Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 1
Mobility Training Center Building Inventory
Space Summary: Facility for Training of Riders, Operators, and Staff
Use:
Training and associated areas
Spaces:
• Training Rooms • Simulation Training Areas • Conference Rooms • Offices • Reception • Desk Area • Kitchen • Multi-Purpose Room • Restrooms • Open Office Area • Mechanical / Electrical Room • I.T. / Data Room • Elevator
Total Existing Area: Approximately 10,500 s.f. (2 Metro Bus in-use floors)
Facility Observation:
Overall the facility is in very good condition internally, as it was completed in 2014. The building exterior is partially in its original condition, and ongoing maintenance of the brick masonry facades will be required. It has been stated that various City and County Transit Authorities from around the country have visited this facility to see how it has been planned. It has been stated it is thousands of square feet smaller than other comparable facilities, an exercise in space conversation. Some of the spaces within the facility are fairly compact, but all seem to be able to serve the functions required.
Facility Deficiencies:
• Exterior brick masonry walls need mortar repair / replacement in some areas • Adjoining building connection to the Training facility is in need of repair • Stone head at first floor windows may be having water issues, should be monitored • Some of the exterior signage is rusting / corroding in spots • Some minimal interior wall finish damage • Low ceiling heights in some areas • Damaged A.C.T. in a few spaces
Figure 1 - Main Floor Plan
Figure 2 - Lower Level Floor Plan
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 2
• No access to natural light in some offices • Some damaged floor tiles • An area of the basement extends underneath the side-
walk, potential ROW concerns • A few renovations are planned for the facility to ad-
dress recent needs
Systems overview:
HVAC and Lighting:
Forced Air HVAC system, RTU’s
Commercial Gas Water Heater
Fire Suppression System
Fluorescent / Incandescent / LED Lighting
Structure:
Masonry Walls
Composite Clay Tile / Concrete Floor Structure
General Notes:
A space efficient training facility
Access & Visibility:
Facility is ADA accessible throughout
Sequence of Entry:
Entry is readily observable / accessible
Area Layout and Use:
Area is efficiently laid out, making
use of a compact space for the
functions provided.
Figure 1 – Mobility Training Center
Figure 3 – Mobility Training Center
Figure 2 – Mobility Training Center
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 3
Analysis and Observations
Entry Vestibule / Reception
• Shared entry vestibule with upstairs tenant
• Accessible with power assisted door operator
• Unit heater in vestibule
• Accessible reception / transaction counter
• Accent lighting and decorative signage
• Security camera system
• Partially exposed ceiling / floor structure
in Reception area
• Overall in very good condition
Waiting Room
• Waiting room for 6 people
• Carpet tiles
• Gyp. board walls
• Partial gyp. board ceiling assembly
• Natural daylighting / views
• Open to reception area
• Direct access to unisex restroom
• TV / Monitor
• Scratched / scuffed walls
• Overall in very good condition
Figure 4 – Mobility Training Center
Figure 5 – Mobility Training Center
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 4
Conference Room
• Conference room for 6 – 8 people
• Carpet tiles
• Gyp. board walls
• A.C.T. ceiling
• Natural daylighting / views
• Open to reception area / waiting room
• Direct access to unisex restroom
• Cabinet with convenience sink
• Wood entry door with sidelights
• Scratched / scuffed walls
• Recessed and suspended light fixtures
• Overall in very good condition
Figure 9 – Mobility Training Center
Figure 7 – Mobility Training Center
Figure 8 – Mobility Training Center
Figure 6 – Mobility Training Center
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 5
Training Area / Circulation
• Training area with simulated conditions
• Floor coating
• Gyp. board walls
• Exposed clay-tile ceiling / floor assembly
• Natural daylighting / views
• Access to reception area
• Direct access to unisex restroom
• Fluorescent lighting
• Scratched / scuffed walls
• Partial bus – for training
• Walking / wheelchair obstacles – for training
• 3 ramps – for training
• Scale area for differently abled
• Size simulation area
• Stoplight / crossing light
• Transit sign
• Flooring / exterior surface simulations
• Overall in very good condition
Figure 10 – Mobility Training Center
Figure 12 – Mobility Training Center
Figure 11 – Mobility Training Center
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 6
Unisex Public Restroom
• Directly adjacent to Waiting Room
• Porcelain wall and floor tiles
• Gyp. board walls
• Natural daylighting
• Solid surface sink
• Changing station
• Fully accessible
• Baseboard heat
• Overall in very good condition
Administrative Area / Back Hallway
• Cabinets with work area
• Carpet tiles
• Gyp. board walls
• Exposed clay-tile ceiling / floor assembly
• Exposed ductwork
• Hardwood veneer plywood cabinets
• Solid surface countertops
• Copying center
• Adjacent to open file storage area
• Damaged A.C.T. ceiling at adjacent file storage room
• Scratched / scuffed walls
• Overall in very good condition
Figure 14 – Mobility Training Center
Figure 15 – Mobility Training Center
Figure 13 – Mobility Training Center
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 7
Individual Offices (2)
• Directly across from Administrative Area
• Gyp. board walls
• Lacks natural daylighting / views
• Carpet tiles
• A.C.T. tiles
• Low ceiling height
• Fluorescent lighting
• Limited storage
• Fire Suppression System
• Wood doors with sidelights
• Workstation
Open Workstations / Back Hallway
• 2 Open Workstations
• Used by staff members and bus operators
• Carpet tiles
• Gyp. board walls
• Exposed clay-tile ceiling / floor assembly
• Exposed ductwork
• Natural daylighting and views
• Scratched / scuffed walls
• Adjacent to Training Room
• Overall in very good condition
Figure 18 – Mobility Training Center
Figure 16 – Mobility Training Center
Figure 17 – Mobility Training Center
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 8
Training Room
• Gyp. board walls
• Natural daylighting and views
• Carpet tiles
• A.C.T. tiles
• Low ceiling height
• Suspended lighting
• Training monitor
• Hardwood veneer cabinets / storage
• Solid surface countertop
• Small convenience sink
• Fire Suppression System
• Wood doors with sidelights
Stairway to Basement / Hallway
• Open staircase
• Tile stairs – damaged in spots
• Carpet tiles
• Porcelain tile landing
• Gyp. board walls
• Gyp. board ceiling
• Alarm system
• Scratched / scuffed walls
• Overall in good condition
Figure 20 – Mobility Training Center
Figure 19 – Mobility Training Center
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 9
I.T., Electrical Service, Fire Alarm Room
• C.M.U. and clay-tile walls
• Low ceiling height
• Suspended fluorescent lighting
• Electrical Panels
• I.T. Equipment
• Fire Alarm Control Panel
• File Storage
• Fire Suppression System
Basement Hallway
• A.C.T. ceiling
• Low ceiling height
• Fluorescent lighting
• C.M.U. walls - painted
• Carpet tiles
• Security cameras
• Emergency access lighting
• Overall in fair condition
Figure 22 – Mobility Training Center
Figure 21 – Mobility Training Center
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 10
Mechanical / Sprinkler / Storage Room
• Basement location – no natural light
• Unfinished area
• Low ceiling height
• Fluorescent lighting
• Fire Protection Service
• File Storage – elevated and covered
• May have water infiltration concerns
• HVAC equipment
• Manhole to street
• Partially below sidewalk – ROW concerns
Men’s and Women’s Restroom
• Basement location – no natural light
• A.C.T. ceilings
• Low ceiling height
• Fluorescent and incandescent lighting
• Gyp. board, C.M.U., and tile walls
• Porcelain floor tiles
• Solid surface countertops
• Plans to change Women’s restroom – to add shower
• Fully accessible restrooms
• Overall in good condition
Figure 24 – Mobility Training Center
Figure 23 – Mobility Training Center
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 11
Kitchenette
• Basement location – no natural light
• Low ceiling height
• Fluorescent lighting
• C.M.U. walls – some scratched / scuffed
• P. Lam. Cabinets and Countertop
• Accessible kitchen sink
• Surface mounted electrical outlets / conduit
• Bi-fold counter door into training room
• P. Lam Cabinet w/ serving counter
• Refrigerator
• Exposed ductwork limits ceiling clearance
Private Back Room / Office (not used)
• Basement location – no natural light
• A.C.T. ceilings
• Low ceiling height
• Fluorescent lighting
• Gyp. board walls
• Carpet tiles
• Dated storage cabinet and shelving
• Fire Suppression
• Overall in fair condition
Figure 26 – Mobility Training Center
Figure 25 – Mobility Training Center
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 12
Planning Manager Office
• Basement location – no natural light
• Low ceiling height
• Fluorescent lighting
• Gyp. Board walls – some tape residue
• Carpet tiles
• Diffuser blows directly onto work station
• Overall in fair condition
Various Rooms
• Basement location – no natural light
• Storage Rooms
• Janitor’s Closet
• Elevator Machine Room
• Low ceiling heights
• Fluorescent lighting
• Some finished and non-finished walls
• Mixture of floor types
• Fire Suppression
• Some spaces not used
• Some storage leased out to upper floor tenant
• Overall in fair condition for use
Figure 27 – Mobility Training Center
Figure 28 – Mobility Training Center
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 13
Training / CDC Training / Break Room
• Basement location – no natural light
• Low ceiling height
• A.C.T. ceiling
• Fluorescent lighting
• Gyp. Board walls – painted
• Carpet tiles
• Operable partitions – dividable space
• Computer stations
• Training monitors
• White boards
• Mobile podium
• Service window to kitchen
• Some surface mounted conduit / outlets
• Fire suppression
• Small coat rack
• Limited storage
• No chair / table storage closet in space
• P. Lam. Cabinets and Countertop
• Exposed water / sewer drain in corner
• Overall in good condition
Figure 30 – Mobility Training Center
Figure 29 – Mobility Training Center
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 14
Conclusions / Summary:
The Mobility Training Center, having been completed in 2014 is in very good shape overall.
• Most of the finishes still look as if new • The facility is generally well planned, especially on the first floor level • There is abundant daylighting and views on most of the first floor level • The entire facility is fully accessible.
The lower level functions acceptably for the purposes served, but does have a few shortcomings:
• The basement level is fairly compact (low ceiling heights) • Does not have any daylighting or exterior views • Is in mixed condition, depending on the room • A number of the storage spaces are not currently used, or barely used
The exterior of the building is in mixed condition
• Two of the facades were updated in 2014, the other two were not • There are a few maintenance items to address and areas that should be monitored, as noted previously
List of Figures
Figure # Location
Figure 1 – Mobility Training Center View of recently renovated exterior façade, at 7th avenue south
Figure 2 – Mobility Training Center View of recently renovated exterior façade, at W. St. Germain Street
Figure 3 – Mobility Training Center View of exterior entry detail
Figure 4 – Mobility Training Center View of reception area, with custom signage
Figure 5 – Mobility Training Center View of waiting area, with natural daylighting / exterior view
Figure 6 – Mobility Training Center View of waiting area and entry to conference room
Figure 7 – Mobility Training Center View of conference room, countertop with convenience sink in background
Figure 8 – Mobility Training Center View of conference room, with natural daylighting / exterior views
Figure 9 – Mobility Training Center View of conference room, with natural daylighting / exterior views
Figure 10 – Mobility Training Center View of training area, bus simulation (front end of bus)
Figure 11 – Mobility Training Center View of training area, multiple simulated environments
Figure 12 – Mobility Training Center View of training area, surface ramp training areas
Existing Facilities Evaluation Appendix D | Mobility Training Center Building Inventory | 15
Figure 13 – Mobility Training Center View of public restroom
Figure 14 – Mobility Training Center View of document working area in back hallway
Figure 15 – Mobility Training Center View of back hallway
Figure 16 – Mobility Training Center View of private office, no natural views or daylighting
Figure 17 – Mobility Training Center View of open workstations, just outside of training room
Figure 18 – Mobility Training Center View of back hallway
Figure 19 – Mobility Training Center View of training room
Figure 20 – Mobility Training Center View of stairway
Figure 21 – Mobility Training Center View of equipment room
Figure 22 – Mobility Training Center View of basement hallway
Figure 23 – Mobility Training Center View of mechanical room
Figure 24 – Mobility Training Center View of restroom
Figure 25 – Mobility Training Center View of kitchenette
Figure 26 – Mobility Training Center View of private back room / office area, currently not used
Figure 27 – Mobility Training Center View of planning manager office, no natural daylighting, no exterior views
Figure 28 – Mobility Training Center View storage closet
Figure 29 – Mobility Training Center View of training room, dividable with operable partitions
Figure 30 – Mobility Training Center View of training room, dividable with operable partitions