Siemens AG 970007, page 1 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Use of the application program
Product family: Display
Product type: Display units
Manufacturer: Siemens AG
Name: Contouch Room Controller UP 204
Order no.: 5WG1 204-2AB11, titanium white,5WG1 204-2AB21, carbon metallic,5WG1 204-2AB31, aluminium metallic,5WG1 204-2AB51, piano black
Table of Contents1 About this manual ................................................................... 22 System description .................................................................. 3
2.1 Overview ................................................................................ 32.2 Contouch Room Controller....................................................... 42.3 Contouch Manager (Plug-In) .................................................... 5
3 Editing parameters .................................................................. 63.1 Overview of the configuration steps ......................................... 63.2 Work area and configuration window ....................................... 7
3.2.1 Menu and symbol bar ..................................................... 83.2.2 Text input ....................................................................... 83.2.3 Labeling of the parameter types ...................................... 9
3.3 Import and export of configuration data ................................... 93.3.1 Importing configuration data .......................................... 93.3.2 Exporting configuration data ........................................... 9
3.4 Basic scenes .......................................................................... 103.4.1 Communication objects for the basic scenes .................. 10
3.5 Languages ............................................................................ 113.5.1 Add language ............................................................... 113.5.2 Delete language ........................................................... 11
3.6 Channels ............................................................................... 123.6.1 Switch channel type ..................................................... 133.6.2 Dimmer channel type ................................................... 143.6.3 Channel type priority control ......................................... 153.6.4 Channel type Shutter .................................................... 153.6.5 Channel type roller blinds ............................................. 163.6.6 Channel type Send value ............................................... 173.6.7 Channel type Scene control ........................................... 193.6.8 Channel type Alarm / Message ...................................... 20
3.6.8.1 Function-specific alarm parameters ............... 203.6.8.2 Function-specific message parameter ............ 21
3.7 General parameters ............................................................... 233.7.1 Standby mode .............................................................. 233.7.2 Pressing buttons ........................................................... 243.7.3 Cleaning mode ............................................................. 243.7.4 LED orientation light ..................................................... 243.7.5 Holding down a pushbutton .......................................... 253.7.6 Query and sending of status objects .............................. 253.7.7 Time and date .............................................................. 253.7.8 Temperature unit.......................................................... 253.7.9 Admin mode ................................................................ 26
3.8 General alarms ...................................................................... 263.9 Room temperature control ..................................................... 27
3.9.1 Functional overview ..................................................... 273.9.2 Parameter pages ........................................................... 283.9.3 Device function ............................................................ 293.9.4 Controller operating modes .......................................... 293.9.5 Actual value specification .............................................. 303.9.6 Setpoint value specification .......................................... 313.9.7 Updating the setpoint value on the basis of outside
temperature ................................................................. 323.9.8 Room operating modes ................................................. 32
3.9.8.1 Automatic / manual mode ............................. 323.9.8.2 Comfort mode .............................................. 333.9.8.3 Pre-comfort mode (standby) ......................... 333.9.8.4 Energy-saving- mode (nighttime reduction) ... 333.9.8.5 Protection mode (frost protection / heat
protection) ................................................... 333.9.8.6 Permanent protection mode.......................... 34
3.9.8.7 Evaluation of the window states .................... 343.9.8.8 Comfort extension ........................................ 343.9.8.9 Dew point mode ........................................... 353.9.8.10 Display on the operating and display system .. 353.9.8.11 Mode toggling via the bus ............................. 363.9.8.12 Control via 1-bit objects ................................ 363.9.8.13 Control via 1-byte objects .............................. 363.9.8.14 Switching off the controller via the bus ......... 37
3.9.9 Ventilation ................................................................... 373.10 Time programs ...................................................................... 39
3.10.1 Time program for temperature control .......................... 403.10.2 Time program of channels ............................................ 403.10.3 Delete time program ..................................................... 41
3.11 Skins .................................................................................... 423.12 Menu structure ..................................................................... 42
3.12.1 Surface concept of the control panel ............................. 423.12.2 Work area and configuration window ............................ 443.12.3 Create function page .................................................... 45
4 Transfer of the configuration data .......................................... 474.1.1 Configuration data for MicroSD card .............................. 474.1.2 Parameters in ETS ......................................................... 474.1.3 Generation errors ......................................................... 47
5 Contouch Manager as separate tool ....................................... 485.1 The menu bar ........................................................................ 49
5.1.1 Menu: Save .................................................................. 495.1.2 Menu: Save as .............................................................. 495.1.3 Menu: Open ................................................................. 495.1.4 Menu: Language .......................................................... 495.1.5 Menu: Show warnings .................................................. 505.1.6 Menu: Extras ................................................................ 505.1.7 Menu: Generate ........................................................... 50
5.2 The Tabs ............................................................................... 505.2.1 Tab: Languages ............................................................ 505.2.2 Tab: Channels ............................................................... 515.2.3 Tab: Parameters ............................................................ 515.2.4 Tab: Scheduler.............................................................. 515.2.5 Tab: Skins ..................................................................... 515.2.6 Tab: Menu structure ..................................................... 51
6 Parameters and communication objects ................................. 526.1 Common parameters ............................................................. 52
6.1.1 Parameter display and operation ................................... 526.1.2 Parameter objects for display and operation .................. 556.1.3 Common alarm parameters........................................... 566.1.4 Common room temperature control parameters ............ 576.1.5 Fan parameters ............................................................ 616.1.6 Parameter: Temperatures, current value ........................ 636.1.7 Parameter Controller/Control Panel mode ...................... 666.1.8 Heating parameter, two-point control ........................... 706.1.9 Heating parameter, PI control ....................................... 716.1.10 Heating parameter, sequence control ............................ 746.1.11 Cooling parameter, two-point control ............................ 766.1.12 Cooling parameter, PI control ........................................ 786.1.13 Cooling parameter, sequence control ............................ 816.1.14 Heating and cooling parameter, PI control ..................... 836.1.15 Communication objects for room temperature control ... 84
6.2 Channels ............................................................................... 916.2.1 Parameter for channel type ........................................... 916.2.2 Switch parameter ......................................................... 916.2.3 Switch communication objects ...................................... 916.2.4 Communication objects for dimming............................. 916.2.5 Blinds parameter .......................................................... 926.2.6 Communication object for blinds................................... 926.2.7 Parameter for shutters .................................................. 936.2.8 Communication objects for shutters .............................. 936.2.9 Send value parameter ................................................... 946.2.10 Send value communication object ................................. 956.2.11 Communication object for forced control ...................... 956.2.12 Channel-specific parameter for alarms and messages..... 956.2.13 Alarm communication objects ....................................... 976.2.14 Message communication object .................................... 986.2.15 Screen control parameter.............................................. 986.2.16 Communication objects for the retrieval and storage of
scenes .......................................................................... 986.3 Time programs ...................................................................... 99
6.3.1 Communication objects for time programs .................... 997 Index .................................................................................. 100
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 2 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
1 About this manualThis manual describes the application program and theContouch Manager (Plug-in) for the configuration of theoperating and display systems of the Contouch RoomController.
The manual is designed for qualified specialists withdetailed knowledge of control systems in buildingtechnology. The following is particularly expected:- In-depth knowledge of the design and operation of the
KNX bus system,- In-depth knowledge of the ETS configuration software.
Notes on using the manualCertain facts are highlighted in the manual.
Note:Notes and further information are highlighted from theusual text by lines.
1. Instructions are presented as a numbered list.Ø The typically expected results of an action are
described at the end of the instruction.
Parameters, parameter values, names of communicationobjects and buttons and displayed in bold.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 3 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
2 System description
2.1 Overview
Figure. 1. System overview
KNX Interface
Commissioning by qualified personnel:Configuration of:
· Function· Relevant KNX parameters· Time programs· Menu structure· Design selection· Alarm messages
Start plug-in
PhysicaladdressesGroupaddressesparameter
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 4 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
2.2 Contouch Room Controller
The multifunctional Contouch display and operatingsystem serves to display the conditions and to operateand control devices in connection with the KNX buildingbus system.
Figure. 2. Contouch display and operating system
1) Touch-Display2) Status and orientation LED3) Rotary control with print function4) Temperature sensor
Function:The buttons presented on the display can be used forswitching, dimming, controlling room temperature, ascontrol commands for shutters, roller blinds and fans orfor the retrieval and storage of scenes.
Properties:- TFT Color display 2.8“ 320x240 Pixel,- Display with touch function and rotary control with
print function for operation,- Status and orientation LED on the rotary knob,- Internal temperature sensor,- Interface to the BCU- Slot for MicroSD card.
Note:Details about the product can be found in the TechnicalProduct Information (TPI) and the Operating andAssembly Manual (BMA) of the device.
CommunicationCommunication with the KNX building bus system occursexclusively through the attached BCU bus coupling unit.
Figure. 3. BCU bus coupling unit
1) Programming LED2) Programming knob3) Holes for the centering spike for attaching the Contouch
Note:Details about the product can be found in the TechnicalProduct Information (TPI) and the Operating andAssembly Manual (BMA) of the device.
1
4
3
2
3
2
1
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 5 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
2.3 Contouch Manager (Plug-In)
The Contouch Manager (Plug-In) makes it possible toconfigure and set parameters for the Contouch RoomController. The program is run as a plug-in in the ETSapplication program. The Contouch Manager can also berun as a separate tool, independent of the ETS Tool (seechapter 5).
The ETS application program in Version 3.0f or higher isrequired for the plug-in.
Function:- Configuration of the Room Controller functions,- Configuration of all parameters for controlling the
connected devices,- Configuration of time programs,- Configuration of the menu structure and selection of
the menu design,- Configuration of alarms and status reports.
System criteria- Operating system: as of Windows XP SP3, Vista SP1 or
Windows 7,- Screen resolution: 1024*768 or higher,- Reader for storage card format microSD or microSDHC
(possibly using adapter SD on microSD or USB microSDreaders) to describe microSD card or microSDHC card.
- Microsoft .Net Framework 3.5 SP1,- ETS Version 3.0f or higher.
Data transmissionThe complete configuration of the Contouch operatingand display system via the KNX bus is not recommendedby reason of its bandwidth restriction (very longtransmission time). Therefore a MicroSD card is used as asecond medium for transmitting the configuration data.
Figure. 4. Interfaces of the Contouch Manager
Note:To avoid irreparable errors it is not allowed to removethe SD-card during boot-up time!
Note:The BCU is always able to communicate. If theContouch Room Controller is not plugged on the BCUor if it stopped with an error message during boot-uptime the request of communication objects willdeliver wrong results. The values are not set on theContouch Room Controller. The correct connectionbetween Contouch Room Controller and BCU has tobe ensured. The correct display and operation on theContouch Room Controller has to be controlled. Thena correct communication between Contouch RoomController and BCU is assured.
ETS ContouchManager(ETS-Plug-
In)
Plug-In
Contouch
RoomController
KNX-Bus- Physical address- Group addresses- Parameters
MicroSD-Card- Specific parameters- Time programs- Menu structure- Designs- Firmware
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 6 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3 Editing parameters
3.1 Overview of the configuration steps
The application program is thematically organized byconfiguration steps. The sequence supports the user inthe recording of the parameters, the arrangement of thetime program, the determination of the menu structureand selection of the design.
Figure. 5. Configuration steps
1.) Definition of the languages
2.) Channels:- Definition of the functions- Designation- Channel-specific
parameter
3.) Parameter
4.) Setting of the time program
5.) Selection of the design
6.) Definition of the menustructure
7a.)Generation of theconfiguration data(Binary data onMicroSD-card)
7b.) Generation of theobjects andconfiguration data(Parameter in ETS)Group addresses
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 7 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
3.2 Work area and configuration window
1. Select the device in the ETS application programand run the Edit parameters function.
Ø The work area (Plug-in) opens with theconfiguration and input windows.
Figure. 6. Contouch Manager Work Area (Example of channel configuration window)
1) Menu and symbol bar2) Configuration window, dependent on context3) Additional input window, dependent on context4) Exit work area without saving5) Save the configuration and exit work area
21 3
45
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 8 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3.2.1 Menu and symbol bar
The menu and symbol bar contain commands anddisplays required to run the application program.
ImportImporting configuration data (see Chapter 3.3.1, Page 9).
ExportExporting configuration data (see Chapter 3.3.2, Page 9).
LanguageThe standard language can be selected in the dropdownmenu next to the Language field.
Only those languages can be chosen which were appliedin the Languages configuration window (see Chapter3.5, page 11).
Displaying warningsTexts and parameters are checked continuously forcorrectness and completeness during input.
Missing inputs are displayed by warning symbols (yellowor red triangle with exclamation mark). An explanatoryerror text is displayed when the warning symbol isclicked or as a tooltip text when the mouse crosses overit.
Checks are made for the following:- Existence of the texts in all active languages,- Compliance with the maximum allowed text length.
1. Activating the Display warnings control box.Ø The warning symbols are displayed.
2. Deactivating the Display warnings control box.Ø The warning symbols are not displayed.
ExtrasAbout…: Display of the current software version.
GenerateCreates the configuration data, which are nottransmitted by KNX Bus (see Chapter 4.1.1, Page 47).
OKSave current settings and close the work area window.
CancelClose the work area window without saving.
3.2.2 Text input
All text inputs are checked for length in the context oftheir usage (e.g. button labels).
Note:The text length is evaluated on a pixel basis to ensurethe display on the Contouch operating and displaysystem. A check based on character number is notpossible, since the text length depends on the type ofletters.
The texts are once again checked for completeness andmaximum length when the output data for the operatingand display system are generated.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 9 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
3.2.3 Labeling of the parameter types
The parameters are transmitted in various ways for theconfiguration of the Contouch operating and displaysystem.
Figure. 7. Data transmission
A symbol in front of the parameter names displays thetransmission route authorized for this parameter.
Figure. 8. Labeling of the parameter types
1) Transmission required only via KNX Bus (ETS)2) Transmission via KNX Bus and MicroSD card required3) Transmission only required via MicroSD card
3.3 Import and export of configuration data
3.3.1 Importing configuration data
The configuration data stored in a project file(*.Contouch) can be imported. In the process the KNXbus parameters and the group address connections arealso read.
Function when importing group address connections:- Pre-existing group address connections are deleted.- Missing group addresses are added.- Group address designations and comments are
adopted for group addresses to be newly created.- Group address designations and comments are not
adopted for existing group addresses.
Import:1. Click on the Import button.Ø The file selection window opens.
2. Search and select Contouch file.3. Click on the Open button.Ø The parameters are imported.
3.3.2 Exporting configuration data
The current configuration data stored can be exported toa project file (*.Contouch).
1. Click on the Export button.Ø The file selection window opens.
2. Enter the file name. File type: *.Contouch.3. Click on the Save button.Ø The project file is saved.
Contouch(Plug-In)
Installation
Contouch
Export/Import
rcconfig.binGenerate
ETS(Database)
Ok
Program
MicroSD/SDHC-card
Insert
1 2 3
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 10 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3.4 Basic scenes
It is possible to directly activate two scenes with thepress function of the rotary control without using thefunctions from the menu pages of the Touch Display.Each time the rotary control is pressed, the Contouchroom controller switches between basic scenes. Thescene numbers of the two basic scenes can beconfigured in the range of 1 – 64. This makes it possible,for example, to activate basic scene 1 (light ON) whenentering a room and to activate basic scene 2 (light OFF)when leaving. This occurrence depends on the value of astatus object. This allows the room controller torecognize that the light is already ON and is switched offwith basic scene 2 or whether the light is OFF andswitched on with basic scene 1.
The pressing action on the rotary knob for sending ascene number is only active when no function isselected.The pressing action on the rotary knob for sending ascene number is not active when the user is in the "Sendvariable value function".The pressing action on the rotary knob for sending ascene number is also not active in one of the followingstates: a room operating mode is selected, the setting ofthe setpoint temperature is selected, the setting of thefan speed is selected or the setting of the comfort modeextension is selected within the room temperaturecontroller.
Note:Any function selected on the Touch Display will berepresented by an orange border around this button.
If one is on the home page, all functions on the touchdisplay are deselected after 5 seconds. Further activity onthe touch display or rotary control within these 5seconds causes this time interval to be reset. Thefunctions can also be manually deselected by pressing onan empty area (no symbol for a function of navigation)on the touch display. The pure display fields (time, date,temperatures, etc.) can also be activated for thispurpose.
3.4.1 Communication objects for the basic scenes
Obj. Object name Function Type Flags114 8-bit basic
sceneRecall 1 Byte CT
This communication object is used in dependence on astatus object Basic scene selection to send scene X(value 0) or scene Y (value 1).The scene numbers X and Y can be configured freely.
115 Basic sceneselect
Receive 1 bit CWTU
This communication object is used to receive the value ofa status object. The scene to be sent by the 1 byte objectis selected with the value of this status object.Object value:- "0" = basic scene X is sent- "1" = basic scene Y is sent
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 11 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
3.5 Languages
The target languages for user prompts on the Contouchoperating and display system are set in this menu.
Note:The contents of the texts to be displayed are notautomatically determined by the language setting. Theymust be entered when defining the channels andstructures.
Missing entries are labeled in the application programwith a warning sign.
Up to 6 languages can be defined. This can be practical inhotels or public buildings, for example.
Figure. 9. Language selection input mask
1) Language added2) Language delete3) Current standard language
3.5.1 Add language
1. Select the Language tab.2. Click Add.Ø The selection window with the available
languages opens, Fig. 10.3. Select language.4. Confirm choice with OK.Ø The language is added and used.
Figure. 10. Language selection
3.5.2 Delete language
Languages can be deleted.
All texts already set to a language are also deleted. Theymust be newly defined when re-entered.
1. Select languages to be deleted.2. Click Delete.Ø The language and the associated texts are
deleted.
1 32
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 12 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3.6 Channels
The channels used are defined in this menu andfunctions assigned to them.
Up to 18 channels are available, which can be assignedthe following functions:
- Switch,- Dimmer,- Sun blind,- Roller shutter,- Send value,- Forced control,- Alarm / Message,- Scene control
Depending on the selected function (channel type),additional parameters are enabled, in which therespective functions can be specified.
Note:The configuration data in the operating and displaysystem must be updated via ETS or the MicroSD cardwhen then parameters are changed.
Figure. 11. Contouch Manager work area (example of channel configuration window)
1) Channel number2) State column for displaying warning messages3) Channel name4) Activation / deactivation of a channel
5) Channel type display (function)6) Languages window for designating the channel7) Parameter window (dependent on function)
5 6 74321
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 13 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Designating the channelsThe functions used are activated and named when thechannels are configured. The designation under theName column is used as a suggestion for the menucaptions (see Chapter 3.12, Page 42) and serves as anorientation for the additional configuration steps.
ActivationThe channels to be used must be marked in the Activecolumn. Only then are they available in the additionalconfiguration steps.
Text input languagesThe designation of the channel is entered in the separateLanguages window. All set languages are listed in thiswindow. Every text field must be filled in.
If a language is not filled in, then a warning messageappears in the status field.
The texts of the standard language are each displayed inthe channel selection window.
Note:See Chap. 6.2, starting on page 91, for a description ofthe communication objects and parameters.
3.6.1 Switch channel type
The Switch is used to send 1 Bit objects for variousswitching functions.
Switching functionThe switching function is specified by the selection of aswitch type. The following switching functions can bechosen:- Switch-on only or switch-off only, independent of the
current status,- Switching: switch On/Off depending on the current
status ,- Bells: Switch on for as long as the button is pressed or
not pressed (adjustable).
The status display can be deactivated by configuration.The associated status object is always visible. The statusdisplay is exclusively controlled by the status object. Thusif no status object is linked, then the status display doesnot change.
Status display visibleIf Status display visible is set with yes, then theswitching status is displayed on the operating anddisplay system.
If Status display visible is set with No then the statusdisplay is deactivated. The associated status object isalways visible.
Note:The status display is controlled by the status object. Ifno status object is linked, then the status display doesnot change.
Status display on the operating and display systemThe status is displayed by a point on the switchingfunction.
Figure. 12. Example for switching status OFF
Figure. 13. Example for switching status ON
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 14 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3.6.2 Dimmer channel type
The Dimmer channel type can be used to set thebrightness of the lighting.
Dimming function- Selection of the channel by pressing the button in the
operating and display system.- The border color of the button changes.- Sending a 1 Bit switch command (ON/OFF) by pressing
the rotary button.- Sending a 1 Byte dimming value telegram by turning
the rotary control. This sent dimming setpoint value isdisplayed for 5 s.
- After this time, the actual status of the dimmer isdisplayed instead of the dimming setpoint value. Theconnection of the 1 Byte communication object isrequired for this.
The dimming value is changed by turning the rotarycontrol on the operating and display system. Slowturning changes the dimming value by 1 Bit (approx. 0.4percentage points) per click. Fast turning leads to agreater change of value.
Note:If configured accordingly the dimmer (actuator) canalso be switched using the 1 Byte communicationobject.
Correct connection of the status objectsIf the status objects are connected incorrectly, theoperating and display system cannot correctly update theinternally held status.
Display on the operating and display systemThe rotary control function is displayed by an arc withtwo arrows (top left).
The dimming function is displayed by a bar on the loweredge of the switch area. The bar is circular at theminimum dimming value.
Figure. 14. Example of dimming (here brightnessvalue around 60%)
Example: Dim light1. Tough the Dim lights button.Ø The corresponding channel is selected.
2. Press the rotary controlØ The dimmer is switched on (1 bit)
3. Turn the rotary control until the desired brightnessvalue is reached.
4. Press the rotary controlØ The dimmer is switched off (1 bit)
Note:The brightness value which takes effect when switchedon (1 bit) is set by configuring the dimmer.
0705 Contouch Room Controller 97000
Siemens AGInfrastructure & Cities Sector, Building TechnologiesControl Products and SystemsP. O. Box 10 09 53, D-93009 Regensburg
3.6.3 Channel type forced control
The channel type Forced control can be used to overrideswitching processes with forced control. For example, inenergy saving or night mode the switching on of specificlights or loads can be prevented.
forced control functionThe following commands and buttons are provided forthe priority control function.- Activate forced control and switching status ON: Send
11,- Activate forced control and switching status OFF: Send
10,- Deactivate forced control without switching: Send
The command is immediately sent by pressing the buttonon the operating and display system.
Display on the operating and display systemPressing the forced control button changes the display inthe priority control submenu, where the commands canbe selected.
Figure. 15. Example of forced control (Activate forced control and switchingstatus ON)
Application program description
Contouch Room Controller 970007
970007, page 15 / 101Infrastructure & Cities Sector, Building Technologies
ã Siemens AG 2017 Update: http://www.siemens.com/gammaSubject to change without further notice
can be used to overridecontrol. For example, in
energy saving or night mode the switching on of specific
mmands and buttons are provided for
control and switching status ON: Send
control and switching status OFF: Send
control without switching: Send 00.
ediately sent by pressing the button
Display on the operating and display systemcontrol button changes the display in
the priority control submenu, where the commands can
control (shown above:control and switching
3.6.4 Channel type sun blind
The functions for operating a sun blindblind channel type.
FunctionTwo 1-bit communication objects are provided for thebasic functions.- Sun blind up/down,- Stop sun blind and slats open/closed.
The stop command always sends amovement of the sun blind at any time.
Note:The stop command and the slat position are senjoint communication object.The sun protection movement is stopped the first timethe button is pressed. Each additional press of thebutton changes the slat position by one step (slatsopen).
Invert slat rotation directionThe rotational direction of the lamellae can be reversed.- No: Turning clockwise sends lamellae closed (1).- Yes: Turning clockwise sends lamellae open (0).
Display status
- display value 0 as question markIn this setting value 0 is interpreted as undefinedstatus and therefore it is indicated as a question markon the display.The value 1 accords to the upper end position.The value 255 accords to the lower end position.
- display value 0 as 0%The value 1 accords to the upper end position, 0%.The value 255 accords to the lower en100%.
State object of actuator availableIf the used sun blind actuator provides a status object(position of the sun blinds), this can be evaluated for thesun blind control.
Note:The actuator status object must be connected to thechannel status object.
GAMMA instabus
Application program description
September 2017
Technical Manual
Update: http://www.siemens.com/gamma
2.12.1.14
sun blind
sun blind are set in the sun
objects are provided for the
and slats open/closed.The stop command always sends a 0. It can end the
at any time.
The stop command and the slat position are sent by a
The sun protection movement is stopped the first timethe button is pressed. Each additional press of thebutton changes the slat position by one step (slats
of the lamellae can be reversed.: Turning clockwise sends lamellae closed (1).: Turning clockwise sends lamellae open (0).
as question markIn this setting value 0 is interpreted as undefined
is indicated as a question mark
accords to the upper end position.The value 255 accords to the lower end position.
The value 1 accords to the upper end position, 0%.The value 255 accords to the lower end position,
State object of actuator availableactuator provides a status object
), this can be evaluated for the
The actuator status object must be connected to the
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 16 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Display on the operating and display systemPressing the sun blind button changes the display on theoperating page. Commands for operating the shutter canbe selected here.
Figure. 16. Sun blind button on the Home-page
The operating page of the sun blinds can be designedwith or without status display.
Figure. 17. Operating page of the sun blind withoutstatus display
1) Sun blind button up2) Stop button3) Sun blind button down4) Change of slat position (set by rotary control)
Figure. 18. Operating page of the sun blinds withstatus display
1) Sun blind button up2) Stop button3) Sun blind button down4) Position display of the sun blind5) Change of slat position (set by rotary control)6) Position display of the slats
3.6.5 Channel type roller shutter
The functions for operating a roller shutter are defined inthe Roller shutter channel type.
FunctionTwo 1-bit communication objects are provided for thefunctions.- Roller shutter up/down,- Stop roller shutter.
The stop command always sends a 0. It can end thetravel of the roller shutter at any time.
State object of actuator availableIf the roller shutter actuator in use provides a statusobject (position of the roller shutter), this can beevaluated for the roller shutter control.
Note:The actuator status object must be connected to thechannel status object.
Display status
- display value 0 as question markIn this setting value 0 is interpreted as undefinedstatus and therefore it is indicated as a question markon the display.The value 1 accords to the upper end position.The value 255 accords to the lower end position.
1 2 3
4
1 2 3
5
4
6
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 17 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
- display value 0 as 0%The value 1 accords to the upper end position, 0%.The value 255 accords to the lower end position,100%.
Display on the operating and display systemPressing the roller shutter button changes the display onthe operating page. Commands for operating the rollershutter can be selected here.
Figure. 19. Roller shutter button on the Home-page
The operating page of the roller shutter can be designedwith or without status display.
Figure. 20. Operating page of the roller blinds withoutstatus display
1) Roller shutter button up2) Stop button3) Roller shutter button down
Figure. 21. Operating page of the roller shutter withstatus display
1) Roller shutter button up2) Stop button3) Roller shutter button down4) Position display of the roller shutter
3.6.6 Channel type Send value
The channel type Send value is used to send fixed orvariable values to the KNX Bus. Various data types andunits can be sent.
Send value function – fixedFixed values are sent to the channel by simpleassignment of a button. An operating page is notavailable. The rotary control on the Contouch operatingand display system has no function.
Send value function – variableVariable values are set and sent on the Contouchoperating and display system. A separate function pageis available for this. The rotary control can be used tochange the values.
The value range (minimum, maximum) is set in theparameter window. The smallest step size is determinedby the resolution of the selected data type.
Variable valueThe parameter specifies the function of the channel type.- No: Send value – fixed- Yes: Send value – variable. The selection of this option
expands the parameter window to include the entriesmaximum, minimum and unit.
1 2 3
1 2 3
4
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 18 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Data typeThe following 8 data types are available: The data typeconsists of the size of the communication object (1, 2 or4 byte) and the number type (%, integer with/withoutsign, floating point value for wind speed, brightness,temperature).
The smallest step size for changing values on theContouch operating and display system is determined bythe data type:- Integers (including percentage values) are changed as
whole numbers.
ValueOnly for the Send value – fixed function.
Sets the value to be sent when the button is pressed.This value cannot be changed on the Contouch operatingand display system.
Maximum / MinimumOnly for the Send value – variable function.
The value range can be restricted in these fields. Themaximum expanse of the value range depends on theselected data type.
When the data type is selected maximums andminimums of the respective data type are automaticallyentered in the respective fields and can be adaptedthere.
Note:The value of the Minimum parameter is displayed onthe operating and display system the first time theoperating page is opened.The last sent/received value is displayed with eachadditional call-up of the operating page.
UnitOnly for the Send value – variable function.
This parameter is used to set the unit displayed under thenumerical value on the operating and display system.- Maximum length: 14 characters.
Display on the operating and display systemThe functions Send value - fixed and Send value -variable are displayed differently.
Figure. 22. Function page with "send value" buttons(example)
1) Symbol for send value – variable2) Symbol for send value – fixed (here: activated)
Send value – fixed:1. Touch button.Ø The fixed set value is sent.
Send value – variable:- The values are displayed on the operating page
according to their data type.
Figure. 23. Operating page for send value – variable
(Example)
1) Naming, corresponds to the channel designation2) Current value, adjustable3) Unit
1 2 3
1 2
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 19 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
1. Touch buttonØ The display changes to the operating page.
2. The value to be sent is set with the rotary control.When the control is turned quickly, the step widthadapts dynamically to the specified value range.
3. Press the rotary control.Ø The value is sent. The sent value is permanently
stored in the operating and display system. It isalso available after the power supply returns.
Note:If the dimmer is activated by sending a 1 byte valuewith the channel type send, the dimmer is dimmed viaa 1 byte dimming value. Therefore the dimmingactuator has to be parameterized in a specific kind, sothat switching the dimmer on or off via a 1-bitswitching object is not necessary. The delivered 1 bytedimming value is dimming the channel on the setdimming value.
3.6.7 Channel type Scene control
The scene control channel type serves to designate ascene and to specify the scene number (Scene-ID), whichis to be sent by the communication object.
Scenes serve to combine switching processes, which leadto the creation of a certain, reproducible state.
The designation of the scenes is used as a suggestion forthe menu-caption in the operating and display system.
Scene number (Scene-ID)The scene number uniquely identifies a scene. It cannotbe changed, not even if other scenes are deleted.- Value range: 1…64.
Display and call-up on the operating and displaysystemScenes are displayed as buttons on the home-page orfunction pages. Scene buttons can be identified by a filmflap symbol in the upper left.
The button border color 1 changes when a scene is calledup.
Figure. 24. Function page with 3 scenes (example)
Change scene settings on the operating and displaysystem1. Consecutively call up all operating pages of the
channels to be changed and change the values.2. Switch to the button of the changed scene.3. Resave the scene by pressing and holding down the
button.Ø A signal tone sounds.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 20 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3.6.8 Channel type Alarm / Message
The channel type Alarm / messages is used to configurealarm and message functions. Alarms and messages arefunctionally differentiated in regard to resolution,signaling and acknowledgement.
Note:The channel-specific parameters for alarms / messagesare set in the Channels configuration window.Global parameters for all alarms are defined in theParameters configuration window (see Chapter 3.8,Page 26).
Alarm functionAlarms are automatically displayed when they occur.Along with being shown on the display, alarms can alsobe signaled by the LED or as a signal tone. The behaviorof Display, LED and signal tone in the case of alarm isconfigured by the parameters specific to each channel.
Alarms are prioritized. Alarms with the highest priorityare displayed first. When priorities are equal, the mostrecent message is displayed first.
Alarms must be acknowledged. The acknowledgementcan be made using the Display on the operating anddisplay system or externally via a communication object.
Message functionMessages are automatically displayed when they occur.They on stored on an operating page. The sequenceconforms to the channel sequence.
Alarms do not need to be acknowledged.
3.6.8.1 Function-specific alarm parameters
Note:The other parameters to be set vary depending on theselected function. The parameters described in thefollowing apply for the Alarm function.
Condition for alarm activationAn alarm is activated when the operating and displaysystem receives value set here from the object triggeredby the alarm (Alarm condition).
Triggering only occursThe alarm can be triggered on time or for each alarm.- Only for the first alarm: The alarm is triggered one
time when the alarm condition first occurs. Possiblyreceived updates of the alarm condition are ignored.
- For every alarm: The alarm always triggers when thealarm condition is received.
Object value for acknowledging the alarmThe value set here is sent in the communication objectvia the Bus after acknowledgement on the Contouch andacknowledgement via the Bus is possible with this value.
Display lighting when an alarm occursThe parameter determines the behavior of the displaylighting when an alarm is triggered.- Switch on: The display lighting always switches on
(switches off after standard display turn-off time).- No change of state: The display lighting remains in
the current state (ON or OFF).
Alarm textThe alarm text is displayed on the operating and displaysystem when the alarm is triggered. The maximum textlength is 64 characters.
Alarm symbolThe alarm symbol is displayed on the operating anddisplay system when the alarm is triggered.
LED behavior in case of alarmThe parameter determines the behavior of the Status LEDon the operating and display systems when an alarm istriggered.
The LED color cannot be influenced. Depending on theset behavior, alarms are always displayed with a redilluminating LED.
Behaviour when an alarm occursThe parameter determines the acoustic behaviour of theoperating and display systems when an alarm istriggered.- Without alarm tone: No acoustic signal sounds when
the alarm is triggered.- One-time alarm tone: A one-time alarm tone sounds
when the alarm is triggered. The length of the alarmtone is set in the global parameter Automatic shut-offof the alarm tone after.
- Alarm tone repeats permanently: An alarm tonesounds for a defined time period when triggered. Thenthe alarm message is displayed silently to then besounded again acoustically. The length of the alarmtone and the repetition interval are set in the globalparameters Automatic shut-off of the alarm toneafter and Repetition of the alarm tone afterautomatic shut-off after.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 21 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
PriorityAlarms are sorted in the events list according to priority.The parameter specifies the priority of the alarm.
Up to 18 priorities can be defined. The value 1 indicatesthe highest priority, the value 18 the lowest.
Alarm text to be sentThe alarm text is sent through the communication objectwhen the alarm is triggered. The text length is 1 - 14characters. Input of an empty character string is notpossible.
3.6.8.2 Function-specific message parameter
Note:The further parameters to be set change depending onthe selected function. The parameters described in thefollowing apply for the Message function.
Symbol for value = “1”The symbol is shown on the operating and displaysystem when the communication object supplies theValue 1 for the message condition.
Symbol for value = “0”The symbol is shown on the operating and displaysystem when the communication object deliveries thevalue 0 for the condition of the message.
Text display for value = “1”The text is shown on the operating and display systemwhen the communication object supplies the Value 1 forthe message condition.
The maximum text length is 64 characters.- Example: "Window open"
Text display for value = “0”The text is shown on the operating and display system ifthe communication object delivers the value 0 for thecondition of the message.
The maximum text length is 64 characters.- Example: "Window closed"
Display on the operating and display systemThe operating pages for alarms and messages can becalled up by pressing separate buttons on the operatingand display system.
The buttons can be placed on any desired function pagesduring configuration (see Chapter 3.12, starting on page42).
Figure. 25. Buttons for alarms and messages(example)
1) Buttons for alarms2) Buttons for messages
Alarms can affect what is shown on the display and alsobe output by LED and signal tone. The behavior of theoperating and display system is specified by theparameters of each channel when an alarm occurs.
Note:The signals for the behavior of LED and signal tone areOR-linked. This means for example: If one alarm isconfigured with sound and a second alarm withoutsound and both alarms are active, then a signal tonesounds
1 2
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 97000
Technical Manual
Update: http://www.siemens.com/gamma
2.12.1.14
Display and acknowledgement of alarmsAlarms are automatically displayed when they occur. Anoverview of all active alarms is shown on the operatingpage.- After the button for alarms is pressed, the operating
page with the first alarm is displayed. If no alarm isactive, the operating page contains a correspondingsymbol (Figure. 26).
- The sequence of alarm displays corresponds to the setpriority. The alarm with the highest priority is displayedfirst.
- For alarms with equal priority, the time of occurrenceis decisive: the most recent message appears first.
- Alarms are not removed from the list until they havebeen acknowledged and deactivated.
Figure. 26. Operating page, when no alarm is active
Figure. 27. Operating page with active alarm(example)
1) Alarm symbol (configured)2) Time stamp for occurrence of the alarm3) Time stamp for occurrence of the alarm4) Alarm text (configured)5) Button for acknowledging the alarm
1 2 3
007
970007, page 22 / 101Infrastructure & Cities Sector, Building Technologies
ã Siemens AG 2017Subject to change without further notice P. O. Box 10 09 53, D
Display and acknowledgement of alarmsAlarms are automatically displayed when they occur. Anoverview of all active alarms is shown on the operating
alarms is pressed, the operatingpage with the first alarm is displayed. If no alarm isactive, the operating page contains a corresponding
sequence of alarm displays corresponds to the setpriority. The alarm with the highest priority is displayed
For alarms with equal priority, the time of occurrenceis decisive: the most recent message appears first.
list until they have
Operating page, when no alarm is active
Operating page with active alarm
Time stamp for occurrence of the alarm – dateTime stamp for occurrence of the alarm – time
Notes for acknowledging an alarm:- Pressing the confirm button acknowledges the alarm.- A communication object received via the KNX Bus can
also acknowledge an alarm.- After acknowledgement, the alarm goes into the
background; LED and signal tone are deactivated. Theconfirm button vanishes. (Observe: the parameter„alarm repetition after acknowledgement after“the acknowledgement symbol afttime).The next, non-acknowledged alarm is displayed.
- Alarms are not removed from the list until they havebeen acknowledged and deactivated.
Notes for deactivating an alarm:- An alarm can only be deactivated by a corresponding
bus telegram (Condition for alarm deactivation).- If an alarm is deactivated which has not yet been
acknowledged, then the LED and signal tone and shutoff for this alarm and the alarm continues to bedisplayed. It is assigned the deactivated status.
Display of messagesMessages are not automatically displayed. Display by LEDor signal tone is not possible.- After the button for messages is pressed, the operating
page with the first message is displayed.- The sequence of message displays corresponds to the
channel sequence.- Messages are not removed from the list since a valid
state is always present.- If the request of the object value fails before a
corresponding bus telegram arrives, then the messageis output for an undefined state. The message containsthe channel name as a headtext (Figure 29).
5
4
Siemens AGCities Sector, Building Technologies
Control Products and SystemsP. O. Box 10 09 53, D-93009 Regensburg
Notes for acknowledging an alarm:Pressing the confirm button acknowledges the alarm.A communication object received via the KNX Bus can
After acknowledgement, the alarm goes into thebackground; LED and signal tone are deactivated. Theconfirm button vanishes. (Observe: the parameteralarm repetition after acknowledgement after“ resets
the acknowledgement symbol after the configured
acknowledged alarm is displayed.Alarms are not removed from the list until they havebeen acknowledged and deactivated.
Notes for deactivating an alarm:An alarm can only be deactivated by a corresponding
telegram (Condition for alarm deactivation).If an alarm is deactivated which has not yet beenacknowledged, then the LED and signal tone and shutoff for this alarm and the alarm continues to bedisplayed. It is assigned the deactivated status.
Messages are not automatically displayed. Display by LED
After the button for messages is pressed, the operatingpage with the first message is displayed.The sequence of message displays corresponds to the
Messages are not removed from the list since a valid
If the request of the object value fails before acorresponding bus telegram arrives, then the messageis output for an undefined state. The message contains
hannel name as a headline and ? as the message
0705 Contouch Room Controller 97000
Siemens AGInfrastructure & Cities Sector, Building TechnologiesControl Products and SystemsP. O. Box 10 09 53, D-93009 Regensburg
Figure. 28. Message window (Example)
1) Symbol (configured)2) Time stamp for change of the object value3) Time stamp for change of the object value4) Channel name (configured)5) Message text (configured)
Figure. 29. Message for undefined state (example)
1) Channel name (configured)2) Message text always ?
1 2 3
1 2
Application program description
Contouch Room Controller 970007
970007, page 23 / 101Infrastructure & Cities Sector, Building Technologies
ã Siemens AG 2017 Update: http://www.siemens.com/gammaSubject to change without further notice
Message window (Example)
Time stamp for change of the object value – dateTime stamp for change of the object value – time
Message for undefined state (example)
3.7 Common parameters
Additional parameters are configured in theconfiguration window and organized thematically.
Settings for the display and operating system are definedunder Common. Different parameters can be displayed,depending on the configured settings.
Figure. 30. Common parameters window
1) Selection of topics2) Control elements for setting the parameters
3.7.1 Standby mode
The display shuts off when the operating and displaysystem is not operated for a longer period of time.
Standby mode is deactivated by:- touching the display,- pressing the rotary control.
Activate standby afterThe parameter specifies the time interval after which thedisplay switches to standby mode when it is notoperated.
At touch in standby jump toThe parameter specifies which page is shown in thedisplay after deactivation of the idle mode.
4
1
5
GAMMA instabus
Application program description
September 2017
Technical Manual
Update: http://www.siemens.com/gamma
2.12.1.14
Additional parameters are configured in the Parametersconfiguration window and organized thematically.
Settings for the display and operating system are defined. Different parameters can be displayed,
depending on the configured settings.
parameters window
Control elements for setting the parameters
The display shuts off when the operating and displaysystem is not operated for a longer period of time.
mode is deactivated by:
The parameter specifies the time interval after which themode when it is not
The parameter specifies which page is shown in thectivation of the idle mode.
2
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 97000
Technical Manual
Update: http://www.siemens.com/gamma
2.12.1.14
3.7.2 Pressing buttons
Pressing of buttons on the operating and display systemcan be emphasized acoustically in the form of short beeptones.
Touch SoundThe parameter specifies whether a signal tone should beoutput when a button is pressed. The type and durationof the signal tone cannot be set.
3.7.3 Cleaning mode
In cleaning mode, the usage of the touchscreen and therotary control is prevented for a specified time.deactivates the use of the press functioncontrol for operating the basic scenes.Cleaning modecannot be deactivated until this time has passed.
The Cleaning mode duration [s] specifies the durationof the cleaning mode.
Display on the operating and display systemThe button for cleaning mode activation can be placedon a function or operating page as well as in the functionlist.
Figure. 31. Cleaning mode button
Note:Alarm messages are displayed during cleaning mode.These, however, cannot be acknowledged by theContouch.
007
970007, page 24 / 101Infrastructure & Cities Sector, Building Technologies
ã Siemens AG 2017Subject to change without further notice P. O. Box 10 09 53, D
Pressing of buttons on the operating and display systemcan be emphasized acoustically in the form of short beep
The parameter specifies whether a signal tone should bepressed. The type and duration
In cleaning mode, the usage of the touchscreen and therotary control is prevented for a specified time. This alsodeactivates the use of the press function of the rotary
Cleaning modecannot be deactivated until this time has passed.
specifies the duration
Display on the operating and display systemaning mode activation can be placed
on a function or operating page as well as in the function
Alarm messages are displayed during cleaning mode.These, however, cannot be acknowledged by the
3.7.4 LED orientation light
The Contouch operating and display system contains anRGB-LED (multi-color LED) as an orientation light and fordisplay of alarms.
Figure. 32. LED orientation light on the device
1) RGB-LED
Color, brightness and saturation are configuredaccording to the HSV color model.
LED colourThe parameter specifies the LED color as orientation lightin the normal state.
Examples of parameter values:- 0 = Red- 42 = Yellow- 85 = Green- 128 = Turquoise- 170 = Blue- 213 = Violet
Note:The color red should not be used as the orientationcolor, since this color is only used to display alarms.
LED brightnessThe parameter specifies the brightness of the LED asorientation light in the normal state.
Examples of parameter values:- 0 = Off- 255 = 100%
Siemens AGCities Sector, Building Technologies
Control Products and SystemsP. O. Box 10 09 53, D-93009 Regensburg
orientation light
The Contouch operating and display system contains ancolor LED) as an orientation light and for
LED orientation light on the device
Color, brightness and saturation are configuredaccording to the HSV color model.
The parameter specifies the LED color as orientation light
Examples of parameter values:
The color red should not be used as the orientationcolor, since this color is only used to display alarms.
The parameter specifies the brightness of the LED aslight in the normal state.
Examples of parameter values:
1
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 25 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
LED saturationThe parameter specifies the saturation of the LED asorientation light in the normal state.
Examples of parameter values:- 0 = No saturation, white light- 255 = maximum saturation
3.7.5 Holding down a pushbutton
Certain functions of the operating and display system arecalled up when the operation holds down a buttonlonger than usual (e.g. storing of scenes).
The parameter Long touch time after determines theminimum amount of time the button needs to bepressed for this to be considered a long button press.
3.7.6 Query and sending of status objects
After the power is restored, the operating and displaysystem automatically queries the status objects of thefollowing bus devices:- External indoor temperature sensor,- Outdoor temperature sensor,- Time / date,- Selection of the basic scene (setting rotary control),- Basic setpoint value,- Window 1 to window 4,- Presence,- Status objects of the switching and dimming channels,- Status objects of the roller blinds – and shutter
channels,- Input objects of the message-type channels- Input objects of the message-type alarm- Room operating mode , query only if the parameter
“Room operating mode after power restoration“ is setto “automatic“ and the parameter “automatic modevia“ is set to “bus telegrams”. If no operating mode isreceived via status objects the operating mode“energy-saving mode” is set. If only the operatingmodes comfort-/protection-mode are parameterizedprotection mode is set.
Read delay for state objectsThe parameter specifies the time delay preceding thequery.
3.7.7 Time and date
The Contouch operating and display system requires thecorrect time and day of week for the time program andthe time stamp for alarms and messages.
The Contouch operating and display system is notequipped with its own real time clock, so that time anddate must each be provided by a communication objectof data type DPT_TimeOfDay (10.001) andDPT_Date (11.001).
If the weekday is not provided in data typeDPT_TimeOfDay, the DPT date is to calculate the day ofweek.
Note:The day of week or date must absolutely be placed inthe telegram. The time program and time stamp of thealarms remain locked until a time/date telegram isreceived.
If the external time sensor fails, the operating anddisplay system can independently compute the time andday of week further, however with limited precision.
Updating the time / changing the clocksThe time should be updated once a day.
Time displayThe parameter determines the format for the timedisplay. The indicators am (morning) or pm (afternoon)are added to the time display for the 12 h format.
Date displayThe parameter determines the format for the datedisplay. The following settings are possible: TT.MM.JJ orMM/DD/YY.
3.7.8 Temperature unit
The temperature unit parameter determines the unitsystem for the temperature display. The temperature canbe set to display °C or °F.
Note:Temperature values are only transmitted to the KNXBus in °C or K.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 26 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Send state objects after restartThe parameter determines whether and after whichdelay the following objects are sent after power isrestored:- Actual value of internal temperature sensor,- Actual value of indoor temperature, rated- Setpoint value shifting,- Setpoint temperature value,- Setpoint comfort mode,- Status objects for the operating mode,- Controller status (Eberle),- Controller status (RHCC),- Heating / Cooling actuating variables…,- Switch Heating / Cooling,- Fan mode.
3.7.9 Admin mode
The admin mode is for clearing of push button or displayarea (e.g. to make hidden operating pages achievable orrepress functions). The setting is set at projection ofmenu structure.
The admin mode can be activated by the followingmethods (dependant on parameterization):
· Permanently activated· On-site activation*· Clearing via bus telegram and on-site
activation*
* pushing longer than 5 s on the left lowerdisplay edge of home-site (see figure 33)
The activated admin mode displayed via a colored, broadedge over the whole display – if not permanentlyactivated (see figure 34).
Figure. 33. Activation area for the admin mode
1) red encircled area
Note:The red rectangle serves for displaying of the area forpushing. It is not displayed in operation.
Figure. 34. Activated admin mode
The communication object for the admin mode is for theclearance or locking of the admin mode on the contouch.This communication object is controlled via 2parameters. The parameter “admin mode alwaysactivated” activates the admin mode on the contouchpermanently. A locking via communication object is notpossible then. The display of the red egde is not appliedin this setting.
The parameter „admin mode activation“ defines, whetherthe activation of admin mode is possible via display orwhether is has to be cleared via a bus telegram at first.This function is meaningful e.g. in public buildings, sothat an activation of admin mode on the device cannotbe made illegal.
3.8 General alarms
The global parameters for alarms are set in the GeneralAlarms configuration window. The specifications sethere apply for all alarms.
Note:The channel-specific parameters for alarms are definedin the Channels configuration window of therespective channel (see Chapter 3.6.8, Page 20).
Automatic switching off of the alarm sound afterThis parameter sets the time after which the acousticsignal is switched off. Alarm tone sounds for this timeduration until the alarm is acknowledged.
1
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 27 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Repeat alarm after acknowledgement afterThis parameter sets the time, after which an alarm isnewly displayed after acknowledgement if it is stillactive.
Repeat the alarm tone after automatic switching-offafterThis parameter sets the time, after which the acousticsignal sounds again after automatic switch-off, if thealarm has not yet been acknowledged and the "Repeatalarm after acknowledgement after" takes effect.
This setting only works for alarms, for which the channel-specific parameter Behavior when an alarm occurs isset to Alarm tone repeats permanently.
3.9 Room temperature control
3.9.1 Functional overview
The room temperature control function contains severalfunction blocks which can be combined with each other.
The room temperature control can be set as:- heating only,- cooling only,- heating and cooling.
The room temperature can optionally be controlled usinga two-point controller, a constant PI controller or aconstant PI controller with sequence control.
The following functions are available:- Toggling between automatic/manual operation via the
display or communication object,- Switching the room operating mode via the display or
communication object,- Shifting the setpoint value using the rotary control or
the communication object,- Display and adjustment of the fan speeds,- Display of the active operating mode,- Display of an opened heating or cooling valve,- Display of a melting point alarm and open window.
The following partial functions are part of the roomtemperature control:- Room temperature measurement using the internal
temperature sensor,- Consideration of a room temperature measurement
made by an external temperature sensor,- Calculation of the current room temperature actual
value (internal and external room temperature sensorsweighted),
- Calculation of the current room temperature setpointvalue from the basic setpoint value, operating modeand setpoint value shifting,
- Extension of comfort mode by time-restricteddeactivation of the pre-comfort, energy-saving andprotection modes,
- PI-control for heating and cooling with constantvariable output (in %) or switching variable outputs(PWM).
Note:See Chap. 6.1, starting on page 52, for a description ofthe communication objects and parameters.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 28 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3.9.2 Parameter pages
The room temperature control is configured on severalparameter pages.
General room temperature controllerThe parameter page General room temperaturecontroller is the main page for the configuration of theroom temperature control. It is always visible.
The settings on this parameter page determine whichadditional parameters are visible.
VentilationThe parameter page is always visible.- The parameters for this are displayed in the setting
"Fan available" set to "Yes".
Temperatures, actual valueThe parameter page is always visible.
Controller operating modeThe parameter page is visible when:- Device function = controller + panel.
Operating mode of panelThe parameter page is visible when:- Device function = panel.
Heating, two-point controlThe parameter page is visible when:- Device function = controller + panel and
Controller mode = heating: two-point controlor- Device function = controller + panel and
Controller mode = Heating & Cooling: Two-pointcontrol
or- Device function = controller + panel and
Controller mode = Heating: two-point control,cooling = sequence control
or- Device function = controller + panel and
mode = Heating: Two-point control,Cooling = PI-Control.
Heating = PI controlThe parameter page is visible when:- Device function = controller + panel and- Controller mode= Heating: PI controlor- Device function = controller + panel and- Controller mode = Heating: PI control- ,
Cooling: Two-point controlor- Device function = controller + panel and
Controller mode = Heating: PI control-
Cooling = Sequence control.
Cooling, PI controlThe parameter page is visible when:- Device function = controller + panel and
Controller mode = Cooling: PI controlor- Device function = controller + panel and
Controller mode = Heating: Two-point control,Cooling: PI control
or- Device function = controller + panel and
Controller mode = Heating: Sequence control,Cooling = PI control.
Heating and cooling, PI controlThe parameter page is visible when:- Device function = controller + panel and
Controller mode = Heating & Cooling: PI control.
Heating, sequence controlThe parameter page is visible when:- Device function = controller + panel and
Controller mode = Heating: Sequence controlor- Device function = controller + panel and
Controller mode = Heating & Cooling: Sequencecontrol
or- Device function = controller + control panel and
Controller mode = Heating: Sequence control,Cooling = Two-point control
or- Device function = controller + panel and
Controller mode = Heating: Sequence control,Cooling = PI control.
Cooling, sequence controlThe parameter page is visible when:- Device function = controller + panel and
Controller mode = Cooling: Sequence controlor- Device function = controller + panel and
Controller mode = Heating & cooling: Sequencecontrol
or- Device function = controller + panel and
Controller mode = Heating: Two-point control,Cooling = Sequence control
or- Device function = controller + panel and
Controller mode= Heating: PI control- Cooling = Sequence control.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 29 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
3.9.3 Device function
The device function parameter specifies whether theoperating and display system should function as a pureoperating device or additionally take over controlfunctions.
The device function is set on the General roomtemperature controller parameter page.
Depending on the selection, additional parameter pagesare visible:- Controller + panel activate the additional parameter
page Controller operating mode.- Panel: activates the additional parameter page panel
mode.
3.9.4 Controller operating modes
The room temperature control system supports theheating, cooling and heating and cooling operatingmodes, each with different control systems.
The controller operating modes are selected on theoperating mode controller parameter page. Dependingon this selection, an additional parameter page appearsfor the specification of the controller mode (e.g.heating, PI control).
Two-point controlThe two-point controller checks the current temperaturesetpoint value in discrete time intervals (cycle time). Theheating / cooling are switched on or off depending onwhether the actual value lies above or below the setpointvalue.
The cycle time of the control and the hysteresis of thetwo-point controller are adjustable.
The two-point control is easy to configure and can beused for controls which permit a minimal fluctuation ofthe room temperature.
PI-ControlThe PI control constantly computes a variable from theinput quantities actual and setpoint value. This variablecan be transmitted via the KNX bus as a variable rangingfrom 0...100 % (Figure. 35) or as a pulse widthmodulated On/Off command (Figure 36) via the KNXBus.
Figure. 35. Constant output of the variable (1 Byte)
Figure. 36. Switching output of the variable (1 Bit)
The type of variable output, the proportional range andthe reset time are adjustable.
Sequence controlCan a room be heated (e.g. via floor heating and radiatorheating) or cooled in two different ways? Is sequencecontrol practical? The two heating/cooling sources arethen not parallel, but controlled in sequence.
An example for heating with floor heating and radiatorheating in one room:- If a room temperature is below the setpoint value, the
valve for the floor heating is opened first (sequence 1).- If the floor heating valve is 100% open and it is still not
warm enough, then the radiator valve will open(sequence 2).
- If the room is too warm, the radiator valve opens firstand then the floor heating valve closes.
EIN
100%
0%
AUS
Computedvariable
Switchingoutput
TT = Period length
100%
100%
0%
0%
Computedvariable
Variableoutput
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 30 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
The sequence control converts the internal variable fromthe constant PI control to two values (Sequence 1variable, Sequence 2 variable).
The value of the control variable, from which Sequence 2begins, can be set. The minimum variable change, forwhich the variable should be sent to the Bus, can also beseparately set for each sequence.
The variables are output as constant variable in the rangeof 0...100 % (1 Byte) (Figure. 37). The output as a pulsewidth modulated On/Off command (1 Bit) is not possible.
Figure. 37. Sequence control variables (1 Byte)
3.9.5 Actual value specification
The settings for the actual value specification are madeon the Temperatures, actual value parameter page.
Internal Temperature sensorAn internal temperature sensor is installed in theContouch operating and display system.
Figure. 38. Internal sensors on the operating anddisplay system
1) Temperature sensor
The internal temperature sensor measures the ambienttemperature of the device in the range of 0° C…+45° Cwith a resolution of 0.1 K. The value can be adapted toenvironmental influences (e.g. if mounted on an externalwall) by means of an offset.
The corrected value is used to specify the actual value.
The sensor value is updated every 10 s.
The sensor values are sent via a communication object.The sending interval can be set.
Behavior of the measured values outside of themeasurement range:- If T < 0° C the display shows LOW. The communication
object continues to send 0° C.- If T > 45° C the display shows HIGH. The
communication object continues to send 45° C.
100%
100%
0%
0%
VariableSequence 2
VariableSequence1
100%0% 50%
Internal variable
1
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 31 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
External indoor temperature sensorAn external indoor temperature sensor can be connectedto the Contouch operating and display system.
The sensor should send every temperature changeautomatically. If this is not the case, the control canquery the current value on the external indoortemperature sensor via an additional communicationobject.
After power restoration, the controller requests thecurrent value from the external indoor temperaturesensor independently.
Actual value computationThe device determines the current room temperatureactual value from:- the corrected value of the internal temperature sensor
(measured value + offset),- the value of the external indoor temperature sensor.
Note:If no values are provided for the following objects basicsetpoint value, external temperature and externalindoor temperature sensor, or no values can bequeried, then a configurable standard value is used.
A configurable weighting is determined to specify theproportion of the externally measured temperatureincluded in the computation of the temperature actualvalue.
The room temperature actual value can be read from itsown communication object or sent automatically orcyclically when a configurable value is changed (seeChapter 6.1.6, page 63).
3.9.6 Setpoint value specification
The settings for the setpoint value specification are madeon the General room temperature controllerparameter page.
The current setpoint value is determined from- the current room operating mode,- the basic setpoint value and- a setpoint value shift which must possibly be
considered.
The basic setpoint value can either be adapted by thecommunication object (basic setpoint value) or set to afixed value by a parameter.
When the basic setpoint value is specified via thecommunication object, the controller independentlyrequests the current value on the bus after restoration ofpower. When a new basic setpoint value is received viathe communication object, the setpoint value shifting isset to the value 0 K.
The setpoint value shifting can be adjusted either viacommunication object (setpoint value shifting) or via therotary control of the operating and display system withinthe parameterized boundaries. When a shifting ofsetpoint value below or above the parameterizedboundaries is received, this value is cut to the lower orupper boundary value.
The setpoint value offset is either input directly in °C / °For as a relative value in K. The relative value is internallyadopted in the setpoint value computation.
Display on the operating and display systemDepending on the configuration, the setpoint isdisplayed on the operating and display system in °C / °For as an offset from the basic setpoint value in K on theRoom temperature control operating page.
The user can change the setpoint value with the rotarycontrol on the operating and display system. The changebecomes active after a 3-second delay.
After a power return or after a download of theapplication program the setpoint value shifting is set tothe value 0 K.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 32 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3.9.7 Updating the setpoint value on the basis ofoutside temperature
The operating mode cooling offers the option ofupdating the setpoint value of the outside temperature.
The outside temperature is read via the objectTemperature, outside temperature. This object cansend read requests to the corresponding object of theexternal outside temperature sensor cyclically so that ittransmits the current value.
If the outside temperature is higher than 26 °C and morethan 6 K higher than the current setpoint temperature,then the target temperature is set to a value 6 K underthe outside temperature. In this case the setpoint valuecannot be shifted to a target temperature which wouldresult in a lower value than the target temperatureupdated by the outside temperature. Operating modesalso have no effect in this case (the mode is changed butthe target temperature continues to be determined bythe outside temperature). An exception is made whenthe setpoint value for frost protection or heat protectionis exceeded.
3.9.8 Room operating modes
The requirements for room temperature control can varydepending on the current usage of the room.
Several operating modes are available for this, which areeach assigned a different setpoint value.- Comfort mode,- Pre-comfort mode,- Energy-saving mode,- Protection mode.
The operating modes can be switched automatically(automatic mode) or manually (manual mode).
Figure. 39. Room operating modes and setpoint values
The settings for the room operating modes are made onthe General room temperature controller and Modecontroller or panel mode parameter pages.
3.9.8.1 Automatic / manual mode
Automatic modeIn automatic mode, the modes are either switched byexternal Bus telegrams (see Chapter 3.9.8.11, page 36)or internal time programs. Switching commands fromeach other control mode are ignored.
Automatic mode is displayed as such on the display.
The Automatic mode via is used to set which type ofautomatic mode should be active.
Manual modeManual mode offers the option of permanently settingthe room operating mode using the display on theoperating and display system.
The mode which is permanently activated in manualmode cannot be changed by external bus telegrams, theinternal time-switching program or by presencedetectors. The permanent protection mode cannot bechanged.
Automatic mode can be reactivated on-site by theContouch or via the corresponding communicationobjects.
The settings in manual mode are only possible if thedevice is not in permanent protection mode
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 33 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
3.9.8.2 Comfort modeComfort mode is used to set the room temperature to acomfortable level when people are present in the room.
The setpoint value is- directly adjusted either on the system rotary control by
the user or- computed from the basic setpoint value and the
adjusted setpoint value shift.
The setpoint value in comfort mode does not depend onwhether heating or cooling is active.
Presence detectorComfort mode can be activated by a presence detector.
The Presence detector object visible parameter is usedto define whether Presence communication objectshould be modified.
Messages sent via this communication object areevaluated for the activation of Comfort mode.
The following rules apply:- Comfort mode is switched on when a Presence = ON
telegram is received.- If a Presence = OFF telegram is received when
Presence = ON, the controller switches after 10 s tothe room operating mode which is activated by theinternal time program or by bus telegram.
- Opening a window during Presence = ON internallyactivates the protection mode.
- The presence detector telegrams are ignored inmanual mode.
Dead zoneA symmetrical dead zone between heating and cooling isdefined in the Heating & Cooling controller mode toensure that the heating valve and the cooling valve arenot open at the same time.
The size of the dead zone is specified by the parameterDead zone between heating and cooling.
The following rules apply:- The dead zone takes effect symmetrically around the
range of the target temperature.- The actual room temperature value T is queried
when power is restored, and heating or cooling isactivated depending on the result:T < Setpoint value: Heating;T ≥ Setpoint value: Cooling.
- The dead zone is only active in comfort mode.
3.9.8.3 Pre-comfort mode (standby)The pre-comfort mode serves to keep the roomtemperature at a specified standby value when no peopleare present and thus to save heating or cooling energy.
The setpoint value depends on whether heating orcooling is active.
The setpoint value is computed:- Heating: basic setpoint value – temperature reduction
for pre-comfort mode + setpoint value shift.- Cooling: basic setpoint value + temperature increase
for pre-comfort mode + setpoint value shift.
3.9.8.4 Energy-saving- mode (nighttime reduction)An additional adjustable value is provided for energy-saving mode, in which the room temperature can becontrolled during longer periods of absence (or in thenighttime hours).
The setpoint value depends on whether heating orcooling is active.
The setpoint value is computed:- Heating: basic setpoint value – temperature reduction
for energy-saving mode + setpoint value shift.- Cooling: basic setpoint value + temperature reduction
for energy-saving mode + setpoint value shift.
3.9.8.5 Protection mode (frost protection / heatprotection)
Protection mode is used to ensure that the roomtemperature does not exceed or drop below a criticalvalue.
These setpoint values can be set separately for heating orcooling.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 34 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3.9.8.6 Permanent protection modeThe room temperature control can be permanentlyswitched to protection mode during longer periods ofabsence (e.g. during holidays).
The parameter Permanent protection mode objectvisible specifies whether the permanent protectionmode object, which can be used to permanently switchthe controller to protection mode, should be modified.
The following rules apply:- If protection mode is activated by the permanent
protection mode communication object, it can also beswitched off by this communication object.
- Display inputs and telegrams from timers, presencedetectors and window contacts are ignored inpermanent protection mode.
- The symbol for permanent protection mode appearswhen the heating operating page is called up.Operation is not possible (Figure. 40).
- If the permanent protection mode is switched off bytelegram in automatic mode, then the controllerswitches to the room operating mode which isactivated at this time by the internal time program orby bus telegram.
- If the permanent protection mode is switched off bytelegram in manual mode, the controller switches toenergy-saving mode after deactivation of thepermanent protection mode (if this mode is notavailable, protection mode remains active).
Figure. 40. Heating operating page in permanentprotection mode
3.9.8.7 Evaluation of the window statesThe evaluation of the window conditions makes itpossible for the controller to react to the opening ofwindows or doors.
Four 1-bit communication objects (# 134 to #137), themessages of which are linked by a logical OR function,are provided for the evaluation of the windowconditions.
The following rules apply:- If at least one of the communication objects reports an
open window, the controller switches to internalprotection mode. This means that although the targetroom temperature value changes (for heating to thevalue for frost protection, for cooling to the value forheat protection), it is not reported to the bus.
- Changing the target room temperature value to thetarget frost protection value or target heat protectionvalue causes (reaction time can be configured) theheating or cooling valve to close (reaction time can beconfigured).
- If at least one of the communication objects reports anopen window, this is shown on the display as asymbol.
- Switching to a different mode when a window is open(e.g. by a bus telegram, an internal time program ordirectly on the Contouch), immediately activates thenew mode, but the setpoint value is not activated untilthe window is closed.
The reaction to open window parameter can be used toset a time delay for switching to internal protectionmode. This is of practical use if no reaction should occurfor every brief opening of a window.
The Invert window contact parameter can be used toset the signal value of the status report for eachindividual window contact:- No: 0 = closed; 1 = open.- Yes: 0 = open; 1 = closed.
3.9.8.8 Comfort extensionThe comfort extension can be used to control the roomat the comfort temperature for a certain time period ifthe room is used outside of the specified comfortoperating time (e.g. in the nighttime hours).
The user presses the comfort extension button on theroom temperature control start screen of the operatingand display system to activate the comfort extension(Figure. 41). The rotary control is then used to set thelength of the comfort extension.
An on-going comfort extension can be prematurelyended at any time by:- Setting the time of the comfort extension to 0 on the
rotary control,- Manually changing the room operating mode.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 35 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
The following rules apply:- If a presence detector is used for presence control,
(presence visible object = yes), then the comfortextension cannot be manually activated (button is thennot visible).
- The comfort extension can be activated from comfortmode, pre-comfort mode, energy-saving mode andprotection mode.
- The comfort extension cannot be activated frompermanent protection mode.
- The comfort extension can be set to a new value at anytime.
- The following applies in automatic mode via aninternal time program:After the comfort mode extension ends, the mode isswitched to the mode which is currently activeaccording to the internal time program.
- The following applies in automatic mode via bustelegrams:After the comfort mode extension ends, the mode isswitched to the mode most recently set by bustelegram.
- The following applies in manual mode:After the comfort mode extension ends, the mode isswitched to energy-saving mode. If this is notavailable, the mode is switched to protection mode.
- A set comfort extension is saved when a power lossoccurs and resumed following return of power.
3.9.8.9 Dew point modeThe controller switches to dew point mode if the dewpoint alarm (#133) communication object sends an ONsignal from a dew point monitor.
The cooling valve closes. It cannot be opened again untilthe controller has received an approval from the dewpoint alarm (value = OFF) communication object.
The dew point alarm is shown by a signal on the display.
If one switches to a different mode in dew point mode(e.g. by bus telegram or the internal time program), thenthe new mode will not become active until the dew pointmode ends.
3.9.8.10 Display on the operating and displaysystem
The room temperature control is shown on the operatingand display system in a multi-level menu structure.
The room temperature control buttons can be placed onthe home-page or on a function page. The roomtemperature control start screen, which on its part refersto operating pages, can be called up by this button.
Figure. 41. Room temperature control start screen
1) Button for mode-toggling operating page2) Temperature specification button (direct target value
setting in the comfort mode in this case)3) Comfort extension button (with display of the current
time remaining)4) "Window open" status symbol5) "Dew point alarm active" status symbol6) "Heating valve open" status symbol7) "Cooling valve open" status symbol
The user can switch manually between operating modesand change to automatic mode on the mode-togglingoperating page.
Note:The modes can only be selected manually when thedevice is not in permanent protection mode.
The number of visible buttons depends on theconfiguration (available modes, fans).
1 2 3
4567
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 36 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Figure. 42. Mode-toggling operating page
1) Mode-toggling button - automatic mode2) Comfort mode (present) button3) Pre-comfort mode (absent) button4) Energy-saving button (nighttime lowering)5) Protection mode button6) Fan level (automatic, 0, 1, 2, 3) button
3.9.8.11 Mode toggling via the busIn automatic mode, the mode can be toggled amongother ways by external bus telegrams.
All telegrams received for operating mode switchingbefore a power loss are deleted.
3.9.8.12 Control via 1-bit objectsFive 1-bit communication objects are provided forswitching the room operating modes (Chapter 6.1.15,objects # 124 to #128).
The following rules apply:- The communication object switching command ON of
the mode to be activated is sufficient for modetoggling.
- Mode-switching per telegram is immediately shown onthe display but not adopted by the controller until after3 seconds.
- All communication objects where the switching stateshave been changed by switching to the new roomoperating modes, are sent without delay.
- The communication object of the previous modeautomatically sends the switching command OFF.
In the case of 2-conductor systems with only one heatexchanger and one control valve, where either cold ofwarm water flow through the piping network, theheating/cooling (#130) communication objectadditionally serves to toggle the control between heatingand cooling mode.
3.9.8.13 Control via 1-byte objectsTwo 1-byte communication objects can also be used forswitching the room operating mode and for the statusdisplay (Chapter 6.1.15, Object # 140, #141).
The 8-bit object room operating mode / roomoperating mode status parameter must be set to Yesfor this.
The following applies for the 1-byte object of roomoperating mode:- An incoming 0 (automatic mode) deactivates manual
mode and activates automatic mode. The roomoperating mode is set to the last mode received via thebus.
- In automatic mode via an internal time program, onlythe 0 is evaluated. Other values are rejected. The roomoperating mode is set to the mode which is active inthe internal time program.
- Telegrams with other values besides 0,1,2,3,4, arerejected as errors.
- Telegrams with modes which are not available for thecontroller are rejected as errors.
Controller Status (Eberle)The controller status (according to the Eberle standard)can be transmitted by an additional 1-bytecommunication object (Chapter 6.1.15, Object # 142).
Both the room operating mode and the controller modeare provided by these objects when changes occur.
The 8-bit object controller status (Eberle) parametermust be set to Yes for this.
Controller Status (RHCC)The status of special controller types (RHCC) can betransmitted by an additional 2-byte communicationobject (Chapter 6.1.15, # 143).
The controller mode and various states are provided bythis object when changes occur.
In addition the 16-Bit Object Controller Status (RHCC)parameter must be set to Yes.
1 2 3
654
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 37 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
3.9.8.14 Switching off the controller via the busThe controller (#129) communication object can be usedto switch the controller on and off.
Switch off controller:- The variable is internally and externally set to OFF.- All operating modes are shown as inactive on the
display.- The actual temperature value continues to be defined.
Telegrams for temperature, frost alarm and heat alarmcontinue to be sent.
- The last active setpoint temperature value is stored.- The status is provided on the 1-bit and 1-byte
communication objects (bits for operating modes = 0).
Switch controller back on:- In automatic mode via bus telegrams, the controller
sets itself to the last room operating mode selected bybus telegram.
- In automatic mode via an internal time program, theroom operating mode is switched to the mode which isactive according to the internal time program at thecurrent time.
- In manual mode, the mode is switched to protectionmode.
3.9.9 Ventilation
The ventilation parameter page is used to configure afan. The parameter page is not displayed unless the fanavailable parameter is set to Yes.
SettingsThe following is specified on the parameter page:- the number of fan speeds and the speed for each
individual fan speed.- the release of the fan for manual mode,- the behavior when switching over and then switching
on again,- the display type on the device,- the value for sending the fan mode via the bus.
Automatic fan modeThe fan switches to automatic mode when one of thefollowing conditions occur:- Change in room operating mode by bus telegram or
the internal time program,- Manual change of the room operating mode at fan
speed 0,- Activation of the room operating mode protection
mode.
Note:With two-point control, there is no automatic activationof the fan speeds. The fan speeds are set manually inthis case.
Manual fan modeThe manual fan mode must be released via the fanmanually operable parameter.
Manually switching to fan speed 0 turns off the fan. Anopen heating or cooling valve closes.
This means that the room can neither be cooled norheated. If, as a result of this, the setpoint value forheating protection is exceeded or the value for frostprotection fallen short of, the controller reacts indifferent ways, depending on the selected mode.
With constant controller:- The fan switches to automatic fan mode.- The controller heats or cools until the frost or heat
protection setpoint value is reached.- The fan also remains in automatic mode after these
setpoint values are achieved.
With two-point control:- The fan switches to the next highest fan speed.- The controller heats or cools until the frost or heat
protection setpoint value is reached.- After reaching the setpoint value the fan switches to
fan speed 1. The fan speed can now be switchedmanually.
Note:A manual change in the fan speed does not take effectuntil the target temperature is reached. The fan thenswitches to the set value.
Automatic activation of the fan speedsThe fan can take on up to 3 fan speeds.
With automation activation, the fan speeds are linked tofixed valve settings of the heating or cooling valve(Figure. 43). With pulse width modulated PI control, therelative time of the open valve setting is used.
Fanspeed
Number of configured fan speeds
1 2 3OFF 0 % 0 % 0 %1 0,5 – 100 % 0,5 – 50 % 0,5 – 33 %2 0 50,5 – 100 % 33,5 – 67 %3 0 67,5 – 100 %
Figure. 43. Activation of the fan speeds depending ontheir number and the setting of theheating valve.
The fan speed in levels parameter can be used to setthe fan speed for each separate fan level.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 38 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Note:It is practical to assign the fan speed for the fan levels inascending order (Level 1 = lowest speed, Level 3 =highest speed).If this is not the case, then the lower level is retainedwhen the mode is automatically switched to automaticmode.
Since some fans do not start up properly which switchedon at fan level 1, the parameter If fan = OFF, start-up inlevel can be used to set a different fan level for the start-up.
Note:The active level is shut off for 0.5 seconds beforeswitching to a new fan level since two fan levels cannotbe switched on simultaneously.It is recommended that the operating and displaysystem and the fan switching actuator be connected tothe same bus line so that this timing of the switchingactuator can be maintained.
Display on the operating and display systemIf the fan control is activated in the fan availableparameter, then the fan button is shown on the display.
Figure. 44. Button for fan control (here, the fan is inautomatic mode)
The fan button can be used to switch the fan toautomatic mode, set the fan to a certain fan level or toswitch it off:1. Select fan button.2. Set fan mode / fan level with the rotary control and
press the rotary knob.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 39 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
3.10 Time programs
The time planner can be used to set time programs forthe controller modes and for individual channels.
The following rules apply for the time programs:- A program can be defined by day of week for
temperature control and every single channel.- A maximum of 16 switching points can be defined for
each program.- After a power loss, the current operating condition is
adopted for the controller mode, even if the lastswitching point lies in the past.
- After a power loss, a past switching point is notexecuted again for the channels.
- The Temperature control time program is activated bythe automatic heating mode.
Figure. 45. Operational range of the time program
1) Time program for controller mode2) Create new line3) Week planner area4) Interval display (time range)5) Interval selection
6) Interval editor7) Delete time program8) Time program for channels
8
3 51 4 6
7
2
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 40 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3.10.1 Time program for temperature control
The time program for temperature control is created andadapted in the controller mode (Figure. 45).
Create time program1. Click on the <new> button in the week planner area.Ø A new line with a pre-set distribution of the
room operating modes appears.
Adapt time program1. Click on the fields in the week planner area of the
weekdays on which the time program is to be active.Ø The selected weekdays are marked by a green
checkmark.
Note:It is not possible to select the same weekday formultiple time programs for temperature control.
2. Select interval.The interval can either be selected directly by mouseclick or in the Interval selection area.Ø The current setting of the selected interval are
displayed in the interval editor area.
Figure. 46. Interval editor (time program fortemperature control)
1) Input of time interval beginning2) Input of time interval end3) Selection of room operating mode4) Divide time interval5) Delete time interval
3. Select room operating mode.4. Input start and end of the interval (only possible
when multiple intervals exist).
Note:The shortest interval is 15 min.Intervals can only be changed in 15-minute steps. Thestart time must precede the end time.
Recreate interval (divide)If a new interval is to be created, a pre-existing intervalmust be divided for this purpose.
1. Select interval to be divided.2. Click on the divide button.Ø The interval is divided into two intervals of the
same size.3. Adapt both intervals to meet the requirements.
Delete intervalA marked interval can be deleted with the delete button.
Since a time program always requires values defined forthe entire day, the following rules apply for deletion:- Deleting a time interval automatically extends the
subsequent interval by this time.- Deleting a day's last time interval automatically
extends the preceding time interval until the end time23:59.
3.10.2 Time program of channels
Every single channel can be separately controlled by atime program. This allows, for example, the light to beswitched on and off several times a day.
Note:See Chapter 3.6, starting on page 12 for the definitionof channels.
The time program for channels is created and adapted inthe Channel area (Figure. 45).
Note:When the time program is used for the channel typedimmer then the dimmer is dimmed via a 1 bytedimming value. Therefore the dimming actuator has tobe parameterized in a specific kind, so that switchingthe dimmer on or off via a 1-bit switching object is notnecessary. The delivered 1 byte dimming value isdimming the channel on the set dimming value.
21
3
4
5
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 41 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Create time program
Figure. 47. Interval editor (time program forchannels)
1) Input of time interval beginning2) Input of time interval end3) The channel value to be sent (dependent on channel)4) Deactivate time interval (only for channels)5) Divide time interval6) Delete time interval
1. Click on the <new> button in the week planner area.Ø An empty line is added.
2. Select channel in the name selection field.3. Select interval.4. Select value in the value selection field.Ø The time program is created with an interval of
00:00 to 23:59.5. Click on the fields in the week planner area of the
weekdays on which the time program is to be active.Ø The selected weekdays are marked by a green
checkmark.
Note:It is not possible to select the same weekday formultiple time programs of one channel.Different channels can be assigned to the sameweekdays.
The interval can be divided and adapted for sendingadditional values to the channel.
Divide and adapt interval1. Select interval to be divided.2. Click on the divide button.Ø The interval is divided into two intervals of the
same size.3. Select value in the value field.4. Define the beginning and end of each interval.
Note:The shortest interval is 15 min.Intervals can only be changed in 15-minute steps. Thestart time must precede the end time.
Deactivate intervalThe first interval can be deactivated.1. Place a checkmark in the no action selection field.Ø The channel cannot be called up in the marked
interval.
Delete intervalA marked interval can be deleted with the delete button.
Since a time program always requires values defined forthe entire day, the following rules apply for deletion:- Deleting a time interval automatically extends the
subsequent interval by this time.- Deleting a day's last time interval automatically
extends the preceding time interval up to the end time23:59:59.
3.10.3 Delete time program
1. Click on the button to delete the time program.Ø The time program is deleted immediately
without a repeated request.
21
3
5
6
4
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 42 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3.11 Skins
Predefined skins are provided for the buttonarrangement.
The skin is used for the entire menu structure.
Note:The skins require storage spaces of various sizes.
The configuration data must be transferred to theoperating and display system by MicroSD card.
Figure. 48. Skins selection with preview window
3.12 Menu structure
The menu structure for the display on the operating anddisplay system is defined in this menu.
3.12.1 Surface concept of the control panel
The display and operation using the touchscreen issubdivided into pages. The pages can be configuredindividually.
The following switching modes are available:- Home-page- Function pages,- Operating pages.
The selection of the configurable pages depends on theavailable storage space of the operating and displaysystem. Configurations with multiple languages orextensive designs, for example, required more storagespace.
Home-pageThe home-page is the top page in the menu structure.
On the home-page,- functions can be called directly,- jumps can be made to other function pages,- jumps can be made to operating pages of functions,- and data displayed.
Figure. 49. Example of a home-page
1) Button area (max. 6 buttons)2) Navigation area (here with temperature and time
display)
The left and middle field of the navigation area can beconfigured.
1
2
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 43 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
For displaying data:- Time,- Date,- Outside temperature- Indoor temperature (current temperature value of
internal and external sensors),- Effective setpoint temperature,- Heating mode,- Current fan speed.
As button:- Language change,- Cleaning function,- Heating mode,- Comfort extension,- Navigation elements (forwards, back, level, start
screen, alarm indications)
Function pagesOn a function page:- functions can be called directly,- jumps can be made to the home-page or to additional
function pages,- jumps can be made to operating pages of functions,- and data displayed.
Multiple function pages can be configured.
Figure. 50. Example of a function page
1) Button area (max. 6 buttons)2) Navigation area
Operating pagesOperating pages serve to control individual functions.They are preconfigured. When a function is added to thehome-page or to a function page, the operating pageassociated with the function is automatically added tothe menu structure.
The button area is designed in different ways dependingon the function.
Manual modification of the operating pages is notpossible.
On an operating page:- Values can be selected and functions run,- Jumps can be made to addition operating pages, to the
associated function pages or to the home-page,
Figure. 51. Example of an operating page
1) Display of the function (channel name)2) Switching area (dependent on function)3) Navigation area
1
2
1
3
2
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 44 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3.12.2 Work area and configuration window
The menu structure is defined using a graphic editor.Various templates are predefined for each page. Thestandard layout consists of six function buttons and threenavigational buttons.
Figure. 52. Operational area of the menu structure
1) Page administration (main levels)2) Page administration (subordinate levels)3) Configuration of the selected page (allocation of the functions)
4) Available functions5) Preview window6) Symbol library7) Activation of admin-mode
Page administration (Main levels)Function pages can be created and deleted in the mainlevels window. Their sequence can also be changedthere.
The home-page is also displayed in this window. Itcannot be deleted or moved.
The home-page and the function pages can be renamedin the context menu of the right mouse button.
AllocationThe page selected in the main levels window can beconfigured in the allocation window.During creation of a new page, an empty templateappears which can be filled with functions and symbolsper Drag&Drop (see Section 3.12.3 on page 45).
The text assigned to the functions is adopted from thefunction description or the channel designation. It can beadapted in the languages window.
The symbols and the associated functions can be deletedin the context menu of the right mouse button.
1 3 4
56
2
7
0705 Contouch Room Controller 97000
Siemens AGInfrastructure & Cities Sector, Building TechnologiesControl Products and SystemsP. O. Box 10 09 53, D-93009 Regensburg
FeaturesAll available functions and displays are listed in thefunctions window:- functions configured by the user (e.g.: switching,
shutter, scenes),- permanently programmed functions and displays
under the item other (e.g. navigation elements, date).
A control element must be assigned to every function.These can be:- simple buttons,- buttons with status displays (e.g. progress bars, rotary
controls) or- buttons which refer to other function pages or
operating pages.
Standard symbols are assigned to certain functioThese symbols can be exchanged for other symbols fromthe symbols window.
Forced control:Jump to operating page
Sun blind:Jump to operating page
Roller shutter:Jump to operating page
Send value – fixed:Activation
Send value – variable:Jump to operating page
Cleaning mode:Activation
Change language:Switching
Figure. 53. Standard symbols for functions
PreviewThe preview window shows how the current settings aredisplayed on the operating and display system.
SymbolsThe symbols window provides a thematically arrangednumber of symbols for displaying the functions.
The thematic arrangement of the symbolssuggestion. Since no function has yet been assigned tothe symbols in the symbols window, they can be freelyused. The symbols are assigned to the functions in theallocation window.
Symbols cannot be added to or deleted from thesymbols window.
Application program description
Contouch Room Controller 970007
970007, page 45 / 101Infrastructure & Cities Sector, Building Technologies
ã Siemens AG 2017 Update: http://www.siemens.com/gammaSubject to change without further notice
All available functions and displays are listed in the
functions configured by the user (e.g.: switching,
permanently programmed functions and displays(e.g. navigation elements, date).
ement must be assigned to every function.
buttons with status displays (e.g. progress bars, rotary
buttons which refer to other function pages or
Standard symbols are assigned to certain functions.These symbols can be exchanged for other symbols from
Standard symbols for functions
window shows how the current settings aredisplayed on the operating and display system.
window provides a thematically arrangednumber of symbols for displaying the functions.
symbols is asuggestion. Since no function has yet been assigned to
window, they can be freelybols are assigned to the functions in the
Symbols cannot be added to or deleted from the
Other levelsFunction pages can be created and deleted in the otherlevels window. Their sequence can also be changedthere.
3.12.3 Create function page
This section describes how a function page is created andconfigured in the main level.
Note:Since the method is the same, the configuration of thehome-page is not described separately.
1. Press the add button in theØ The add level dialog window appears.
2. Select the template for the page layout in theselection template.
3. Enter the name of the function page in the text field“New page name”.
4. Click on the add button.Ø The new function page
the list in the main level
The sequence of the function pages can be changedusing the upwards and downwards
The buttons can now be consecutively assigned to thedesired functions in the allocation window:5. Grab the function from the
the mouse, drag it with the pressed mouse button tothe button in the Allocationmouse button there (Drag&Drop).Ø The switch field is assigned to the function.
Note:If a switch field is already occupied, then the oldfunctions are written over when a new assignment ismade.
Continue configuration manuallyFor certain functions (e.g. roller blinds, send value) allrequired information is transferred with the assignment.For other functions the configuration of the buttonsmust be continued manually.
GAMMA instabus
Application program description
September 2017
Technical Manual
Update: http://www.siemens.com/gamma
2.12.1.14
Function pages can be created and deleted in the otherlevels window. Their sequence can also be changed
function page
This section describes how a function page is created and
Since the method is the same, the configuration of thepage is not described separately.
button in the main level window.dialog window appears.
Select the template for the page layout in the
Enter the name of the function page in the text field
new function page is added to the end ofmain level window.
The sequence of the function pages can be changeddownwards buttons.
The buttons can now be consecutively assigned to thedesired functions in the allocation window:
Grab the function from the Functions window withthe mouse, drag it with the pressed mouse button to
Allocation window and release themouse button there (Drag&Drop).
The switch field is assigned to the function.
is already occupied, then the oldfunctions are written over when a new assignment is
Continue configuration manuallyFor certain functions (e.g. roller blinds, send value) allrequired information is transferred with the assignment.
functions the configuration of the buttons
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 46 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Figure. 54. Examples of warnings during buttonconfiguration
1) Button completely configured2) Symbol is missing3) Symbol is missing and function not completely defined
If a symbol is missing:1. Drag a suitable symbol from the symbols window
via Drag&Drop.Ø If the function is incomplete a selection field
with the available functions (e.g. listing of thejump targets for the “Go to Layer” function)appears on the button in the allocationwindow.
2. Select function in the selection field.
Note:If a warning is displayed even though the button iscompletely configured, then the function parametersare either incomplete or contain errors. In this case thefunction parameter setting should be checked.
.
1
3
2
0705 Contouch Room Controller 97000
Siemens AGInfrastructure & Cities Sector, Building TechnologiesControl Products and SystemsP. O. Box 10 09 53, D-93009 Regensburg
4 Transfer of the configuration dataConfiguration data cannot be transferred to the deviceunless the parameters and menu structure are complete.Therefore the configuration is continuously checkedduring input for:- Existence of all texts in all languages,- The accessibility of all functions (incl. scenes and alarm
functions).
Note:The generation will possibly be cancelled if a warningmessage or error exists.
4.1.1 Configuration data for MicroSD card
1. Connect MicroSD card to the PC2. Click on the generate button in the menu and
symbol bar.Ø A check is made for errors or warning messages.Ø Configuration data which cannot be transmitted
via the KNX bus are generated and stored onthe SD card as rcconfig.bin.
Ø The project Firmware file is stored on the SDcard as rc.bin.
Ø If a file with the name RC-Programmingcard.info is located in the root directory of aremovable data carrier, then it is interpreted asContouch MicroSD. Otherwise:
3. Select the removable data carrier.
Note:Pre-existing data are written over without furtherinquiry.If an attempt to write to the SD card fails or is cancelled,the data will be written to the local TEMP directory. Thispath will be shown.
4. Insert the MicroSD card into the Contouch; execute abus download if required and restart the Contouch(see Chapter 2.2, page 4 and chapter
Note:To avoid irreparable errors it is not allowedthe SD-card during boot-up time!
Errors or warningsIf warning messages or errors are found, they are listedin a dialog. The generation of the configuration data canbe continued despite errors or cancelled.- Generate: The configuration data are generated and
transferred to the MicroSD card.- Cancel: No configuration data is generated. A new tab
generation errors appears in the menu and symbolbar (see Chapter 4.1.3, page 47).
Application program description
Contouch Room Controller 970007
970007, page 47 / 101Infrastructure & Cities Sector, Building Technologies
ã Siemens AG 2017 Update: http://www.siemens.com/gammaSubject to change without further notice
Transfer of the configuration dataConfiguration data cannot be transferred to the deviceunless the parameters and menu structure are complete.
the configuration is continuously checked
The accessibility of all functions (incl. scenes and alarm
The generation will possibly be cancelled if a warning
Configuration data for MicroSD card
button in the menu and
A check is made for errors or warning messages.Configuration data which cannot be transmitted
and stored on
The project Firmware file is stored on the SD
Programming-is located in the root directory of a
removable data carrier, then it is interpreted as
existing data are written over without further
card fails or is cancelled,the data will be written to the local TEMP directory. This
Insert the MicroSD card into the Contouch; execute abus download if required and restart the Contouch
and chapter 3.2.3. page 9).
To avoid irreparable errors it is not allowed to remove
messages or errors are found, they are listedin a dialog. The generation of the configuration data canbe continued despite errors or cancelled.
: The configuration data are generated and
ata is generated. A new tabappears in the menu and symbol
4.1.2 Parameters in ETS
1. Click the OK button.Ø All configuration data are stored in the ETS
database.Ø Communication objects will possibly be faded in
and out and the designations adapted accordingto the channel designations.
Ø Create group address configuration (seeChapter 3.3.1, Page 9
Ø Plug-In is closed.2. In ETS click on Edità Program
and application programØ A note appears with the request:
programming button...3. Use a sharp object to press the programming button
in the BCU (see Chapter 2.2The physical address is transmitted.
Note:Certain parameters require an update of BCU andContouch. For this reason the BCU must first beprogrammed by ETS before the update can occur viathe MicroSD card.If the update via the MicroSD card occurs before theBCU is programmed, then the copying pcancelled and the Contouch displays an error message.
4.1.3 Generation errors
The Generation errors tab only appears if theconfiguration data has been generated with errors. A listof all the errors is stored here so that threctified in sequence.
Figure. 55. Window generation errors (example)
GAMMA instabus
Application program description
September 2017
Technical Manual
Update: http://www.siemens.com/gamma
2.12.1.14
All configuration data are stored in the ETS
Communication objects will possibly be faded inand out and the designations adapted accordingto the channel designations.Create group address configuration (see
9).
ProgramàPhysical addressand application program.
A note appears with the request: Please pressprogramming button...
Use a sharp object to press the programming button2.2, page 4).
The physical address is transmitted.
Certain parameters require an update of BCU andContouch. For this reason the BCU must first beprogrammed by ETS before the update can occur via
If the update via the MicroSD card occurs before theBCU is programmed, then the copying procedure iscancelled and the Contouch displays an error message.
tab only appears if theconfiguration data has been generated with errors. A listof all the errors is stored here so that they can be
Window generation errors (example)
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 48 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
5 Contouch Manager as separate tool
This section describes configuration settings using the"Contouch Manager" tool. This tool is started separatelyand runs independently of the ETS application program.
This independent PC-based tool provides the user withthe option of independently making different settingsand changes to the configuration. The ETS applicationprogram is not needed for this.
The configuration can be saved in a project file(*.Contouch) and imported for processing andadaptation.
The MicroSD card is used for transmitting the adaptedconfiguration to the Contouch, also see Section 2.3, 3and 4.
Figure. 56. Data transmission
The following configurations can be implementedsolely with the Contouch Manager:
- Definition of the languages- Settings of certain parameters, general alarms- Setting of time programs- Design selection- Determination of the menu structure
A symbol in front of this parameter name displays thetransmission path permitted for this parameter, seeSection 3.2.3.
Figure. 57. Labeling of the parameter types
1) Transmission required only via KNX Bus (ETS)2) Transmission via KNX Bus and MicroSD card required3) Transmission only required via MicroSD card
For changing the configuration exclusively with theContouch Manager, only the parameters whichare preceded by the symbol 3 are suited.
Starting the Contouch Manager
To run the "Contouch Manager",start the file: Contouch Manager_6.0.0.2282.msion your PC.
An installation routine is then started.
Figure. 58. Ending the installation routine
After ending the installation, start theContouch Manager in your Windows program bar:
The Contouch Manager appears in its usualdisplay, identical to the Contouch Manager (Plug-In)within the ETS, see Section 3.Identical menus and tabs are offered.
Contouch(Plug-In)
Installation
Contouch
Export/Import
rcconfig.binGenerate
MicroSD/SDHC-card
Insert
1 2 3
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 49 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Figure. 59. Work area of the Contouch Manager as a separate tool
1 Menu bar2 Tab
5.1 The menu bar
5.1.1 Menu: Save
The configuration data is saved in the project file(*.Contouch).
1. Click the Save button in the menu bar.Ø Any pre-existing project file will be overwritten
by saving.
5.1.2 Menu: Save as
1. Click the Save as button in the menu bar.Ø The file selection window opens.
2. Enter file name. File type:*.Contouch.3. Click the Save button.
The project file is saved.
The relocation of the project file is accompanied by adata backup of the Contouch configuration.
5.1.3 Menu: Open
The configuration data saved in a project file(*.Contouch) can be imported as follows.
1. Click the Open button in the menu bar.Ø The file selection window opens.
2. Search for and select the Contouch file.3. Click the Open button.Ø The project file is imported.
5.1.4 Menu: Language
1. Click the Language button in the menu bar.Ø Switching between the different, pre-
configured languages.
The various functions which have already been set up aredisplayed under the "Channels" tab and in the menustructure in the language selected.
1 2
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 50 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
5.1.5 Menu: Show warnings
Incorrect or missing configuration settings, particularlyfor the functions or the menu structure, are signalled bywarning symbols. The warning display can be disabled.
1. Click on the check-box to activate Display warningsin the menu bar.Ø All missing configuration settings will be
displayed by warning symbols.
5.1.6 Menu: Extras
1. Click the Extras - About button in the menu bar.Ø The software version is displayed:
Figure. 60. Display software-version
Ø Link to the Internet site: "Gamma BuildingSystem Technologies".
Ø The OSS licenses for software used can beaccessed.
-
5.1.7 Menu: Generate
1. Press the Generate button in the menu bar.Ø After configuration is ended, all configuration
data which cannot be transmitted by the KNXbus is generated in the rcconfig.bin, seeSection 4.
2. Selection of the drive:Ø The configuration file is saved on the SD card,
see Section 4.
Figure. 61. Selection removable medium
5.2 The Tabs
5.2.1 Tab: Languages
1. Click the Language tab within the menu bar.Ø The target languages for user guidance on the
Contouch operating and display device aredefined, see Section 3.5.
Note:The contents of the texts to be displayed are notautomatically determined by the language setting. Theymust be entered when defining the channels andstructures.
Missing entries are labeled in the application programwith a warning sign.
Note:The addition or deletion of languages is fully possiblewith the separate Contouch Manager tool and can becarried out independently of the ETS.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 51 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
5.2.2 Tab: Channels
1. Click the Channels tab beneath the menu bar.Ø The channels used are defined in this menu and
functions are assigned to them, see Section 3.6.
Note:The assigned functions and parameter settings aretransmitted to Contouch with the download using theETS and the rcconfig.bin configuration file with theMicroSD card. It is not possible to change thesesettings with the Contouch Manager tool!
5.2.3 Tab: Parameters
1. Click the Parameters tab beneath the menu bar.Ø Choose Alarms, common selection.Global parameters for alarms are defined in theCommon alarms configuration window. Theconfigurations made here apply for all alarms, seeSection 3.8.
Note:All additional parameter settings, Common, Commonroom-temperature controller, Fans, Actualtemperature value, Controller mode, Heating, andCooling are transmitted to Contouch exclusively with adownload by ETS or additionally by the transport of thercconfig.bin configuration file with the MicroSD card.It is not possible to change these parameters withthe Contouch Manager tool!
5.2.4 Tab: Scheduler
The time planner can be used to create time programsfor the controller modes and for the individualchannels/functions, see Section 3.10.
1. Click the Scheduler tab beneath the menu bar.Ø Selection of Controller mode for the creation or
adjustment of the time programs fortemperature control, see Section 3.10.1.
orØ Selection of channel for the creation or
adjustment of the time programs for theindividual functions, which were created underthe Channels tab, see Section 3.10.2.
Note:The creation, adjustment or deletion of time-switchcommands is fully possible with the separate ContouchManager tool and can be carried out independently ofthe ETS.
5.2.5 Tab: Skins
Four predefined designs are provided for the Contouchdisplay and user interface and its button arrangement.The design is applied to the entire menu structure, seeSection 3.11.
1. Click the Skins tab beneath the menu bar.Ø Selection of the Classic designorØ Selection of the Elegant designorØ Selection of the Magic designorØ Selection of the Modern design
Note:The setting of the various designs is fully possible withthe separate Contouch Manager tool and can be carriedout independently of the ETS.
5.2.6 Tab: Menu structure
This tab is used to define the menu structure, the pagesetup, the allocation of functions and the navigation. Thestructure of the levels is also defined. The functions oneach of the pages are assigned a symbol, see Section3.12.
1. Click the Menu structure tab beneath the menu bar.2. Selection of Home page or Add new pages.3. Place functions from the functions window on the
corresponding page.4. Apply or adapt the function labelling or navigation
buttons in each language.5. Assignment of the symbols to the functions of each
page.
Note:The projection of the menu structure is fully possiblewith the separate Contouch Manager tool and can becarried out independently of the ETS.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 52 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
6 Parameters and communication objectsThis chapter provides an overview of the availablecommunication objects and parameters.
The parameter settings determine which communicationobjects are visible and to which group addresses they canbe linked.
6.1 Common parameters
Figure. 62. Parameter view: Common
6.1.1 Parameter display and operation
Parameter SettingsActivate standby after 10 s
30 s1 min2 min5 min10 min
Setting of the display time of the Contouch-Display.The display switches off automatically if is hasn’t beenused within the time set here.
Transmission: ETS
Parameter page: Common
Parameter SettingsAt touch in standby jumpto
homelast page used
Display of the Contouch-Display after standby time.Touching the display or operating the rotary control inthe standby state shows the page set here.
Transmission: ETS
Parameter page: Common
Parameter SettingsTouch sound no
yes
Touching the display to trigger commands and functionsis signaled acoustically (short beep) or not signaled.
Transmission: ETS
Parameter page: Common
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 53 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Parameter SettingsCleaning mode duration [s] 5…255
Default value: 60
Defining the duration of the cleaning function
Transmission: ETS
Parameter page: Common
Parameter SettingsSetting scene number X:1..64 (sent out with statusvalue: 0)
1…64Default value: 1
Setting of scene number X. This basic scene X isaccessed in the "Basic scene select" object when thestatus value 0 is received.The basic scene numbers X and Y can also be configuredwith the same scene number.
Transmission: ETS
Parameter page: Common
Parameter SettingsSetting scene number Y:1..64 (sent out with statusvalue: 1)
1…64Default value: 2
Setting of scene number Y. This basic scene Y is accessedin the "Basic scene select" object when the status value 1is received.The basic scene numbers X and Y can also be configuredwith the same scene number.
Transmission: ETS
Parameter page: Common
Parameter SettingsLED colour 0…255
Examples of settings:
0:42:85:128:170:213:
RedYellowGreenTurquoiseBlueViolet
Defining the LED color as orientation light
Transmission: ETS
Parameter page: Common
Parameter SettingsLED brightness 0…255
Examples of settings:
0:25:255:
OffPre-set value100% An
Defining the LED brightness as orientation light
Transmission: ETS
Parameter page: Common
Parameter SettingsLED saturation 0…255
Examples of settings:
0:254:255:
No saturation, white lightPre-set valueMaximum saturation,complete colors
Defining the LED saturation as orientation light
Transmission: ETS
Parameter page: General
Parameter SettingsLong touch time after 2 s
3 s5 s10 s
Defining the time period, after which a prolonged keyactivation is evaluated as holding down the key. Holdingdown the key is required, for example, to store scenes.
Transmission: ETS
Parameter page: Common
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 54 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Parameter SettingsRead delay for stateobjects
0 s10 s20 s30 s1 min2 min3 min4 min5 min
Setting the delay time, after which the following statusobjects are queried when the power is restored.- External indoor temperature sensor (#118),- Outdoor temperature sensor (#116),- Time (#111),- Date (#112),- Basic scene select (#115),- Basic setpoint value (#120),- Window 1 to window 4 (#134, #135, #136, # 137),- Presence (#138),- Room operating mode (#140),- Room operating modes (#123… # 127),- Status objects of the switching and dimming channels,- Status objects of the roller shutter and sun blind
channels,- Status objects of the message and alarm channels
Transmission: ETS
Parameter page: Common
Parameter SettingsTime display 24 h
12 h
Specification of the time display format.With the 12 h format the indicator am (morning) or pm(afternoon) is added to the time display.
Transmission: ETS
Parameter page: Common
Parameter SettingsDate display TT.MM.JJ
MM/DD/YY
Definition of the date display format.
Transmission: ETS
Parameter page: Common
Parameter SettingsTemperature unit °C
°F
Definition of the unit system for the temperature display
Transmission: ETS
Parameter page: Common
Parameter SettingsSend state objects afterrestart
nodelayed by 10 sdelayed by 15 sdelayed by 18 s
Settings defining whether and with which the delay timethe following status objects are sent when the power isrestored.- #113: Brightness, actual value- #117: Temperature, actual value of internal sensor,- #119: Temperature, actual indoor value, weighted,- #121: Setpoint value shifting,- #110: Setpoint comfort mode,- #122: Temperature, setpoint value,- #123 to #127: Status objects of the mode (only the
objects of the active mode are sent here)- #130: Heating / cooling,- #141: State room operation mode- #142: Controller status (Eberle)- #143: Controller status (RHCC)- #144 to #153: Heating / cooling actuating variables- #154: Fan mode
Transmission: ETS
Parameter page: Common
Parameter SettingsAdmin mode always active no
yes
This parameter activates admin mode permanently. Incondition „yes“ an external activation control viacommunication object is not possible.
Transmission: ETS
Parameter page: Common
Parameter SettingsAdmin mode activation allow
allow after enabling viacommunication object
This parameter controls the activation of admin mode.The additional clearing via a communication object ismeaningful, e.g. in public buildings.
Transmission: ETS
Parameter page: Common
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 55 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Parameter SettingsLeave admin mode after never
1 min2 min5 min10 min20 min
This parameter sets the time for automatic turn-off ofadmin-mode.
Transmission: ETS
Parameter page: Common
6.1.2 Parameter objects for display and operation
Obj. Object name Function Type Flags111 Time / day of
weekReceive 3 Byte
DPT_TimeOfDayCWTU
This communication object can be used to receive timeand weekday data from an external sensor via the KNXbus.The communication object sends a read request whenpower is restored.
112 Date Receive 3 ByteDPT_Date
CWTU
This communication object can be used to receive thedate from an external sensor via the KNX bus.The communication object sends a read request whenpower is restored.
Obj. Object name Function Type Flags108 GUI-Id Receive 2 Byte
DPT_3.47CWTU
This communication object can be used to change thedisplayed language via the bus. Therefore an ASCII Code(i.e. country code DE = Germany with codec 6465h, FR =France with codec 656Eh) is received. The received ASCIICode has to correlate with the languages, set in theplugin.
Obj. Object name Function Type Flags197 Admin
modeReceiveallowenable
1 bit CWU
This communication object makes the admin modeactivatable. The final activation is achieved via display.Value „1“ clears the on-site activation of admin mode,value “0” locks it.The received value is saved persistently. Therefore is itavailable after bus voltage recovery.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 56 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
6.1.3 Common alarm parameters
Figure. 63. Parameter view: Common alarms
Parameter SettingsMute alarm sound after 10 s / 30 s /
1 min /2 min / 3 min / 4 min /5 min / 6 min / 10 min /15 min / 20 min / 25 min /30 min
Setting the length of the acoustic signal tone when thealarm is not acknowledged.
Transmission: sdCard
Parameter page: Alarms, common
Parameter SettingsRepeat alarm afteracknowledge after
never /1 min /2 min / 3 min / 4 min /5 min / 6 min / 10 min /15 min / 20 min / 25 min /30 min / 60 min / 120 min
Setting the time period after which an alarm is displayedagain after acknowledgement, if it is still set to active bythe alarm input communication object.
Transmission: sdCard
Parameter page: Alarms, common
Parameter SettingsRepeat alarm sound aftermute after
10 s / 30 s / 1 min 2 min /3 min / 4 min /5 min /6 min / 10 min / 15 min /20 min / 25 min / 30 min
Setting the time period after which the acoustic signalsounds again after it was switched off automatically. Thealarm tone is only repeated if the alarm has not beenacknowledged.The alarm repetition only works for alarms, for which thechannel-specific parameter Behavior when an alarmoccurs is set to Alarm tone repeats permanently.
Transmission: sdCard
Parameter page: Alarms, common
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 57 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
6.1.4 Common room temperature control parameters
Figure. 64. Common room temperature controller
Parameter SettingsDevice function controller + panel
panel
Setting the device function.The setting controls the visibility of the parameter pagesmode controller + panel and panel mode and alsothat of the specific parameter pages for heating andcooling.
Transmission: ETS and sdCard
Parameter page: Room temperature control common
Parameter SettingsEnable Object ‘Presence’ no
yes
Specification of whether the presence communicationobject should be modified. Messages sent via thiscommunication object are evaluated for the activation ofComfort mode.
Transmission: ETS und sdCard
Parameter page: Room temperature control common
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 58 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Parameter SettingsEnable object‘Permanent protectionmode’
noyes
Specification of whether the permanent protectionmode communication object should be modified.The Yes setting permanently switches the controller tothe room operating mode protection mode via thecommunication object.
Transmission: ETS and sdCard
Parameter page: Room temperature control common
Parameter SettingsEnable manual roomoperation mode change
noyes
Defines whether the user can change the roomtemperature controller mode (in manual mode).
Transmission: ETS
Parameter page: Room temperature control common
Parameter SettingsEnable manual setpointshift
noyes
Defines whether the user can change the setpoint valuevia the rotary control.
Transmission: ETS
Parameter page: Room temperature control common
Parameter SettingsRoom operation modeafter restart
as before voltage failurecomfort modepre-comfort modeenergy saving modeprotection modeautomatic mode
Specification of the room operating mode to beautomatically activated after power is restored.The controller is switched in manual mode for comfortmode, pre-comfort mode, energy-saving mode andprotection mode.
Transmission: ETS
Parameter page: Room temperature control common
Parameter SettingsEnable 8-Bit objects for‘room operation mode’
noyes
Specification of whether the room operating mode androom operating mode status communication objectsshould be modified.The values transmitted with these objects are used to setthe room operating mode or to report the current roomoperating mode.
Transmission: ETS and sdCard
Parameter page: Room temperature control common
Parameter SettingsDisplay of setpoint shift temperature
setpoint shift
Definition of how the setpoint value adjustment shouldbe displayed.- Temperature: Display of the setpoint temperature in
°C or °F- Offset: Display of the setpoint value offset in K
Transmission: ETS
Parameter page: Room temperature control commonThe parameter is only visible when:release setpoint value adjustment = Yes
Parameter SettingsShifting range of setpoint ± 2.0 K
± 3.0 K± 4.0 K± 5.0 K
Setting of the value range (in Kelvin) for the offset of thebasic setpoint value to a higher or lower temperature.When a shifting of setpoint value below or above theparameterized boundaries is received, this value is cut tothe lower or upper boundary value.
Transmission: ETS
Parameter page: Room temperature control commonThe parameter is only visible when:release setpoint value adjustment = Yes
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 59 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Parameter SettingsStrategy Heating / Cooling via internal room
temperature controllervia central control
With the setting „via the internal room temperaturecontroller“ the controller calculates the strategy heatingor cooling and sends this status via object 130 to thebus.With the setting „via central control“ the strategy heatingor cooling is preset for the controller via object 164(Appendix: 2-pipe-system, BMS delivers the strategy).Appropriate to this setting only heating or cooling ispossible.
Transmission: ETS and sdCard
Parameter page: Room temperature control commonThe parameter is only visible when:Device function = controller + panel
Parameter SettingsEnable 8-Bit controllerstate object (Eberle)
noyes
Specification of whether the controller state (Eberle)communication object should be modified.This object is used to send the controller status and theroom operating mode status. This object can also beused to query the status.- Bit 0: 1 = comfort mode On- Bit 1: 1 = pre-comfort mode On- Bit 2: 1 = energy-saving mode On- Bit 3: 1 = protection mode On- Bit 4: 1 = dew point alarm On- Bit 5: 1 = heating mode- Bit 5: 0 = cooling mode- Bit 6: 1 = controller Off- Bit 6: 0 = controller On- Bit 7: 1 = frost alarm / heating alarm
Transmission: ETS and sdCard
Parameter page: Room temperature control common
Parameter SettingsEnable 16-bit controllerstate object (RHCC)
noyes
Specification to define whether the communicationobject Controller state (RHCC) should be modified.This object is used to send the controller status and theroom operating mode status. This object can also beused to query the status.- Bit 8: 0 = cooling mode- Bit 8: 1 = heating mode,- Bit 12: 1 = dew point alarm On- Bit 13: 1 = frost alarm On- Bit 14: 1 = heat alarm OnThe bits: 0, 1, 2, 3, 4, 5, 6, 7, 9, 10, 11 and 15 arepermanently set toValue = 0.Note:Behavior as described in the KNX-Manual, DPT 22.101
Transmission: ETS and sdCard
Parameter page: Room temperature control common
Parameter SettingsMaximum duration ofcomfort extension
inactive / 15 min / 30 min /45 min / 60 min / 90 min /120 min / 180 min /210 min / 240 min
Definition of the maximum time period of the comfort -extension which can be set by the user on the device(value range).- Inactive: Comfort extension is not possible. The
function is not available on the device- 15...240 minutes: The function is available on the
device The length of the comfort extension can be seton the display at 15-minute intervals within the setvalue range.
Transmission: ETS and sdCard
Parameter page: Room temperature control commonThe parameter is only visible when:Presence object visible = No.
Parameter SettingsEnable object ‘Statecomfort extension’
noyes
Specification of whether the comfort extension statuscommunication object should be modified.
Transmission: ETS and sdCard
Parameter page: Room temperature control commonThe parameter is only visible when:Presence object visible = No andmaximum time of comfort extension ≠ inactive
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 60 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Parameter SettingsTarget temperature [°C] 16 … 26
Default value: 21
Setting the basic setpoint value for comfort mode. Thevalue set here can be changed using the basic setpointvalue communication object.When the basic setpoint value is adjusted via thecommunication object, then the shifting of setpointvalue is set to the value 0 K.
Transmission: ETS
Parameter page: Room temperature control common
Parameter SettingsReaction on open windows directly
15 s30 s60 s
Setting the time delay for a reaction after evaluation ofthe window state.The window open status causes the target roomtemperature value, depending on the setting, to switcheither immediately or after the set time delay to the frostprotection value in heating mode or to the heatprotection value in cooling mode and also causes theprotection mode to become internally activated (nomessage to the bus or switching of the mode on thedisplay).Setting a delay time prevents immediately switching tointernal protection mode every time a window is brieflyopened.
Transmission: ETS
Parameter page: Room temperature control common
Parameter SettingsInvert window contact 1 no
yes
Specifies whether the signal from window contact #1 isinverted.- No: 0 = closed, 1 = open- Yes: 1 = closed, 0 = open
Transmission: ETS
Parameter page: Room temperature control common
Parameter SettingsInvert window contact 2 no
yes
Specifies whether the signal from window contact #2 isinverted.- No: 0 = closed, 1 = open- Yes: 1 = closed, 0 = open
Transmission: ETS
Parameter page: Room temperature control common
Parameter SettingsInvert window contact 3 no
yes
Specifies whether the signal from window contact #3 isinverted.- No: 0 = closed, 1 = open- Yes: 1 = closed, 0 = open
Transmission: ETS
Parameter page: Room temperature control common
Parameter SettingsInvert window contact 4 no
yes
Specifies whether the signal from window contact #4 isinverted.- No: 0 = closed, 1 = open- Yes: 1 = closed, 0 = open
Transmission: ETS
Parameter page: Room temperature control common
Parameter SettingsAutomatic mode via internal scheduler
bus telegrams
Specification of the control for switching the roomoperating modes in automatic mode.The switching commands from each other control areignored.
Transmission: ETS
Parameter page: Room temperature control common
Parameter SettingsEnable object ‘Basesetpoint’
noyes
Specification of whether the base setpointcommunication object should be visible.
Transmission: ETS and sdCard
Parameter page: Room temperature control common
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 61 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
6.1.5 Fan parameters
Figure. 65. Parameter view: Fan
Parameter SettingsFan available no
yes
Specifies whether a fan is connected.
Transmission: ETS and sdCard
Parameter page: Fan
Parameter SettingsNumber of fan levels 1
23
Sets the number of adjustable fan speeds.The fan speed in levels parameter window is displayedin accordance with the number defined here.
Transmission: ETS and sdCard
Parameter page: FanThe parameter is only visible when:Fan available = Yes
Parameter SettingsFan speed for level 1 [%] 1…100 %
Default value: 33
Fan speed setting (relative to the maximum speed)At a setting of 100%, the value 255 is sent via the bus.
Transmission: ETS
Parameter page: FanThe parameter is only visible when:Fan available = Yes
Parameter SettingsFan speed for level 2 [%] 1…100 %
Default value: 67
Fan speed setting (relative to the maximum speed)At a setting of 100%, the value 255 is sent via the bus.
Transmission: ETS
Parameter page: FanThe parameter is only visible when:Fan available = Yes andNumber of fan speeds ≥ 2
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 62 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Parameter SettingsFan speed for level 3 [%] 1…100 %
Default value: 100
Fan speed setting (relative to the maximum speed)At a setting of 100%, the value 255 is sent via the bus.
Transmission: ETS
Parameter page: FanThe parameter is only visible when:Fan available = Yes andNumber of fan speeds = 3
Parameter SettingsEnable manual fan control no
yes
Release of the manual adjustment of the fan speed onthe device. If released, the fan speed can be switchedmanually to automatic, OFF, 1, 2 or 3 on the operatingand display system.
Transmission: ETS
Parameter page: FanThe parameter is only visible when:Fan available = Yes
Parameter SettingsIf fan off, start at level 1
23
Setting the fan speed at which a previously deactivatedfan should briefly (for 1 s) start up so than it starts upsecurely when switched on at level 1. A delay of 0.5 s isalways maintained when switching from one fan speedto another.
Transmission: ETS
Parameter page: FanThe parameter is only visible when:Fan available = Yes
Parameter SettingsCalculate fan level displayby revolution speed
noyes
Specification of how the values for displaying the currentfan level should be determined.- Yes: Computation of the current fan level from the
values received via the fan speed status object.- No: Direct display of the fan level status objects 1 [2,
3].
Transmission: ETS
Parameter page: FanThe parameter is only visible when:Fan available = Yes
Parameter SettingsInvert fan operation modevalue
noyes
Specifies whether the fan mode value is to be invertedwhen sent or received.- No: 1 = automatic mode, 0 = manual mode- Yes: 1 = manual mode, 0 = automatic mode
Transmission: ETS
Parameter page: FanThe parameter is only visible when:Fan available = Yes
Parameter SettingsHolding time for fan level inactive
1 min2 min5 min
Setting the minimum residence time at the set fan levelin the case of automatic switching by the controller bymeans of the valve setting.The holding time prevents valve setting changes withinthe areas around the fan level switching thresholds fromconstantly changing the fan speed.
Transmission: ETS
Parameter page: FanThe parameter is only visible when:Fan available = Yes
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 63 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
6.1.6 Parameter: Temperatures, current value
Figure. 66. Parameter view: Temperatures, current value
Parameter SettingsInternal indoortemperature sensor, offsetto value
+ 10 K…+0.1 Kno offset−0.1 K…−10 K
Specification of the correction value for the temperaturevalue measured by the internal sensor.
Transmission: ETS
Parameter page: Temperatures, current value
Parameter SettingsExternal indoortemperature sensor,available
noyes
Setting to define whether the room temperature shouldbe additionally measured at another location in theroom.- No: No additional indoor temperature sensors
connected.- Yes: The communication objects Temperature, actual
value of indoor external sensor and Temperature,actual indoor value, weighted are modified.
Transmission: ETS and sdCard
Parameter page: Temperatures, current value
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 64 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Parameter SettingsSend temperature value atchange by
0.1 K…5.0 Kinactive
Defines the value by which the actual value must havechanged to be resent automatically.The object is internally updated every 10 s
Transmission: ETS
Parameter page: Temperatures, current value
Parameter SettingsCycle time to sendtemperature value
5 min…10 min…120 mininactive
Sets the time interval for resending of the actualtemperature value (in addition to automatic sendingwhen changes occur).
Transmission: ETS
Parameter page: Temperatures, current value
Parameter SettingsHysteresis for temperaturevalue
± 0.1 K± 0.3 K± 0.5 K± 0.7 K
Determination of the value range of the hysteresis forthe actual temperature value.Hysteresis prevents minor temperature fluctuations fromconstantly sending new actual values.
Transmission: ETS
Parameter page: Temperatures, current value
Parameter SettingsExternal indoor temperaturesensor, read cycle time
5 min…120 mininactive
Sets the time interval for a new query of the additionalindoor temperature measurement.
Transmission: ETS
Parameter page: Temperatures, current valueThe parameter is only visible when:External indoor temperature sensor = Yes
Parameter SettingsExternal indoortemperature sensor, offsetto value
+ 10 K…+0.1 Kno offset−0.1 K…−10 K
Specification of the correction value for the temperaturevalue measured by the external sensor.
Transmission: ETS
Parameter page: Temperatures, current valueThe parameter is only visible when:External indoor temperature sensor = Yes
Parameter SettingsWeighting indoortemperature sensors,external / built-in
only external sensor90 % / 10 %80 % / 20 %70 % / 30 %60 % / 40 %50 % / 50 %40 % / 60 %30 % / 70 %20 % / 80 %10 % / 90 %only internal sensor
Defines at which ratio (weighting) the measured valuesof the external and internal sensors should be used tocompute the current actual value.- Value 1: external sensor,- Value 2: internal sensor.
Transmission: ETS
Parameter page: Temperatures, current valueThe parameter is only visible when:External indoor temperature sensor = Yes
Parameter SettingsExternal indoortemperature sensor,default value [°C]
0…40Default value: 18
Specification of the default value of the externallymeasured indoor temperature to be used if no value isreceived by the corresponding communication object.
Transmission: ETS
Parameter page: Temperatures, current valueThe parameter is only visible when:External indoor temperature sensor = Yes
Parameter SettingsOutdoor temperature, readcycle time
5 min…10 min…120 mininactive
Setting of the time interval for querying the outsidetemperature sensor.
Transmission: ETS
Parameter page: Temperatures, current value
Parameter SettingsOutdoor temperaturesensor, offset to value
+ 10 K…+0.1 Kno offset−0.1 K…−10 K
Specification of the correction value for the temperaturevalue measured by the outside temperature sensor.
Transmission: ETS
Parameter page: Temperatures, current value
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 65 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Parameter SettingsOutside temperaturesensor, default value [°C]
0…40Default value: 18
Specification of the default value of the outsidetemperature to be used if no value is received by thecorresponding communication object.
Transmission: ETS
Parameter page: Temperatures, current value
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 66 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
6.1.7 Parameter Controller/ Panel mode
Note:The prerequisite for this parameter page to be visible is:- Device function parameter = controller + panel (see Section 6.1.4, on page 57).
Figure. 67. Parameter view: Controller operating mode
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 67 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Parameter SettingsOperationMode
heating two-point control
heating PI-Control
heating sequence control
cooling two-point control
cooling PI control
cooling sequence control
heating & cooling two-point control
heating & cooling PI control
heating & cooling sequence control
heating two-point control,cooling PI control
heating PI-control,cooling two-point control
heating PI-control,cooling sequence control
heating sequence control,cooling PI-Control
heating two-point control,cooling sequence control
heating sequence control,cooling two-point control
Determining the modes
Transmission: ETS and sdCard
Parameter page: Operation mode “controller”The parameter is only visible when:Device function = controller + panel
Parameter SettingsDead band betweenheating and cooling
± 0.25 K± 0.5 K± 0.75 K± 1.0 K± 1.5 K± 2.0 K± 2.5 K± 3.0 K
Sets the dead zone between heating and coolingThe dead zone is only effective in comfort mode.
Transmission: ETS
Parameter page: Operation mode “controller”The parameter is only visible when:- Mode = heating and coolingParameter page: Operating mode of control panelThe parameter is only visible when:- Execute setpoint value computation = Yes
Parameter SettingsRoomoperationmodes
comfort/protection mode
comfort/energy-saving/ protectionmode
comfort/pre-comfort /energy-saving/protection mode
Setting the room operating modes for room temperaturecontrol
Transmission: ETS and sdCard
Parameter page: Operation mode “controller”Parameter page: Operation mode “panel”
Parameter SettingsCooling, increasetemperature for pre-comfort mode
1 K2 K3 K4 K5 K
Setting the temperature value by which the setpointvalue of the room temperature should be raised whencomfort mode is switched to pre-comfort mode incooling mode.
Transmission: ETS
Parameter page: Operation mode “controller”The parameter is only visible when:- Mode = cooling or mode = heating and cooling and- Room operating modes = comfort/pre-comfort
/energy-saving/ protection modeParameter page: Operation mode “panel”The parameter is only visible when:- Execute setpoint value computation = Yes
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 68 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Parameter SettingsHeating, decreasetemperature for pre-comfort mode
1 K2 K3 K4 K5 K6 K
Setting the temperature value by which the setpointvalue of the room temperature should be lowered whencomfort mode is switched to pre-comfort mode inheating mode.
Transmission: ETS
Parameter page: Operation mode “controller”The parameter is only visible when:- Mode = heating or mode = heating and cooling and- Room operating modes = Comfort-/Pre-Comfort-
/Energy-saving-/Protection mode or Room operatingmodes = Comfort-/Energy-saving-/Protection mode
Parameter page: Operation mode “panel”The parameter is only visible when:- Execute setpoint value computation = Yes
Parameter SettingsHeating, decreasetemperature for energysaving mode
1 K2 K3 K4 K5 K
Setting the temperature value by which the setpointvalue of the room temperature should be lowered whencomfort mode is switched to energy saving mode inheating mode.
Transmission: ETS
Parameter page: Operation mode “controller”The parameter is only visible when:- Mode = heating or mode = heating and cooling and- Room operating modes = comfort/pre-comfort
/energy-saving/ protection modeParameter page: Operation mode “panel”The parameter is only visible when:- Execute setpoint value computation = Yes
Parameter SettingsCooling, increasetemperature for energysaving mode
1 K2 K3 K4 K5 K6 K
Setting of the temperature value by which the setpointvalue of the room temperature should be raised asopposed to comfort mode when the mode is switched toenergy-saving mode.
Transmission: ETS
Parameter page: Operation mode “controller”The parameter is only visible when:- Mode = cooling or mode = heating and cooling and- Room operating modes = Comfort/Pre-
comfort/Energy-saving/Protection mode or Roomoperating modes = Comfort/Energy-saving/Protection mode
Parameter page: Operation mode “panel”The parameter is only visible when:- Execute setpoint value computation = Yes
Parameter SettingsCooling, adjust targettemperature depending onoutdoor temperature
noyes
Setting to define whether the setpoint temperatureshould track the outside temperature in cooling mode.If Yes is selected:The setpoint temperature value updated in accordancewith the outside temperature if the outside temperatureis above 26 °C and 6 K above the currently set targettemperature. The setpoint temperature in this case is 6 Kbelow the outside temperature.- The setpoint temperature for cooling is set to the
value of the heat protection cooling setpointparameter if the updated setpoint temperature > thevalue of the heat protection cooling setpointparameter.
- The cooling valve closes completely when the dewpoint alarm parameter = active.
Transmission: ETS
Parameter page: Operation mode “controller”The parameter is only visible when:- Mode = cooling or mode = heating and cooling
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 69 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Parameter SettingsSetpoint for frostprotection
5 °C…10 °CDefault value: 7 °C
Specification of the setpoint value for the frostprotection mode.The frost protection mode (internal only) is activated, forexample, if the window open status is received and thecontroller is in heating mode.
Transmission: ETS
Parameter page: Operation mode “controller”The parameter is only visible when:- Mode = heating or mode = heating and coolingParameter page: Operation mode “panel”The parameter is only visible when:- Execute setpoint value computation = Yes
Parameter SettingsSetpoint for heat protection 30 °C…40 °C
Default value: 35 °C
Specification of the setpoint value for the Heatprotection mode.The frost protection mode (internal only) is activated, forexample, if the window open status is received and thecontroller is in cooling mode.
Transmission: ETS
Parameter page: Operation mode “controller”The parameter is only visible when:- Mode = cooling or mode = heating and coolingParameter page: Operation mode “panel”The parameter is only visible when:- Execute setpoint value computation = Yes
Parameter SettingsFrost alarm, threshold non
0 °C…5,0 °CDefault value: 5,0 °C
Specification of the temperature value limit, after whichthe controller reports a frost alarm.
Transmission: ETS
Parameter page: Operation mode “controller”Parameter page: Operation mode “panel”
Parameter SettingsFrost alarm, cycle time forsending
5 min…120 minInactiveDefault value: 10 min
Setting the time interval for resending of the frost alarm(in addition to automatic sending when changes occur).Cyclical sending only occurs when an alarm condition ispresent.
Transmission: ETS
Parameter page: Operation mode “controller”Parameter page: Operation mode “panel”
Parameter SettingsHeat alarm threshold non
30 °C…45 °CDefault value: 40 °C
Specification of the temperature value limit, after whichthe controller reports a heat alarm.
Transmission: ETS
Parameter page: Operation mode “controller”Parameter page: Operation mode “panel”
Parameter SettingsHeat alarm, cycle time forsending
5 min…120 minInactiveDefault value: 10 min
Setting the time interval for resending of the heat alarm(in addition to automatic sending when changes occur).Cyclical sending only occurs when an alarm condition ispresent.
Transmission: ETS
Parameter page: Operation mode “controller”Parameter page: Operation mode “panel”
Parameter SettingsCalculate setpoint no
yes
Specification as to whether the room temperaturecontroller should execute its own setpoint valuecomputation.- No: The room temperature controller is operated as a
pure operating station.- Yes: The room temperature controller is operated as a
control panel, but executes its own setpoint valuecomputation. Corresponding objects and parametersare blended in.
Transmission: ETS and sdCard
Parameter page: Operation mode “panel”The parameter is only visible when:Device function = panel
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 70 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
6.1.8 Heating parameter, two-point control
Note:The prerequisites for this parameter page to be visible are:- Device function parameter = controller + panel (see Section 6.1.4, on page 57).- Parameter Mode = Heating: Two-point control (see Section 6.1.7, on page 66).
Figure. 68. Parameter view: Heating, two-point control
Parameter SettingsHeating, hysteresis ± 0.1 K…± 2.5 K
Default value: ± 0.5 K
Setting the switching hysteresis of the two-pointcontroller for heating mode.Although the precision of the room temperature setpointvalue increases as the hysteresis becomes smaller, theswitching frequency of the controller increases.
Transmission: ETS
Parameter page: Heating, two-point control
Parameter SettingsDouble hysteresis forenergy saving andprotection mode
noyes
Setting the double switching hysteresis in energy-savingor frost protection mode.This allows room temperature fluctuations in energy-saving or frost-protection mode to be twice as large,thus reducing the switching frequency of the valves andpreserving them.
Transmission: ETS
Parameter page: Heating, two-point control
Parameter SettingsDirection of actuatingvariable
normalinverted
Setting to define the form in which the variable shouldbe output.- Normal: Output of the variable in accordance with the
computed variable.- Inverted: Output of the variable reverses the desired
effect of the variable.With this parameter, the setting depends on the type ofvalve (whether opened or closed when there is nocurrent) or actuator used.
Transmission: ETS
Parameter page: Heating, two-point control
Parameter SettingsHeating, cycle time for twopoint control
0.5 min…15 minDefault value: 5 min
Setting the time interval for reactivation of the two-pointcontroller.The setting causes the two-point control, for example, tooccur only every 5 minutes. Hysteresis and cycle timeinfluence the degree to which the room temperature candeviate from its setpoint value.
Transmission: ETS
Parameter page: Heating, two-point control
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 71 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
6.1.9 Heating parameter, PI control
Note:The prerequisites for this parameter page to be visible are:- Device function parameter = controller + panel (see Section 6.1.4, on page 57).- Parameter Mode = Heating: PI-Control (see Section 6.1.7, on page 66).
Figure. 69. Parameter view: Heating = PI control
Parameter SettingsHeating, output type ofactuating variable
continuous (8 bit)switching (1 bit)
Setting of the output type of the variable- Continuous: the output variable corresponds to the
computed variable with a resolution of 8 bits.- Switching: The variable is output as a pulse width
modulated switching command, whereby the dutyfactor between ON and OFF corresponds to thecomputed variable.
Transmission: ETS and sdCard
Parameter pages: Heating = PI controlHeating and cooling, PI control
Parameter SettingsHeating, direction ofactuating variable
normalinverted
Setting to define the form in which the variable shouldbe output.- Normal: Output of the variable in accordance with the
computed variable.- Inverted: Output of the variable reverses the desired
effect of the variable.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for heating = switching
(1 Bit)- Type of variable output for heating and cooling =
switching (1 Bit) to joint object
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 72 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Parameter SettingsHeating, cycle duration atpulse width modulation
1 min…30 minDefault value: 10 min
Setting the period length for the pulse width modulationof the switching variable output in heating mode.The variable corresponds to the duty factor (time ratio)between "ON (1)" and "OFF (0)" within one period.CAUTION: During thermo-drive, please note that theperiod length cannot be shorter than the sum of theheating and cooling times of the thermo-drive.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for heating = switching
(1 Bit)- Type of variable output for heating and cooling =
switching (1 Bit) to joint object
Parameter SettingsHeating, always on from 40 %...100 % of actuating
variableDefault value: 90 %
Setting of the minimum percentage value of the variablerequired for the variable to always be ON.The valve characteristics can be adapted through this toreduce the switching frequency.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for heating = switching
(1 Bit)- Type of variable output for heating and cooling =
switching (1 Bit) to joint object
Parameter SettingsHeating, always off to 1 %...50 % of actuating
variableDefault value: 10 %
Setting of the maximum percentage value of the variableat which the variable is always OFF.The valve characteristics can be adapted through this toreduce the switching frequency.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for heating = switching
(1 Bit)- Type of variable output for heating and cooling =
switching (1 Bit) to joint object
Parameter Settings
Heating, reset time 5 min…120 mininactiveDefault value: 30 min
Setting the reset time of the PI controller for heatingmode.A reset time of 30 min means that within this time the I-portion is equal to the P-portion.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI controlHeating, sequence control
Parameter SettingsHeating, proportionalrange
1.0 K…5.0 KDefault value: 3.0 K
Setting the proportional range of the PI controller forheating mode.A proportional range of 3.0 K means that a routinedeviation of 3 K results in a variable change of 100 %.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI controlHeating, sequence control
The parameter is only visible when:- Type of variable output for heating = continuous
(8 bit) or- Type of variable output for heating and cooling =
continuous (8 Bit) to joint object
Parameter SettingsHeating, maximumactuating variable
0 %...100 %Default value: 100 %
Setting the upper threshold for the heating variable.If the internal variable is above the value defined here,then the value defined here will always be output.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for heating = continuous
(8 bit) or- Type of variable output for heating and cooling =
continuous (8 Bit) to joint object
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 73 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Parameter SettingsHeating, minimumactuating variable
0 %...100 %Default value: 0 %
Setting the lower threshold for the heating variable.If the internal variable is below the value defined here,then 0 % will always be output.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for heating = continuous
(8 bit) or- Type of variable output for heating and cooling =
continuous (8 Bit) to joint object
Parameter SettingsHeating, direction /scaling of actuatingvariable
+1 %...+100 % (normal)−1 %...−100 % (inverted)Default value: +100 %(normal)
Setting to define the form in which the variable shouldbe output.In the 100% (normal) setting, the control assumes thatthe valve is open when the variable is +100%. If incontrast, the valve, for example, is closed at 100%, thenthe desired effect of the variable must be inverted.Scaling of the variable is achieved by reducing thepercentage value.The setting depends on the type of valve or actuatorused.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for heating = continuous
(8 bit) or- Type of variable output for heating and cooling =
continuous (8 Bit) to joint object
Parameter SettingsHeating, send actuatingvariable at change by
1 %...100 %Default value: 5 %
Setting to define the minimum change required for theheating variable to be automatically sent.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for heating = continuous
(8 bit) or- Type of variable output for heating and cooling =
continuous (8 Bit) to joint object
Parameter SettingsHeating, cycle time tosend actuating variable
non5 min…120 minDefault value: 10 min
Setting to define the minimum time interval in which theheating variable should be automatically sent.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI controlHeating, sequence control
The parameter is only visible when:- Type of variable output for heating = continuous
(8 bit) or- Type of variable output for heating and cooling =
continuous (8 Bit) to joint object
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 74 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
6.1.10 Heating parameter, sequence control
Note:The prerequisites for this parameter page to be visible are:- Device function parameter = controller + panel (see Section 6.1.4, on page 57).- Parameter Mode = Heating: Sequence control (see Section 6.1.7, on page 66).
Figure. 70. Parameter view: Heating, sequence control
Parameter SettingsHeating, sequence 2 startsat [%]
5…95Pre-set value: 50
Specification of the minimum variable of the controlleroutput for heating at which sequence 2 should begin.
Transmission: ETS
Parameter page: Heating, sequence control
Parameter SettingsHeating, sequence 1, sendactuating variable atchange by
1 %…25 %Pre-set value: 5 %
Setting to define the minimum change required for theheating sequence 1 variable to be automatically sent.
Transmission: ETS
Parameter pages: Heating, sequence control
Parameter SettingsHeating, sequence 2, sendactuating variable atchange by
1 %…25 %Pre-set value: 5 %
Specification to define the minimum change for whichthe variable of Heating, Sequence 2 should beautomatically sent
Transmission: ETS
Parameter pages: Heating, sequence control
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 75 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Parameter SettingsHeating, proportionalrange
1.0 K…5.0 KDefault value: 3.0 K
Setting the proportional range of the PI controller forheating mode.A proportional range of 3.0 K means that a routinedeviation of 3 K results in a variable change of 100 %.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI controlHeating, sequence control
Parameter SettingsHeating, reset time 5 min…240 min
inactiveDefault value: 30 min
Setting the reset time of the PI controller for heatingmode.A reset time of 30 min means that within this time the I-portion is equal to the P-portion.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI controlHeating, sequence control
Parameter SettingsHeating, cycle time tosend actuating variable
none5 min…120 minDefault value: 15 min
Setting to define the minimum time interval in which theheating variable should be automatically sent.
Transmission: ETS
Parameter pages: Heating = PI controlHeating and cooling, PI controlHeating, sequence control
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 76 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
6.1.11 Cooling parameter, two-point control
Note:The prerequisites for this parameter page to be visible are:- Device function parameter = controller + panel (see Section 6.1.4, on page 57).- Parameter Mode = Cooling: Two-point control (see Section 6.1.7, on page 66).
Figure. 71. Parameter view: Cooling, two-point control
Parameter SettingsCooling, hysteresis ± 0.1 K…± 2.5 K
Default value: ± 0.5 K
Setting the switching hysteresis of the two-pointcontroller for cooling mode.Although the precision of the room temperature setpointvalue increases as the hysteresis becomes smaller, theswitching frequency of the controller increases.
Transmission: ETS
Parameter page: Cooling, two-point control
Parameter SettingsDouble hysteresis forenergy saving andprotection mode
noyes
Setting the double switching hysteresis in energy-savingor heat protection mode.This allows room temperature fluctuations in energy-saving or heat protection mode to be twice as large inorder to save energy.
Transmission: ETS
Parameter page: Cooling, two-point control
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 77 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Parameter SettingsCooling, direction ofactuating variable
normalinverted
Defines the form in which the variable should be output.- Normal: Output of the variable in accordance with the
computed variable.- Inverted: Output of the variable reverses the desired
effect of the variable.With this parameter, the setting depends on the type ofvalve (whether opened or closed when there is nocurrent) or actuator used.
Transmission: ETS
Parameter page: Cooling, two-point control
Parameter SettingsCooling, cycle time for twopoint control
0.5 min…15 minDefault value: 5 min
Setting the time interval for reactivation of the two-pointcontroller.The setting causes the two-point control, for example, tooccur only every 5 minutes. Hysteresis and cycle timeinfluence the degree to which the room temperature candeviate from its setpoint value.
Transmission: ETS
Parameter page: Cooling, two-point control
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 78 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
6.1.12 Cooling parameter, PI control
Note:The prerequisites for this parameter page to be visible are:- Device function parameter = controller + panel (see Section 6.1.4, on page 57).- Parameter Mode = Cooling: PI-Control (see Section 6.1.7, on page 66).
Figure. 72. Parameter view: Cooling, PI control
Parameter SettingsCooling, output type ofactuating variable
continuous (8 bit)switching (1 bit)
Setting of the output type of the variable- continuous: the output variable corresponds to the
computed variable with a resolution of 8 bit.- Switching: The variable is output as a pulse width
modulated switching command, whereby the dutyfactor between ON and OFF corresponds to thecomputed variable.
Transmission: ETS and sdCard
Parameter pages: Cooling, PI controlHeating and cooling, PI control
Parameter SettingsCooling, proportionalrange
1.0 K…5.0 KDefault value: 3.0 K
Setting the proportional range of the PI controller forcooling mode.A proportional range of 3.0 K means that a routinedeviation of 3 K results in a variable change of 100 %.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI controlCooling, sequence control
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 79 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Parameter SettingsCooling, cycle duration forpulse width modulation
5 min…120 minDefault value: 10 min
Setting to define the minimum time interval in which thecooling variable should be automatically sent.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI controlCooling, sequence control
The parameter is only visible when:- Type of variable output for cooling =continuous
(8 Bit) or- Type of variable output for heating & cooling =
continuous (8 Bit) to joint object
Parameter SettingsCooling, reset time 5 min…240 min
inactiveDefault value: 30 min
Setting the reset time of the PI controller for coolingmode.A reset time of 30 min means that within this time the I-portion is equal to the P-portion.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI controlCooling, sequence control
Parameter SettingsCooling, maximumactuating variable
0 %...100 %Default value: 100 %
Setting the upper threshold for the cooling variable.If the internal variable is above the value defined here,then the value defined here will always be output.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for cooling = continuous
(8 Bit) or- Type of variable output for heating & cooling =
continuous (8 Bit) to joint object
Parameter SettingsCooling, minimumactuating variable
0 %...100 %Default value: 0 %
Setting the lower threshold for the cooling variable.If the internal variable is below the value defined here,then 0 % will always be output.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for cooling = continuous
(8 Bit) or- Type of variable output for heating & cooling =
continuous (8 Bit) to joint object
Parameter SettingsCooling, direction / scalingof actuating variable
+1 %...+100 % (normal)−1 %...−100 % (inverted)Default value: +100 %(normal)
Setting to define the form in which the variable shouldbe output.In the 100% (normal) setting, the control assumes thatthe valve is open when the variable is +100%. If incontrast, the valve, for example, is closed at 100%, thenthe desired effect of the variable must be inverted.Scaling of the variable is achieved by reducing thepercentage value.The setting depends on the type of valve or actuatorused.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable for cooling = continuous (8 Bit) or- Type of variable for heating & cooling = continuous
(8 Bit) to joint object
Parameter SettingsCooling, send actuatingvariable at change by
1 %...100 %Default value: 5 %
Setting to define the minimum change required for thecooling variable to be automatically sent.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for cooling = continuous
(8 Bit) or- Type of variable output for heating & cooling =
continuous (8 Bit) to joint object
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 80 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Parameter SettingsCooling, direction ofactuating variable
normalinverted
Setting to define the form in which the variable shouldbe output.- Normal: Output of the variable in accordance with the
computed variable.- Inverted: Output of the variable reverses the desired
effect of the variable.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable for cooling = switching (1 Bit)- Type of variable output for heating and cooling =
switching (1 Bit) to joint object
Parameter SettingsCooling, cycle duration forpulse width modulation
1 min…30 minDefault value: 10 min
Setting the period length for the pulse width modulationof the switching variable output in cooling mode.The variable corresponds to the duty factor (time ratio)between "ON (1)" and "OFF (0)" within one period.CAUTION: During thermo-drive, please note that theperiod length cannot be shorter than the sum of the re-cooling and cooling times of the thermo-drive.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for cooling = switching
(1 Bit) or- Type of variable output for heating and cooling =
switching (1 Bit) to joint object
Parameter SettingsCooling always on from 40 %...100 % of actuating
variableDefault value: 90 %
Setting of the minimum percentage value of the variablerequired for the variable to always be ON.The valve characteristics can be adapted through this toreduce the switching frequency.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for cooling = switching
(1 Bit) or- Type of variable output for heating and cooling =
switching (1 Bit) to joint object
Parameter SettingsCooling always off to 1 %...50 % of actuating
variableDefault value: 10 %
Setting of the maximum percentage value of the variableat which the variable is always OFF.The valve characteristics can be adapted through this toreduce the switching frequency.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI control
The parameter is only visible when:- Type of variable output for cooling = switching
(1 Bit) or- Type of variable output for heating and cooling =
switching (1 Bit) to joint object
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 81 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
6.1.13 Cooling parameter, sequence control
Note:The prerequisites for this parameter page to be visible are:- Device function parameter = controller + panel (see Section 6.1.4, on page 57).- Parameter Mode = Cooling: Sequence control (see Section 6.1.7, on page 66).
Figure. 73. Parameter view: Cooling, sequence control
Parameter SettingsCooling, sequence 2 startsat [%]
5…95Pre-set value: 50
Specification of the minimum variable of the controlleroutput for cooling at which sequence 2 should begin.
Transmission: ETS
Parameter page: Cooling, sequence control
Parameter SettingsCooling, sequence 1, sendactuating variable atchange by
1 %…25 %Pre-set value: 5 %
Specification to define the minimal change of thecooling variable for which Sequence 1 should beautomatically sent
Transmission: ETS
Parameter pages: Cooling, sequence control
Parameter SettingsCooling, sequence 2, sendactuating variable atchange by
1 %…25 %Pre-set value: 5 %
Specification to define the minimal change of thecooling variable for which Sequence 2 should beautomatically sent
Transmission: ETS
Parameter pages: Cooling, sequence control
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 82 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Parameter SettingsCooling, proportionalrange
1.0 K…5.0 KDefault value: 3.0 K
Setting the proportional range of the PI controller forheating mode.A proportional range of 3.0 K means that a routinedeviation of 3 K results in a variable change of 100 %.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI controlCooling, sequence control
Parameter SettingsCooling, reset time 5 min…240 min
inactiveDefault value: 30 min
Setting the reset time of the PI controller for heatingmode.A reset time of 30 min means that within this time the I-portion is equal to the P-portion.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI controlCooling, sequence control
Parameter SettingsCooling, cycle time tosend actuating variable
none5 min…120 minDefault value: 15 min
Setting to define the minimum time interval in which thecooling variable should be automatically sent.
Transmission: ETS
Parameter pages: Cooling, PI controlHeating and cooling, PI controlCooling, sequence control
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 83 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
6.1.14 Heating and cooling parameter, PI control
Note:The prerequisites for this parameter page to be visible are:- Device function parameter = controller + panel (see Section 6.1.4, on page 57).- Parameter Mode = Heating & Cooling: PI-control (see Section 6.1.7, on page 66).
Figure. 74. Parameter view: Heating and cooling, PI control
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 84 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Parameter SettingsHeating and cooling, outputtype of actuating variable
via separate objectscontinuous (8-bit) viacommon objectswitching (1-bit) viacommon object
Setting the variable output type for the heating andcooling mode.- Via separate objects: the settings for heating and
cooling are made separately on the respectiveparameter pages.
- continuous: the output variable corresponds to thecomputed variable with a resolution of 8 bit.
- Switching: the variable is output as a pulse widthmodulated switching command, whereby the dutycycle between On and Off corresponds to thecomputed variable.
Transmission: ETS and sdCard
Parameter pages: Cooling, PI controlHeating and cooling, PI control
Explanation of additional heating parameters: seeChapter 6.1.9, starting on page 71.
Explanation of additional cooling parameters: seeChapter 6.1.12, starting on page 78.
6.1.15 Communication objects for roomtemperature control
Obj. Object name Function Type Flags116 Outdoor
temperatureReceive 2 Byte
DPT_Value_Temp
CWTU
This communication object is used to receive the outsidetemperature from an external sensor.This communication object sends a read request whenpower is restored. If there is no answer, then aconfigurable default value is used.Obj. Object name Function Type Flags117 Indoor
temperature,built-in sensor
Send 2 ByteDPT_Value_Temp
CRT
This object is used to send the value (in °C) measuredand corrected by the installed indoor temperaturesensor. The value can also be sent automatically if thetemperature changes by a configurable value. Thetemperature can also be queried.Obj. Object name Function Type Flags118 Indoor
temperature,external sensor
Receive 2 ByteDPT_Value_Temp
CWTU
This object receives the current actual temperature valueof the external indoor temperature sensor (in °C). Thisobject can be used to cyclically send read telegrams tothe external temperature sensor so that this sends itscurrent value back.This communication object sends a read request whenpower is restored. If there is no answer, then aconfigurable default value is used.
This object is only available if:External indoor temperature sensor = YesObj. Object name Function Type Flags119 Indoor
temperature,weighted
Send 2 ByteDPT_Value_Temp
CRT
This object contains the current actual temperaturevalue for the controller. This value is computed takingthe configured weighting into account, which isdetermined from the values measured by the correctedinternal and the corrected external indoor temperaturesensors. The value is send automatically when aconfigurable change occurs.This object is only available if:External indoor temperature sensor = YesObj. Object name Function Type Flags120 Base setpoint Receive 2 Byte
DPT_Value_Temp
CRWTU
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 85 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
This object can be used to read the basic setpoint value(in °C) and to change it via the bus by telegram.This value corresponds to the setpoint value in comfortmode with a setpoint offset = 0. If values outside of the16..26 °C range are received, the value is set to thecorresponding minimum or maximum value.This communication object sends a read request whenpower is restored. If there is no answer, then aconfigurable default value is used.
This object is only available if:Basic setpoint value visible object = YesObj. Object name Function Type Flags121 Setpoint shift Receive/send 2 Byte
DPT_Value_Temp
CRWTU
This object can be used to receive a shifting of setpointvalue via the bus. When values outside of theparameterized area for the shifting of setpoint values arereceived, the value is cut to the relevant areaboundaries.This object can be used to send every change in thesetpoint value offset (in Kelvin) after 3 s.Obj. Object name Function Type Flags122 Temperature,
setpointSend 2 Byte
DPT_Value_Temp
CRT
This object contains the current, effective setpoint valueof the room temperature (in °C), which is computedunder consideration of the basic setpoint value, modeand shifting.Obj. Object name Function Type Flags110 Setpoint comfort
modeSend 2 Byte
DPT_Value_Temp
CRWT
This object contains the current setpoint value of theroom temperature (in °C) for the comfort mode, which iscomputed under consideration of the basic setpointvalue and shifting.
Obj. Objektname Funktion Typ Flags
123 Automatic mode Receive/ send:On/Off
1 bit CRWTU
This object can be used to switch to automatic mode viathe bus. Upon receipt, only "1" telegrams are evaluated;"0" telegrams are rejected.
This object is additionally used to send the status (0:manual mode, 1: automatic mode).Obj. Object name Function Type Flags124 Comfort mode Receive/ Send:
On/Off1 bit CRWTU
When the Automatic mode via parameter is set to Bustelegrams, then comfort mode can be switched on viathe bus. Upon receipt, both "1" and "0" telegrams areevaluated. Upon receipt of a "0", if no correspondingcommand arrives within 3 seconds, the mode isswitched to energy-saving mode or to protection mode,if energy-saving mode is not available.Moreover this object is used to report changes occurringin the comfort mode status (such as those causedmanually or by an internal time program).Obj. Object name Function Type Flags125 Pre-comfort mode Receive/ send:
On/Off1 bit CRWTU
If the parameter Automatic mode via is set to Bus-Telegrams, then the operating mode “pre-comfortmode“ (standby operation) can be switch via this objectby the bus. Upon receipt of a "0", if no correspondingcommand arrives within 3 seconds, the mode isswitched to energy-saving mode or to protection mode,if energy-saving mode is not available. Moreover thisobject is used to report changes occurring in the comfortmode status (such as those caused manually or by aninternal time program).
This object is only available if:Controller 4 of the room operating modes can beactivatedObj. Object name Function Type Flags126 Energy saving
modeReceive/ Send:On/Off
1 bit CRWTU
When the Automatic mode via parameter is set to Bustelegrams, then this object can be used to switch themode to energy-saving mode (nighttime operation) viathe bus.Upon receipt of a "0", if no corresponding commandarrives within 3 seconds, the energy-saving moderemains active.
Moreover this object is used to report changes occurringin the energy-saving mode status (such as those causedmanually or by an internal time program).
This object is only available if:Controller 3 or 4 of the room operating modes can beactivated
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 86 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Obj. Object name Function Type Flags127 Protection mode receive/ send:
On/Off1 bit CRWTU
When the Automatic mode via parameter is set to Bustelegrams, then this object can be used to switch themode to "protection mode" (frost/heat protection) viathe bus. Upon receipt of a "0", if no correspondingcommand arrives within 3 seconds, the mode isswitched to energy-saving mode (if available, otherwiseprotection mode is maintained).Moreover this object is used to report changes occurringin the protection mode status (such as those causedmanually or by an internal time program).Obj. Object name Function Type Flags128 Permanent
Protection modeReceive:On/Off
1 bit CRWTU
The controller can use this object to switch permanentlyto "protection mode" (frost/heat protection) (e.g. duringprolonged absence or holidays). In this case, no othermode objects can be used by a time program, timer,presence detector or manually to switch to a differentmode.If "permanent protection mode" is switched off, then thecontroller automatically switches to:- "energy-saving mode" in manual mode if available,
otherwise to protection mode- the currently active mode in automatic mode (from
bus telegram or internal time program)
This object is only available if:Object for permanent protection mode visible = YesObj. Object name Function Type Flags129 Controller Receive:
On/Off1 bit CRWU
This object can be used to switch the control on or off. Ifthe control is set to "heating and cooling", then bothcontrols are switched on and off jointly.If the controller is switched to OFF, then the variables forheating and cooling are set to "0". The value "0" is sentonce after the controller is switched off.
This object is only available if:Device function = controller + control panelObj. Object name Function Type Flags130 Heating/ cooling. 1 = heating /
0 = cooling1 bit CRTU
This object shows if the control is in heating or coolingmode. If the status changes it is sent automatically.
Obj. Object name Function Type Flags131 Frost alarm Send: On/Off 1 bit CRT
This object can be used to query the "frost alarm" status("1" = alarm active, "0" = alarm inactive). When theobject value changes, it is sent automatically.Obj. Object name Function Type Flags132 Heat alarm Send: On/Off 1 bit CRT
This object can be used to query the "heat alarm" status("1" = alarm active, "0" = alarm inactive). When theobject value changes, it is sent automatically.Obj. Object name Function Type Flags133 Dew-point alarm Receive:
On/Off1 bit CWU
This object can be used in cooling mode to receive a dewpoint alarm sent by a dew point monitor and to show iton the display. A received dew point alarm causes thecontroller to switch to "dew point mode" and the coolingvalve to close until the dew point alarm is no longerpending.This object is not evaluated unless the controller is incooling mode.Obj. Object name Function Type Flags134 Window 1 Receive 1 bit CWTU
This object is used to receive the status of window 1. Ifthe object value = "1" (window open), the roomtemperature controller switches internally to "protectionmode" and stays in this mode until the object value forone of the window objects = "1".Parameters can be used to invert the behavior.This communication object sends a read request whenpower is restored.Obj. Object name Function Type Flags135 Window 2 Receive 1 bit CWTU
This object is used to receive the status of window 2. Ifthe object value = "1" (window open), the roomtemperature controller switches internally to "protectionmode" and stays in this mode until the object value forone of the window objects = "1".Parameters can be used to invert the behavior.This communication object sends a read request whenpower is restored.Obj. Object name Function Type Flags136 Window 3 Receive 1 bit CWTU
This object is used to receive the status of window 3. Ifthe object value = "1" (window open), the roomtemperature controller switches internally to "protectionmode" and stays in this mode until the object value forone of the window objects = "1".Parameters can be used to invert the behavior.This communication object sends a read request whenpower is restored.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 87 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Obj. Object name Function Type Flags137 Window 4 Receive 1 bit CWTU
This object is used to receive the status of window 4. Ifthe object value = "1" (window open), the roomtemperature controller switches internally to "protectionmode" and stays in this mode until the object value forone of the window objects = "1".Parameters can be used to invert the behavior.This communication object sends a read request whenpower is restored.Obj. Object name Function Type Flags138 Presence Receive:
On/Off1 bit CWTU
The controller contains an optional object for the"presence" state for usage in rooms with a presencedetector. Its telegrams are evaluated for switching theroom operating mode.This communication object sends a read request whenpower is restored.
This object is only available if:Object for presence visible = YesObj. Object name Function Type Flags139 State comfort
extensionSend:On/Off
1 bit CRT
The controller uses this object to report that the "comfortextension" mode has been switched on or off.
This object is only available if:Object for presence visible = No andComfort extension status object = YesObj. Object name Function Type Flags140 Room operation
modeReceived:0…4
1 Byte CWTU
This object is used to switch the room operating modedepending on the value received. The following rulesallocations apply:- 0 = Automatic mode- 1 = Comfort mode- 2 = Pre-comfort mode- 3 = Energy-saving mode- 4 = Protection mode.If a value other than 0...4 is received or a value of amode not available to the controller, then the telegramis rejected as erroneous.If the Automatic mode via parameter is set to internaltime program then only the value "0" is evaluated.Other values are rejected. If a 0 is received when theAutomatic mode via parameter is set to Bus telegrams,the room operating mode will be set to the mode mostrecently received via the 1-byte or 1-bit objects.This communication object sends a read request whenpower is restored.
This object is only available if:8-bit objects for room operating mode / room operatingmode status = YesObj. Object name Function Type Flags141 State room
operation modeSend:0…4
1 Byte CRT
This object is used to report the current mode after theroom operating mode is switched.
For the case "controller + control panel" the followingallocations apply for the transmitted values:- 1 = Comfort mode- 2 = Pre-comfort mode- 3 = Energy-saving mode- 4 = Protection mode.0 (= automatic mode) never occurs in this case, since amode different from "0" always results.
For the case "control panel" with internal time program,the following allocations apply for the transmittedvalues:- 1 = Comfort mode- 2 = Pre-comfort mode- 3 = Energy-saving mode- 4 = Protection mode.
For the case "control panel" with external time program,the following allocations apply for the transmittedvalues:- 0 = Automatic mode (ext. time switch program)- 1 = Comfort mode- 2 = Pre-comfort mode- 3 = Energy-saving mode- 4 = Protection mode.Value ≠ 0 here means: Manual mode
This object is only available if:8-bit objects for room operating mode / room operatingmode status = YesObj. Object name Function Type Flags142 Controller state
(Eberle)Send 1 Byte CRT
This object contains the current controller status, whichis automatically sent when the status changes.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 88 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
The individual bits have the following meaning:- Bit 0: 1 = comfort mode On- Bit 1: 1 = pre-comfort mode On- Bit 2: 1 = energy-saving mode On- Bit 3: 1 = protection mode On- Bit 4: 1 = dew point alarm- Bit 5: 1 = heating mode, 0 = cooling mode- Bit 6: 1 = controller Off, 0 = controller On- Bit 7: 1 = Frost/heat alarm (depending on the value of
bit 5)
This object is only available if:8-Bit object controller status (Eberle) = YesObj. Object name Function Type Flags143 Controller state
(RHCC)Send:16-Bit Status
2 Byte CRT
This object contains the current controller status, whichis automatically sent when the status changes.The following bits are supported:Fault (Bit 0), HeatCoolMode (Bit 8), DewPointStatus(Bit 12), FrostAlarm (Bit 13) und OverheatAlarm (Bit 14).The other bits (1..7, 9..11 and 15) are set to 0.
This object is only available if:16-Bit object controller status (RHCC) = YesObj. Object name Function Type Flags144 Heating/ Cooling,
actuating variableswitching
Send:On/Off
1 bit CRT
This object is used to send the variable as an On/Offswitching command in both heating and cooling mode.
This object is only available if:- Device function = controller + panel and- Heating = with two-point control and cooling ) with
two-point controlor- Device function = controller + panel and- Heating = with PI control and cooling = with PI control
and- Type of variable output for heating and cooling =
switching (1 bit) to a joint object
Obj. Object name Function Type Flags145 Heating/ cooling,
actuating variablecontinuous
Send:0…100 %
1 ByteDPT_Scaling
CRT
This object is used to send the variable as a percentile inboth heating and cooling mode.
This object is only available if:- Device function = controller + paneland- Heating = PI controland- Cooling = with PI controland- Type of variable output for heating and cooling =
continuous (8 bit) to a joint objectObj. Object name Function Type Flags146 Heating, actuating
variable switchingSend:On/Off
1 bit CRT
This object is used to send the variable as an On/Offswitching command in heating mode.
This object is only available if:- Device function = controller + panel and- Heating with two-point controlor- Device function = controller + panel and- Heating = with PI control and- Variable output type for heating and cooling = via
separated objects and- type of variable output for heating = switching (1 Bit)Obj. Object name Function Type Flags147 Heating, actuating
variablecontinuous
Send:0…100 %
1 ByteDPT_Scaling
CRT
This object is used to send the variable as a percentile inheating mode with PI control and the "internal" variableof the control with sequence control in PI control.
This object is only available if:- Device function = controller + continuous panel and- Heating = with PI-control or- Heating = with PI control and sequence control and- Variable output type for heating and cooling = via
separated objects and- type of variable output for heating = continuous (8 Bit)
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 89 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Obj. Object name Function Type Flags148 Heating, actuating
variable,sequence 1
Send:0…100 %
1 ByteDPT_Scaling
CRT
This object is used in heating mode with sequencecontrol to send the variable of the first sequence as apercentile.
This object is only available if:- Device function = controller + panel and- Heating = with PI control and sequence controlObj. Object name Function Type Flags149 Heating, actuating
variable,sequence 2
Send:0…100 %
1 ByteDPT_Scaling
CRT
This object is used in heating mode with sequencecontrol to send the variable of the second sequence as apercentile.
This object is only available if:- Device function = controller + panel and- Heating = with PI control and sequence controlObj. Object name Function Type Flags150 Cooling, actuating
variable switchingSend:On/Off
1 bit CRT
This object is then used to send the variable as an On/Offswitching command in cooling mode.
This object is only available if:- Device function = controller + panel and- Cooling = two-point controlor- Device function = controller + panel and- Cooling = with PI control and- Variable output type for heating and cooling = via
separated objects and- type of variable output for cooling = switching (1 Bit)Obj. Object name Function Type Flags151 Cooling, actuating
variablecontinuous
Send:0…100 %
1 ByteDPT_Scaling
CRT
This object is used to send the variable as a percentile incooling mode with PI control and the "internal" variableof the control with sequence control in PI control.
This object is only available if:- Device function = controller + panel and- Cooling = with PI control or
Cooling = with PI control and sequence control and- Variable output type for heating and cooling = via
separated objects and- type of variable output for cooling = continuous (8 Bit)
Obj. Object name Function Type Flags152 Cooling, actuating
variable,sequence 1
Send:0…100 %
1 ByteDPT_Scaling
CRT
This object is used in cooling mode with sequencecontrol to send the variable of the first sequence as apercentile.
This object is only available if:- Device function = controller + panel and- Cooling = with PI control and sequence controlObj. Object name Function Type Flags153 Cooling, actuating
variable,sequence 2
Send:0…100 %
1 ByteDPT_Scaling
CRT
This object is used in cooling mode with sequencecontrol to send the variable of the second sequence as apercentile.
This object is only available if:- Device function = controller + panel and- Cooling = with PI control and sequence controlObj. Object name Function Type Flags154 Fan mode Send: 1 bit CRT
This object sends the set fan mode. Depending on thesetting of the "invert value of fan mode" parameter, thefollowing applies:- No: Value “0“ = Fan-manual mode,
Value “1“ = Fan automatic mode- Yes: Value “1“ = Fan-manual mode,
Value “0“ = Fan automatic mode
This object is only available if:- Fan available = YesObj. Object name Function Type Flags155 State fan mode Receive 1 bit CWU
This object is used to receive and display the status ofthe fan mode.
Depending on the setting of the "invert value of fanmode" parameter, the following applies:- No: Value “0“ = Fan-manual mode,
Value “1“ = Fan automatic mode- Yes: Value “1“ = Fan-manual mode,
Value “0“ = Fan automatic mode
This object is only available if:- Fan available = Yes
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 90 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Obj. Object name Function Type Flags156 Fan speed Send:
0…100 %1 ByteDPT_Scaling
CRT
After a change in the fan level, this object is used in bothautomatic and manual mode to send the current fanspeed. This object can therefore be used to start up a fanwith an adjustable speed in the range of 0...100%.The allocation of a speed value to a fan level in the "fan"parameter window is used to determine which fan levelsymbol is to be shown on the display.
This object is only available if:- Fan available = YesObj. Object name Function Type Flags157 State fan speed Receive:
0…100 %1 ByteDPT_Scaling
CWU
This object is used to receive the current fan speed.
This object is only available if:- Fan available = YesObj. Object name Function Type Flags158 Fan level 1 Send:
On/Off1 bit CRT
This object is used to send the command for switchingfan level 1 on and off.
This object is only available if:- Fan available = YesObj. Object name Function Type Flags159 Fan level 2 Send:
On/Off1 bit CRT
This object is used to send the command for switchingfan level 2 on and off.
This object is only available if:- Fan available = Yes and- Number of fan speeds = 2 or
number of fan speeds = 3Obj. Object name Function Type Flags160 Fan level 3 Send:
On/Off1 bit CRT
This object is used to send the command for switchingfan level 3 on and off.
This object is only available if:- Fan available = Yes and- Number of fan levels = 3Obj. Object name Function Type Flags161 State fan level 1 Receive:
On/Off1 bit CWU
This object is used to receive and display the status offan level 1.If the status is set to more than one of objects 161...163,then the highest fan level is displayed in each case.
This object is only available if:- Fan available = YesObj. Object name Function Type Flags162 State fan level 2 Receive:
On/Off1 bit CWU
This object is used to receive and display the status offan level 2.If the status is set to more than one of objects 161...163,then the highest fan level is displayed in each case.
This object is only available if:- Fan available = Yes and- Number off an speeds = 2 or
number off an speeds = 3Obj. Object name Function Type Flags163 State fan level 3 Receive:
On/Off1 bit CWU
This object is used to receive and display the status offan level 3.If the status is set to more than one of objects 161...163,then the highest fan level is displayed in each case.
This object is only available if:- Fan available = Yes and- Number of fan levels = 3Obj. Object name Function Type Flags164 Heating / cooling
switch1 = heating/0 = cooling
1 bit CWTU
This object sets the strategy heating or cooling via bus,e.g. from a BMS or a system control. This switching ismandatory with 2-pipe-systems appropriate to theexisting device. Therefore only heating or cooling ispossible at once. The actuating variables for heating andcooling are locked against each other.
This object is only available if:- Strategy Heating / Cooling = via central control
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 91 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
6.2 Channels
6.2.1 Parameter for channel type
Parameter SettingsChannel type unused
switchdimmersun blindroller shutter,send valueforced controlalarm / messagescene control
Specification of the channel type and activation of thechannel.
Transmission: ETS/sdCard
Parameter page: Channels
6.2.2 Switch parameter
Parameter SettingsSwitch mode off
on
toggle
bell on at push, off at release
bell off at push, on at release
Setting the switch types.
Transmission: sdCard
Parameter page: Channel
Parameter SettingsEnable statedisplay
yesno
Specification as to whether the status display of theswitching state should be visible on the display.
Transmission: sdCard
Parameter page: Channel
6.2.3 Switch communication objects
The following communication objects refer to channels 1– 18.
Obj. Object name Function Type Flags0, 6, 12,18, 24, 30,36, 42, 4854, 60, 66,72, 78, 8490, 96, 102
<Channel no.>- switch
Send:On/Off
1 bit CWT
This object sends a switching command when a key ispressed.
1, 7, 13,19, 25, 31,37, 43, 4955, 61, 67,73, 79, 8591, 97, 103
< Channel no.>- state on/off
Receive:On/Off
1 bit CWTU
This object is used to receive the status. The status canbe shown on the display. The switch over function usesthe status to synchronize the internal status.This communication object sends a read request whenpower is restored.
6.2.4 Communication objects for dimming
The following communication objects refer to channels 1– 18.
Obj. Object name Function Type Flags0, 6, 12,18, 24, 30,36, 42, 4854, 60, 66,72, 78, 8490, 96, 102
< Channel no.>- switch
Send:On/Off
1 bit CWTU
This object sends a switching command when a key ispressed.Obj. Object name Function Type Flags2, 8, 14,20, 26, 32,38, 44, 5056, 62, 68,74, 80, 8692, 98, 104
< Channel no.>- dim value
Send:Value
1 ByteDPT_Scaling
CT
This object is used to send the dimming value in steps asan 8-bit data telegram.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 92 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
3, 9, 15,21, 27, 33,39, 45, 5157, 63, 69,75, 81, 8793, 99, 105
< Channel no.>- state dimvalue
Received:Value
1 ByteDPT_Scaling
CWTU
This object is used to display received values by thelength of the bar.This communication object sends a read request whenpower is restored.
6.2.5 Sun blind parameter
Parameter SettingsInvert slat rotationdirection
noyes
Setting to define whether the rotational direction of theslat setting should be reversed.- No: Turning clockwise sends Slats closed (1)- Yes: Turning clockwise sends Slats open (0)
Transmission: sdCard
Parameter page: Channel
Parameter SettingsState object of actuatoravailable
yesno
Setting to define whether the actuator used provides an8-bit status object (shutter position).The actuator status object must be connected to thechannel status object.
Transmission: ETS/sdCard
Parameter page: Channel
Parameter SettingsDisplay status display value 0 as
question markdisplay value 0 as 0 %
Setting, as the 8 bit status value (Blind position)shall interpret and displayed.- display value 0 as question mark
In this setting value 0 is interpreted as undefinedstatus and therefore it is indicated as a question markon the display.The value 1 accords to the upper end position.The value 255 accords to the lower end position.
- display value 0 as 0%The value 1 accords to the upper end position, 0%.The value 255 accords to the lower end position,100%.
Transmission: sdCard
Parameter page: Channel
6.2.6 Communication object for blinds
The following communication objects refer to channels 1– 18.
Obj. Object name Function Type Flags0, 6, 12,18, 24, 30,36, 42, 4854, 60, 66,72, 78, 8490, 96, 102
<Channel no.>sun blind
Send:Up/down
1 bit CT
This object sends a switching command when a key ispressed.Obj. Object name Function Type Flags1, 7, 13,19, 25, 31,37, 43, 4955, 61, 67,73, 79, 8591, 97, 103
<Channel no.>stop/slat
Send:Stop,Open/ Close
1 bit CT
This object sends a switching command when a key ispressed.The sun protection receives the stop command or openor closed.Obj. Object name Function Type Flags2, 8, 14,20, 26, 32,38, 44, 5056, 62, 68,74, 80, 8692, 98, 104
<Channel no.>blind position
Send:Value
1 Byte CT
This object is used to directly set the position of the sunprotection. The value 0 is sent to completely open theshutter.This object is used by the internal time scheduler to startup the sun protection position.Obj. Object name Function Type Flags3, 9, 15,21, 27, 33,39, 45, 5157, 63, 69,75, 81, 8793, 99, 105
<Channel no.>state sun blindposition
Receive:Value
1 Byte CWTU
Received values are used via this object to display theresponse symbol. The value 0 indicates undefinedposition, value 1 means the shutter is completely open.In the case of undefined position, an "?" is displayed.This communication object sends a read request whenpower is restored.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 93 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Obj. Object name Function Type Flags4, 10, 16,22, 28, 34,40, 46, 5258, 64, 70,76, 82, 8894, 100,106
<Channel no.>slat position
Send:Value
1 Byte CT
This object is used to directly set the position of the slats.The value 0 is sent to completely open the slats.This object is used by the internal time scheduler to setthe shutter position.Obj. Object name Function Type Flags5, 11, 17,23, 29, 35,41, 47, 5359, 65, 71,77, 83, 8995, 101,107
<Channel no.>state slatposition
Receive:Value
1 Byte CWTU
Received values are used via this object to display theresponse symbol. The value 0 indicates undefinedposition, value 1 means the slats are completely open. Inthe case of undefined position, an "?" is displayed.This communication object sends a read request whenpower is restored.
6.2.7 Parameter for roller shutter
Parameter SettingsState object of actuatoravailable
yesno
Setting to define whether the actuator used provides a1-byte status object (roller blind position).The actuator status object must be connected to thechannel status object.
Transmission: ETS/sdCard
Parameter page: Channel
Parameter SettingsDisplay status display value 0 as
question markdisplay value 0 as 0 %
Setting, as the 8 bit status value (Shutter position)shall interpret and displayed.- display value 0 as question mark
In this setting value 0 is interpreted as undefinedstatus and therefore it is indicated as a question markon the display.The value 1 accords to the upper end position.
The value 255 accords to the lower end position.- display value 0 as 0%
The value 1 accords to the upper end position, 0%.The value 255 accords to the lower end position,100%.
Transmission: sdCard
Parameter page: Channel
6.2.8 Communication objects for shutters
The following communication objects refer to channels 1– 18.
Obj. Object name Function Type Flags0, 6, 12,18, 24, 30,36, 42, 4854, 60, 66,72, 78, 8490, 96, 102
<Channel no.>roller shutter
Send:Up/down
1 bit CT
This object sends a switching command when a key ispressed.Obj. Object name Function Type Flags1, 7, 13,19, 25, 31,37, 43, 4955, 61, 67,73, 79, 8591, 97, 103
<Channel no.>stop rollershutter
Send 1 bit CT
This object sends a switching command when a key ispressed. The roller blinds receive the stop command.Obj. Object name Function Type Flags2, 8, 14,20, 26, 32,38, 44, 5056, 62, 68,74, 80, 8692, 98, 104
<Channel no.>roller shutterposition
Send:Value
1 Byte CT
This object is used to directly set the position of the rollerblind. The value 0 is sent to completely open roller blind.This object is used by the internal time scheduler to startup the roller blind position.Obj. Object name Function Type Flags3, 9, 15,21, 27, 33,39, 45, 5157, 63, 69,75, 81, 8793, 99, 105
<Channel no.>state rollershutter position
Receive:Value
1 Byte CWTU
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 94 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Received values are used via this object to display theresponse symbol. The value 0 indicates undefinedposition, value 1 means the roller blind is completelyopen. In the case of undefined position, an "?" isdisplayed.This communication object sends a read request whenpower is restored.
6.2.9 Send value parameter
Parameter SettingsVariable value yes
no
Specification as to whether the value to be sent is aconstant value or a variable (can be set on the device).
Transmission: ETS/sdCard
Parameter page: Channel
Parameter SettingsData type 1-byte in %
1-byte unsigned integer1-byte signed integer2-byte unsigned integer2-byte signed integer4-byte unsigned integer4-byte signed integerWind speed in m/sLuminance in LuxTemperature in °C
Setting of which data type is to be sent. The setting Windspeed, Luminance and Temperature are data typefloating point.
Transmission: ETS/sdCard
Parameter page: Channel
Parameter SettingsValue Value in the value range of the
specified data typePre-set value: 0
Setting of the value to be sent when sending constantvalues.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Variable value = No
Parameter SettingsMinimum Value in the value range of the
specified data typePre-set value: smallest value in thevalue range
Setting of the smallest allowed input value for inputtingvariable values.This value is displayed the first time the operating pageis called up if no value has yet been received via thevalue object.The last sent/received value is displayed with eachadditional call-up of the operating page.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Variable value = yes
Parameter SettingsMaximum Value in the value range of the
specified data typePre-set value: largest value in thevalue range
Setting of the largest allowed input value for inputtingvariable values.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Variable value = yes
Parameter SettingsUnit
Specification of the unit of the displayed numericalvalue.Maximum length: 14 characters.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Variable value = yes
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 95 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
6.2.10 Send value communication object
The following communication objects refer to channels 1– 18.
Obj. Object name Function Type Flags3, 9, 15,21, 27, 33,39, 45, 5157, 63, 69,75, 81, 8793, 99, 105
<Channel no.>Value (datatype)
Send 1 Byte2 Byte4 Byte
CWTU
This object is used to send the fixed configured values orthe variable adjusted values via the rotary/push button.
6.2.11 Communication object for forced control
The following communication objects refer to channels 1– 18.
Obj. Object name Function Type Flags0, 6, 12,18, 24, 30,36, 42, 4854, 60, 66,72, 78, 8490, 96, 102
<Channel no.>- forced control
Send 2 bit CTU
This object is used to send the forced-control controltelegram for the respective channel.
6.2.12 Channel-specific parameter for alarms andmessages
Parameter SettingsFunction message
alarm
Specification of whether or not the message should bean alarm message. If a bus telegram is received with avalue triggering an alarm, then this message isautomatically shown on the display.An additional object is created in the correspondingformat to trigger the alarm.
Transmission: ETS/sdCard
Parameter page: Channel
Parameter SettingsAlarm condition (1 bit) 0
1
Specification to define the value of the alarm triggeringobject for which an alarm should be activated.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Alarm
Parameter SettingsAlarm if at first alarm only
at every alarm
Specification to define whether a new alarm should beactivated when the alarm triggering object is updated.- only for the first alarm: One-time triggering of the
alarm,- for every alarm: the alarm is triggered every time a
value identical to the configured threshold value isreceived by the triggering object.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Alarm
Parameter SettingsObject value toacknowledge alarm
10
Specification to define which value in the object can beused to acknowledge the alarm (Alarmacknowledgement input) and which value in the objectshould be sent after acknowledgement (Alarm-acknowledgement output).
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Alarm
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 96 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Parameter SettingsDisplay illuminationat alarm
no changeswitch on
Specification of the behavior of the display lightingwhen an alarm is triggered.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Alarm
Parameter SettingsAlarm text
Specification of the text to be shown on the displaywhen the alarm condition is fulfilled.The maximum text length is 64 characters.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Alarm
Parameter SettingsAlarm symbol
Specification of the symbol to be shown on the displaywhen the alarm condition is fulfilled.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Alarm
Parameter SettingsLED behaviour atalarm
offpermanent redblinking red
Specification of the behavior of the orientation LEDwhen an alarm is triggered.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Alarm
Parameter SettingsBehavior at alarm set no alarm sound
one-time alarm soundrepeating alarm sound
Specification to define whether and how the triggeringof an alarm should be acoustically clarified.- without alarm tone: The alarm is shown on the display
without an acoustic signal.- One-time alarm tone A one-time alarm tone is output
for a specified time.- Alarm tone repeats permanently A one-time alarm
tone is output for a specified time and at set intervals.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Alarm
Parameter SettingsPriority 1…18
Pre-set value: 1
Specification of the priority of an alarm.The alarms are sorted in an events list according topriority and the time of their occurrence.- highest priority: 1,- lowest priority: 18.- in the case of equal priority: Most recent alarm
message first.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Alarm
Parameter SettingsAlarm text tosend
Specification of the text to be sent through thecommunication object when an alarm is triggered.The maximum length is 14 characters. Input of an emptycharacter string is not possible.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Alarm
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 97 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Parameter SettingsSymbol at value = “1”
Selection of a symbol for the message. This is shown onthe display when the value contains "1".
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Message
Parameter SettingsSymbol at value = “0”
Selection of a symbol for the message. This is shown onthe display when the value contains "0".
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Message
Parameter SettingsText display at value =“1”
Entry of a message text This is shown on the displaywhen the value contains "1".The maximum text length is 64 characters.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Message
Parameter SettingsText display at value =“0”
Entry of a message text This is shown on the displaywhen the value contains "0".The maximum text length is 64 characters.
Transmission: sdCard
Parameter page: Channel
The parameter is only visible when:- Function = Message
6.2.13 Alarm communication objects
The following communication objects refer to channels 1– 18.
Obj. Object name Function Type Flags4, 10, 16,22, 28, 34,40, 46, 5258, 64, 70,76, 82, 8894, 100,106
<Channel no.>- alarm input
Receive 1 bit CWTU
The value content of these objects is compared with atriggering condition (0 or 1). An alarm is triggered ordeactivated accordingly.
This object is only available if:- Function = AlarmObj. Object name Function Type Flags2, 8, 14,20, 26, 32,38, 44, 5056, 62, 68,74, 80, 8692, 98,104
<Channel no.>- alarm output
Send 1 bit CT
When an alarm is triggered (fulfillment of the alarmcondition) the value of this object is set to 1 and sent. A0 is sent if the alarm is deactivated. No action occursupon acknowledgement.
This object is only available if:- Function = AlarmObj. Object name Function Type Flags3, 9, 15,21, 27, 33,39, 45, 5157, 63, 69,75, 81, 8793, 99,105
<Channel no.>- alarm text
Send 14 ByteDPT_String_ASCII
CT
If the alarm condition was met and an alarm wastriggered, a configured alarm text is sent though the busby this object.
This object is only available if:- Function = Alarm
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 98 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
Obj. Object name Function Type Flags0, 6, 12,18, 24, 30,36, 42, 4854, 60, 66,72, 78, 8490, 96,102
<Channel no.>- alarm ACKoutput
Send 1 bit CT
If, after an alarm was triggered, the alarm wasacknowledged on the display, the value of this object isset to 1 or 0 and sent. If the acknowledgement is madeby bus telegrams, then no telegram is sent about this.
This object is only available if:- Function = AlarmObj. Object name Function Type Flags1, 7, 13,19, 25, 31,37, 43, 4955, 61, 67,73, 79, 8591, 97,103
<Channel no.>- alarm ACKinput
Receive 1 bit CW
This object can be used to receive an alarmacknowledgement through the bus. The alarm isconfirmed depending on the configured object value.
This object is only available if:- Function = AlarmObj. Object name Function Type Flags196 Acknowledge
all alarmsReceive 1 bit CW
This object can be used to receive an acknowledgementof all alarms through the bus. The value 1 is alwaysexpected for the acknowledgement. The value 0 isignored.
6.2.14 Message communication object
The following communication object refers to channels 1– 18.
Obj. Object name Function Type Flags4, 10, 16,22, 28, 34,40, 46, 5258, 64, 70,76, 82, 8894, 100,106
<Channel no.>- message
Receive 1 bit CWTU
A configured text and a symbol are displayed by thisobject in accordance with the received value. Thiscommunication object sends a read request when poweris restored. If the request of the object value fails, then a? is displayed as the message text (until a correspondingbus telegram arrives).
This object is only available if:- Function = Message
6.2.15 Screen control parameter
Parameter SettingsScene number 1…64
Pre-set value: 1
Specification of the number of scenes to be sent via the1-byte scene control communication object.The values 0 - 63 are sent via the bus.
Transmission: sdCard
Parameter page: Channel
6.2.16 Communication objects for the retrieval andstorage of scenes
Obj. Object name Function Type Flags0, 6, 12,18, 24, 30,36, 42, 48,54, 60, 66,72, 78, 84,90, 96, 102
<Channel no.>- call scene
Send 1 bit CT
This object is used to send a 1-bit value for the retrievalof scenes.The value 1 is always sent.Obj. Object name Function Type Flags1, 7, 13,19, 25, 31,37, 43, 49,55, 61, 67,73, 79, 85,91, 97, 103
<Channel no.>- save scene
Send 1 bit CT
This object is used to send a 1-bit value for the storage ofscenes.The value 1 is always sent.Obj. Object name Function Type Flags2, 8, 14,20, 26, 32,38, 44, 50,56, 62, 68,74, 80, 86,92, 98, 104
<Channel no.>-8-bit scene
Send:Activate /store
1 Byte CT
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 99 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
A value 0...63 is sent to activate a scene 1...64.A value 128...192 is sent to store a scene 1...64 (scenenumber + 127).
6.3 Time programs
6.3.1 Communication objects for time programs
Obj. Object name Function Type Flags187 Scheduler,
channelsReceive:Activate
1 bit CRWU
This object is used to receive a 1-bit command for theactivation (1) or deactivation (0) of the internal timeprogram for single channels.All channel switching programs become inactive whenthis is deactivated.The received value is persistently stored in memory andis thus available when power is restored.
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Technical Manual 970007, page 100 / 101 Siemens AGInfrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma ã Siemens AG 2017 Control Products and SystemsSubject to change without further notice P. O. Box 10 09 53, D-93009 Regensburg
2.12.1.14
7 Index
A
Actual value specification ........................................... 29Alarm
acoustic behaviour .................................................. 20Display lighting ....................................................... 20General ................................................................... 25LED-behaviour ......................................................... 20Symbol .................................................................... 20Text ......................................................................... 20
Alarm communication objects .................................... 89Alarm priority .............................................................. 20automatic mode ......................................................... 30
C
Channel type .............................................................. 12Channel type Alarm / Message .................................... 19Channel type priority control ...................................... 14Channel type roller blinds ........................................... 16Channel type Scene control ........................................ 18Channel type Send value ............................................ 16Channel type Shutter .................................................. 15Channels
activation ................................................................ 13designation ............................................................. 13
Channel-specific parameter for alarms and messages . 87Cleaning mode ........................................................... 23Comfort extension ...................................................... 32Communication object for forced control ................... 87Communication object for shutters ............................ 85Communication objects for dimming .......................... 84Communication objects for room temperature control77Communication objects for shutters ........................... 86Communication objects for the retrieval and storage of
scenes ..................................................................... 90Communication objects for time programs ................. 91Configuration window for channels ............................ 12Controller operating mode
sequence control..................................................... 28two-point control .................................................... 27
Controller operating modes ........................................ 27Controller status (Eberle) ............................................ 34Controller status (RHCC) ............................................. 34Cooling parameter, PI control ..................................... 71Cooling parameter, sequence control ......................... 74Cooling parameter, two-point control......................... 69Create function page .................................................. 43
D
Date display ................................................................ 25Dead zone................................................................... 31Delete time program ................................................... 39Designs ....................................................................... 40
Dewpoint mode .......................................................... 33Dimmer channel type .................................................. 13
E
Evaluation of the window conditions .......................... 32External indoor temperature sensor ............................ 29
F
Fan in automatic mode ............................................... 35Fan in manual mode ................................................... 35Function pages ........................................................... 41Function-specific message parameters ....................... 21
G
General alarm parameters ........................................... 49General room temperature control parameters ........... 50Generation errors ........................................................ 45
H
Heating and cooling parameter, PI control .................. 76Heating parameter, PI control ..................................... 64Heating parameter, sequence control ......................... 67Heating parameter, two-point control ........................ 63Home-page ................................................................. 40
I
Internal temperature sensor........................................ 29
L
LED brightness ............................................................ 24LED orientation light ................................................... 24LED-Colour .................................................................. 24
M
Manual mode .............................................................. 31Message communication object .................................. 90Mode controller parameter/control panel ................... 59
O
Operating pages ......................................................... 41
P
Page administration (main levels) ............................... 42Parameter
Temperatures, actual value ..................................... 56Parameter display and operation................................. 46Parameter for channel type ......................................... 83Parameter for roller blinds .......................................... 85
GAMMA instabus
Application program description
September 2017
0705 Contouch Room Controller 970007
Siemens AG 970007, page 101 / 101 Technical ManualInfrastructure & Cities Sector, Building TechnologiesControl Products and Systems ã Siemens AG 2017 Update: http://www.siemens.com/gammaP. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.12.1.14
Parameter objects for display and operation ............... 48Parameter pages ......................................................... 26Presence detector ....................................................... 31
R
Room operating modecomfort mode ......................................................... 31energy-saving mode (nighttime reduction) ............. 31permanent Protection mode ................................... 32Pre-comfort mode (standby) ................................... 31protection mode (frost protection / heat protection)
............................................................................ 31Room operating modes .............................................. 30Room temperature control ......................................... 25
S
Scene number (Scene ID) ........................................... 18Screen control parameter ........................................... 90Send value communication object .............................. 87Send value parameter ................................................. 86
Setpoint value specification ........................................ 29Shutters parameter ..................................................... 84Standby mode ............................................................. 23Surface concept of the control panel .......................... 40Switch channel type .................................................... 13Switch communication objects ................................... 84Switch parameter ........................................................ 83
T
Temperature display ................................................... 25Time and date ............................................................. 25Time program for temperature control ....................... 38Time program of channels .......................................... 38Time programs ............................................................ 37Transfer configuration data ......................................... 45
V
Ventilation .................................................................. 35Ventilation parameters ............................................... 54