01 R134a DX Screw Chiller 50Hz
-
Upload
diem-cong-viet -
Category
Documents
-
view
216 -
download
5
description
Transcript of 01 R134a DX Screw Chiller 50Hz
LSBLG/MC IOMM
Installation Operation Maintenance Manual
Water-Cooled Screw Chiller
LSBLG /MC Series
Version:200901a
★Please read this manual carefully before installing and Operating your chiller★
LSBLG/MC IOMM
CONTENTS 1. General
1.1 Brief Introduction
1.2 Nomenclature
1.3 Storage
1.4 Main Parts
1.4.1 The Compressor
1.4.2 The Condenser
1.4.3 The Evaporator
1.4.4 The Oil Separator
1.4.5 The Throttle
1.4.6 The Capacity Control
1.4.7 The Refrigerant
1.4.8 The Lubricant
1.4.9 The Oil Filter
1.4.10 The Refrigerant Filter
2. Safety Instructions 2.1 Installation Safety Instructions
2.2 Maintenance Safety Instructions
2.3 Repairing Safety Instructions
2.4 Electrical Safety Instructions
3. Installation 3.1 Installation Environment
3.2 Acceptance
3.3 Rigging
3.4 Installation
3.4.1 Installation Foundation
3.4.2 Fixation of Unit
3.4.3 Service Space
3.5 Installation of Other System
3.5.1 Water System
3.5.2 Electrical System
4. Running 4.1 Running Range
4.2 Water Flow Rate Range
4.3 Specifications
4.4 Check before Start
4.4.1 Electrical Part
4.4.2 Water System
4.4.3 The Unit
4.5 Start the Unit
4.5.1 Normal Start and Stop
4.5.2 Emergency Stop
4.5.3 Running under Low Ambient Temperature
4.6 PLC Operation
4.6.1 Structure of PLC Control System
4.6.2 Welcome Page
4.6.3 Main Page
4.6.4 System Settings
4.6.5 Parameter Check
4.6.6 Warning and Protection Page
4.6.7 Trend Curves Page
4.6.8 Data Report Page
LSBLG/MC IOMM
5. Maintenance 5.1 Routine Check
5.2 Charge the Lubricant
5.3 Charge the Refrigerant Gas
5.4 Change the Core of Dry Filter
5.5 Maintenance of Bearing of the Compressor
5.6 Check the Rotors of the Compressor
5.7 Check the Heat Exchange Tubes
5.8 Electrical Control Cabinet
5.9 Seasonal Maintenance
5.9.1 Stop in Winter
5.9.2 Start in Summer
5.10 Anti-freezing Protection in Low Ambient Temperature
5.10.1 Anti-freezing Protection of Condenser
5.10.2 Anti-freezing Protection of Evaporator
5.11 Common Faulty Diagnosis
5.11.1 Reset of Warning
5.11.2 Troubleshooting
5.12 Clean Procedure
5.12.1 Relation between water quality, scale and degree of corrosivity
5.12.2 Wash the Shell and Tube Heat Exchange
6. Appendix
6.1 Outline Dimension Diagram
6.2 Refrigeration Circuit Diagram
6.3 Electrical Circuit Diagram 6.4 Pressure Enthalpy Chart of R134a
Midea® reserves the right to improve the product and technology without prior notice.
LSBLG/MC IOMM
1.General
1.1 Brief Introduction
Midea water cooled LSBLG/MCF series chillers equipped with 1 or 2 twin screw
compressors using the latest 5-6 asymmetry dentiform. They are manufactured to satisfy
the requirements of the consultant and the end user. Midea LSBLG/MCF series units
minimized energy costs while maximizing the refrigeration capacities. Once again Midea
has developed a line of chillers unsurpassed in performance and quality that will meet the
most stringent requirement of comfort cooling, plastic, electroplating, food processing and
chemical industrial, etc.
1.2 Nomenclature
LS B LG 115 /M C
Design Code
Norminal Capacity (kW)
LG: Screw Compressor
B: Semi-hermetic Compressor
Water Chiller
Refrigerant Code: R134a
1.3 Storage Please follow the rules if the chiller has to be put aside for a long time before it is installed:
Put the unit indoor, and the ambient temperature should be no more than 50℃;
Put the unit far away from any heat source;
Put the unit where the water doesn’t go into easily;
Never put the unit under the direct sunlight.
1.4 Main Parts
LSBLG /MC screw water chiller consist of four main parts which are compressor,
condenser, throttle and evaporator. There are single compressor and dual-compressor
units which capacity is from 115kW to 1300kW.
1.4.1 The Compressor
The LSBLG/MC series screw chiller equipped with the 3rd generation industrial compressor that has the latest advanced 5-6 asymmetry dentiform semi-hermetic screw rotors. The
LSBLG/MC IOMM
lubricant is supplied automatically by pressure difference inside the compressor. It is unnecessary to add an extra lubricant pump. The bearing of the compressor is from SKF, Sweden, the long lifespan of which ensures screw-type main unit to run continuously more than 30,000 hours.
Fig 1.1 Rotors Fig 1.2 The Compressor
Working Principle
Suction While the rotors rotating, the refrigerant is sucked inside from the lower position of the rotors.
Fig 1.3 Suction Process
Compression
Since the rotors running, the room between the gears (V room) reduces because of the mating, which makes the gas compressed and the pressure increased.
Fig1.4 Compression Process
Discharge The V room connects to the discharge port, which start the discharge process. This process continues until the gas gets out completely.
LSBLG/MC IOMM
Fig 1.5 Discharge Process
1.4.2 The Condenser
High quality shell is made of rolled steel plate. It is covered with anti-rust paint which can maintain at least 20 years after shot peening treatment.
High precise temperature difference makes the COP increased rapidly. It can be designed to suitable for different fouling factors. There is a reserved 15% heat
exchange capacity design which can make the condenser provide enough capacity even
the cooling water temperature reaches 32℃ or there is fouling inside the water system.
High efficient sub-cooler inside the condenser makes the liquid refrigerant cooled again to increase the cooling efficiency.
Fig 1.6 Internal Structure of the Condenser
1.4.3 The Evaporator
LSBLG/MC series screw chiller is equipped with high efficiency shell and tube evaporator that are constructed by seamless steel tube with anti-corrosive treatment. The evaporator is a direct expansion type with refrigerant inside the copper tubes and water on the outside. The copper tubes are roll expanded into carbon steel tube plates. Constructed with seamless integrally finned copper, the water pipe system makes the evaporator attain optimal heat exchange efficient. Two return passages of water flow and the straight water pipe is easy for cleaning and maintenance. Both end covers are made of iron and attached with protection valve and snuffle valve. Also they are removable, which makes it available for altering water piping arrangement. The design working pressure for both evaporator and condenser are 1.0MPa, higher pressure demand can be customized.
LSBLG/MC IOMM
Fig 1.7 Internal Structure of the evaporator
1.4.4 The Oil Separator There is a high efficient oil separator inside the compressor. The oil is supplied by the oil pressure difference so that there is no oil pump, which makes sure the unit can work under the worst conditions.
1.4.5 The Throttle The throttle is a thermal expansion valve or an electronic expansion valve according to different cooling capacity. It can control the super heat of suction gas precisely to make sure the unit works efficiently under full load and part load conditions.
1.4.6 The Capacity Control The control system will change the output of the compressor with high precise valves when the cooling load changes. The output control can be 4-step (25%, 50%, 75% and 100%) or
stepless. (NOTE: This part is only suitable for HANBELL
® compressor. If another brand compressor is in use,
please refer to the instructions of the compressor.)
Fig 1.8 The Compressor Structure
Chilled water in
Liquid in
Gas out
Chilled water out
LSBLG/MC IOMM
Item Part Name Item Part Name Item Part Name
1 Suction filter 7 Discharge port bearing 13 Capillary
2 Refrigerant gas 8 Discharge pipe 14 Electronic valve (start) SV1
3 Motor 9 Refrigerant gas (with oil) 15 Electronic valve (for 50%) SV3
4 Oil filter 10 Lubricant oil 16 Electronic valve (for 75%) SV3
5 Suction port bearing 11 Filter of oil separator 17 Slider
6 Rotors of compressor 12 Refrigerant gas
Table 1.1 Part Name of the Compressor
Valve
Load SV1 SV2 SV3
100% off off Off
75% off on off
50% off off On
25% (Start) on off off
Table 1.2 Working Schedule of the Electronic Valves of 4-step Output Control
1.4.7 The Refrigerant
The LSBLG/MC series screw chiller uses the R134a Environmentally friendly refrigerant.
1.4.8 The Lubricant Oil The LSBLG/MC series screw chiller uses the special compressor lubricant supplied by
HABELL® which brand is: HBR-B04
(NOTE: This part is only suitable for HANBELL® compressor. If another brand compressor is in use,
please refer to the instructions of the compressor.)
1.4.9 Oil Separator The oil separator is inside the compressor.
1.4.10 Refrigerant Filter There is a filter installed inside the suction port the compressor for preventing the impurities in the circuit pipe to go inside the compressor.
LSBLG/MC IOMM
2. Safety Instructions Before the unit start, all stuffs who responses for the commissioning and maintenance should read the instructions very carefully to make clear about all the working specifications. The design of the unit includes the convenience of the installation, start, running and maintenance. As long as running under the design conditions, the unit can provide the safe and reliable service. If some special factors are ignored such as running pressure, electrical components, voltage and installation position, the operation and maintenance of the unit will be very dangerous. This manual is arranged according with the normal operation sequence of the unit. During all the operations, the operator should read, understand and obey correlative instructions in the manual and the safety stickers on the unit or components.
2.1 Installation Safety Instructions The installation should be carried out following the installation instructions. When arrives in the site, the unit should be checked carefully if there is any damage
especially the components and the pipes of refrigerant circuit, or if there is some part missing according to the packing list. Once the damage or something missing is found, please contact the transportation company for compensation.
If the unit is not in right installation position, never remove the package or the base. Move the unit at the right position and direction and rig the unit at only the signed rigging holes.
When rig the unit, please choose suitable cables and rig it according to the rigging drawings and instructions.
Before the unit start, please check the voltage and frequency if they are suitable for the unit normal running.
If any of above rules is broken, damage and personal injury may occur.
2.2 Maintenance Safety Instructions
NEVER cover or shut off any of the safety device such as the valves on water system and the refrigerant system. Before the unit start, please make sure the valves installed correctly.
Be sure the refrigerant won’t get out from the safety valves and keep the installation room ventilated well.
High concentration of refrigerant vapor is harmful to the human body will lead to arrhythmia, unconsciousness or even death. It is heavier than air, and will reduce the amount of oxygen inhalation of human, and also irritate the eyes and the skin.
The operation of the electrical parts and refrigeration parts should be carried out by authorized people who know well about the installation of the unit.
All welding should be carried out by qualified professionals. Check the leakage termly. Once a leakage is found, it should be fixed immediately. Never maintain the unit when it is electrified. When fix the electrical parts, at first cut off
the main power supply. Important: All protection devices should be checked at least once a year. If the working conditions are
worse, this frequency should be increased.
2.3 Repairing Safety Instructions
To avoid the damage to the unit and human hazard, all installed parts should be maintained by special stuffs. Once there is a faulty or leakage, the unit should be fixed immediately by authorized technical persons. After maintenance, all the safety devices
LSBLG/MC IOMM
should be checked. When a leakage occurs, all the refrigerant should be got out. After the leakage point is
fixed, fill the system with enough R134a refrigerant which is marked on the rating label. If the leakage occurs on some parts on the unit which can be isolated, it is no need to get all the refrigerant out.
Before fill the refrigerant, make sure the type is R134a. Otherwise the unit would be damaged or even destroyed.
If charge the lubricant while maintenance, please make sure the model of it is the correct one mentioned in the specifications.
DO NOT try to make the oxygen into the pipe system of the unit because there will be drastic reactions between the oxygen and the grease inside the pipes.
DO NOT make the unit run more than its maximum working pressure. DO NOT check leakage with air but refrigerant gas or dry nitrogen. NEVER cut any refrigeration pipes or components with electrical welding cutting or flame
cutting unless there is no refrigerant gas or liquid. There will be poison gas if the refrigerant contact with the flame. So there should be some
protection devices such as fire extinguishers for accident. To avoid the refrigerant liquid touch on skin or inside the eyes, please be sure to wear
protection glasses. Use soap and water to get rid of the refrigerant on the skin. If the refrigerant goes into the eyes, wash the eyes again and again, and go to the hospital in time.
DO NOT heat the vessel with flame or steam, or there will be dangerous extra high pressure. If the refrigerant has to be heated, you can only use warm water to heat the vessel.
When the unit is running or under some pressure, NEVER try to remove any seal cover or connector. Any time you want to operate some valves which can make the unit inside connect to the atmosphere, be sure there is no pressure inside the unit.
When some rust, dust, dirties or fouling is found inside the valves, or mechanical damage to the valves, DO NOT try to fix them or re-calibrate them. You should change them if possible.
NOTE: DO NOT walk on the pipes of the unit to avoid refrigerant leakage caused by damage pipes. DO NOT climb the unit. If you have to, please use safety flat or falsework. Be careful when rig some parts with a mechanical crane. Even a light part, there may be some
risk of losing balance or sliding down. If some parts need to be changed, please contact the dealer or Midea company for help. There
is no spare part as accessory if no special comment. Before install the filter and flow switch on the water system, please shut off the inlet and outlet
valve to drain out the water inside the unit. Check the connector of valves, pipes to see if there is corrosion, block, leakage or damage.
2.4 Electrical Safety Instructions
Only these qualified professionals can operate the electrical components. Before any operation to the electrical parts, the power supply to the unit should be cutoff at firstly. NOTE: Electrical Shock: Even the main power supply is cutoff, some parts in the control system may
be still electrified because they are supplied by isolated power source. Burn: The current will make electrical components heat, so be careful when touch the power
line, control cable, cable shell, cable sleeve, cover of wiring box and the motor shell. Even the unit is shut down, the power lines are still electrified as long as the main breaker is on.
Please refer to the circuit diagram and use safe operation. The unit is in accordance with the present electromagnetic compatibility standard. If you have to deal with the PCB, please wear a pair of antistatic gloves to avoid the
LSBLG/MC IOMM
components to be exposed under high voltage. When change the PCB, the new one should be inside the antistatic bag until it is to be installed in position.
3. Installation
3.1 Installation Environment
LSBLG/MC series screw chiller is only for indoor installation. Please do not install it at anywhere there is a flood risk which may lead to electric leakage or short circuit. Also do not install the unit in room where the direct sunlight can touch.
The installation environment should be ventilated well in case of the human hazard caused by refrigerant leakage.
There should not be inflammable gas, flame, heavy vibration or other objects do harm to the mechanical parts or electrical components.
The installation room should have suitable humidity and temperature. There should be enough support points in the installation position. There should be tough base to bear the weight of the unit and enough fixing devices.
3.2 Acceptance
Before the unit into the site, be sure the unit and the accessories are in accordance with your order requirement and the model no. is same as the rating label.
Please check if the all parts of the unit and the accessories are complete. If something is missing, please contact Midea or authorized dealer immediately.
3.3 Rigging
DO NOT make the unit impact the ground to avoid the damage when move the unit into the installation room.
Use some rollers under the unit to move the chiller. Please refer to Fig 3.1 for rigging superposition-type single-compressor unit. It’s
applicable for following models: LSBLG115/MC, LSBLG170/MC and LSBLG275/MC.
Fig 3.1 Rigging sketch for superposition-type single-compressor screw chiller
LSBLG/MC IOMM
Please refer to Fig 3.2 for rigging the juxtaposition-type single-compressor unit. It is
suitable for LSBLG350/MC, LSBLG420/MC, LSBLG560/MC and LSBLG650/MC。
Fig 3.2 Rigging sketch for juxtaposition-type single-compressor screw chiller
Please refer to Fig 3.3 for rigging the dual-compressor unit. It is suitable for LSBLG700/MC, LSBLG840/MC, LSBLG975/MC, LSBLG1120/MC and LSBLG1300/MC.
Fig 3.3 Lifting sketch map for dual-compressor screw chiller
Safety Instructions To prevent electric box and the body of machine from being damaged while lifting,
please use groove steel for supporting. Make sure the steel wire is on the right position that indicated in the sketch map while
lifting. Make sure the steel wire is fixed on the 4 hooking holes on the pedestal by hooks
while lifting. Please find the dimension and the weight data in product manual, and then select
LSBLG/MC IOMM
right steel wires.
3.4 Installation Process
3.4.1 Foundation There should be some barrel-drains around the foundation for drain the water
conveniently. There should be absorbers between the unit and the foundation to cut off the transferring
of noise and vibration. Be sure the unit is even and you can add anti-vibration base if necessary.
Fig 3.4 Sketch of Installation Foundation
Model
Dim.
LSBLG***/MC
115 170 275 350 420 560
D(mm) 1400 1600 1600 1600 1800 1800
E(mm) 520 520 570 1250 1250 1250
Model
Dim.
LSBLG***/MC
650 700 840 975 1120 1300
D(mm) 1800 1800 2000 2000 2000 2000
E(mm) 1350 1440 1400 1440 1540 1640
Table 3.1 Installation Dimension Table
LSBLG/MC IOMM
3.4.2 Fixation of unit
Fig 3.5 Type 1 Fig 3.6 Type 2
Note:
(1) For type 1, please reserve the installation holes for foundation bolt on the basement
according to installation basement diagram.
(2) For type 2, reserve the holes for the installation of absorber on the basement.
3.4.3 Service Space
Fig 3.7 Service Space
Table 3.2 LSBLG/MC Service Spaces
Service Space
A ≥700 Front
B ≥600 Rear
C ≥2000 Left
D ≥3500 (Single-compressor)
≥5000 (Dual-compressor) Right (Water Pipe Connection)
E ≥600 Top
Absorber
Basement
Washer
Foundation bolt
Iron plateThickness>2mm
Bottom of unit
Nut cap
M20(Refer to practical situation
for the length of bolt.)
Absorber
Foundation bolt
Washer
Installation hole
Nut cap
Bottom of unitM20(Refer to practical situation
for the length of bolt.)
LSBLG/MC IOMM
3.5 Installation of Other Systems 3.5.1 Installation of Water System The valves on water inlet/outlet pipes should be well-insulated to reduce the energy loss
and to prevent condensing. Water flow switches should be installed on water outlet side of evaporator and condenser
to ensure enough water in pipeline. The water flow switches are interlocked with compressor; otherwise it may cause chilled water inside evaporator to freeze, low pressure on gas side, bad oil return, overpressure in condenser or high-pressure protection due to lack of water (It is suggested that using water switch manufactured by Shanghai Fengshen Refrigeration controller co. Ltd. The model is FSF50P-1, 3# target lamina, two G1 connectors were provided as our standard accessories).
In close loop water system, to diminish the impact on water pipe because of the expansion or contraction of water volume and to avoid the influence caused by supplementing water pressure, water return side should be fitted with an expansion water tank whose water surface should be at least 1m higher than the highest point of water pipe system.
Chilled water pump of water chiller should be installed on the inlet of evaporator. In order to expel the air from water system, install an automatic discharge valve on the
highest place of local water pipe and the horizontal pipe should be up tilted for about 1/250 degree. Do scaling and cleaning on water pipeline before installation and the unit should be maintained clean before operation.
Shockproof hose should be installed on water inlet and outlet to diminish the vibration which may be transmitted to indoor side.
It’s suggested to install a thermometer and a pressure gauge on the inlet and outlet of unit, which will provide convenience for daily check.
During the operation of water chiller, water or other secondary refrigerants inside the evaporator should not less than 70% of rated flow to avoid accident.
The accessories of water inlet pipe and outlet pipe should be installed with sockets to easily separate them from water pipes when doing maintenance.
Do not load the weight of water pipe onto the unit. When connecting water inlet/outlet with corresponding water pipe, soft connection such as rubber joint should be used to avoid the transmission and inter-disturbance of vibration and noise.
Refer to Fig 3.8 for the piping of condenser. Refer to Fig 3.9 for the piping of evaporator.
Wat
er c
hil
ler
Con
den
ser
F
a b cd e f g
h j
ikb
Water inlet,
condenser
Water outlet,
condenser
Cooling tower
Fig 3.8 Piping of Condenser
a. Shockproof joint; b. Temperature sensor; c. Butterfly valve; d. Pressure gauge; e. Thermometer; f. Platinum resistance thermometer; g. Automatic discharge valve; h. Water pump; i. Drain valve; j. Y-filter; k. Water flow switch (Note: All the fittings of water pipe and water flow switch are provided by the users.)
LSBLG/MC IOMM
F
c de f g
h j
ikba
aW
ate
r chil
ler
Evapora
tor Water inlet,
Evaporator
Water outlet ,Evaporator
Water supply
Water outlet
Water return
Fig 3.9 Piping of Evaporator
a. Temperature Sensor; b. Pressure thermostat; c. Shockproof joint; d. Butterfly valve; e. Pressure gauge; f. Thermometer g. Automatic discharge valve; h. water pump; i. Drain valve; j. Y-filter; k. Water flow switch (Note: All the fittings of water pipe and water switch are provided by the users.)
There should be a water flow switch on the horizontal water out pipe of each condenser and evaporator. The distance from the switch to each end of the horizontal pipe should be 5 times of the diameter of the pipe. Adjust the lamina according to the pipe specification (please refer to the manual of the water flow switch). Connect the switch to the terminals inside the control cabinet (please refer to the circuit diagram).
WARNING: PLEASE CONFIRM THE WATER FLOW DIRECTION; THE WATER FLOW SWITCH IS JUST A SAFETY DEVICE AND CANNOT BE USED FOR CONTROL THE UNIT.
Water Quality
The quality of cycling water should be in accordance with relevant standard and the design fouling factor of the evaporator and the condenser.
The cooling water is open type cycling system and its PH value should be between 7.0 and 9.0 (alkalescent ). The quantity of calcium ion should be less than 200 mg/l.
Anti-freezing Protection
When the ambient temperature may go down below 0℃ where the unit works, it is
suggested to add a anti-freezing device to protect the normal working of the unit. If the unit stops and there is no any anti-freezing device, all the water inside the evaporator and condenser should be drained out. If there is a damage caused by ice from the water inside the heat exchangers, Midea will not be response for it.
3. 5.2 Electrical System The Power Supply The voltage of power supply should be constant. Taking all factors causing voltage
drop into account, the working voltage of unit should be within±10% of rated value.
Too high or too low voltage will have bad effect on the unit. The voltage difference between phases should not higher than 2% of rated value and
!
LSBLG/MC IOMM
the current difference between the highest and the lowest phase should be lower than 3% of rated value, otherwise the compressor may be overheated.
The frequency of power supply should be within ±2% of rated value.
The lowest starting voltage should be higher than 90% of rated value. Too long power supply cable may disable the compressor to start; therefore, the
length of the cable wire should be proper enough to ensure that the voltage drop between two terminals is lower than 2% of rated value. In case the length cannot be changed, the cable size should be thickened.
Wiring work between power supply and the unit should be strictly done according to Electric Standard and be well insulated which is measured by ohmmeter of 500V. The
insulation resistance should be higher than 10MΩ.
The parameters of running current and input power on the nameplate are measured under standard working condition, which may differ due to actual load on system and actual temperature of chilled water. Hence please select the power supply, transformer, non-fuse breaker and the capacity of wiring in the light of possible worst working condition.
WARNING: THE UNIT SHOULD HAVE SPECIAL ISOLATED CIRCUIT TO WORK. ONLY THE QULIFIED STUFF CAN OPERATE OR USE THE ELECTRICAL COMPONENTS. THE CAPACITY LOSS OF THE CIRCUIT OR INCORRECT OPERATION MAY LEAD TO ELECTRICAL SHOCK OR FIRE HAZARD.
Wiring Specification
Prepare the wiring plan according to the set overload conditions of the unit. NEVER choose the wire specification by the running conditions comes from the rated output of the motor or other individual specification because it is very dangerous. Please refer to the table 3.3 to choose the recommended wiring specification.
Model Cable Type Min. cross area of each phase cable mm
2
=(n×min. Cross area of each cable)
LSBLG 115/MC BVR 50 LSBLG 170/MC BVR 50 LSBLG 275/MC BVR 50 LSBLG 350/MC BVR 70 LSBLG 420/MC BVR 95 LSBLG 560/MC BVR 120 LSBLG 650/MC BVR 150
LSBLG 700/MC BVR 2×70
LSBLG 840/MC BVR 2×95
LSBLG 975/MC BVR 2×95
LSBLG 1120/MC BVR 2×120
LSBLG 1300/MC BVR 2×120
Table 3.3: LSBLG/MC Cable Specifications
The installers are response for the wiring specification according to the real electrical conditions of the site. Above table and suggest are only for reference (The min. cross area of each phase cable means the min. cross area of the cable goes along the bridge supporter, not goes through the wiring pipes.) After choosing the cable specification, the wiring work can be carried out. The installer should make the wiring work conveniently and make detailed instructions of any necessary change.
!
!
LSBLG/MC IOMM
WARNING: THE EXTERNAL WIRING PLAN SHOULD OBEY THE RULES. INCORRECT WIRE SPECIFITION WILL LEAD TO HEAT AND FIRE HAZARD.
Reliable Connection
Make the wiring connection reliable in case of wrong phase or phase loss. Avoid external force on the wires. After connection, check again to ensure there is no relaxing or wrong connection.
WARNING: THE WIRES MUST BE THE APPOINTED AND IT IS SHOULD BE SURE THE CONNECTION IS RELIABLE AND SAFE. NEVER ADD EXTERNAL FORCES ON THE CONNECTION TERMINALS. IF THE CONNECTION OR FIXING IS INCOMPLETE, IT WILL LEAD TO HEAT OR FIRE.
Grounding
For safety and according to the electrical work rules, the case of unit should be well and reliably grounded to avoid electric shock.
Only the qualified professional can carry out the grounding work. The grounding terminals are inside the control cabinet.
NOTE:
NEVER CONNECT THE GROUNDING WIRE TO GAS PIPES, WATER PIPES, LIGHTNING ROD OR TELEPHONE WIRE.
GAS PIPE: GAS LEAKAGE WILL LEAD TO EXPLOSION OR FIRE. WATER PIPE WILL DAMAGE THE INSULATION OF THE WIRES.
LIGHTNING ROD OR TELEPHONE WIRE: IF THERE IS A LIGHTNING, THE
GROUNDING VOLTAGE WILL INCREASE RAPIDLY.
Installing the Power Breaker
Install one power breaker for each of the units.
To eliminate the damage to transformer, wiring and the like electric device caused by
short-circuit and to control the ON/OFF of compressor separately, every leadin of
power supply cable should be equipped with non-fuse breaker with a certain capacity.
See the following chart:
NFB
TSR
!
!
LSBLG/MC IOMM
Fig 3.10 Wiring Diagram of None-fuse Breaker
WARNING: THERE SHOULD BE POWER BREAKER INSTALLED ACCORDING TO THE TECHNICAL STANDARD OF ELECTRICAL EQUIPMENT. THE LONG INSTALLING DISTANCE WILL LEAD TO ELECTRICAL SHOCK. EACH UNIT SHOULD HAVE ONE BREAKER. NEVER MAKE TWO OR MORE UNITS SHARE ONE BREAKER, OR THERE MAY BE ELECTRICAL SHOCK OR FIRE HAZARD.
This work should be carried out after covering the components inside the control cabinet.
DO NOT damage the bolts while wiring. The other components such as warning sign and fuse are inside the control cabinet
and they are not supposed to be touched. After installing the breaker, clear the tools and remainder wires.
WARNING: NEVER INSTALL ANY POWER CABLE BETWEEN THE UNITS IN CASEOF FIRE HAZARD.
Water Flow Switch The wiring of water flow switch should be carried out by the users. Without water flow switch, the unit cannot start and run normally. See the following chart for wiring: (Note: the wire is shielded wire of 0.75mm2.) (Note: The wiring may differ in different models, please refer to circuit diagram attached to this unit for details.)
Fig 3.11 Wiring Diagram of Water Flow Switch
Temperature Sensor Chilled water temperature sensor is provided as standard accessories. Users should remove the 10K resistance or direct connection wire before wiring. The unit cannot start and run normally unless there are chilled water temperature sensor or 10K resistance or direct connection wire. Please refer to the following diagram: (Note: The wiring may differ in different models, please refer to wiring diagram attached to this unit for details.)
207207202202
1 2 3 4
Wate
r sw
itch,
coole
d w
ate
r
Wate
r sw
itch,
chil
led w
ate
r
Shielded wire
terminal
!
!
LSBLG/MC IOMM
Fig 3.12 Wiring Diagram of Water Temperature Sensor
The Main Power Supply The wiring of power supply is shown below: (Note: In order to prevent dust from entering electric box, users should install a dustproof cover in leadin of electric wire or use a wire casing to seal the leadin after wiring.)
A B C
Green
Yellow
Yellow
Green
RedRed
3 ~380V 50HzTerminal block TC4004
Fig 3.13 Main Power Wiring Diagram
For detailed information, please refer to the wiring diagrams that attached to this manual.
Note: after wiring, please add a anti-dust shell to cover the inlet of the main power cables or seal the inlet to avoid the dust to go inside the wiring cabinet.
Water Pump and Cooling Tower Electromagnetic switches for cooling water pump, chilled water pump and cooling tower fan motor should be connected with the circuit of unit. The electromagnetic switches
Out
let
chil
led
wat
er t
emp.
sen
sor
Inle
t ch
ille
d w
ater
tem
p. s
enso
r
Junc
tion
, shi
elde
d w
ire
Inle
t co
oled
wat
er t
emp.
sen
sor
Out
let
cool
ed w
ater
tem
p. s
enso
r
Junc
tion
, shi
elde
d w
ire
Main control board
LSBLG/MC IOMM
above installed on site by the installer are not contained in electric box of the unit.
4. Running
4.1 Running Range
Fig 4.1 Running Range of LSBLG/MC Series R134a DX Type Screw Chillers
Note: The area around by the quadrangle is the full-load range of the chillers; When the chiller is running at full-load and standard water flow rate, the temperature
difference between the water inlet and outlet of the condenser and the evaporator is 5℃;
When the cooling water entering temperature is lower than 20℃, it is necessary to add a
by-pass valve at the cooling water pipe system to maintain the condensing pressure or
heat the cooling water to more than 20℃
If the -10℃~3℃ chilled water is required, we can make a special design as non-standard
low-temperature chiller.
15
20
25
30
35
40
45
0 5 10 15 20
蒸发器出水温度(℃)
冷凝器出水温度(
℃)
Water Leaving Temperature of Evaporator (℃)
Wat
er L
eavi
ng
Tem
per
atu
re o
f C
on
den
ser
(℃)
LSBLG/MC IOMM
4.2 Water Flow Rate Range
Flow rate
Model
Chilled Water Flow Rate Range
(m3/h)
Cooling Water Flow Rate Range
(m3/h)
LSBLG 115/MC 14-24 16.8-28.8
LSBLG 170/MC 20.3-34.8 24.5-42
LSBLG 275/MC 32.9-56.4 39.9-68.4
LSBLG 350/MC 42-72 51.1-87.6
LSBLG 420/MC 50.4-86.4 60.9-104.4
LSBLG 560/MC 67.2-115.2 80.5-138
LSBLG 650/MC 78.4-134.4 93.8-160.8
LSBLG 700/MC 84.7-145.2 102.2-175.2
LSBLG 840/MC 100.8-172.8 121.1-207.6
LSBLG 975/MC 117.6-201.6 140.7-241.2
LSBLG1120/MC 135.1-231.6 161.7-277.2
LSBLG1300/MC 156.8-268.8 187.6-321.6
Table 4.1 Water Flow Rate Range of LSBLG/MC
Instruction:
The given water flow range is for ensuring the chiller can work under normal working conditions.
If the water flow rate is too low and when the cooling load changes, the water temperature will change rapidly, which will make the compressor start and stop frequently.
If the water flow rate of the evaporator is required very low, we can provide 3-pass or 4-pass chiller.
If the water flow rate is required very high, it will take too long to cool down the water and the pressure drop of the evaporator will be too high. So we can provide single-pass design.
Note: The control system of LSBLG/MC screw chiller contains the chain control of the cooling
tower and the pumps but it is only for ON/OFF, not variable. Above flow data range means the chiller works under some constant water flow rate.
If the variable primary flow system is in use, the unit can be self-adjusted to fit it. But the water flow change rate should not be more than 30% per minute.
LSBLG/MC IOMM
4.3 Specifications
Table 4.2 Specifications of R134a DX Type Screw Chiller (Single-Compressor)
Unit Model LSBLG
115/MC
LSBLG
170/MC
LSBLG
275/MC
LSBLG
350/MC
LSBLG
420/MC
LSBLG
560/MC
LSBLG
650/MC
Nominal
Cooling Capacity
RT 32.7 47.8 78.2 99.8 119.4 159.2 184.8
kW 115 168 275 351 420 560 650
Power Supply 380V/3N/50Hz (400/415V as option)
Power input kW 24 35 57 72 84 112 127
Rated current A 41 60 97 123 143 191 221
Compressor
Type / Semi-hermetical single screw compressor
Starter Mode / Y-Δ
Energy adjusting % 25%、50%、75%、100% four step control(25%-100% Stepless Control, Optional)
Quantity / 1 1 1 1 1 1 1
Refrigerant Type / R134a
Charge volume kg 40 50 60 90 100 120 150
Evaporator
Type / Direct Expansion Evaporator
Quantity / 1 1 1 1 1 1 1
Flow Rate m3/h 20 29 47 60 72 96 112
Pressure Drop kPa 60 81 81 74 83 83 85
Inlet/Outlet mm DN80 DN100 DN100 DN125 DN125 DN125 DN150
Condenser
Type / Tube-and-shell condenser
Quantity / 1 1 1 1 1 1 1
Flow Rate m3/h 24 35 57 73 87 115 134
Pressure Drop kPa 12 23 23 16 21 31 42
Inlet/Outlet mm DN80 DN100 DN100 DN125 DN125 DN125 DN150
Unit
Dimension
Length mm 2940 2940 2970 2995 3600 3600 3600
Width mm 800 800 850 1350 1380 1390 1450
Height mm 1740 1770 1880 1480 1540 1660 1720
shipping Weight kg 1330 1640 1895 2480 3000 3320 4100
Running Weight kg 1480 1790 2045 2780 3300 3620 4500
NOTE:
(1)The performance data is based on the standard conditions: Chilled water in/out temperature is 12/7℃;
and cooling water in/out temperature is 30/35℃;
(2)The water side design working pressure of the condenser and the evaporator is 1.0MPa. If you want it
to be higher than 1.0 MPa, please make a special comment in the order.
(3)The fouling factor of the evaporator and the condenser is 0.086 m2·℃/kW.
(4)If the working conditions change, a new speciation will be provided.
LSBLG/MC IOMM
Table 4.3 Specifications of R134a DX Type Screw Chiller (Dual-Compressor)
Unit Model LSBLG
700/MC
LSBLG
840/MC
LSBLG
975/MC LSBLG1120/MC LSBLG1300/MC
Nominal
Cooling Capacity
RT 199.6 238.8 276.9 318.5 369.6
kW 702 840 974 1120 1300
kcal/h
603,720 722,400 837,640 963,200 1,118,000
Power Supply 380V/3N /50Hz (400/415V as option)
Power input kW 72×2 84×2 96×2 112×2 127×2
Rated current A 123×2 143×2 165×2 191×2 221×2
Compressor
Type / Semi-hermetical twin screw compressor
Starter Mode / Y-Δ
Energy
adjusting % 25%、50%、75%、100% four step control(25%-100% Stepless Control,Optional)
Quantity / 2 2 2 2 2
Refrigerant
Type / R134a
Charge
volume kg 85×2 95×2 110×2 120×2 150×2
Evaporator
Type / Dry Expansion Evaporator
Quantity / 1 1 1 1 1
Flow Rate m3/h 121 144 168 193 224
Pressure Drop kPa 85 87 87 86 86
Inlet/Outlet mm DN150 DN150 DN150 DN150 DN200
Condenser
Type / Tube-and-shell condenser
Quantity / 1 1 1 1 1
Flow Rate m3/h 146 173 201 231 268
Pressure Drop kPa 40 45 30 38 40
Inlet/Outlet mm DN150 DN150 DN150 DN150 DN200
Unit
Dimention
Length mm 3800 4400 4400 4800 4800
Width mm 1570 1500 1540 1670 1740
Height mm 1720 1690 1740 1740 1865
shipping Weight kg 4400 5220 6050 6130 6600
Running Weight kg 4800 5620 6380 6580 7200
NOTE:
(1)The performance data is based on the standard conditions: Chilled water in/out temperature is 12/7℃;
and cooling water in/out temperature is 30/35℃;
(2)The water side design working pressure of the condenser and the evaporator is 1.0MPa. If you want it
to be higher than 1.0 MPa, please make a special comment in the order.
(3)The fouling factor of the evaporator and the condenser is 0.086 m2·℃/kW.
(4)If the working conditions change, a new speciation will be provided.
LSBLG/MC IOMM
Performance Table
Item
Model
Chilled
Water
Leaving
T ℃
Cooling Water Entering Temperature℃
25 28 30 32 35
Capacity kW
Power Input kW
Capacity kW
Power Input kW
Capacity kW
Power Input kW
Capacity kW
Power Input kW
Capacity kW
Power Input kW
LSBLG115/MC
4 107 21.9 103.8 22.7 101 23.4 99 24.2 95 25.5
5 112 22.1 108.1 22.9 106 23.6 103 24.4 99 25.7
6 116 22.3 112.6 23.1 110 23.8 107 24.6 103 25.7
7 121 22.4 117.1 23.3 115 24 112 24.8 107 25.7
8 126 22.6 121.9 23.5 119 24.2 116 25.0 112 26.1
9 131 22.8 126.7 23.7 124 24.4 121 25.2 116 26.6
LSBLG170/MC
4 158 32.0 152.4 33.2 149 34.1 145 35.3 139 37.1
5 164 32.2 158.8 33.4 155 34.4 151 35.6 145 37.5
6 171 32.5 165.4 33.7 162 34.7 158 35.9 151 37.8
7 178 32.8 172.0 34.0 168 35 164 36.2 158 38.1
8 185 33.0 179.0 34.3 175 35.3 171 36.5 164 38.4
9 192 33.2 186.0 34.5 182 35.6 177 36.7 171 38.7
LSBLG275/MC
4 258 52.1 249.6 54.1 244 55.7 238 57.5 228 60.6
5 269 52.6 259.9 54.5 254 56.1 247 57.9 238 61.1
6 280 53.0 270.7 54.9 264 56.5 258 58.4 248 61.6
7 291 53.4 281.5 55.4 275 57 268 58.9 258 62.1
8 303 53.8 293.0 55.8 286 57.5 279 59.4 269 62.6
9 315 54.2 304.4 56.3 298 57.9 290 59.8 279 63.1
LSBLG350/MC
4 330 65.8 318.6 68.3 311 70.3 303 72.6 291 76.5
5 343 66.3 331.8 68.8 324 70.9 316 73.2 303 77.1
6 357 66.9 345.6 69.4 337 0.0 329 73.8 316 77.8
7 371 67.4 359.3 69.9 351 72 342 74.4 329 78.5
8 387 67.9 374.0 70.5 365 0.0 357 75.0 343 79.1
9 402 68.4 388.7 71.1 380 73.1 371 75.6 357 79.7
LSBLG/MC IOMM
(Continue)
Item
Model
Chilled
Water
Leaving
T ℃
Cooling Water Entering Temperature℃
25 28 30 32 35
Capacity kW
Power Input kW
Capacity kW
Power Input kW
Capacity kW
Power Input kW
Capacity kW
Power Input kW
Capacity kW
Power Input kW
LSBLG420/MC
4 394 76.8 381.1 79.7 372 82.0 363 84.7 348 89.3
5 411 77.4 397.0 80.3 388 82.7 378 85.4 363 90.0
6 427 78.0 413.5 80.9 404 83.3 394 86.1 378 90.8
7 444 78.6 430.0 81.6 420 84 410 86.8 394 91.5
8 462 79.2 447.5 82.2 437 84.7 427 87.5 410 92.3
9 480 79.8 465.0 82.9 452 85.4 444 88.2 427 93.0
LSBLG560/MC
4 526 102.3 508.2 106.2 496 109.2 484 112.8 464 119.0
5 547 103.1 529.2 107.0 517 110.2 504 113.7 484 120.0
6 570 103.9 551.3 107.9 538 111.1 525 114.7 505 121.0
7 593 104.7 573.4 108.8 560 112 546 115.6 525 122.0
8 617 105.5 596.7 109.6 583 112.9 569 116.6 547 123.0
9 641 106.3 620.0 110.4 606 113.7 591 117.5 569 123.9
LSBLG650/MC
4 614 116.1 593.6 120.4 579 123.9 565 127.9 542 135.0
5 639 117.0 618.2 121.4 604 125.0 589 129.0 565 136.1
6 666 117.9 643.9 122.4 627 126.0 613 130.1 589 137.2
7 692 118.8 669.7 123.3 650 127 638 131.2 613 138.3
8 720 119.7 696.9 124.3 679 128.0 664 132.3 639 139.4
9 748 120.6 724.2 125.3 708 129.0 691 133.3 664 140.6
LSBLG700/MC
4 659 131.7 637.1 136.6 622 140.5 606 145.2 582 153.1
5 686 132.7 663.6 137.6 648 141.7 632 146.5 607 154.3
6 715 133.7 691.1 138.8 675 0.0 658 147.6 633 155.6
7 743 134.7 718.7 139.9 702 144 685 148.7 658 157.0
8 773 135.8 748.0 141.0 731 0.0 713 150.0 686 158.2
9 803 136.8 777.4 142.1 760 146.3 741 151.2 713 159.4
LSBLG/MC IOMM
(Continue)
Item
Model
Chilled
Water
Leavin
g T ℃
Cooling Water Entering Temperature℃
25 28 30 32 35
Capacity kW
Power Input kW
Capacity kW
Power Input kW
Capacity kW
Power Input kW
Capacity kW
Power Input kW
Capacity kW
Power Input kW
LSBLG840/MC
4 789 153.6 762.3 159.4 744 164.0 726 169.4 696 178.6
5 821 154.8 794.0 160.6 775 165.4 756 170.8 726 180.0
6 855 156.0 827.0 161.9 808 166.7 788 172.2 757 181.5
7 889 157.2 860.0 163.2 840 168 820 173.6 788 183.0
8 925 158.4 895.0 164.5 874 169.4 853 175.0 821 184.5
9 961 159.6 930.1 165.8 904 170.8 887 176.4 853 186.0
LSBLG975/MC
4 914 175.5 883.9 182.1 863 187.4 841 193.4 808 203.9
5 952 176.9 920.5 183.5 899 188.8 876 195.0 842 205.7
6 941 849.7 941.4 849.7 941 849.7 941 849.7 941 849.7
7 1031 179.5 997.1 186.4 974 192 950 198.4 913 209.1
8 941 849.7 941.4 849.7 941 849.7 941 849.7 941 849.7
9 1114 182.3 1078.4 189.4 1054 195.0 1028 201.5 989 212.5
LSBLG1120/M
C
4 1051 204.6 1016.4 212.4 992 218.4 967 225.6 929 238.0
5 1095 206.2 1058.5 214.0 1034 220.4 1008 227.4 968 240.0
6 1140 207.8 1102.6 215.8 1077 222.2 1050 229.3 1009 242.0
7 1185 209.4 1146.7 217.6 1120 224 1093 231.2 1050 244.0
8 1233 211.0 1193.4 219.2 1166 225.7 1138 233.1 1094 245.9
9 1281 212.6 1240.0 220.8 1212 227.4 1183 235.0 1138 247.8
LSBLG1300/M
C
4 1228 232.2 1187.2 240.7 1159 247.9 1130 255.8 1085 269.9
5 1279 234.0 1236.3 242.8 1207 249.9 1177 258.1 1131 272.2
6 1332 235.8 1287.8 244.7 1254 252.0 1227 260.2 1179 274.4
7 1384 237.7 1339.4 246.7 1300 254 1276 262.4 1227 276.6
8 1440 239.4 1393.8 248.6 1358 256.0 1329 264.5 1278 278.9
9 1496 241.1 1448.3 250.5 1415 258.1 1381 266.6 1329 281.1
LSBLG/MC IOMM
4.4 Check before Start Before the pre-check, please read the following instructions carefully for safety of the human and the unit. Also please following safety instructions in Chapter 2. If anything wrong is found before the pre-check, please contact Midea® immediately.
4.4.1 Electrical Part The following points should be confirmed before electrifying the unit for safety.
The insulation resistance of power-ground and phase-phase should be checked to be enough.
The connection of power supply cables should be correct without phase lack or wrong phase sequence. Check if the connection is released.
The grounding should be correct. Clean the inside of the control cabinet completely. The specification of the supply cables should be correct.
The voltage should be in 10% of the rated voltage, and the frequency should be 2% of the rated. Confirm that the voltage difference among the 3 phases should not be more
than 2% of the rated. The unit should be electrified to make the oil heater work for at least 8 hours before start
to avoid any problem and make the compressor runs stable. WARNING: MAKE THE UNIT GROUNDED RELIABLE, OR THERE WILL BE ELECTRICAL
SHOCK HAZARD. NEVER CONNECT THE GROUNDING WIRE TO THE GAS PIPES, WATER PIPES, LIGHTNING ARRESTOR OR TELEPHONE WIRES.
NEVER PUT ANY UNNECESSARY OBJECTS INSIDE THE CONTROL CABINET IN CASE OF ELECTRICAL SHOCK AND FIRE HAZARD.
CHECK THE POWER SUPPLY CAPACITY IF IT IS SUITABLE FOR THE UNIT. IF THE CAPACITY IS LESS THAN WHAT THE UNIT NEED, THERE WOULD BE FIRE HAZARD OR ELECTRICAL SHOCK.
4.4.2 Water System Check all the water pipe system to confirm the pipes connected to the evaporator and the
condenser and the water flow direction are correct. Check the installation of the temperature sensor of the entering water and leaving water
of the condenser and the evaporator to see if the connection is reliable and the temperature reading is correct.
Open all the water valves and start the pumps to check if there is leakage at connection flange and make the air out of the condenser and the evaporator.
Check the water side pressure drop of both heat exchangers. Check if the water flow switch and water pressure difference switch act correctly.
4.4.3 The Unit Check whether the lubricating oil in compressor has been heated for enough time which
is about 2~8 hours. (The time depends on ambient temperature, the lower the ambient temperature, the longer the heating time is.) The setting of oil heating time can be done on the touch screen.
Check whether there is sufficient water in chilled water circulating system as well as in cooling water system and open the water supplementing valve.
Check whether all the pipeline and handles of valves or switches are in proper position. Check whether the switches and components in distribution box are in normal state.
!
LSBLG/MC IOMM
Make sure the power supply and voltage are perfect. Check the pressure gauge of main unit. Usually, the pressure is between 7~10kgf/cm2G
when the indoor temperature is between 25℃~28℃.
4.5 Start the Unit 4.5.1 Normal Start and Stop Normal Start
(1) Start the fan motor of cooling tower. (2) Run the cooling water pump. (3) Run the chilled water pump (4) Start the compressor. (Caution: Keep a close watch on pressure gauge while starting the compressor. Stop it if there is any problem.)
Stop Procedure
Reverse to starting procedures. When the compressor stops, wait for at least 5 minutes before to stop chilled water pump, then stop cooling water pump and cooling tower fan motor by another two 5 minutes interval.
Precaution While Running
Electric
A. Check whether the voltage is normal after starting. B. Check whether all the switches of power supply have been closed. C. Make sure the power supply is normal after starting. Unit
A. Whether all the motors run normally. B. Make sure there is no abnormal noise while operation. C. Whether the circulating water pumps are working in good condition and the water pressure gauges are normal. D. Whether the high/low pressure gauges of compressor are normal. E. In case the protection switches of high/low pressure activated, eliminate the troubles before restart the unit.
4.5.2 Emergency Stop The red button on the door of the control cabinet is emergency stop switch. Press it when something is wrong, the unit will stop immediately. Rotate it anti-clockwise to reset it.
4.5.3 Running under Low Ambient Temperature The best entering cooling water temperature is 24℃~35℃. Too low temperature will make
the oil pressure be not enough so that the loading of the compressor will be more difficult and it may occur that the compressor cannot work under 100% load. If working under low oil pressure difference for a long time, the compressor will not be lubricated well, which will lead to shorter working life of the compressor. If running under low temperature is required, please be sure the entering cooling water
temperature is more than 20℃, or please increase the condensing pressure with following
method: By-pass control of cooling tower: control the quantity of the water into the cooling tower
with manual or automatically by-pass valve to ensure the temperature of the water going to the condenser.
LSBLG/MC IOMM
Adjusting the cooling water flow: maintain the entering cooling water temperature, and control the condensing temperature by reducing the water flow through the condenser.
4.6 PLC Operation Note: You will not be informed in advance if following interfaces are changed partly or fully, please refer to the real interface pictures.
4.6.1 Structure of PLC Control System
WORK STATE HISTORYWARNING &PROTECTION
WELCOME
MAIN
TRENDCURVE
PARAMETERCHECK
SETTING PAGE
PASSWORD
PARAMETERSETTING
Fig 4.3 Structure of PLC Control System
4.6.2 Welcome Page When the chiller system is electrified and the control system starts, WELCOME PAGE will be displayed on the touch screen as following picture
Fig 4.4 Welcome Page
LSBLG/MC IOMM
4.6.3 Main Page Press anywhere of the WELCOME page to get into the WORK STATE page of the system as
following:
Fig 4.5 Main Page
Main Page is used for displaying the main working parameters. The meaning of this page:
20yy/mm/dd HH:MM
Current Date and Time, Format:00YY/MM/DD Hr:Min
WARN Warning: when there is a warning, it will be high-lighted in the PARAMETER CHECK page. Press it to get into the WARNING page.
SYST SET. System Settings
PRMT CHCK Parameter Check: to check every parameter
CURT TRND Trend Curve: to check curves of every temperature
DATA REPT History Report: to check the history data of every temperature.
Alarm Alarm Indicator: it will be on when there is something wrong.
Chill WLT Chilled Water Leaving Temperature, ℃
Cool WET Cooling Water Entering Temperature, ℃
START / STOP button: If all the conditions are satisfied for running, the chiller system can be
started by pressing the START button on right of the screen. When the chiller is running, the START button will change to STOP button. If the condition is satisfied for stop when the chiller
system is running, you can press STOP button to stop it. (The word on the button is current
operable state)
The working state of chiller is displayed on the mid-upper area of the screen: initializing, standby, starting, running, pause, stop, protecting and etc. At the first time the chiller is electrified, it will start without delay. In other occasions, before start or stop the chiller, there will be a few minutes delay.
LSBLG/MC IOMM
If the condition is not suitable for start or stop, when you press START/STOP button, there will
show a warning box with reasons for not start or stop on the touch screen. Press OK to close
the box.
If the temperature of outlet chilled water is lower than the set temperature 2℃ , the
compressor will stop working, which will be displayed PAUSE state. If the compressor stops due to a fault, it will be displayed that the chiller system is in fault protection state. Press the 5 buttons on the left and the lower of the screen, you can get into relevant pages (Parameter Setting Page needs password). The state bar on the right screen indicates load percent of the unit.
Press button to enter help page on which there are some simple operation instructions.
Fig 4.6 HELP page
Press MAIN button to close this page.
4.6.4 System Setting
1.Press button on the main running state page, there will show a password keypad.
Input the password to enter the user settings page shown as following:
LSBLG/MC IOMM
Fig 4.7 User Setting Page Fig 4.8 Password Input Page
In this page the user can choose Local or Remote control. The word in the button means the
current control mode of the unit. (if it sais Local, then the unit can be only controlled manually;
if it sais Remote, then the unit can be only controlled by remote directives.)
If you want to set some temperature (only when the compressor stops), just press the relevant value box. A keypad for input appears. You need to input the value according to the upper referenced format #~#### (if the value you input exceeds this range, it will be invalid)
and then press ENT to confirm or press ESC to cancel (if it is cancelled, the keypad for input
will disappear). According to the specifications of this chiller system, the minimum chilled
water outlet temperature is 3~4℃, and the relevant temperature for recovering from pause
should be at least 8℃ higher than this data.
Press button to get into Time Setting page. In this page, user can set the date and time to current.
Fig 4.9 Time Setting
There are input box for year, month, day and time. If the date and time is to be set, 4 boxes should be all input. If you want to set date or time (only when the compressor stops), just press the relevant value box. A keypad for input appears. You need to input the value according to the upper referenced format #~#### (if the value you input exceeds this range, it
will be invalid) and then press ENT to confirm or press ESC to cancel (if it is cancelled, the
keypad for input will disappear).(For Time setting, you should input a dot between the hour
value and the minute value). After input, press button to confirm. Press button
LSBLG/MC IOMM
to Main page.
Press button to set the water system.
Fig 4.10 Water System Setting
Cool Fan Cooling Tower Fan
Cool PP Cooling Water Pump
Chill PP Chilled Water Pump
When the unit is standing-by, press the relevant button to start or stop the relevant equipments. This function is for starting the water system before start the unit, only for commissioning the water system.
Press button to back to User Setting Page.
4.6.5 Parameter Check
Input button on the main page to go into the Parameter Check Page as following
picture:
Fig 4.11 Parameter Check Page
LSBLG/MC IOMM
Fig 4.12 Output Page
Legend:
Cool Fan Cooling Tower Fan
Cool PP Cooling Water Pump
Chill PP Chilled Water Pump
Alarm Alarm
Comp. Compressor
25% Valve 25% Electromagnetic Valve
50% Valve 50% Electromagnetic Valve
75% Valve 75% Electromagnetic Valve
Liquid V. Liquid Electromagnetic Valve
Running Running Indicator
Fig 4.13 Input Page
Legend: Tele Start Remote Start
Tele Stop Remote Stop
Chill WF Chilled Water Flow
Cool WF Cooling Water Flow
High Pre High Pressure Protection
Low Pre Low Pressure Protection
Overload Overload Protection
Motor Internal Protection
LSBLG/MC IOMM
Oil LP Oil Level Protection
Anti-freez Anti-freezing Protection
Oil DP Oil Pressure Difference Protection
Phase Phase Protection
4.6.6 Warning and Protection Page Press WARN button at the running state page to enter the real-time warning page:
Fig 4.14 Warning and Protection Page
This page monitors the warning and protection state (time and name) of chiller system. If
there is a warning, the warning bell will ring. Then you can press MUTE button to shutdown
the ring, but the protection continues. When chiller system comes back from protection state,
you must press RESET button to reset the warning system, and then restart the chiller.
Press MAIN PAGE to close warning page and back to running state page.
4.6.7 Trend Curves Page Press CURT TRND button at the running state page to enter the TEMPERATURE TREND
page as follow:
Fig 4.15 Trend Curve Page
This page displays 4 real-time temperature of the system. The lower number is current value of the check point. The color and the linetype of curves are same as the ones under the relevant text of temperature. Press MAIN to close trend curve page and back to running state page.
LSBLG/MC IOMM
4.6.8 Data Report Page Press DATA REPT button at the running state page to enter the data report page shown as
follow:
Fig 4.16 Data Report Page
History records of 4 temperature data (from the left to the right: inlet chilled water temperature,
outlet chilled water temperature, inlet cooling water temperature, outlet cooling water
temperature) are saved in this page. You can check the history records of the temperatures
by dragging the scroll bar on right side.
Press MAIN to close this page and back to running state page.
LSBLG/MC IOMM
5. Maintenance
5.1 Routine Check
Make a routine record for each unit for recording the running and analyzing any possible problem.
Item Frequency Method Remark
General Items
Noise At any time Listen Stand at 1 m from
the unit to observe Vibration At any time Observe to see whether there is
vibration with high amplitude
Voltage of power
supply At any time Within ±10% of rated voltage
Appearance
Cleaning At any time Keep the unit clean
Rust At any time Do scaling with iron brush and
cover it with antirust paint
Stableness At any time Fasten every screw
Insulating
material flakes
off
At any time Stick them with adhesive
Water leakage Monthly Check whether the drainpipe is
blocked
Compressor
Noise At any time No noise when starting, running or
stopping
Insulation
resistance Yearly
It should be over 5MΩ when
measuring with ohmmeter of
DV500V.
Shockproof
rubber gets
ageing
Yearly It should be elastic when touching.
Middle
inspection
Once per 3000
hours
Pay attention to noise, vibration
and oil level.
Middle
inspection
Once per 6000
hours
Confirm the operation of safety
device and protection device
Condenser
Cooling water
Flow
Temperature
Water quality
At any time
Monthly
Adjust the water flow to keep the
pressure within fiducial value.
Keep it within fiducial value.
See Fig. I
Refer to
relationship chart
between water
quality and scale
Cleanness At any time Keep high pressure within fiducial
value.
Drainage At any time Drain the water before longtime
rest.
Water in pipes
should be also
drained.
Evaporator
Chilled water
Flow
Temperature
Thickness of
antifreeze
Water quality
At any time
Monthly
Monthly
Within fiducial value
Above set thickness
Within fiducial value
See Fig. II
Refer to
characteristic of
antifreeze
Refer to
relationship chart
between water
quality and scale
Cleanness At any time Keep low pressure within fiducial
value. See Fig.Ⅱ
Drainage At any time Drain the water before longtime
rest.
Water in pipes
should be also
LSBLG/MC IOMM
Item Frequency Method Remark
drained.
Thermal
Expansion
Valve
Performance Monthly
The pressure on low-pressure side
does not change when unscrew or
fasten the screw on expansion
valve.
Refer to Fig. I, II
or running pressure
High and Low
Pressure
Switch
Performance Monthly Check according to “performance
of protection device”.
Check whether
every joint is in
good condition.
Pressure
Gauge Performance Yearly Ditto
Operation
Valves Pointer Half-yearly
Compare with the accurate pressure
gauge.
Refrigeration
Cycle Performance Monthly The opening and closing are good.
Electrical
Control
Refrigerant
leakage Monthly
Seek the leakage on the unit and the
pipe joint with leak detector.
Expel the water from condenser and
evaporator and seek leakage on
water inlet and outlet.
Seek-leak can be
done with
electronic detector,
torch detector or
soap water.
Insulation
resistance Monthly
It should be over 1MΩ when
measuring with ohmmeter of
500VDC.
Conductibility of
wire Monthly
Insulating layer should be intact
and well connected. The bolts are
fastened.
Electromagnetic
contactor Monthly
No spark or buzz sound when
pressing ON/OFF of contact
repeatedly.
The interval
should be more
than 3 minutes or
the contact may be
damaged
Rotary switch Monthly Works normally.
Auxiliary relay Monthly Works normally.
Time-limit relay Monthly Works normally.
Table 5.1 Routine Check Table
High pressure: See the following figures for the relation between pressure and outlet cooled water temperature; (The pressure below 12Kg/cm2G or above 18Kg/cm2G is considered abnormal.)
12
2
14
16
18
20
22 24 26 28 30 32 34 36
Outlet cooled water temp.(°C)
Hig
h p
ressure(kg/cm G)
The more the scale on
condenser, the high the
pressure will be.
25
2 20
15
10
20 25 30 35 40
Outlet cooled water temp.(°C)
Hig
h p
ress
ure(kg/cm G)
Saturation curve
This area should be cleaned.
FIG I Full load high pressure
LSBLG/MC IOMM
Low pressure: See the following figures for the relation between pressure and outlet chilled water temperature; (The pressure below 3Kg/cm2G or above 6Kg/cm2G is considered abnormal.)
6
2 5
4
3
5 7 9 11 13 15
Outlet chilled water temp.(°C)(evaporator)
Lo
w p
ress
ure(kg/cm G)
8
2
6
4
25 10 15
Outlet chilled water temp.(°C)(evaporator)
Low
pre
ssure(kg/cm G)
Saturation curve
This area should be cleaned.
FIG II Full load low pressure (standard)
5.2 Charge the Lubricant
The lubricant can be charged with special oil pump or pushed by the atmosphere pressure while vacuum work. It can be charged from the charge port above the oil groove or from the low pressure gas charge port when the unit is running. Use a pump to charge the lubricant into a high pressure system. Be sure there is enough lubricant oil inside the oil tank of the pump before connect the charging hose to the charging port. Drain the air out of the charging hose with the refrigerant, then turn on the pump to start charging. During the charging, the open of the suction pipe cannot be higher than the oil level to avoid the air going inside. After charging, shut off the valve and the oil pump. Clean the pump and store it for next charging work. If charging the lubricant into an empty system, you can vacuum the system firstly and then make the oil pushed into the system by atmosphere pressure. Connect the charging hose to the charging port of the unit, and put the other side of the hose into the lubricant oil. When the pressure difference between the system and the atmosphere is enough, the oil will goes into the system automatically. When charging work completes, shut off the valve of the charging port to avoid the water inside the air to go into the system. Store the lubricant inside the dry and closed container and put it where the sunshine cannot touch. Seal the container to avoid the water inside the air to go into it. The lubricant oil with different model no cannot be stored and used together. Charge the lubricant oil according to the compressor’s rating label. Check the quality of the oil seasonal, drop some oil on the white bibulous paper. If the center of the oil drop is black, it means the lubricant oil cannot be used and should be changed. Superfluous lubricant will reduce the heat exchange efficiency so that the capacity reduces.
5.3 Charge the Refrigerant Gas
The refrigerant can be charged with special charging machine or be directly charged with the gas cylinder. Before the charging work, be sure there is no leakage at the system and the vacuum of it is enough. You can make a mensurable charge work with the charging machine. Connect the charging pipe to the gas charging port of the unit, set the quantity and start the machine. After the charging, seal the port of the unit. If you charge the gas directly with a gas cylinder, you should add a pressure gauge on the pipe between the cylinder and the unit. The cylinder should be put aslant or upside-down for making the liquid refrigerant go into the system rapidly. Watch the pressure gauge, if the
LSBLG/MC IOMM
pressure of the cylinder is same as the system, the charging work cannot go on. Then you can use hot water to shower the cylinder or use a heater to heat the cylinder to increase the pressure inside it. Besides, you can charge the rest of the gas from the low pressure side of the system (behind the expansion valve) while the unit is running. Before charging, push the air inside the connection pipe with a little refrigerant inside the cylinder. If the refrigerant is liquid, you should control the valve to avoid the liquid gas to go inside the compressor which will lead to damage. We suggest charging refrigerant gas while the unit is running for safety.
5.4 Change the Core of the Dry Filter
Close the turnoff valves on both sides of strainer. (If there is only one turnoff valve on one side, refrigerant should be recycled.)
Expel a little refrigerant in drying strainer. Open the cover of drying strainer. Remove the old drying core and fit it with a new one. Install the cover of drying strainer and fasten the bolt. (Please make sure the gasket is
intact.) Vacuum the drying strainer. Open the turnoff valves for starting.
5.5 Maintenance of Bearing of the Compressor
The key of the maintenance of the bearing is the lubricant system. Special lubricant oil should be in use and should maintain a certain oil level and temperature, which should be checked periodically. The abrasion of the bearing can be told by the vibration of the compressor. If there is a heavy vibration of the compressor, please contact Midea Service Department for vibration analysis.
5.6 Check the Rotors of Compressor
The abrasion of the rotors of the compressor can be told by the capacity drop. If the capacity reduces too much, please ask some professionals to check the rotors. This check can be carried out every 5 or 10 years or determined by the real situation.
5.7 Check the Heat Exchange Tubes
The open type water circuit will easily lead to fouling of the heat exchange tubes, which will reduce the heat exchange efficiency so that the capacity of the unit will reduce and the power consumption of the compressor will increase. Soft water is strongly recommended to use in the system. The check and clean the tubes should be carried out every 3 running months. If the water is polluted, it should be more frequently. Use a rotary clean tool to wash the heat exchange tubes because there are screws inside the tubes. According to the check result, you can make sure if the water treatment devices are efficient and determine the period of clean. Always check if there is fouling or rust at the water temperature sensor. NOTE:
Before clean, you should isolated the part you want to cleaned from the system; After clean with the chemical detergent, the tubes should be washed with a lot of water
to dilute the detergent inside the tubes until the PH of the water back to 6-8; Special brush should be used to clean the tubes to avoid to damage the tubes.
LSBLG/MC IOMM
5.8 Electrical Control Cabinet
NOTE: Before maintain the electrical parts, the power supply should be cutoff.
The stuff who maintains the control cabinet should be aware of the circuit diagram and the sunning principle of the unit. The electrical parts need no special maintenance, it is just necessary that checking and tightening the connection wires every month. To ensure the normal running of the unit, the control cabinet should be electrified at least one hour every half year. WARNING:
IF THE WIRING WORK IS NOT CARRIED OUT ACCORDING TO THE INSTRUCTIONS, THE QUALITY GUARANTEE WOULD BE INVALID. IF THE FUSE IS BROKEN OR PROTECTION RELAY IS OFF, IT MEANS THERE IS SHORT-CIRCUIT OR OVERLOAD OF THE SYSTEM. BEFORE CHANGE THE FUSE AND RESTART THE COMPRESSOR, THE FAULTY MUST BE FOUND OUT AND FIXED. THE CONTROL CABINET SHOULD BE REPAIRED BY PROFESSIONALS. IF THERE IS SOME DAMAGE LED BY WIRING CHANGE, MIDEA WILL NOT BE RESPONSE FOR IT.
5.9 Seasonal Maintenance 5.9.1 Stop in Winter
When the ambient temperature reduces to freezing point in winter, the water inside the condenser and evaporator should be all drained out to avoid the damage to the heat exchange tubes led by ice. Be sure the water supply valves would not be open. If the cooling tower is in use and exposed in the ambient as well as the water pump, the water inside the cooling tower and pumps should be drained out. Check if there is rust on the surface of the unit. If there is, the rust must be got rid of and repaint the point. The end cover of the condenser and the evaporator should be open and check and clean the tubes at least once a year.
5.9.2 Start in Summer
Before start a unit stops for a long time, the insulation resistance should be measured with a
500V high-resistant meter, and the value should be higher than 10MΩ. The unit should be
electrified for at least 8 hours to ensure the oil temperature is higher than 23℃.
The control circuit should be electrified unless maintenance. If the oil temperature reduces because of power off, then the oil should be heated for 24 hours before the unit start. Check the electrical components, fix any loose connection.
If the drain plug of cooling pump is got rid of when the unit stop, change a new plug. Install a new fuse inside the breaker if the old one is taken out. Open the water supply valve.
5.10 Anti-freezing Protection in Low Ambient Temperature 5.10.1 Anti-freezing Protection of the Evaporator When the unit stops in winter, the water inside the unit should be all drained out. Wash the evaporator with ethylene glycol to avoid freezing. All chilled water pipes should be heat-insulated well. Before this work, please contact local dealer of Midea for correct instructions.
LSBLG/MC IOMM
5.10.2 Anti-freezing Protection of the Condenser If the cooling water is lake water or the water valve is exposed in the outdoor cold air, the temperature inside the condenser is possible lower than the indoor temperature. All the cooling water should be drained out and the water system should be washed with ethylene glycol to avoid freezing.
5.11 Common Faulty Diagnosis The control system of LSBLG/MC screw chiller has many functions about faulty diagnosis. All the running parameter can be checked with the human-machine interface. If there is a faulty, the control system will give out a warning and it will be recorded in the history warning page for checking.
5.11.1 Reset of Warning
When the faulty is repaired, the unit cannot start until the reset button is pressed. There are 2 modes (auto and manual) of reset. Even the unit is running, the reset can be operated.
5.11.2 Troubleshooting Table 5.2 Troubleshooting
Symptom Cause Treatment
1. Compressor cannot
work
No power;
Switch works (over current);
Starting switch failure;
The fuse is melted;
Interlocking device does not work;
High/low pressure switch work
Switch on the power after checking;
Find out the cause. Replace the switch or adjust
the voltage.
Examine and replace it
Replace it
Check if the fan of cooling tower and all the
water pump work, if not, make them run.
Adjust the pressure.
2.The unit stops
immediately after
starting
High/low pressure switches work Insufficient cooled water in condenser. Add
water into it.
Expel the incondensable air from condenser.
Clean the expansion pipe or replace it if it is
damaged.
Clean the cooled water strainer.
3. Discharge pressure
is too low
Insufficient refrigerant;
High degree of superheat of
expansion valve;
Excessive cooled water or the water
temp. is too low;
Drying strainer is blocked.
Check the leakage and add the refrigerant into
the unit.
Adjust it.
Adjust the water volume.
Replace and clean the filter.
4. Over high discharge
pressure
Excessive refrigerant;
Incondensable air inside;
Bad effect of cooling tower;
Water pump is damaged;
Pipes of condenser are dirty;
High-pressure gauge can not indicate
precise figure;
Insufficient cooled water;
Expel some refrigerant.
Expel the air.
Check it and do reparation.
Repair it.
Do cleaning.
Replace a new gauge.
Replenish the water.
LSBLG/MC IOMM
Symptom Cause Treatment
Strainer of cooled water is blocked. Do cleaning.
5.Suction pressure is
too high
Chilling overload;
Low degree of superheat of
expansion valve;
Excessive refrigerant.
Adjust the load.
Adjust it.
Expel some refrigerant.
6.Suction pressure is
too low
Insufficient refrigerant;
Blocked by desiccant;
Chilling load is too low;
Insufficient chilled water;
Strainer of chilled water is blocked.
Check the leakage and add the refrigerant into
the unit.
Replace and clean the filter.
Adjust the load.
Replenish the water.
Do cleaning.
7. Capacity adjusting
device failure
Thermostat failure;
Solenoid valve is damaged;
Capillary tube is blocked.
Replace it with a new one.
Replace it with a new one.
Do cleaning.
8. Compressor
overheat
Defective bearing of compressor;
Over high pressure on liquid side;
Temp. and pressure of refrigerant on
gas side is too high;
Electromotor is overheated.
Replace the compressor.
Refer to item 4.
Adjust the pressure on gas side and the
unfolding degree of solenoid valve.
Refer to item 10.
9. NFB jumps
Short circuit of wiring.
Wiring is grounded.
Electromotor of compressor failure.
Measure the insulation resistance.
Ditto.
Measure the grounding insulation resistance and
phase insulation resistance.
10. Over loading relay
of compressor
electromotor works
NFB jumps, unit runs with single
phase power;
Voltage too high or too low,
unbalanced voltage;
Defective solenoid switch cause the
unit run with single phase power;
Defective electromotor;
Temp. inside distribution box is too
high;
Over high running pressure;
Compressor starts frequently;
Insufficient chilled engine oil in
compressor.
Check it.
Check the distribution box.
Repair or replace it.
Repair or replace it; if it is burnt, clean the
refrigerant pipelines.
Keep the temp. below 40℃.
Refer to item 4 and 5.
Check all the automatic devices.
Clean the oil filter.
5.13 Clean Procedure 5.13.1 Relation between water quality, scale and degree of corrosivity:
Water Quality Scale Corrosivity Remark
1 PH≤6 Acid water Hard Strong Generates insoluble CaSO4
2 PH≥8 Alkali water Soft ——
Soft fluid deposit may be
caused by ions iron or
aluminum
3 Water with much Ca2+
and Mg2+
Hard —— Easily generates hard scale.
4 Water with much Cl- Dirt Ultra-strong Corrosive to copper and iron.
5 Water with much SO42-
and SiO22-
Hard Strong Generates hard CaSO4 and
CaSiO2
6 Water with much Fe3+
Large quantity,
hard Strong
Generates deposits Fe(OH)3
and Fe2O3
7 Odorous water Large quantity Ultra-strong Generates sulfide, ammonia
LSBLG/MC IOMM
and marsh gas, especially H2S
which has great corrosivity to
copper.
8 Water with organic substance Large quantity —— Easily generates scale
9
Exhaust gas from auto, chemical
factory, plating factory, sewage
plant, ammonia refrigeration plant
and fiber factory
Strong
Copper tubes of condenser may
be eroded and perforated.
10 Dusty places such as plastic plant Large quantity
11 Sulfurous gas in the air Ultra-strong
12
Natural pollution such as damp air
near the coast or insects in the
field goes into cooling tower.
Large quantity Strong
Table 5.3 Relation between water quality, scale and degree of corrosivity
Cycle under normal temperature (A): (Capacity of condenser+ Capacity of pipe+ Capacity of container) ×1/3(Thickness of detergent 33%)
Cycle under normal temperature (B): (Capacity of flume of cooling tower+ Capacity of
condenser+ Capacity of pipe)×1/10(Thickness of detergent 10%)
In case doing cleaning after the unit stops, the capacity of flume of cooling tower can be 1/2 or 1/3 of rated value; if doing cleaning as the unit is running, the capacity should achieve rated value.
Precautions on usage of detergent When doing cleaning, please wear rubber gloves and do not expose your
skin or your clothes to the detergent. In case touching the detergent, please wash it with clean water.
The container for detergent should be made of plastic or glass rather than lead.
The used detergent should be neutralized with lime or soda before draining into drain channel.
Detergent is harmful to human; please keep it away from children. Turn on the unit after cleaning to ensure it is clean. If necessary, please do
cleaning again.
5.13.2 Wash the Shell and Tube Heat Exchanger Stop the unit and the cycling water pump, shut the connection between the unit and the water system and form a water circuit with a anti-acid water pump showed as Fig 5.1;
Tank Waste Tank
Connection Pipe
Washing Fluid
PumpChilled Water
Inlet
Chilled Water
Outlet
She
ll an
d T
ube
Hea
t Exc
hang
er
Connection Pipe
Fig 5.1 Connection Diagram of Cleaning of the Water System
LSBLG/MC IOMM
Fill clean water inside the tank and start the pump. Check if there is a leakage or strange noise in the system and make the clean room ventilated well. Do some protection for the equipments surrounded to avoid the clean detergent to damage them. Drain all the water out of the A/C system and fill it with clean water as well as the detergent. Start the anti-acid pump for a period which is determined according to the detergent and the fouling to make the water cycled to clean the system. Stop the pump and drain out the polluted water to the waste tank. Then fill clean water into the tank and start the pump to wash the system with clean water. Measure the PH value of the water with PH test paper. Add some neutralizer step by step until the PH value is 7, and then keep the pump working for a while for completing the neutralization reaction. Use clean water to wash the system again after drain the polluted water out until there is no water with fouling going out. Add some neutralizer into the waste water tank and contact some special company to treat the waste water. Connect the unit into the system again and make sure the unit can work normally.
Note for the detergent: Wear a pair of rubber gloves when making the wash work. DO NOT make the detergent touch the cloths, face or body. If so, please wash it with clean water immediately. The container for detergent should be rubber or glass bottle, never use plumbous can. The used detergent should be neutralized with calcareousness or soda, and then contact special waste-treatment company to treat it. The detergent will do harm to human body, never put it where children can touch. Confirm the washing effect before start the unit again. If this effect is not so good, the exchangers have to be washed again.
LSBLG/MC IOMM
6. Appendix
6.1 Outline Dimension Diagrams
Single Compressor Serried Unit
chilled water outlet chilled water inlet
cooling
water outlet
AB
C
D
E
KJ
H
GF 50
cooling
water inlet
foundation bolt
4-M20×220
Mode
LSBLG A B C D E F H J K
Cooling
water
Inlet/outlet
Chilled
water
Inlet/outlet
115/MC 2940 800 1740 1400 520 2140 810 187 200 DN80 DN80
170/MC 2940 800 1770 1600 520 2200 830 210 225 DN100 DN100
275/MC 2970 850 1880 1600 570 2180 900 203 225 DN100 DN100
Single Compressor Paratactic Unit
chilled water outlet chilled water inlet
coolingwater outlet
water inletcooling
foundation bolt
4-M20×220
C A
K
D
J
B
E
H
GF
Mode
LSBLG A B C D E F H J K
Cooling
water
Inlet/outlet
Chilled
water
Inlet/outlet
350/MC 2995 1350 1480 1600 1250 2180 450 240 200 DN125 DN125
420/MC 3600 1380 1540 1800 1250 2180 450 215 250 DN125 DN125
560/MC 3600 1390 1660 1800 1250 2790 468 235 250 DN125 DN125
650/MC 3600 1450 1720 1800 1350 2680 545 255 285 DN150 DN150
LSBLG/MC IOMM
Dual-compressor Paratactic Unit
chilledchilled water
coolingwater outlet
coolingwater inlet
foundation bolt
4-M20×220
C A
KD
E
B
J
FG
H
inletwater outlet
Mode
LSBLG A B C D E F H J K
Cooling
water
Inlet/outlet
Chilled
water
Inlet/outlet
700/MC 3800 1570 1720 1800 1440 2680 540 248 285 DN150 DN150
840/MC 4400 1500 1690 2000 1440 3100 550 258 284 DN150 DN150
975/MC 4400 1540 1740 2000 1440 3130 575 265 250 DN150 DN150
1120/MC 4800 1670 1740 2000 1540 3080 615 294 240 DN150 DN150
1300/MC 4800 1740 1865 2000 1640 3080 640 315 340 DN200 DN200
LSBLG/MC IOMM
6.2 Refrigeration Circuit Diagram
Single-compressor Unit
Condenser
Compressor
Evaporator
Dry-filter
Cooling Water Out
Cooling Water In
Chilled Water Out
Chilled Water In
Thermoswitch
Low-pressure GaugeHigh-pressure Gauge
Pressure Controller
Dual-compressor Unit
Condenser
Compressor
Evaporator
Dry-filter
Cooling Water Out
Cooling Water In
Chilled Water In
Low-pressure GaugeHigh-pressure Gauge
Pressure ControllerCompressor
Dry-filter
Chilled Water In
Low-pressure GaugeHigh-pressure Gauge
Pressure Controller
Condenser
LSBLG/MC IOMM
6.3 Electrical Circuit Diagram
Diagram 1 for single-compressor, 4-step control unit
Fan Motor
Current
Switch
Voltage
Switch
Inside the
wiring box of
motor
Internal
Protection
Switch
Discharge-Temp
Protection Switch
LSBLG/MC IOMM
Diagram 2 for single-compressor, 4-step control unit
LSBLG/MC IOMM
Diagram 3 for single-compressor, 4-step control unit
LSBLG/MC IOMM
Diagram 1 for single-compressor, continuous control unit
Current
Switch
Voltage
Switch
Inside the
wiring box of
motor
Internal
Protection
Switch
Discharge-Temp
Protection Switch
Loading electromagnetic valve
Start electromagnetic valve
Unloading electromagnetic valve
Liquid electromagnetic valve
LSBLG/MC IOMM
Diagram 2 for single-compressor, continuous control unit
LSBLG/MC IOMM
Diagram 3 for single-compressor, continuous control unit
LSBLG/MC IOMM
Diagram 1 for dual-compressor, 4-step control unit
LSBLG/MC IOMM
Diagram 2 for dual-compressor, 4-step control unit
LSBLG/MC IOMM
Diagram 3 for dual-compressor, 4-step control unit
LSBLG/MC IOMM
Diagram 4 for dual-compressor, 4-step control unit
LSBLG/MC IOMM
Diagram 1 for dual-compressor, continuous control unit
LSBLG/MC IOMM
Diagram 2 for dual-compressor, continuous control unit
LSBLG/MC IOMM
Diagram 3 for dual-compressor, continuous control unit
LSBLG/MC IOMM
Diagram 4 for dual-compressor, continuous control unit
LSBLG/MC IOMM
6.7 Pressure Enthalpy Chart of R134a