2008-05 www.huawei.com HUAWEI Confidential Security Level: Internal Use HUAWEI EMU By Jefferson Simarmata

description

TELELCOM

Transcript of 05 EMU Installation

Page 1: 05 EMU Installation

2008-05

www.huawei.com

HUAWEI Confidential

Security Level: Internal Use

HUAWEI EMU

By Jefferson Simarmata

Page 2: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 2

The connection between EMU and BTS

DB9

RJ45

MON1 UEIU (RJ45)

Page 3: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 3

Cable Power

Connect to SPARE1

Page 4: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 4

DIP Switch on DEMU

SW_RST

SW1 - SW8

SW9 – SW16

SW17 – SW24

SW25 – SW32

Page 5: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 5

Water Immersed Sensor

Temperature and Humidity Sensor

Smog

Door Sensor----> Move to switch 9 (SW9)

Special Alarm

Extend Alarm

Page 6: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 6

Special Alarm

Temp & Humi Smog

Water

Page 7: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 7

External Alarm

Page 8: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 8

How to find main fail, module rectifier fail and

Battery low voltage ??

Hold until alarm appear, check all cable output by

Multimeter, which cable short/open because this alarm give

label “Module rectifier fail”

Return it back to normal:

Turn off one MCB AC Main

Turn off one MCB AC Main, check all cable output by

Multimeter, which cable short/open because this alarm,

will be have 2 alarm appear:

1st “Main fail “

2nd “Module rectifier fail” (already give label before)

Check load current, go to

“configuration low load” and set low

load limit higher than load current,

check all cable output by Multimeter,

which cable short/open because this

alarm give label “Battery low

voltage”

Page 9: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 9

Configuration in LMT

Add DEMU board in subrack 2 slot 1

Page 10: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 10

Configure DEMU board attributes

- Gate Magnetism disabled because gate sensor move to Switch 9

- Water Immersed in low level because sensor output NO (Normaly Open)

Page 11: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 11

32 Switch can used

If sensor output NC (Normally Close), switch valid level High level

If sensor output NO (Normally Open), switch valid level Low level

Page 12: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 12

Alarm auto clear permit

Page 13: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 13

How to rename alarm ID in LMT base on alarm ID in IM2000 (1)

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=1, SW=OPEN, AID=65384, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=19, SW=OPEN, AID=65420, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=20, SW=OPEN, AID=65422, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=21, SW=OPEN, AID=65424, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=2, SW=OPEN, AID=65386, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=3, SW=OPEN, AID=65388, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=4, SW=OPEN, AID=65390, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=5, SW=OPEN, AID=65392, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=6, SW=OPEN, AID=65394, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=7, SW=OPEN, AID=65396, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=8, SW=OPEN, AID=65398, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=9, SW=OPEN, AID=65400, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=10, SW=OPEN, AID=65402, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=11, SW=OPEN, AID=65404, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=12, SW=OPEN, AID=65406, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=13, SW=OPEN, AID=65408, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=14, SW=OPEN, AID=65410, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=15, SW=OPEN, AID=65412, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=16, SW=OPEN, AID=65414, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=17, SW=OPEN, AID=65416, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=18, SW=OPEN, AID=65418, PT=BOOL;

Use MML and run this command;

Page 14: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 14

How to rename alarm ID in LMT base on alarm ID in IM2000 (2)

In LMT open “Alarm Maintenance”, click “Query Alarm Configuration”

Start Alarm ID from: 65384

Start Alarm ID from: 65424

Page 15: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 15

How to rename alarm ID in LMT base on alarm ID in IM2000 (3)

Right click an alarm name and then “Set Environment Alarm Configuration”

After Query Alarm Configuration

Page 16: 05 EMU Installation

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 16

How to rename alarm ID in LMT base on alarm ID in IM2000 (4)

Alarm name and alarm saverity after config;

Page 17: 05 EMU Installation

Thank You