02-Non-Dir

download 02-Non-Dir

of 58

Transcript of 02-Non-Dir

  • 8/8/2019 02-Non-Dir

    1/58

  • 8/8/2019 02-Non-Dir

    2/58

    Application of Non-Directional Overcurrentand Earthfault Protection

  • 8/8/2019 02-Non-Dir

    3/58

    Non-Directional Overcurrent and Earth

    Fault Protection

  • 8/8/2019 02-Non-Dir

    4/58

    Overcurrent ProtectionPurpose of Protection

    Detect abnormal conditions

    Isolate faulty part of the system

    Speed

    Fast operation to minimise damage and danger

    Discrimination

    Isolate only the faulty section

    Dependability / reliability

    Security / stability

    Cost of protection / against cost of potential hazards

  • 8/8/2019 02-Non-Dir

    5/58

  • 8/8/2019 02-Non-Dir

    6/58

    Fuses

  • 8/8/2019 02-Non-Dir

    7/58

    Overcurrent ProtectionFuses

    Simple

    Can provide very fast fault clearance

  • 8/8/2019 02-Non-Dir

    8/58

    Overcurrent ProtectionFuses - disadvantages

    Problematic co-ordination

    IFA approx 2 x IFB

    Limited sensitivity to earth faults

    Single phasing

    Fixed characteristic

    Need replacing following fault clearance

    Fuse A Fuse B

  • 8/8/2019 02-Non-Dir

    9/58

    Tripping Methods

  • 8/8/2019 02-Non-Dir

    10/58

    Overcurrent ProtectionDirect Acting AC Trip

    AC series trip

    common for electromechanical O/C relays

    51

    IF

    Trip Coil

  • 8/8/2019 02-Non-Dir

    11/58

    Overcurrent ProtectionDirect Acting AC Trip

    Capacitor discharge trip

    used with static relays where no secure DCsupply is available

    IF'

    SensitiveTripCoil

    IF

    51

    +

    -

  • 8/8/2019 02-Non-Dir

    12/58

    Overcurrent ProtectionDC Shunt Trip

    Requires secure DC auxiliary

    No trip if DC fails

    IF'IF

    DCBATTERY

    SHUNTTRIP COIL

    51

  • 8/8/2019 02-Non-Dir

    13/58

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    14/58

    Overcurrent ProtectionPrinciples

    Operating Speed

    Instantaneous Time delayed

    Discrimination

    Current setting

    Time setting

    Current and time

    Cost

    Generally cheapest form of protection relay

  • 8/8/2019 02-Non-Dir

    15/58

    IF1IF1IF2

    Overcurrent ProtectionInstantaneous Relays

    Current settings chosen so that relay closest tofault operates

    Problem

    Relies on there being a difference in fault levelbetween the two relay locations

    Cannot discriminate if IF1 = IF2

    50

    B

    50

    A

    IF1IF2

  • 8/8/2019 02-Non-Dir

    16/58

    Overcurrent ProtectionDefinite (Independent) Time Relays

    TOP

    TIME

    IS Applied Current

    (Relay Current Setting)

  • 8/8/2019 02-Non-Dir

    17/58

    Overcurrent ProtectionDefinite (Independent) Time Relays

    Operating time is independent of current

    Relay closest to fault has shortest operating time

    Problem

    Longest operating time is at the source wherefault level is highest

    51

    0.9 sec 0.5 sec

    51

  • 8/8/2019 02-Non-Dir

    18/58

    Overcurrent ProtectionIDMT

    Inverse Definite Minimum Time characteristic

    TIME

    Applied Current(Relay Current Setting)

    IS

  • 8/8/2019 02-Non-Dir

    19/58

    Overcurrent ProtectionDisc Type O/C Relays

    Current setting via plug bridge

    Time multiplier setting via discmovement

    Single characteristic

    Consider 2 ph & EF or 3 phplus additional EF relay

  • 8/8/2019 02-Non-Dir

    20/58

    Overcurrent ProtectionStatic Relay

    Electronic, multi characteristic

    Fine settings, wide range

    Integral instantaneous elements

    RESET

    A B C

    INST

    t

    I > Is

    INST

    t

    I > Is

    No

    Ph +

    In

    Vx V

    Hz

    0.05000000

    111

    0.050.050.10.20.30.4

    124810

    0.05000000

    111

    0.050.050.10.20.30.4

    124810

    0.10.10.20.40.40.40.8

    000

    0.02500000

    000000

    D

    LT1

    S1V1

    E1 I

    t

    sI =

    x IssI =

    x Is

    x t =

    x t =

    I =INST

    x sII =INST

    x sI

    MCGG

  • 8/8/2019 02-Non-Dir

    21/58

    Overcurrent ProtectionNumerical Relay

    Multiple characteristics and stages

    Current settings in primary or secondaryvalues

    Additional protection elements

    Current

    Time

    I>1

    I>2

    I>3

    I>4

  • 8/8/2019 02-Non-Dir

    22/58

  • 8/8/2019 02-Non-Dir

    23/58

    Overcurrent ProtectionCo-ordination Principle

    Relay closest to faultmust operate first

    Other relays must haveadequate additionaloperating time to

    prevent them operating Current setting chosen

    to allow FLC

    Consider worst caseconditions, operatingmodes and currentflows

    T

    IS1IS2MaximumFault

    Level

    I

    R2R1IF1

  • 8/8/2019 02-Non-Dir

    24/58

    Overcurrent ProtectionCo-ordination Example

    C AB

    0.01

    0.1

    1

    10

    Operatingtime(s)

    Current (A) FLB FLC FLD

    ED

    C

    B

    DE

  • 8/8/2019 02-Non-Dir

    25/58

    Overcurrent ProtectionIEC Characteristics

    SI t = 0.14(I0.02 -1)

    VI t = 13.5(I2 -1)

    EI t = 80(I2 -1)

    LTI t = 120(I - 1)

    Current (Multiples of Is)

    0.1

    1

    10

    100

    1000

    1 10010

    Operating

    Time(s)

    VI

    EI

    SI

    LTI

  • 8/8/2019 02-Non-Dir

    26/58

    Overcurrent ProtectionOperating Time Setting - Terms Used

    Relay operating times can becalculated using relay

    characteristic charts

    Published characteristcs aredrawn against a multiple of

    current setting or Plug SettingMultiplier

    Therefore characteristics can beused for any applicationregardless of actual relay currentsetting

    e.g at 10x setting (or PSM of 10)

    SI curve op time is 3s

    Current (Multiples of Is)

    0.1

    1

    10

    100

    1000

    1 10010

    Operat

    ingTime(s)

  • 8/8/2019 02-Non-Dir

    27/58

    Overcurrent ProtectionCurrent Setting

    Set just above full load current

    allow 10% tolerance Allow relay to reset if fault is cleared by

    downstream device

    consider pickup/drop off ratio (reset ratio)

    relay must fully reset with full load currentflowing

    PU/DO for static/numerical = 95%

    PU/DO for EM relay = 90%

    e.g for numerical relay, Is = 1.1 x IFL/0.95

  • 8/8/2019 02-Non-Dir

    28/58

    Overcurrent ProtectionCurrent Setting

    Current grading

    ensure that if upstream relay has started

    downstream relay has also started

    Set upstream device current setting greater thandownstream relay

    e.g. IsR1 = 1.1 x IsR2

    R1 R2 IF1

  • 8/8/2019 02-Non-Dir

    29/58

    Overcurrent ProtectionGrading Margin

    Operating time difference between two devices toensure that downstream device will clear fault beforeupstream device trips

    Must include

    breaker opening time

    allowance for errors

    relay overshoot time

    safety margin

    GRADINGMARGIN

  • 8/8/2019 02-Non-Dir

    30/58

    Overcurrent ProtectionGrading Margin - between relays

    Traditional

    breaker op time - 0.1 relay overshoot - 0.05

    allow. For errors - 0.15

    safety margin - 0.1

    Total 0.4s

    Calculate using formula

    R2R1

  • 8/8/2019 02-Non-Dir

    31/58

    Overcurrent ProtectionGrading Margin - between relays

    Formula

    t = (2Er + Ect) t/100 + tcb + to + ts

    Er = relay timing error

    Ect = CT measurement error

    t = op time of downstream relay

    tcb = CB interupting time

    to = relay overshoot time

    ts = safety margin

    Op time of Downstream Relay t = 0.5s

    0.375s margin for EM relay, oil CB

    0.24s margin for static relay, vacuum CB

  • 8/8/2019 02-Non-Dir

    32/58

    Overcurrent ProtectionGrading Margin - relay with fuse

    Grading Margin = 0.4Tf + 0.15s over whole characteristic

    Assume fuse minimum operating time = 0.01s

    Use EI or VI curve to grade with fuse

    Current setting of relay should be 3-4 x rating of fuse toensure co-ordination

  • 8/8/2019 02-Non-Dir

    33/58

    Overcurrent ProtectionGrading Margin - relay with upstream fuse

    1.175Tr + 0.1 + 0.1 = 0.6Tf

    or

    Tf

    = 2Tr

    + 0.33s

    Allowance for CTand relay error

    CB Safety margin Allowance for fuseerror (fast)

    Tf

    Tr

    IFMAX

  • 8/8/2019 02-Non-Dir

    34/58

    Overcurrent ProtectionTime Multiplier Setting

    Used to adjust the operatingtime of an inversecharacteristic

    Not a time setting but a

    multiplier

    Calculate TMS to givedesired operating time inaccordance with the gradingmargin

    Current (Multiples of Is)

    0.1

    1

    10

    100

    1 10010

    OperatingTime(s)

  • 8/8/2019 02-Non-Dir

    35/58

    Overcurrent ProtectionTime Multiplier Setting - Calculation

    Calculate relay operating time required, Treq

    consider grading margin

    fault level

    Calculate op time of inverse characteristic

    with TMS = 1, T1

    TMS = Treq /T1

    O P i

  • 8/8/2019 02-Non-Dir

    36/58

    Overcurrent ProtectionCo-ordination - Procedure

    Calculate required operating current

    Calculate required grading margin

    Calculate required operating time

    Select characteristic

    Calculate required TMS

    Draw characteristic, check grading over wholecurve

    Grading curves should be drawn to a commonvoltage base to aid comparison

    O t P t ti

  • 8/8/2019 02-Non-Dir

    37/58

    Overcurrent ProtectionCo-ordination Example

    Grade relay B with relay A

    Co-ordinate at max fault level seen by both relays =1400A

    Assume grading margin of 0.4s

    Is = 5 Amp; TMS = 0.05, SI

    IFMAX= 1400 Amp

    B A

    200/5 100/5

    Is = 5 Amp

    O t P t ti

  • 8/8/2019 02-Non-Dir

    38/58

    Overcurrent ProtectionCo-ordination Example

    Relay B is set to 200A primary, 5A secondary

    Relay A set to 100A If (1400A) = PSM of 14relay A OP time = t = 0.14 x TMS = 0.14 x 0.05 = 0.13(I0.02 -1) (140.02 -1)

    Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s

    Relay A uses SI curve so relay B should also use SI curve

    Is = 5 Amp; TMS = 0.05, SI

    I

    FMAX= 1400 Amp

    B A

    200/5 100/5

    Is = 5 Amp

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    39/58

    Overcurrent ProtectionCo-ordination Example

    Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s

    Relay A uses SI curve so relay B should also use SI curve

    Relay B set to 200A If (1400A) = PSM of 7relay B OP time TMS = 1 = 0.14 x TMS = 0.14 = 3.52s

    (I0.02 -1) (70.02 -1)

    Required TMS = Required Op time = 0.53 = 0.15Op time TMS=1 3.52

    Set relay B to 200A, TMS = 0.15, SI

    Is = 5 Amp; TMS = 0.05, SI

    IFMAX= 1400 Amp

    B A

    200/5 100/5

    Is = 5 Amp

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    40/58

    Overcurrent ProtectionLV Protection Co-ordination

    ZA2118B

    Relay 1Relay 2

    Relay 3Relay 4Fuse

    1

    2

    3

    4

    F

    350MVA4 4

    3 3

    2

    F

    11kV

    MCGG CB

    ACB CTZ61 (Open)CTZ61

    ACBMCCB

    27MVA

    20MVALoad

    Fuse

    2 x 1.5MVA11kV/433V

    5.1%

    K

    1

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    41/58

    Overcurrent ProtectionLV Protection Co-ordination

    ZA2119

    1000S

    100S

    10S

    1.0S

    0.1S

    0.01S

    0. 1kA 10kA 1000kA

    TX damage

    Veryinverse

    MC

    CB

    (cold

    )

    Relay 2

    Relay 3

    R

    elay4

    Fuse

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    42/58

    Overcurrent ProtectionLV Protection Co-ordination

    ZA2120C

    Relay 1Relay 2

    Relay 3Relay 4Fuse

    1

    2

    3

    4

    F

    350MVA4 4

    3 3

    2

    1

    F

    11kV

    KCGG 142 CB

    ACB (Open)KCEG 142

    ACBMCCB

    27MVA

    20MVALoad

    Fuse

    2 x 1.5MVA11kV/433V

    5.1%

    K

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    43/58

    Overcurrent ProtectionLV Protection Co-ordination

    ZA2121

    1000S

    100S

    10S

    1.0S

    0.1S

    0.01S

    0. 1kA 10kA 1000kA

    TX damage

    Long timeinverse

    MC

    CB

    (co

    ld)

    Relay 2

    Relay 3

    Relay 4

    Fuse

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    44/58

    ZA2135

    R3

    R2

    R1

    Block t >

    I > StartIF2

    IF1

    M (Transient backfeed ?)

    Graded

    protection

    Blockedprotection

    Overcurrent ProtectionBlocked OC Schemes

  • 8/8/2019 02-Non-Dir

    45/58

    Delta / Star Transformers

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    46/58

    A phase-phase fault on one

    side of transformerproduces 2-1-1 distributionon other side

    Use an overcurrent elementin each phase (cover the 2xphase)

    2 & EF relays can be usedprovided fault current > 4xsetting

    Iline

    0.866 If3

    Turns Ratio

    = 3 :1

    Idelta

    Overcurrent ProtectionTransformer Protection - 2-1-1 Fault Current

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    47/58

    Istar = E-/2Xt = 3 E-n/2Xt

    Istar = 0.866 E-n/Xt Istar = 0.866 If3 Idelta = Istar/3 = If3 /2 Iline = If3

    Iline

    0.866 If3

    Turns Ratio

    = 3 :1

    Idelta

    Overcurrent ProtectionTransformer Protection - 2-1-1 Fault Current

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    48/58

    Grade HV relay withrespect to 2-1-1 for

    - fault

    Not only at maxfault level

    51HV

    /

    51LV

    If386.6%If3

    Overcurrent ProtectionTransformer Protection - 2-1-1 Fault Current

  • 8/8/2019 02-Non-Dir

    49/58

    Use of High Sets

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    50/58

    Fast clearance of faults

    ensure good operation factor, If >> Is (5 x ?)

    Current setting must be co-ordinated to preventovertripping

    Used to provide fast tripping on HV side of transformers

    Used on feeders with Auto Reclose, prevents transientfaults becoming permanent

    AR ensures healthy feeders are re-energised

    Consider operation due to DC offset - transientoverreach

    Instantaneous Protection

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    51/58

    Set HV inst 130% IfLV

    Stable for inrush

    No operation for LV fault

    Fast operation for HVfault

    Reduces op times

    required of upstreamrelays

    HV2 LVHV1

    HV2

    LVTIME

    CURRENT

    HV1

    IF(LV) IF(HV)

    1.3IF(LV)

    Instantaneous OC on Transformer Feeders

  • 8/8/2019 02-Non-Dir

    52/58

    Earthfault Protection

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    53/58

    Earth fault current may be limited

    Sensitivity and speed requirements may not be met byovercurrent relays

    Use dedicated EF protection relays

    Connect to measure residual (zero sequence) current

    Can be set to values less than full load current

    Co-ordinate as for OC elements May not be possible to provide co-ordination with

    fuses

    Earth Fault Protection

    Overcurrent Protection

  • 8/8/2019 02-Non-Dir

    54/58

    Combined with OC relays

    E/F OC OC OC E/F OC OC

    Economise using 2x OCrelays

    Earth Fault Relay Connection - 3 Wire System

    Overcurrent ProtectionE th F lt R l C ti 4 Wi S t

  • 8/8/2019 02-Non-Dir

    55/58

    EF relay setting must begreater than normalneutral current

    Independent of neutralcurrent but must use 3 OCrelays for phase to neutralfaults

    E/F OC OC OC E/F OC OC OC

    Earth Fault Relay Connection - 4 Wire System

    Overcurrent ProtectionE th F lt R l C t S tti

  • 8/8/2019 02-Non-Dir

    56/58

    Solid earth

    30% Ifull loadadequate

    Resistance earth

    setting w.r.t earth fault

    level

    special considerationsfor impedance earthing

    - directional?

    Earth Fault Relays Current Setting

    Overcurrent ProtectionSensitive Earth Fault Relays

  • 8/8/2019 02-Non-Dir

    57/58

    Settings down to0.2% possible

    Isolated/high

    impedance earth networks For low settings cannot use residual connection, use

    dedicated CT

    Advisable to use core balance CT CT ratio related to earth fault current not line current

    Relays tuned to system frequency to reject 3rd

    harmonic

    B

    C

    E/F

    A

    Sensitive Earth Fault Relays

    Overcurrent ProtectionCore Balance CT Connections

  • 8/8/2019 02-Non-Dir

    58/58

    Need to take care with corebalance CT and armouredcables

    Sheath acts as earth return

    path

    Must account for earth currentpath in connections - insulatecable gland

    NO OPERATION OPERATION

    CABLEBOX

    CABLE GLAND

    CABLE GLAND/SHEATHEARTH CONNECTION

    E/F

    Core Balance CT Connections