EMERSON Process ManagementPower and Water Solutions
Copyrighted Material / Duplication Prohibited
Ovation Safety Instrumented System (SIS) OverviewOvation Safety Instrumented System (SIS) Overview
![Page 2: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/2.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 2
EMERSON Process ManagementPower and Water Solutions
ObjectiveObjectiveUpon completion of this module, you will be able to define
• Basic Process Control System
• Safety Instrumented System
• Safety Instrumented Function
• Ovation SIS hardware architecture
• Ovation SIS software architecture
• Ovation SIS capacities
• Ovation SIS building blocks
• Project procedures
![Page 3: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/3.jpg)
EMERSON Process ManagementPower and Water Solutions
Copyrighted Material / Duplication Prohibited
Part-1Safety Instrumented System (SIS) Basics
Part-1Safety Instrumented System (SIS) Basics
![Page 4: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/4.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 4
EMERSON Process ManagementPower and Water Solutions
Behavior of a processBehavior of a process
BPCS (HMI & Alarm Handling)
BPCS(Process Control)
SIS (SIFs)
Process
Valuenormal behaviour
Trip level alarmPreventPrevent
MitigateMitigate
Active protection
(example: Relief valve, rupture disk)
Passive protection(example: bund)
Emergency responsex x
Incident
operator
interventionprocess alarm
![Page 5: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/5.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 5
EMERSON Process ManagementPower and Water Solutions
Why BPCS?Why BPCS?
A Basic Process Control System (BPCS) compares the process values continuously against Operator set points and regulates final control element to maintain those set points.
Ovation Automation System is a BPCS.It regulates the process to maintain desired:
• Quality
• Rate of production
• Cost of production
![Page 6: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/6.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 6
EMERSON Process ManagementPower and Water Solutions
Why SIS?Why SIS?To Reduce RISK so as to:
• take the process to the Safe State at the shortest possible time (ESD)
• allow process to go ahead when per missives and interlocks are through (BMS)
• mitigate the risk if the incidence happens in the plant (FGS)
![Page 7: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/7.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 7
EMERSON Process ManagementPower and Water Solutions
A Safety Instrumented Function (SIF) is a combination of sensors, Logic Solver and final elements with a specified safety integrity level that detects an out of limit condition and brings the process to a functionally safe state.
SIF1, monitors a high pressure condition and closes the solenoid valve to stop catalyst flow to avoid a hazardous event.
Various “Functions”Various “Functions”
Control Function
Safety Function
Safety Instrumented Function
![Page 8: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/8.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 8
EMERSON Process ManagementPower and Water Solutions
TerminologyTerminology
BPCS: Basic Process Control System – A DCS. Intention is to control the QUALITY of the product by process control.
SIF: Safety Instrumented Function – A smallest building block of a SIS. Many SIFs make a SIS.
SIS: Safety Instrumented System – Intention is to reduce RISK to acceptable level by prevention and/or mitigation.
IL: Integrity Level – The level of risk reduction (Targeted / achieved) SIL: Safety Integrity Level EIL: Environmental Integrity Level CIL: Commercial Integrity Level
When more than one ILs are applicable, highest one is qualifying IL.
![Page 9: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/9.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 9
EMERSON Process ManagementPower and Water Solutions
Safety Instrumented Function (SIF)Safety Instrumented Function (SIF)
![Page 10: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/10.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 10
EMERSON Process ManagementPower and Water Solutions
Safety Instrumented Systems (SIS)Safety Instrumented Systems (SIS)A Safety Instrumented System (SIS) consists of sensors, Logic Solvers executing SIFs and final control elements. A SIS will typically execute multiple SIFs. The example below consists of a SIS executing SIF1 for high pressure and SIF2 for high temperature.
![Page 11: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/11.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 11
EMERSON Process ManagementPower and Water Solutions
Failure – The main concernFailure – The main concern• Why things fail?
− When Stress is more than strength, things fail!
• Why stress can be more than the strength?
− Natural calamities :: Random Failures
− Man made mistakes :: Systematic Failures
• Modes of failure
− Safe / Dangerous
− Detected / undetected
• Behavior of failures
− On demand
− Average
![Page 12: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/12.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 12
EMERSON Process ManagementPower and Water Solutions
Failure rates – a basic measureFailure rates – a basic measure• Failure record of the device (element of SIF): No of devices :: No. of hours of
operation :: No of devices failed. This will help to determine Failure rate of the device.
− Failures / Year ()
• is not a constant, but it changes with time. of a new system is minimal and as it ages, it rises exponentially. In other words, probability of failure increases with time.
• We can find an average of probability of failure over a period of time – Pavg.
• Failures are of two types – Safe and Dangerous.
• What matters is dangerous failures, which put the process in dangerous states.
• Also probability of dangerous failure matters the most when the system is required to do it’s intended job than it is idle or not in demand.
• Hence, the term Probability of failure in demand (average) of a SIF is of key importance in Safety engineering.
![Page 13: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/13.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 13
EMERSON Process ManagementPower and Water Solutions
Safety Integrity Level (SIL)Safety Integrity Level (SIL)Each SIF is designed to meet a Safety Integrity Level (SIL). A SIL is determined by a target risk reduction shown in the right column of the table below.
Various qualitative or quantitative methods can be used to calculate the target risk reduction which is a combination of likelihood and consequence of an event.
Safety Integrity Level (SIL)Target average Probability of
Failure on Demand (Demand Mode of Operation) Target Risk Reduction
4 > 10-5 to <10-4 >10,000 to <100,000
3 > 10-4 to <10-3 >1,000 to <10,000
2 > 10-3 to <10-2 >100 to <1,000
1 > 10-2 to <10-1 >10 to <100
![Page 14: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/14.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 14
EMERSON Process ManagementPower and Water Solutions
Safety Integrity Level (SIL)Safety Integrity Level (SIL)To ensure a SIF will perform on demand, the combination of the sensors, Logic Solver and final elements together must meet a Probability of Failure on Demand (PFD).
Assuming that a target risk reduction of SIL3 is required, then the failure rates of the instruments and Logic Solver combined must fall within the PFD of > 10-4 to <10-3.
Safety Integrity Level (SIL)Target average Probability of
Failure on Demand (Demand Mode of Operation) Target Risk Reduction
4 > 10-5 to <10-4 >10,000 to <100,000
3 > 10-4 to <10-3 >1,000 to <10,000
2 > 10-3 to <10-2 >100 to <1,000
1 > 10-2 to <10-1 >10 to <100
![Page 15: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/15.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 15
EMERSON Process ManagementPower and Water Solutions
SIF – SIS - SILSIF – SIS - SIL
Be particular about the usage of these acronyms!
• Many SIFs can make a SIS
• A SIF has a SIL but SIS does not have a SIL
• Customers ask for a SIL rated system – a misnomer
• SIL is not a constant!
![Page 16: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/16.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 16
EMERSON Process ManagementPower and Water Solutions
BPCS – SIS IntegrationBPCS – SIS IntegrationData is often passed between a BPCS and the SIS for coordination and interlocking. The BPCS and SIS are typically from different vendors which can make the integration effort extensive.
![Page 17: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/17.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 17
EMERSON Process ManagementPower and Water Solutions
OrientationOrientation
Knowing the basic requirements of the Safety Engineering, the system training is required by the following:
• The Design Group (End Customer, EPC, Safety consultant)
• The Safety Engineering Group (Vendor – Marketing, Proposals & Sales, Engineering)
• The Operations and Maintenance Group (O&M of End Customer)
Every phase of the Life Cycle can call upon in-depth study of the every subject, however further training is intended for the understanding of the Safety Instrumented System Hardware requirements and implementation requirements and techniques as required by the Operations and Maintenance Group of Marafiq at Yanbu-II.
![Page 18: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/18.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 18
EMERSON Process ManagementPower and Water Solutions
A Safety System componentsA Safety System componentsSafety Critical components:
• SIL rated Field Instruments and Equipment and interface devices.
• SIL rated Logic Solver(s)
• SIL rated interface devices and accessories
• Qualified hardware design
• Qualified programming tools and components
• Dedicated and certified communication channel
Non-safety critical components:
• Interface to DCS
• HMI and HMI builder tools
• Interface to third party systems
• Other supporting functions
![Page 19: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/19.jpg)
EMERSON Process ManagementPower and Water Solutions
Copyrighted Material / Duplication Prohibited
Part-2Ovation SIS SystemPart-2Ovation SIS System
![Page 20: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/20.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 20
EMERSON Process ManagementPower and Water Solutions
Emerson’s Control and Safety systemsEmerson’s Control and Safety systems
RS-3 DCS
DeltaV DCS
DeltaV SIS
WDPF DCS
Ovation DCS
Ovation SIS
Standalone DCS Standalone SIS ICSS
Third Party Safety System
![Page 21: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/21.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 21
EMERSON Process ManagementPower and Water Solutions
Ovation SIS ArchitectureOvation SIS Architecture
![Page 22: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/22.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 22
EMERSON Process ManagementPower and Water Solutions
Ovation SIS - HardwareOvation SIS - Hardware
Hardware components:
• Safety Logic Solvers
• Safety Data Server with Power Supply
• SIS Net repeater / SIS Net extender
• Power Supplies and diodes
• Interface devices – Safety Relay; Safety Barrier
• SIS LAN Switches
• SIS Routers
• Dedicated Ovation controller
![Page 23: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/23.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 23
EMERSON Process ManagementPower and Water Solutions
Ovation SIS – Safety Logic Solver(SLS)Ovation SIS – Safety Logic Solver(SLS)
Read Inputs Resolve and execute
Safety Logic Deliver Outputs Universal IOs – 16 per
SLS Redundant
configuration
![Page 24: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/24.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 24
EMERSON Process ManagementPower and Water Solutions
Ovation SIS – Safety Data Server (SDS)Ovation SIS – Safety Data Server (SDS)
Load the Logic Solvers
Communicate with the DCS system
Provide Diagnostic information
Execute non-critical safety functions like Alarm and Graphics tasks
![Page 25: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/25.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 25
EMERSON Process ManagementPower and Water Solutions
Ovation SIS – SISNet repeaterOvation SIS – SISNet repeater
Provide as a dedicated communication device between Logic solvers
Provide to extend the Safety network
Handle Safety critical communication protocol
![Page 26: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/26.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 26
EMERSON Process ManagementPower and Water Solutions
Ovation SIS – Capacity ChartOvation SIS – Capacity Chart
![Page 27: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/27.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 27
EMERSON Process ManagementPower and Water Solutions
SIS I/O – Hardwired IOsSIS I/O – Hardwired IOsEach Logic Solver has 16 I/O channels. The channels are universal
• Analog Inputs
• HART Analog Inputs
• HART Two-state Outputs
• Discrete Inputs
• Discrete Outputs
SLS 1508
SIF1
+--
Ch1…....…Ch16
SLS 1508
SIFX
SLS 1508
SIFX
Ch1…....Ch16
+--
![Page 28: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/28.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 28
EMERSON Process ManagementPower and Water Solutions
SIS I/O – Soft IOs - Secure ParametersSIS I/O – Soft IOs - Secure ParametersOvation Logic Solvers communicate with each other using peer to peer communications through secure parameters and secure parameter references. All Logic Solvers under the same controller can read any secure parameters on the Local Peer to Peer. Each Logic Solver has 16 High-density secure parameters that can be broadcast on the Local Peer to Peer.
SLS 1508
SIF1
SLS 1508
SIFX
Secure Parameter Secure Parameter Reference
Local Peer to Peer
![Page 29: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/29.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 29
EMERSON Process ManagementPower and Water Solutions
SISNet Repeaters and SISNetworkSISNet Repeaters and SISNetworkSISNet Repeaters provide communication between Logic Solvers that are attached to different controllers for Remote Peer to Peer communications. Only Boolean data can be transferred between SIS modules on different controllers and a total of sixteen Booleans can be broadcast by a Logic Solver.
SLS 1508 SLS 1508
SLS 1508 SLS 1508
![Page 30: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/30.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 30
EMERSON Process ManagementPower and Water Solutions
SIS LANSIS LANSIS LAN is configured of SIS Data Servers (SDSs). The Switch is uplinked to the router. Refer to typical SIS architecture shown on next page.
Components of SIS Network include
• Ovation Controller OCR1100
− For dedicated traffic and secondary functions
• SIS Data Server SDS
− Main communication gateway to Ovation LAN
• SIS Logic Solver SLS1508
• CISCO Switch IE3000
− Forms a SIS LAN
• CISCO Routers R2801
− Interface between Ovation and SISLAN
![Page 31: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/31.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 31
EMERSON Process ManagementPower and Water Solutions
Ovation SIS Network Architecture Ovation SIS Network Architecture
Note: All components are present in Redundant Configuration.
![Page 32: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/32.jpg)
EMERSON Process ManagementPower and Water Solutions
Copyrighted Material / Duplication Prohibited
Ovation ApplicationsOvation Applications
![Page 33: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/33.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 33
EMERSON Process ManagementPower and Water Solutions
Integrated Yet Separate…!Integrated Yet Separate…!
The BPCS and SIS systems share :
• Common Database
• Common Applications
• Common Network and devices for Non-safety Critical traffic
• Dedicated Network and devices for Safety Critical traffic
Next slides show the common environment already existing for the Ovation BPCS.
![Page 34: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/34.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 34
EMERSON Process ManagementPower and Water Solutions
Ovation SIS - ApplicationsOvation SIS - ApplicationsMain Applications:
Developer Studio
Control Builder
Other Ovation Applications
![Page 35: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/35.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 35
EMERSON Process ManagementPower and Water Solutions
SIS - ApplicationsSIS - Applications
![Page 36: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/36.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 36
EMERSON Process ManagementPower and Water Solutions
SIS - ApplicationsSIS - Applications
![Page 37: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/37.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 37
EMERSON Process ManagementPower and Water Solutions
SIS - ApplicationsSIS - Applications
![Page 38: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/38.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 38
EMERSON Process ManagementPower and Water Solutions
SIS - ApplicationsSIS - Applications
![Page 39: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/39.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 39
EMERSON Process ManagementPower and Water Solutions
Ovation SIS AlarmOvation SIS AlarmAll SIS signals can be identified using a special characterization called as “S “ in the alarm window. Please refer to the AY column in the alarm window as shown on next page. Pre-trip and trip alarms are notified by the same colors as in Ovation DCS. Ovation SIS has alarms for
• Sensor pre-trip thresholds
• Sensor trip thresholds
• Voter Alarm
• SOE Alarm
• Trip Alarm
![Page 40: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/40.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 40
EMERSON Process ManagementPower and Water Solutions
Ovation Alarm WindowOvation Alarm Window
![Page 41: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/41.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 41
EMERSON Process ManagementPower and Water Solutions
Ovation SIS User Rights Ovation SIS User Rights Specific user rights are allocated for SIS functions. Details below shows how the Ovation SIS roles are categorized for different users.
•Operator
SIS-Allow test Mode on-off
• SIS Engineer
SIS - Allow test Mode on-off
SIS – Enable control functions
SIS – Enable Tuning functions
SIS – Enable Enter Value
Note: Any change in the SIS control function in the future is not allowed and in case if there is any mandatory reason to make change, then it is expected from the person to follow the proper procedure/channel and inform the right person before making any change.
If the change is considered to be relevant then the right person will be allocated this task and the changes will be made. Changes in the logic, ranges, loading SLS, loading OCR is not permitted.
![Page 42: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/42.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 42
EMERSON Process ManagementPower and Water Solutions
Engineering / Operator RolesEngineering / Operator Roles
![Page 43: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/43.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 43
EMERSON Process ManagementPower and Water Solutions
Trends & Historical reviewsTrends & Historical reviewsAll SIS signals are available on the Historical alarms, trends, reviews and its past values can be viewed for easy analysis. Operator can view data in graphical form or in data form.
![Page 44: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/44.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 44
EMERSON Process ManagementPower and Water Solutions
Sequence of Events (SOE)Sequence of Events (SOE)SOE is a feature available on an Historian which shows timestamp for events that occur in the process.
Operator can make use of SOE to analyze the different causes which caused a trip along with the timestamps.
Further information given from the SOE can be used by Operational personnel to further investigate on a trip and to avoid such occurrence in the future.
SOE shows
• Date
• Time
• Point Name
• Description
• State (Normal/Trip)
![Page 45: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/45.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 45
EMERSON Process ManagementPower and Water Solutions
SOE WindowSOE Window
Fig. Shows a sample on how SOE are recorded onto the historian and is available on all Operator workstation which can be utilized for analysing past values and for other important reason. SOE together with SIS Master Trip First – Out will help maintenance people to easily judge the root cause of failure and to avoid such failure in the future.
![Page 46: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/46.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 46
EMERSON Process ManagementPower and Water Solutions
Graphics OverviewGraphics OverviewGraphics offers,
• First Out
• Thresholds, Voting logics
• Bypasses status
• Acknowledge alarms
• Trip Status for all protection signals
• Delays
• Conditions to Activate Protections
![Page 47: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/47.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 47
EMERSON Process ManagementPower and Water Solutions
Graphics WindowGraphics Window
![Page 48: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/48.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 48
EMERSON Process ManagementPower and Water Solutions
SIS DiagnosticsSIS DiagnosticsAlthough there is no Diagnostic application available for SIS, we usually show Diagnostics on Graphics which shows all SIS related components, their status and hardware errors.
Diagnostics page offers the following Information
• Logic Solver (SLS) CRC
• SIS Network Architecture
• Switch Diagnostics, Port Status, Power ON-OFF
• Ovation Controller (OCR) Status and Mode
• Logic Solver (SLS) Status (Active/Standby)
• Channel Configuration (Click on the resp. Logic Solver and a pop-up window appears showing the Channel Configuration for that SLS)
• SIS Data Server (SDS) Status – Active/Standby Mode
![Page 49: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/49.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 49
EMERSON Process ManagementPower and Water Solutions
Diagnostic WindowDiagnostic Window
![Page 50: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/50.jpg)
EMERSON Process ManagementPower and Water Solutions
Copyrighted Material / Duplication Prohibited
Ovation SIS ComponentsOvation SIS Components
![Page 51: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/51.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 51
EMERSON Process ManagementPower and Water Solutions
OW331_47.pdf
![Page 52: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/52.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 52
EMERSON Process ManagementPower and Water Solutions
SIS Function BlocksSIS Function BlocksIO Logic Functions Timing Special Connectors
LSAI LSAND LSBFI LSOFFD LSAVTR SIS connector algorithm table
LSDI LSNAND LSBFO LSOND LSDVTR GSECPARAMREF
LSDO LSNDE LSCMP LSTP LSCEM NONSECPARAM
LSDVC LSNOR LSLIM LSRET LSSEQ SECPARAM
LSNOT LSBDE LSSTD SECPARAMREF
LSOR LSALM LSCALC
LSPDE LSMID
LSRS
LSSR
LSXNOR
LSXOR
IO Logic Functions Timing Special Connectors
LSAI LSAND LSBFI LSOFFD LSAVTR SIS connector algorithm table
LSDI LSNAND LSBFO LSOND LSDVTR GSECPARAMREF
LSDO LSNDE LSCMP LSTP LSCEM NONSECPARAM
LSDVC LSNOR LSLIM LSRET LSSEQ SECPARAM
LSNOT LSBDE LSSTD SECPARAMREF
LSOR LSALM LSCALC
LSPDE LSMID
LSRS
LSSR
LSXNOR
LSXOR
IO Logic Functions Timing Special Connectors
LSAI LSAND LSBFI LSOFFD LSAVTR SIS connector algorithm table
LSDI LSNAND LSBFO LSOND LSDVTR GSECPARAMREF
LSDO LSNDE LSCMP LSTP LSCEM NONSECPARAM
LSDVC LSNOR LSLIM LSRET LSSEQ SECPARAM
LSNOT LSBDE LSSTD SECPARAMREF
LSOR LSALM LSCALC
LSPDE LSMID
LSRS
LSSR
LSXNOR
LSXOR
IO Logic Functions Timing Special Connectors
LSAI LSAND LSBFI LSOFFD LSAVTR SIS connector algorithm table
LSDI LSNAND LSBFO LSOND LSDVTR GSECPARAMREF
LSDO LSNDE LSCMP LSTP LSCEM NONSECPARAM
LSDVC LSNOR LSLIM LSRET LSSEQ SECPARAM
LSNOT LSBDE LSSTD SECPARAMREF
LSOR LSALM LSCALC
LSPDE LSMID
LSRS
LSSR
LSXNOR
LSXOR
IO Logic Functions Timing Special Connectors
LSAI LSAND LSBFI LSOFFD LSAVTR SIS connector algorithm table
LSDI LSNAND LSBFO LSOND LSDVTR GSECPARAMREF
LSDO LSNDE LSCMP LSTP LSCEM NONSECPARAM
LSDVC LSNOR LSLIM LSRET LSSEQ SECPARAM
LSNOT LSBDE LSSTD SECPARAMREF
LSOR LSALM LSCALC
LSPDE LSMID
LSRS
LSSR
LSXNOR
LSXOR
IO Logic Functions Timing Special Connectors
LSAI LSAND LSBFI LSOFFD LSAVTR SIS connector algorithm table
LSDI LSNAND LSBFO LSOND LSDVTR GSECPARAMREF
LSDO LSNDE LSCMP LSTP LSCEM NONSECPARAM
LSDVC LSNOR LSLIM LSRET LSSEQ SECPARAM
LSNOT LSBDE LSSTD SECPARAMREF
LSOR LSALM LSCALC
LSPDE LSMID
LSRS
LSSR
LSXNOR
LSXOR
![Page 53: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/53.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 53
EMERSON Process ManagementPower and Water Solutions
SIS Algorithm Palette - IOSIS Algorithm Palette - IO
• Analog Input – Accepts a single analog signal from an I/O channel and makes it available to other algorithms.
• Digital Valve Controller – Similar to a digital output algorithm, however it drives a two-state analog output channel connected to a Fisher Controls DVC6000. Contains parameters for partial stroke testing.
• Digital Input – Accepts a single digital input from a two-state field device and makes the processed physical input available to other algorithms.
• Digital Output – Drives an output channel to a solenoid or other final element using a 24VDC channel.
![Page 54: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/54.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 54
EMERSON Process ManagementPower and Water Solutions
SIS Algorithm Palette - LogicSIS Algorithm Palette - Logic• Calculation Logic – Evaluates an expression you define in
structured text including mathematical functions, logical operators, constants, and parameter references.
• Comparator – Compares a digital value with a compare value 1 and sets a LT, GT, EQ, or NEQ output. Additionally, a compare value 2 can be used to determine if the value is in range INRGE.
• Limit – Limits an input value between a high and low limit. A limit indicator signals whether the value was limited high or low.
• Middle Signal Select – Selects a middle value input from multiple analog inputs. When there is an even number of inputs, the average of the middle two are used as the output. As many as 16 inputs may be used.
![Page 55: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/55.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 55
EMERSON Process ManagementPower and Water Solutions
SIS Algorithm Palette - LogicSIS Algorithm Palette - Logic• Alarm – Performs alarm detection on an analog input you
specify.
• Bi-directional Edge Trigger – Generates a True(1) digital output when the digital input makes a False-to-True transition or a True-to-False transition.
• Boolean Fan In – Generates a digital output based on a binary weighted input (up to 16 inputs), and first out trapping.
• Boolean Fan Out – Decodes a binary weighted input into as many as 16 bits.
• Logical And – Performs an AND function on as many as 16 inputs.
![Page 56: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/56.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 56
EMERSON Process ManagementPower and Water Solutions
SIS Algorithm Palette - LogicSIS Algorithm Palette - Logic• Logical XOR – Performs an exclusive OR function on 2 digital
inputs.
• Neg-directional Edge Trigger – Generates a True (1) digital output when the digital input makes a negative (True-to-False) transition.
• Pos-directional Edge Trigger – Generates a True (1) digital output when the digital input makes a positive False-to-True transition.
• Reset Set Flip Flop – Generates a digital output value based on NOR logic of the reset and set inputs.
• Set Reset Flip Flop – Generates a digital output value based on NAND logic of the set and reset inputs.
![Page 57: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/57.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 57
EMERSON Process ManagementPower and Water Solutions
SIS Algorithm Palette - TimersSIS Algorithm Palette - Timers• Off Delay – Delays the transfer of a False(0) digital input
value to the output by a specified time.
• On Delay – Delays the transfer of a True(1) digital input value to the output by a specified time.
• Retentive Timer – Generates a True(1) digital output after the input has been True for a specified time period.
• Timed Pulse – Generates a True(1) digital output for a specified time duration when the input makes a positive (False-to-True) transition.
![Page 58: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/58.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 58
EMERSON Process ManagementPower and Water Solutions
SIS Algorithm Palette – Special FunctionsSIS Algorithm Palette – Special Functions• Analog Voter – Monitors as many as 16 Analog Inputs and
initiates a safety procedure if a predetermined number of inputs vote to trip.
• Digital Voter – Monitors as many as 16 digital Inputs and initiates a safety procedure if a predetermined number of inputs vote to trip.
• Cause Effect Matrix – Associated 16 inputs (Causes) with 16 outputs (Effects) to control one or more final elements.
• State Transition Diagram – Employs a state machine to determine the algorithm’s state based on the state of inputs and active transitions.
• Step Sequencer – Defines as many as 16 states, and as many as 16 output values may be defined in each state. May automatically increment and decrement through the states.
![Page 59: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/59.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 59
EMERSON Process ManagementPower and Water Solutions
SIS Algorithm Palette - ConnectorsSIS Algorithm Palette - Connectors• External Input Point – Reads data from outside the current sheet, but within
the same SIS Module.
• External Output Point – Writes data to a point, which can be referred by some other control sheet, within the same module
• Secparam – Sends Boolean data to other SIS modules.
• Secparamref – Receives Boolean data from other SIS modules from within the same SIS Node.
• Gsecparamref - Receives Boolean data from other SIS modules from an external SIS Node.
• Nonsecparam - Receives non safety critical boolean data from other SIS modules or BPCS control sheets/tasks.
![Page 60: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/60.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 60
EMERSON Process ManagementPower and Water Solutions
SIS TreeSIS TreeDatabase Point Database
Network Analog Points
Unit Digital Points
Drop Module Points
Device Node Points
SISLAN SDS
SDS SLS
Control Module
Control Sheet
Secure Parameters
![Page 61: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/61.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 61
EMERSON Process ManagementPower and Water Solutions
Most generic SIS Functions - ESDMost generic SIS Functions - ESD
Emergency Shutdown Function:
1. Acquisition and conditioning
2. Trip Voting
3. Trip resolution
4. Drive Output
![Page 62: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/62.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 62
EMERSON Process ManagementPower and Water Solutions
Most generic SIS Functions - ESDMost generic SIS Functions - ESD
AI
AI
AI
DI
DI
SPR
NSPR
AVTR
DVTR
CEM DO
DVC
RST
SP
E1 E2 E3
C1 X
C2 X
C3 X X X
C4 X
Logic 1 = Normal
![Page 63: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/63.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 63
EMERSON Process ManagementPower and Water Solutions
Most generic SIS Functions - BMSMost generic SIS Functions - BMS
1
Tripped
2
Ready
Reset
3
Air On
Fan On FB
Fan Off FB
4
Prepare Purging
Start PB
5 Purging
Purge Conditions FB
6 Prepare Ignition
Purge Time Over
7
Ignition
Ignition Conditions FB
8
Post Ignition
Safety Time Over
9
Burner On
Post Ignition Time Over
10Close Valves
Stop PB
Stop PBStop PBStop PBStop PBStop PB
11Open Vent
Valves Close FB
Vent Open FB
From
all States
Trip
![Page 64: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/64.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 64
EMERSON Process ManagementPower and Water Solutions
Ovation SIS – Sequence executionOvation SIS – Sequence execution
An Excel template is available to support such an approach and to document the functional requirements.
State Transition Diagram
State Transition Diagram
OutputsOutputs
TripsTrips
TransitionsTransitions
![Page 65: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/65.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 65
EMERSON Process ManagementPower and Water Solutions
Secure Write MechanismSecure Write MechanismA Secure Write Mechanism, TUV-certified software, allows you to change the value of a writeable parameter in a Logic Solver. This significantly reduces the risk of an unintentional change to the Logic Solver by the following means:
• Does not accept the type of change message that is sent to a Control Module.
• Only accepts a new pair of change messages, command and confirm
• Only accepts configuration changes if the SLS 1508 is unlocked
• Integrity checks include, checking for error corruption and a two minute timeout between the command and confirm in all applications except Ovation Operate Run where the timeout is 1 minute.
Secure Write Mechanism
SLS 1508
Bypass
![Page 66: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/66.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 66
EMERSON Process ManagementPower and Water Solutions
Standalone SIS project implementation - OutlineStandalone SIS project implementation - Outline
• Separate SIS Database at Engineering Centre
• Database server is created and Ovation SIS installed with licenses
• For multiple units power project, it is convenient to work on the single unit and then multiply
• Create the SIS tree and organize the devices around the database server
• Implement the One-burner-One-Unit project
• Test and verify the functions along with the Graphics
• Integrate with BPCS
• Multiply for other burners and other units
• FAT
• Commissioning and startup
• SAT
![Page 67: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/67.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 67
EMERSON Process ManagementPower and Water Solutions
Steps to construct a Safety ProjectSteps to construct a Safety Project• Receive Customer Inputs
• Compare IO and Logic and clear the queries
• Freeze the IO List and Logic to 90%
• Create the Database server
• Estimate Logic solvers and SDS – Go for HW design – Freeze BOM
• IO Allocation to SIFs
• Conceptual Design – HW and SW – Customer approval
• Start HW Detail Design
• Start Prototype making for Control modules, Graphics for typical unit
• Complete Implementation of modules and Graphics
• Generate Internal test plans
• Generate FAT Plans – Get Customer approvals
• Internal testing and verification
• Integration with BPCS and verification
![Page 68: 01_OV-235-01-Overview](https://reader030.fdocuments.in/reader030/viewer/2022032704/55cf8f2a550346703b998650/html5/thumbnails/68.jpg)
Course OV 236 – Rev 2 – 01/02/2010 Copyrighted Material / Duplication Prohibited
1 - 68
EMERSON Process ManagementPower and Water Solutions
SummarySummary• Basic Process Control System
• Safety Instrumented System
• Safety Instrumented Function
• Ovation SIS hardware architecture
• Ovation SIS software architecture
• Ovation SIS capacities
• Ovation SIS building blocks
• Project procedures