Treatment of Mechanical Extract Ventilation and Balanced Whole House Mechanical Ventilation

in DEAP

Date October-2007

Definition of Ventilation Systems Ref: DEAP Manual Section 2.6

Mechanical extract ventilation (MEV):is a fan driven ventilation system, which only extracts air from the dwelling. The DEAP calculation is based on a throughput of 0.5 air changes per hour through the mechanical system, plus infiltration.

Balanced whole house mechanical ventilation no heat recovery (MVNHR):is a fan driven ventilation system, which provides fresh air to the rooms in the dwelling and also extracts exhaust air from the dwelling. The system is not fitted with a heat recovery unit. The DEAP calculation in such cases is based on a throughput of 0.5 air changes per hour through the mechanical system, plus infiltration.

Balanced whole house mechanical ventilation with heat recovery (MVHR):

is a fan driven ventilation system, which provides fresh air to the rooms in the dwelling and also extracts exhaust air from the dwelling. The system is fitted with a heat recovery unit. The DEAP calculation in such cases is based on a throughput of 0.5 air changes per hour through the mechanical system, plus infiltration. The heat loss by mechanical ventilation is reduced by the factor v where v = 0.66 is the default efficiency assumed for the heat recovery system.

DEAP Default Data: Specific Fan Power

• The fans in mechanical ventilation system consume electricity.

• The electricity consumption is reflected by the specific fan power (SFP) of the unit.

• Default SFPs are detailed in DEAP Table 4g:

System Type SFP

MEV 0.8 W/litre/sec

MVNHR 2.0 W/litre/sec

MVHR 2.0 W/litre/sec

DEAP Default Data: Heat Exchanger Efficiency

• MVHR systems recover heat from the exhaust air and use this to warm inlet air.

• The efficiency of the heat recovery system is reflected in the rated heat exchanger efficiency of the unit.

• The default heat exchanger efficiency used in DEAP is 66%

• The DEAP software uses the default data unless otherwise specified

Treatment of Mechanical Ventilation Heat Recovery Systems in DEAP (default values)

Select appropriate ventilation system and default values are

automatically used

Treatment of Mechanical Ventilation Heat Recovery Systems in DEAP (default values)

Click here and you will see the default values

Testing Ventilation Systems• Test methods• Developed by EST (Energy Saving Trust), BRE (Building Research

Establishment), TEHVA (The Electric Heating and Ventilation Association), RVA (Residential Ventilation Association)

• Based on the European standards • Must be read alongside the European standards:

• BS EN 13141-6:2004 to define the duct configurations• BS EN 13141-7:2004 covering testing of heat recovery ventilation• MVHR Test temperatures

Operation of MEV Systems

Kitchen exhaust

Bathroom exhaust

Toilet exhaust

Outlet terminal

Fan unit

1. SFP (W/litre/sec) - power input to the fan at the minimum flow rate at each operating point when the system is installed in accordance with the manufacturers instructions.

Operation of MVHR Systems

Bedroom 1

supply Bedroom 2

supplyLounge supply

Kitchen/dinner supply

Kitchen exhaust

Bathroom exhaust

Toilet exhaust

Duct from fan to Outlet terminal

Duct from fan to Supply terminal

Heat recovery and fan unit

T1 T4

T3 T2

1. SFP (W/litre/sec) - power input to the fans at the minimum flow rate at each operating point when the system is installed in accordance with the manufacturers instructions.

2. Thermal performance (efficiency) of assembled supply and exhaust package with heat recovery used for a single dwelling (T2 - T1) / (T3 – T1)

Operation of MVNHR Systems

Bedroom 1

supply Bedroom 2

supplyLounge supply

Kitchen/dinner supply

Kitchen exhaust

Bathroom exhaust

Toilet exhaust

Duct from fan to Outlet terminal

Duct from fan to Supply terminal

Fan unit

1. SFP (W/litre/sec) - power input to the fans at the minimum flow rate at each operating point when the system is installed in accordance with the manufacturers instructions.

Procedure for Handling Ventilation Systems with more Efficient Parameter Data

1. Search the SAP Appendix Q Product Database (www.sap-appendixq.org.uk )

2. Use the product specification to identify the appropriate specific fan power or the SFP and Heat exchanger efficiency for the configuration that best matches that of the particular dwelling – including the nature of the ductwork, viz. rigid or flexible.

3. Enter the specific fan or the specific fan power and heat exchanger efficiency values directly in to DEAP software, Ventilation tab.

Example

Search SAP Appendix Q Databasewww.sap-appendixq.org.uk

Search SAP Appendix Q Databasewww.sap-appendixq.org.uk

Search SAP Appendix Q Databasewww.sap-appendixq.org.uk

Refer to the Specification for the Appropriate Product (example below)

Select the Specific Fan Power and Heat Exchanger Efficiency (if MVHR) for the

configuration that best fits the assessment dwelling

ExampleExample

Enter the Data into DEAP Software, Ventilation Tab

Energy saved by MVHR system should not also be entered into Energy Requirements, Fuel Data Tab

Other Considerations• Dwellings with MEV/MVHR systems will yield better

BERs when combined with improved air tightness measures.

• If a product is not listed on SAP Appendix Q, product manufacturers should refer to the “Testing Standards” page on SAP Appendix Q website for details of how to get a product listed.

DEAP Queries

• Refer to guidance in DEAP manual

• Check FAQ section of www.sei.ie/ber

• Email deap@sei.ie