame provides a ground faultprotection on the line side (optional) as well as on the load side. When the ACBis used for protection of a three-pole, four-wire system, the same currenttransformer for the neutral line shown above is provided.

    Z2 Z3

    Rated 800A Primary 1250 A Current (A) 1600 A 1600 A

    Z2 Z3 Z4

    Rated 2000 A 2000 APrimary 2500 ACurrent (A) 3200 A 4000 A

    Rated secondary current is 5A

    Rated secondary current is 5A

  • 7/23/2019 07_09_ACB Z Frame

    29/6628

    ON-OFF button cover

    An ON-OFF button cover prevents inadvertent or unauthorised operation of theON or OFF button. It can be locked with up to three padlocks with 6 hasp.

    Padlocks are not supplied.

    Door flange

    A door flange can be used as a decoration panel that covers the cut-out on theswitchboard panel and provides IP31 protection.

  • 7/23/2019 07_09_ACB Z Frame

    30/6629

    Factory Fitted AccessoriesLocking Devices (factory fitted)

    Castell interlock

    The key interlock is a system of interlocking between ACBs, each fitted with a keylock of lock-in OFF type.

    A key must be inserted to release the lock before the ACB can be closed.

    The ACB must be opened and locked in the OFF position before the key canbe removed.

    Utilising the lock-in OFF type key lock feature and then a limited number of keys,by default, provides an effective and reliable interlock system.

    Using the same keys also allows interlocking between an ACB and other devices(such as a switchboard door).

    ACBs can be supplied with a type FS-2 Castell lock (with an angular movement90 clockwise to trap key) or the provision to fit a Castell lock.

    A double Castell interlocking facility suitable for applications such as UPS systemsis available as a special specification contact Tyco Electronics.

    Facility or full option including locks are available, see following order code chart.

    Cylinder lock

    The key lock is the lock-in OFF type that locks the ACB in the open position.

    When the ACB is fitted with a key lock, the operator cannot operate the ACBunless using a matched key, see following order code chart.

    Example: Interlock for prevention of parallel feeding from two sources

  • 7/23/2019 07_09_ACB Z Frame

    31/6630

    Padlockable device

    Permits the ACB to be padlocked in the OFF position. Max. three padlocks with 6hasp can be fitted. Padlocking is possible only when ON-OFF indicator shows OFF.When the ACB is padlocked in the OFF position both manual and electrical closingbecome inoperative, but the charging of the closing spring by manual or motor isstill possible.

    Note 1: OFF padlock facility cannot be fitted with key lock or key interlock.

    Order code Description

    0 Not fitted

    1 Castell ref DS1 fitted

    2 Castell ref DS2 fitted

    3 Castell ref DS3 fitted

    4 Castell provision for FS2 type lock

    5 Castell ref DS4 fitted

    6 Cylinder lock OFF

    7 Padlock device fitted

    8 Castell symbol A fitted

    9 Castell symbol B fitted

    *

    * (With angular movement 90 clockwise to trap key)

    Shunt trip rating (Continuously rated type)

    Order Rated Operational Peak excitation Steady-state Opening timecode voltage voltage current current (max.)

    (V) (V) (A) (A) (ms)

    0 Not fitted

    1 AC240 AC168264 0.18 0.12 40

    2 AC220 AC154242 0.19 0.13

    3 AC200 AC140220 0.24 0.16

    4 AC120 AC84132 0.37 0.24

    5 AC110 AC77121 0.39 0.26

    6 AC100 AC70110 0.48 0.32

    7 DC24 DC16.826.4 1.65 1.140

    8 DC48 DC33.6-52.8 0.86 0.57

    9 DC125 DC87.5-137.5 0.31 0.21

    u DC100 DC70-110 0.39 0.26

    v DC110 DC77-121 0.37 0.25

    w DC200 DC140-220 0.19 0.13

    x DC220 DC154-242 0.18 0.12

    y DC30 DC21-33

    Continuously-rated shunt trip device (factory fitted)

    The continuous-rated shunt trip device allows the ACB to be opened when anexternal protection relay against over-current or reverse power is activated.

    Because of its continuous rating, the device can also be used to provide anelectrical interlock to the ACB.

    Continuously rated shunt trip and under-voltage trip cannot be fitted to the sameACB. However, instantaneously rated shunt trip can be used together with under-voltage trip with special specification. Special double opening and closing coils are

    available. Contact Tyco Electronics for details.

    40

    Please contact Tyco Electronics.

    * *

    *

  • 7/23/2019 07_09_ACB Z Frame

    32/6631

    Under-voltage trip device (UVT) (factory fitted)

    The under-voltage trip device (UVT) trips the ACB when the control voltagedrops below the opening voltage. When the control voltage is restored to thepick up voltage, the ACB can be closed. The pick up voltage is fixed to 85% ofthe rated voltage.

    The UVT consists of a tripping mechanism and an under-voltage trip controldevice. The trip control device is available in two types, standard and delayed.

    Type standard provides an instantaneous trip to the ACB when the control voltagedrops below the opening voltage. The delayed type provides a delayed trip to theACB when the control voltage remains below the opening voltage for at least 500ms. Adding a push button switch (with normally opened contacts) betweenterminals 24 and 30 allows the ACB to be tripped remotely.

    Tripping signal is 48v dc/5 mA.

    Apply tripping signal for at least 80ms. If a constant tripping signal is applied an/o auxiliary switch must be used in series with the PB.

    Ratings

    Order code Rated Opening Pick up Coil excitation Powervoltage voltage voltage current Consumption (VA)

    Standard Delayed 50-60Hz (V) (V) (V) (A) Normal Reset

    0 Not fitted

    1 D 240 84-168 204

    2 E 220 77-154187

    3 F 200 70-140 170

    4 G 120 42-84 1025 H 110 38.5-77 93.5

    6 J AC100 35-70 85

    7 K 440 154-308 374

    8 L 415 145-290 352

    9 M 380 133-266 323

    A *DC24 8.4-16.8 20.4

    B *48 16.8-33.6 40.8

    C * 100 35-7085

    Under-voltage trip control circuit (for ac)

    *

    0.1 8 10

    Soon to be available. Contact Tyco Electronics for details.*

  • 7/23/2019 07_09_ACB Z Frame

    33/6632

    Auxiliary switches (factory fitted)

    The auxiliary switches operate during the ACB ON/OFF operation.

    Connections to the switches are made via screw terminals. The auxiliary switchesfor draw-out type ACBs operate in the CONNECTED and TEST positions.

    The auxiliary switches for ACBs conforming to classification societys rules operatein the CONNECTED position only.

    The auxiliary switches have change-over contacts and are available for generalservice and for microload.

    The standard contact arrangement of the auxiliary switches is 4c.

    (Form c: Change-over, single gap, three terminals)

    Suited to electronic circuits

    Note: 4c is the maximum arrangement when any one of the ground faultprotection on the line side, zone interlock, external display, orcommunication function is incorporated or in the case of type AGR-31BLOCR with the ground fault trip function incorporated.

    Note 1: The chattering of b-contacts due to ON-OFF operation of the ACB lasts forless than 20 ms.

    Note 2: Do not supply different voltages to contacts of a switch.

    Order code For general service For microload Total contacts

    0=Supplied as std 4c 4c

    1 7c 7c

    3 4c 3c 7c

    2 10c 10c

    4 7c 3c 10c

    **

    *

    *

    Auxiliary switch ratings

    Category For general service For microload

    Resistive Inductive ac: cos 0.3 Resistive Inductive ac: cos 0.6 Min. appl.

    load (A) load (A) dc: L/R 0.01 load (A) load (A) dc: L/R 0.007 load

    AC 5 5 0.1 0.1100-250V

    AC 5 5 251-500V

    DC30V 1 1 0.1 0.1

    DC 1 1 125-250V

    Voltage

    DC5V

    1mA

    **

  • 7/23/2019 07_09_ACB Z Frame

    34/6633

    Position switches (factory fitted)

    The position switch operates to give an indication of the breaker position:CONNECTED, TEST, ISOLATED and INSERT.

    There are two contact arrangements: 2c and 4c.

    Connections to the switches are made via screw type terminals.

    The following table lists the available types of the switches.

    Position switch operation sequence

    INSERT position means the breaker body is in any position between ISOLATEDand CONNECTED.

    Voltage Resistive load (A) Inductive load (A)

    (COS = 0.6, L/R = 0.07)

    AC 100-250V 11 6

    DC 250V 0.3 0.3

    DC 125V 0.6 0.6

    DC 30V 6 5

    DC 8V 10 6

    Order code Type Number of Contact Arrangement

    contacts Insert Isolated Test Conn

    0 None fitted

    1 ALR-0101P 2c 0 1 0 1

    2 ALR-1111P 4c 1 1 1 1

    3 ALR-0211P 4c 0 2 1 14 ALR-0112P 4c 0 1 1 2

    5 ALR-0202P 4c 0 2 0 2

    Position switch ratings

    CONNECTEDposition switch

    TESTposition switch

    ISOLATEDposition switch

    INSERTposition switch

    ISOLATED TEST CONNECTED

    a- contact ON

    a- contact ON

    a- contact ON

    a- contact ON

  • 7/23/2019 07_09_ACB Z Frame

    35/6634

    Mechanical Interlock Horizontal Type (factory fitted)

    The mechanical interlock uses a cable system to provide a positive interlockbetween two or three ACBs. In conjunction with an electrical interlock, it willenhance safety and reliability of power distribution systems.

    Interlocking is possible between any frame size within the Dorman SmithFrame Range.

    A configuration

    B configuration

    C configuration

    1 1

    3 3 3

    1 2 1

    Mains 1 Mains 2 Generator

    Mechanical Interlock

    Mechanism Type

    A Configuration

    Any one breaker can be closed outof three. Each breaker to be orderedseparately with appropriate mechtype.

    Example:-

    Breaker reference Mains 1 requiresmech type.

    Breaker reference Mains 2 requiresmech type.

    Breaker reference Generatorrequires mech type.

    B Configuration

    Any two breakers can be closed outof three.

    C ConfigurationAny one breaker can be closed outof two.

    Order Codes

    0 = None fitted

    1 = Mechanism Type

    2 = Mechanism Type

    3 = Mechanism Type

    Cable pairs to be orderedseparately see page 41

    1

    2

    3

    1

    2

    1

    Spring charge indicator switch (factory fitted)

    This switch can be used to indicate that the closing springs have been fully charged.

    For contact ratings of the switch, see table 3 -1 on page 20.

    See following accessory for order code.

    Under-voltage alarm function UV (factory fitted)

    (for AGR-31B only)This function monitors the main circuit voltage and gives an alarm on the LCDand an output signal via an alarm contact when the voltage drops below thesetting voltage.

    The alarm is activated when the main circuit voltage drops below the setting voltage(selectable from 40%, 60% or 80% of the rated main circuit voltage [Vn]), and isdeactivated when the main circuit voltage rises to the recovery setting voltage(selectable from 80%, 85%, 90% or 95% of the rated main circuit voltage [Vn]).

    If the rated main circuit voltage exceeds 250V ac, a step-down power transformer isneeded. When ordering the ACB, state the step-down ratio of the transformer youwill use.

    Note 1: The under-voltage alarm function is disabled unless the main circuitvoltage has once risen to the recovery setting voltage or higher.

    Note 2: If the under-voltage alarm function is used in conjunction with the under-voltage trip device (see page 31), an alarm may occur after the ACB tripsopen, depending on the alarm setting voltage.

    Order code: 0 = NoneOrder code: 1 = Spring charge indicator switch fitted

    Order code: 2 = Under-voltage alarm fitted

  • 7/23/2019 07_09_ACB Z Frame

    36/6635

    Automatic spring discharge device (factory fitted)

    This device allows the charged closing springs to be automatically released whenthe ACB is drawn out.

    ANSI or NEMA-compliant ACBs require this option.

    Order code: 0 = None 1 = Fitted

    Trip indication switch (factory fitted)

    This switch indicates when the ACB has been tripped from a source other thanthe OCR unit.

    See phase rotation protection accessory for order code.

    Restricted ground fault trip function (factory fitted)

    (for AGR-21BL and AGR-31BL only)

    Restricted and unrestricted ground fault protection is available as option.This enable protection against ground fault on the line side of the ACB.

    Restricted ground fault protection is only available with PG function.

    See phase rotation protection accessory for order code.

    Contact temperature monitoring function OH (factory

    fitted) (for AGR-31BL only)

    The HEAT function prevents the ACB from suffering damage due to overheat.

    It monitors the temperature of the ACB main contacts, and gives an alarm onthe LCD and an output signal via the alarm contact (1a-contact) when thetemperature exceeds 155C. The alarm can be manually reset when thetemperature drops to a normal level.

    This function needs the control power.See phase rotation protection accessory for order code.

    Phase rotation protection function NS (factory fitted)

    (for AGR-21BL and AGR-31BL only)

    This function detects the negative-phase current occurring due to reversephase or phase loss and prevents burnout of a motor or damage to equipment.The protection set point ranges from 20% to 100% of the main circuit ratedcurrent [In].

    Order code:0 = None fitted1 = Trip indicator switch fitted2 = Restricted ground fault fitted3 = Contact temperature monitoring

    4 = Phase rotation protection fitted

  • 7/23/2019 07_09_ACB Z Frame

    37/6636

    Loadline Z-Frame Accessories - Factory Fitted Order CodesHow to Order Factory Fitted AccessoriesExample (See Page 25):- Z2D3J16HOKDA fitted with:-

    DS1 Castell Lock, 120V ac shunt trip, 10c Auxiliary Switches, 1111 Position

    Switches = Z2D3J16HOKDA14022

    Resulting Order Code = Z2D3J16HOKDA14022

    D S 1

    C astell

    Fitted

    D S 2

    C astell

    Fitted

    D S 3

    C astell

    Fitted

    C astell

    Provision

    Cylinder

    Lock O ff

    Padlock

    O ffNone

    None

    N one 0101 0211 01121111 0202

    7c SW 's 10c SW 's 4c SW 's+ 3c (m icroload) 7c S W 's+3c (m icroload)

    NoneSpring C harge Indicator

    Fitted

    None Fitted

    None Trip Indicator Sw itchFitted

    1

    0

    0

    None

    0

    Interlock M echanism

    Type 1

    1

    0 1

    0 1

    0 1

    Restricted G round FaultFitted

    Interlock M echanism

    Type 2

    2

    Interlock M echanism

    Type 3

    3

    1 2 3 4 5

    1 2 3 4

    None240V

    AC

    220V

    AC

    200V

    AC

    120V

    AC

    110V

    AC

    100V

    AC

    440V

    AC

    380V

    AC

    415V

    AC

    0

    0

    1 2 3 4 5 6 7 8 9

    24Vx2

    D C

    A

    48Vx2

    D C

    B

    2 3 4 5 6 7

    U ndervoltage A larm - U V

    Fitted2

    Auxiliary Sw itche s

    O rder C ode

    O rder C ode

    Locks

    None240V

    AC

    220V

    AC

    200V

    AC

    120V

    AC

    110V

    AC

    100V

    AC

    0 1 2 3 4 5 6 7 8 9

    24V

    D C

    48V

    D C

    125V

    D C

    u

    100V

    D C

    v

    110V

    D C

    D S 4

    C astell

    Fitted8

    A

    C astell

    Fitted9

    B

    C astell

    Fitted

    2

    Shunt Trip

    O rder C ode

    O rder C ode

    U VT

    O rder C ode

    Position Sw itches

    M echanical

    Interlock

    O rder C ode

    Spring C harge Indicator or

    U ndervoltage A larm - U V

    O rder C ode

    O rder C ode

    Auto Spring

    D ischarge D evice

    O rder C ode

    Trip Indicator Sw itch or Re stricted

    G round F ault or Con tact Tem peratureM on itoring P hase R otation P rotection

  • 7/23/2019 07_09_ACB Z Frame

    38/66

    100Vx2

    D C

    C

    240V AC

    D elayed

    D

    220V AC

    D elayed

    E

    200V AC

    D elayed

    F

    120V A C

    D elayed

    G

    110V A C

    D elayed

    H

    100V AC

    D elayed

    J

    440V AC

    D elayed

    K

    415V A C

    D elayed

    L

    380V AC

    D elayed

    M

    w

    200V

    D C

    x

    220V

    D C

    y

    30V

    D C

    C ontact Tem perature M onitoringFitted

    3

    Phase Rotation ProtectionFitted

    4

    AGR-21BL & 31BL only

    AGR-31BL only

    37

  • 7/23/2019 07_09_ACB Z Frame

    39/66

    Accessories Supplied LooseTest JumperThe test jumper is a plug-in type, and allows ON-OFF tests on all the Loadline ZFrame series ACBs with the breaker body drawn out from the draw-out cradle.

    The standard jumper cable is 5 m long.

    Catalogue numberZDTJC

    Catalogue numberZDFB

    Description Catalogue numberZ2 & Z3 Frames Z23DLIFTZ4 Frame Z4DLIFT

    Breaker Fixing BoltsThe breaker fixing bolts hold the breaker body securely to the draw-outcradle in position. Use them if the ACB is subject to strong vibration.

    LiftersA special lifter is available to allow easy and safe transportation orinstallation of the ACB. A drop prevention mechanism is standard.

    w927

    95

    2300

    GripWinchhandle

    Loader

    ACB

    Section 3

    38

  • 7/23/2019 07_09_ACB Z Frame

    40/66

    Catalogue number

    ZDMID

    Description Catalogue numberZ2 and Z3 frames Z23DSPDZ4 frame Z4DSPD

    Description Catalogue numberCranked handle ZDHStowaway handle ZDHS

    Mal-insertion preventionInterchangeability exists within the Loadline Z Frame series of ACBs.Because of this feature, there is a possibility for an ACB of a differentspecification being placed into the draw-out cradle. Using the mal-insertionprevention device eliminates such a possibility.

    This device is capable of distinguishing nine different breaker bodies.

    Shutter Padlocking DeviceThe main circuit safety shutters automatically conceal the main circuitcontacts on the draw-out cradle when the ACB is drawn out.

    The top and bottom shutters operate independently and can be separatelypadlocked in the closed position.

    Up to three padlocks (with 6 hasp) can be installed on each side usingpadlocking unit. (Padlock not supplied)

    In the closed position, the shutters are locked to the extent that they cannotbe easily unlocked by hand. They can be unlocked and held open if requiredfor the purpose of inspection or maintenance.

    Spare Draw-out HandleCranked handle for withdrawing moving chassis from fixed portion.Stowaway handle for withdrawing moving chassis can be stored withinmoving chassis.

    Motor Step-down Transformer (external)The maximum rated control voltage applicable to the operation powersupply is AC240V. For higher voltages, a step-down transformer is needed.

    The following step-down transformers are available as options. The 220V acmotor should be specified.

    Rated control Transformer Cataloguevoltage Capacity Voltage ratio no.

    AC410-470V 300VA 450/220V ZMT4522A

    AC350-395V 300VA 380/220V ZMT3822A

    39

  • 7/23/2019 07_09_ACB Z Frame

    41/66

    Capacitor Trip DeviceIn conjunction with the continuously-rated shunt trip device, the capacitor tripdevice can be used to trip the ACB within a limited period of 30 seconds if alarge voltage drop occurs due to an ac power failure or short-circuit.

    When the continuously-rated shunt trip is used with a capacitor trip device, Acontact of auxiliary switch of ACB should be inserted into the series, otherwiseinternal damage may occur.

    When ordering the capacitor trip device, a 48V dc shunt trip is required to beordered separately.

    OCR CheckerThe OCR checker allows easy checking of the long time-delay trip, short time-delay trip, instantaneous trip, ground fault trip functions and the pretrip alarmfunction of the OCR in the field.

    Rated voltage AC100-120VOperational voltage Rated Voltage X 70 to 110%Rated frequency 50/60HzRated voltage of shunt trip used DC48VPower consumption 100VACatalogue number ZSTCD

    Power supply AC100-110V, 50/60HzorAC100-240V, 50/60Hz with type C plug

    4 x AA alkaline cellsPower consumption 7VADimensions 101(w) x 195(h) x 44(d) mmWeight 400gCatalogue number Z0CRC

    Control circuit Outline dimensions

    Ratings and specifications

    40

  • 7/23/2019 07_09_ACB Z Frame

    42/66

    ONOFF Cycle CounterThe ON-OFF cycle counter is a mechanical 5-digit readout that shows thenumber of ON-OFF cycles of the ACB.

    Counter readings serve as a guide for maintenance or inspection.

    Catalogue numberZCC

    Catalogue numberZLPLTS

    Mechanical Interlock CablesUsed in conjunction with Horizontal Interlocking Mechanism.

    Lifting PlateLifting plates are detachable tools that can be used to lift a breaker body outof a draw-out cradle.

    Length of Cable Z = (Cable length for pitch X) + Ymm

    e.g. If X = 800mm and Y = 600mmCable Z = (1320mm) + 600mm = 1920mm cable length.

    Mechanical Interlock Cables

    Pitch X or Y Cable length Catalogueno.

    500 or 600 1120mm (pair) ZMECHHC1120700 1220mm (pair) ZMECHHC1220

    800 1320mm (pair) ZMECHHC1320

    900 1420mm (pair) ZMECHHC1420

    1000 1520mm (pair) ZMECHHC1520

    1100 or 1200 1620mm (pair) ZMECHHC1620

    1720mm (pair) ZMECHHC1720

    1920mm (pair) ZMECHHC1920

    2120mm (pair) ZMECHHC2120

    2320mm (pair) ZMECHHC2320

    2520mm (pair) ZMECHHC2520

    2720mm (pair) ZMECHHC2720

    41

  • 7/23/2019 07_09_ACB Z Frame

    43/6642

    Control Circuit Terminal CoverA control circuit terminal cover protects the terminal blocks for auxiliary switches,position switches and control circuits from being accidentally touched, thusenhancing safety.

    Terminal BarrierAn inter-pole barrier prevents a possible short-circuit due to foreign objectsentering between the poles of the main circuit terminals or between the line andload ends, thus enhancing operational reliability of the ACB.

    This barrier can be applied to the draw-out type ACB with vertical terminals orhorizontal terminals.

    Catalogue numberZ2 frame 3-pole Z2D3CCTCZ3 frame 3-pole Z3D3CCTCZ4 frame 3-pole Z4D3CCTCZ2 frame 4-pole Z2D4CCTCZ3 frame 4-pole Z3D4CCTCZ4 frame 4-pole Z4D4CCTC

    Catalogue numberZ2 frame 3-pole Z2D3TBZ3 frame 3-pole Z3D3TBZ4 frame 3-pole Z4D3TBZ2 frame 4-pole Z2D4TBZ3 frame 4-pole Z3D4TBZ4 frame 4-pole Z4D4TB

  • 7/23/2019 07_09_ACB Z Frame

    44/66

    IP CoverAn IP cover provides an IP55 grade of protection as defined in IEC 60529.

    Even if the breaker body is on the ISOLATED position, IP cover can still be fittedon the ACB.

    Catalogue numberZIP55

    43

  • 7/23/2019 07_09_ACB Z Frame

    45/6644

    Outline DimensionsZ2 Draw-out800A, 1250A, 1600A and 2000A standard series1250A, 1600A & 2000A high series

    CP: ACB Front cover centre line

    Terminal size t1 t2 t3 w

    800A, STD 10 10 15 17.51250A, STD 10 10 15 17.51600A, STD 20 15 25 22.52000A, STD 20 15 25 1250A, HIGH 20 15 1600A, HIGH 20 15 2000A, HIGH 20 15

    1 Conductors including connecting bolts should be separateda minimum of 7mm from Draw-out handle.

    2 Panel cut should be 335mm not 339mm when the doorflange is not used. If IP55 door flange is used see page 43.

    N represents the neutral-pole of four-pole ACBs.

    For High fault series vertical terminal is standard andhorizontal terminal is optional and front connection isnot available.

    Section 4

  • 7/23/2019 07_09_ACB Z Frame

    46/6645

  • 7/23/2019 07_09_ACB Z Frame

    47/6646

    Outline DimensionsZ2 Fixed800A, 1250A, 1600A and 2000A standard series

    CP: ACB Front cover centre line

    Terminal size t1 t2 t3 w

    800A, STD 10 10 15 17.51250A, STD 10 10 15 17.51600A, STD 20 15 25 22.52000A, STD 20 15 25

    2 Panel cut should be 335mm not 339mm when the doorflange is not used. If IP55 door flange is used see page 43.

    N represents the neutral-pole of four-pole ACBs.

  • 7/23/2019 07_09_ACB Z Frame

    48/6647

  • 7/23/2019 07_09_ACB Z Frame

    49/6648

    Outline DimensionsZ3 Draw-out2500A and 3200A standard series1600A, 2000A, 2500A and 3200A high series

    CP: ACB Front cover centre line

    1 Conductors including connecting bolts should be separateda minimum of 7mm from Draw-out handle.

    2 Panel cut should be 335mm not 339mm when the doorflange is not used. If IP55 door flange is used see page 43.

    N represents the neutral-pole of four-pole ACBs.

    For High fault series vertical terminal is standard andhorizontal terminal is optional, and front connection isnot available.

  • 7/23/2019 07_09_ACB Z Frame

    50/6649

  • 7/23/2019 07_09_ACB Z Frame

    51/6650

    Outline DimensionsZ3 Fixed2500A and 3200A standard series

    CP: ACB Front cover centre line

    2 Panel cut should be 335mm not 339mm when the doorflange is not used. If IP55 door flange is used see page 43.

    N represents the neutral-pole of four-pole ACBs.

  • 7/23/2019 07_09_ACB Z Frame

    52/6651

  • 7/23/2019 07_09_ACB Z Frame

    53/6652

    Outline DimensionsZ4 Draw-out4000A standard series

    CP: ACB Front cover centre line

    1 Conductors including connecting bolts should be separateda minimum of 7mm from Draw-out handle.

    2 Panel cut should be 335mm not 339mm when the doorflange is not used. If IP55 door flange is used see page 43.

    N represents the neutral-pole of four-pole ACBs.

  • 7/23/2019 07_09_ACB Z Frame

    54/6653

  • 7/23/2019 07_09_ACB Z Frame

    55/6654

    Circuit diagram (with AGR-11BL OCR)

  • 7/23/2019 07_09_ACB Z Frame

    56/6655

  • 7/23/2019 07_09_ACB Z Frame

    57/6656

    Circuit Diagram (with AGR-21BL OCR)

    31

    40

  • 7/23/2019 07_09_ACB Z Frame

    58/66

    33

    57

  • 7/23/2019 07_09_ACB Z Frame

    59/66

    Circuit Diagram (with AGR-31BL OCR)

    31

    40

    58

  • 7/23/2019 07_09_ACB Z Frame

    60/66

    33

    59

  • 7/23/2019 07_09_ACB Z Frame

    61/66

    Circuit Withstand voltage (at 50/60 Hz)

    Main circuit Between terminals, AC3500V for 1 minute 12kVterminal group to earth

    Auxiliary switches For general service Terminal group to earth AC2500V for 1 minute 6kV

    For microload Terminal group to earth AC2000V for 1 minute 4kV

    Position switches Terminal group to earth AC2000V for 1 minute 4kV

    Over-current release (OCR) Terminal group to earth AC2000V for 1 minute 4kV

    Power supply for under-voltage/ Terminal group to earth AC2500V for 1 minute 6kVreverse power trip function

    Other accessories Terminal group to earth AC2000V for 1 minute 4kV

    Controlcircuits

    Rated impulse withstandvoltage Uimp

    60

    Technical Data and ApplicationsDielectric strength

    Frame Z2 Z3 Z4

    Rated current (A) 800 1250 1600 2000 2500 3200 4000

    DC internal resistance per pole (m) 0.033 0.033 0.028 0.024 0.014 0.014 0.014

    AC power consumption for 3-poles (W) 200 350 350 490 600 780 1060

    Frame Z2 Z3 Z4

    Standard series current rating 800/1250A 1600A 2000A 2500/3200A 4000AHigh series current rating 1600-2000A 1600-3200A

    3P 4P 3P 4P 3P 4P 3P 4P 3P 4P

    Draw-out body (Kg) 45 51 46 52 46 52 56 68 71 92

    Draw-out chassis (Kg) 28 35 30 38 33 42 49 57 68 84

    Total draw-out weight (Kg) 73 86 76 90 79 94 105 125 139 176

    Fixed (Kg) 53 59 54 60 54 60 80 92

    Frame Z2 Z3

    Rated current (A) 1250 1600 2000 1600 2000 2500 3200

    DC internal resistance per pole (m) 0.024 0.024 0.024 0.014 0.014 0.014 0.014

    AC power consumption for 3-poles (W) 260 350 490 310 430 600 780

    Note: The values shown above are those measured on phase connections andcannot be applied to control terminals on the ACB.

    Note: The above weights are based on normal specifications with the OCR andstandard accessories.

    Internal Resistance and Power Consumption

    Standard series

    Weight

    High fault series

    Section 5

  • 7/23/2019 07_09_ACB Z Frame

    62/6661

    Frame Z2 Z3 Z4

    Based Ambient Rated current 800 1250 1600 2000 2500 3200 4000standards temperature connecting 2x50x5t 2x80x5t 2x100x5t 3x100x5t 2x100x10t 3x100x10t 4x150x6t

    (C) bar sizes

    IEC60947-2 40 (Standard ambient 800 1250 1600 2000 2500 3200 4000EN 60947-2 temperature)

    AS3947.2 45 800 1250 1600 2000 2500 3200 4000

    50 800 1250 1600 2000 2500 3200 4000

    55 800 1200 1540 1820 2500 2990 3940

    60 800 1150 1460 1740 2400 2850 3760

    NEMA,SG-3 40 (Standard ambient 800 1250 1540 2000 2500 3200 3700ANSI C37.13 temperature)

    45 800 1190 1470 1960 2500 3010 3580

    50 800 1130 1390 1860 2440 2860 3470

    55 790 1070 1310 1750 2300 2690 3350

    60 740 1000 1230 1640 2150 2520 3140

    JIS C8372 40 (Standard ambient 800 1250 1600 2000 2500 3200 3700temperature)

    45 800 1250 1600 1900 2500 2900 3580

    50 800 1190 1540 1820 2500 2800 3470

    55 800 1130 1460 1740 2400 2710 3350

    60 800 1080 1390 1650 2280 2610 3230

    Frame Z2 Z3

    Based Ambient Rated current 1250 1600 2000 1600 2000 2500 3200standards temperature connecting 2x80x5t 2x100x5t 3x100x5t 2x100x5t 3x100x5t 2x100x10t 3x100x10t

    (C) bar sizes

    IEC60947-2 40 (Standard ambient 1250 1600 2000 1600 2000 2500 3200EN 60947-2 temperature)

    AS3947.2 45 1250 1600 2000 1600 2000 2500 3200

    50 1250 1600 2000 1600 2000 2500 3200

    55 1250 1600 1820 1600 2000 2500 2990

    60 1250 1550 1740 1600 2000 2400 2850

    NEMA,SG-3 40 (Standard ambient 1600 2000 2500 3200ANSI C37.13 temperature)

    45 1600 1960 2500 3010

    50 1600 1860 2440 2860

    55 1510 1750 2300 2690

    60 1420 1640 2150 2520

    JIS C8372 40 (Standard ambient 1250 1600 2000 1600 2000 2500 3200temperature)

    45 1250 1600 1900 1600 2000 2500 2900

    50 1250 1600 1820 1600 2000 2500 2800

    55 1250 1550 1740 1600 2000 2400 2710

    60 1250 1480 1650 1600 1900 2280 2610

    Note: The values are applicable for both draw-out type and fixed type.The values for 800A, 1250A and 1600A are for horizontal terminals onboth line and load side.The values for 2000A, 2500A, 3200A and 4000A are for verticalterminals on both line and load side.Above figures are subject to the design of the enclosure and rating

    of busbar.

    Note: The values are for vertical terminals on both line and load side.Above figures are subject to the design of the enclosure and rating of busbar.

    : Contact Tyco Electronics for details.

    Derating

    Standard series

    *

    * ****

    ****

    *

    ***

    * *

    High fault series

  • 7/23/2019 07_09_ACB Z Frame

    63/6662

    Application DataWhat Is Discrimination?

    Discrimination, also called selectivity, is the coordination of protective devices suchthat a fault is cleared by the protective device installed immediately upstream ofthe fault and by that device alone.

    Total discrimination

    Discrimination is said to be total if the downstream circuit breaker opens and theupstream circuit breaker remains closed. This ensures maximum availability of

    the system.

    Partial discrimination

    Discrimination is partial if the above condition is not fulfiled up to the prospectiveshort-circuit current, but to a lesser value, termed the selectivity limit current (Is).

    Above this value both circuit breakers could open, resulting in loss of selectivity.

    How To Read The Discrimination Tables

    Boxes containing the letter T indicate total discrimination between the relevantupstream and downstream circuit breakers. Total discrimination applies for all faultlevels up to the breaking capacity of the upstream or the downstream circuitbreaker, whichever is the lesser.

    For the other boxes, discrimination is either partial or there is no discrimination.

    Worked ExamplesQ (1) A main switchboard requires a 1600A ACB feeding a 400A MCCB. The fault

    level is 65kA. What combination of protective devices would provide totaldiscrimination?

    A (1) A Loadline 1600A, Z2 ACB feeding a Loadline YA5J MCCB would providetotal discrimination up to 65kA. See page 63.

    Note: Discrimination would be total whether the Loadline ACB had an integral orexternal protection relay because Icw (1s) = Ics. Most other ACBs haveIcw(1s) < Ics.

    Recommendation for Busbars connection

    The busbars to the ACB should be firmly supported near the ACB terminal. Faultcurrents flow through the busbars developing large electromagnetic forcebetween the busbars, and the support must be strong enough to withstand suchforces. The ACB should not be relied on as a single support.

    Short-circuit current (kA) 30 50 65 80 100

    D istance Z2 fram e 300 250 150 150

    L (m m ) Z3 & Z4 fram e 350 300 250 150 150

    The maximum distance of the connection point of ACB to the first busbar support

  • 7/23/2019 07_09_ACB Z Frame

    64/6663

    Discrimination Table

    Loadline Z Frame

    Upstream: Loadline Z Frame ACB with or without Integral Protection Relay

    Downstream: Loadline YA Frame MCCB

    Frame 800A 1250A 1600A 2000A 2500A 3200A4000A

    Model

    Breaking capacity

    125A YA2N 25kA T T T T T T T T T T T T T

    YA2S 36kA T T T T T T T T T T T T T

    YA2J 65kA T T T T T T T T T T T T T

    160A/ YA3N 25kA T T T T T T T T T T T T T

    250A YA3S 36kA T T T T T T T T T T T T T

    YA3J 65kA T T T T T T T T T T T T T

    YA3J-E 70kA T T T T T T T T T T T T T

    400A/ YA5N 25kA T T T T T T T T T T T T T

    360A YA5S 36kA T T T T T T T T T T T T T

    YA5H 50kA T T T T T T T T T T T T T

    YA5J 70kA T T T T T T T T T T T T T

    YA5J-E 70kA T T T T T T T T T T T T T

    800A Y6H 65kA T T T T T T T T T T T T T

    Y6J-E 65kA T T T T T T T T T T T T T

    Y6K 100kA T T T T T T T T T T T T T

    Y6H-E 50kA T T T T T T T T T T T T T

    Y7J-E 65kA T T T T T T T T T T T T T

    Y8K-E 85kA T T T T T T T T T T T T T

    800A

    STDseries

    &high

    series

    1250A

    STDseries

    &high

    series

    1600A

    STDseries

    &high

    series

    2000A

    STDseries

    &high

    series

    2500A

    STDseries

    &high

    series

    3200A

    STDseries

    &high

    series

    4000A

    STDseries

    65kA 80kA 80kA 80kA 80kA 85kA 85kA100kA 100kA 100kA65kA 65kA 65kA

    Note: 1. All ACBs have Ii set at NON, MCR ON.2. Assuming ACB time settings are greater than MCCB.3. The above table is in accordance with IEC 60947-2, Annex A4. External relay can be used - Contact Tyco Electronics for further details.5. All values shown at 400V ac.

    T = Total selectivity

    DownstreamM

    CCB

    Upstream ACB

  • 7/23/2019 07_09_ACB Z Frame

    65/6664

    Discrimination with T type fuses

    The following table should be used as a guide when selecting Dorman SmithLoadline Z Frame Air Circuit Breakers and fuses (BS88/IEC269) which areimmediately downstream from a transformer.

    In and Ir are set to the full rated current of the transformer and tr, Isd and tsd areat standard transformer settings.

    Listed are the maximum fuse ratings that can be used when downstream from agiven ACB at these settings.

    Also included are the maximum fuse ratings that can be used downstream when tr,Isd and tsd are at their maximum settings.

    All information listed is based on a transformer secondary voltage of 415V.

    Transformer kVA 500 630 750 800 1000 1250 1600 2000F.L.C. (A) 696 876 1043 1113 1391 1739 2226 2782

    Loadline Z Frame Frame Z2 Z2 Z2 Z2 Z2 Z2 Z3 Z3(standard series) C.T. (A) 800 1250 1250 1250 1600 2000 2500 3200

    In 1 0.8 1 1 1 1 1 1IR 0.9 0.9 0.85 0.9 0.9 0.9 0.9 0.9

    tR (sec) 20 20 20 20 20 20 20 20Isd 6 6 6 6 6 6 6 6

    tsd (mcec) 400 400 400 400 400 400 400 400Max. fuse rating withstandard ACB settings (Amps)*Max. fuse rating withmaximum ACB settings (Amps)

    355 400 500 500 500 630 800 1000

    450 500 670 710 800 1000 1250 1250**

    Settings(AGR-L)

    > The above In settings are based on 100% of Rated Current (Ict).

    > Table Reference : Ir - Long Time Delay Pickup Current, tr - Long Time Delay Time Setting, Isd - Short TimeDelay Pickup Current, tsd - Short Time Delay Time Setting.

    Notes:

    * It is possible to increase the maximum fuse rating by utilising the rampfacility on the Loadline Z Frame Protection Relay (AGR).

    ** Information on fuses above 1250A rating was not available.

    *** Al