06239627
-
Upload
herokaboss1987 -
Category
Documents
-
view
215 -
download
0
Transcript of 06239627
-
7/27/2019 06239627
1/11
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012 1843
A Decentralized Robust Control Strategy forMulti-DER MicrogridsPart I:
Fundamental ConceptsAmir H. Etemadi, Student Member, IEEE, Edward J. Davison, Life Fellow, IEEE, and Reza Iravani, Fellow, IEEE
AbstractThis paper presents fundamental concepts of acentral power-management system (PMS) and a decentralized,robust control strategy for autonomous mode of operation of a mi-
crogrid that includes multiple distributed energy resource (DER)
units. The DER units are interfaced to the utility grid throughvoltage-sourced converters (VSCs). The frequency of each DERunit is specified by its independent internal oscillator and alloscillators are synchronized by a common time-reference signalreceived from a global positioning system. The PMS specifies
the voltage set points for the local controllers. A linear, time-in-
variant, multivariable, robust, decentralized, servomechanismcontrol system is designed to track the set points. Each controlagent guarantees fast tracking, zero steady-state error, and robustperformance despite uncertainties of the microgrid parameter,
topology, and the operating point. The theoretical concept of theproposed control strategy, including the existence conditions,
design of the controller, robust stability analysis of the closed-loopsystem, time-delay tolerance, tolerance to high-frequency effectsand its gain-margins, are presented in this Part I paper. Part IIreports on the performance of the control strategy based on digital
time-domain simulation and hardware-in-the-loop case studies.
Index TermsAutonomous mode of operation, decentralizedcontrol, microgrid, robust control.
I. INTRODUCTION
T ECHNICAL and economical viability of the distributedenergy resource (DER) technologies for distributionvoltage class applications have resulted in the emergence of
the microgrid concept [1], [2]. Impacts of the DER units on the
host microgrid and their control, protection, and management
requirements for successful operation of the microgrid have
been extensively reported in the technical literature [3][7].
However, the anticipated high-depth of penetration of DERunits in the microgrid necessitates a systematic and compre-
hensive approach to their integration. This stems from the need
to 1) enable the microgrid to operate in the grid-connected
mode, the islanded mode, and the virtual power plant (VPP)
mode; 2) respond to the external commands (e.g., market
Manuscript received June 06, 2011; revised November 04, 2011, February29, 2012; accepted May 27, 2012. Date of publication July 13, 2012; date ofcurrent version September 19, 2012. Paper no. TPWRD-00490-2011.
The authors are with the Department of Electrical and Computer Engi-neering, University of Toronto, Toronto, ON M5S 3G4, Canada (e-mail: [email protected]; [email protected]; [email protected]).
Digital Object Identifier 10.1109/TPWRD.2012.2202920
signals); 3) accommodate the microgrid inherent unbalanced
conditions, uncertainties in parameters and topology, and
frequent load/generation changes; and 4) make provisions for
demand-side integration.
The existing/reported DER control strategies of a microgrid
are as follows.
Droop-based methods [7][19]: The main advantage of
the droop-based approach is that it obviates the need for
communication and operates based on local measurements.However, it presents several limitations [20][22]: 1) poor
transient performance; 2) lack of robustness due to in-
ability to account for load dynamics; and 3) inherent lack
of black-start capability.
Centralized-control methods [23], [24]: This approach re-
lies on fast and high-bandwidth communication, and the
communication failure can lead to the system collapse.
Master/slave control method [25]: This method is flexible
in terms of connection and disconnection of DER units;
however, it requires a dominant DER unit for satisfactory
operation.
Robust servomechanism control method [26]: Althoughthis method is robust to microgrid parametric uncertain-
ties, it is not readily applicable to multiple DER units.
This paper presents a power-management system (PMS) and
a control strategy for an islanded multi-DER microgrid to over-
come the drawbacks of the existing approaches. Based on the
proposed strategy: 1) the PMS specifies voltage set points for
each voltage-controlled bus, based on a fast power flow anal-
ysis; 2) local voltage controllers (LCs) provide tracking of the
voltage set points; and 3) an open-loop frequency control and
synchronization scheme maintains system frequency.
The prominent features of the proposed strategy are the fol-
lowing: 1) The PMS precisely controls powerflow of thesystem
and achieves a prescribed load sharing among the DER units;
2) LCs track corresponding voltage set points and rapidly re-
ject disturbances; 3) LCs are highly robust to parametric, topo-
logical, and unmodeled uncertainties of the microgrid; 4) LCs
are implemented in a decentralized manner; this obviates the
need for a high-bandwidth communication medium to feed the
systems information to a central authority and makes it scal-
able for larger number of DER units; 5) LCs enable the system
to sudden connection/disconnection of DER units; and 6) fre-
quency of the system is fixed and cannot deviate due to tran-
sients. The proposed approach requires low-bandwidth commu-
nication for both synchronization and PMS data transmission.
Furthermore, temporary failure of communication will not lead
0885-8977/$31.00 2012 IEEE
-
7/27/2019 06239627
2/11
-
7/27/2019 06239627
3/11
ETEMADI et al.: DECENTRALIZED ROBUST CONTROL STRATEGY FOR MULTI-DER MICROGRIDSPART I 1845
Fig. 2. Angle waveform generated by a crystal oscillator.
reference signal provided by a GPS, Fig. 1(b). These entities are
further described in Sections II-B1, II-B2, and II-B3.
1) Power-Management System: The main function of the
PMS is to provide load sharing among DER units based on ei-
ther a cost function associated with each DER unit or a market
signal. In the proposed method, voltage angle and magnitude
of each DER PC bus are directly controlled; thus, the ac-
tive/reactive power injection by at the th PC-bus is
(1)
(2)
Equations (1) and (2) indicate that powerflow of the system
is determined based on the voltage magnitude and angle of
, and [Fig. 1(a)]. The power-management
process should be performed frequently to maintain the pre-
specified load sharing scheme among the DER units as the
microgrid operating point changes (e.g., due to load changes).
The time-interval between setpoint updates depends on the rate
of microgrid operating point variation.2) Frequency Control and Synchronization: The microgrid
frequency is controlled in an open-loop manner. The LC of
each DER unit includes a crystal oscillator which generates
, where and is the nominal power
frequency of the microgrid. Fig. 2 illustrates the angle waveform
deduced from the oscillator of which is usedfor the
to transformation of the mathematical model.
Based on the proposed control strategy, all DERunits are syn-
chronized by a global synchronization signal that is communi-
cated to the crystal oscillators of DER units [Fig. 1(b)] through
a GPS [27]. The global synchronization signal is communicated
at relatively large time intervals (e.g., once per second) to 1) pre-vent drift among local oscillators and 2) to initialize incoming
DER units. Crystal oscillators with high accuracies (e.g., an
error of to seconds per year) and rela-
tively low costs are currently available [28]. All LCs can be syn-
chronized with a high degree of reliability of a common timing
source of the GPS radio clock (e.g., with a theoretical accuracy
of higher than 1 s [29]). Although there are 610 satellites vis-
ible to each area at all times, one can rely on the accuracy of
crystal oscillators in case of the unavailability of the synchro-
nizing signal.
3) Local Controllers: The LC of each DER unit tracks the
setpoints specified by the PMS and rejects disturbances. Each
LC measures the voltage of thecorresponding PC bus, and trans-
forms the three-phase voltage to the frame based on the
Fig. 3. Block diagram of the th local control agent.
angle signal generated by its internal oscillator and syn-
chronized with the time-reference signal received from a GPS.The voltage magnitude and angle setpoints received from the
PMS are also transformed to the frame to generate
-based reference values (i.e., and
). The measured and reference values are
provided to the LC to determine the voltage components of
the terminal of the corresponding DER unit (i.e., and )
and generate the terminal voltage at the high-voltage
side of the transformer. is divided by the turn ratio
of the transformer and shifted by 30 to obtain corre-
sponding to the low-voltage side of the transformer.
is then fed to the PWM signal generator of the interface VSC
of the DER unit. It should be noted that although the realisticand theoretical turn ratio and phase shift of the transformer are
slightly different, the controller can compensate for the mis-
match. Fig. 3 illustrates a block diagram of where the mea-
sured and reference voltages are transformed to the frame of
reference. After performing the control action, the outputs are
transformed to the frame to generate the PWM switching
signals of the th interface VSC. Section IV describes the de-
sign steps of the controller based on the mathematical model of
the system. It should be noted that although the controllers are
designed based on RLC load models, other types of loads (e.g.,
motor loads) can be handled by the proposed controllers due to
their robustness.The control strategy is developed based on a decentralized
robust servomechanism approach to devise a decentralized con-
troller so that outputs of the system asymptotically track con-
stant reference inputs independent of 1) constant disturbances
which the microgrid is subjected to and 2) variations in the plant
parameters and gains of the control system [30]. The robustness
and the decentralized nature of the controller are highly desir-
able for a microgrid since:
a centralized controller which requires all inputs to be com-
municated to a common center is uneconomical due to the
complexity and cost of the required high-bandwidth com-
munication system;
a robust controller overcomes the uncertainty issues of the
plant structure and/or parameters.
-
7/27/2019 06239627
4/11
1846 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012
Fig. 4. Single-line diagram of the microgrid of Fig. 1 used to derive state-space equations.
The conditions for the existence of a centralized system so-lution based on the servomechanism problem [31] differ from
those of a decentralized system [30], [32]. In this case, a plant
often has a number of control agents and each control agent has
a number of local control inputs and outputs, and a separate and
distinct controller is applied to each control agent. In particular,
there exists a solution to the problem of stabilizing a plant based
on a decentralized control system if and only if the plant has
no unstable decentralized fixed modes (DFMs) and that certain
rank conditions of the plant data hold true [33].
The notion of robustness leads to the problem of constructing
a controller for a plant such that the resultant closed-loop system
satisfies a given robustness constraint (e.g., having a compa-rable so-called real stability radius for both open-loop and
closed-loop systems [34], [35]). Thiscan be done by a decentral-
ized controller design based on the approach of [30], [32], [36],
[37], subject to a robustness constraint. The constraints depend
on the problem under consideration. The principles of applica-
tion of this decentralized control scheme to conventional power
systems are provided in [38][42].
In this paper, the decentralized control strategy is applied to
a microgrid system which is generally more susceptible to os-
cillations caused by transients compared with the conventional
power system. To ensure robust performance of the controller,
the decentralized controller optimization is carried out subjectto a specified robustness constraint [35]. To solve the robust ser-
vomechanism problem and to achieve further improvements for
the microgrid performance, the normal optimal control perfor-
mance index , which is used for
obtaining optimal controllers to reject impulse disturbances, is
replaced with the performance index ,
where is a small weighting parameter. The resulting op-
timal controller is now an optimal servomechanism controller
[43]. The microgrid model, existence conditions of the con-
troller, design procedure, and the properties of the closed-loop
system (e.g., robustness, gain margin, and tolerance to time-
delay and unmodelled high-frequency effects) are discussed in
the following sections.
III. MATHEMATICAL MODEL OF THE MICROGRID
The proposed decentralized control is developed based on a
linearized model of the microgrid of Fig. 1(a) in a synchronously
rotating frame. Fig. 4 shows a one-line diagram of the micro-
grid. The controller is designed based on the fundamental fre-
quency component of the system of Fig. 4. Each DER unit is
represented by a three-phase controlled voltage source and a se-
ries RL branch. Each load is modeled by an equivalent parallel
RLC network (Fig. 4). Each distribution line is represented by
lumped series RL elements.
The microgrid of Fig. 4 is virtually partitioned into three sub-
systems. The mathematical model of Subsystem in the
frame is
(3)
where is a 3 1 vector. Assuming a three-wire system,
(3) is transformed to the synchronously rotating frame of
reference, as described in Section II.B.2 by [44]
(4)
where is the phase angle generated by the crystal oscillator
internal to DER . Based on (3) and (4), the mathematical model
of Subsystem in the frame is
(5)
-
7/27/2019 06239627
5/11
ETEMADI et al.: DECENTRALIZED ROBUST CONTROL STRATEGY FOR MULTI-DER MICROGRIDSPART I 1847
Similarly, the frame-based models of Subsystem and
Subsystem , are also developed and used to construct the
state-space model of the overall system
(6)
where
, and are the state
matrices as given in the Appendix.
The system (6) can alternatively be written as
(7)
where
and a decentralized controller
(8)
is to be found, where denotes the system error, de-
notes the input, and the controller transfer function in (8) is re-
stricted to being a proper transfer function .
IV. DECENTRALIZED CONTROLLER STRATEGY
This section elaborates on the properties of the open-loop
system, and characterizes its robust properties. Then, a pro-
posed robust decentralized servomechanism controller is de-
signed with a real stability radius constraint imposed [35]. Fi-
nally, a robust stability analysis and performance evaluation
of the closed-loop system is provided. The decentralized con-
troller will be found so that the real stability radius of the final
closed-loop system is approximately the same as the open-loop
system (i.e., the closed-loop system should have a robustness
index which is not worse than, say, 50% of the robustness index
of the open-loop system).
Throughout this paper, the norm is assumed to be the
spectral norm and a square real matrix is said to be asymptoti-
cally stable if the eigenvalues of the matrix are contained in the
open left-half part of the complex plane.
An extended LTI model of the microgrid based on (6) is given
by
(9)
TABLE IIOPEN-LOOP PLANT EIGENVALUES AND TRANSMISSION ZEROS
where is the state, is the input, is
the output, is an unmeasurable constant disturbance,
is the desired constant set point for the system, and
is the error in the system.
We impose the condition that the system must contain
control agents, each corresponding to one of the three virtual
subsystems of Fig. 4, and we rewrite (9) as
(10)
where and are the inputs and outputs of control agent , and
is the error in control agent . The open-loop
eigenvalues and transmission zeros [45] of (9), corresponding
to the system of Fig. 4, are given in Table II, which indicates
that the system is stable and minimum phase.
A. Controller Design Requirements for the Decentralized
Robust Servomechanism Problem (DRSP)
A decentralized controller for the plant (10) includes the fol-
lowing desired features.
1) The closed-loop system is asymptotically stable.
2) Steady-state asymptotic tracking and disturbance regula-
tion occurs for 1) all constant setpoints and
2) all constant disturbances (i.e.,
) for all constant disturbances and setpoints.
3) The controller is robust. That is, condition 2) should holdfor any perturbations of the plant model (10), including dy-
namic perturbations which do not destabilize the perturbed
closed-loop system.
4) The controller should be fast with smooth non-peaking
transients (e.g., it should respond to constant setpoints and
constant disturbance changes within about three cycles of
60 Hz).
5) Low interaction should occur among the output channels
of the control agents, and among the outputs contained
in each of the control agents, for tracking and regulation
[46].
6) It is required that the aforementioned conditions should be
satisfied for as wide as possible a range of the load param-
eters , and of each of the control agents.
-
7/27/2019 06239627
6/11
1848 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012
These conditions will be achieved by a decentralized controller
based on the solution of the DRSP [30], [32].
B. Existence Conditions
The following existence conditions for a solution to the
DRSP, so that conditions 1), 2), 3) from before all hold, are
obtained from [30]. Given plant (10), let
(11)
where
...
and let . and .
Theorem 1 [30]: Given the system (10), then there exists a
solution to the DRSP such that conditions 1), 2), and 3) all hold,
if and only if the following conditions are all satisfied:
1) The system (10) has no unstable decentralized fixed modes
(DFM).
2) , where is the number of outputs of the th con-
trol agent and is the numberof outputs of Subsystem
.
3) The system has no .
Remark: If , the condition 3) becomes
For the microgrid of Fig. 4,it can beverified that the existence
conditions of Theorem 1 are all satisfied. In particular, 1) plant
(10) has no decentralized fixed modes; 2) it has
; and 3) the rank of the matrix , given by
(6), is equal to .
Remark: In the plant model (9), the three load parameters
, and of each subsystem (Fig. 4) can vary and result in
structural uncertainty in the plants nominal model. It is also ob-
served in (9) that the load parameters affect neither the outputs
gain matrix nor the input control matrix . Therefore, only
matrix of (9) is affected by changing load parameters. We use
this observation to design a controller with the desirable robust-
ness properties.
The following analysis shows that condition 3) of Theorem
1 always holds true for the study microgrid regardless of its
numerical values. The determinant of the matrix is
given by where
Clearly, the determinant is always nonzero which implies
for any numerical value of microgrid
parameters and, thus, the third condition of Theorem 1 always
holds.
C. Real Stability Radius Constraints
To evaluate the robustness of a control scheme, the following
definition is used [35].
Given a real matrix which is asymptotically stable,
assume that is subject to a real perturbation ,
where and are given real matrices, and is a real matrix
of uncertain parameters. Then, it is desired to find ,
so that 1) is asymptotically stable for all real per-
turbations with the property that and 2) there
exists a perturbation with the property that ,
so that is unstable. In this case, rstab is called the
real stability radius of .
D. Controller Design Procedure
Given the plant (10) with , to solve the DRSP, it is
necessary [30] that the decentralized controller should include
the decentralized servo-compensator
(12)
where , together with a decentralized stabi-
lizing compensator, which will be assumed to have the structure
(13)
where
so that the controlled closed-loop system is described by
(14)
In this case, the controller parameters (13) are obtained by ap-
plying the optimal controller design method [47], [48] to min-
-
7/27/2019 06239627
7/11
ETEMADI et al.: DECENTRALIZED ROBUST CONTROL STRATEGY FOR MULTI-DER MICROGRIDSPART I 1849
imize the expected value of the performance index
given by
(15)
where is obtained by solving the Lyapunov matrix equa-
tion corresponding to
(16)
where , subject to the conditions that
1) the resultant closed-loop system (14) is asymptotically
stable;
2) the real stability radius of the closed-loop system
should be greater than or equal
to the real stability radius of the open-loop system, where
Substituting for and from (14) in (16) provides a closed-
form expression for (16)
(17)
where [47]. The control design problem
becomes, therefore, a constrained parameter optimization
problem whose solution yields the control parameters
, and .
The reason to impose the robust constraint above is that the
load parameters , may vary, but since they
affect only the matrix and not the , and
matrices of (10), then it is desired to minimize the effect of
load parameter perturbations by keeping the closed-loop system
robustness index, as measured by the real stability radius, as
close as possible to the open-loop robustness index. In this
case, the constraint imposed is such that the closed-loop robust-
ness index is not worse than the open-loop robustnessindex.
E. Obtained Decentralized Controller
On carrying out the optimization of the controller (13) as
measured by the performance index (15), the following decen-
tralized controller is obtained for the microgrid of Fig. 4
(18)
whose variables are defined in the equation at the bottom of the
next page.
F. Properties of the Closed-Loop System
A transfer function representation of the control agents of the
decentralized controller (18) is given by
where and are the outputs
and errors of controllers, and plants outputs, respectively. Poles
of the decentralized controller are 0 (repeated 6 times),
, and . The closed-loop eigenvalues of the plant,
using the decentralized controller (18), are listed in Table III.
G. Robustness Properties of the Closed-Loop System
The closed-loop system of plant (10) and controller (18) is
highly robust with respect to changes in the load parameters
of the microgrid. In particular assume
that in the open-loop system (9) the matrix is subject to un-certainty (e.g., due to changes in the load parameters and per-
turbations in the elements of the matrix ). Also assume that
, where is an unknown real perturbation ma-
trix, and where is an asymptotically stable matrix. The largest
perturbations for which the system remains stable are deter-
mined from the real stability radius of [35].
In this case, the open-loop perturbed plant
remains asymptotically stable for all real matrix pertur-
bations with if and only if , where
. This implies that the open-loop plant
remains asymptotically stable for any real pertur-
bation of size 0.15% or less.
Consider now the closed-loop system obtained by applying
the controller (18) to (10), and assume that the elements of the
-
7/27/2019 06239627
8/11
1850 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012
TABLE IIICLOSED-LOOP EIGENVALUES OF THE PLANT OBTAINED
USING THE DECENTRALIZED CONTROLLER(18)
controller are fixed and that the and el-
ements of the plant are fixed, but that due to load changes in
(and other perturbations), the elements
of are allowed to perturb. We also assume in the closed-loop
plant (14) that , where is an unknown per-
turbation matrix. In this case, we obtain from [35] that the per-
turbed closed-loop system remains asymptotically stable for all
Fig. 5. Bode plot of the closed-loop system for control agent No. 1 (associatedwith input and output ).
real matrix perturbations with if and only if
, where .
Thus, the stability robustness index of the closed-loop system
with respect to perturbations of the
matrix is larger than the open-loop system given by
, and so there is no deterioration in robustness of
-
7/27/2019 06239627
9/11
ETEMADI et al.: DECENTRALIZED ROBUST CONTROL STRATEGY FOR MULTI-DER MICROGRIDSPART I 1851
the closed-loop system compared to the open-loop system with
respect to perturbations of the elements of . A bode plot of the
closed-loop system is illustrated in Fig. 5. Fig. 5 shows that the
closed-loop transfer function from to of the first control
agent has a gain margin of 29.5 dB at the frequency of 372 Hz
(as denoted bya dotted line) and a phase margin of which
clearly highlights the robust stability of the closed-loop system.
H. Other Robust Measures of the Closed-Loop System
1) Input and Output Gain Margins: The following definition
which is an extension of the classical SISO gain margin to mul-
tivariable systems [49] is provided.Definition: Given a plant controlled
by a controller , assume that the
closed-loop system is asymptotically stable. Let be
replaced by a , where is a constant gain
matrix; then if the closed-loop system remains stable with
, the system has an output gain margin of .
Also let be replaced by ; then if the closed-loop
system remains stable with , the system is said
to have an input gain margin of of . The gain margin can
be calculated from the real stability radius of the system, and the
closed-loop system (10), (18) has output and input gain margins
of 1.38 and 1.28, respectively, which are quite satisfactory [50].
2) Input Time-Delay Tolerance: Often a system may have
time-delays which are ignored in the modeling of a system, and
it is important that the controlled system be robust to such un-
modelled effects. The following definition is used to describe
such a robust property [51].
Definition: Given a plant con-
trolled by the controller assume
that the closed-loop system is asymptotically stable, and let
be replaced by , corresponding to a time-delay of s.
Then, if there exists such that the closed-loop system re-
mains stable , the closed-loop system has an input
time-delay tolerance of [51]. In this case, the closed-loop
system (10), (18) has an input time-delay tolerance of
s, which is acceptable considering the switching frequencyof the VSCs.
3) Tolerance to Unmodelled High-Frequency Effects: It is
of interest to determine the extent that the closed-loop system is
tolerant to unmodelled high-frequency effects in the plant model
(9). This is captured by including the term in the model of
the plant as follows:
(19)
where are given in (9), and is a real per-
turbation matrix. In this case, on applying the same
controller (18) to plant (19), we obtain that the resul-
tant closed-loop system remains asymptotically stable
-
7/27/2019 06239627
10/11
1852 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012
if and only if , where
[35]. This implies that the per-
turbed closed-loop system remains asymptotically stable
for all perturbations in the gain matrix of (9) with the
property that % %
(where ), which satisfactorily meets the
requirements.
V. CONCLUSION
This paper presents a power-management and control
strategy for an autonomous, multi-DER microgrid. The envi-
sioned strategy provides: 1) power management of the overall
microgrid; 2) open-loop frequency control and synchroniza-
tion; and 3) a local, decentralized control for each DER unit.
The power-management system, based on classical power-flow
analysis, determines the terminal voltage setpoints for DER
units. The frequency of the system is controlled in an open-loop
manner by utilizing an internal crystal oscillator for each
DER unit that also generates the angle waveform requiredfor transformations. Synchronization of DER
units is achieved by exploiting a GPS-based time-reference
signal. The local control of each DER unit, which is the main
focus of this paper, is designed based on a new multivariable
decentralized robust servomechanism approach which utilizes
a linear state-space model of the microgrid. Various attributes
of the controller (i.e., the existence conditions, gain margins,
robustness, and tolerance to delays and high-frequency effects)
are analytically discussed, and the design procedures are out-
lined. The performance evaluation of the controller, based on
offline digital time-domain simulation studies and real-time
hardware-in-the-loop implementation, is presented in Part II of
this paper.
APPENDIX
SYSTEM EQUATIONS AND STATE MATRICES
The -matrix of (6), , is
, where , , and are de-
fined at the top of the previous page. Other entries of are
zero except for the following:
, and
. Nonzero entries of are
, and. Nonzero entries of , that is,
, and are unity.
REFERENCES
[1] R. H. Lasseter and P. Piagi, Microgrid: A conceptual solution, inProc. IEEE 35th Annu. Power Electron. Specialists Conf., Jun. 2004,vol. 6, pp. 42854290.
[2] J. M. Carrasco, L. G. Franquelo, J. T. Bialasiewicz, E. Galvan, R. C. P.Guisado, M. A. M. Prats, J. I. Leon, and N. Moreno-Alfonso, Power-electronic systems for the grid integrationof renewable energy sources:A survey, IEEE Trans. Ind. Electron., vol. 53, no. 4, pp. 10021016,Jun. 2006.
[3] M. T. Doyle, Reviewing the impacts of distributed generation on dis-
tribution system protection, in Proc. IEEE Power Eng. Soc. SummerMeeting, 2002, vol. 1, pp. 103105.
[4] P. C. D. K. N. Jenkins, R. Allan, and G. Strbac, Embedded Genera-tion. London, U.K.: Inst. Elect. Eng., 2000.
[5] R. A. Walling, R. Saint, R. C. Dugan, J. Burke, and L. A. Kojovic,Summary of distributed resources impacton powerdelivery systems,
IEEE Trans. Power Del., vol. 23, no. 3, pp. 16361644, Jul. 2008.[6] B. Kroposki, R. Lasseter, T. Ise, S. Morozumi, S. Papatlianassiou, and
N. Hatziargyriou, Making microgrids work, IEEE Power EnergyMag., vol. 6, no. 3, pp. 4053, May/Jun. 2008.
[7] F. Katiraei, M. R. Iravani, and P. W. Lehn, Micro-grid autonomousoperation during and subsequent to islanding process, IEEE Trans.
Power Del., vol. 20, no. 1, pp. 248257, Jan. 2005.[8] P. Piagi and R. H. Lasseter, Autonomous control of microgrids, pre-
sented at the IEEE Power Eng. Soc. Gen. Meeting, Montreal, QC,Canada, 2006.
[9] F. Katiraei and M. R. Iravani, Power management strategies for a mi-crogrid with multiple distributed generation units,IEEE Trans. PowerSyst., vol. 21, no. 4, pp. 18211831, Nov. 2006.
[10] M. C. Chandorkar, D. M. Divan, and R. Adapa, Control of parallelconnected inverters in standalone AC supply systems, IEEE Trans.
Ind. Appl., vol. 29, no. 1, pt. 1, pp. 136143, Jan./Feb. 1993.[11] H. Nikkhajoei and R. H. Lasseter, Distributed generation interface to
the CERTS microgrid, IEEE Trans. Power Del., vol. 24, no. 3, pp.15981608, Jul. 2009.
[12] S. Krishnamurthy and R. H. Lasseter, Consortium for Electric Re-liability Technology Solutions (CERTS), Control of wound field
synchronous machine gensets for operation in a CERTS microgrid,Madison, WI, DE-FC02-06CH11350, Mar. 2009.
[13] E. Barklund, N. Pogaku, M. Prodanovic, C. Hernandez-Aramburo, andT. C. Green, Energy management in autonomous microgrid using sta-bility-constrained droop control of inverters,IEEE Trans. Power Elec-tron., vol. 23, no. 5, pp. 23462352, Sep. 2008.
[14] J. C. Vasquez, J. M. Guerrero, A. Luna, P. Rodriguez, and R. Teodor-escu, Adaptive droop control applied to voltage-source inverters op-erating in grid-connected and islanded modes, IEEE Trans. Ind. Elec-tron., vol. 56, no. 10, pp. 40884096, Oct. 2009.
[15] Y. W. Li and C.-N. Kao, An accurate power control strategy forpower-electronics-interfaced distributed generation units operating ina low-voltage multibus microgrid, IEEE Trans. Power Electron., vol.24, no. 12, pp. 29772988, Dec. 2009.
[16] C. K. Sao and P. W. Lehn, Control and power management of con-verter fed microgrids, IEEE Trans. Power Syst., vol. 23, no. 3, pp.10881098, Aug. 2008.
[17] G. Diaz, C. Gonzalez-Moran, J. Gomez-Aleixandre, and A. Diez,Scheduling of droop coefficients for frequency and voltage regulationin isolated microgrids, IEEE Trans. Power Syst., vol. 25, no. 1, pp.489496, Feb. 2010.
[18] M. N. Marwali and A. Keyhani, Control of distributed generation sys-temsPart I: Voltages and currents control, IEEE Trans. Power Elec-tron., vol. 19, no. 6, pp. 15411550, Nov. 2004.
[19] M. N. Marwali, J.-W. Jung, and A. Keyhani, Control of distributedgeneration systemsPart II: Load sharing control, IEEE Trans.
Power Electron., vol. 19, no. 6, pp. 15511561, Nov. 2004.[20] J. M. Guerrero, L. G. de Vicuna, J. Matas, M. Castilla, and J. Miret,
A wireless controller to enhance dynamic performance of parallel in-verters in distributed generation systems, IEEE Trans. Power Elec-tron., vol. 19, no. 5, pp. 12051213, Sep. 2004.
[21] J. M. Guerrero, L. GarciadeVicuna, J. Matas, M. Castilla, and J. Miret,Output impedance design of parallel-connected ups inverters with
wireless load-sharing control, IEEE Trans. Ind. Electron., vol. 52,no. 4, pp. 11261135, Aug. 2005.
[22] M. C. Chandorkar and D. M. Divan, Decentralized operation of dis-tributed ups systems, inProc. Int Power Electron., Drives Energy Syst.
Ind. Growth Conf., 1996, vol. 1, pp. 565571.[23] N. Pogaku, M. Prodanovic, and T. C. Green, Modeling, analysis and
testing of autonomousoperation of an inverter-based microgrid,IEEETrans. Power Electron., vol. 22, no. 2, pp. 613625, Mar. 2007.
[24] J. M. Guerrero, L. Hang, and J. Uceda, Control of distributed uninter-ruptible power supply systems, IEEE Trans. Ind. Electron., vol. 55,no. 8, pp. 28452859, Aug. 2008.
[25] J. A. P. Lopes, C. L. Moreira, and A. G. Madureira, Defining controlstrategies for analysing microgrids islanded operation, in Proc. IEEE
Russia Power Tech., 2005, pp. 17.[26] H. Karimi, E. J. Davison, and R. Iravani, Multivariable servomech-
anism controller for autonomous operation of a distributed generation
unit: Design and performance evaluation, IEEE Trans. Power Syst.,vol. 25, no. 2, pp. 853865, May 2010.
-
7/27/2019 06239627
11/11
ETEMADI et al.: DECENTRALIZED ROBUST CONTROL STRATEGY FOR MULTI-DER MICROGRIDSPART I 1853
[27] IEEE Standard for Synchrophasors for Power Systems, IEEE StandardC37.118-2005, 2006, (Revision of IEEE Standard 1344-1995).
[28] J. Vig, Quartz crystal resonators and oscillators for frequencycontrol and timing applications: A tutorial, U.S. Army Commu-nications-Electronics Command, Fort Monmouth, NJ, Tech. Rep.SLCET-TR-88-1 (Rev. 8.4.2), 2000.
[29] A. Phadke and J. Thorp, , M. Pai, Ed., Sync hronized Ph asor Measure-ments and Their Applications, 1st ed. New York: Springer, 2008.
[30] E. J. Davison, The robust decentralized control of a general servo-mechanism problem, IEEE Trans. Autom. Control, vol. AC-21, no. 1,pp. 1424, Feb. 1976.
[31] E. J. Davison and A. Goldenberg, The robust control of a general ser-vomechanism problem: The servocompensator, Automatica, vol. 11,no. 5, pp. 461471, Sep. 1975.
[32] E. J. Davison, The robust decentralized servomechanism problemwith extra stabilizing control agents, IEEE Trans. Autom. Control,vol. AC-22, no. 2, pp. 256258, Apr. 1977.
[33] S.-H. Wang and E. J. Davison, On the stabilization of decentralizedcontrol systems, IEEE Trans. Autom. Control, vol. AC-18, no. 5, pp.473478, Oct. 1973.
[34] E. J. Davison, Robust control for industrial systems, in Proc. 25thIEEE Conf. Dec. Co ntrol, Dec. 1986, vol. 25, pp. 367374.
[35] Q. Li, B. Bernhardsson, A. Rantzer, E. J. Davison, P. M. Young, andJ. C. Doyle, A formula for computation of the real stability radius,
Automatica, vol. 31, no. 6, pp. 879890, Jun. 1995.
[36] E. J. Davison and U. Ozguner, Synthesis of the decentralized robustservomechanism problem using local models, IEEE Trans. Autom.Control, vol. AC27, no. 3, pp. 583600, Jun. 1982.
[37] E. J. Davison, Decentralizedrobust control of unknown systems usingtuning regulators, IEEE Trans. Autom. Control, vol. AC-23, no. 2, pp.276289, Apr. 1978.
[38] E. J. Davison, N. S. Rau, and F. V. Palmay, The optimal decentralizedcontrol of a power system consisting of a number of interconnectedsynchronous machines, Int. J. Control, vol. 18, no. 6, pp. 13131328,1973.
[39] E. J. Davison and N. Tripathi, The optimal decentralized control of alarge power system: Load and frequency control, IEEE Trans. Autom.Control, vol. AC-23, no. 2, pp. 312325, Apr. 1978.
[40] N. K. Tripathi and E. J. Davison, Automatic generation control of alarge multi-area interconnected power system by optimal decentralizedcontrol, in Large Scale Systems Engineering Applications, A. T. M.Singh, Ed. Amsterdam, the Netherlands: North-Holland, 1979, pp.472795.
[41] N. K. Tripathi and E. J. Davison, The automatic generation controlof a multiarea interconnected system using reduced order models, in
Proc. IFAC Symp. Comput. Appl. Large Scale Pow er Syst., New Delhi,India, Aug. 1618, 1979, pp. 117126.
[42] E. J. Davison and N. K. Tripathi, Decentralized tuning regulators:An application to solve the load and frequency control problem for alarge power system, in Proc. 18th IEEE Conf. Dec. Control IncludingSymp. Adaptive Process., Fort Lauderdale, FL, Dec. 1979, vol. 18, pp.879885.
[43] D. E. Davison and E. J. Davison, Optimal transient response shapingof the servomechanism problem, J. Optim. Theory Appl., vol. 115, no.3, pp. 491515, Dec. 2002.
[44] P. Krause, O. Wasynczuk, and S. Sudhoff, Analysis of Electric Ma-chinery and Drive Systems, 2nded. Hoboken, NJ:Wiley-IEEE Press,2002.
[45] E. J. Davison and S. Wang, Properties & calculation of transmis-sion zeros of linear multivariable systems, Automatica, vol. 10, pp.643658, 1974.
[46] E. J. Davison and B. Scherzinger, Perfect control of the robust servo-mechanism problem, IEEE Trans. Autom. Control, vol. AC-32, no. 8,pp. 689702, Nov. 1987.
[47] E. J. Davison and I. Ferguson, The design of controllers for the multi-variable robust servomechanism problem usingparameter optimizationmethods, IEEE Trans. Autom. Control, vol. AC-26, no. 1, pp. 93110,Feb. 1981.
[48] E. J. Davison and T. N. Chang, Decentralized controller design usingparameter optimization, Control: Theory Adv. Technol., Special IssueLarge Scale Complex Syst., vol. 2, no. 2, pp. 131154, Jun. 1986.
[49] E. Davison and B. Copeland, Gain margin and time lag toleranceconstraints applied to the stabilization problem and robust servomech-anism problem, IEEE Trans. Autom. Control, vol. AC-30, no. 3, pp.229239, Mar. 1985.
[50] E. J. Davison and T. N. Chang, The decentralized stabilization and ro-bust servomechanism problem subject to gain margin and time lag tol-erance constraints, in Proc. 4th IFAC Symp. Large Scale Syst., Zurich,Switzerland, Aug. 1986, pp. 236241.
[51] G. Hu and E. J. Davison, Real stability radius of LTI time-delay sys-tems, Syst. Control Lett., vol. 50, no. 3, pp. 209219, 2003.