Installation Instructions
POINT I/O 2 Current Output and 2 VoltageOutput Analog Modules
Catalog Numbers 1734-OE2C and 1734-OE2V, Series C
Inside
For This Topic See Page
Important User Informat ion 2
Prevent ing Electrostat ic Discharge 3
Environment and Enclosure 4
Before You Begin 5
Ident ify M odule Components 5
Install the M ount ing Base 6
Install the M odule 7
Install the Removable Terminal Block (RTB) 8
Remove a M ount ing Base 9
Communicate w ith Your M odule 11
W ire the M odule 12
Troubleshoot w ith Indicators 15
Nort h Am erican Hazardous Location A pproval 18
European Hazardous Locati on Approval 19
Specifications 20
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
2/24
2 POINT I/ O 2 Current Output and 2 Voltage Output Analog M odules
Publication1734-IN 002C-EN-E - Apri l 2005
Important User Information
Solid state equipment has operational characteristics differing from those ofelectromechanical equipment. Safety Guidelines for the Appl ication, Install ation andM aintenance of Solid State Controls(Publicatio n SGI-1.1 availabl e f rom your l ocal Rockw ellAutomation sales off ice or online at http:// l i terature.rockw ellautomation.com) describessome important diff erences betw een solid state equipment and hard-w iredelectromechanical devices. Because of t his diff erence, and also because of t he w ide varietyof uses for solid state equipmen t, all persons responsible for applying thi s equipment mustsatisfy themselves that each intended application of this equipment is acceptable.
In no event w ill Rockw ell Aut omati on, Inc. be responsible or liable for indirect or
consequential damages resulting f rom the use or application of this equipment .The examples and diagrams in t his manual are included solely for i llustrat ive purposes.Because of the many variables and requirements associated w ith any particular installat ion,Rockw ell Aut omati on, Inc. cannot assume responsibilit y or liability f or actual use based onthe examples and diagrams.
No patent l iabil i t y is assumed by Rockw ell Aut omation, Inc. w ith respect to use ofinformation, circuits, equipment, or software described in this manual.
Reproduction of t he contents of this manual, in w hole or in part, w ithout w ritten permission
of Rockw ell Aut omati on, Inc., is prohibited.Throughout t his manual, w hen necessary, w e use notes to make you aware of safetyconsiderations.
WARNING Identifies information about practices or circumstances that can cause an explosion in ahazardous environment, w hich may lead to personal injury or death, property damage, oreconomic loss.
IMPORTANTIdentifi es information t hat is critical for successful application and understanding of t heproduct.
ATTENTION Identif ies informat ion about practices or circumstances that can lead to personal injury ordeath, property damage, or economic loss. Attentions help you:
identi fy a hazard avoid a hazard recognize t he consequence
SHOCK HAZARD Labels may be located on or inside t he equipment (e.g., drive or motor) to alert peopl ethat dangerous voltage may be present.
BURN HAZARD Labels may be located on or inside t he equipment (e.g., drive or motor) to alert peopl ethat surfaces may be dangerous temperatures.
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
3/24
POINT I/ O 2 Current Output and 2 Voltage Output A nalog M odules 3
Publication 1734-IN 002C-EN-E - Apr il 2005
ATTENTION Preventing Electrostatic DischargeThis equipm ent is sensitive to electrostatic
discharge, w hich can cause internal dam age and
affect norm al operation. Follow these guidelines
w hen you handle this equipm ent:
Touch a grounded object to discharge
potential static.
W ear an approved grounding w riststrap. D o not touch connectors or pins on
com ponent boards.
D o not touch circuit com ponents inside the
equipm ent.
If available, use a static-safe w orkstation.
W hen not in use, store the equipm ent in
appropriate static-safe packaging.
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
4/24
4 POINT I/ O 2 Current Output and 2 Voltage Output Analog M odules
Publication1734-IN 002C-EN-E - Apri l 2005
ATTENTION Environment and Enclosure
This equipm ent is intended for use in a Pollution
D egree 2 industrial environm ent, in overvoltage
Category II applications (as defined in IEC
publication 60664-1), at altitudes up to 2000 m eters
w ithout derating.
This equipm ent is considered G roup 1, Class A
industrial equipm ent according to IEC/CISPR
Publication 11. W ithout appropriate precautions,
there m ay be potential difficulties ensuringelectrom agnetic com patibility in other environm ents
due to conducted as w ell as radiated disturbance.
This equipm ent is supplied as open type
equipm ent. It m ust be m ounted w ithin an enclosure
that is suitably designed for those specific
environm ental conditions that w ill be present and
appropriately designed to prevent personal injuryresulting from accessibility to live parts. The interior
of the enclosure m ust be accessible only by the use
of a tool. Subsequent sections of this publication
m ay contain additional inform ation regarding
specific enclosure type ratings that are required to
com ply w ith certain product safety certifications.
See N EM A Standards publication 250 and IEC
publication 60529, as applicable, for explanations of
the degrees of protection provided by different
types of enclosure. Also, see the appropriate
sections in this publication, as w ell as the
Allen-Bradley publication 1770-4.1 (Industrial
Autom ation W iring and G rounding G uidelines), for
additional installation requirem ents pertaining to
this equipm ent.
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
5/24
POINT I/ O 2 Current Output and 2 Voltage Output A nalog M odules 5
Publication 1734-IN 002C-EN-E - Apr il 2005
Before You Begin
You can use these Series C m odules w ith D eviceN et and PRO FIBU S
adapters. If you are using RSLogix 5000 softw are, version 11 orhigher, you can also use the Series C m odules w ith ControlN et and
Ethernet adapters.
Identify Module Components
U se the figure to identify the external features of the m odules.
Analog
Volta
ge
Outp
ut
Mod
ule
Status
Netw
ork
Status
NOD
E:
0
1
The w iring base assembly includes t erminal base, 1734-TB or 1734-TBS,
43931
Interlocking
Side Pieces
DIN Rail
Locking
Screw
(orange) Removable Terminal Block (RTB)
Slide-in W ritable Label
Insertable I/O M odule
Module
WiringDiagram
M ounting Base
RTB Removab le Handle
Module
Locking
Mechanism
Mechanical
Keying(orange)
w hich consists of mounting base, 1734-M B, and removable terminal block,1734-RTB or 1734-RTBS.
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
6/24
6 POINT I/ O 2 Current Output and 2 Voltage Output Analog M odules
Publication1734-IN 002C-EN-E - Apri l 2005
Install the Mounting Base
To install the m ounting base on the D IN rail, proceed as follow s.
1. Position the m ounting base vertically above the installed units
(adapter, pow er supply, or existing m odule).
2. Slide the m ounting base dow n to m ake the interlocking side
pieces engage the adjacent m odule or adapter.
3. Press firm ly to seat the m ounting base on the D IN rail.
The m ounting base w ill snap into place.
ATTENTION PO IN T I/O is grounded through the D IN rail to
chassis ground. U se zinc-plated, yellow -chrom ated
steel D IN rail to assure proper grounding. The use
of D IN rail m aterials (e.g., alum inum , plastic, etc.)
that can corrode, oxidize, or are poor conductors
can result in im proper or interm ittent grounding.
Secure D IN rail to m ounting surface approxim atelyevery 200 m m .
ATTENTION D o not discard the end cap supplied w ith an
adapter or com m unication interface m odule.
U se this end cap to cover the exposed
interconnections on the last m ounting base on theD IN rail. Failure to do so could result in
equipm ent dam age or injury from electric shock.
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
7/24
POINT I/ O 2 Current Output and 2 Voltage Output A nalog M odules 7
Publication 1734-IN 002C-EN-E - Apr il 2005
Install the Module
Install the m odule before or after base installation. M ake sure that
you:
correctly keyed the m ounting base before installing the
m odule into the m ounting base
positioned the m ounting base locking screw horizontal w ithreference to the base
To install the m odule proceed as follow s.
1. U sing a bladed screw driver, rotate the keysw itch on the
m ounting base clockw ise until the num ber required for the
type of m odule you are installing aligns w ith the notch in the
base.
2. M ake certain the D IN rail locking screw is in the horizontal
position.
You cannot insert the m odule if you have unlocked the
locking m echanism .
3. Insert the m odule straight dow n into the m ounting base andpress to secure.
The m odule w ill lock into place.
WARNING W hen you insert or rem ove the m odule w hilebackplane pow er is on, an electrical arc can occur.
This could cause an explosion in hazardous
location installations.
Be sure that pow er is rem oved or the area is
nonhazardous before proceeding. Repeated
electrical arcing causes excessive w ear to contacts
on both the m odule and its m ating connector. W orn
contacts m ay create electrical resistance that can
affect m odule operation.
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
8/24
8 POINT I/ O 2 Current Output and 2 Voltage Output Analog M odules
Publication1734-IN 002C-EN-E - Apri l 2005
Install the Removable Terminal Block (RTB)
A rem ovable term inal block com es w ith your w iring base assem bly.
To rem ove, pull up on the RTB handle. You can now rem ove them ounting base and replace as necessary w ithout rem oving any of the
w iring. To reinsert the rem ovable term inal block, proceed as follow s.
1. Insert the end opposite the handle into the base unit.
This end has a curved section that engages w ith the w iring
base.
2. Rotate the term inal block into the w iring base until it locks
itself in place.
3. If an I/O m odule is installed, snap th e RTB handle into place
on the m odule.
WARNING W hen you connect or disconnect the rem ovable
term inal block (RTB) w ith field-side pow er
applied, an electrical arc can occur. This could
cause an explosion in hazardous location
installations.
Be sure that pow er is rem oved or the area is
nonhazardous before proceeding.
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
9/24
POINT I/ O 2 Current Output and 2 Voltage Output A nalog M odules 9
Publication 1734-IN 002C-EN-E - Apr il 2005
Remove a Mounting Base
To rem ove a m ounting base, you m ust rem ove any installed m odule,
and the m odule installed in the base to the right. Rem ove therem ovable term inal block, if w ired.
1. U nlatch the RTB handle on the I/O m odule.
2. Pull on the RTB handle to rem ove the rem ovable term inal
block.
3. Press on the m odule lock on the top of the m odule.
4. Pull on the I/O m odule to rem ove from the base.
WARNING W hen you connect or disconnect the rem ovable
term inal block (RTB) w ith field-side pow er
applied, an electrical arc can occur. This could
cause an explosion in hazardous location
installations.
Be sure that pow er is rem oved or the area is
nonhazardous before proceeding.
WARNINGW hen you insert or rem ove the m odule w hile
backplane pow er is on, an electrical arc can occur.
This could cause an explosion in hazardous
location installations.
Be sure that pow er is rem oved or the area is
nonhazardous before proceeding. Repeated
electrical arcing causes excessive w ear to contacts
on both the m odule and its m ating connector. W orn
contacts m ay create electrical resistance that canaffect m odule operation.
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
10/24
10 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules
Publication1734-IN 002C-EN-E - Apri l 2005
5. Repeat steps 1, 2, 3, and 4 for the m odule to the right.
6. U se a sm all-bladed screw driver to rotate the orange, baselocking screw to a vertical position.
This releases the locking m echanism .
7. Lift straight up to rem ove.
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
11/24
POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 11
Publication 1734-IN 002C-EN-E - Apr il 2005
Communicate with Your Module
PO IN T I/O m odules send (consum e) and receive (produce) I/O
m essages. You m ap these m essages into the processors m em ory.
These m odules produce 2 bytes of input data (scanner Rx) (fault
status). These m odules consum e 4 bytes of output data (scanner Tx).
Message size: 2 Bytes
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Produces
(scanner Rx)
High Byte - Channel 1 St atus Low Byte - Channel 0 Stat us
Not used H
C
A
L
C
A
C
M
C
F
Not used H
C
A
L
C
A
C
M
C
F
Where:
CF = Channel Fault st atus; 0 = no error, 1 = faultCM = Calibrati on M ode; 0 = normal, 1 = calibration mode
HCA = High Clamp A larm ; 0 = no error, 1 = fault
LCA = Low Clam p Alarm ; 0 = no error, 1 = fault
Message size: 4 bytes
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Consumes
(scanner Tx)
Output Channel 0 High Byte Output Channel 0 Low Byte
Output Channel 1 High Byte Output Channel 1 Low Byte
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
12/24
12 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules
Publication1734-IN 002C-EN-E - Apri l 2005
Wire the Module
WARNING If you connect or disconnect w iring w hile the
field-side pow er is on, an electrical arc can occur.
This could cause an explosion in hazardous
location installations. Be sure that pow er is
rem oved or the area is nonhazardous before
proceeding.
1734
OE2C
NODE:
0
1
43962
1734-OE2C POINT I/O 2 Current Output Analog Module
M odule Status
Network Status
Status of Output 0Status of Output 1
Output 0 Connection 0 1 Output 1 Connection
5 CChas Gnd = Chassis Ground
C = Common
V = Supply
3 Chas GndChas Gnd 2
C 4
V 6 7 V
Module
Status
Network
Status
4-20mA
Analog
Output
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
13/24
POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 13
Publication 1734-IN 002C-EN-E - Apr il 2005
Channel CurrentOutput
ChassisGround
Common Supply
0 0 2 4 6
1 1 3 5 7
12/ 24V dc pow er is provided by the internal f ield pow er bus.
CurrentOutputDevice
CurrentOutputDevice
2-wire4-wire
ac or dc
43964
Out = Output Channel
Chas Gnd = Chassis Ground
C= Common
V = 12/ 24V dc supply
0 1
32
Out0
Out1
ChasGnd
ChasGnd
54C C
76
VV
1734-OE2C POINT I/O 2 Current Output Analog Module
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
14/24
14 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules
Publication1734-IN 002C-EN-E - Apri l 2005
43963
M odule Status
Netw ork Status
Status of Output 0
Status of Output 1
Output 0 Connection 0
Chas Gnd 2
C 4
V 6
5 C
7 V
Chas Gnd = Chassis g roundC = Comm onV = Supply
1734-OE2V POINT I/O 2 Voltage Output Analog Module
3 Chas Gnd
1734
OE2V
NODE:
0
1
1 Output 1 Connection
Module
Status
Network
Status
Analog
Voltage
Output
Out 0 Out 1
ChasGndChasGnd
C C
VV
VoltageOutput
43965
3
5
7
0 1
2
4
6
VoltageOutput
1734-OE2V POINT I/O 2 Voltage Output Analog Module
Out = Output channelChas Gnd = Chassis GroundC = CommonV = 12/24V dc supply
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
15/24
POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 15
Publication 1734-IN 002C-EN-E - Apr il 2005
Troubleshoot with Indicators
U se the status indicators and tables to troubleshoot your m odule.
Channel Voltage Output Chassis Ground Common Supply0 0 2 4 6
1 1 3 5 7
12/24V dc pow er is provided by the internal f ield pow er bus.
M odule Status
Netw ork Status
1734-OE2C
POINT I/O 2 Current
Output Analog Module
NODE:
0
1
43962
ModuleStatus
NetworkStatus
4-20mAAnalogOutput
Status of Output 0
Status of Output 1
1734-OE2V
POINT I/O 2 Voltage
Output Analog Module
M odule Status
Netw ork Status
NODE:
0
143963
ModuleStatus
Network
Status
AnalogVoltageOutput
Status of Output 0
Status of Output 1
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
16/24
16 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules
Publication1734-IN 002C-EN-E - Apri l 2005
Indication Probable CauseModule Status
Off No pow er is appl ied to device.
Green Device is operat ing normal ly.
Flash ing Green Device needs commission ing due to conf igura t ion missing,
incomplet e, or incorrect.
Flashing Red Recoverable fault is present .Red Unrecoverable fault may require device replacement .
Flashing Red/ Green Device is in sel f -test .
Indication Probable Cause
Network StatusOff Device is not online.
- Device has not completed dup_M AC_id test.
- Device not pow ered. Check module stat us indicator.
Flash ing Green Device i s onl ine but has no connect ions in the establ ished sta te .
Green Device is online and has connect ions in the establ ished state.
Fl ashi ng Re d One or m ore I/ O conne ct ions are i n t im ed-out st at e
Red Crit ical l ink failure is present w ith failed communicat ion device.
Device detected error that prevents it communicat ing on the
network.
Flashing
Red/Green
Communi cation faul ted device is present.
The device detected a net w ork access error and is in communicati on
faulted state.
Device received and accepted an Identif y Communicat ion Faulted
Request - l ong protocol m essage.
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
17/24
POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 17
Publication 1734-IN 002C-EN-E - Apr il 2005
Indication Probable Cause1734-OE2C Probable Cause1734-OE2V
Channel Status
Off M odule is in CAL mode.
Green N ormal operat ion is present w ith channel act ively controll ing
outputs.
Flashing Green Channel is be ing cal ib ra ted.
Flashing Red Open w i re or no f ield pow er is
present.
A low or high clamp is present.
Red - No f ield pow er is present .
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
18/24
18 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules
Publication1734-IN 002C-EN-E - Apri l 2005
North American Hazardous Location Approval
The following information applies whenoperating this equipment in hazardouslocations:
Informations sur lutilisation de cet quipementen environnements dangereux:
Products marked CL I, DIV 2, GP A, B, C, D are suit ablefor use in Class I Division 2 Groups A , B, C, D, HazardousLocations and nonhazardous locations only. Each productis supplied w ith markings on the rating nameplateindicating the hazardous location temperature code. W hencombining products w ithin a system, t he most adversetemperature code (low est T number) may be used tohelp determine the overall temperature code of thesystem. Combinations of equipment in your system are
subject t o investigation by the local Aut hority HavingJurisdiction at the time of i nstallation.
Les produits marqus CL I, DIV 2, GP A, B, C, D neconviennent qu une uti lisatio n en environnements de Classe IDivision 2 Groupes A, B, C, D dangereux et non dangereux.Chaque produit est l ivr avec des marquages sur sa plaquedidentification qui indiquent le code de temprature pour lesenvironnement s dangereux. Lorsque plusieurs produits sontcombins dans un systme, le code de temprature le plusdfavorable (code de temprature le plus faible) peut treutil is pour dterminer le code de temprature global du
systme. Les combinaisons dquip ements dans le systmesont sujettes inspection par les autorits locales qualifiesau moment de l installation.
EXPLOSION HAZARD - Do not disconnect equipment unless
pow er has been removed or t he areais know n to be nonhazardous.
Do not disconnect connections tothis equipment unless power hasbeen removed or the area is knownto be nonhazardous. Secure anyexternal connections that mate tothis equipment by using screws,sliding latches, threadedconnectors, or other means providedw ith this product.
Substitut ion of components mayimpai r suitabili ty for Class I, Division2.
If t his product contains batteries,they must onl y be changed in anarea known to be nonhazardous.
RISQUE DEXPLOSION Couper le courant ou sassurer que
lenvironnement est class nondangereux avant de dbrancherl'quipement.
Couper le courant ou s'assurer quelenvironnement est class nondangereux avant de dbrancher lesconnecteurs. Fixer t ous lesconnecteurs externes relis cetquipement l'aide de vis, loquetscoulissants, connecteurs filets ouautres moyens fourni s avec ceproduit.
La substitution de composants peutrendre cet quipement inadapt uneutil isation en environnement deClasse 1, Division 2.
Sassurer que lenvironnement estclass non dangereux avant dechanger les piles.
WARNING AVERTISSEMENT
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
19/24
POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 19
Publication 1734-IN 002C-EN-E - Apr il 2005
European Hazardous Location Approval
European Zone 2 Certification (The following applies when the product bears theEEx marking)This equipment is intended f or use in potentiall y explosive atmospheres as defined by
European Union Direct ive 94/ 9/ EC.
DEM KO certif ies that thi s equipment has been found to comply wi th the Essential Health
and Safety Requirement s relating to t he design and construction of Category 3 equipment
intended f or use in potenti ally explosive atmospheres, given in Annex II to thi s Directive.
The examinat ion and test results are recorded in confident ial report N o 03NK30347.
Compliance w ith t he Essential Health and Safet y Requirements has been assured bycompliance with EN 50021.
IMPORTANT O bserve the follow ing additional Zone 2 certification
requirem ents.
This equipm ent is not resistant to sunlight or
other sources of U V radiation.
The secondary of a current transform er shall not
be open-circuited w hen applied in Class I, Zone
2 environm ents.
Equipm ent of lesser Enclosure Type Rating m ust
be installed in an enclosure providing at least
IP54 protection w hen applied in Class I, Zone 2
environm ents. This equipm ent shall be used w ithin its specified
ratings defined by Allen-Bradley.
Provision shall be m ade to prevent the rated
voltage from being exceeded by transient
disturbances of m ore than 40% w hen applied in
Class I, Zone 2 environm ents.
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
20/24
20 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules
Publication1734-IN 002C-EN-E - Apri l 2005
Specifications
Output Specifications 1734-OE2C 1734-OE2V
Number of Outputs 2 single-ended, non-isolated
Resolut ion 13 bits - over 0-21mA
2.5A/ cnt (average value -
typical range:
2.3...2.7A/cnt)
14 bits
(13 plus sign)
1.28mV/cnt in unipolar or
bipolar mode
Output Current 0mA output unt i l
communication
established
4-20mA user configurable
0-20mA user configurable
-
Output Voltage - 0V output unt i l
communication
established
0-10V (user configurable)
(-0.0V under, +0.5V over)
+10V user configurable
(-0.5V under, +0.5V over)
Absolute A ccuracy1 Current Output
0.1% Full Scale @ 25oC
Voltage Output
0.1% Full Scale @ 25oC
Accuracy Drift w/Temp. 30ppm/ oC 5ppm/ oC
Step Response to 63% of FS 24 sCurrent Load on
Voltage Output
- 3mA
Resisti ve Load on
Current Output
0...750 -
Conversion Type Digital to analog converter
Conversion Rate 16s 20s
Data Format Signed Integer
Calibrat ion Factory Calibrated
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
21/24
POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 21
Publication 1734-IN 002C-EN-E - Apr il 2005
General Specifications 1734-OE2C 1734-OE2V
M odule Locat ion 1734-TB, 1734-TBS, 1734-TB3, 17340TB3S
w iring base assembly
POINTBus Current 75 mA @5V dc
Pow er Dissipation -
M aximum at 28.8V
750 load on each output
- 1.23 W
0 load on each output
- 1.83 W
1.0W
Thermal Dissipation -
M aximum at 28.8V
75 0load on each output
- 4.19 BTU/hr
0 load on each output
- 6.24 BTU/ hr
3.4BTU/hr
Isolation Voltage
(Continuous-voltage
W ithstand Rating)
50V Continuous
Tested to w ithst and 2200V dc for 60 sNo isolation betw een individual channels
External dc pow er
Supply Voltage
Voltage Range
Supply Current
24V dc nominal
10...28.8V dc
70 mA @ 24V dc (including
outputs @20 mA)
24V dc nominal
10...28.8V dc
35 mA @ 24V dc (including
outputs @3 mA)
Indicators 1 green/ red module status indicator, logic side
1 green/ red netw ork stat us indicator, logic side
2 green/ red output stat us indicators, logic side
Keysw itch Posit ion 4
Dimensions H x W x L
56 x 12 x 75.5 mm (2.21 x 0.47 x 2.97 in)
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
22/24
22 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules
Publication1734-IN 002C-EN-E - Apri l 2005
General Specifications(Continued)
1734-OE2C 1734-OE2V
Operat ional Temperature IEC 60068-2-1 (Test Ad, Operat ing Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb , Operati ng Thermal Shock):
-20 55 C (-4 131 F)
Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperat i ng Co ld ),
IEC 60068-2 -2 (Test Bb, Unpackaged N onopera ti ng Dry
Heat),
IEC 60068-2 -14 (Test N a, Unpackaged N onopera ti ng
Thermal Shock):
-40 85 C (-40 185 F)
Relat ive Humidity IEC 60068-2-30
(Test Db, Unpackaged Nonoperating Damp Heat):
5 95% noncondensing
Vibrat ion IEC60068-2-6 (Test Fc, Operat ing)
5 g @ 10...500 Hz
Shock
Operating
Non-Operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
50 g
Emissions CISPR 11: Group 1, Class A
ESD Immunity IEC6100-4-2
6 kV contact di scharges
8 kV air discharges
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
23/24
POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 23
Publication 1734-IN 002C-EN-E - Apr il 2005
General Specifications(Continued)
1734-OE2C 1734-OE2V
Radiated RF Immunity IEC 61000-4-3:
10 V/ m w ith 1kHz sine-wave 80% AM from 30 M Hz to
2000 M Hz
10 V/ m w ith 200 Hz 50% Pulse 100% AM at 900 M hz
10 V/ m w ith 200 Hz 50% Pulse 100% AM at 1890 M Hz
EFT/ B Immunit y IEC 61000-4-4:3 kV at 2.5 kHz on signal port s
Surge Transien t Immuni ty IEC 61000-4 -5:
2 kV line-earth(CM ) on shielded ports
Conduct ed RF Immunit y IEC61000-4-6
10 Vrms w ith 1 kHz sine-w ave 80% AM
from 150 kHz to 80 M Hz
Enclosure Type Rat ing N one (open-style)
W ire Size 14 AW G (2.5mm2) - 22 AW G (0.25mm 2) solid or stranded
copper w ire rated at 75 oC or greater
3/ 64 inch (1.2 mm) insulation m aximum
W ire Category2 1 - on signal ports
Terminal Base Screw Torque 0.6 Nm (7 lb-in)
W eight 0.036 kg (0.08 lb)
Publ ica ti ons - User M anua l 1734-UM 001
7/25/2019 Ult REL Output Analog Modules 1734-In002 En
24/24
Publication1734-IN002C-EN-E - April 2005 PN 957955-48Supersedes Publication 1734-IN002B-EN-P - April 2002 and
Certification3 (When Product is Marked) 1734-OE2C 1734-OE2V
c-UL-us UL Listed Industrial Control Equipment ,
certif ied for U.S. and Canada
c-UL-us UL Listed for Class I, Divi sion 2 Group A,B,C,D
Hazardous Locati ons, certif ied for U.S. and Canada
CE European Union 89/ 336/EEC EM C Directive,
compliant w ith:
EN 50082-2; Industrial Immuni ty EN 61326; M eas./Control/ Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immuni ty
EN 61000-6-4; Industrial Emissions
C-Tick Austral ian Radiocommuni cations Act ,
compliant w ith:
AS/ NZS CISPR 11, Industri al Emi ssions
EEX European Union 94/ 9/ EC ATEX Direct ive,
compliant w ith: EN 50021; Potent iall y Explosive At mospheres,
Protecti on n (Zone 2)
X
X
X
X
X
X
X
X
X
1. Includes off set, gain, non-linearit y and repeatabil ity error terms.2. Use this Category information for planning routing. Refer to Industrial Automation W iring and Grounding Guidelines, publicati on 1770-4.1.3. See the Product Certification l ink at w w w.ab.com f or Declarations of Conformity, Certificates, and other certification details.
PO IN T I/O , PO IN TBus, and RSLogix 5000 are tradem arks of Rockw ell Autom ation.ControlN et is a tradem ark of ControlN et International, Ltd.D eviceN et is a tradem ark of O pen D eviceN et Vendor Association.