    Single Shot and Work Tag

    On the ADVC Controller

    With the flexVUE Operator Interface

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    2/18

    Schneider Electric 2 < AUTHOR >

    Single Shot Mode

    Single Shot Mode is used to

    provide an appropriate protection

    curve when non-reclosingoperation is required.

    For example:

    When Auto Reclose is OFF

    When closing onto a fault.

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    3/18

    Schneider Electric 3 < AUTHOR >

    Single Shot Operation

    In Single Shot Mode the controllergoes directly to lockout after one

    trip and will not Auto-Reclose.

    Single Shot Mode is activatedwhen:

    -Auto-Reclose is turned off andWork Tag is not applied.

    -The circuit breaker is closed byoperator command irrespective ofthe state of Auto-Reclose.

    Single Shot is de-activated when:

    -Auto-Reclose is turned back on.

    -Work Tag is not active, and theSingle Shot Timer expires without a

    protection pickup occurring.

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    4/18

    Schneider Electric 4 < AUTHOR >

    Single Shot Timer

    This may be disabled by setting

    the Single Shot reset time to zero.

    When set to zero, auto-reclosing

    will always be enabled while Auto

    Reclose is ON.

    The Single Shot timer starts when

    the switchgear is manually closed

    and runs for the preset number ofseconds.

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    5/18

    Schneider Electric 5 < AUTHOR >

    Single Shot Timer Indication

    OPERATOR CONTROLS

    Lockout

    Single Shot Active

    LOCAL CONTROL ON

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    6/18

    Schneider Electric 6 < AUTHOR >

    Single Shot Timer initiated by Operator Close

    SS Timer

    CB Status

    t

    Single Shot

    Timer Expires

    OPEN CLOSED

    Single Shot

    Timer Setting

    Single Shot Mode Auto Reclose Mode

    Operator

    Close

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    7/18Schneider Electric 7 < AUTHOR >

    Protection Pickup during Single Shot Timing

    CB Status

    Pickup

    t

    SS Timer

    Operator

    Close

    OPEN OPEN

    Protection

    Pickup

    Single

    Shot

    Protection

    Trip

    CLOSED

    Time to Trip

    Single Shot

    Timer Setting

    Single Shot Mode

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    8/18Schneider Electric 8 < AUTHOR >

    Protection Reset during Single Shot Timing

    CB Status

    Pickup

    t

    SS Timer

    OPEN CLOSED

    Single Shot

    Timer Setting

    Protection

    Reset

    Single Shot Mode

    Single Shot

    Timer Expires

    Operator

    Close

    Protection

    Pickup

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    9/18Schneider Electric 9 < AUTHOR >

    Single Shot Protection Settings in WSOS

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    10/18Schneider Electric 10 < AUTHOR >

    GLOBAL CONTROL

    Global control

    (Display, Copy, Trips to

    lockout, Seq reset time,

    Max time, Auto restore,Auto reclose)

    Global pickup

    (Current & mult for Phase,

    Earth, SEF, NPS)

    Fault reset

    (FR time, Reset Threshold

    Mult for Phase, Earth and

    NPS, Start at RstThresh/Pickup)

    PROT TRIP SETTINGS

    Trip 1, 2, 3, 4

    (Reclose time, Protection &

    reset curve for P, E, SEF,

    NPS)Single Shot

    (SS reset time, Protection

    & reset curve for P, E, SEF,

    NPS)

    Work Tag

    (Protection & reset curve

    for P, E, SEF, NPS)

    Under Over Frequency(Under, Over, Normal

    Close, Low V inhibit,

    Bushing)

    Under Over Voltage

    (Under, Over, Config)

    Loss of Phase

    (On/Off/Alarm, Voltage,

    Timeout)

    PROTECTION CONTROL

    Cold Load Pickup

    (On/Off, Time, Multiplier)

    Inrush Restraint

    (On/Off, Time, Multiplier)

    High Current Lockout

    (On/Off, Current, Trip)

    Dead Lockout On/Off

    Live Load Blocking On/Off

    Sequence Control On/Off

    DIRECTIONAL ELEMENT

    Directional Blocking

    (Phase, Earth, SEF, NPS,

    System Voltage, High Vzps

    Alarm, balance)Directional Protection

    (Phase, Earth, SEF, NPS,

    System Voltage, High Vzps

    Alarm, balance)

    PROTECTION MENU

    PROT TRIP SETTINGS

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    11/18

    Schneider Electric 11 < AUTHOR >

    Single Shot - Summary

    An ACR will always go directly to

    Lockout following a protection trip

    if it is in Single Shot mode.

    Providing the Work Tag has not

    been applied, an ACR will be in

    Single Shot mode if:

    Auto Reclose is OFF

    An operator has closed onto afault. Providing:

    -The Single Shot Timer has not

    been set to zero.

    The timing of a trip that occurswhen the ACR is in Single Shot

    mode is determined by dedicated

    Single Shot settings for the

    particular type of fault.

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    12/18

    Schneider Electric 12 < AUTHOR >

    Work Tag

    Applying the Work Tag ensuresthat closing cannot take place at

    all, either by a local operator, aremote operator or automatically.

    The switchgear cannot closewhile the Work Tag is applied but

    Work Tag can be applied whenthe switchgear is closed providingnothing is inhibiting tripping.

    If a protection trip occurs while theWork Tag is applied, theswitchgear will always go tolockout even if Auto Reclose isON.

    The protection pickup and time to

    trip will be determined by theWork Tag protection settings andWork Tag Trip will be recorded in

    the Event Log.

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    13/18

    Schneider Electric 13 < AUTHOR >

    Selecting Work Tag ON in WSOS

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    14/18

    Schneider Electric 14 < AUTHOR >

    OPERATOR CONTROLS

    Local/Remote

    Autoreclose ON/OFF

    Earth SEF ON/OFF

    NPS Alarm/Trip/OFF

    Protection Group Active

    APGS Off/Auto

    Work Tag On/OFF

    Cold LoadBattery health test manual

    start

    Radio supply On/Off

    Low Gas Inhibit on/off

    Demand Period

    Sequence

    SWITCHGEAR STATUS

    Switchgear Info

    (Function, Type, Serial #,

    Rating, Software version)

    Switchgear Data

    (Pressure, Status,

    Operations Count, Contact

    Wear)

    MEASUREMENTS

    System Measurements

    (AVG Current, Voltage,

    Frequency, Power Factor,

    3 PH Power P and Q)

    Current

    (Phase, Earth Magnitude &

    Angle)

    Bushing Indication

    (Source and Load side

    Live/Dead)

    Maximum Demand Ind

    (Phase Max & time, Reset)

    INDICATIONS

    Flags

    (O/C, E/F, SEF, LOP, UOV,

    NPS, EXT, FRQ)

    Operations Count

    OPERATOR MENU

    OPERATOR CONTROLS

    OPERATOR CONTROLS

    Work Tag OFFWork Tag Applied

    1 Alerts Active

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    15/18

    Schneider Electric 15 < AUTHOR >

    Work Tag Protection Settings in WSOS

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    16/18

    Schneider Electric 16 < AUTHOR >

    GLOBAL CONTROL

    Global control

    (Display, Copy, Trips to

    lockout, Seq reset time,

    Max time, Auto restore,Auto reclose)

    Global pickup

    (Current & mult for Phase,

    Earth, SEF, NPS)

    Fault reset

    (FR time, Reset Threshold

    Mult for Phase, Earth and

    NPS, Start at RstThresh/Pickup)

    PROT TRIP SETTINGS

    Trip 1, 2, 3, 4

    (Reclose time, Protection &

    reset curve for P, E, SEF,

    NPS)Single Shot

    (SS reset time, Protection

    & reset curve for P, E, SEF,

    NPS)

    Work Tag

    (Protection & reset curve

    for P, E, SEF, NPS)

    Under Over Frequency(Under, Over, Normal

    Close, Low V inhibit,

    Bushing)

    Under Over Voltage

    (Under, Over, Config)

    Loss of Phase

    (On/Off/Alarm, Voltage,

    Timeout)

    PROTECTION CONTROL

    Cold Load Pickup

    (On/Off, Time, Multiplier)

    Inrush Restraint

    (On/Off, Time, Multiplier)

    High Current Lockout

    (On/Off, Current, Trip)

    Dead Lockout On/Off

    Live Load Blocking On/Off

    Sequence Control On/Off

    DIRECTIONAL ELEMENT

    Directional Blocking

    (Phase, Earth, SEF, NPS,

    System Voltage, High Vzps

    Alarm, balance)Directional Protection

    (Phase, Earth, SEF, NPS,

    System Voltage, High Vzps

    Alarm, balance)

    PROTECTION MENU

    PROT TRIP SETTINGS

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    17/18

    Schneider Electric 17 < AUTHOR >

    Work Tag and Controller Mode

    The controller is always in either

    Local or Remote mode.

    Only a local operator can

    apply/remove the Work Tag when

    the controller is in Local Mode.

    Only a remote operator can

    apply/remove the Work Tag when

    the controller is in Remote Mode.

    This means that for a local

    operator to remove the Work Tag

    which was applied by a remote

    operator, they must first put the

    controller into Local mode. OPERATOR CONTROLSWork Tag AppliedWORK TAG DENIED- CHANGE TO LOCALSELECT to continue

  • 7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag

    18/18

    Schneider Electric 18 < AUTHOR >

    Single Shot and Work Tag Modes

    Single Shot and Work Tag modeswill both cause an ACR to go

    directly to Lockout if a protectiontrip occurs.

    i.e.

    -They both prevent automatic

    reclosing.

    Work Tag mode prevents manualclosing as well.

    Single Shot and Work Tag tripsoccur according to their own

    respective settings.

    i.e.

    -In Single Shot mode the ACRwill trip according to the Single

    Shot settings.

    -In Work Tag mode the ACR willtrip according to the Work Tagsettings.

    An ACR will always be in WorkTag mode if the Work Tag isapplied regardless of the SingleShot status.