BRS2111(2.1M) Outdoor Power System 1 Telecom Power RBS2111 (2.1M) Outdoor System NTBU

Transcript of 01 2 rbs2111 2-1 m od system

Page 1: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

1

Telecom Power RBS2111 (2.1M)

Outdoor System

NTBU

Page 2: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

21

Telecom Power System

Telecom Power SystemTelecom Power System

AC

Distribution U

nit

Rectifier # 1

Control Supervisory Unit (CSU)

LOA

D (Sw

itch ,AD

SL…E.T.C

.)

Output D

C D

istribution Unit

LVDS

Rectifier # 3

Rectifier # 2

Rectifier # N

Battery

AC Input

Generator

U.P.S

Page 3: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

3

ContentsSystem Overview

Main Features /Configuration

Outdoor Cabinet type (2.1M)

Power Distribution configuration (AC,Surge , DC Load , Battery.

Rectifier Power shelf configuration

Rectifier module specification (DP2700)

New Smart CSU controller with LCD Display

System Function Introduction

Delta Remote/Monitor function

-- NRMS monitor software (RS-232 port)

-- Web Server/ SNMP function (Optional)

Q&A

Page 4: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

4

Delta DPS 2700 Series Power System

Main Features:AC Input: Optional for three conditions

1. 220Vac, Single phase (Already) 2. 380Vac, Three phases / Five Wire ( Y Connection)

System Capacity: -54Vdc / 150A Max. IP Protect:Power Battery Space: IP54, Equipment Space: IP55DC Distribution: Load Breaker Configurations: Breaker (DIN rail ), Battery Breaker: ~125A Breaker, 2 Positions Max.LVDB *1 (Standard): 150A on Battery SideLVDL *1: 150A on Load SideRectifier: -54Vdc/50A (DPR2700) *3Controller: New Smart CSU with LCD Relay Output: Total 8 Positions, Customer DefinableLocal/Remote Monitoring and Control – NRMS software

− Local Access: By NRMS via RS232 Interface− Internet Web Server Function: By Web Server Software/SNMP via RJ45 Interface

(Optional)System Dimension (W*D*H): 55.1” x 29.6” x 29.6” inch / 2100 x 750 x 750mmOperating Temperature: 0℃~+55℃(32℉~131℉)

Page 5: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

5PDU (Several Configurations)

Rectifier ESR-48/56A

Battery & Base

New Smart CSU (Main Board))

New Smart CSU (Relay Board))

19” Rectifier Shelf (SB-05N/HG A )

Heat-exchange

CCU (Climate Control Unit )

Fan Tray

Page 6: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

6

RBS2111 Outdoor System Drawing

Page 7: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

7

Delta Power System Drawing

Page 8: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

8

Delta Power System Drawing - Cooling

Page 9: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

9

RBS2111 (2.1M) Outdoor System Overviews

Dimension: W750mm * D750mm * H2100mmTwo-walled aluminum alloy (5052-H32) constructions (Cabinets)IP54: Power system & battery compartment , IP55: Equipment compartmentPlinth: Steel with powder coating Enclosure/Plinth’s color: Ericsson LMY 904, (NCS2502)Eyebolts inside removable roof

W

H

D

Delta P/N: ESOA150-ABB01 (Average capacity case)Delta P/N: ESOA150-ABB02 (High capacity case)

Average capacity case expandableTo High capacity case adding Another Hex

Estimated Weight: 155Kg (with Power system)

Equipment Compartment

Power system and Battery compartment

Page 10: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

10

HEXAverage capacity case : 2pcs HEXHigh capacity case : 3pcs HEX

RBS2111 (2.1M) Configurations

Fan tray mounted on inside of side panel

Power system

Changeover SwitchClimate Control Unit

Genset Socket, 32A 3N~(R,S,T,N ,PE)

Air filter

TransmissionEquipment

10U(H) x 19”(W)208(D) Maxi.

Partition

Equipment Compartment

Power system and Battery compartment (Battery excluded in cabinets)

(Battery excluded in cabinets)

2nd Battery ShelfMax. Space suitable forCSB TPX122200 * 4pcs

1st Battery ShelfMax. Space suitable forCSB TPX122200 * 4pcs

Smoke Sensor

Humidity Sensor

DC Light mounted on inside of Frame

Page 11: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

11

RBS2111 (2.1M) Cable Entries 7pcs of Side cable entries reserved

6pcs of Compartment cable entries reserved

5pcs MG32A 3-hole Cable GlandsFor cable range (OD 5~10mm)

1pce MG25A 1-hole Cable GlandFor cable range (OD): 10~16mm

1pce MG32A 1-hole Cable Gland For cable range (OD): 15~22mm

3pcs MG32A 3-hole Cable GlandsFor cable range (OD): 5~10mm

2pce MG25A 1-holeFor cable range (OD): 10~16mm

1pce MG32A 1-holeFor cable range (OD): 15~22mm

4pcs of bottom cable entries reserved

3pcs MG32A 3-hole Cable Gland For cable range (OD): 5~10mmFor AC Terminations

1pce MG25A 1-hole Cable Gland For cable range (OD): 12~16mmFor DC grounding cable

Page 12: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

12

Grounding bus bar Location and Grounding cable path

Grounding BUS Bar4pcs M6 insert nut pre-installedFixed on plinth and equipment bay

Page 13: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

13

Grounding bus bar Location and Grounding cable path

Grounding cable pass through cable gland from equipment compartment to power system compartment.

Pass through bottom cable gland link to grounding bus bar which fixed on plinth.

Page 14: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

14

Plate (1pcs):Pre-install on right sideDesign to block unused side

RBS2111 (2.1M) AC Cable Entry on Both Sides

AC cables pass through left side of plinth.

New requirement:AC cables can pass through right side of plinth.

AP32

Page 15: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

15

Cabinet Mountings

600

83

705

Anchor Pattern and Footprint 15mm X 4

: Footprint Area

35

550

71283

35

Installation template (1pcs) for RBS2111 system along with first shipment

(2.1M and 1.6M systems are the same template.)

Page 16: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

16

Recommended Spare Parts & Part Numbers

 

RBS 2111 2.1MESOA150-ABB01,02

Remark

CU-18A A-SClimate Control Unit V

3790335100-SController(NCSU)-LCD Display V

5505602118-SController(NCSU)-Main Board V

ESR-48/56A A-SRectifier 2700W (DPR2700) V

3790335000Temperature Sensor Cable 3M V

EX-F01 B-SFan Tray V

EX-H01 A-SHeat Exchanger 22W/K

(Delta HEX)V

Air Filter G33243139500 V

Heat Exchanger160W/K

50400000196NA

Model NameSpare parts(Delta P/N)

Page 17: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

17

SMR Shelf 19” H type

SB-05N/HG A DPS 2700 shelf 54V/150A

W x H x D=19 x 1.7 x 11.7 inch =483 x 44 x 297.8 mm

Page 18: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

18

Features and Benefits-48V/41.7A, Output; Max. Power 2000W

Wide Input Voltage Range (90V~300V)

Power Factor Correction (>0.99)

Hot-pluggable, All Connectors are at the rear

Compact Size

≅ 24W/in3 (48V) Power Density

Dimension:42mm/1U(H)*125.5mm/2.8U(W)*268mm(D)

Light weight:1.64 Kg (4.4lb)

Horizontal(1U)/Vertical(2.8U) Models Available

High Efficiency: >91% (48V)

Fan cooling and Easy replaceable fan design

Operation temp.:-5oC~+65oC

UL/CUL,TUV/CE Certificated

DP 2000 Series Rectifier

Page 19: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

19

Rectifier - Interface

I/O ConnectorOutputSignalInput

Load Sharing Bus IBUSD2

ID digitalIDDD1

ID analogIDAC2

Short pin for well connectionINHC1

Communication groundCGNDB1

RS 485 + communicationRS485+A2

RS 485 – communicationRS485-B2

Signal ground SGNDOA1

DC Output “+”VO+P8-P10

DC Output “-”VO-P5-P7

Precharge VOPP4

DescriptionSignal Pin Number

AC main, frame groundFGP3

AC main, N terminalAC_NP2

AC main, L terminal AC_LP1

DescriptionSignal Pin Number

Page 20: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

20

RS-485

New Smart CSU: DPS 2700 Series

Configuration,Supervision Terminal Interface

Web/SNMP Card

Ethernet

Configuration,Supervision

(web browser)

54Vdc/50A With SMR

AnalogSignal Detection

LCD Display

RS-485 X 3 With SMR

RS-485 With SMR

AnalogI.D address

Page 21: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

21

Easy integration with most Delta power systemsModular system controllerUser friendly operating interface

Large 128 x 64 pixel LCD Display Entry of alarm and system parameters from keypad

High reliable RS-485 communication with RectifierEasy system expansion

Easy extendable custom-design I/O boardComplete function support

More then 100 system events logTemperature & Voltage compensation chargingSmart Battery managementGreen Function

Different possibilities for remote monitoring1 outside communication port (RS-232) DB9Local Access monitoring & ControlWeb Server Function (RJ-45)

Power System Controller – New Smart CSU

User Interface

Page 22: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

22

Delta Power System Monitoring & Control

Build in HTTP Web Server

AC Distribution Rectifiers

DC Distribution Battery Management

Environment Data

Acquisition

Control &Supervisory

Unit

Client User Client User

Internet

Telecom Power Manage Program

Local

Client User

Mini USB

Page 23: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

23

Local Access

Mini USB

NRMS Monitor software

Page 24: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

24

Web Server Function and Feature (Optional)Features:

Applied in TCP/IP Internet/Intranet Environment

Complete Supervising to Power System

User-friendly Graphic Interface

Dynamic information presentation

Password function

Multi Language Support

Microsoft Explorer and Netscape SupportMain Screen

StatusParameter Setting

Alarm Configuration

Page 25: 01 2 rbs2111 2-1 m od system

BRS2111(2.1M) Outdoor Power System

25