    EnergySavingOpportunitiesforTransformers

    AasitM.Naik

    VoltampEnergySAOG,Oman

    WestAsiaCopperForum

    GrandHyatt Dubai

    May5,2010

    May5,2010

  • 8/2/2019 07-Voltamp

    2/24

    May5,2010

    1KW

    Energy

    saved

    =

    2KW

    of

    Energy

    Generated

    1KW

    Energy

    saved

    =

    2KW

    of

    Energy

    Generated

  • 8/2/2019 07-Voltamp

    3/24

    May5,2010

    Content

    OmanOverview

    ElectricityinOman

    EnergyDemand/Projects

    Needfor

    Energy

    Efficiency

    T&DLosses

    Advantages

    of

    Energy

    Efficiency Whatsthecatch?

    OmanOverview

    Electricityin

    Oman

    EnergyDemand/Projects

    Needfor

    Energy

    Efficiency

    T&DLosses

    Advantages

    of

    Energy

    Efficiency Whatsthecatch?

  • 8/2/2019 07-Voltamp

    4/24

    May5,2010

    OmanOverview

    Area : 309,550sqkm.

    Population : 2,845,000[2009e]

    GDP(PPP) : $74.431Bn[2009e]

    PerCapita

    : 25,109

    USD

    GDP(Nominal): $53.395Bn

    Installed

    capacity

    : 4,360

    KW

    [2009]

    Area : 309,550sqkm.

    Population

    : 2,845,000[2009e]

    GDP(PPP) : $74.431Bn[2009e]

    PerCapita

    : 25,109

    USD

    GDP(Nominal): $53.395Bn

    Installed

    capacity

    : 4,360

    KW

    [2009]

  • 8/2/2019 07-Voltamp

    5/24

    OmanInstalled

    Capacity

    KW

    May5,2010

  • 8/2/2019 07-Voltamp

    6/24

    May5,2010

    Description 2009 2010p 2011p 2012p 2013p

    InstalledCapacity 4,360 4,412 5,291 5,770 6,179

    GrossGeneration 3,523 3,474 4,134 4,586 4,960

    DesalinationandAuxiliaryLoad 166 166 174 178 200

    NetGeneration 3,357 3,308 3,959 4,407 4,760

    ExternalInfeed 40 501 464 468 546

    Load 3,325 3,719 4,326 4,801 5,223

    GridLosses

    72.5 90.4 97.1 74.2 83.1

    GridLosses(%) 2.1 2.4 2.2 1.5 1.6

    LoadGrowthRate(%) 12 16 11 9

    OmanElectricityScenario MW

  • 8/2/2019 07-Voltamp

    7/24

    May5,2010

    TransformerTenderrequirementsplannedbyOTEC&

    Utilities(MVA)

    Description 2010 2011 2012

    220kVTransformers 576 500

    132kV

    Transformers 1,846

    2,516

    3,626

    33kVTransformers 810 515 900

    11

    kV

    Transformers 1,786

    1,875

    1,969

    TOTALMVA 4,442 5,482 6,995

  • 8/2/2019 07-Voltamp

    8/24

    May5,2010

    WhyTransformer

    Efficiency?

    LossesoccuratallstagesfromGenerationto

    Transmissionto

    Distribution

    SavingspotentialexistsforOman

    Technologyexists

    using

    better

    grades

    of

    CRGO&optimizationofDesigns

    Oileconomieshavepotentialforspendingfor

    betterefficiency.

    Capacity

    to

    spend

    would

    declinewiththedryingupofOil.

    LossesoccuratallstagesfromGenerationto

    Transmissionto

    Distribution

    SavingspotentialexistsforOman

    Technologyexists

    using

    better

    grades

    of

    CRGO&optimizationofDesigns

    Oileconomieshavepotentialforspendingfor

    betterefficiency.

    Capacity

    to

    spend

    would

    declinewiththedryingupofOil.

  • 8/2/2019 07-Voltamp

    9/24

    May5,2010

    Transformer

    efficiencySl.No. Rating [email protected]@0.75load

    1 100kVA,11/0.433kV 97.68%

    2 200kVA,11/0.433kV 98.21%

    3 315kVA,11/0.433kV 98.61%

    4 500kVA,11/0.433kV 98.84%

    5 1000kVA,11/0.433kV 99.01%

    6 1600kVA,

    11/0.433

    kV 99.02%

    7 2000kVA,11/0.433kV 98.88%

    8 3MVA,33/11.5kV 99.13%

    9 6MVA,33/11.5kV 99.29%

    10 10MVA,33/11.5kV 98.32%

    11 20MVA,33/11.5kV 99.31%

    11 125MVA,132/33kV 99.59%

  • 8/2/2019 07-Voltamp

    10/24

    May5,2010

    Lossesin

    distribution

    transformers

    Noloadloss,orironloss(NL)

    Loadloss,

    or

    copper

    loss

    (LL)

    DCloss

    Extralosses

    eddycurrentlossinwindings

    strayloss

    Otherlosses

    (ventilation,

    )

    Noloadloss,orironloss(NL)

    Loadloss,

    or

    copper

    loss

    (LL)

    DCloss

    Extra

    losses eddycurrentlossinwindings

    strayloss

    Otherlosses

    (ventilation,

    )

  • 8/2/2019 07-Voltamp

    11/24

    May5,2010

    Noloadloss

    Extraloss

    Resisitiveloss

    Conventionalload

    lossexclharmonics

    Extraloss

    due

    to

    harmonics

    Unloaded Ratedload Actualload Actualload

    (exclharmonics) (inclharmonics)

    Loadloss

    Lossesin

    distribution

    transformers

  • 8/2/2019 07-Voltamp

    12/24

    May5,2010

    EvolutionofCRGOmaterial

  • 8/2/2019 07-Voltamp

    13/24

    SavingsDue

    To

    Lower

    Losses

    May5,2010

    Transformer Rating: 1000KVAEff at 75% Load &

    0.8 pf 99.30% 98.84%

    Low Loss Transformers Standard Transformer

    No Load Loss (NLL) in Watts 1200 1500

    Load Loss (LL) in Watts 6000 8000

    Loss Load Factor (LLF) 0.75

    Number of days transformer operating 365

    NLL Saved LL Saved Annual savings in KWH

    Watts Watts Due to NLL with LLF* Due to LL with LLF* Total kWH

    300 2000 2,628 13,140 15,768

    Energy saved inKWH 15,768 kWh

    Cost of Energy 0.02RO

    Total AnnualSaving 315 RO

    For 30 years 9,461 RO ( $ 24,586)

  • 8/2/2019 07-Voltamp

    14/24

    May5,2010

    Extremecases

    HighlossDesign LowlossDesign

  • 8/2/2019 07-Voltamp

    15/24

    May5,2010

    Conductormaterials

    CuandAltransformerscanbebuilttocomply

    tothe

    same

    performance

    and

    quality

    standard

    Ingeneral,useofCuleadsto:

    heavier,but

    more

    compact

    windings

    asmallercore

    a

    smaller,

    more

    compact

    transformeralowernoiselevel

    lessoilcontent

  • 8/2/2019 07-Voltamp

    16/24

    May5,2010

    Advantages Saveenergy

    BetterShort

    circuit

    withstand

    (bigger

    mass)

    Saveemissions Noise

    Reducedheating

    Improvedlifetime Reliability

    Morerobust

    against

    harmonics

    Paybackinapprox.6yearsforincrementalcost

    Saveenergy

    BetterShort

    circuit

    withstand

    (bigger

    mass)

    Saveemissions Noise

    Reducedheating

    Improvedlifetime Reliability

    Morerobust

    against

    harmonics

    Paybackinapprox.6yearsforincrementalcost

  • 8/2/2019 07-Voltamp

    17/24

    May5,2010

    Whatsthe

    catch?

    Increasedcapitaloutlay Transformer

    procurementcosts

    will

    go

    up

    by

    50%

    Commercialpolicyofsuppliers Premiumonbettergradesofmaterial

    Fasteravailabilityofbetter/highergradesofCRGO

    Smallamounts

    The

    Capitalization

    rates

    alreadyhigh.dximprovementstillpossible.

    Increasedcapitaloutlay Transformer

    procurementcosts

    will

    go

    up

    by

    50%

    Commercialpolicyofsuppliers Premiumonbettergradesofmaterial

    Fasteravailabilityofbetter/highergradesofCRGO

    Smallamounts

    The

    Capitalization

    rates

    alreadyhigh.dximprovementstillpossible.

  • 8/2/2019 07-Voltamp

    18/24

    May5,2010

    Energy&emissionsavingspotentialsrelatedto

    transformers&

    standby

    power

    Region EnergysavingsTWh/yr

    CO2SavingsMilliontonne/yr

    Source

    EU 22 9 THERMIEC&EE 5 5 ECIUS 45 34China 47 52 IIECJapan 24 ToprunnerTotal 143 100

  • 8/2/2019 07-Voltamp

    19/24

    PresentEnergyEfficiencyStandards

    May5,2010

    PresentlyOman buysTransformers

    asperIEC/OES/DEPSpecifications

    Efficiency

    Levels

    :

    around

    98

    %

    AverageEfficiencylevelsinDevelopedCountries :99.3 99.7%

    AssumingOmancanimprovebyeven0.5%

    Energysavedwillbe: 0.5%oftheconnectedload

    AssuminganMVAof(refslide8)andaloadfactorof75%

    This

    will

    mean

    :

    Saving

    of

    70,956,000

    KWH

    SavedinOMR :42,573,600atpresenttariff

    PresentlyOman buysTransformers

    asperIEC/OES/DEPSpecifications

    EfficiencyLevels:around98%

    AverageEfficiencylevelsinDevelopedCountries :99.3 99.7%

    AssumingOmancanimprovebyeven0.5%

    Energysavedwillbe: 0.5%oftheconnectedload

    AssuminganMVAof(refslide8)andaloadfactorof75%

    Thiswillmean:Savingof70,956,000KWH

    SavedinOMR :42,573,600atpresenttariff

  • 8/2/2019 07-Voltamp

    20/24

    AgenciesThat

    Govern

    May5,2010

    DCRP forDistributionCos.(Majan/Mazoon/

    MEDC/RAECo/DPC

    OETC ForGeneration&TransmissionSectorfor

    Voltagesabove33kV

    PDO Follow

    DEP

    Specifications

    Consultants EnergoProjects,Parsons,Mott

    MacDonalds,Atkin,etc

    OccidentalofOman GenerallyfollowPDO/DEP

    Specifications

  • 8/2/2019 07-Voltamp

    21/24

    Whatwill

    be

    Required

    May5,2010

    IntroduceLowLossconcept BothforNoLoadLoss

    aswellasLoadLosstoachievemaximumefficiency

    tothe

    tune

    of

    99.5

    to

    99.7%

    NoloadLosscanbebroughtdownfurtherbyusing

    newlaserscribedmaterialsintroducedbytheMills

    whichpromise

    10

    15%%

    lower

    W/kg

    at

    marginal

    increaseincost

    ReduceLoadlossesinthespecifications,additional

    priceowing

    to

    extra

    Copper

    would

    be

    easily

    offset

    throughenergysavings.

  • 8/2/2019 07-Voltamp

    22/24

    ProposedICA

    Initiative

    May5,2010

    IntroduceEnergyEfficiencyconcepttotheRegulatorsandConsultantsthroughinitiativesbased

    onglobal

    experiences

    and

    best

    practices

    AwellcoordinatedprogramcanbedesignedtofinallycauseachangeinTechnicalSpecifications

    Voltampwould

    actively

    support

    ICA

    initiatives

    for

    a

    collaborativedialoguewiththeRegulatorsand

    Consultants

    Abusiness

    Case

    can

    be

    jointly

    developed

    by

    Voltamp &ICA;whichICAcanthenpresentto

    regulatorsona neutralplatform

  • 8/2/2019 07-Voltamp

    23/24

    May5,2010

    AbouttheSpeaker

    AasitM.NaikAsst.GeneralManager Marketing&SalesVoltampEnergySAOG

    AasitheadstheMarketing&SalesfortheVoltampGroupacrossMENAregion,responsibleforTransformer&SwitchgearPantsforRusaylPlants andthenew

    SoharPowerPlant.AasitjoinedVoltampTransformersOmanLLCin 2004,aftera

    longcareerof20yearsintheTransformersandSwitchgearIndustryinIndiaat

    reputedmanufacturerslikeCromptonGreaves,EMCO,GEC(nowAREVA)and

    VoltampIndia.

    AasithasBachelorsDegreeinElectricalEngineeringandPostGraduateDiploma

    inMarketingManagementandalsoacertifiedSAP SDConsultant

    ContactDetails:

    Tel:+968244472E203Fax:+968244471Mob:+96899337423

    Email:[email protected]

  • 8/2/2019 07-Voltamp

    24/24

    Thankyou

    May5,2010