Post on 03-Jun-2020
Catalog 613-3
Water-Cooled Scroll Compressor ChillersModel WGZ, D Vintage 30 to 200 Tons (100 to 700 kW) HFC-410A Refrigerant 60/50 Hz
Packaged and Condenserless Units
CAT 613-3 • MODEL WGZ CHILLERS 2 www.DaikinApplied.com
Table of ConTenTs
Table of ConTenTs
©2015 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to make changes in design and construction at any time without notice.
Manufactured in an ISO 9001 & ISO 14001 certified facility
ConTenTs
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . 4Application Considerations . . . . . . . . . . . . . . . . . . . . . 7Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . 16Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Pressure Drop Data . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Physical Data - Packaged Units . . . . . . . . . . . . . . . . 24Physical Data - Condenserless Units . . . . . . . . . . . . 27Dimensions - Packaged Units . . . . . . . . . . . . . . . . . . 30Dimensions - Condenserless Units . . . . . . . . . . . . . 34Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Options and Accessories . . . . . . . . . . . . . . . . . . . . . 50Engineering Guide Specifications . . . . . . . . . . . . . . 51
InTroduCTIon
www.DaikinApplied.com 3 CAT 613-3 • MODEL WGZ CHILLERS
Technology That Just Makes SenseThe 30 to 200-ton WGZ scroll compressor chillers are a product of Daikin Applied’s ongoing commitment to offer energy-efficient equipment design. It is a design approach that carefully combines high quality compressors, efficient shell-and-tube condensers, low pressure drop brazed-plate or shell-and-tube evaporators and dependable controls into a unit of uncompromised operating efficiency and reliability. Model WGZ chillers have many important features:
• Easy serviceablility• Hermetic scroll compressors• User-friendly MicroTech® controls• Open Choices™ feature for BAS of your choice• HFC-410A refrigerant
(Zero ozone depletion and no refrigerant phase out)• AHRI certification
Features and Benefits SummaryFlexible Design
• WGZ chillers can be selected and customized to meet specific job requirements.
The Compressor Technology• Excellent part-load efficiency is achieved due to the
selective cycling of hermetic scroll compressors.The Control Technology
• Onboard digital electronics provide smart controls, self-diagnostic checks, and troubleshooting to ensure that the chiller runs smoothly and efficiently. Includes Open Choices™ BAS flexibility.
Certifications and Standards• Meets ASHRAE Std. 90.1, AHRI 550/590, and contributes
to LEED® credits.Factory Testing
• Ensures trouble free startup and reliable operation.
Water-Cooled Chiller Products
0 500 1000 1500 2000 2500 3000
WGZWater-Cooled Scroll Chiller30 - 200 Tons
WGSWater-Cooled Screw Chiller130 - 190 Tons
Magnitude® Magnetic Bearing Centrifugal ChillerWMC 100 - 400 TonsWME 400 - 1500 Tons
WSCSingle Centrifugal Compressor Chiller
200 - 1250 Tons
WDCDual Centrifugal Compressor Chiller
400 - 2500 Tons
WCCSeries Counterflow Centrifugal Compressor Chiller
1200 - 2700 Tons
15� - �255� tons �cooling
200� - �1200� tons �cooling 3000� - �18000� MBH �heating
320� - �3410� MBH �heating
Templifier™ Heat Recovery Water HeatersTGZ (Scroll Compressor)
TSC (Centrifugal Compressor)
063 079 087 100 113 126
063 079 087 100 113 126
WMC WME
100 113 126
2F-4056 (11/14) ©2014 Daikin Applied
InTroduCTIon
CAT 613-3 • MODEL WGZ CHILLERS 4 www.DaikinApplied.com
feaTures and benefITs
CHILLER NOMENCLATURE
W G Z XXX D W
Flexible Design The Daikin WGZ water chillers are completely factory assembled, piped, wired and shipped in one piece, ready for field connection of power, water piping, and refrigerant piping on remote air or evaporative cooled condenser models. Each chiller consists of compressors, insulated brazed plate or shell-and-tube evaporator and centralized electrical control panel containing all necessary equipment protection and operating controls. Packaged units (“DW”) come complete with mounted, water-cooled condensers with integral subcooler circuits. Condenserless units (“DA”) are provided without condensers to allow for remote installation of air-cooled or evaporative condensing equipment.
The WGZ chillers come in 16 sizes between 30 and 200 nominal tons (105 and 700 kW). This small capacity increment allows a selection that can closely match the required job capacity.
Many optional features can be added to fit job requirements. Several options for power connections can match field requirements. Phase failure/reversal protection and acoustical sound blankets around each compressor are a factory-installed option.
The Compressor TechnologyWGZ chillers use rugged hermetic scroll compressors constructed with an integral cast iron frame, cast iron scrolls, coated bearings, and three oil filtration devices for each compressor. Model WGZ units use environmentally acceptable R-410A refrigerant. Each refrigerant circuit has specially designed oil and gas equalization lines to control oil migration.
The design also offers radial and axial compliance (no tip seals), a large internal volume for liquid handling, a removable suction screen, and a rotary dirt trap and oil screen. In addition, the compressor is self-compensating for wear, handles liquid and debris, and inherently yields high efficiency.
Units are available in 60-hertz with voltages from 208 to 575 volt and in 50-hertz, 400 volt.
Efficient OperationCompressors are placed in tandem or trio arrangements to allow for optimized capacity modulation. Excellent part-load efficiency is obtained by operating one compressor on a tandem compressor circuit and one or two on three-compressor circuits. Each running compressor discharges to the full-sized condenser and operates at lower compression ratios with substantial power savings.
Reduced NoiseThe hermetic scroll compressors equipped on WGZ chillers are inherently quiet. Optional insulated acoustical compressor blankets will further reduce sound levels.
EvaporatorsDifferent evaporators are used depending on chiller model.
Models WGZ030D through WGZ130D: Evaporators are a compact, high efficiency, two-circuit, brazed-plate type heat exchanger consisting of parallel type 304 stainless steel plates, with a design water-side pressure of 653 psi. Each evaporator is designed and constructed according to, and listed by, Underwriters Laboratories (UL).
Models WGZ150D through WGZ200D:Evaporators are a direct-expansion, shell-and-tube type with water flowing in the baffled shell side and refrigerant flowing through the tubes. The water side working pressure is 152 psig (1048 kPa). Each evaporator is designed, constructed, inspected, and stamped according to the requirements of the ASME Boiler and Pressure Vessel Code. Double thickness insulation is available as an option.
Water-Cooled CondensersThe WGZ-DW water-cooled condensers are cleanable shell and tube type with water in the tubes and two refrigerant circuits in the shell side, divided by a vertical, midpoint partition. Each condenser circuit is capable of holding the circuit’s refrigerant charge and each circuit has its own charging and relief valves.
The condenser is constructed with a carbon steel shell and seamless integrally finned high efficiency copper tubes roller expanded into steel tubesheets. The water heads at each end have vent and drain connections and are removable.
Water-Cooled
Global Design
Scroll Compressor
Application W = Standard Packaged A = Less Condenser
Design VintageNominal Tons
feaTures and benefITs
feaTures and benefITs
www.DaikinApplied.com 5 CAT 613-3 • MODEL WGZ CHILLERS
Also included is a liquid shutoff valve, purge valve, and relief valve per ANSI/ASHRAE Pressure Vessel Code, Section VIII. Water-side working pressure is 232 psi (1599 kPa). Standard condenser connections are located on the right end looking at the control panel. Optional left hand connections available.
Air-Cooled Condensers (for WGZ-DA models)WGZ-DA chillers are designed for use with appropriately sized and configured remote air-cooled or evaporative condensers, such as Daikin Model ACH, ACL, and ACX air-cooled condensers. These condensers are available with single- or double-row, vertical discharge fans; double-row (double-circuit) are usually used with Daikin Applied chillers. Two single row (single circuit) can be used where space restrictions dictate. They are fully described and rated in the air-cooled scroll condensing unit catalog, available on www.DaikinApplied.com. They are packed with features offering tangible benefits to owners:
• Complete range of capacities from 10 to 210 tons• Circuits matched to WGZ chillers• Direct drive fan motors at 1140/830 RPM for lower sound • Patented floating tube design to eliminate tube sheet
leaks• High efficiency coil and fan motor design• Internal baffles between all fan cells• Weatherproof control panel & door-mounted disconnect
switch• G90 painted galvanized steel cabinets• Single-point power connection• Independent fusing and contactors for each fan motor• Integral pre-piped subcooler circuit
Figure 1: Daikin Applied Air-Cooled Condenser
Factory Installed Refrigerant Line ComponentsEach chiller’s refrigerant circuit has manual liquid line shutoff valve, one or two replaceable-core filter-driers (depending on size), solenoid valve, liquid line sight glass/moisture indicator, expansion valve (thermal on WGZ 030-130, electronic on WGZ 150-200) and discharge line shutoff valve. Filter-driers are replaceable-core type on all remote condenser model sizes.
The DA models for remote condenser are similarly equipped. Since there is no water-cooled condenser, a high-side pressure relief valve must be field installed in the discharge line.
The Control TechnologyThe model WGZ chiller utilizes MicroTech® II digital control electronics to proactively manage unit operation. This powerful, user-friendly control system provides the flexibility and performance needed for a stand-alone unit as well as multiple units tied into a network system.
MicroTech® II ControllerThe MicroTech® II controller’s state-of-the-art design will not only permit the chiller to run more efficiently, but will also simplify troubleshooting if a system failure occurs. The MicroTech® II controller continuously performs self-diagnostic checks, monitoring system temperatures, pressures and protection devices, and will automatically shutdown a compressor, a refrigerant circuit or the entire unit if a fault occurs. The cause of the shutdown will be retained in memory and can be easily displayed in plain language for operator review. The MicroTech® II chiller controller will also retain and display the time the fault occurred and the operating conditions that were present at the time of the fault, which is an extremely useful feature for troubleshooting. In addition to displaying alarm diagnostics, the MicroTech® II chiller controller also provides the operator with a warning of pre-alarm conditions.
Condenser Fan ControlOn remote air-cooled condenser units, the MicroTech® II controller provides control of up to four condenser fans for each of the two circuits. The control sequences condenser fans based on discharge pressure. This function may also be furnished as part of the condenser control.
CAT 613-3 • MODEL WGZ CHILLERS 6 www.DaikinApplied.com
feaTures and benefITs
Open Choices™ BAS FlexibilityThe exclusive Open Choices™ feature provides seamless integration and comprehensive monitoring, control, and two-way data exchange using industry standard protocols such as LonTalk®, BACnet® or Modbus®. Open Choices™ offers simple and inexpensive flexibility to use the Building Automation System of your choice without an expensive gateway panel. Open Choices™ benefits include:
• Easy to integrate into your BAS of choice• Factory- or field-installed communications module• Integrated control logic for factory options• Easy-to-use local user interface• Comprehensive data exchange
Certifications and StandardsAs with many other Daikin Applied chiller products, model WGZ meets the necessary certifications and standards.
All WGZ units are constructed and/or rated with the latest ANSI/ASHRAE 15 Safety Code, National Electrical Code and ASME Boiler and Pressure Vessel Code. All models are ETL or cETL listed.
AHRI CertificationPart load performance can be presented in terms of Integrated Part Load Value (IPLV), which is defined by AHRI Standard 550/590. Based on AHRI Standard 550/590, and as shown in Figure 2, a typical chiller can operate up to 99% of the time at off-peak conditions and usually spends most of this time at less than 60% of design capacity.
Figure 2: IPLV Defined by AHRI Standard 550/590
WGZ-DW chillers are rated and certified to AHRI Standard 550/590. The ability of WGZ chillers to achieve excellent part load efficiencies, as evidenced by their IPLV ratings, is achieved by selectively cycling four or six scroll compressors. For more information on compressor functionality, see “The Compressor Technology” on page 4.
Compliance with ASHRAE Std. 90.1ASHRAE Standard 90.1 was developed to assist owners and designers make informed choices on a building’s design, systems, and equipment selection. WGZ-DW models meet or exceed ASHRAE 90.1 minimum efficiency requirements.
LEED®
Developed by the U.S. Green Building Council (USGBC) in 1998, Leadership in Energy and Environmental Design (LEED®) is an internationally recognized certification program and intends to provide building owners and operators a consistent structure for identifying and implementing practical and measurable green building design, construction, operations and maintenance solutions. For building owners who want to pursue LEED® Green Building Certification, most WGZ-D models will qualify for the Energy and Atmosphere Credit 4, Enhanced Refrigerant Management worth 2 points. Contact your local sales representative for more details.
Factory TestingExtensive quality control checks and functional tests are performed on every unit to check that each control is properly calibrated and operates correctly. Each unit is pressure tested, evacuated and charged with refrigerant prior to testing. Each unit is then rechecked for refrigerant leakage after operation. This extensive testing helps to ensure trouble-free start-ups.
0
10
20
30
40
50
100 75 50 25
1 Percent
42 Percent45 Percent
12 Percent
Perc
ent T
on-H
our W
eigh
ting
Percent Load
applICaTIon ConsIderaTIons
www.DaikinApplied.com 7 CAT 613-3 • MODEL WGZ CHILLERS
Location and Space RequirementsWGZ-D units are designed for indoor application and must be located in a space where the operating and standby conditions are 40°F to 122°F (4.4°C to 50°C).
Provide clearance of 3 ft. (914 mm) on each side and end for piping and to provide space for servicing the unit. Provide sufficient clearance above the unit for component removal.
Provide clearance at either end of the unit to permit cleaning or removal of condenser tubes (see dimensional data). If a properly located door or window is provided in the wall at one end of the unit, the tubes may be able to be replaced through the opening provided.
FoundationMount the unit on a level concrete foundation. Floors must be strong enough to support the unit operating weight. If necessary, use structural supports to transfer the weight of the unit to the nearest beams.
Vibration IsolationOptional rubber-in-shear or spring vibration mounts are recommended for upper floor installations or where compressor noises might be objectionable (next to occupied spaces such as offices, meeting rooms, etc.).
Pipe vibration eliminators may be required for water piping connected to the unit to minimize transmission of water or pump noise into occupied spaces.
System Water VolumeIt is important to have adequate water volume in the system to provide an opportunity for the chiller to sense a load change, adjust to the change and stabilize. As the expected load change becomes more rapid, a greater water volume is needed. The system water volume is the total amount of water in the evaporator, air handling products and associated piping. If the water volume is too low, operational problems can occur, including rapid compressor cycling, rapid loading and unloading of compressors, erratic refrigerant flow in the chiller, improper motor cooling, shortened equipment life and other undesirable occurrences.
For normal comfort cooling applications where the cooling load changes relatively slowly, Daikin Applied recommends a minimum system volume of two to three times the flow rate (GPM). For example, if the design chiller flow rate is 120 GPM, we recommend a minimum system volume of 240 to 360 gallons.
For process applications where the cooling load can change rapidly, additional system water volume is needed. A process example would be the cooling of hot metal objects. The load would be very stable until the hot metal is dipped into the water tank. Then, the load would increase drastically.
Since there are many other factors that can influence performance, systems can successfully operate below these suggestions. However, as the water volume decreases below these values, the possibility of system instability increases.
Evaporator Variable FlowReducing evaporator flow in proportion to load can reduce system power consumption. Certain restrictions apply to the amount and rate of flow change. The rate of flow change should be a maximum of 10 percent of the change per minute. Do not reduce flow lower than the minimum flows listed in the evaporator pressure drop table: Table 25 on page 23.
Chilled Water PipingIf factory-installed flow switches are not ordered, install a flow switch in the horizontal piping of the system supply (evaporator outlet) water line.
Provide drain connections at low points in the system to permit complete drainage of the system. Locate air vents at the high points in the system to purge air out of the system. Purge air from the water system before unit start-up to ensure adequate flow through the evaporator. For WGZ models 030 to 130, the evaporators do not have vent or drain connections and they must be supplied in the field piping. For WGZ models 150 to 200, drain and vent connections are provided on the evaporator.
NOTE: Install a perforated metal basket strainer (0.062-inch perforations, 41% open area for models for WGZ 030 through 130, and a strainer with 0.125-inch perforations, 40% open area for WGZ 150 through 200) in the return chilled water line before the inlet to the evaporator.
Flush the system water piping thoroughly before making connections to the unit evaporator. Design the water piping so the chilled water circulating pump discharges into the evaporator inlet.
Install pressure gauges in the inlet and outlet water lines to the evaporator. Measure pressure drop through the evaporator to calculate proper flow. Vibration eliminators are recommended in both the supply and return water lines.
Insulate chilled water piping to reduce heat loss and prevent condensation.
applICaTIon ConsIderaTIons
CAT 613-3 • MODEL WGZ CHILLERS 8 www.DaikinApplied.com
applICaTIon ConsIderaTIons
Figure 3: Typical Chilled Water Piping, models WGZ030-130D (Brazed Plate Evaporator)
Figure 4: Typical Chilled Water Piping, models WGZ150-200D (Shell & Tube type Evaporator)
Condenser WaterBe certain the condenser water enters the bottom connection of the condenser and exits the condenser from the top connection. Head pressure control must be provided if the entering condenser water can fall below 60°F (15°C). Install a 20-mesh strainer in the condenser inlet line. The WGZ condenser has two refrigerant circuits with a common condenser water circuit. This arrangement makes head pressure control with discharge pressure actuated control valves difficult.
If for some reason the tower water temperature cannot be maintained at a 60°F (15°C) minimum, or when pond, lake, or well water that can fall below 60°F (15°C) is used as the condensing medium, special discharge pressure control must be used. A water recirculating system with recirculating pump, as shown in Figure 5, is recommended. This system also has the advantage of maintaining tube velocity to help prevent tube fouling. The pump should cycle with the chiller.
AirVent
FlowSwitch
VibrationEliminators
Drain
Outlet
Inlet
PIsolationValves
Strainer
LEAVING FLUIDTEMP. SENSOR
VENT3/8” PIPE PLUG
VIBRATIONELIMINATOR
FLOWSWITCH
GATEVALVE
FLOW
FLOW
GATEVALVE
OUTLET
DRAIN
BALANCINGVALVE
VIBRATIONELIMINATOR
WATERSTRAINER
VALVEDPRESSURE
GAUGE
PROTECT ALL FIELD PIPINGAGAINST FREEZING
applICaTIon ConsIderaTIons
www.DaikinApplied.com 9 CAT 613-3 • MODEL WGZ CHILLERS
Figure 5: Recirculating Discharge Pressure Control System
Ice Storage ApplicationsThe MicroTech® II controller has logic to change setpoints from the low ice-making mode to higher normal comfort cooling setpoints. It is important that the MicroTech® II controller receive a 0 VAC (normal operation) to 24 VAC (ice mode) signal to convert from ice mode to normal operating mode. MicroTech® II includes the logic to keep compressors fully loaded when operating in the ice mode. The double insulation thickness option is recommend to prevent sweating.
Two Pipe Systems When the same two pipes are used for both heating and cooling water, several limitations should be observed. The maximum allowable temperature that the evaporator should experience in a non-operating mode is 100°F (38°C). For unit operation and system changeover from heating to cooling, the maximum allowable temperature entering the evaporator is 90°F. System controls, provided by others, must prevent chiller operation until the loop temperature drops to 90°F (32°C).
Series or Parallel OperationConsider system pressure drop when designing the water piping. Parallel piped systems have half of the total system flow going through the evaporator of each chiller, reducing the individual unit and total system pressure drop for a two chiller installation.
Series piped evaporators require that the total system water flows through both evaporators. Not only is the pressure drop through each evaporator increased but the pressure drops must be added together to obtain the total evaporator pressure drop. Series piped evaporators normally require larger circulating pumps for the chilled water system.
Electrical ConnectionEvery WGZ chiller requires field installation of the main supply power plus mandatory flow switch interlock, optional pump starter auxiliary contact interlock or other field-installed devices. A control circuit transformer installed at the factory
eliminates the need for field installation of a separate 115V supply to the control circuit. However, if desired, a separate 115V field connection to the control circuit can be substituted. A system time clock and remote on-off switch can also be field installed.
See Figure 17 on page 40 (packaged units) or Figure 18 on page 41 (remote condenser models) for field control wiring diagrams. The diagrams shown represents all WGZ units; however, individual terminal numbers can vary between unit sizes. Each unit is provided with its specific wiring diagram in the control panel. All wiring must be done according to local and national codes.
Main Power Supply Disconnect SwitchEvery WGZ unit with the standard single-point power supply is equipped with compressor circuit breakers as standard. Multiple-point power connection is available as an option using two power blocks. Circuit breakers are not available with the multiple-point option.
A factory-installed, non-fused disconnect switch (required to meet NEC Code for disconnects) with a through-the-door handle is available as an option with single or multiple-point power supply. The disconnect switch(s) is properly sized for the model and voltage supplied.
A field-supplied and installed remote disconnect switch can also be used.
Control CircuitA control power transformer is standard equipment on WGZ units. Terminals are provided in the unit control center (terminals TB1 and TB1-20) for field connection to a remote 115V power supply if desired.
Terminals are also provided for field connection of the chilled water flow switch, unit time clock, ambient thermostat and/or remote on/off switch.
Circuit #1 Outlet
Condenser
TemperatureControlValve
CondenserWater
Circuit #2 Outlet
Circuit #1 Inlet
Circuit #2 Inlet
CAT 613-3 • MODEL WGZ CHILLERS 10 www.DaikinApplied.com
applICaTIon ConsIderaTIons
Condenser Pump InterlockThe condenser water pump should be interlocked to cycle with the compressor(s). This will prevent the refrigerant pressure from being overly depressed during the off cycle and allows the energy savings of pump shutdown. Interlock terminals are provided in the unit control panel.
Remote Condenser Refrigerant PipingRemote condensers are usually air cooled or evaporative. Careful design of refrigerant piping is necessary for proper system operation. The refrigerant piping should be designed to accomplish the following:
• Assure proper refrigerant feed to the evaporator.• Provide practical and economical refrigerant line sizes
without excess pressure drop.• Maintain uniform oil return to the compressor under all
load conditions.• Refer to the latest version of the ASHRAE Handbook for
recommended piping practice.Limit the length of refrigerant piping by locating the condenser as close to the chiller as possible. Avoid all unnecessary changes in direction or elevation. Two separate condensers (one for each circuit) can be selected or a single two-row condenser with the standard two-circuit manifold. The circuits must not be combined and precautions must be taken during installation to avoid cross-connecting the circuits.
CAUTIONDo not run refrigerant piping underground.
Liquid LineWhere there is a vertical lift from the condenser to the chiller, adequate subcooling must be provided to prevent liquid flashing before the expansion valve. A shutoff valve should be installed in the liquid line to allow isolation of the remote condenser.
Discharge LineThe discharge line should be trapped at the compressor and looped at the condenser (inverted trap) to prevent liquid refrigerant from draining back to the compressor. Pressure drop should be held at a minimum. Install a discharge check valve in the discharge piping in a horizontal run, close to the condenser.
Recommended Line SizingThe following tables can be used for initial line sizing. Final design should be based on ASHRAE design practice. See the WGZ-D Installation and Maintenance Manual, which can be found at www.DaikinApplied.com, for additional piping information.
Table 1: Equivalent Feet for Fittings
Table 2: Maximum Line Size for Oil Carry Up a Discharge Riser, R-410A
Fitting Type 7/8" 1 1/8" 1 3/8" 1 5/8" 2 1/8" 2 5/8" 3 1/8"
ELBOWS 90º Standard 2.0 2.6 3.3 4.0 5.0 6.0 7.5
90º Long Radius 1.4 1.7 2.3 2.6 3.3 4.1 5.0
90º Street 3.2 4.1 5.6 6.3 8.2 10.0 12.0
45º Standard 0.9 1.3 1.7 2.1 2.6 3.2 4.0
45º Street 1.5 2.1 3.0 3.4 4.5 5.2 6.4
180º Bend 3.2 4.1 5.6 6.3 8.2 10.0 12.0
TEES Full Size 1.4 1.7 2.3 2.6 3.3 4.1 5.0
Reducing 2.0 2.6 3.3 4.0 5.0 6.0 7.5
VALVES Globe Valve, Open 22.0 29.0 38.0 43.0 55.0 69.0 84.0
Gate Valve, Open 0.9 1.0 1.5 1.8 2.3 2.8 3.2
Angle Valve, Open 9.0 12.0 15.0 18.0 24.0 29.0 35.0
Unit Size Line Size (in .)
WGZ030 1 3/8
WGZ035 1 3/8
WGZ040 1 5/8
WGZ045 1 5/8
WGZ050 1 5/8
WGZ055 1 5/8
WGZ060 1 5/8
WGZ070 1 5/8
WGZ080 2 1/8
WGZ090 2 1/8
WGZ100 2 1/8
WGZ115 2 5/8
WGZ130 2 5/8
WGZ150 2 1/8
WGZ170 2 5/8
WGZ200 2 5/8
applICaTIon ConsIderaTIons
www.DaikinApplied.com 11 CAT 613-3 • MODEL WGZ CHILLERS
Table 3: Recommended Liquid Line Size, R-410A
Table 4: Recommended Horizontal or Downflow Discharge Line Size, R-410A
Unit Model Conn . Size at Unit (in .)
Recommended Liquid Line Size (in.)
Up to 50 Equiv. Ft
Up to 75 Equiv. Ft
Up to 100 Equiv. Ft
Up to 125 Equiv. Ft
Up to 150 Equiv. Ft
WGZ030 7/8 7/8 7/8 7/8 7/8 7/8
WGZ035 7/8 7/8 7/8 7/8 7/8 1 1/8
WGZ040 7/8 7/8 7/8 7/8 1 1/8 1 1/8
WGZ045 7/8 7/8 7/8 7/8 1 1/8 1 1/8
WGZ050 7/8 7/8 7/8 7/8 1 1/8 1 1/8
WGZ055 7/8 7/8 7/8 1 1/8 1 1/8 1 1/8
WGZ060 7/8 7/8 7/8 1 1/8 1 1/8 1 1/8
WGZ070 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
WGZ080 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
WGZ090 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
WGZ100 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
WGZ115 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8
WGZ130 1 1/8 1 1/8 1 3/8 1 1/8 1 3/8 1 3/8
WGZ150 1 3/8 1 3/8 1 1/8 1 3/8 1 3/8 1 3/8
WGZ170 1 3/8 1 3/8 1 1/8 1 3/8 1 3/8 1 3/8
WGZ200 1 3/8 1 3/8 1 1/8 1 3/8 1 3/8 1 3/8
Unit Model Conn . Size at Unit (in .)
Recommended Discharge Line Sizes (in.)
Up to 50 Equiv. Ft
Up to 75 Equiv. Ft
Up to 100 Equiv. Ft
Up to 125 Equiv. Ft
Up to 150 Equiv. Ft
WGZ030 1 3/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
WGZ035 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8
WGZ040 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8
WGZ045 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8
WGZ050 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8
WGZ055 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8
WGZ060 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8
WGZ070 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8
WGZ080 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8
WGZ090 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8
WGZ100 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8
WGZ115 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8
WGZ130 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8
WGZ150 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
WGZ170 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
WGZ200 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8
CAT 613-3 • MODEL WGZ CHILLERS 12 www.DaikinApplied.com
sound daTa
Test DataSound testing is performed in accordance with ARI Standard 575. Values are taken at one meter from the unit and with the units fully loaded. Values are mid-band. Octave band readings are non-”A” weighted; however, overall are “A” weighted.
Sound ReductionSound blankets are available as an option on all size WGZ units. One blanket is supplied for each compressor.
Table 5: 60 Hz Sound Power without Sound Insulation
Table 6: 60 Hz Sound Pressure without Sound Insulation
WGZ-D Unit Size
Flat Db Octave Band Sound Power Levels per ARI Standard 575 (dB) Overall “A” Weighted 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
30 72 64 70 80 70 75 69 56 80
35 72 66 71 79 71 79 70 56 82
40 72 66 70 86 75 79 74 64 86
45 72 66 70 86 75 79 74 64 86
50 72 65 70 83 73 77 74 64 83
55 72 65 70 83 73 77 74 64 83
60 72 65 70 83 73 77 74 64 83
70 72 66 70 86 75 79 74 64 86
80 83 77 81 86 86 84 81 71 90
90 83 77 81 86 86 84 81 71 90
100 84 78 83 87 88 85 82 73 92
115 84 78 83 87 89 87 82 73 93
130 84 78 84 89 91 89 83 76 95
150 84 78 83 87 88 85 82 73 92
170 84 78 84 88 90 87 83 74 94
200 86 79 84 89 92 90 84 76 96
WGZ-D Unit Size
Flat Db Octave Band Sound Pressure Levels per ARI Standard 575 (dB) Overall “A” Weighted 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
30 64 56 62 71 62 67 61 48 72
35 64 58 63 71 63 71 62 48 74
40 64 58 62 78 67 71 66 56 78
45 64 58 62 78 67 71 66 56 78
50 64 57 62 75 65 69 65 56 75
55 64 57 62 75 65 69 65 56 75
60 64 57 62 75 65 69 65 56 75
70 64 58 62 78 67 71 66 56 78
80 75 69 73 78 78 76 72 63 82
90 75 69 73 78 78 76 72 63 82
100 76 70 75 79 80 77 74 65 84
115 76 70 75 79 81 79 74 65 85
130 76 70 76 81 83 81 75 68 87
150 76 70 75 79 80 77 74 65 84
170 76 70 76 80 82 79 75 66 86
200 78 71 76 81 84 82 76 68 88
sound daTa
sound daTa
www.DaikinApplied.com 13 CAT 613-3 • MODEL WGZ CHILLERS
Table 7: 60 Hz Sound Power with Sound Insulation
Table 8: 60 Hz Sound Pressure with Sound Insulation
WGZ-D Unit Size
Flat Db Octave Band Sound Power Levels per ARI Standard 575 (dB) Overall “A” Weighted 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
30 72 64 67 76 63 69 61 50 75
35 72 66 67 75 64 72 63 50 76
40 72 66 67 78 65 72 63 51 78
45 72 66 67 78 66 72 68 57 78
50 72 65 67 75 64 72 63 50 76
55 72 65 67 75 64 72 63 50 76
60 72 65 67 75 64 72 63 50 76
70 72 66 67 78 66 72 68 57 78
80 83 77 77 82 78 76 73 64 84
90 83 77 77 82 78 76 73 64 84
100 84 78 79 83 81 79 74 66 86
115 84 78 80 85 82 80 74 68 87
130 84 78 81 86 83 83 76 69 89
150 84 78 79 83 81 79 74 66 86
170 84 78 81 84 83 82 76 68 88
200 86 79 83 86 86 85 79 71 91
WGZ-D Unit Size
Flat Db Octave Band Sound Pressure Levels per ARI Standard 575 (dB) Overall “A” Weighted 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
30 64 56 59 68 55 61 53 42 68
35 64 58 59 67 56 64 55 42 68
40 64 58 59 70 57 64 55 43 70
45 64 58 59 70 58 64 60 49 70
50 64 57 59 67 56 64 55 42 68
55 64 57 59 67 56 64 55 42 68
60 64 57 59 67 56 64 55 42 68
70 64 58 59 70 58 64 60 49 70
80 75 69 69 74 70 68 65 56 76
90 75 69 69 74 70 68 65 56 76
100 76 70 71 75 73 71 66 58 78
115 76 70 72 77 74 72 66 60 79
130 76 70 73 78 75 75 68 61 81
150 76 70 71 75 73 71 66 58 78
170 76 70 73 76 75 74 68 60 80
200 78 71 75 78 78 77 71 63 83
CAT 613-3 • MODEL WGZ CHILLERS 14 www.DaikinApplied.com
sound daTa
Table 9: 50 Hz Sound Power without Sound Insulation
Table 10: 50 Hz Sound Pressure without Sound Insulation
WGZ-D Unit Size
Flat Db Octave Band Sound Power Levels per ARI Standard 575 (dB) Overall “A” Weighted 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
30 96 77 75 80 67 71 65 54 77
35 96 79 76 79 68 75 66 54 79
40 96 79 75 86 72 75 70 62 83
45 96 79 75 86 72 75 70 62 83
50 96 78 75 83 70 73 70 62 80
55 96 78 75 83 70 73 70 62 80
60 96 78 75 83 70 73 70 62 80
70 96 79 75 86 72 75 70 62 83
80 107 90 86 86 83 80 77 69 87
90 107 90 86 86 83 80 77 69 87
100 108 91 88 87 85 81 78 71 89
115 108 91 88 87 86 83 78 71 90
130 108 91 89 89 88 85 79 74 92
150 108 91 88 87 85 81 78 71 89
170 108 91 89 88 87 83 79 72 91
200 110 92 89 89 89 86 80 74 93
WGZ-D Unit Size
Flat Db Octave Band Sound Pressure Levels per ARI Standard 575 (dB) Overall “A” Weighted 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
30 88 69 67 71 59 63 57 46 69
35 88 71 68 71 60 67 58 46 71
40 88 71 67 78 64 67 62 54 75
45 88 71 67 78 64 67 62 54 75
50 88 70 67 75 62 65 61 54 72
55 88 70 67 75 62 65 61 54 72
60 88 70 67 75 62 65 61 54 72
70 88 71 67 78 64 67 62 54 75
80 99 82 78 78 75 72 68 61 79
90 99 82 78 78 75 72 68 61 79
100 100 83 80 79 77 73 70 63 81
115 100 83 80 79 78 75 70 63 82
130 100 83 81 81 80 77 71 66 84
150 100 83 80 79 77 73 70 63 81
170 100 83 81 80 79 75 71 64 83
200 102 84 81 81 81 78 72 66 85
sound daTa
www.DaikinApplied.com 15 CAT 613-3 • MODEL WGZ CHILLERS
Table 11: 50 Hz Sound Power with Sound Insulation
Table 12: 50 Hz Sound Pressure with Sound Insulation
WGZ-D Unit Size
Flat Db Octave Band Sound Power Levels per ARI Standard 575 (dB) Overall “A” Weighted 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
30 97 78 73 77 61 66 58 49 73
35 97 80 73 76 62 69 60 49 74
40 97 80 73 79 63 69 60 50 76
45 97 80 73 79 64 69 65 56 76
50 97 79 73 76 62 69 60 49 74
55 97 79 73 76 62 69 60 49 74
60 97 79 73 76 62 69 60 49 74
70 97 80 73 79 64 69 65 56 76
80 108 91 83 83 76 73 70 63 82
90 108 91 83 83 76 73 70 63 82
100 109 92 85 84 79 76 71 65 84
115 109 92 86 86 80 77 71 67 85
130 109 92 87 87 81 80 73 68 87
150 109 92 85 84 79 76 71 65 84
170 109 92 87 85 81 79 73 67 86
200 111 93 89 87 84 82 76 70 89
WGZ-D Unit Size
Flat Db Octave Band Sound Pressure Levels per ARI Standard 575 (dB) Overall “A” Weighted 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
30 89 70 65 69 53 58 50 41 66
35 89 72 65 68 54 61 52 41 66
40 89 72 65 71 55 61 52 42 68
45 89 72 65 71 56 61 57 48 68
50 89 71 65 68 54 61 52 41 66
55 89 71 65 68 54 61 52 41 66
60 89 71 65 68 54 61 52 41 66
70 89 72 65 71 56 61 57 48 68
80 100 83 75 75 68 65 62 55 74
90 100 83 75 75 68 65 62 55 74
100 101 84 77 76 71 68 63 57 76
115 101 84 78 78 72 69 63 59 77
130 101 84 79 79 73 72 65 60 79
150 101 84 77 76 71 68 63 57 76
170 101 84 79 77 73 71 65 59 78
200 103 85 81 79 76 74 68 62 81
CAT 613-3 • MODEL WGZ CHILLERS 16 www.DaikinApplied.com
seleCTIon proCedure
Packaged Chillers (Models WGZ-DW)1. Ratings are based and certified in accordance with AHRI
Standard 550/590.
2. Performance ratings, beginning on page 18, can be interpolated for any chiller water temperature between 40°F and 50°F (4.4°C and 10.0°C) but cannot be extrapolated.
3. Chilled water quantities: ratings are based on a 10°F (5.6°C) chilled water range (2.4 gpm/ton) and can be used for a Delta-T range of 6 to 16°F (3.3 to 8.8°C) by applying performance adjustments from Table 16. The maximum/nominal/minimum flow rates and pressure drops are shown beginning on page 22. The maximum flow rate and pressure drop are based on a 6-degree chilled water temperature drop. Avoid higher flow rates with resulting lower temperature drops to prevent potential control problems resulting from very small control bands and limited start up/shut off temperature changes. The minimum flow and pressure drop is based on a full load evaporator temperature drop of 16-degrees required to maintain turbulent flow. These minimum flow rates assume that flow will be reduced proportionally to the cooling load.
4. Ratings are based on 0.0001 fouling factor for the evaporator. For other fouling factors, multiply ratings by evaporator factors from Table 16. For applications using a glycol solution, see Table 14 or Table 15 corrections.
5. Ratings are based on condenser flow of 3 gpm/ton (10°F, 5.6°C) delta-T and 0.00025 fouling factor. Corrections for other conditions are in Table 17.
Performance Adjustment FactorsAltitude Correction FactorsPerformance tables are based at sea level. Elevations other than sea level affect the performance of the unit. The decreased air density will reduce condenser capacity consequently reducing the unit’s performance. For performance at elevations other than sea level refer to Table 13.
Table 13: Altitude Correction Factors
Ethylene & Propylene Glycol FactorsWGZ units are designed to operate with a leaving chilled fluid temperature from 15°F (-9.4°C) to 60°F (16°C). Leaving chilled fluid temperatures below 40°F (4.6°C) result in suction temperatures at or below the freezing point of water and a glycol anti-freeze solution is required. The use of glycol in the evaporator will reduce the performance of the unit. The reduction in performance depends upon the glycol
concentration and temperature. This should be taken into consideration during initial system design.
Daikin Applied encourages a minimum concentration of 25% be provided on all glycol applications. Glycol concentrations below 25% are too diluted for long-term corrosion protection of ferrous metals and corrosion inhibitors need to be recalculated and possibly added to the system. Glycol in the condenser will have a negligible effect on performance because glycol at these higher temperatures will perform with characteristics similar to water.NOTE: Ethylene and propylene glycol ratings are outside the
scope of AHRI Standard 550/590-2003 certification program.
Table 14: Ethylene Glycol Correction Factors
Table 15: Propylene Glycol Correction Factors
Fouling FactorPerformance tables are based on water with a fouling factor of 0.0001 ft² x hr x °F/BTU (0.0176 m² x C/kW) in the evaporator and 0.00025 ft² x hr x °F/BTU (0.044 m² x C/kW) in water-cooled condensers according to ARI 550/590. As fouling is increased, performance decreases. See Table 16 and Table 17 for performance with other fouling factors.
For optimum unit operation, proper water treatment must be maintained. Scaling and dirt in a system will vary significantly depending on local water conditions. Water treatment should be based on characteristics of the area’s water. Improper or untreated water can lead to scale buildup, erosion and corrosion in both the condenser and evaporator.
Table 16: Evaporator Fouling Factors
Altitude 1000 ft . 2000 ft . 3000 ft . 4000 ft . 5000 ft . 6000 ft . Capacity 0.995 0.991 0.986 0.981 0.976 0.971
EER 0.990 0.980 0.969 0.957 0.946 0.936
% E .G .Freeze Point
Capacity Power Flow Pressure Drop° F ° C
10 25.0 -3.9 0.997 0.999 1.030 1.113
20 18.0 -7.8 0.993 0.997 1.060 1.226
30 7.0 -13.9 0.987 0.995 1.092 1.369
40 -7.0 -21.7 0.980 0.992 1.132 1.557
50 -28.0 -33.3 0.973 0.991 1.182 1.791
% P .G .Freeze Point
Capacity Power Flow Pressure Drop° F ° C
10 25.0 -3.9 0.994 0.998 1.016 1.106
20 19.0 -7.2 0.987 0.995 1.032 1.211
30 9.0 -12.8 0.978 0.992 1.057 1.380
40 -5.0 -20.6 0.964 0.987 1.092 1.703
50 -27.0 -32.8 0.952 0.983 1.140 2.250
Water Delta T.
Fouling Factor0.000 0.000 0.001 0.001 0.001
oF oC Cap. Power Cap. Power Cap. Power Cap. Power Cap. Power10 5.6 1.000 1.000 0.991 0.998 0.977 0.995 0.957 0.991 0.937 0.985
seleCTIon proCedure
seleCTIon proCedure
www.DaikinApplied.com 17 CAT 613-3 • MODEL WGZ CHILLERS
Table 17: Condenser Fouling Factors
Evaporator and Condenser Delta-T FactorsPerformance tables are based on a 10°F (5°C) temperature difference through the evaporator and condenser. A temperature difference other than 10°F (5°C) will result in unit performance being different from what is shown. Adjustment factors for applications having temperature drops between 6°F and 16°F (3.3°C to 8.9°C) can be found in Table 18 and Table 19.
Table 18: Evaporator Delta-T Adjustment Factors
Table 19: Condenser Delta-T Adjustment Factors
Selection ProcedureKnowing the required chiller capacity in tons, the leaving water temperature and either the chilled water temperature range (Delta T) or the flow, determine the unknown quantity using the formula:
Tons= GPM x Delta T/24 (water only)
Knowing the required chiller capacity (tons), the entering condenser water temperature, and either the condenser water temperature range-delta T, or the GPM, determine the unknown quantity using the formula:
With the previous data, the appropriate unit can be selected from using the performance data tables, which start on Table 20. Correct the capacity and power if conditions are other than standard as described above. Pressure drop for condensers
and for evaporators can be found in Table 24 on page 22 and Table 25 on page 23, respectively.
Sample Selection Given: Cool 115 GPM of water from 58°F to 44°F with condenser water available at 85°F. Condenser water temperature rise to be 10°F. Fouling factor of 0.0001 in the evaporator and 0.00025 in the condenser.
Find:
A. WGZ packaged water chiller selection
B. Compressor power input
C. Condenser water flow rate
D. Corrected EER
E. Evaporator and condenser water pressure drop
Solution:
1. Chilled water range: 58°F - 44°F = 14°F (Nonstandard Temperature Difference).
2. Tons = 115 x 14°F/24 = 67 Tons
3. From Table 20 on page 18, a model WGZ-070DW has the capacity to meet the job requirement. For an evaporator leaving water temperature of 44°F and condenser water entering temperature of 85°F with a 10°F rise, the unit capacity rating table indicates:
• Capacity: 70.2 Tons• Power: 53.3 kW
4. Correct for 14°F Delta-T in the evaporator with factors from Table 18.
• Capacity: 70.2 x 1.015 = 71.2 Tons• Power: 53.3 x 1.004 = 53.7 kW
5. Calculate new EER: (71.2 Tons x 12000) / (53.7 kW x 1000) = 15.9
6. Determine condenser water from the following:
• From Table 25 on page 23, the evaporator pressure drop at 115 GPM is 6.2 feet.
• Condenser flow = 67 Tons x 30/10 degrees=201 GPM. From Table 24 on page 22, the condenser pressure drop at 201 GPM is 9.6 feet water.
WGZ-DA Remote CondenserContact the Daikin Applied sales office for a computerized selection using a Daikin Applied condenser.
AHRI CertificationPerformance on all 60Hz standard packaged models is certified per AHRI standard 550/590. Chillers with optional remote evaporators or chillers with glycol applications are outside the scope of the AHRI rating program. Ratings in bold are at AHRI standard conditions.
Water Delta T .
Fouling Factor 0 .000 0 .001 0 .001 0 .001
oF oC Cap . Power Cap . Power Cap . Power Cap . Power10 5.6 1.000 1.000 0.995 1.010 0.990 1.022 0.981 1.035
Water Delta T .
Fouling Factor 0 .0001
oF oC Capacity Power 6 3.3 0.981 0.996
8 4.4 0.991 0.998
10 5.6 1.000 1.000
12 6.7 1.008 1.002
14 7.7 1.015 1.004
16 8.9 1.021 1.005
Water Delta T .
Fouling Factor 0 .00025
oF oC Capacity Power 6 3.3 1.012 0.960
8 4.4 1.006 0.980
10 5.6 1.000 1.000
12 6.7 0.994 1.018
14 7.7 0.988 1.036
16 8.9 0.981 1.055
CAT 613-3 • MODEL WGZ CHILLERS 18 www.DaikinApplied.com
performanCe daTa
Table 20: 60 Hz Part Load Performance Data (IP) Table 20 continued: 60 Hz Part Load Performance Data (IP)
WGZ-DW Unit Size
Percent Load
Capacity (Tons)
Power (kW)
Unit EER IPLV
030
100 30.0 23.3 15.4
19 .975 22.5 14.8 18.4
50 15.0 8.5 21.2
25 7.5 4.3 20.9
035
100 34.6 25.8 16.1
20 .375 26.0 16.4 19.0
50 17.3 9.7 21.4
25 8.7 4.9 21.3
040
100 40.7 30.3 16.1
20 .475 30.5 19.3 19.0
50 20.4 11.4 21.5
25 10.2 5.7 21.5
045
100 45.5 34.5 15.8
20 .375 34.1 21.7 18.9
50 22.8 12.8 21.4
25 11.4 6.4 21.4
050
100 51.4 39.5 15.6
20 .175 38.6 25.0 18.5
50 25.7 14.5 21.3
25 12.9 7.3 21.2
055
100 56.4 43.1 15.7
20 .375 42.3 26.9 18.9
50 28.2 15.8 21.4
25 14.1 7.9 21.4
060
100 60.5 46.5 15.6
20 .275 45.4 29.0 18.8
50 30.3 17.1 21.3
25 15.1 8.5 21.3
070
100 70.2 53.3 15.8
20 .375 52.7 33.5 18.9
50 35.1 19.7 21.4
25 17.6 9.8 21.5
WGZ-DW Unit Size
Percent Load
Capacity (Tons)
Power (kW)
Unit EER IPLV
080
100 78.3 59.5 15.8
20 .375 58.7 37.3 18.9
50 39.2 22.0 21.4
25 19.6 11.0 21.4
090
100 87.1 66.6 15.7
20 .275 65.3 41.5 18.9
50 43.6 24.6 21.3
25 21.8 12.3 21.3
100
100 97.8 73.4 16.0
20 .475 73.4 46.1 19.1
50 48.9 27.4 21.4
25 24.5 13.7 21.4
115
100 112.9 85.2 15.9
20 .375 84.7 53.8 18.9
50 56.5 31.7 21.4
25 28.2 15.8 21.4
130
100 126.7 97.4 15.6
20 .275 95.0 60.6 18.8
50 63.4 35.7 21.3
25 31.7 17.8 21.4
150
100 148.2 111.2 16.0
21 .175 111.2 67.7 19.7
50 74.1 39.9 22.3
25 37.1 20.1 22.1
170
100 169.3 127.0 16.0
21 .375 127.0 76.6 19.9
50 84.7 45.4 22.4
25 42.3 23.0 22.2
200
100 188.1 141.1 16.0
21 .075 141.1 86.4 19.6
50 94.1 50.9 22.2
25 47.0 25.4 22.2
performanCe daTa
performanCe daTa
www.DaikinApplied.com 19 CAT 613-3 • MODEL WGZ CHILLERS
Table 21: 60 Hz Part Load Performance Data (SI) Table 21 continued: 60 Hz Part Load Performance Data (SI)
WGZ-DW Unit Size
Percent Load
Capacity (Tons)
Power (kW)
Unit EER IPLV
030
100 105.5 23.3 4.5
5 .875 79.1 14.8 5.3
50 52.7 8.5 6.2
25 26.4 4.3 6.1
035
100 121.7 25.8 4.7
6 .075 91.2 16.4 5.6
50 60.8 9.7 6.3
25 30.4 4.9 6.2
040
100 143.1 30.3 4.7
6 .075 107.3 19.3 5.6
50 71.6 11.4 6.3
25 35.8 5.7 6.3
045
100 160.0 34.5 4.6
5 .975 120.0 21.7 5.5
50 80.0 12.8 6.2
25 40.0 6.4 6.2
050
100 180.7 39.5 4.6
5 .975 135.5 25.0 5.4
50 90.4 14.5 6.2
25 45.2 7.3 6.2
055
100 198.3 43.1 4.6
5 .975 148.7 26.9 5.5
50 99.2 15.8 6.3
25 49.6 7.9 6.3
060
100 212.7 46.5 4.6
5 .975 159.5 29.0 5.5
50 106.4 17.1 6.2
25 53.2 8.5 6.3
070
100 246.8 53.3 4.6
5 .975 185.1 33.5 5.5
50 123.4 19.7 6.3
25 61.7 9.8 6.3
WGZ-DW Unit Size
Percent Load
Capacity (Tons)
Power (kW)
Unit EER IPLV
080
100 275.3 59.5 4.6
5 .975 206.5 37.3 5.5
50 137.7 22.0 6.3
25 68.8 11.0 6.3
090
100 306.3 66.6 4.6
5 .975 229.7 41.5 5.5
50 153.1 24.6 6.2
25 76.6 12.3 6.2
100
100 343.9 73.4 4.7
6 .075 257.9 46.1 5.6
50 171.9 27.4 6.3
25 86.0 13.7 6.3
115
100 397.0 85.2 4.7
5 .975 297.7 53.8 5.5
50 198.5 31.7 6.3
25 99.2 15.8 6.3
130
100 445.5 97.4 4.6
5 .975 334.1 60.6 5.5
50 222.7 35.7 6.2
25 111.4 17.8 6.3
150
100 521.1 111.2 4.7
6 .275 390.8 67.7 5.8
50 260.5 39.9 6.5
25 130.3 20.1 6.5
170
100 595.3 127.0 4.7
6 .275 446.5 76.6 5.8
50 297.6 45.4 6.6
25 148.8 23.0 6.5
200
100 661.4 141.1 4.7
6 .275 496.0 86.4 5.7
50 330.7 50.9 6.5
25 165.3 25.4 6.5
CAT 613-3 • MODEL WGZ CHILLERS 20 www.DaikinApplied.com
performanCe daTa
Table 22: 50 Hz Part Load Performance Data (IP) Table 22 continued: 50 Hz Part Load Performance Data (IP)
WGZ-DW Unit Size
Percent Load
Capacity (Tons)
Power (kW)
Unit EER IPLV
030
100 24.9 18.6 16.0
20 .775 18.7 11.8 18.9
50 12.5 6.8 22.0
25 6.2 3.4 21.7
035
100 28.7 20.6 16.7
21 .175 21.5 13.1 19.7
50 14.4 7.8 22.2
25 7.2 3.9 22.0
040
100 33.8 24.2 16.7
21 .275 25.3 15.4 19.7
50 16.9 9.1 22.2
25 8.4 4.6 22.2
045
100 37.8 27.6 16.4
21 .175 28.3 17.4 19.6
50 18.9 10.2 22.1
25 9.4 5.1 22.1
050
100 42.7 31.6 16.2
20 .875 32.0 20.0 19.2
50 21.3 11.6 22.1
25 10.7 5.8 21.9
055
100 46.8 34.5 16.3
21 .175 35.1 21.5 19.6
50 23.4 12.6 22.2
25 11.7 6.3 22.2
060
100 50.2 37.2 16.2
21 .075 37.7 23.2 19.5
50 25.1 13.7 22.0
25 12.6 6.8 22.2
070
100 58.3 42.6 16.4
21 .175 43.7 26.8 19.6
50 29.1 15.8 22.2
25 14.6 7.8 22.3
WGZ-DW Unit Size
Percent Load
Capacity (Tons)
Power (kW)
Unit EER IPLV
080
100 65.0 47.6 16.4
21 .175 48.7 29.8 19.6
50 32.5 17.6 22.2
25 16.2 8.8 22.2
090
100 72.3 53.3 16.3
21 .075 54.2 33.2 19.6
50 36.1 19.7 22.0
25 18.1 9.8 22.0
100
100 81.2 58.7 16.6
21 .175 60.9 36.9 19.8
50 40.6 21.9 22.2
25 20.3 11.0 22.2
115
100 93.7 68.2 16.5
21 .175 70.3 43.0 19.6
50 46.9 25.4 22.2
25 23.4 12.6 22.2
130
100 105.2 77.9 16.2
21 .075 78.9 48.5 19.5
50 52.6 28.6 22.1
25 26.3 14.2 22.2
150
100 123.0 89.0 16.6
21 .975 92.3 54.2 20.4
50 61.5 31.9 23.1
25 30.8 16.1 22.9
170
100 140.5 101.6 16.6
22 .175 105.4 61.3 20.6
50 70.3 36.3 23.2
25 35.1 18.4 22.9
200
100 156.1 112.9 16.6
21 .875 117.1 69.1 20.3
50 78.1 40.7 23.0
25 39.0 20.3 23.0
performanCe daTa
www.DaikinApplied.com 21 CAT 613-3 • MODEL WGZ CHILLERS
Table 23: 50 Hz Part Load Performance Data (SI) Table 23 continued: 50 Hz Part Load Performance Data (SI)
WGZ-DW Unit Size
Percent Load
Capacity (Tons)
Power (kW)
Unit EER IPLV
030
100 87.6 18.6 4.7
6 .175 65.7 11.8 5.5
50 43.8 6.8 6.4
25 21.9 3.4 6.4
035
100 101.0 20.6 4.9
6 .275 75.7 13.1 5.8
50 50.5 7.8 6.5
25 25.2 3.9 6.4
040
100 118.8 24.2 4.9
6 .275 89.1 15.4 5.8
50 59.4 9.1 6.5
25 29.7 4.6 6.5
045
100 132.8 27.6 4.8
6 .275 99.6 17.4 5.7
50 66.4 10.2 6.5
25 33.2 5.1 6.5
050
100 150.0 31.6 4.7
6 .175 112.5 20.0 5.6
50 75.0 11.6 6.5
25 37.5 5.8 6.4
055
100 164.6 34.5 4.8
6 .275 123.4 21.5 5.7
50 82.3 12.6 6.5
25 41.1 6.3 6.5
060
100 176.6 37.2 4.7
6 .175 132.4 23.2 5.7
50 88.3 13.7 6.5
25 44.1 6.8 6.5
070
100 204.9 42.6 4.8
6 .275 153.7 26.8 5.7
50 102.4 15.8 6.5
25 51.2 7.8 6.5
WGZ-DW Unit Size
Percent Load
Capacity (Tons)
Power (kW)
Unit EER IPLV
080
100 228.5 47.6 4.8
6 .275 171.4 29.8 5.7
50 114.3 17.6 6.5
25 57.1 8.8 6.5
090
100 254.2 53.3 4.8
6 .275 190.6 33.2 5.7
50 127.1 19.7 6.5
25 63.5 9.8 6.5
100
100 285.4 58.7 4.9
6 .275 214.1 36.9 5.8
50 142.7 21.9 6.5
25 71.4 11.0 6.5
115
100 329.5 68.2 4.8
6 .275 247.1 43.0 5.7
50 164.7 25.4 6.5
25 82.4 12.6 6.5
130
100 369.8 77.9 4.7
6 .175 277.3 48.5 5.7
50 184.9 28.6 6.5
25 92.4 14.2 6.5
150
100 432.5 89.0 4.9
6 .475 324.4 54.2 6.0
50 216.3 31.9 6.8
25 108.1 16.1 6.7
170
100 494.1 101.6 4.9
6 .575 370.6 61.3 6.0
50 247.0 36.3 6.8
25 123.5 18.4 6.7
200
100 549.0 112.9 4.9
6 .475 411.7 69.1 6.0
50 274.5 40.7 6.7
25 137.2 20.3 6.8
CAT 613-3 • MODEL WGZ CHILLERS 22 www.DaikinApplied.com
pressure drop daTa
Figure 6: WGZ-D Condenser Pressure Drop Curves
Table 24: WGZ-D Condenser Pressure Drop Data
A
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
I
I
J
J
K
K
L
L
M
M
N
N
O
O
P
P
1
10
100
10 100 1000
Dp
(ft)
Flow Rate (gpm)
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Model Curve Ref
Minimum Flow & Pressure Drop Nominal Flow & Pressure Drop Maximum Flow & Pressure DropInch-Pound S .I . Inch-Pound S .I . Inch-Pound S .I .
GPM Ft L/S kPa GPM Ft L/S kPa GPM Ft L/S kPaWGZ030D A 56.3 2.6 3.5 7.7 90.0 6.3 5.6 18.8 150.0 16.6 9.4 49.7
WGZ035D B 64.9 3.6 4.1 10.8 103.8 8.8 6.5 26.3 173.0 23.2 10.8 69.4
WGZ040D C 76.3 2.9 4.8 8.6 122.1 7.0 7.6 20.9 203.5 18.5 12.7 55.2
WGZ045D D 85.3 3.9 5.3 11.6 136.5 9.5 8.5 28.4 227.5 25.1 14.2 74.9
WGZ050D E 96.4 3.0 6.0 9.1 154.2 7.4 9.6 22.1 257.0 19.5 16.1 58.4
WGZ055D F 105.8 4.1 6.6 12.1 169.2 9.9 10.6 29.6 282.0 26.1 17.6 78.1
WGZ060D G 113.4 5.2 7.1 15.4 181.5 12.6 11.3 37.7 302.5 33.3 18.9 99.4
WGZ070D H 131.6 4.3 8.2 12.8 210.6 10.5 13.2 31.4 351.0 27.7 21.9 82.8
WGZ080D I 146.8 3.9 9.2 11.6 234.9 9.5 14.7 28.4 391.5 25.1 24.5 74.9
WGZ090D J 163.3 3.8 10.2 11.3 261.3 9.2 16.3 27.5 435.5 24.3 27.2 72.6
WGZ100D K 183.4 3.8 11.5 11.3 293.4 9.2 18.3 27.5 489.0 24.3 30.6 72.6
WGZ115D L 237.6 5.0 14.8 15.1 380.1 12.3 23.8 36.8 633.5 32.5 39.6 97.0
WGZ130D M 237.6 6.6 14.8 19.8 380.1 16.2 23.8 48.4 633.5 42.8 39.6 127.8
WGZ150D N 277.9 6.5 17.4 19.3 444.6 15.8 27.8 47.2 741.0 41.7 46.3 124.7
WGZ170D O 317.4 5.7 19.8 17.1 507.9 14.0 31.7 41.8 846.5 37.0 52.9 110.5
WGZ200D P 352.7 7.7 22.0 23.0 564.3 18.8 35.3 56.2 940.5 49.6 58.8 148.3
pressure drop daTa
pressure drop daTa
www.DaikinApplied.com 23 CAT 613-3 • MODEL WGZ CHILLERS
Figure 7: WGZ-D Evaporator Pressure Drop Curves
Table 25: WGZ-D Evaporator Pressure Drop Data
A
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
I
I
J
J
K
K
L
L
M
M
N
N
O
O
P
P
1
10
100
10 100 1000
Dp
(ft)
Flow Rate (gpm)
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Model Curve Ref
Minimum Flow & Pressure Drop Nominal Flow & Pressure Drop Maximum Flow & Pressure DropInch-Pound S .I . Inch-Pound S .I . Inch-Pound S .I .
GPM Ft L/S kPa GPM Ft L/S kPa GPM Ft L/S kPaWGZ030D A 45.0 4.9 2.8 14.7 72.0 12.0 4.5 35.9 120.0 31.7 7.5 94.7
WGZ035D B 51.9 5.4 3.2 16.3 83.0 13.3 5.2 39.8 138.3 35.1 8.6 104.9
WGZ040D C 61.1 6.3 3.8 19.0 97.7 15.5 6.1 46.3 162.8 40.9 10.2 122.3
WGZ045D D 68.3 6.0 4.3 18.0 109.2 14.7 6.8 43.9 182.0 38.8 11.4 116.0
WGZ050D E 77.1 6.1 4.8 18.2 123.4 14.9 7.7 44.5 205.7 39.3 12.9 117.6
WGZ055D F 84.6 6.5 5.3 19.3 135.4 15.8 8.5 47.2 225.7 41.7 14.1 124.7
WGZ060D G 90.8 5.9 5.7 17.7 145.2 14.5 9.1 43.3 242.0 38.3 15.1 114.4
WGZ070D H 105.3 6.5 6.6 19.3 168.5 15.8 10.5 47.2 280.8 41.7 17.6 124.7
WGZ080D I 117.4 4.9 7.3 14.7 187.9 12.0 11.7 35.9 313.2 31.7 19.6 94.7
WGZ090D J 130.6 5.2 8.2 15.7 209.0 12.8 13.1 38.3 348.3 33.8 21.8 101.0
WGZ100D K 146.7 4.8 9.2 14.4 234.7 11.8 14.7 35.3 391.2 31.1 24.4 93.1
WGZ115D L 169.4 5.0 10.6 15.1 271.0 12.3 16.9 36.8 451.7 32.5 28.2 97.0
WGZ130D M 190.1 5.3 11.9 15.9 304.1 13.0 19.0 38.9 506.8 34.3 31.7 102.6
WGZ150D N 222.3 6.2 13.9 18.6 355.7 15.2 22.2 45.4 592.8 40.1 37.1 119.9
WGZ170D O 253.9 7.4 15.9 22.0 406.3 18.0 25.4 53.8 677.2 47.5 42.3 142.0
WGZ200D P 282.1 9.0 17.6 26.9 451.4 22.0 28.2 65.8 752.3 58.1 47.0 173.6
CAT 613-3 • MODEL WGZ CHILLERS 24 www.DaikinApplied.com
physICal daTa - paCkaged unITs
Table 26: Physical Data - WGZ030D - WGZ040D
Table 27: Physical Data - WGZ045D - WGZ055D
Physical Data (Packaged Chillers)WGZ030D WGZ035D WGZ040D
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2BASIC DATA Operating Weight- lb (kg) 2484 (1127) 2564 (1163) 2615 (1186) Shipping Weight- lb (kg) 2408 (1092) 2488 (1129) 2523 (1144) R410A Operating Charge- lb (kg) 43 (19.5) 43 (19.5) 43 (19.5) 43 (19.5) 43 (19.5) 43 (19.5)COMPRESSORS, SCROLL, HERMETIC Nominal HP 7.5 / 7.5 7.5 / 7.5 9 / 9 9 / 9 10 / 10 10 / 10
Oil Charge, per Compressor- oz (L)85 (2.5) 85 (2.5) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3)85 (2.5) 85 (2.5) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3)
Staging, 4 Stages (If Circuit is in Lead) 25-50-75-100 25-50-75-100 25-50-75-100 25-50-75-100 25-50-75-100 25-50-75-100CONDENSER Diameter- in. (mm) 10 (254) 10 (254) 10 (254) Tube Length- in. (mm) 120 (3048) 120 (3048) 120 (3048) Refrigerant Side Working Pressure- psig (kPa) 500 (3447) 500 (3447) 500 (3447) Water Side Working Pressure- psig (kPa) 232 (1599) 232 (1599) 232 (1599) Pump-Out Capacity- lb (kg) [90% Full at 90°F] 245.8 (111.7) 245.8 (111.7) 228.2 (103.7) Grooved Conn. In & Out- in. (mm) 4 (102) 4 (102) 4 (102) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9) Purge Valve, Flare- in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) Vent & Drain- in. (mm) NPT 1/4 (6.4) 1/4 (6.4) 1/4 (6.4)EVAPORATOR, BRAZED-PLATE Water Volume- gal (L) 1.6 (6.1) 1.8 (6.8) 2.0 (7.6) Refrigerant Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) 653 (4500) Water Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) 653 (4500) Grooved Conn. In & Out- in. (mm) 2.5 (65) 2.5 (65) 2.5 (65) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9) Vent & Drain Field Field Field
Physical Data (Packaged Chillers)WGZ045D WGZ050D WGZ055D
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2BASIC DATA Operating Weight- lb (kg) 2631 (1193) 2719 (1233) 2731 (1239) Shipping Weight- lb (kg) 2539 (1152) 2606 (1182) 2618 (1188) R410A Operating Charge- lb (kg) 47 (21.4) 47 (21.4) 47 (21.4) 47 (21.4) 50 (22.7) 50 (22.7)COMPRESSORS, SCROLL, HERMETIC Nominal HP 12 / 12 12 / 12 13 / 13 13 / 13 13 / 13 15 / 15
Oil Charge, per Compressor- oz (L)110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3)110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3)
Staging, 4 Stages (If Circuit is in Lead) 25-50-75-100 25-50-75-100 25-50-75-100 25-50-75-100 23-50-73-100 27-50-77-100CONDENSER Diameter- in. (mm) 10 (254) 10 (254) 10 (254) Tube Length- in. (mm) 120 (3048) 120 (3048) 120 (3048) Refrigerant Side Working Pressure- psig (kPa) 500 (3447) 500 (3447) 500 (3447) Water Side Working Pressure- psig (kPa) 232 (1599) 232 (1599) 232 (1599) Pump-Out Capacity- lb (kg) [90% Full at 90°F] 228.2 (103.7) 205.4 (93.4) 205.4 (93.4) Grooved Conn. In & Out- in. (mm) 4 (102) 4 (102) 4 (102) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9) Purge Valve, Flare- in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) Vent & Drain- in. (mm) NPT 1/4 (6.4) 1/4 (6.4) 1/4 (6.4)EVAPORATOR, BRAZED-PLATE Water Volume- gal (L) 2.3 (8.7) 2.6 (9.8) 2.8 (10.6) Refrigerant Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) 653 (4500) Water Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) 653 (4500) Grooved Conn. In & Out- in. (mm) 2.5 (65) 2.5 (65) 2.5 (65) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9) Vent & Drain Field Field Field
physICal daTa - paCkaged unITs
physICal daTa - paCkaged unITs
www.DaikinApplied.com 25 CAT 613-3 • MODEL WGZ CHILLERS
Table 28: Physical Data - WGZ060D - WGZ070D
Table 29: Physical Data - WGZ080D - WGZ090D
Physical Data (Packaged Chillers)WGZ060D WGZ070D
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2BASIC DATA Operating Weight- lb (kg) 2771 (1257) 3696 (1676) Shipping Weight- lb (kg) 2658 (1206) 3555 (1613) R410A Operating Charge- lb (kg) 50 (22.7) 50 (22.7) 74 (33.6) 74 (33.6)COMPRESSORS, SCROLL, HERMETIC Nominal HP 15 / 15 15 / 15 15 / 20 15 / 20
Oil Charge, per Compressor- oz (L)110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3)110 (3.3) 110 (3.3) 152 (4.5) 152 (4.5)
Staging, 4 Stages (If Circuit is in Lead) 25-50-75-100 25-50-75-100 22-44-72-100 22-44-72-100CONDENSER Diameter- in. (mm) 10 (254) 14 (356) Tube Length- in. (mm) 120 (3048) 120 (3048) Refrigerant Side Working Pressure- psig (kPa) 500 (3447) 500 (3447) Water Side Working Pressure- psig (kPa) 232 (1599) 232 (1599) Pump-Out Capacity- lb (kg) [90% Full at 90°F] 205.4 (93.4) 415.1 (188.7) Grooved Conn. In & Out- in. (mm) 4 (102) 4 (102) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) Purge Valve, Flare- in. (mm) 1/2 (12.7) 1/2 (12.7) Vent & Drain- in. (mm) NPT 1/4 (6.4) 1/4 (6.4)EVAPORATOR, BRAZED-PLATE Water Volume- gal (L) 3.2 (12.0) 5.6 (21.2) Refrigerant Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) Water Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) Grooved Conn. In & Out- in. (mm) 2.5 (65) 3 (76) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) Vent & Drain Field Field
Physical Data (Packaged Chillers)WGZ080D WGZ090D
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2BASIC DATA Operating Weight- lb (kg) 4128 (1872) 4320 (1960) Shipping Weight- lb (kg) 3971 (1801) 4140 (1878) R410A Operating Charge- lb (kg) 80 (36.4) 80 (36.4) 80 (36.4) 80 (36.4)COMPRESSORS, SCROLL, HERMETIC Nominal HP 20 / 20 20 / 20 20 / 26 20 / 26
Oil Charge, per Compressor- oz (L)152 (4.5) 152 (4.5) 152 (4.5) 152 (4.5)152 (4.5) 152 (4.5) 152 (4.5) 152 (4.5)
Staging, 4 Stages (If Circuit is in Lead) 25-50-75-100 25-50-75-100 22-44-72-100 22-44-72-100CONDENSER Diameter- in. (mm) 14 (356) 14 (356) Tube Length- in. (mm) 120 (3048) 120 (3048) Refrigerant Side Working Pressure- psig (kPa) 500 (3447) 500 (3447) Water Side Working Pressure- psig (kPa) 232 (1599) 232 (1599) Pump-Out Capacity- lb (kg) [90% Full at 90°F] 397.5 (180.7) 371.1 (168.7) Grooved Conn. In & Out- in. (mm) 4 (102) 4 (102) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) Purge Valve, Flare- in. (mm) 1/2 (12.7) 1/2 (12.7) Vent & Drain- in. (mm) NPT 1/4 (6.4) 1/4 (6.4)EVAPORATOR, BRAZED-PLATE Water Volume- gal (L) 6.3 (23.8) 6.8 (25.7) Refrigerant Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) Water Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) Grooved Conn. In & Out- in. (mm) 3 (76) 3 (76) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) Vent & Drain Field Field
CAT 613-3 • MODEL WGZ CHILLERS 26 www.DaikinApplied.com
physICal daTa - paCkaged unITs
Table 30: Physical Data - WGZ100D - WGZ130D
Table 31: Physical Data - WGZ150D - WGZ200D
Physical Data (Packaged Chillers)WGZ100D WGZ115D WGZ130D
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2BASIC DATA Operating Weight- lb (kg) 4515 (2048) 4434 (2011) 4737 (2149) Shipping Weight- lb (kg) 4311 (1955) 4230 (1919) 4533 (2056) R410A Operating Charge- lb (kg) 90 (40.9) 90 (40.9) 100 (45.5) 100 (45.5) 100 (45.5) 100 (45.5)COMPRESSORS, SCROLL, HERMETIC Nominal HP 26 / 26 26 / 26 26 / 30 26 / 30 30 / 30 30 / 30
Oil Charge, per Compressor- oz (L)152 (4.5) 152 (4.5) 152 (4.5) 152 (4.5) 213 (6.3) 213 (6.3)152 (4.5) 152 (4.5) 213 (6.3) 213 (6.3) 213 (6.3) 213 (6.3)
Staging, 4 Stages (If Circuit is in Lead) 25-50-75-100 25-50-75-100 22-44-72-100 22-44-72-100 25-50-75-100 25-50-75-100CONDENSER Diameter- in. (mm) 14 (356) 14 (356) 14 (356) Tube Length- in. (mm) 120 (3048) 120 (3048) 120 (3048) Refrigerant Side Working Pressure- psig (kPa) 500 (3447) 500 (3447) 500 (3447) Water Side Working Pressure- psig (kPa) 232 (1599) 232 (1599) 232 (1599) Pump-Out Capacity- lb (kg) [90% Full at 90°F] 344.7 (156.7) 344.7 (156.7) 344.7 (156.7) Grooved Conn. In & Out- in. (mm) 4 (102) 4 (102) 4 (102) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9) Purge Valve, Flare- in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) Vent & Drain- in. (mm) NPT 1/4 (6.4) 1/4 (6.4) 1/4 (6.4)EVAPORATOR, BRAZED-PLATE Water Volume- gal (L) 8.0 (30.2) 9.6 (36.3) 10.8 (40.9) Refrigerant Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) 653 (4500) Water Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) 653 (4500) Grooved Conn. In & Out- in. (mm) 3 (76) 3 (76) 3 (76) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9) Vent & Drain Field Field Field
Physical Data (Packaged Chillers)WGZ150D WGZ170D WGZ200D
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2BASIC DATA Operating Weight- lb (kg) 6662 (3022) 7214 (3272) 7509 (3406) Shipping Weight- lb (kg) 5873 (2664) 6377 (2893) 6672 (3026) R410A Operating Charge- lb (kg) 150 (68.2) 150 (68.2) 150 (68.2) 150 (68.2) 150 (68.2) 150 (68.2)COMPRESSORS, SCROLL, HERMETIC Nominal HP 26 / 26 / 26 26 / 26 / 26 26 / 26 / 26 30 / 30 / 30 30 / 30 / 30 30 / 30 / 30
Oil Charge, per Compressor- oz (L)152 (4.5) 152 (4.5) 152 (4.5) 213 (6.3) 213 (6.3) 213 (6.3)152 (4.5) 152 (4.5) 152 (4.5) 213 (6.3) 213 (6.3) 213 (6.3)152 (4.5) 152 (4.5) 152 (4.5) 213 (6.3) 213 (6.3) 213 (6.3)
Staging, 6 Stages (If Circuit is in Lead) 17-33-50-67- 83-100
17-33-50-67- 83-100
15-33-48-67- 81-100
19-33-52-67- 86-100
17-33-50-67- 83-100
17-33-50-67- 83-100
CONDENSER Diameter- in. (mm) 16 (406.4) 16 (406.4) 16 (406.4) Tube Length- in. (mm) 144 (3658) 144 (3658) 144 (3658) Refrigerant Side Working Pressure- psig (kPa) 500 (3447) 500 (3447) 500 (3447) Water Side Working Pressure- psig (kPa) 232 (1599) 232 (1599) 232 (1599) Pump-Out Capacity- lb (kg) [90% Full at 90°F] 572.3 (260.1) 508.9 (231.3) 508.9 (231.3) Grooved Conn. In & Out- in. (mm) 5 (127) 5 (127) 5 (127) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9) Purge Valve, Flare- in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) Vent & Drain- in. (mm) NPT 1/4 (6.4) 1/4 (6.4) 1/4 (6.4)EVAPORATOR, SHELL-AND-TUBE Water Volume- gal (L) 57.6 (218.0) 56.9 (215.4) 56.9 (215.4) Refrigerant Side Working Pressure- psig (kPa) 450 (3102) 450 (3102) 450 (3102) Water Side Working Pressure- psig (kPa) 150 (1034) 150 (1034) 150 (1034) Grooved Conn. In & Out- in. (mm) 8 (203) 8 (203) 8 (203) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9)
physICal daTa - Condenserless unITs
www.DaikinApplied.com 27 CAT 613-3 • MODEL WGZ CHILLERS
Table 32: Physical Data - WGZ030D - WGZ040D
Table 33: Physical Data - WGZ045D - WGZ055D
Physical Data (Condenserless Chillers)WGZ030D WGZ035D WGZ040D
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2BASIC DATA Operating Weight- lb (kg) 1604 (728) 1690 (767) 1699 (771) Shipping Weight- lb (kg) 1578 (716) 1662 (754) 1669 (757)COMPRESSORS, SCROLL, HERMETIC Nominal HP 7.5 / 7.5 7.5 / 7.5 9 / 9 9 / 9 10 / 10 10 / 10
Oil Charge, per Compressor- oz. (L)85 (2.5) 85 (2.5) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3)85 (2.5) 85 (2.5) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3)
Staging, 4 Stages (If Circuit is in Lead) 25-50-75-100 25-50-75-100 25-50-75-100 25-50-75-100 25-50-75-100 25-50-75-100EVAPORATOR, BRAZED PLATE Water Volume- gal (L) 1.6 (6.1) 1.8 (6.8) 2.0 (7.6) Refrigerant Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) 653 (4500)) Water Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) 653 (4500)) Grooved Conn. In & Out- in. (mm) 2.5 (65) 2.5 (65) 2.5 (65) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9) Vent & Drain Field Field Field
Physical Data (Condenserless Chillers)WGZ045D WGZ050D WGZ055D
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2BASIC DATA Operating Weight- lb (kg) 1719 (780) 1740 (789) 1755 (796) Shipping Weight- lb (kg) 1685 (764) 1702 (772) 1714 (778)COMPRESSORS, SCROLL, HERMETIC Nominal HP 12 / 12 12 / 12 13 / 13 13 / 13 13 / 13 15 / 15
Oil Charge, per Compressor- oz. (L)110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3)110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3)
Staging, 4 Stages (If Circuit is in Lead) 25-50-75-100 25-50-75-100 25-50-75-100 25-50-75-100 23-50-73-100 27-50-77-100EVAPORATOR, BRAZED PLATE Water Volume- gal (L) 2.3 (8.7) 2.6 (9.8) 2.8 (10.6) Refrigerant Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) 653 (4500) Water Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) 653 (4500) Grooved Conn. In & Out- in. (mm) 2.5 (65) 2.5 (65) 2.5 (65) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9) Vent & Drain Field Field Field
physICal daTa - Condenserless unITs
CAT 613-3 • MODEL WGZ CHILLERS 28 www.DaikinApplied.com
physICal daTa - Condenserless unITs
Table 34: Physical Data - WGZ060D - WGZ070D
Table 35: Physical Data - WGZ080D - WGZ090D
Physical Data (Condenserless Chillers)WGZ060D WGZ070D
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2BASIC DATA Operating Weight- lb (kg) 1786 (810) 2296 (1041) Shipping Weight- lb (kg) 1741 (790) 2228 (1010)COMPRESSORS, SCROLL, HERMETIC Nominal HP 15 / 15 15 / 15 15 / 20 15 / 20
Oil Charge, per Compressor- oz. (L)110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3)110 (3.3) 110 (3.3) 152 (4.5) 152 (4.5)
Staging, 4 Stages (If Circuit is in Lead) 25-50-75-100 25-50-75-100 22-50-72-100 22-50-72-100EVAPORATOR, BRAZED PLATE Water Volume- gal (L) 3.2 (12.0) 5.6 (21.2) Refrigerant Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) Water Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) Grooved Conn. In & Out- in. (mm) 2.5 (63) 3 (76) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) Vent & Drain Field Field
Physical Data (Condenserless Chillers)WGZ080D WGZ090D
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2BASIC DATA Operating Weight- lb (kg) 2649 (1202) 2778 (1260) Shipping Weight- lb (kg) 2579 (1170) 2701 (1225)COMPRESSORS, SCROLL, HERMETIC Nominal HP 20 / 20 20 / 20 20 / 26 20 / 26
Oil Charge, per Compressor- oz. (L)152 (4.5) 152 (4.5) 152 (4.5) 152 (4.5)152 (4.5) 152 (4.5) 152 (4.5) 152 (4.5)
Staging, 4 Stages (If Circuit is in Lead) 25-50-75-100 25-50-75-100 22-44-72-100 22-44-72-100EVAPORATOR, BRAZED PLATE Water Volume- gal (L) 6.3 (23.8) 6.8 (25.7) Refrigerant Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) Water Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) Grooved Conn. In & Out- in. (mm) 3 (76) 3 (76) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) Vent & Drain Field Field
physICal daTa - Condenserless unITs
www.DaikinApplied.com 29 CAT 613-3 • MODEL WGZ CHILLERS
Table 36: Physical Data - WGZ100D - WGZ130D
Table 37: Physical Data - WGZ150D - WGZ200D
Physical Data (Condenserless Chillers)WGZ100D WGZ115D WGZ130D
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2BASIC DATA Operating Weight- lb (kg) 2923 (1326) 2878 (1305) 3196 (1450) Shipping Weight- lb (kg) 2841 (1289) 2792 (1266) 3094 (1403)COMPRESSORS, SCROLL, HERMETIC Nominal HP 26 / 26 26 / 26 26 / 30 26 / 30 30 / 30 30 / 30
Oil Charge, per Compressor- oz. (L)152 (4.5) 152 (4.5) 152 (4.5) 152 (4.5) 213 (6.3) 213 (6.3)152 (4.5) 152 (4.5) 213 (6.3) 213 (6.3) 213 (6.3) 213 (6.3)
Staging, 4 Stages (If Circuit is in Lead) 25-50-75-100 25-50-75-100 22-50-72-100 22-50-72-100 25-50-75-100 25-50-75-100EVAPORATOR, BRAZED PLATE Water Volume- gal (L) 8.0 (30.2) 8.5 (32.1) 10.5 (39.7) Refrigerant Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) 653 (4500) Water Side Working Pressure- psig (kPa) 653 (4500) 653 (4500) 653 (4500) Grooved Conn. In & Out- in. (mm) 3 (76) 3 (76) 3 (76) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9) Vent & Drain Field Field Field
Physical Data (Condenserless Chillers)WGZ150D WGZ170D WGZ200D
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2BASIC DATA Operating Weight- lb (kg) 4571 (2073) 4841 (2196) 5134 (2334) Shipping Weight- lb (kg) 4071 (1847) 4347 (1972) 4640 (2105)COMPRESSORS, SCROLL, HERMETIC Nominal HP 26 / 26 / 26 26 / 26 / 26 26 / 26 / 26 30 / 30 / 30 30 / 30 / 30 30 / 30 / 30
Oil Charge, per Compressor- oz. (L)152 (4.5) 152 (4.5) 152 (4.5) 213 (6.3) 213 (6.3) 213 (6.3)152 (4.5) 152 (4.5) 152 (4.5) 213 (6.3) 213 (6.3) 213 (6.3)152 (4.5) 152 (4.5) 152 (4.5) 213 (6.3) 213 (6.3) 213 (6.3)
Staging, 6 Stages (If Circuit is in Lead) 17-33-50-67- 83-100
17-33-50-67- 83-100
15-33-48-67- 81-100
19-33-52-67- 86-100
17-33-50-67- 83-100
17-33-50-67- 83-100
EVAPORATOR, SHELL-AND-TUBE Water Volume- gal (L) 57.6 (218.0) 56.9 (215.4) 56.9 (215.4) Refrigerant Side Working Pressure- psig (kPa) 450 (3102) 450 (3102) 450 (3102) Water Side Working Pressure- psig (kPa) 150 (1034) 150 (1034) 150 (1034) Grooved Conn. In & Out- in. (mm) 8 (203) 8 (203) 8 (203) Relief Valve, Flare- in. (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9)
CAT 613-3 • MODEL WGZ CHILLERS 30 www.DaikinApplied.com
dImensIons - paCkaged unITs
Figure 8: WGZ030DW - 060DW (Packaged)
121.
130
753.
8 98
134.
634
19
9.7
246
X
Y
29.0
.875
DIA
. MO
UN
TIN
G H
OLE
S (4
)73
7
13.3
338
2.0 51
23.3
592
Z
"A"
15.59
REF
.
*333
6115
21*
p. 1
of 2
CERT
IFIE
D, W
GZ0
30-0
60D
, PA
CKA
GE
REV
00
CIRC
UIT
2
OU
TLET
INLE
T
DRA
IN
VEN
T
WA
TER
CON
NEC
TIO
NS
MIC
ROTE
CH II
USE
R IN
TERF
ACE
CON
DEN
SER
COU
LD B
E O
N O
PPO
SITE
NO
TE: C
ON
DEN
SER
END
IF O
RDER
ED A
S LH
.
CIRC
UIT
1
RELI
EF V
ALV
ES
3.9
100
EVA
PORA
TOR
FOR
SHIP
PIN
G
OU
TLET
REM
OVE
BRK
T.
DIS
C. H
AN
DLE
.88
KNO
CKO
UTS
.88
KNO
CKO
UTS
CON
NEC
TIO
NS
INLE
T
ON
OPP
OSI
TE S
IDE
REM
OVA
BLE
ON
LY
POW
ER
CON
TRO
LCO
NN
ECTI
ON
S
770
30.3
1609
63.4
30.4
771
14.1
359
8.2
209
32.0
813
1140
44.9
1016
40.0
314
12.4
508
20.0
33.0
837
6.0
153
CON
DEN
SER
WAT
ER
CON
NEC
TIO
N IN
(MM
) VI
CTAU
LIC
SIZ
E (N
OM
)A
SIZ
E (N
OM
)X
YZ
2.5
14.4
459
.222
.414
.1(6
4)(3
66)
(102
)(1
504)
(569
)(3
58)
2.5
13.7
459
.923
.314
.2(6
4)(3
49)
(102
)(1
522)
(592
)(3
61)
2.5
13.0
459
.523
.214
.2(6
4)(3
31)
(102
)(1
511)
(589
)(3
61)
2.5
11.7
459
.123
.314
.2(6
4)(2
96)
(102
)(1
501)
(592
)(3
61)
2.5
10.3
458
.920
.214
.2(6
4)(2
60)
(102
)(1
496)
(513
)(3
61)
2.5
9.6
458
.520
.314
.2(6
4)(2
43)
(102
)(1
486)
(516
)(3
61)
2.5
7.8
457
.920
.514
.3(6
4)(1
99)
(102
)(1
471)
(521
)(3
63)
CHIL
LER
WAT
ER
CON
NEC
TIO
N
IN(M
M) V
ICTA
ULI
C
CEN
TER
OF
GRA
VITY
WG
Z M
OD
EL
NU
MBE
R
WG
Z030
D
WG
Z055
D
WG
Z060
D
WG
Z035
D
WG
Z040
D
WG
Z045
D
WG
Z050
D
dImensIons - paCkaged unITs
dImensIons - paCkaged unITs
www.DaikinApplied.com 31 CAT 613-3 • MODEL WGZ CHILLERS
Figure 9: WGZ070DW (Packaged)
145.
536
95
10.2
259
121.
130
75
14.2
361
X
Y
2.0 51
29.0
.875
DIA
MO
UN
TIN
G H
OLE
S (4
)73
7
13.0
330
23.5
597
Z
*333
6116
21*
p. 1
&2 o
f 3CE
RTIF
IED
, WG
Z070
-130
D, P
ACK
AG
ERE
V 0A
VEN
T
DRA
IN
CG
NO
TE: C
ON
DEN
SER
WA
TER
CON
NEC
TIO
NS
CON
DEN
SER
OU
TLET
COU
LD B
E O
N O
PPO
SITE
MIC
ROTE
CH II
USE
R IN
TERF
ACE
INLE
T
END
IF O
RDER
ED A
S LH
.RE
LIEF
VA
LVES
CIRC
UIT
2CI
RCU
IT 1
4 IN
. VIC
TAU
LIC
CON
NEC
TIO
NS
4.0
102
ON
LY
REM
OVE
BRK
T.
INLE
T
FOR
SHIP
PIN
G
.88
KNO
CKO
UTS
CON
NEC
TIO
NS
REM
OVA
BLE
.88
KNO
CKO
UTS
CON
TRO
L
DIS
C. H
AN
DLE
CON
NEC
TIO
NS
EVA
PORA
TOR
CG
ON
OPP
OSI
TE S
IDE
OU
TLET
POW
ER
3 IN
. VIC
TAU
LIC
CON
NEC
TIO
NS
14.5
369
20.0
508
65.5
1664
35.2
894 32
.682
7
1016
40.0
1434
56.4
866
34.1
454
17.9
253
10.0
813
32.040
.210
21
.6 15A
OU
TLET
INLE
T
6.0
152
CON
DEN
SER
WAT
ER
CON
NEC
TIO
N IN
(MM
) VI
CTAU
LIC
SIZ
E (N
OM
)A
SIZ
E (N
OM
)X
YZ
3
CHIL
LER
WAT
ER
CON
NEC
TIO
N
IN(M
M) V
ICTA
ULI
C
CEN
TER
OF
GRA
VITY
WG
Z M
OD
EL
NU
MBE
R
WG
Z070
D(7
6)11
.3(2
87)
4(1
02)
61.7
(156
8)28
.2(7
16)
15.0
(381
)
CAT 613-3 • MODEL WGZ CHILLERS 32 www.DaikinApplied.com
dImensIons - paCkaged unITs
Figure 10: WGZ080DW - 130DW (Packaged)
121.
130
75
14.2
361
L
T
Y
X
"A"
2.0 51
29.0
.875
DIA
MO
UN
TIN
G H
OLE
S (4
)73
7
13.0
330
23.5
597
Z
*333
6116
21*
p. 3
of 4
CERT
IFIE
D, W
GZ0
70-1
30D
, PA
CKA
GE
REV
0A
MIC
ROTE
CH II
USE
R IN
TERF
ACE
CIRC
UIT
2CI
RCU
IT 1
CON
DEN
SER
RELI
EF V
ALV
ES
VEN
T
OU
TLET
INLE
T
DRA
IN
NO
TE: C
ON
DEN
SER
WA
TER
CON
NEC
TIO
NS
COU
LD B
E O
N O
PPO
SITE
END
IF O
RDER
ED A
S LH
.
4.0
102
6.0
152
POW
ERCO
NN
ECTI
ON
S.8
8 KN
OCK
OU
TS
REM
OVA
BLE
DIS
C. H
AN
DLE
CON
TRO
LCO
NN
ECTI
ON
S.8
8 KN
OCK
OU
TSO
N O
PPO
SITE
SID
E
REM
OVE
BRK
T.FO
R SH
IPPI
NG
ON
LY
EVA
PORA
TOR
INLE
T
OU
TLET
40.0
1016
56.4
1434
34.1
866
17.9
454
10.0
253
32.0
813
20.0
508
14.5
369
65.5
1664
35.2
89440
.210
22
32.6
827
MAX
IMU
M
OVE
RALL
LE
NG
TH IN
(MM
)
CO
ND
ENSE
R W
ATER
C
ON
NEC
TIO
N IN
(MM
) VI
CTA
ULI
C
LSI
ZE (N
OM
)A
SIZE
(NO
M)
TX
YZ
149
38.
84
13.8
64.2
29.5
15(3
785)
(76)
(224
)(1
02)
(351
)(1
631)
(749
)(3
81)
149
38.
04
13.8
67.2
32.6
16(3
785)
(76)
(203
)(1
02)
(351
)(1
707)
(828
)(4
06)
149
36.
04
13.8
69.2
35.4
17(3
785)
(76)
(152
)(1
02)
(351
)(1
758)
(899
)(4
32)
148
33.
14
12.9
6835
.617
(375
9)(7
6)(7
9)(1
02)
(328
)(1
727)
(904
)(4
32)
149
31.
04
13.7
67.7
36.1
17(3
785)
(76)
(25)
(102
)(3
48)
(172
0)(9
17)
(432
)
CH
ILLE
R W
ATER
C
ON
NEC
TIO
N
IN(M
M) V
ICTA
ULI
C
CEN
TER
OF
GRA
VITY
WG
Z130
D
WG
Z080
D
WG
Z M
OD
EL
NU
MBE
R
WG
Z090
D
WG
Z100
D
WG
Z115
D
dImensIons - paCkaged unITs
www.DaikinApplied.com 33 CAT 613-3 • MODEL WGZ CHILLERS
Figure 11: WGZ150DW - 200DW (Packaged)
X
Y
T
14
.23
61
14
5.1
36
85
Z
35
.89
08
13
.33
37
OU
TL
ET
36
.9
EV
AP
INL
ET
/
93
8
2.0 51
.87
5 D
IA. M
OU
NT
ING
HO
LE
S (
4)
29
.07
37
77
.21
96
12
3.5
59
6
*33
36
11
70
1*
p. 1
of 2
CE
RT.
, WG
Z1
50
-20
0D
, PA
CK
AG
E
RE
V 0
0
INL
ET
EV
AP
OR
AT
OR
DR
AIN
CO
ND
EN
SE
R
VE
NT
DR
AIN
VE
NT
MIC
RO
TE
CH
II U
SE
R IN
TE
RF
AC
EC
IRC
UIT
2C
IRC
UIT
1
OU
TL
ET
RE
LIE
F V
AL
VE
S
10
24
.0
17
0.3
43
26
ON
OP
PO
SIT
E S
IDE
ON
LY
RE
MO
VA
BL
E
.88
KN
OC
KO
UT
S
DIS
C. H
AN
DL
E
.88
KN
OC
KO
UT
SC
ON
NE
CT
ION
S
FO
R S
HIP
PIN
G
CO
NN
EC
TIO
NS
PO
WE
R
CO
NT
RO
L
RE
MO
VE
BR
KT
.
20
.05
08
40
.01
01
6
32
.08
13
18
.34
64
9.6
24
3
94
33
7.110
42
41
.0
31
8
H
12
.5
34
.58
76
EV
AP
OR
AT
OR
OU
TL
ET
EV
AP
OR
AT
OR
INL
ET
1.3 34
MA
XIM
UM
OV
ER
AL
L
HE
IGH
T I
N(M
M)
CH
ILL
ER
WA
TE
R
CO
NN
EC
TIO
N I
N(M
M)
VIC
TA
UL
IC
CO
ND
EN
SE
R W
AT
ER
CO
NN
EC
TIO
N I
N(M
M)
VIC
TA
UL
IC
HS
IZE
(N
OM
)S
IZE
(N
OM
)T
XY
Z
76.9
85
11
75
37.8
14.8
(1953)
(203)
(127)
(279)
(1905)
(960)
(376)
76.9
85
10.9
77.7
37.7
14.9
(1953)
(203)
(127)
(276)
(1974)
(958)
(379)
77.7
85
10.9
77.9
38.3
15
(1973)
(203)
(127)
(276)
(1979)
(973)
(381)
CE
NT
ER
OF
GR
AV
ITY
WG
Z150
D
WG
Z170
D
WG
Z200
D
WG
Z
MO
DE
L
NU
MB
ER
CAT 613-3 • MODEL WGZ CHILLERS 34 www.DaikinApplied.com
dImensIons - Condenserless unITs
Figure 12: WGZ030DA - 060DA (Condenserless)
Y
X
2.0 51
23.5
597
Z
41.3
1050
26.8
681
*333
6115
31*
p. 1
of 2
CERT
., WG
Z030
-060
D, L
ESS
CON
DRE
V 00
CIRC
UIT
1CI
RCU
IT 2
MIC
ROTE
CH II
USE
R IN
TERF
ACE
137.
034
80
152
312
12.3
6.0
20.2
512
ON
LY
OU
TLET
FOR
SHIP
PIN
GD
ISC.
HA
ND
LERE
MO
VABL
ERE
MO
VE B
RKT.
.88
DIA
. KN
OCK
OU
TS
INLE
T
ON
OPP
OSI
TE S
IDE
EVA
PORA
TOR
CON
TRO
L CO
NN
ECTI
ON
POW
ERCO
NN
ECTI
ON
S.8
8" D
IA. K
NO
CKO
UTS
ISO
LATO
R H
OLE
S (4
)76
2
DIS
CHA
RGE
60.0
419
CON
NEC
TIO
NS
5.9
150
CON
NEC
TIO
NS
LIQ
UID
1524
2.5 64
2.0
6.1
155
34.0
864
40.0
1016
9.0
229
20.0
508
5116
.5
EVA
P. A
ND
30.0
30.4
772
.88
LIQ
UID
INLE
T
OU
TLET
CON
NEC
TIO
NS
1.38
DIS
CHA
RGE
CON
NEC
TIO
NS
98.8
178
7.0
2509
2334
91.9
38.2
970
31.4
798
258
A
10.2
6.0
152
SIZE
(NO
M)
AX
YZ
2.5
22.4
67.3
22.8
13.3
(64)
(569
)(1
709)
(579
)(3
38)
2.5
21.7
68.2
23.8
13.4
(64)
(551
)(1
732)
(605
)(3
40)
2.5
21.0
67.6
23.9
13.5
(64)
(533
)(1
717)
(607
)(3
43)
2.5
19.6
67.1
24.0
13.6
(64)
(498
)(1
704)
(610
)(3
45)
2.5
18.2
66.7
24.4
13.6
(64)
(462
)(1
694)
(620
)(3
45)
2.5
17.5
66.1
24.5
13.6
(64)
(445
)(1
679)
(622
)(3
45)
2.5
15.8
65.7
24.6
13.7
(64)
(401
)(1
669)
(625
)(3
48)
CHIL
LER
WAT
ER
CON
NEC
TIO
N
IN(M
M) V
ICTA
ULI
CCE
NTE
R O
F G
RAVI
TYW
GZ
MO
DEL
N
UM
BER
WG
Z030
D
WG
Z055
D
WG
Z060
D
WG
Z035
D
WG
Z040
D
WG
Z045
D
WG
Z050
D
dImensIons - Condenserless unITs
dImensIons - Condenserless unITs
www.DaikinApplied.com 35 CAT 613-3 • MODEL WGZ CHILLERS
Figure 13: WGZ070DA (Condenserless)
Y
572.2
X
2.0 51
23.5
597
Z
CERT
. WG
Z070
-130
D, L
ESS
CON
DRE
V 00
*333
6116
31*
p. 1
of 3
CIRC
UIT
2
REM
OVA
BLE
USE
R IN
TERF
ACE
CG
BRA
CKET
CIRC
UIT
1M
ICRO
TECH
II
312
12.3
588
152
137.
0
23.2
3480
6.0
7.0
178
CON
TRO
L
CG
ON
LY
.88
KNO
CKO
UTS
CON
NEC
T-IO
NS
FOR
SHIP
PIN
G
OU
TLET
EVA
PORA
TOR
EVA
P. A
ND
ON
OPP
OSI
TE S
IDE
REM
OVA
BLE
DIS
CHA
RGE
DIS
C. H
AN
DLE
.88
KNO
CKO
UTS
CON
NEC
TIO
NS
CON
NEC
TIO
NS
INLE
T
LIQ
UID
POW
ERCO
NN
ECTI
ON
S
REM
OVE
BRA
CKET
.
229
9.0
512.0
762
ISO
LATO
R H
OLE
S (4
)
15.5
394
34.0
864
1.5 38
40.0
1016
4.0
101
155
32.4
823
60.0
1524
20.0
508
6.1
30.040
.110
17
1.38
DIS
CHA
RGE
CON
NEC
TIO
NS
INLE
T
1.13
LIQ
UID
CO
NN
ECTI
ON
S
OU
TLET
2457
96.7
659
25.9
28.6
725
338
13.3
98.7
2507
50.9
1293
38.2
970
A
9.4
238
6.0
152
SIZE
(NO
M)
AX
YZ
3 (76)
CHIL
LER
WAT
ER
CON
NEC
TIO
N
IN(M
M) V
ICTA
ULI
CCE
NTE
R O
F G
RAVI
TYW
GZ
MO
DEL
N
UM
BER
WG
Z070
D19
.2(4
89)
71.0
(180
4)28
.5(7
24)
15.3
(388
)
CAT 613-3 • MODEL WGZ CHILLERS 36 www.DaikinApplied.com
dImensIons - Condenserless unITs
Figure 14: WGZ080DA - 130DA (Condenserless)
X
Y
2.0 51
23.5
597
Z
CERT
. WG
Z070
-130
D, L
ESS
CON
DRE
V 00
*333
6116
31*
p. 2
of 3
REM
OVA
BLE
USE
R IN
TERF
ACE
CIRC
UIT
2
MIC
ROTE
CH II
CIRC
UIT
1
BRA
CKET
152
148
6.0
137.
034
80
12.3
312
5.8
588
23.2
7.0
178
CON
NEC
TIO
NS
INLE
T
FOR
SHIP
PIN
G
CON
NEC
TIO
NS
DIS
CHA
RGE
CON
TRO
L
DIS
C. H
AN
DLE
ION
S
ON
OPP
OSI
TE S
IDE
.88
KNO
CKO
UTS
REM
OVE
BRA
CKET
.RE
MO
VABL
E
EVA
PORA
TOR
OU
TLET
.88
KNO
CKO
UTS
ON
LY
LIQ
UID
CON
NEC
T-
POW
ERCO
NN
ECTI
ON
S
EVA
PORA
TOR
&6.
115
5
229
9.0
20.0
508
60.0
1524
2.0 51
ISO
LATO
R H
OLE
S (4
)76
2
394
15.5
864
34.0
32.4
1.5 38
40.0
1016
4.0
101
823
30.040
.110
17
DIS
CHA
RGE
CON
NEC
TIO
NS
"B"
OU
TLET
LIQ
UID
CO
NN
ECTI
ON
S "C
"
INLE
T
50.9
1293
28.6
725
7.4
"A"
188
96.5
2451
26.0
659
971
38.2
188
7.4
2509
98.8
338
13.3
6.0
152
SIZE
(NO
M)
AB
(DIS
CH
)C
(LIQ
)X
YZ
316
.875
.129
.515
.3)983(
)947()8091(
)724()67(
316
75.7
30.0
15.4
)193()267(
)3291()604(
)67(3
13.9
75.5
30.1
15.4
)193()567(
)8191()353(
)67(3
1173
.230
.215
.7)993(
)767()9581(
)972()67(
39
73.9
30.7
15.4
)193()087(
)7781()922(
)67(1.
62 O
.D.
1.13
O.D
.
1.13
O.D
.
1.13
O.D
.
1.13
O.D
.
WG
Z130
D
WG
Z080
D
WG
Z090
D
WG
Z100
D
WG
Z115
D
1.13
O.D
.
1.62
O.D
.
1.62
O.D
.
1.62
O.D
.
1.62
O.D
.
WG
Z M
OD
EL
NU
MBE
R
CHIL
LER
WAT
ER
CON
NEC
TIO
N IN
(MM
) VI
CTA
ULI
CCE
NTE
R O
F G
RAVI
TYRE
FRIG
ERA
NT
PIPI
NG
CO
NN
ECTI
ON
SIZ
E (IN
CHES
)
dImensIons - Condenserless unITs
www.DaikinApplied.com 37 CAT 613-3 • MODEL WGZ CHILLERS
Figure 15: WGZ150DA - 200DA (Condenserless) (see next page for more dimensions)
Y
X
2.0 51
23
.55
97
Z
*333611711*
p. 1
of 3
CE
RT
. W
GZ
15
0-2
00
D, L
ES
S C
ON
D.
RE
V 0
0
MIC
RO
TE
CH
II U
SE
R IN
TE
RF
AC
E
CIR
CU
IT 1
CIR
CU
IT 2
39
12
15
4.0
1.9 48
FO
R S
HIP
PIN
GO
NL
Y
DIS
C. H
AN
DL
ER
EM
OV
AB
LE
(QT
Y. 3
).8
8 K
NO
CK
OU
TS
CO
NN
EC
TIO
NS
PO
WE
R
ON
OP
PO
SIT
E S
IDE
.88
KN
OC
KO
UT
SC
ON
NE
CT
ION
SC
ON
TR
OL
RE
MO
VE
BR
KT
.
4.0
LIQ
UID
CO
NN
EC
TIO
NS
10
1
74
19
03
74
.9
10
16
40
.0
86
43
4.012
7
76
2IS
OL
AT
OR
HO
LE
S (
6)
51
2.0
50
82
0.0
22
99
.0
5.0
30
.0
2.9
40
.51
02
9
CH
ILL
ER
WA
TE
R
CO
NN
EC
TIO
N
IN(M
M)
VIC
TA
UL
ICS
IZE
(N
OM
)X
YZ
87
5.4
42
.61
5.9
(20
3)
(19
15
)(1
08
2)
(40
4)
87
7.3
43
.21
5.9
(20
3)
(19
63
)(1
09
7)
(40
4)
87
7.9
43
.71
5.7
(20
3)
(19
79
)(1
11
0)
(39
9)
CE
NT
ER
OF
GR
AV
ITY
WG
Z150D
WG
Z170D
WG
Z200D
WG
Z
MO
DE
L
NU
MB
ER
CAT 613-3 • MODEL WGZ CHILLERS 38 www.DaikinApplied.com
dImensIons - Condenserless unITs
Figure 16: WGZ150DA - 200DA (Condenserless) (continued)
*333611711*
p. 2
of 3
CE
RT
. W
GZ
15
0-2
00
D, L
ES
S C
ON
D.
RE
V 0
0
CIR
CU
IT 1
1.3
8 O
.D. L
IQU
IDC
ON
NE
CT
ION
S
CIR
CU
IT 2
OU
TL
ET
INL
ET
2.1
2 O
.D. D
ISC
HA
RG
EC
ON
NE
CT
ION
S
20
.95
30
17
96
70
.7
17
.44
43
34
.08
63
58
82
3.2
15
26
.0
10
69
42
.1
30
30
11
9.3
86
73
4.2
96
.22
44
3
11
.42
89
90
INL
ET
/OU
TL
ET
EV
AP
OR
AT
OR
59
CIR
CU
IT 1
DIS
CH
AR
GE
2.3
20
0
CIR
UC
IT 2
3.6
7.9
DIS
CH
AR
GE
12
.83
25
eleCTrICal daTa
www.DaikinApplied.com 39 CAT 613-3 • MODEL WGZ CHILLERS
Electrical Notes Notes for “Electrical Data Single Point” Power:
1. If a separate 115V power supply is used for the control circuit, then the wire sizing amps is 10 amps for all unit sizes.
2. Recommended power lead wire sizes for 3 conductors per conduit are based on 100% conductor ampacity in accordance with NEC. Voltage drop has not been included. It is recommended that power leads be kept short. All terminal block connections must be made with copper (type THW) wire.
3. The recommended power lead wire sizes are based on an ambient temperature of 86°F (30°C). Ampacity correction factors must be applied for other ambient temperatures. Refer to the National Electrical Code Handbook.
4. Must be electrically grounded according to national and local electrical codes.
Voltage Limitations:1. Within 10 percent of nameplate rating
2. Voltage unbalance not to exceed 2% with a resultant current unbalance of 6 to 10 times the voltage unbalance per NEMA MG-1, 1998 Standard. This is an important restriction that must be adhered to.
Notes for “Field Wiring Data”1. Requires a single disconnect to supply electrical power
to the unit. This power supply must either be fused or use an HACR type circuit breaker.
2. All field wiring to unit power block or optional non-fused disconnect switch must be copper.
3. All field wire size values given in the Electrical Data tables starting on page 44 apply to 75°C rated wire per NEC.
Supplemental Overloads OptionThe supplemental overloads option is used to reduce the required electrical service size and wire sizing (cost) to the packaged version of WGZ chillers (WGZ-DW models). This option is available for units with single point or multiple point electrical power connections. Refer to the data tables starting on page 42 for electrical information on units with and without the overloads option.
Circuit BreakersThe circuit breaker used in the High Short Circuit panel option may have a higher trip rating than the unit Maximum Overload Protection (MOP) value shown on the unit name plate. The circuit breaker is installed as a service disconnect switch and does not function as branch circuit protection, mainly that the protection device must be installed at the point of origin of the power wiring. The breaker (disconnect switch) is oversized to avoid nuisance trips at high ambient temperature conditions.
Panel RatingsUnits without Supplemental Overloads
Table 38: Standard Panel Ratings for Units without Supplemental Overloads
Voltage HzWGZ-D Model Size
WGZ 030-040 WGZ 045-090 WGZ 100-200
208-230 60 5 5 10
380 60 5 5 5
400 50 5 5 5
460 60 5 5 5
575 60 5 5 5
Table 39: Optional High Short Circuit Current Ratings for Units without Supplemental Overloads
Voltage Hz Options, Single-Point Power Connection Only
208-230 60 100
380 60 65
400 50 65
460 60 65
575 60 Not Available
Units with Supplemental Overloads
Table 40: Standard Panel Ratings for Units with Supplemental Overloads
Voltage HzWGZ-D Model Size
WGZ 030-040 WGZ 045-090 WGZ 100-200
208-230 60 5 5 10
380 60 5 5 5
400 50 5 5 5
460 60 5 5 5
575 60 5 5 5
Table 41: Optional High Short Circuit Current Ratings for Units with Supplemental Overloads
Voltage Hz Options, Single-Point Power Connection Only
208-230 60 100
380 60 65
400 50 65
460 60 65
575 60 Not Available
eleCTrICal daTa
CAT 613-3 • MODEL WGZ CHILLERS 40 www.DaikinApplied.com
eleCTrICal daTa
Figure 17: Field Wiring Diagram (Packaged Units)
WGZ050D-200DSINGLE POINTPACKAGE UNIT333920201-2
TB3CONTROLLER
TB3-90
TB3-91
TB3-92
N
N
TB1-12
J12-NO3
TB1-12
J15-NO8
J18-NO13
120VAC
120VAC
120VAC
CDW PUMP RELAY(BY OTHERS)
120 VAC 1.0 AMP MAX
TOWER FAN #1 COIL(BY OTHERS)
120 VAC 1.0 AMP MAX
TOWER FAN #2 COIL(BY OTHERS)
120 VAC 1.0 AMP MAX
RSS1
IMS1
LUGGND
VDC0-10
(BY OTHERS)VFD
COOLING TOWER
(BY OTHERS)BYPASS
COOLING TOWER
TB2
80
79N
78
77
VDC0-10
N
11
14VAC120
N
-
GND
+DEMAND LIMIT
FOR4-20MA
-
GND
+
(BY OTHERS)CHW RESET
FOR4-20MA
(OPTIONAL)PUMP AUX. CONTACTS
NOR. OPEN
(BY OTHERS)---MANDATORY--
SWITCHCHWI FLOW
585FROM TERM. TB2 40 TO 53.REMOVE LEAD 585CONTROL IS USED,IF REMOTE STOP
(BY OTHERS)SWITCH
REMOTE STOP
MANUAL
ON
OFFAUTO
MANUAL
ON
OFFCLOCKTIME
AUTO
SUPPLY
NO COM
21BELL
ALARM BELL OPTION
RELAYALARM BELL
50
49
44
33
55
43
53
40
59
42
15
10
52
51
OPTIONBELL
ALARM
FIELD WIREDALARM
FACTORY SUPPLIED
RELAYALARM BELL
GND
VAC 120
OPTIONSUPPLIED
FIELD
N
(BY OTHERS)DISCONNECT
120 VAC 1.0 AMP MAX.(BY OTHERS)
CHWR1 PUMP RELAY
TB1-20
120 VAC
OPTIONTRANSFORMER
CIRCUITFUSED CONTROL
BLOCKTERMINAL
UNIT MAIN
CONTROL POWER120VAC
POWER3 PHASE
OTHERS)(BY
DISCONNECT
COMPRESSOR(S)TO
(BY OTHERS)SWITCH
ICE MODE
TB2
(BY OTHERS)
CHWR2 PUMP RELAY(BY OTHERS)
120 VAC 1.0 AMP MAX.
N
120VAC
910
904
TB3
908
909
VAC120
N
120 VAC 1.0 AMP MAX.(BY OTHERS)
CWPR2 PUMP RELAY
CFS FLOWSWITCH
---MANDATORY--(BY OTHERS)
NOR. OPEN
(OPTIONAL)41
54
ABR
NOTE: ALL FIELD
WIRING TO BE
INSTALLED AS NEC
CLASS 1
WIRING SYSTEM WITH
CONDUCTOR
RATED 600 VOLTS.
TB1CONTROLCIRCUIT
FUSE
2 FU6
eleCTrICal daTa
www.DaikinApplied.com 41 CAT 613-3 • MODEL WGZ CHILLERS
Figure 18: Field Wiring Diagram (Condenserless Units)
RSS1
IMS1
ABR
54
41
(OPTIONAL)
NOR. OPEN
(BY OTHERS)---MANDATORY--
SWITCHCFS FLOW
CWPR2 PUMP RELAY(BY OTHERS)
120 VAC 1.0 AMP MAX.
N
120VAC
909
908
TB3
904
910
VAC120
N
120 VAC 1.0 AMP MAX.(BY OTHERS)
CHWR2 PUMP RELAY
(BY OTHERS)
TB2
ICE MODESWITCH
(BY OTHERS)
TOCOMPRESSOR(S)
OTHERS)
3 PHASEPOWER
120VACCONTROL POWER
BLOCK
FUSED CONTROLCIRCUIT
TRANSFORMEROPTION
120 VAC
TB1
TB1-20
CHWR1 PUMP RELAY(BY OTHERS)
120 VAC 1.0 AMP MAX.
DISCONNECT(BY OTHERS)
N
FIELDSUPPLIED
OPTION
120VAC
GND
ALARM BELLRELAY
FACTORY SUPPLIED
ALARMFIELD WIRED
ALARMBELL
OPTION
51
52
10
15
2
42
59
40
53
43
55
33
44
49
50
ALARM BELLRELAY
ALARM BELL OPTION
BELL1 2
COMNO
NOTE: ALL FIELD
WIRING TO BE
INSTALLED AS NEC
CLASS 1
WIRING SYSTEM WITH
CONDUCTOR
RATED 600 VOLTS.
SUPPLY
AUTO
TIME
CLOCK OFF
ON
MANUAL
AUTO OFF
ON
MANUAL
REMOTE STOPSWITCH
(BY OTHERS)IF REMOTE STOPCONTROL IS USED,REMOVE LEAD 585FROM TERM. TB2 40 TO 53.
585
CHWI FLOWSWITCH
---MANDATORY--(BY OTHERS)
NOR. OPEN
PUMP AUX. CONTACTS(OPTIONAL)
4-20MAFOR
CHW RESET(BY OTHERS)
+
GND
-
4-20MAFOR
DEMAND LIMIT+
GND
-
CONTROLLER
NOTE:
CONDENSER FAN MOTORSCAN ALSO BE CONTROLLED BY PRESSURE SWITCHESON THE CONDENSER.
J22-NO17
J22-NO18
J15-NO8
J18-NO13
J22-NO16
120VAC
120VAC
120VAC
120VAC
120VAC
FAN MOTOR #11COIL
(BY OTHERS)120 VAC 1.0
AMP MAX.N
TB1-12
J12-NO3
120VAC
FAN MOTOR #21COIL
(BY OTHERS)120 VAC 1.0
AMP MAX.
FAN MOTOR #12COIL
(BY OTHERS)120 VAC 1.0AMP MAX.
FAN MOTOR #22COIL
(BY OTHERS)120 VAC 1.0
AMP MAX.
FAN MOTOR #13 & #14COIL
(BY OTHERS)120 VAC 1.0
AMP MAX.
FAN MOTOR #23 & #24COIL
(BY OTHERS)120 VAC 1.0
AMP MAX.
TB3-90
TB3-91
TB3-94
TB3-92
TB3-93
TB3-95
N
120VAC
14
11
LUG
EXB1-NO3
120VAC
FAN MOTOR #15 & #16COIL
(BY OTHERS)120 VAC 1.0
AMP MAX.TB3-96
TB3
CONTROLCIRCUIT
FUSEFU6
EXB1-NO4
120VAC
FAN MOTOR #25 & #26COIL
(BY OTHERS)120 VAC 1.0
AMP MAX.TB3-97
WGZ050D-200DSINGLE POINTWITH REMOTE CONDENSER333920201-3
CAT 613-3 • MODEL WGZ CHILLERS 42 www.DaikinApplied.com
eleCTrICal daTa
Table 42: Compressor Amp Draw (with and without optional external overloads)
Model Size
Voltage / Freq.
Rated Load Amps Per Compressor Locked Rotor AmpsUnit w/o Optional External Overloads Unit with Optional External Overloads Across-The-Line Starting
Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2#1 #3 #5 #2 #4 #6 #1 #3 #5 #2 #4 #6 #1 #3 #5 #2 #4 #6
030D
208V/60 29.5 29.5 -- 29.5 29.5 -- 22.4 22.4 -- 22.4 22.4 -- 195 195 -- 195 195 --
230V/60 29.5 29.5 -- 29.5 29.5 -- 20.0 20.0 -- 20.0 20.0 -- 195 195 -- 195 195 --
380V/60 16.7 16.7 -- 16.7 16.7 -- 13.6 13.6 -- 13.6 13.6 -- 123 123 -- 123 123 --
400V/50 14.7 14.7 -- 14.7 14.7 -- 12.0 12.0 -- 12.0 12.0 -- 95 95 -- 95 95 --
460V/60 14.7 14.7 -- 14.7 14.7 -- 12.0 12.0 -- 12.0 12.0 -- 95 95 -- 95 95 --
575V/60 12.2 12.2 -- 12.2 12.2 -- N/A N/A -- N/A N/A -- 80 80 -- 80 80 --
035D
208V/60 30.1 30.1 -- 30.1 30.1 -- 25.0 25.0 -- 25.0 25.0 -- 225 225 -- 225 225 --
230V/60 30.1 30.1 -- 30.1 30.1 -- 23.2 23.2 -- 23.2 23.2 -- 225 225 -- 225 225 --
380V/60 19.2 19.2 -- 19.2 19.2 -- 13.8 13.8 -- 13.8 13.8 -- 140 140 -- 140 140 --
400V/50 16.7 16.7 -- 16.7 16.7 -- 12.0 12.0 -- 12.0 12.0 -- 111 111 -- 111 111 --
460V/60 16.7 16.7 -- 16.7 16.7 -- 12.0 12.0 -- 12.0 12.0 -- 114 114 -- 114 114 --
575V/60 12.2 12.2 -- 12.2 12.2 -- N/A N/A -- N/A N/A -- 80 80 -- 80 80 --
040D
208V/60 33.3 33.3 -- 33.3 33.3 -- 28.6 28.6 -- 28.6 28.6 -- 239 239 -- 239 239 --
230V/60 33.3 33.3 -- 33.3 33.3 -- 25.6 25.6 -- 25.6 25.6 -- 239 239 -- 239 239 --
380V/60 23.7 23.7 -- 23.7 23.7 -- 16.9 16.9 -- 16.9 16.9 -- 145 145 -- 145 145 --
400V/50 17.9 17.9 -- 17.9 17.9 -- 12.8 12.8 -- 12.8 12.8 -- 118 118 -- 118 118 --
460V/60 17.9 17.9 -- 17.9 17.9 -- 12.8 12.8 -- 12.8 12.8 -- 125 125 -- 125 125 --
575V/60 12.8 12.8 -- 12.8 12.8 -- N/A N/A -- N/A N/A -- 80 80 -- 80 80 --
045D
208V/60 48.1 48.1 -- 48.1 48.1 -- 30.5 30.5 -- 30.5 30.5 -- 245 245 -- 245 245 --
230V/60 48.1 48.1 -- 48.1 48.1 -- 28.0 28.0 -- 28.0 28.0 -- 245 245 -- 245 245 --
380V/60 23.7 23.7 -- 23.7 23.7 -- 18.3 18.3 -- 18.3 18.3 -- 145 145 -- 145 145 --
400V/50 18.6 18.6 -- 18.6 18.6 -- 14.4 14.4 -- 14.4 14.4 -- 118 118 -- 118 118 --
460V/60 18.6 18.6 -- 18.6 18.6 -- 14.4 14.4 -- 14.4 14.4 -- 125 125 -- 125 125 --
575V/60 14.7 14.7 -- 14.7 14.7 -- 12.0 12.0 -- 12.0 12.0 -- 100 100 -- 100 100 --
050D
208V/60 51.3 51.3 -- 51.3 51.3 -- 36.0 36.0 -- 36.0 36.0 -- 300 300 -- 300 300 --
230V/60 51.3 51.3 -- 51.3 51.3 -- 32.8 32.8 -- 32.8 32.8 -- 300 300 -- 300 300 --
380V/60 26.9 26.9 -- 26.9 26.9 -- 19.6 19.6 -- 19.6 19.6 -- 139 139 -- 139 139 --
400V/50 23.1 23.1 -- 23.1 23.1 -- 16.8 16.8 -- 16.8 16.8 -- 140 140 -- 140 140 --
460V/60 23.1 23.1 -- 23.1 23.1 -- 16.8 16.8 -- 16.8 16.8 -- 150 150 -- 150 150 --
575V/60 19.9 19.9 -- 19.9 19.9 -- 13.6 13.6 -- 13.6 13.6 -- 109 109 -- 109 109 --
055D
208V/60 51.3 51.3 -- 55.8 55.8 -- 36.0 36.0 -- 44.0 44.0 -- 300 300 -- 340 340 --
230V/60 51.3 51.3 -- 55.8 55.8 -- 32.8 32.8 -- 40.0 40.0 -- 300 300 -- 340 340 --
380V/60 26.9 26.9 -- 34.0 34.0 -- 19.6 19.6 -- 25.3 25.3 -- 139 139 -- 196 196 --
400V/50 23.1 23.1 -- 26.9 26.9 -- 16.8 16.8 -- 20.0 20.0 -- 140 140 -- 173 173 --
460V/60 23.1 23.1 -- 26.9 26.9 -- 16.8 16.8 -- 20.0 20.0 -- 150 150 -- 173 173 --
575V/60 19.9 19.9 -- 23.7 23.7 -- 13.6 13.6 -- 16.0 16.0 -- 109 109 -- 132 132 --
060D
208V/60 55.8 55.8 -- 55.8 55.8 -- 44.0 44.0 -- 44.0 44.0 -- 340 340 -- 340 340 --
230V/60 55.8 55.8 -- 55.8 55.8 -- 40.0 40.0 -- 40.0 40.0 -- 340 340 -- 340 340 --
380V/60 34.0 34.0 -- 34.0 34.0 -- 25.3 25.3 -- 25.3 25.3 -- 196 196 -- 196 196 --
400V/50 26.9 26.9 -- 26.9 26.9 -- 20.0 20.0 -- 20.0 20.0 -- 173 173 -- 173 173 --
460V/60 26.9 26.9 -- 26.9 26.9 -- 20.0 20.0 -- 20.0 20.0 -- 173 173 -- 173 173 --
575V/60 23.7 23.7 -- 23.7 23.7 -- 16.0 16.0 -- 16.0 16.0 -- 132 132 -- 132 132 --
070D
208V/60 72.4 55.8 -- 72.4 55.8 -- 54.4 44.0 -- 54.4 44.0 -- 505 340 -- 505 340 --
230V/60 72.4 55.8 -- 72.4 55.8 -- 49.6 40.0 -- 49.6 40.0 -- 505 340 -- 505 340 --
380V/60 35.3 34.0 -- 35.3 34.0 -- 31.2 25.3 -- 31.2 25.3 -- 290 196 -- 290 196 --
400V/50 30.8 26.9 -- 30.8 26.9 -- 24.8 20.0 -- 24.8 20.0 -- 229 173 -- 229 173 --
460V/60 30.8 26.9 -- 30.8 26.9 -- 24.8 20.0 -- 24.8 20.0 -- 229 173 -- 229 173 --
575V/60 25.0 23.7 -- 25.0 23.7 -- 20.0 16.0 -- 20.0 16.0 -- 180 132 -- 180 132 --
eleCTrICal daTa
www.DaikinApplied.com 43 CAT 613-3 • MODEL WGZ CHILLERS
Table 43: Compressor Amp Draw (with and without optional external overloads)
Model Size
Voltage / Freq.
Rated Load Amps Per Compressor Locked Rotor AmpsUnit w/o Optional External Overloads Unit with Optional External Overloads Across-The-Line Starting
Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2#1 #3 #5 #2 #4 #6 #1 #3 #5 #2 #4 #6 #1 #3 #5 #2 #4 #6
080D
208V/60 72.4 72.4 -- 72.4 72.4 -- 54.4 54.4 -- 54.4 54.4 -- 538 538 -- 538 538 --
230V/60 72.4 72.4 -- 72.4 72.4 -- 49.6 49.6 -- 49.6 49.6 -- 538 538 -- 538 538 --
380V/60 35.3 35.3 -- 35.3 35.3 -- 31.2 31.2 -- 31.2 31.2 -- 290 290 -- 290 290 --
400V/50 30.8 30.8 -- 30.8 30.8 -- 24.8 24.8 -- 24.8 24.8 -- 229 229 -- 229 229 --
460V/60 30.8 30.8 -- 30.8 30.8 -- 24.8 24.8 -- 24.8 24.8 -- 229 229 -- 229 229 --
575V/60 25.0 25.0 -- 25.0 25.0 -- 20.0 20.0 -- 20.0 20.0 -- 180 180 -- 180 180 --
090D
208V/60 85.3 72.4 -- 85.3 72.4 -- 64.8 54.4 -- 64.8 54.4 -- 605 538 -- 605 538 --
230V/60 85.3 72.4 -- 85.3 72.4 -- 58.4 49.6 -- 58.4 49.6 -- 605 538 -- 605 538 --
380V/60 51.9 35.3 -- 51.9 35.3 -- 36.7 31.2 -- 36.7 31.2 -- 380 290 -- 380 290 --
400V/50 37.8 30.8 -- 37.8 30.8 -- 29.6 24.8 -- 29.6 24.8 -- 320 229 -- 320 229 --
460V/60 37.8 30.8 -- 37.8 30.8 -- 29.6 24.8 -- 29.6 24.8 -- 320 229 -- 320 229 --
575V/60 34.6 25.0 -- 34.6 25.0 -- 23.2 20.0 -- 23.2 20.0 -- 250 180 -- 250 180 --
100D
208V/60 85.3 85.3 -- 85.3 85.3 -- 64.8 64.8 -- 64.8 64.8 -- 605 605 -- 605 605 --
230V/60 85.3 85.3 -- 85.3 85.3 -- 58.4 58.4 -- 58.4 58.4 -- 605 605 -- 605 605 --
380V/60 51.9 51.9 -- 51.9 51.9 -- 36.7 36.7 -- 36.7 36.7 -- 380 380 -- 380 380 --
400V/50 37.8 37.8 -- 37.8 37.8 -- 29.6 29.6 -- 29.6 29.6 -- 320 320 -- 320 320 --
460V/60 37.8 37.8 -- 37.8 37.8 -- 29.6 29.6 -- 29.6 29.6 -- 320 320 -- 320 320 --
575V/60 34.6 34.6 -- 34.6 34.6 -- 23.2 23.2 -- 23.2 23.2 -- 250 250 -- 250 250 --
115D
208V/60 109.6 85.3 -- 109.6 85.3 -- 83.2 64.8 -- 83.2 64.8 -- 599 605 -- 599 605 --
230V/60 109.6 85.3 -- 109.6 85.3 -- 75.2 58.4 -- 75.2 58.4 -- 599 605 -- 599 605 --
380V/60 69.2 51.9 -- 69.2 51.9 -- 47.7 36.7 -- 47.7 36.7 -- 358 380 -- 358 380 --
400V/50 54.5 37.8 -- 54.5 37.8 -- 37.6 29.6 -- 37.6 29.6 -- 310 320 -- 310 320 --
460V/60 54.5 37.8 -- 54.5 37.8 -- 37.6 29.6 -- 37.6 29.6 -- 310 320 -- 310 320 --
575V/60 49.4 34.6 -- 49.4 34.6 -- 30.4 23.2 -- 30.4 23.2 -- 239 250 -- 239 250 --
130D
208V/60 109.6 109.6 -- 109.6 109.6 -- 83.2 83.2 -- 83.2 83.2 -- 599 599 -- 599 599 --
230V/60 109.6 109.6 -- 109.6 109.6 -- 75.2 75.2 -- 75.2 75.2 -- 599 599 -- 599 599 --
380V/60 69.2 69.2 -- 69.2 69.2 -- 47.7 47.7 -- 47.7 47.7 -- 358 358 -- 358 358 --
400V/50 54.5 54.5 -- 54.5 54.5 -- 37.6 37.6 -- 37.6 37.6 -- 310 310 -- 310 310 --
460V/60 54.5 54.5 -- 54.5 54.5 -- 37.6 37.6 -- 37.6 37.6 -- 310 310 -- 310 310 --
575V/60 49.4 49.4 -- 49.4 49.4 -- 30.4 30.4 -- 30.4 30.4 -- 239 239 -- 239 239 --
150D
208V/60 85.3 85.3 85.3 85.3 85.3 85.3 64.8 64.8 64.8 64.8 64.8 64.8 605 605 605 605 605 605
230V/60 85.3 85.3 85.3 85.3 85.3 85.3 58.4 58.4 58.4 58.4 58.4 58.4 605 605 605 605 605 605
380V/60 51.9 51.9 51.9 51.9 51.9 51.9 36.7 36.7 36.7 36.7 36.7 36.7 380 380 380 380 380 380
400V/50 37.8 37.8 37.8 37.8 37.8 37.8 29.6 29.6 29.6 29.6 29.6 29.6 320 320 320 320 320 320
460V/60 37.8 37.8 37.8 37.8 37.8 37.8 29.6 29.6 29.6 29.6 29.6 29.6 320 320 320 320 320 320
575V/60 34.6 34.6 34.6 34.6 34.6 34.6 23.2 23.2 23.2 23.2 23.2 23.2 250 250 250 250 250 250
170D
208V/60 85.3 85.3 85.3 109.6 109.6 109.6 64.8 64.8 64.8 83.2 83.2 83.2 605 605 605 599 599 599
230V/60 85.3 85.3 85.3 109.6 109.6 109.6 58.4 58.4 58.4 75.2 75.2 75.2 605 605 605 599 599 599
380V/60 51.9 51.9 51.9 69.2 69.2 69.2 36.7 36.7 36.7 47.7 47.7 47.7 380 380 380 358 358 358
400V/50 37.8 37.8 37.8 54.5 54.5 54.5 29.6 29.6 29.6 37.6 37.6 37.6 320 320 320 310 310 310
460V/60 37.8 37.8 37.8 54.5 54.5 54.5 29.6 29.6 29.6 37.6 37.6 37.6 320 320 320 310 310 310
575V/60 34.6 34.6 34.6 49.4 49.4 49.4 23.2 23.2 23.2 30.4 30.4 30.4 250 250 250 239 239 239
200D
208V/60 109.6 109.6 109.6 109.6 109.6 109.6 83.2 83.2 83.2 83.2 83.2 83.2 599 599 599 599 599 599
230V/60 109.6 109.6 109.6 109.6 109.6 109.6 75.2 75.2 75.2 75.2 75.2 75.2 599 599 599 599 599 599
380V/60 69.2 69.2 69.2 69.2 69.2 69.2 47.7 47.7 47.7 47.7 47.7 47.7 358 358 358 358 358 358
400V/50 54.5 54.5 54.5 54.5 54.5 54.5 37.6 37.6 37.6 37.6 37.6 37.6 310 310 310 310 310 310
460V/60 54.5 54.5 54.5 54.5 54.5 54.5 37.6 37.6 37.6 37.6 37.6 37.6 310 310 310 310 310 310
575V/60 49.4 49.4 49.4 49.4 49.4 49.4 30.4 30.4 30.4 30.4 30.4 30.4 239 239 239 239 239 239
CAT 613-3 • MODEL WGZ CHILLERS 44 www.DaikinApplied.com
eleCTrICal daTa
Table 44: Electrical Data - Single Point Without Optional External Overloads
Table 44 continued: Electrical Data - Single Point Without Optional External Overloads
Model Size Voltage
Single Point Field Data
Ratings Lug Range
MCA MFS Power Block Disconnect Switch
030D
208V 126 150 (1) 2/0 - #14 (1) 350 - #6
230V 126 150 (1) 2/0 - #14 (1) 350 - #6
380V 71 80 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 63 70 (1) 2/0 - #14 (1) 1/0 - #10
575V 52 60 (1) 2/0 - #14 (1) 1/0 - #10
035D
208V 128 150 (1) 2/0 - #14 (1) 350 - #6
230V 128 150 (1) 2/0 - #14 (1) 350 - #6
380V 82 100 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 71 80 (1) 2/0 - #14 (1) 1/0 - #10
575V 52 60 (1) 2/0 - #14 (1) 1/0 - #10
040D
208V 142 175 (1) 2/0 - #14 (1) 350 - #6
230V 142 175 (1) 2/0 - #14 (1) 350 - #6
380V 101 110 (1) 2/0 - #14 (1) 3/0 - #3
400-460V 77 90 (1) 2/0 - #14 (1) 1/0 - #10
575V 55 60 (1) 2/0 - #14 (1) 1/0 - #10
045D
208V 205 250 (1) 500 - #4 (1) 350 - #6
230V 205 250 (1) 500 - #4 (1) 350 - #6
380V 101 110 (1) 2/0 - #14 (1) 3/0 - #3
400-460V 80 90 (1) 2/0 - #14 (1) 1/0 - #10
575V 63 70 (1) 2/0 - #14 (1) 1/0 - #10
050D
208V 218 250 (1) 500 - #4 (1) 350 - #6
230V 218 250 (1) 500 - #4 (1) 350 - #6
380V 115 125 (1) 2/0 - #14 (1) 3/0 - #3
400-460V 99 110 (1) 2/0 - #14 (1) 3/0 - #3
575V 85 100 (1) 2/0 - #14 (1) 1/0 - #10
055D
208V 229 250 (1) 500 - #4 (1) 350 - #6
230V 229 250 (1) 500 - #4 (1) 350 - #6
380V 131 150 (1) 2/0 - #14 (1) 350 - #6
400-460V 107 125 (1) 2/0 - #14 (1) 3/0 - #3
575V 94 110 (1) 2/0 - #14 (1) 3/0 - #3
060D
208V 238 250 (1) 500 - #4 (2) 500 - 3/0
230V 238 250 (1) 500 - #4 (2) 500 - 3/0
380V 145 175 (1) 2/0 - #14 (1) 350 - #6
400-460V 115 125 (1) 2/0 - #14 (1) 3/0 - #3
575V 101 110 (1) 2/0 - #14 (1) 3/0 - #3
070D
208V 275 300 (1) 500 - #4 (2) 500 - 3/0
230V 275 300 (1) 500 - #4 (2) 500 - 3/0
380V 148 175 (1) 2/0 - #14 (1) 350 - #6
400-460V 124 150 (1) 2/0 - #14 (1) 350 - #6
575V 104 125 (1) 2/0 - #14 (1) 3/0 - #3
NOTE: MCA = Minimum Current Ampacity, MFS = Maximum Fuse Size.
Model Size Voltage
Single Point Field Data
Ratings Lug Range
MCA MFS Power Block Disconnect Switch
080D
208V 308 350 (1) 500 - #4 (2) 500 - 3/0
230V 308 350 (1) 500 - #4 (2) 500 - 3/0
380V 150 175 (1) 2/0 - #14 (1) 350 - #6
400-460V 131 150 (1) 2/0 - #14 (1) 350 - #6
575V 107 125 (1) 2/0 - #14 (1) 3/0 - #3
090D
208V 337 400 (1) 500 - #4 (2) 500 - 3/0
230V 337 400 (1) 500 - #4 (2) 500 - 3/0
380V 188 200 (1) 500 - #4 (1) 350 - #6
400-460V 147 175 (1) 2/0 - #14 (1) 350 - #6
575V 128 150 (1) 2/0 - #14 (1) 350 - #6
100D
208V 363 400 (1) 500 - #4 (2) 500 - 3/0
230V 363 400 (1) 500 - #4 (2) 500 - 3/0
380V 221 250 (1) 500 - #4 (1) 350 - #6
400-460V 161 175 (1) 2/0 - #14 (1) 350 - #6
575V 148 175 (1) 2/0 - #14 (1) 350 - #6
115D
208V 418 500 (2) 500 - #4 (2) 500 - 3/0
230V 418 500 (2) 500 - #4 (2) 500 - 3/0
380V 260 300 (1) 500 - #4 (2) 500 - 3/0
400-460V 199 250 (1) 500 - #4 (1) 350 - #6
575V 181 225 (1) 500 - #4 (1) 350 - #6
130D
208V 466 500 (2) 500 - #4 (2) 500 - 3/0
230V 466 500 (2) 500 - #4 (2) 500 - 3/0
380V 295 350 (1) 500 - #4 (2) 500 - 3/0
400-460V 232 250 (1) 500 - #4 (2) 500 - 3/0
575V 210 250 (1) 500 - #4 (1) 350 - #6
150D
208V 534 600 (2) 500 - #4 (2) 500 - 3/0
230V 534 600 (2) 500 - #4 (2) 500 - 3/0
380V 325 350 (1) 500 - #4 (2) 500 - 3/0
400-460V 237 250 (1) 500 - #4 (2) 500 - 3/0
575V 217 250 (1) 500 - #4 (1) 350 - #6
170D
208V 613 700 (2) 500 - #4 (3) 500 - 3/0
230V 613 700 (2) 500 - #4 (3) 500 - 3/0
380V 381 400 (2) 500 - #4 (2) 500 - 3/0
400-460V 291 300 (1) 500 - #4 (2) 500 - 3/0
575V 265 300 (1) 500 - #4 (2) 500 - 3/0
200D
208V 685 700 (2) 500 - #4 (4) 500 - 250
230V 685 700 (2) 500 - #4 (4) 500 - 250
380V 433 500 (2) 500 - #4 (2) 500 - 3/0
400-460V 341 350 (1) 500 - #4 (2) 500 - 3/0
575V 309 350 (1) 500 - #4 (2) 500 - 3/0
eleCTrICal daTa
www.DaikinApplied.com 45 CAT 613-3 • MODEL WGZ CHILLERS
Table 45: Electrical Data - Single Point With Optional External Overloads
Table 45 continued: Electrical Data - Single Point With Optional External Overloads
Model Size Voltage
Single Point Field Data
Ratings Lug Range
MCA MFS Power Block Disconnect Switch
030D
208V 96 110 (1) 2/0 - #14 (1) 3/0 - #3
230V 85 100 (1) 2/0 - #14 (1) 1/0 - #10
380V 58 70 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 51 60 (1) 2/0 - #14 (1) 1/0 - #10
575V N/A -- -- --
035D
208V 107 125 (1) 2/0 - #14 (1) 3/0 - #3
230V 99 110 (1) 2/0 - #14 (1) 3/0 - #3
380V 59 70 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 51 60 (1) 2/0 - #14 (1) 1/0 - #10
575V N/A -- -- --
040D
208V 122 150 (1) 2/0 - #14 (1) 350 - #6
230V 109 125 (1) 2/0 - #14 (1) 3/0 - #3
380V 72 80 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 55 60 (1) 2/0 - #14 (1) 1/0 - #10
575V N/A -- -- --
045D
208V 130 150 (1) 2/0 - #14 (1) 350 - #6
230V 119 125 (1) 2/0 - #14 (1) 350 - #6
380V 78 90 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 62 70 (1) 2/0 - #14 (1) 1/0 - #10
575V 51 60 (1) 2/0 - #14 (1) 1/0 - #10
050D
208V 153 175 (1) 2/0 - #14 (1) 350 - #6
230V 140 150 (1) 2/0 - #14 (1) 350 - #6
380V 84 100 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 72 80 (1) 2/0 - #14 (1) 1/0 - #10
575V 58 70 (1) 2/0 - #14 (1) 1/0 - #10
055D
208V 171 200 (1) 500 - #4 (1) 350 - #6
230V 156 175 (1) 2/0 - #14 (1) 350 - #6
380V 97 110 (1) 2/0 - #14 (1) 3/0 - #3
400-460V 79 90 (1) 2/0 - #14 (1) 1/0 - #10
575V 64 70 (1) 2/0 - #14 (1) 1/0 - #10
060D
208V 187 225 (1) 500 - #4 (1) 350 - #6
230V 170 200 (1) 500 - #4 (1) 350 - #6
380V 108 125 (1) 2/0 - #14 (1) 3/0 - #3
400-460V 85 100 (1) 2/0 - #14 (1) 1/0 - #10
575V 68 80 (1) 2/0 - #14 (1) 1/0 - #10
070D
208V 211 250 (1) 500 - #4 (1) 350 - #6
230V 192 225 (1) 500 - #4 (1) 350 - #6
380V 121 150 (1) 2/0 - #14 (1) 350 - #6
400-460V 96 110 (1) 2/0 - #14 (1) 3/0 - #3
575V 77 90 (1) 2/0 - #14 (1) 1/0 - #10
NOTE: MCA = Minimum Current Ampacity, MFS = Maximum Fuse Size.
Model Size Voltage
Single Point Field Data
Ratings Lug Range
MCA MFS Power Block Disconnect Switch
080D
208V 232 250 (1) 500 - #4 (2) 500 - 3/0
230V 211 250 (1) 500 - #4 (1) 350 - #6
380V 133 150 (1) 2/0 - #14 (1) 350 - #6
400-460V 106 125 (1) 2/0 - #14 (1) 3/0 - #3
575V 85 100 (1) 2/0 - #14 (1) 1/0 - #10
090D
208V 255 300 (1) 500 - #4 (2) 500 - 3/0
230V 231 250 (1) 500 - #4 (1) 350 - #6
380V 145 175 (1) 2/0 - #14 (1) 350 - #6
400-460V 117 125 (1) 2/0 - #14 (1) 350 - #6
575V 93 110 (1) 2/0 - #14 (1) 1/0 - #10
100D
208V 276 300 (1) 500 - #4 (2) 500 - 3/0
230V 249 300 (1) 500 - #4 (2) 500 - 3/0
380V 156 175 (1) 2/0 - #14 (1) 350 - #6
400-460V 126 150 (1) 2/0 - #14 (1) 350 - #6
575V 99 110 (1) 2/0 - #14 (1) 3/0 - #3
115D
208V 317 400 (1) 500 - #4 (2) 500 - 3/0
230V 286 350 (1) 500 - #4 (2) 500 - 3/0
380V 181 225 (1) 500 - #4 (1) 350 - #6
400-460V 144 175 (1) 2/0 - #14 (1) 350 - #6
575V 115 125 (1) 2/0 - #14 (1) 3/0 - #3
130D
208V 354 400 (1) 500 - #4 (2) 500 - 3/0
230V 320 350 (1) 500 - #4 (2) 500 - 3/0
380V 203 250 (1) 500 - #4 (1) 350 - #6
400-460V 160 175 (1) 2/0 - #14 (1) 350 - #6
575V 130 150 (1) 2/0 - #14 (1) 350 - #6
150D
208V 405 450 (2) 500 - #4 (2) 500 - 3/0
230V 365 400 (1) 500 - #4 (2) 500 - 3/0
380V 230 250 (1) 500 - #4 (2) 500 - 3/0
400-460V 185 200 (1) 500 - #4 (1) 350 - #6
575V 145 150 (1) 2/0 - #14 (1) 350 - #6
170D
208V 465 500 (2) 500 - #4 (2) 500 - 3/0
230V 420 450 (2) 500 - #4 (2) 500 - 3/0
380V 266 300 (1) 500 - #4 (2) 500 - 3/0
400-460V 211 225 (1) 500 - #4 (1) 350 - #6
575V 169 175 (1) 500 - #4 (1) 350 - #6
200D
208V 520 600 (2) 500 - #4 (2) 500 - 3/0
230V 470 500 (2) 500 - #4 (2) 500 - 3/0
380V 299 300 (1) 500 - #4 (2) 500 - 3/0
400-460V 235 250 (1) 500 - #4 (2) 500 - 3/0
575V 190 200 (1) 500 - #4 (1) 350 - #6
CAT 613-3 • MODEL WGZ CHILLERS 46 www.DaikinApplied.com
eleCTrICal daTa
Table 46: Electrical Data - Multiple Point Without Optional External Overloads
Model Size Voltage
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Ratings Lug Range Ratings Lug Range
MCA MFS Power Block Disconnect Switch MCA MFS Power Block Disconnect Switch
030D
208V 66 90 (1) 2/0 - #14 (1) 1/0 - #10 66 90 (1) 2/0 - #14 (1) 1/0 - #10
230V 66 90 (1) 2/0 - #14 (1) 1/0 - #10 66 90 (1) 2/0 - #14 (1) 1/0 - #10
380V 38 50 (1) 2/0 - #14 (1) 1/0 - #10 38 50 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 33 45 (1) 2/0 - #14 (1) 1/0 - #10 33 45 (1) 2/0 - #14 (1) 1/0 - #10
575V 27 35 (1) 2/0 - #14 (1) 1/0 - #10 27 35 (1) 2/0 - #14 (1) 1/0 - #10
035D
208V 68 90 (1) 2/0 - #14 (1) 1/0 - #10 68 90 (1) 2/0 - #14 (1) 1/0 - #10
230V 68 90 (1) 2/0 - #14 (1) 1/0 - #10 68 90 (1) 2/0 - #14 (1) 1/0 - #10
380V 43 60 (1) 2/0 - #14 (1) 1/0 - #10 43 60 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 38 50 (1) 2/0 - #14 (1) 1/0 - #10 38 50 (1) 2/0 - #14 (1) 1/0 - #10
575V 27 35 (1) 2/0 - #14 (1) 1/0 - #10 27 35 (1) 2/0 - #14 (1) 1/0 - #10
040D
208V 75 100 (1) 2/0 - #14 (1) 1/0 - #10 75 100 (1) 2/0 - #14 (1) 1/0 - #10
230V 75 100 (1) 2/0 - #14 (1) 1/0 - #10 75 100 (1) 2/0 - #14 (1) 1/0 - #10
380V 53 70 (1) 2/0 - #14 (1) 1/0 - #10 53 70 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 40 50 (1) 2/0 - #14 (1) 1/0 - #10 40 50 (1) 2/0 - #14 (1) 1/0 - #10
575V 29 40 (1) 2/0 - #14 (1) 1/0 - #10 29 40 (1) 2/0 - #14 (1) 1/0 - #10
045D
208V 108 150 (1) 2/0 - #14 (1) 3/0 - #3 108 150 (1) 2/0 - #14 (1) 3/0 - #3
230V 108 150 (1) 2/0 - #14 (1) 3/0 - #3 108 150 (1) 2/0 - #14 (1) 3/0 - #3
380V 53 70 (1) 2/0 - #14 (1) 1/0 - #10 53 70 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 42 60 (1) 2/0 - #14 (1) 1/0 - #10 42 60 (1) 2/0 - #14 (1) 1/0 - #10
575V 33 45 (1) 2/0 - #14 (1) 1/0 - #10 33 45 (1) 2/0 - #14 (1) 1/0 - #10
050D
208V 115 150 (1) 2/0 - #14 (1) 3/0 - #3 115 150 (1) 2/0 - #14 (1) 3/0 - #3
230V 115 150 (1) 2/0 - #14 (1) 3/0 - #3 115 150 (1) 2/0 - #14 (1) 3/0 - #3
380V 61 80 (1) 2/0 - #14 (1) 1/0 - #10 61 80 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 52 70 (1) 2/0 - #14 (1) 1/0 - #10 52 70 (1) 2/0 - #14 (1) 1/0 - #10
575V 45 60 (1) 2/0 - #14 (1) 1/0 - #10 45 60 (1) 2/0 - #14 (1) 1/0 - #10
055D
208V 115 150 (1) 2/0 - #14 (1) 3/0 - #3 126 175 (1) 2/0 - #14 (1) 350 - #6
230V 115 150 (1) 2/0 - #14 (1) 3/0 - #3 126 175 (1) 2/0 - #14 (1) 350 - #6
380V 61 80 (1) 2/0 - #14 (1) 1/0 - #10 77 110 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 52 70 (1) 2/0 - #14 (1) 1/0 - #10 61 80 (1) 2/0 - #14 (1) 1/0 - #10
575V 45 60 (1) 2/0 - #14 (1) 1/0 - #10 53 70 (1) 2/0 - #14 (1) 1/0 - #10
060D
208V 126 175 (1) 2/0 - #14 (1) 350 - #6 126 175 (1) 2/0 - #14 (1) 350 - #6
230V 126 175 (1) 2/0 - #14 (1) 350 - #6 126 175 (1) 2/0 - #14 (1) 350 - #6
380V 77 110 (1) 2/0 - #14 (1) 1/0 - #10 77 110 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 61 80 (1) 2/0 - #14 (1) 1/0 - #10 61 80 (1) 2/0 - #14 (1) 1/0 - #10
575V 53 70 (1) 2/0 - #14 (1) 1/0 - #10 53 70 (1) 2/0 - #14 (1) 1/0 - #10
070D
208V 146 200 (1) 2/0 - #14 (1) 350 - #6 146 200 (1) 2/0 - #14 (1) 350 - #6
230V 146 200 (1) 2/0 - #14 (1) 350 - #6 146 200 (1) 2/0 - #14 (1) 350 - #6
380V 78 110 (1) 2/0 - #14 (1) 1/0 - #10 78 110 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 65 90 (1) 2/0 - #14 (1) 1/0 - #10 65 90 (1) 2/0 - #14 (1) 1/0 - #10
575V 55 80 (1) 2/0 - #14 (1) 1/0 - #10 55 80 (1) 2/0 - #14 (1) 1/0 - #10
NOTE: MCA = Minimum Current Ampacity, MFS = Maximum Fuse Size.
eleCTrICal daTa
www.DaikinApplied.com 47 CAT 613-3 • MODEL WGZ CHILLERS
Table 46 continued: Electrical Data - Multiple Point Without Optional External Overloads
Model Size Voltage
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Ratings Lug Range Ratings Lug Range
MCA MFS Power Block Disconnect Switch MCA MFS Power Block Disconnect Switch
080D
208V 163 225 (1) 2/0 - #14 (1) 350 - #6 163 225 (1) 2/0 - #14 (1) 350 - #6
230V 163 225 (1) 2/0 - #14 (1) 350 - #6 163 225 (1) 2/0 - #14 (1) 350 - #6
380V 79 110 (1) 2/0 - #14 (1) 1/0 - #10 79 110 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 69 100 (1) 2/0 - #14 (1) 1/0 - #10 69 100 (1) 2/0 - #14 (1) 1/0 - #10
575V 56 70 (1) 2/0 - #14 (1) 1/0 - #10 56 70 (1) 2/0 - #14 (1) 1/0 - #10
090D
208V 179 225 (1) 500 - #4 (1) 350 - #6 179 250 (1) 500 - #4 (1) 350 - #6
230V 179 225 (1) 500 - #4 (1) 350 - #6 179 250 (1) 500 - #4 (1) 350 - #6
380V 100 125 (1) 2/0 - #14 (1) 3/0 - #3 100 125 (1) 2/0 - #14 (1) 3/0 - #3
400-460V 78 100 (1) 2/0 - #14 (1) 1/0 - #10 78 100 (1) 2/0 - #14 (1) 1/0 - #10
575V 68 90 (1) 2/0 - #14 (1) 1/0 - #10 68 90 (1) 2/0 - #14 (1) 1/0 - #10
100D
208V 192 250 (1) 500 - #4 (1) 350 - #6 192 250 (1) 500 - #4 (1) 350 - #6
230V 192 250 (1) 500 - #4 (1) 350 - #6 192 250 (1) 500 - #4 (1) 350 - #6
380V 117 150 (1) 2/0 - #14 (1) 3/0 - #3 117 150 (1) 2/0 - #14 (1) 3/0 - #3
400-460V 85 110 (1) 2/0 - #14 (1) 1/0 - #10 85 110 (1) 2/0 - #14 (1) 1/0 - #10
575V 78 110 (1) 2/0 - #14 (1) 1/0 - #10 78 110 (1) 2/0 - #14 (1) 1/0 - #10
115D
208V 222 300 (1) 500 - #4 (1) 350 - #6 222 300 (1) 500 - #4 (1) 350 - #6
230V 222 300 (1) 500 - #4 (1) 350 - #6 222 300 (1) 500 - #4 (1) 350 - #6
380V 138 200 (1) 2/0 - #14 (1) 350 - #6 138 200 (1) 2/0 - #14 (1) 350 - #6
400-460V 106 150 (1) 2/0 - #14 (1) 3/0 - #3 106 150 (1) 2/0 - #14 (1) 3/0 - #3
575V 96 125 (1) 2/0 - #14 (1) 1/0 - #10 96 125 (1) 2/0 - #14 (1) 1/0 - #10
130D
208V 247 350 (1) 500 - #4 (2) 500 - 3/0 247 350 (1) 500 - #4 (2) 500 - 3/0
230V 247 350 (1) 500 - #4 (2) 500 - 3/0 247 350 (1) 500 - #4 (2) 500 - 3/0
380V 156 225 (1) 2/0 - #14 (1) 350 - #6 156 225 (1) 2/0 - #14 (1) 350 - #6
400-460V 123 175 (1) 2/0 - #14 (1) 350 - #6 123 175 (1) 2/0 - #14 (1) 350 - #6
575V 111 150 (1) 2/0 - #14 (1) 3/0 - #3 111 150 (1) 2/0 - #14 (1) 3/0 - #3
150D
208V 277 350 (1) 500 - #4 (2) 500 - 3/0 277 350 (1) 500 - #4 (2) 500 - 3/0
230V 277 350 (1) 500 - #4 (2) 500 - 3/0 277 350 (1) 500 - #4 (2) 500 - 3/0
380V 169 200 (1) 500 - #4 (1) 350 - #6 169 200 (1) 500 - #4 (1) 350 - #6
400-460V 123 150 (1) 2/0 - #14 (1) 350 - #6 123 150 (1) 2/0 - #14 (1) 350 - #6
575V 112 125 (1) 2/0 - #14 (1) 3/0 - #3 112 125 (1) 2/0 - #14 (1) 3/0 - #3
170D
208V 277 350 (1) 500 - #4 (2) 500 - 3/0 356 450 (1) 500 - #4 (2) 500 - 3/0
230V 277 350 (1) 500 - #4 (2) 500 - 3/0 356 450 (1) 500 - #4 (2) 500 - 3/0
380V 169 200 (1) 500 - #4 (1) 350 - #6 225 250 (1) 500 - #4 (1) 350 - #6
400-460V 123 150 (1) 2/0 - #14 (1) 350 - #6 177 225 (1) 500 - #4 (1) 350 - #6
575V 112 125 (1) 2/0 - #14 (1) 3/0 - #3 161 200 (1) 2/0 - #14 (1) 350 - #6
200D
208V 356 450 (1) 500 - #4 (2) 500 - 3/0 356 450 (1) 500 - #4 (2) 500 - 3/0
230V 356 450 (1) 500 - #4 (2) 500 - 3/0 356 450 (1) 500 - #4 (2) 500 - 3/0
380V 225 250 (1) 500 - #4 (1) 350 - #6 225 250 (1) 500 - #4 (1) 350 - #6
400-460V 177 225 (1) 500 - #4 (1) 350 - #6 177 225 (1) 500 - #4 (1) 350 - #6
575V 161 200 (1) 2/0 - #14 (1) 350 - #6 161 200 (1) 2/0 - #14 (1) 350 - #6
NOTE: MCA = Minimum Current Ampacity, MFS = Maximum Fuse Size.
CAT 613-3 • MODEL WGZ CHILLERS 48 www.DaikinApplied.com
eleCTrICal daTa
Table 47: Electrical Data - Multiple Point With Optional External Overloads
Model Size Voltage
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Ratings Lug Range Ratings Lug Range
MCA MFS Power Block Disconnect Switch MCA MFS Power Block Disconnect Switch
030D
208V 50 70 (1) 2/0 - #14 (1) 1/0 - #10 50 70 (1) 2/0 - #14 (1) 1/0 - #10
230V 45 60 (1) 2/0 - #14 (1) 1/0 - #10 45 60 (1) 2/0 - #14 (1) 1/0 - #10
380V 31 40 (1) 2/0 - #14 (1) 1/0 - #10 31 40 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 27 35 (1) 2/0 - #14 (1) 1/0 - #10 27 35 (1) 2/0 - #14 (1) 1/0 - #10
575V N/A -- -- -- N/A -- -- --
035D
208V 56 80 (1) 2/0 - #14 (1) 1/0 - #10 56 80 (1) 2/0 - #14 (1) 1/0 - #10
230V 52 70 (1) 2/0 - #14 (1) 1/0 - #10 52 70 (1) 2/0 - #14 (1) 1/0 - #10
380V 31 45 (1) 2/0 - #14 (1) 1/0 - #10 31 45 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 27 35 (1) 2/0 - #14 (1) 1/0 - #10 27 35 (1) 2/0 - #14 (1) 1/0 - #10
575V N/A -- -- -- N/A -- -- --
040D
208V 64 90 (1) 2/0 - #14 (1) 1/0 - #10 64 90 (1) 2/0 - #14 (1) 1/0 - #10
230V 58 80 (1) 2/0 - #14 (1) 1/0 - #10 58 80 (1) 2/0 - #14 (1) 1/0 - #10
380V 38 50 (1) 2/0 - #14 (1) 1/0 - #10 38 50 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 29 40 (1) 2/0 - #14 (1) 1/0 - #10 29 40 (1) 2/0 - #14 (1) 1/0 - #10
575V N/A -- -- -- N/A -- -- --
045D
208V 69 90 (1) 2/0 - #14 (1) 1/0 - #10 69 90 (1) 2/0 - #14 (1) 1/0 - #10
230V 63 90 (1) 2/0 - #14 (1) 1/0 - #10 63 90 (1) 2/0 - #14 (1) 1/0 - #10
380V 41 50 (1) 2/0 - #14 (1) 1/0 - #10 41 50 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 32 45 (1) 2/0 - #14 (1) 1/0 - #10 32 45 (1) 2/0 - #14 (1) 1/0 - #10
575V 27 35 (1) 2/0 - #14 (1) 1/0 - #10 27 35 (1) 2/0 - #14 (1) 1/0 - #10
050D
208V 81 110 (1) 2/0 - #14 (1) 1/0 - #10 81 110 (1) 2/0 - #14 (1) 1/0 - #10
230V 74 100 (1) 2/0 - #14 (1) 1/0 - #10 74 100 (1) 2/0 - #14 (1) 1/0 - #10
380V 44 60 (1) 2/0 - #14 (1) 1/0 - #10 44 60 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 38 50 (1) 2/0 - #14 (1) 1/0 - #10 38 50 (1) 2/0 - #14 (1) 1/0 - #10
575V 31 40 (1) 2/0 - #14 (1) 1/0 - #10 31 40 (1) 2/0 - #14 (1) 1/0 - #10
055D
208V 81 110 (1) 2/0 - #14 (1) 1/0 - #10 99 125 (1) 2/0 - #14 (1) 3/0 - #3
230V 74 100 (1) 2/0 - #14 (1) 1/0 - #10 90 125 (1) 2/0 - #14 (1) 1/0 - #10
380V 44 60 (1) 2/0 - #14 (1) 1/0 - #10 57 80 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 38 50 (1) 2/0 - #14 (1) 1/0 - #10 45 60 (1) 2/0 - #14 (1) 1/0 - #10
575V 31 40 (1) 2/0 - #14 (1) 1/0 - #10 36 50 (1) 2/0 - #14 (1) 1/0 - #10
060D
208V 99 125 (1) 2/0 - #14 (1) 3/0 - #3 99 125 (1) 2/0 - #14 (1) 3/0 - #3
230V 90 125 (1) 2/0 - #14 (1) 1/0 - #10 90 125 (1) 2/0 - #14 (1) 1/0 - #10
380V 57 80 (1) 2/0 - #14 (1) 1/0 - #10 57 80 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 45 60 (1) 2/0 - #14 (1) 1/0 - #10 45 60 (1) 2/0 - #14 (1) 1/0 - #10
575V 36 50 (1) 2/0 - #14 (1) 1/0 - #10 36 50 (1) 2/0 - #14 (1) 1/0 - #10
070D
208V 112 150 (1) 2/0 - #14 (1) 3/0 - #3 112 150 (1) 2/0 - #14 (1) 3/0 - #3
230V 102 150 (1) 2/0 - #14 (1) 3/0 - #3 102 150 (1) 2/0 - #14 (1) 3/0 - #3
380V 64 90 (1) 2/0 - #14 (1) 1/0 - #10 64 90 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 51 70 (1) 2/0 - #14 (1) 1/0 - #10 51 70 (1) 2/0 - #14 (1) 1/0 - #10
575V 41 60 (1) 2/0 - #14 (1) 1/0 - #10 41 60 (1) 2/0 - #14 (1) 1/0 - #10
NOTE: MCA = Minimum Current Ampacity, MFS = Maximum Fuse Size.
eleCTrICal daTa
www.DaikinApplied.com 49 CAT 613-3 • MODEL WGZ CHILLERS
Table 47 continued: Electrical Data - Multiple Point With Optional External Overloads
Model Size Voltage
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Ratings Lug Range Ratings Lug Range
MCA MFS Power Block Disconnect Switch MCA MFS Power Block Disconnect Switch
080D
208V 122 175 (1) 2/0 - #14 (1) 350 - #6 122 175 (1) 2/0 - #14 (1) 350 - #6
230V 112 150 (1) 2/0 - #14 (1) 3/0 - #3 112 150 (1) 2/0 - #14 (1) 3/0 - #3
380V 70 100 (1) 2/0 - #14 (1) 1/0 - #10 70 100 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 56 80 (1) 2/0 - #14 (1) 1/0 - #10 56 80 (1) 2/0 - #14 (1) 1/0 - #10
575V 45 60 (1) 2/0 - #14 (1) 1/0 - #10 45 60 (1) 2/0 - #14 (1) 1/0 - #10
090D
208V 135 200 (1) 2/0 - #14 (1) 350 - #6 135 200 (1) 2/0 - #14 (1) 350 - #6
230V 123 175 (1) 2/0 - #14 (1) 3/0 - #3 123 175 (1) 2/0 - #14 (1) 3/0 - #3
380V 77 110 (1) 2/0 - #14 (1) 1/0 - #10 77 110 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 62 90 (1) 2/0 - #14 (1) 1/0 - #10 62 90 (1) 2/0 - #14 (1) 1/0 - #10
575V 49 70 (1) 2/0 - #14 (1) 1/0 - #10 49 70 (1) 2/0 - #14 (1) 1/0 - #10
100D
208V 146 200 (1) 2/0 - #14 (1) 350 - #6 146 200 (1) 2/0 - #14 (1) 350 - #6
230V 131 175 (1) 2/0 - #14 (1) 350 - #6 131 175 (1) 2/0 - #14 (1) 350 - #6
380V 83 110 (1) 2/0 - #14 (1) 1/0 - #10 83 110 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 67 90 (1) 2/0 - #14 (1) 1/0 - #10 67 90 (1) 2/0 - #14 (1) 1/0 - #10
575V 52 70 (1) 2/0 - #14 (1) 1/0 - #10 52 70 (1) 2/0 - #14 (1) 1/0 - #10
115D
208V 169 250 (1) 2/0 - #14 (1) 350 - #6 169 250 (1) 2/0 - #14 (1) 350 - #6
230V 152 225 (1) 2/0 - #14 (1) 350 - #6 152 225 (1) 2/0 - #14 (1) 350 - #6
380V 96 125 (1) 2/0 - #14 (1) 1/0 - #10 96 125 (1) 2/0 - #14 (1) 1/0 - #10
400-460V 77 110 (1) 2/0 - #14 (1) 1/0 - #10 77 110 (1) 2/0 - #14 (1) 1/0 - #10
575V 61 90 (1) 2/0 - #14 (1) 1/0 - #10 61 90 (1) 2/0 - #14 (1) 1/0 - #10
130D
208V 187 250 (1) 500 - #4 (1) 350 - #6 187 250 (1) 500 - #4 (1) 350 - #6
230V 169 225 (1) 500 - #4 (1) 350 - #6 169 225 (1) 500 - #4 (1) 350 - #6
380V 107 150 (1) 2/0 - #14 (1) 3/0 - #3 107 150 (1) 2/0 - #14 (1) 3/0 - #3
400-460V 85 110 (1) 2/0 - #14 (1) 1/0 - #10 85 110 (1) 2/0 - #14 (1) 1/0 - #10
575V 68 90 (1) 2/0 - #14 (1) 1/0 - #10 68 90 (1) 2/0 - #14 (1) 1/0 - #10
150D
208V 211 250 (1) 500 - #4 (1) 350 - #6 211 250 (1) 500 - #4 (1) 350 - #6
230V 190 225 (1) 500 - #4 (1) 350 - #6 190 225 (1) 500 - #4 (1) 350 - #6
380V 119 150 (1) 2/0 - #14 (1) 350 - #6 119 150 (1) 2/0 - #14 (1) 350 - #6
400-460V 96 125 (1) 2/0 - #14 (1) 3/0 - #3 96 125 (1) 2/0 - #14 (1) 3/0 - #3
575V 75 90 (1) 2/0 - #14 (1) 1/0 - #10 75 90 (1) 2/0 - #14 (1) 1/0 - #10
170D
208V 211 250 (1) 500 - #4 (1) 350 - #6 270 350 (1) 500 - #4 (2) 500 - 3/0
230V 190 225 (1) 500 - #4 (1) 350 - #6 244 300 (1) 500 - #4 (2) 500 - 3/0
380V 119 150 (1) 2/0 - #14 (1) 350 - #6 155 200 (1) 2/0 - #14 (1) 350 - #6
400-460V 96 125 (1) 2/0 - #14 (1) 3/0 - #3 122 150 (1) 2/0 - #14 (1) 350 - #6
575V 75 90 (1) 2/0 - #14 (1) 1/0 - #10 99 125 (1) 2/0 - #14 (1) 3/0 - #3
200D
208V 270 350 (1) 500 - #4 (2) 500 - 3/0 270 350 (1) 500 - #4 (2) 500 - 3/0
230V 244 300 (1) 500 - #4 (2) 500 - 3/0 244 300 (1) 500 - #4 (2) 500 - 3/0
380V 155 200 (1) 2/0 - #14 (1) 350 - #6 155 200 (1) 2/0 - #14 (1) 350 - #6
400-460V 122 150 (1) 2/0 - #14 (1) 350 - #6 122 150 (1) 2/0 - #14 (1) 350 - #6
575V 99 125 (1) 2/0 - #14 (1) 3/0 - #3 99 125 (1) 2/0 - #14 (1) 3/0 - #3
NOTE: MCA = Minimum Current Ampacity, MFS = Maximum Fuse Size.
CAT 613-3 • MODEL WGZ CHILLERS 50 www.DaikinApplied.com
opTIons and aCCessorIes
Unit OptionsHot Gas BypassFactory mounted hot gas bypass permits unit operation down to 10% of full load capacity and includes a hot gas bypass valve, solenoid valve and manual shutoff valve. Hot gas bypass is provided on both refrigerant circuits.
Vibration IsolatorsSpring or rubber-in-shear vibration isolators are available as a kit for field installation to reduce vibration transmission through the unit base.
Acoustical Compressor WrapsFactory-installed acoustical compressor wraps are available for all units when ultra low sound levels are required. There is one wrap for each compressor and they are easily removed for servicing.
Condenser ConnectionsLeft-hand condenser water connections (as viewed looking at the control panel) are optional.
Double InsulationThe evaporator is available with an additional layer of 3/4-inch insulation. This option is included as standard for ELWT below 34° (1.1°F) and optional for other special applications such as a high ambient humidity location.
Skid (WGZ-DW Water Cooled Only)The packaged unit is equipped with a disposable wooden skid to assist in some rigging situations. The skid option is strongly recommended for ease of handling and to help prevent damage if a crane is not available for rigging at site. Not required on WGZD-A condenserless units.
PaintAs standard, the compressors have the manufacturer’s black paint and insulation and piping is unpainted. As an option, the entire unit can be painted with Daikin Applied beige paint.
Electrical Options Power ConnectionsThe WGZ chillers are supplied as standard for milti-point (2) connection to unit power blocks and compressor contractors Compressor circuit breakers are not required on multi-point units. Available options are:
• Multi-point power connection to disconnect switches in lieu of power blocks, no compressor circuit breakers
• Single-point power connection to power block with compressor circuit breakers, contactors and internal compressor protection
• Single-point power connection to disconnect switch with compressor circuit breakers, contactors and internal
compressor protection• High short circuit current rating with single-point
disconnect switch and compressor circuit breakers and contactors. Ratings on page 39. Not available on 575V units or models 170 and 200 at 208/230V without optional overloads.
Phase and Under/Over Voltage ProtectionFactory-installed option- phase loss with under/over voltage protection with LED indication of fault type.
Ground Fault ProtectionProtects equipment from damage from low level line-to-ground fault currents, less than those required for conductor protection and quickly shuts off power.
Supplementary OverloadsThe supplemental overloads option is used to reduce the required electrical service size and wire sizing to the water-cooled version of WGZ chillers. The overload option is only available for models with water cooled condensers (DW).
Controls/Instrumentation OptionsWater Flow SwitchFactory-installed evaporator and condenser water flow switches in the water piping to safeguard the unit from flow interruptions. Installation of water flow switches is mandatory and they must be installed in the field if the factory option is not ordered.
Remote Interface PanelA remote interface panel, field wired to the unit, providing all the data viewable on the unit’s controller, including alarm clearing and setpoint change capability.
BAS InterfaceThe Daikin Open Choice’s feature consists of a factory-installed communication module for LonMark® , Modbus®, or BACnet® MSTP or BACnet® Ethernet or IP.
Dual Pump ControlStandard control for remote evaporator and condensers pumps is a single output for each. For two pumps in a primary/secondary arrangement, a field-supplied alternating device must be installed. Optionally, the unit can be equipped with programmable, dual outputs for the evaporator pumps and condenser pumps.
opTIons and aCCessorIes
engIneerIng guIde speCIfICaTIons
www.DaikinApplied.com 51 CAT 613-3 • MODEL WGZ CHILLERS
Scroll Compressor, Packaged Water-Cooled Chiller (WGZ030DW - WGZ200DW)
PART 1 - GENERAL
1 .01 SUMMARYA. Section includes design, performance criteria,
refrigerants, controls, and installation requirements for water-cooled scroll compressor packaged chillers.
1 .02 REFERENCESA. Comply with applicable Standards/Codes of AHRI
550/590-98, ANSI/ASHRAE 15, ASME Section VIII, NEC, and OSHA as adopted by the State.
1.03 SUBMITTALSA. Submit shop drawings and product data in accordance
with contract specifications.
B. Submittals shall include the following:
1. Dimensioned plan and elevation view drawings, required clearances, and location of all field connections.
2. Summary of all auxiliary utility requirements such as: electricity, water, etc. Summary shall indicate quality and quantity of each required utility.
3. Single-line schematic drawing of the power field hookup requirements, indicating all items that are furnished.
4. Schematic diagram of control system indicating points for field connection. Diagram shall fully delineate field and factory wiring.
5. Installation manual.
1.04 QUALITY ASSURANCEA. Qualifications: Equipment manufacturer must specialize
in the manufacture of the products specified and have five years experience with similar equipment and the refrigerant offered.
B. Regulatory Requirements: Comply with the codes and standards specified.
C. Chiller manufacturer’s facility must be ISO registered.
1.05 DELIVERY AND HANDLINGA. Chillers shall be delivered to the job site completely
assembled and charged with refrigerant and oil by the manufacturer.
B. Comply with the manufacturer’s instructions for rigging and handling equipment.
1 .06 WARRANTYThe chiller manufacturer’s warranty shall cover parts and labor costs for the repair or replacement of defects in material
or workmanship [OPTION] including refrigerant for the entire unit, for a period of one year from equipment startup or 18 months from shipment, whichever occurs first, [OPTION] and also include an additional extended warranty for (one OR two OR three OR four) years on (the entire unit) OR (on entire unit including refrigerant coverage) OR (compressor and drive train only). Warranty support shall be provided by company direct or factory authorized service permanently located near the job site.
PART 2 - PRODUCTS
2.01 ACCEPTABLE MANUFACTURERSA. Daikin Applied
B. (Approved Equal)
2 .02 UNIT DESCRIPTIONA. Provide and install as shown on the plans factory
assembled, factory charged, water-cooled scroll compressor packaged chillers in the quantity specified. Each chiller shall consist of multiple hermetic scroll compressors, dual-circuit brazed plate or shell-and-tube evaporator, shell-and-tube water-cooled condensers, control system and all components necessary for controlled unit operation. Refrigerant shall be R-410A.
B. Each chiller shall be factory run-tested with water to verify full load operation. Operating controls and refrigerant charge shall be verified for proper operation and optimum performance. Any deviation shall be remedied prior to shipment and the unit retested if necessary to confirm repairs or adjustments.
2 .03 DESIGN REQUIREMENTSA. General: Provide a complete scroll packaged chiller as
specified herein and as shown on the drawings. The unit shall be in accordance with the standards referenced in section 1.02 and any local codes in effect.
B. Performance: Refer to the schedule of performance on the drawings. Performance shall be in accordance with applicable AHRI Standard.
C. Acoustics: Sound pressure levels for the unit shall not exceed the following specified levels. The manufacturer shall provide the necessary sound treatment to meet these levels if required. Sound data shall be provided with the quotation. Test shall be in accordance with AHRI Standard 575.
Octave Band 63 125 250 500 1000 2000 4000 8000 dBA
____ ____ ____ ____ ____ ____ ____ ____ ____
engIneerIng guIde speCIfICaTIons
CAT 613-3 • MODEL WGZ CHILLERS 52 www.DaikinApplied.com
engIneerIng guIde speCIfICaTIons
2.04 CHILLER COMPONENTSA. Compressors: The compressors shall be sealed hermetic
scroll type with crankcase oil heater and suction strainer. The compressor motor shall be refrigerant gas cooled, high torque, hermetic induction type, two-pole, with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads.
[OPTION] The compressors shall be covered with factory-installed acoustical sound reduction blankets.
B. Evaporator: On units 30 tons to 130 tons, the evaporator shall be direct expansion type with stainless steel brazed plates. It shall be insulated with ¾ inch (19mm), 0.28 k value, closed cell polyurethane insulation and have 653 psi (4500 kPa) water side working pressure.
[OPTION] The evaporator shall have an additional layer of ¾-inch insulation
On units from 150 to 200 tons, the evaporator shall be shell-and-tube construction, insulated with 3/4 inch (19mm) closed cell polyurethane insulation, and with 150 psi (1033kPa) water-side working pressure.
[OPTION] The evaporator shall have an additional layer of ¾-inch insulation
C. Condenser: Horizontal shell and finned tube type with steel shell and integral finned copper tubes rolled into steel tube sheets. The chiller shall be equipped with intermediate tube supports. Construct condenser in accordance with the requirements of ASME Section VIII Unfired Pressure Vessel Code and ANSI B9.1 Safety Code. It shall be designed for 232 psi (1599 kPa) water side working pressure and 450 psig (3104 kPa) refrigerant side pressure and be provided with ASME, ANSI B9.1 pressure relief valves.
D. Refrigerant Circuit: Each refrigerant circuit shall include a liquid line shutoff valve, replaceable core or sealed filter-drier, sight glass with moisture indicator, liquid line solenoid valve, thermal expansion valve, and insulated suction line.
[OPTION] The unit shall include hot gas bypass on all circuits.
E. Control/Power Panel: The control panel shall contain a microprocessor controller providing operating and equipment protection controls plus motor starting equipment, factory wired, operationally tested, and ready for operation. Standard components shall include a control transformer with primary and secondary fusing, microprocessor transformers with integral fusing and switches for each circuit pumpdown and unit control power. Power connection shall be multi-point (2) to power block. The control panel shall have a hinged tool-locked door.
[OPTION]Multi-point power connection to disconnect switches
[OPTION]Single point power connection to a power block with compressor circuit breakers
[OPTION]Single point power connection to a disconnect switch with compressor circuit breakers
[OPTION]High short circuit current rating (HSCCR) single point power connection to a disconnect switch with compressor circuit breakers
The control system shall stage the compressors based on the leaving water temperature. Equipment protection devices controlled by the microprocessor include motor protection, high pressure, loss of refrigerant, loss of water flow, freeze protection, and low refrigerant pressure. Controls shall include auto/stop switch, chilled water setpoint adjustment, anti-recycle timer, and digital display with water temperature and setpoint, operating temperatures and pressures, and diagnostic messages. The following features and functions shall be included:
1. The LCD-type display shall have a minimum of 20 characters with all messages in English. Coded messages are not acceptable.
2. Critical parameters shall have their own section of control and shall be password protected.
3. Resetting chilled water temperature by a remote 4-20mA DC signal.
4. A soft load function to prevent the system from operating at full load during the chilled water pulldown period.
5. An electronic time clock to allow programming of a yearly schedule accommodating weekends and holidays.
6. Auto restart after a power failure, not requiring external battery backup or auxiliary power for maintaining program memory.
7. Shutdowns shall be date and time stamped with system temperatures and pressures recorded. A minimum of six previous occurrences shall be kept in a revolving memory.
8. Start-to-start and stop-to-start timers to provide minimum compressor off-time with maximum motor protection.
9. Capability of communication with a PC or remote monitoring through a twisted pair RS-232 interface.
10. Demand limiting via a 4-20ma remote signal
11. Lead/lag manually or automatically by compressor number of starts.
12. Continuous diagnostic checks of unit to provide a pre-alarm signal in advance of a shutdown allowing time for remedial action to be taken.
13. The controller shall contain the following features as a minimum:
a. Equipment Protection -The unit shall be protected in two ways: (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition. Shut down
engIneerIng guIde speCIfICaTIons
www.DaikinApplied.com 53 CAT 613-3 • MODEL WGZ CHILLERS
alarms shall activate an alarm signal.
b. Shutdown Alarms
• No evaporator water flow• Low evaporator pressure• High condenser pressure• Motor protection system• Phase voltage protection (Optional)• Outside ambient temperature• Evaporator freeze protection• Sensor failures
c. Limit Alarms
• Condenser pressure stage down, unloads unit at high discharge pressures
• Low ambient lockout, shuts off unit at low ambient temperatures
• Low evaporator pressure hold, holds stage #1 until pressure rises
• Low evaporator pressure unload, shuts off one compressor
d. Unit Enable Selection
• Enables unit operation from local keypad, digital input, or BAS
e. Unit Mode Selection
• Selects cooling, ice, glycol, or test operation mode
f. Analog Inputs
• Reset of leaving water temperature, 4-20 mA
g. Digital Inputs
• Unit off switch• Remote start/stop• Flow switch• Ice mode, converts operation and setpoints
for ice production• Motor protection
h. Digital Outputs
• Shutdown alarm; field wired, activates on an alarm condition, off when alarm is cleared
• Evaporator pump; field wired, starts pump when unit is set to start
14. Optional Building Automation System (BAS) Interface
a. The unit shall be equipped with an optional factory-installed BAS communication module. Factory mounted DDC controller(s) shall support operation on a BACnet®, Modbus® or LonMark® network via one of the data link / physical layers listed below as specified by the successful Building Automation System (BAS) supplier.
• BACnet® MS/TP master (Clause 9)
• BACnet® IP, (Annex J)• BACnet® ISO 8802-3, (Ethernet)• LonMark® FTT-10A. The unit controller shall
be LonMark® certified.The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring, control and alarm notification as specified in the unit sequence of operation and the unit points list.
For chillers communicating over a LonMark® network, the corresponding LonMark® eXternal Interface File (XIF) shall be provided with the chiller submittal data.
All communication from the chiller unit controller as specified in the points list shall be via standard BACnet® objects. Proprietary BACnet® objects shall not be allowed. BACnet® communications shall conform to the BACnet® protocol (ANSI/ASHRAE135-2001). A BACnet® Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal.
The following options are to be included:
[OPTION] The unit shall be shipped with R-I-S vibration isolators for field installation per plans.
[OPTION] The unit shall be shipped with spring vibration isolators for field installation per plans.
[OPTION] Shipping skid
PART 3 - EXECUTION
3.01 INSTALLATIONA. Install in strict accordance with manufacturer’s
requirements, shop drawings, and Contract Documents.
B. Adjust and level chiller in alignment on supports.
C. Coordinate electrical installation with electrical contractor.
D. Coordinate controls with control contractor.
E. Provide all appurtenances required to ensure a fully operational and functional chiller.
3 .02 START-UPA. Ensure proper charge of refrigerant and oil.
B. Provide testing, and starting of machine, and instruct the Owner in its proper operation and maintenance.
CAT 613-3 • MODEL WGZ CHILLERS 54 www.DaikinApplied.com
engIneerIng guIde speCIfICaTIons
Scroll Compressor Chiller, Less W-C Condenser (WGZ 030DA - WGZ 200DA)
PART 1 - GENERAL
1 .01 SUMMARYA. Section includes design, performance criteria,
refrigerants, controls, and installation requirements for water-cooled scroll compressor packaged chillers.
1 .02 REFERENCESA. Comply with applicable Standards/Codes of ANSI/
ASHRAE 15, NEC, and OSHA as adopted by the State.
B. Equipment shall meet efficiency standards of ASHRAE Standard 90.1.
1.03 SUBMITTALSA. Submit shop drawings and product data in accordance
with contract specifications.
B. Submittals shall include the following:
1. Dimensioned plan and elevation view drawings, required clearances, and location of all field connections.
2. Summary of all auxiliary utility requirements such as: electricity, water, etc. Summary shall indicate quality and quantity of each required utility.
3. Single-line schematic drawing of the power field hookup requirements, indicating all items that are furnished.
4. Schematic diagram of control system indicating points for field connection. Diagram shall fully delineate field and factory wiring.
5. Installation manual.
1.04 QUALITY ASSURANCEA. Qualifications: Equipment manufacturer must specialize
in the manufacture of the products specified and have five years experience with similar equipment and the refrigerant offered.
B. Regulatory Requirements: Comply with the codes and standards specified.
C. Chiller manufacturer must be ISO registered.
1.05 DELIVERY AND HANDLINGA. Chillers shall be delivered to the job site completely
assembled and ready for connection to a remote condenser. It shall be shipped a holding charge of nitrogen which shall be removed prior to charging with R-410A.
B. Comply with the manufacturer’s instructions for rigging and handling equipment.
1 .04 WARRANTYThe equipment manufacturer’s warranty shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment. The warranty shall provide for repair or replacement due to failures caused by defective material and workmanship within the above period, excluding refrigerant.
PART 2 - PRODUCTS
2.01 ACCEPTABLE MANUFACTURERSA. Daikin Applied
B. (Approved Equal)
2 .02 UNIT DESCRIPTIONA. Provide and install as shown on the plans, factory
assembled, (remote condenser furnished by others), scroll compressor packaged chiller(s) in the quantity specified. Each chiller shall consist of multiple hermetic scroll compressors, dual-circuit direct expansion evaporator, control system and, when completely installed with the remote condenser, constitute all components necessary for controlled unit operation. Refrigerant shall be R-410A. The condenser interconnecting piping shall be furnished and installed by the contractor.
2 .03 DESIGN REQUIREMENTSA. General: Provide a complete scroll compressor
packaged chiller as specified herein and as shown on the drawings. The unit shall be in accordance with the standards referenced in section 1.02 and any local codes in effect.
B. Performance: Refer to the schedule of performance on the drawings. Performance shall be in accordance with applicable AHRI Standard.
C. Acoustics: Sound pressure levels for the unit shall not exceed the following specified levels. The manufacturer shall provide the necessary sound treatment to meet these levels if required. Sound data shall be provided with the quotation. Test shall be in accordance with AHRI Standard 575.
Octave Band 63 125 250 500 1000 2000 4000 8000 dBA
____ ____ ____ ____ ____ ____ ____ ____ ____
2.04 CHILLER COMPONENTSA. Compressors: The compressors shall be sealed hermetic
scroll type with crankcase oil heater and suction strainer. The compressor motor shall be refrigerant gas cooled, high torque, hermetic induction type, two-pole, with inherent thermal protection on all three phases and shall
engIneerIng guIde speCIfICaTIons
www.DaikinApplied.com 55 CAT 613-3 • MODEL WGZ CHILLERS
be mounted on RIS vibration isolator pads.
[OPTION] The compressors shall be covered with factory-installed sound reduction acoustical blankets.
B. Evaporator: On units 30 tons to 130 tons, the evaporator shall be direct expansion type with stainless steel plates brazed together. It shall be insulated with 3/4 inch (19mm), 0.28 k value, closed cell polyurethane insulation. It shall be designed for 653 psi (4500 kPa) water side working pressure.
[OPTION] The evaporator shall have an additional layer of ¾-inch insulation
On units from 150 to 200 tons, the evaporator shall be shell-and-tube construction, designed for 150 psig (1033 kPa) water side pressure, and insulated with 3/4 inch (19mm) closed cell polyurethane insulation..
[OPTION] The evaporator shall have an additional layer of ¾-inch insulation
C. Condenser: contractor supplied and installed to match the chiller performance at specified ambient conditions.
D. Refrigerant Circuit: Each refrigerant circuit shall include a liquid line shutoff valve, replaceable core or sealed filter-drier, sight glass with moisture indicator, liquid line solenoid valve (no exceptions), thermal expansion valve, and insulated suction line.
[OPTION] The unit shall include hot gas bypass on all circuits.
E. Control Panel: The control panel shall contain a microprocessor controller providing operating and equipment protection controls plus motor starting equipment, factory wired, operationally tested, and ready for operation. Standard components shall include a control transformer with primary and secondary fusing, microprocessor transformers with integral fusing and switches for each circuit pumpdown and unit control power. Power connection shall be multi-point (2) to power block. The control panel shall have a hinged tool-locked door.
[OPTION] Multi-point power connection to disconnect switches
[OPTION] Single point power connection to a power block with compressor circuit breakers
[OPTION] Single point power connection to a disconnect switch with compressor circuit breakers
[OPTION] High short circuit current rating (HSCCR) single point power connection to a disconnect switch with compressor circuit breakers
The control system shall stage the compressors based on the leaving water temperature. Equipment protection devices controlled by the microprocessor include motor protection, high pressure, loss of refrigerant, loss of water flow, freeze protection, and low refrigerant pressure. Controls shall include auto/stop switch, chilled water setpoint adjustment, anti-recycle timer, and digital display with water temperature and setpoint, operating
temperatures and pressures, and diagnostic messages. The following features and functions shall be included:
1. The LCD type display shall have a minimum of 20 characters with all messages in English. Coded messages are not acceptable.
2. Critical parameters shall have their own section of control and shall be password protected.
3. Resetting chilled water temperature by a remote 4-20mA DC signal.
4. A soft load function to prevent the system from operating at full load during the chilled water pulldown period.
5. An electronic time clock to allow programming of a yearly schedule accommodating weekends and holidays.
6. Auto restart after a power failure, not requiring external battery back-up or auxiliary power for maintaining program memory.
7. Shutdowns shall be date and time stamped with system temperatures and pressures recorded. A minimum of six previous occurrences shall be kept in a revolving memory.
8. Start-to-start and stop-to-start timers t.
9. Capability of communication with a PC or remote monitoring through a twisted pair RS-232 interface.
10. Lead/lag by manually or automatically by compressor number of starts.
11. Continuous diagnostic checks of unit operation to provide a pre-alarm signal in advance of a shutdown allowing time for remedial action to be taken.
12. Contacts for control of up to 8 condenser fans
13. An advanced DDC microprocessor unit controller with a 4-line by 20-character liquid crystal display provides the operating and protection functions. The controller shall take pre-emptive limiting action in case of high discharge pressure or low evaporator pressure. The controller shall contain the following features as a minimum:
a. Equipment Protection - The unit shall be protected in two ways: (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition. Shut down alarms shall activate an alarm signal.
b. Shutdown Alarms
• No evaporator water flow• Low evaporator pressure• High condenser pressure• Motor protection system• Phase voltage protection (Optional)• Outside ambient temperature• Evaporator freeze protection
CAT 613-3 • MODEL WGZ CHILLERS 56 www.DaikinApplied.com
engIneerIng guIde speCIfICaTIons
• Sensor failuresc. Limit Alarms
• Condenser pressure stage down, unloads unit at high discharge pressures
• Low ambient lockout, shuts off unit at low ambient temperatures
• Low evaporator pressure hold, holds stage #1 until pressure rises
• Low evaporator pressure unload, shuts off one compressor
d. Unit Enable Selection
• Enables unit operation from local keypad, digital input, or BAS
e. Unit Mode Selection
• Selects cooling, ice, glycol, or test operation mode
f. Analog Inputs
• Reset of leaving water temperature, 4-20 mA
g. Digital Inputs
• Unit off switch• Remote start/stop• Flow switch• Ice mode, converts operation and setpoints
for ice production• Motor protection
h. Digital Outputs
• Shutdown alarm; field wired, activates on an alarm condition, off when alarm is cleared
• Evaporator pump; field wired, starts pump when unit is set to start
i. Condenser Fan Control
The unit controller shall be able to provide control of the remote condenser fans. The controller shall sequence condenser fans based on compressor discharge pressure.
j. Building Automation System (BAS) Interface
The unit shall be equipped with an optional factory-installed BAS communication module
Factory mounted DDC controller(s) shall support operation on a BACnet®, Modbus® or LonMark® network via one of the data link / physical layers listed below as specified by the successful Building Automation System (BAS) supplier.
• BACnet® MS/TP master (Clause 9)• BACnet® IP, (Annex J)• BACnet® ISO 8802-3, (Ethernet)• LonMark® FTT-10A. The unit controller shall
be LonMark® certified.
The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring, control and alarm notification as specified in the unit sequence of operation and the unit points list.
For chillers communicating over a LonMark® network, the corresponding LonMark® eXternal Interface File (XIF) shall be provided with the chiller submittal data.
All communication from the chiller unit controller as specified in the points list shall be via standard BACnet® objects. Proprietary BACnet® objects shall not be allowed. BACnet® communications shall conform to the BACnet® protocol (ANSI/ASHRAE135-2001). A BACnet® Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal.
[OPTION] Supplemental overloads reduce the required electrical service size and wire sizing
F. The following options are to be included:
1. [OPTION] The unit shall be shipped with R-I-S vibration isolators for field installation per plans.
2. [OPTION] The unit shall be shipped with spring vibration isolators for field installation per plans.
3. [OPTION]The unit shall be shipped on a shipping skid.
PART 3 - EXECUTION
3.01 INSTALLATIONA. Install chiller and remote condenser with interconnecting
piping and wiring in strict accordance with manufacturer’s requirements, shop drawings, and Contract Documents. Chiller manufacturer must approve the refrigerant piping design.
B. Adjust and level chiller in alignment on supports.
C. Coordinate electrical installation with electrical contractor.
D. Coordinate controls with control contractor.
E. Install, pressure test, and evacuate field refrigerant piping.
F. Provide all appurtenances required to insure a fully operational and functional chiller.
G. Purge chiller unit and charge system with refrigerant and oil.
3 .02 START-UPA. Ensure proper charge of refrigerant and oil.
B. Provide testing, and starting of machine, and instruct the Owner in its proper operation and maintenance.
Daikin Applied Training and DevelopmentNow that you have made an investment in modern, efficient Daikin Applied equipment, its care should be a high priority. For training information on all Daikin Applied HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Applied Representative for warranty details. To find your local Daikin Applied Representative, go to www.DaikinApplied.com.
Aftermarket Services
To find y our l ocal p arts o ffice, vi sit www.DaikinApplied.com or ca ll 800-37PARTS (800-377-2787). To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.DaikinApplied.com.
Products manufactured in an ISO Certified Facility.
CAT 613-3 (02/15) ©2015 Daikin Applied | (800) 432–1342 | www.DaikinApplied.com