@�0 INSTALLATION OPERATION 1W ; 1 INSTRUCTIONS �2 . * I.L. 41-2778 MAINTENANCE TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been inserted for the purpose of securing the parts during shipment. Make sure that all moving parts operate freely. I nspect the con- tacts to see that they are clean and can close properly. Operate the relay to check the settings and electrical connections. APPLICATION A COQ relay operates to disconnect a genera- tor from a faulted line before negative sequence currents can damage the machine. CONSTRUCTION D OPAON The type COQ relay consists of an induction disc type overcurrent element, a contactor s�itch, an operation indicator, and a negative sequence current filter. OVERCURRENT ELEMENT This is operated by an induction-disc type element negative sequence quantities supplied to an electromagnet in the rear of the relay. A voltage is induced in the secondary coil of this electromagnet by trans- former action of the main coil. Both coils are located on the center leg of the electro- magnet. Current flow is from the secondary coil to coils on the outer legs of the elec- tromagnet. The reaction between the outer leg coil fluxes and the main coil flux creates an operating torque on a spiral shaped aluminum disc mounted on a vertical shaft. The vertical shaft is supported to the ele- ment frame by a pin and end stone type bearing on the lower end and a pin and olive bearing on the upper end. Both shaft bearings as well SUPERSEDES I. L. 41-277A enotes changed from superseded issue. as their 2djustable pins are removable. A set screw and nylon plug locks the bottom pin in position, and a sho�lder nut of the time dial locks the top pin in position. Attached to an insulated section of the disc shaft is a rigid arm holding a small silver hemisphere. This combination of arm and silver hemisphere comprises the moving contact assembly which is part of an elec- trical circuit. This circuit is completed by a spiral spring with one end soldered to the rigid arm and the other end fastened to a slotted spring adjuster which in turn fastens to the element frame. The stationary contact assembly consists of a silver contact attached to the free end of the leaf spring. This spring is fastened to a Micarta block mounted on the element frame. A small set screw permits the adjustment of con- tact follow. Contactor Switch This switch is a small d-e solenoid type conneqted in series with the main contacts of the relay and the trip coil of a breaker. When the relay contacts close, the solenoid coil becomes energized and moves a cylindrical plunger upward. A silver disc is mounted on the plunger's lower end, and it bridges three contacts which are in parallel with the main contacts. The main contacts are thereby re- lieved of the duty of carrying tripping cur- rents. These three contacts remain closed until the trip circuit is opened by an auxili- ary switch on the breaker. Operation I ndicator The operation indicator is a small solenoid EFFECTIVE APRIL 1957 www . ElectricalPartManuals . com

Transcript of -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before...

Page 1: -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been

@�!10 INSTALLATION • OPERATION

10:W:;;1 INSTRUCTIONS � -- �2�---------------------------------------, ... * •

I.L. 41-2778

• MAINTENANCE

TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY

CAUTION Before putting protective relays

into service, remove all blocking which may have been inserted for the purpose of securing

the parts during shipment. Make sure that all moving parts operate freely. I nspect the con­tacts to see that they are clean and can close

properly. Operate the relay to check the settings and electrical connections.

APPLICATION A COQ relay operates to disconnect a genera-

tor from a faulted line before negative sequence currents can damage the machine.

CONSTRUCTION AND OPERATION The type COQ relay consists of an induction

disc type overcurrent element, a contactor

s�itch, an operation indicator, and a negative sequence current filter.

OVERCURRENT ELEMENT This is

operated by

an induction-disc type element

negative sequence quantities

supplied to an electromagnet in the rear of the relay. A voltage is induced in the secondary coil of this electromagnet by trans­former action of the main coil. Both coils are located on the center leg of the electro­magnet. Current flow is from the secondary coil to coils on the outer legs of the elec­

tromagnet. The reaction between the outer leg

coil fluxes and the main coil flux creates an

operating torque on a spiral shaped aluminum

disc mounted on a vertical shaft.

The vertical shaft is supported to the ele­

ment frame by a pin and end stone type bearing on the lower end and a pin and olive bearing

on the upper end. Both shaft bearings as well

SUPERSEDES I. L. 41-277A 4<])enotes changed from superseded issue.

as their 2djustable pins are removable. A set

screw and nylon plug locks the bottom pin in

position, and a sho�lder nut of the time dial locks the top pin in position.

Attached to an insulated section of the disc shaft is a rigid arm holding a small silver hemisphere. This combination of arm

and silver hemisphere comprises the moving

contact assembly which is part of an elec­trical circuit. This circuit is completed by a spiral spring with one end soldered to the

rigid arm and the other end fastened to a

slotted spring adjuster which in turn fastens

to the element frame.

The stationary contact assembly consists of

a silver contact attached to the free end of

the leaf spring. This spring is fastened to a Micarta block mounted on the element frame. A

small set screw permits the adjustment of con­tact follow.

Contactor Switch

This switch is a small d-e solenoid type conneqted in series with the main contacts of

the relay and the trip coil of a breaker. When the relay contacts close, the solenoid coil becomes energized and moves a cylindrical plunger upward. A silver disc is mounted on the plunger's lower end, and it bridges three

contacts which are in parallel with the main

contacts. The main contacts are thereby re­

lieved of the duty of carrying tripping cur­

rents. These three contacts remain closed

until the trip circuit is opened by an auxili­

ary switch on the breaker.

Operation I ndicator

The operation indicator is a small solenoid

EFFECTIVE APRIL 1957 www . El

ectric

alPar

tMan

uals

. com

Page 2: -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been

TYPE COQ RELAY

CONTACTOA SWI

/-TEST SJI'ITCH

- OVERCURRE!ff ELEMENT

3 Hl.wDIM>'S MUTl/Ai REACTOR!

ITHTHIH�;�DR:;_";�u CURRENT TEST JACK

L. -=--=-=-=--=----'---"�----'-TO BAS£ 7£RM9,

FRo.-vr V!E� CHA.S�JS OPERATED 26-D-1428 ShORT!'-"' SW/TCH

Fig. 1-Internal Schematic Of The COQ Relay In FT Case.

coil connected in the trip circuit. When the coil is energized a spring-restrained armature releases the white target which falls by gravity to indicate completion of the trip

circuit. The indicator may be reset from out­

side of the case.

Negative Sequence Current Filter

The negative sequence current filter con­

sists of a reactor and an adjustable resistor. These elements are connected in such a manner

that the output of the filter is proportional to the negative sequence input.

CHARACTERISTICS The COQ negative sequence relay is available

with the following negative sequence current

taps:

3 3-25 3-5 4.2 4.6 5.0

These tap values represent the current

transformer secondary amperes which corres­

pond to one per unit generator current. At

these values of negative sequence currents,

the moving contact will leave the time dial stop and reach the stationary contacts in a

time as determined by the time dial setting and as shown by Fig. 3· For example, with a

2

time dial setting of "4" the relay will close

its contacts in 30 seconds with the above tap

currents applied to the relay.

As shown by the curves of figure 2, the

relay's characteristic is defined by a genera-

tor characteristic I�T = K. The relay charac­

teristic is such that it coincides with the generator characteristic at l per unit nega­

tive sequence current but at higher values of negative sequence current, the relay charac­

teristic is substantially parallel and slight­

ly less than the generator characteristic. In this manner, a suitable margin of safety is obtained between the two characteristics.

Figure 2 defines the relay characteristics

for two generators - one with a permissible

constant of "3 0 " and the other with a constant

of "90". The time dial settings for these

constants are "4" and "11" Similar protection for other

I�T constants between "30"

respectively.

generators with

and "90" is ob-

tained by settings of the time dial. Figure 3 shows the necessary ti�e dial settings for

various I�T constants. By referring to this

figure, the time dial can be set so that the relay protects different generators whose l�T constants range from "30" to "90".

Typical operating characteristics

relay are shown in flgure 4. of the

* Minimum pickup of t�e relay is approximately .G per u�it.

The burdens and thermal ratings are listed

under Energy Requirements.

3-25 Circuit

The main contacts will safely close 30 amperes at 250 V. d-e, and the switch contacts will safely carry this current long enough to trip a breaker.

As shipped from the factory, the operation

indicator and the contactor switch are con-

nected in parallel. This circuit is suitable

for all trip currents above 2"25 amperes d-e. I f the trip current is less than 2.25 amperes,

there is no need for the contactor s witch and

it should be dlsconnected. To disconnect the

coil remove the short lead to the coil on the

front stationary contact of the co�tactor

switcho This lead should be fastened

www . El

ectric

alPar

tMan

uals

. com

Page 3: -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been

TYPE COQ RELAY ______________________________________ t_L_41--2�77s

r./) 0 z 0 t) w CJ) z -w � -t-

100 90 BO 70 60 50

40

30 25

20

15

10 9 8 7 6

� \. \\ \\

� \ � \ \\

\ \ �

\ � _\ \-""

\\ 1 \

5 RELAY 4 1--- CHARACTERISTICS

TIME DIAL

3 f--SETJ�

II '2.5

'2

1.5

1\

�\ \ r--

\ i\\ \

� -----

� \

GENERATORS CHARACTERISTIC

---12 2T = '30 '2 ----12 T- 30

\ ' \ \_\ \\ \ \

\ \\ � � �

\ \ 1\\ \ \

t---I--

1.s .6 .7 .8 .9 1.0 1.5 2 2.5 3 �

4 5 6 7 8 9 10 NEGATIVE SEQUENCE CURRENT IN PER UNIT ( 1.0 PER UNIT = TAP VALUE CURRENT )

Fiq. 2-Comparison 0£ Relay Characteristic With Generator Characteristic,

27-D-554:)

3 www . El

ectric

alPar

tMan

uals

. com

Page 4: -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been

TYPE COQ RELAY __________________ _

90

1-z w C{ C{ 80 :::> () w � u

I v I

I I z II uJ t- 70 ::>('J a C\J w (/} H

L I

w (J > t- 60 � ([)

rr \j w w 1-z u

w <!

:J cr 50 _j <!

<! I > u

I I I v

I 0.. rr <i 0 I- � � cr 40

w z (J) w I- l-' l) <! lJ..J I- I 30 z I-

I I J

I I 0 lL ()

0 w <.n � 0

20 .J 0 u (f)

_j 0 <! 1-

(/) 0 10 z 0 () w (f)

2 3 4 5 6 7 8 9 10 II

TIME. DIAL SETTING 27-D-5609

Fig. 3-Tirne Dial Setting Versus Permissible Constant Of Generator.

4 www . El

ectric

alPar

tMan

uals

. com

Page 5: -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been

TYPE COQ RELAY ______________ .::.;::I.L_:_: 41�-27..:...::7B

(/) Q z 0 u w (/) z -w :i r-

100 90 80 70 60 50

40

30 '25

20

15

10 9 8 7 6 5

4

3 2.5

2

1.5

\ �\ \\\\ \\\\\ �\\� �\� � \\\\\ � \\\\ �� \� �� � \ � ��

TIME

��\� DIAL SETTING

\\6'\\' ._\\ \>�1\ \' �\\\ \ �\\ \\' l\ \ \\ \'\ �\ �\ \\ �\\\ �\ \\ 1\\� :\

\ \ l\\' � \ \ \\' \\\ t\'; � \ \\ \ I

.5 .6 .7 .8 .9 1.0 1.5 2. '2.5 3 4 5 6 7 8 9 10 NEGATIVE SEQUENCE CURRENT IN PER UNIT ( 1.0 PER UNIT = TAP VALUE CURRENT )

Fig. 4-Typical Operating Curves Of The COO Relay.

27-D-5544

5 www . El

ectric

alPar

tMan

uals

. com

Page 6: -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been

TYPE COQ RELAY ____________________________________ __

(dead-ended) under the small filister head

screw located in the Micarta base of the

contactor switch.

CONTACT CIRCUIT CONSTANTS Universal Trip Circuit

Resistance of 0.2 ampere Target .... 2.88 ohms Resistance of 2.0 ampere

Contactor Switch ................. 0.25 ohms

Resistance of Target and

Switch in Parallel ............... 0.23 ohms

INSTALLATION The relays should be mounted on switch­

board panels or their equivalent in a location

free from dirt, moisture, excessive vibration

and heat. Mount the relay vertically by means

of the two mounting studs for the type FT pro­jection case or by means of the four mounting holes on the flange for the semi-flush type FT case. Either of the studs or the mounting

screws may be utilized for grounding the relay. The electrical connections may be made

direct to the terminals by means of screws for

steel panel mounting or to terminal studs fur<>

nished with the relay for ebony-asbestos or slate panel mounting. The terminal studs may

be easily removed or inserted by locking two nuts on the studs and then turning the proper nut with a wrench.

SETTINGS

There are two settings namely, the tap

value and the time dial settings. For the

protection of generators from excessive nega­

tive sequence currents, the settings must be

determined by the type of machine and the full

load current rating of the machine.

Tap Value Setting

This setting is determined by the full load

current of the generator expressed in current

transformer secondary amperes.

6

Time Dial Setting

Settings of the time dial are determined by

the type of machine to be protected. The time dial indicates a I�T = K curve of a generator

for which the relay protects. By turning the

time dial, the relay can be used to protect generators with I�T constants varying from

"30" to "90" as shown in Fig. 3.

ADJUSTMENTS AND MAINTENANCE All the relays should be inspected peri-

odically and the time of operation should be

checked at least once every six months or at such other time intervals as may be dictated by experience to be suitable to the particular

application. Phantom loads should not be used

in testing induction-�ype relays because of the resulting distorted current wave form

which produces an error in timing.

All contacts should be cleaned periodically.

A contact burnisher S#l82A836H01 llirecommended

for this purpose. The use of abrasive material for cleaning contacts is not recommended, be­cause of the danger of embedding small parti­

cles in the face of the soft silver and thus impairing the contact.

The proper adjustments to insure correct operation of this relay have been made at the

factory and should not require after receipt by the customer.

readjustment If the adjust-

ments have been changed or the relay taken

apart for repairs, the instructions should be followed.

below

Adjust the stationary contact by means of

its adjusting screw such that the contact

spring is just free of the front spring stop. By means of the time dial, move the moving contacts until they deflect the stationary

contacts approximately 1/64 inch. Set the

index pointer such that it points to the "O"

mark on the time dial. Adjust the stationary

contact by means of its adjusting screw until the moving and stationary contacts just touch.

This adjustment is to set "O" on the time dial

and provide follow for the contacts.

-

www . El

ectric

alPar

tMan

uals

. com

Page 7: -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been

I�

TYPE COQ RELAY ____________________ ...;;..tl:;_ . ..;.:41-=-2 .:....:.77�8

Negative Sequence Filter

Adjustment. of the filter resistor to obtain

no response to positive sequence currents is

obtained as follows:

a ) Connect terminal 8 to terminal 14

b ) Remove tap screw from the COQ element

c ) Pass 10 amperes into terminal 7 and out

terminal 13

d ) With a low reading, high resistance Rectox

voltmeter, measure the voltage between

* termiual 8 and the tap plate.

e ) Place the voltmeter across terminals 7 and

8. Adjust the resistor lead on the right

of the reactor until the voltmeter reads

1.732 times the voltage reading of step ( d.

Adjustment of the filter resistance to ob­

tain no response to the zero sequence current

is conveniently made by referring to Fig. 5.

Pass 5 amperes into terminal 8 and 10 amperes

into terminal 7. Adjust the resistor lead on

the left of the reactor until the voltmeter

reads zero.

TIME CURVE CALIBRATION

With the time dial set on " 0"·, wind up the

spring until approximately 5-1/2 convolutions

show. This is an initial rough adjustment. From this preliminary setting,

minimum tap setting and time dial

"11", adjust the permanent magnet

relay operates in 8 . 2 seconds

and using

setting of

until the

with 15.6

amperes single phase or 3 per unit between

terminals 8 and 14. This adjustment is made

by means of the damping magnet screw. A dia­

gram of the test connections is shown in

Fig. 6.

Next adjust the spring tension until the

relay will close contacts in 90 seconds with

5.2 amp e re s single per unit negative

between terminals 8

phase (tap value or one sequence current) applied

and 14. This adjustment

is made by means of the spiral spring ad­

juster. All spring convolutions must be free.

TRIP CIRCUIT

Universal Trip

This combination uses a 2.0 amp. contactor

s*itch and a 0.2 amp.

connected in parallel.

operation indicator

Adjust the conta.ctor

switch and indicator a.s outlined below;

Contactor Switch - Turn the relay up side down. Screw up the core screw until the con-tact ring starts rotating. Now back off the

core until the contact ring stops rotating.

Back off the core screw one more turn and lock in place. Adjust the two nuts a.t the bottom of the switch so that there is 3/32 inch clearance between the moving contact ring and

the stationary contacts in the open position.

The guide rod may be used as a. scale as it has 52 threads per inch, therefore, 5 turns of the nuts will equal approximately 3/32 inch.

Combination Test - Close the main relay con­tacts and pass 2.25 amps d.c. through the trip

circuit. The conta.ctor switch must pick-up.

Adjust the operation indicator by moving the flag holder such that the indicator operates

with the application of the 2. 25 amps. Pass

30 amps d. c. through the trip circuit. The

indicator and contactor switch must not stick

in the operated position when the current is

interrupted.

7 www . El

ectric

alPar

tMan

uals

. com

Page 8: -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been

TYPE COQ RELAY------------------

RENEWAL PARTS

Repair work can be done most satisfactorily

at the factory. However, interchangeable

parts can be furnished to the customers who

are equipped for doing repair work. When

Continuous One Second

Phase Rating-Amps Rating-Amps

A 5 100 B 5 100 c 5 100

-----TAP SCREW REMOVED

-- -RESISTANCE LOAD

REAR VIEW 3�-- n •• I£ITR

L--============�:::::5,'- � '!� ����:s DIAGRAM OF TEST CONNECTIONS

OF THE COO RELAY. FOR

ADJUSTING FILTER TO HAVE NO

RESPONSE TO ZERO SEQUENCE.

27-D-5445

*Fig. 5-Diagram Of Test Connections Of The Type COO Relay. For Adjusting Filter To Have No Response To Zero Sequence.

8

ordering parts, always give the complete name­

plate data.

ENERGY REQUIREMENTS

The burdens of the type COQ Relay are as

follows:

Watts Volt Amps Power Factor

at 5 Amps at 5 Amps Angle

5.3 5.3 00 0.0 .98 90° Lag

4.0 7.25 56° Lag

TIMER STOPS

.------------------10

si��ER =�3v

"�oMTAtT OPENS

TitER STARTS .-------------�- TO TIMER WHEN SWITCH START •s• CLOSES

27-D-5444

Fig. 6-Diagram of Single Phase Test Connections Of The COO Relay For Time Curve Check.

www . El

ectric

alPar

tMan

uals

. com

Page 9: -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been

TYPE COQ RELAY I.L. 41-277 8

• • c A 3 C

:::;:-;;XCT 51!> AMI"£• f�

2 7-D-5441 27-D--5440

Fig. 7 -External Connections Of The COO Relay With Neutral Formed at Relay.

Fig. 8-External Connections Of The COO Relay With Neutral Formed At Point Other Than COO .

I I 0

, ,

. 1!)0-92. TlltM. -:tCKif'w!l U$£ .leQ-32. STVD FOR

PI\HEL LOCATION TM\CK PANI.L MTG FOR PRo.JECTION ----.....____ \ T"fPE MTC ------------- 1 }. \)\� �\.£ Olti\J .. �, � KR INT<RNALSCH£-

CUT OUT r;Q" SEHI FLUSH MOUNTING

0

rt2l --.j\M"TIC f:Otl �JEt�

��� . :' \r)'c:,�,.�G ON_T_.,-"c"'rit=="�*���:::====;::-�c\JT OUT l=OR. � P1\0J£.CT\ON

MTC..�T"'IN PI<NEI.&.

I

PANEL. I.OCA1'\0trrl FOR SEMI-FW&\ot TVPE I'm;..

Fig. 9-0utline And Drilling Plan Of The MlO Projection Or Semi-Flush FT Flexitest Case.

16-B-2477

9 www . El

ectric

alPar

tMan

uals

. com

Page 10: -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been

www . El

ectric

alPar

tMan

uals

. com

Page 11: -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been

www . El

ectric

alPar

tMan

uals

. com

Page 12: -- TYPE COQ NEGATIVE SEQUENCE GENERATOR …TYPE COQ NEGATIVE SEQUENCE GENERATOR RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been

WESTINGHOUSE ELECTRIC CORPORATION METER DIVISION NEWARK, N.J.

Printed in U.S.A. www . El

ectric

alPar

tMan

uals

. com