SECTOSSF6 load break fault make switches for overhead networks
© M
V T
echn
olog
y -
2 -
Distribution network
Sectos NXB + DTU
© M
V T
echn
olog
y -
3 -
Definition of a Switching Device
Open a circuit
Close a circuit
Open a Load Close a Fault
A switch CAN A switch CAN NOT Open a Fault
A disconnectorMust provide a safe isolating distance
© M
V T
echn
olog
y -
4 -
Sectos
Sectos switch-disconnector
12…24 kV (BIL max. 125 kV) 24…36 kV (BIL max. 170 kV)NXB technology NXA technology
NXB NXBD
Motor up Manual
Conical epoxy bushings
Outdoor epoxy bushings
NXA
Motor down
Conical epoxy bushings
ManualMotor up
© M
V T
echn
olog
y -
5 -
Sectos
NXA 36kV, 630A
NXB 12...24kV, 630A
NXBD 12...24kV, 630A
© M
V T
echn
olog
y -
6 -
Sectos NXA
36kV (38kV ANSI)
2-position load break-fault make switch
single or double spring mechanism
Manual or motor operated
Manual operation by hook stick
© M
V T
echn
olog
y -
7 -
Sectos NXA
Insulation level (IEC 60265-1 (1998))
Rated voltage 36 kV
Power frequency withstand voltage, 60 sec wet- to earth and between phases 70 kV- across isolating distance 80 kV
Lighting impulse withstand voltage- to earth and between phases 170 kV- across isolating distance 195 kV
© M
V T
echn
olog
y -
8 -
Sectos NXA
Current ratings (IEC 60265-1 (1998))
Electrical endurance class E2 / E3
Rated normal current 630 A
Mainly active load breaking current 630 A / 400 A
Number of breaking operations CO 50 / 100
Closed loop breaking current 630 A
Line-charging breaking current 40 A
Cable-charging breaking current 40 A
Earth fault breaking current 175 A
Cable charging breaking currentunder earth fault conditions 87 A
No-load transformer breaking current 20 A
© M
V T
echn
olog
y -
9 -
Sectos NXA
Short-circuit ratings (IEC 60265-1 (1998))
Electrical endurance class E2 / E3
Short-time withstand current, Ith (3 s) 12,5 kA
Peak withstand current, Idyn, peak 31,5 kA
Short-circuit making current 31,5 / 25 kA
Number of making operations 3 / 5
Mechanical endurance class M2
Number of close-open operations 5000
Ambient air temperature limits -40...+60 oC
Filling pressure 1.5 bar (abs)
Weight with plug-in insulators 95 kg
© M
V T
echn
olog
y -
10
-
Sectos NXB
12, 17.5 and 24kv
2- or 3-position load break-fault make switch
Single or double spring mechanism
Manual or motor operated
Manual operation by hook stick
© M
V T
echn
olog
y -
11
-
Sectos NXB
Insulation level (IEC 60265-1 (1998))
Rated voltage kV 12 17.5 24
Power frequency withstand voltage, 60 sec wet
- to earth and between phases kV 28 38 50- across isolating distance kV 32 45 60
Lighting impulse withstand voltage- to earth and between phases kV 75 95 125- across isolating distance kV 85 110 145
© M
V T
echn
olog
y -
12
-
Sectos NXB
Current ratings (IEC 60265-1 (1998))
Rated normal current 630 A
Mainly active load breaking current (100 CO) 630 A
Line-charging breaking current 50 A
Cable-charging breaking current 50 A
Earth fault breaking current 50 A
Cable charging breaking currentunder earth fault conditions 28 A
No-load transformer breaking current 6.3 A
© M
V T
echn
olog
y -
13
-
Sectos NXB
Short-circuit ratings (IEC 60265-1 (1998))
Short-time withstand current, Ith (3 s) 20 kA
Peak withstand current, Idyn, peak 50 kA
Short-circuit making current 50 kA
Number of making operations n
- main switch 50 kA (CL E2) 3
- main switch 31.5 kA (CL E3) 10
- earthing switch 50 kA (CL E2) 3
- earthing switch 31.5 kA (CL E3) 5
© M
V T
echn
olog
y -
14
-
Sectos NXB
Mechanical endurance (IEC 60265-1 (1998))
Number of close-open operations n
- main switch 5000
- earthing switch 1000
Ambient air temperature limits -40...+60 oC
Filling pressure (abs) 1.5 barWeight
- cast resin insulators 81 kg
- silicone insulators 82 kg
- without bushing 71 kg
© M
V T
echn
olog
y -
15
-
Sectos NXBD
12, 17.5 and 24kV
Two switches in same housing two switched ways and one tapped
way
2- or 3-position load break-fault make switches
single or double spring mechanism
Manual operation by hook stick
© M
V T
echn
olog
y -
16
-
Sectos
Silicone rubber insulators
Series 400 Outer Conebushings, M16
Reliable position indicator
Rating plate
Earthing terminal
Gas filling valve
Stainless steel housing (sealed pressure system, IEC 56)
Hook-stick lever
Terminal pad
© M
V T
echn
olog
y -
17
-
Details
Large position indicator symbols
Reflective colours
The reliable indication of the device fulfills the design and testing of IEC 129 A2
© M
V T
echn
olog
y -
18
-
Details
Mechanical housing made of aluminium alloy
Stainless steel spring mechanism
IPX7
© M
V T
echn
olog
y -
19
-
Details
Manual operation, single spring mechanism
Motor operation, single spring mechanism
© M
V T
echn
olog
y -
20
-
Details
Temperature compensated gas density switch as standard
Optional gas density gauge
© M
V T
echn
olog
y -
21
-
Details
Optional low gas locking mechanism
© M
V T
echn
olog
y -
22
-
Details
Stainless steel housing
AISI 304
Laser cut, robot welded
© M
V T
echn
olog
y -
23
-
Details
Outer cone bushings, series 400
Flexible plug-in silicone rubber insulators
© M
V T
echn
olog
y -
24
-
Details
Hook-stick lever (3 position switch)
Hook-stick lever (2 position switch) + optional locking device
© M
V T
echn
olog
y -
25
-
Accessories
Many different types of mounting accesories
© M
V T
echn
olog
y -
26
-
Accessories
Different types of terminal pads
© M
V T
echn
olog
y -
27
-
Current Transformer
Ring type transformer, installed around the bushings
Type: KOKU 072 G4
Ratio: 600/1 A
Burden/Class 3 VA / 5P10
0.5 VA / 5P20
Standards IEC 185
© M
V T
echn
olog
y -
28
-
DTU (Distribution Terminal Unit)
REC 501 Digital inputs
24 VDC battery
1…2 contactor logic with local control push buttons and MCB’s
Place for communication device
Heating element
IP55 stainless steel enclosure
© M
V T
echn
olog
y -
29
-
DTU (Distribution Terminal Unit)
REC 523 Digital inputs (15 pcs)
Analog inputs for measuring transformers and sensors (3…9pcs)
24 VDC battery
1…4 contactor logic with local control push buttons and MCB’s
Place for communication device
Heating element
IP55 stainless steel enclosure
© M
V T
echn
olog
y -
30
-
REC 5xx
REC 501 REC 523
© M
V T
echn
olog
y -
31
-
Desired Signals
Some key signals which are desired from a remotely controlled switch
Position: OPEN / CLOSE / EARTH
Operation: LOCAL / REMOTE
Gas level: Enough gas to permit safe operation
Battery status: enough to operate the switch and maintain communication
Cabinet temperature
Door alarm
Fault passage indicator
Fault passage counter
Measurements: Voltage, Current
© M
V T
echn
olog
y -
32
-
REC 5xx
Network Control protocol
Network controlsystem
Remote-controlledequipment
RMU
Disconnector
DLC
Modem
Radio
DLC
Modem
Radio
REC 5xx
Optionalmodem
Public line
Leased lines
Optionaladapter
Optical cable
RS 232
Modem
A GSM AGSM
Adapter
Radio modem Radio modem
Compact switchgear
• LON / SPA interface ( REC 501 only SPA)• RS232 interface• Fibre-optic connection• Radio modem• Modem (option) for
- conventional radio telephone- fixed or switched cable connection- leased or public telephone lines- GSM
• DLC
Communication media Protocols• SPA• LON (for REC 501 with adapter)• ANSI X3.28 • RP570 (REC 501)• IEC 870-5-101• DNP 3.0• MODBUS• Others...
© M
V T
echn
olog
y -
33
-
Feeder Automation Ready Solutions
Ready-made, fully tested packages Sectos
DTU
REC 523
From remotly controllable packages to automatic sectionalizer functions with current and voltage logic
I O
Controlcircuits
Control box
Control cable
Measuring cable
CT:s
OptionalVT
Surge arresters
Connection boxM
NXB_ 3-pos. switch
© M
V T
echn
olog
y -
34
-
Feeder Automation Ready Solutions
I O
Controlcircuits
Control box
Control cable
Measuring cable
CT:s
OptionalVT
Surge arresters
Connection boxM
NXB_ 3-pos. switch Sectos NXB switch-disconnector
Motor operating device integrated in the switch
CT’s installed around the bushings
Cable for motor control , position indication and gas density monitoring
Control box type DTU131 including REC 523
Optional VT’s for power supply and voltage measurement
Surge arresters recommended as an option
© M
V T
echn
olog
y -
35
-
Vegetation, nesting birds and other animals?
The sealed enclosure eliminates risks from environmental hazards and increases the reliability of electrical distribution systems.
Solved by Sectos!
Cali, Colombia
© M
V T
echn
olog
y -
36
-
Salt, sand, moisture and pollution?
The enclosure of stainless steel is hermetically sealed and corrosion resistant. The hydrophobic silicone rubber insulators are well suited even to the most extreme conditions.
Solved by Sectos!
Israel Norway China
© M
V T
echn
olog
y -
37
-
Ice, snow and high altitudes?
The switch inside the sealed tank in an inert SF6 gas atmosphere is insensitive to outside pressure changes. Sectos is also practically maintenance-free.
Solved by Sectos!Finland
Bolivia (3750 m)
© M
V T
echn
olog
y -
38
-
Tölby station outside Vaasa, Finland
SECTOS NXBD24. Double switch-disconnectors 2pcs. All 4 motors remote controlled from same DTU131 operating box using REC523 type of RTU.
Before