© ABB Oy, 9.5.2008 EN -1- Recent trends in variable speed wind turbine drives NORPIE 2008-05-09 Dr. Jouko Niiranen ABB Oy Drives © ABB Oy, 9.5.2008 EN -2 Wind Power -> 2012 -> 2017 Annual Global Wind Power Development Actual 1990-2007 Forecast 2008-2012 Prediction 2013-2017 0 10,000 20,000 30,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 110,000 1990 2007 2012 2017 MW Prediction Offshore (Forecast) Forecast Existing capacity Source: BTM Consult ApS - March 2008

Transcript of © ABB Oy, 9.5.2008 EN - 1

Page 1: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-1-

Recent trends in variable speed windturbine drives

NORPIE 2008-05-09

Dr. Jouko NiiranenABB Oy Drives

©AB

B Oy

, 9.5.

2008

EN

-2

Wind Power -> 2012 -> 2017 Annual Global Wind Power DevelopmentActual 1990-2007 Forecast 2008-2012 Prediction 2013-2017

0

10,00020,000

30,000

40,00050,000

60,00070,000

80,000

90,000100,000

110,000

1990 2007 2012 2017

MW

Prediction Offshore (Forecast) Forecast Existing capacitySource: BTM Consult ApS - March 2008

Page 2: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-3Wind power 2007 versus 2012

Global Wind Power ForecastCumulative MW by end of 2007 & Forecast 2012

020,00040,00060,00080,000

100,000120,000140,000

Europe USA Asia Rest of World2007 (94,005 MW) 2012 (287,940 MW)Source: BTM Consult ApS - March 2008

©AB

B Oy

, 9.5.

2008

EN

-4

ABB – The Component Manufacturer for Wind Power

Page 3: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-5ABB – The Component Manufacturer for Wind Power

©AB

B Oy

, 9.5.

2008

EN

-6

System Concepts available for Wind Power Generation

Variable speed concepts with frequency converters� Doubly-fed asynchronous generator with slip energy recoveryfrequency converter and high speed gear (typically 1500 rpm)

� Asynchronous generator with high speed gear� Gearless synchronous generator with wound rotor� Gearless permanent magnet (PM) synchronous generator� PM generator with integrated low-speed gear� PM generator with high-speed gear

Fixed speed concept� Traditional asynchronous machine directly coupled to grid

Page 4: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-7

65

System Concepts for Wind Power Generation

With Speed Control:Doubly fedWide power range Vestas, GE Wind Energy, Gamesa, Nordex, Acciona, RePower, Ecotècnia, etc

TraditionalTraditional ((withoutwithout speedspeed controlcontrol))

Traditional 15 %

Doublyfed 65%

Market shares and trends for different concepts

15 % gearlessor low speed,full power converter

With Speed Control: Gearless or low speedMulti MW-class => speed control is mustEnercon, Multibrid, JSW, WinWind, MTorres, etc

5 % High speed, full power converter

Siemens, Nordex, Vestas, Suzlon, Mitsubishi, Ecotècnia, etc

With Speed Control:Full power converter, High speed gear Siemens, Clipper etc

Note: 2007 market shares shown are approximate

©AB

B Oy

, 9.5.

2008

EN

-8

Market shares

Page 5: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-9Turbine average power (kW)

Global Average Annual WTG in kW

0

200

400

600

800

1,000

1,200

1,400

1,600

1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007

kWSource: BTM Consult ApS - March 2008

� Average power is 1.5 MW in 2007� 6 MW turbine prototypes exist

©AB

B Oy

, 9.5.

2008

EN

-10

Variable Speed Wind Turbine trends� Double fed still going strong

� Gamesa, Vestas, GE Wind, etc� Full Power increasing in Europe

� Permanent magnet generators� Induction generators

� Average size increasing steadily� Frequency converters are in transition from air-cooled to liquid-cooled types

� Chinese OEM’s are growing fast� Grid-codes are demanding

� Variable speed market in 2007� Total power about 16 000 MW� Equals to 11000 pcs of 1,5 MW turbines

Page 6: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-11

Doubly fed asynchronous generator with slip power recovery

10...24 kV, f = 50 Hzor 60 Hz

line couplingtransformer

generatorsideconverter

grid sideconverter

gearbox

brake

pitchdrive

rotor bearing

main circuit breakerfor protection

converter control

wind turbine control

medium voltageswitchgear

frequencyconverter

main contactor fornormal on-off operation

Activecrowbarprotection

asynchronousgeneratorwith slip rings1500 rpm ±30%

©AB

B Oy

, 9.5.

2008

EN

-12

Wind turbine with doubly fed asynchronous generator

Generator ACS800 Drive

Transformer20 kV / 690 V

Page 7: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-13

frequencyconverter

Gearless permanent magnet synchronous generator

DCgenerator sideconverter

grid sideconverter

wind turbine control

brakepitchdriverotor bearing

synchronousGeneratornN = 17…30 rpm

convertercontrol

10...24 kV, f = 50 Hz

line couplingtransformer

main circuitbreaker

medium voltageswitchgear

©AB

B Oy

, 9.5.

2008

EN

-14

frequencyconverter

PM generator with integrated low speed gear

PM synchronousgenerator(typicallynN = 120...450 rpm)

integratedgear

brake

pitchdrive

rotorbearing

wind turbine control

convertercontrol

DCgenerator sideconverter

grid sideconverter

10 ... 24 kV, f = 50 Hzor 60 Hz

line couplingtransformer

main circuitbreaker

medium voltageswitchgear

Page 8: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-15

Grid Code Evolution

©AB

B Oy

, 9.5.

2008

EN

-16

Grid Code Evolution

Voltage dips� Wind turbines’ share of electricity production

has been increasing rapidly. � Thus sudden disconnection of large number of

wind turbines during grid fault could nowadays cause instability.

Page 9: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-17

Voltage dip ride through gets tougher

� The grid codes issued by power transmission companies have rapidly become more demanding:� 2000: Voltage dip ride through without

disconnection� 2003: Reactive current support during the

dip� 2006: Zero voltage ride through,

asymmetric dips

©AB

B Oy

, 9.5.

2008

EN

-18

Voltage dip ride through gets tougher� Example 1: US FERC Schedule H, after Dec 31, 2007:� three-phase 9 cycle zero voltage ride through, no support� single-phase delayed clearing zero voltage ride through, no

support� Example 2: German E-ON 2006:

No disconnection above this line (not negotiable)No disconnection above this line (negotiable)

Reactive currentsupport

Page 10: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-19

Unsymmetrical dip requirement caused theoretical problem

� Reactive current support has to be verified in tests� Problem: Many definitions exist for reactive power – and give different

results!� Aron method� Delayed voltage method� Instantaneous reactive power method� Fundamental component method

� Use of reactive power and current based on the positive sequence of the fundamental component is recommended when both the voltages and currents are unsymmetrical (most likely the future 2nd edition of IEC 61400-21 standard will specify this as well)

©AB

B Oy

, 9.5.

2008

EN

-20

Zero voltage dip

� Zero voltage dip still a problem – How to define reactive and active current if voltage is zero?

Page 11: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-21

Voltage dip ride through tester

Photo: E2Q� Example of medium voltage field test equipment in a trailer (max. 5 MW turbine can be tested)

Tester

©AB

B Oy

, 9.5.

2008

EN

-22

Symmetrical dip with 20 % remaining voltage (field test)

� Doubly fed fault ride through (2006)

RMS voltages (MV side)

Active powerReactive powerReactive currentPower factor

150 ms

Page 12: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-23

Why crowbar is needed for doubly-fed drives?

Line side converter

DC link

3 - phase network

Doubly fed generator

Rotor side converter

Crowbar

� Low converter power rating means high locked rotor voltage (about 3 UN)� Voltage dip stops the stator flux vector Ψs� Rotor continues to rotate – thus high slip and high induced voltage� High induced voltage inside the winding causes high rotor currents� High voltages and currents can damage the frequency converter� Crowbar protects the converter by short circuiting the rotor

( )∫ −= tiRu d ssssψFlux path before fault

©AB

B Oy

, 9.5.

2008

EN

-24

Symmetrical dip with 23 % remaining voltage (factory test)

� Doubly fed fault ride through (2008)

RMS voltageReactive current

40 ms

Page 13: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-25

Full-power converter (factory test)

� Zero voltage ride through (2008)

40 ms

©AB

B Oy

, 9.5.

2008

EN

-26

Full-power converter (factory test)

� Zero voltage 2-ph fault ride through (2008)

Positive sequence reactive power

Negative sequence reactive power

35 ms

Page 14: © ABB Oy, 9.5.2008 EN - 1

©AB

B Oy

, 9.5.

2008

EN

-27

Future

� Grid codes will continue to evolve� EWEA is trying to harmonize grid codes� There are signs that zero voltage dip reactivecurrent support may not be required in the future� Thus doubly fed concept may continue to stayon market lead� Full scale converters will, however, gain marketshare