SIEMENS 3WLAir Circuit Breakers
The SENTRON 3WL circuit breaker takes into account the increased demands made on air circuit breakers in terms of operator control and monitoring of networks. With it’s great flexibility it can be used as an incoming-feeder, distribution, tie, and outgoing-feeder circuit breakers in electrical installations or for switching and protecting motors, capacitors, generators,transformers, busbars and cables.
It is easy to use and universally communication-capable. Connected to an electronic control system, it offers comprehensive possibilities for monitoring of network events.
Highlights
• Universalcommunicationsolutions,whichcanalsobeusedincombinationwiththe3VLMCCB.
•Withonlythreesizes,theSENTRON3WLcoversapowerrangefrom630to6300Awithamodulardesignanduniversal,uniformaccessoriesacrossallsizes.
• Simpleplanning,assemblyandretrofittingasaresultofthemodulardesign
Now AvailableRetro Fit Kits to Replace most old ACB’s with Siemens 3WL ACB’s
Switching, Protection, Measuring and Monitoring Devices
SENT
RON
3WLA
ir Ci
rcui
t Bre
aker
s
your link to the worlds best products www.ramelec.com.au 1
Air Circuit Breakers3WL air circuit breakers
Overviewofcomponentsandaccessoryparts
Modulardesignofthecircuitbreakerwithstandardizedaccessories
your link to the worlds best products www.ramelec.com.au 2
Air Circuit Breakers3WL air circuit breakers
BenefitsLow space requirementsTheSENTRON3WLdevicesrequireverylittlespace.SizeIdevices(upto1600A)fitintoa400mmwideswitchgearpanel.SizeIIIdevices(upto6300A)arethesmallestoftheirkindandwiththeirconstructionwidthof704mmfitintoa800mmwideswitchgearpanel.
Modular designComponentslikeauxiliaryreleases,motorizedoperatingmechanisms,electronicreleases,currentsensors,auxiliarycircuitsignalingswitches,automaticresetdevices,interlocksandengagementoperatingmechanismscanallbeexchangedorretrofittedatalaterstage,thusallowingthecircuitbreakertobeadaptedtonew,changingrequirements.Themaincontactelementscanallbereplacedinordertoincreasetheenduranceofthecircuitbreaker.
Retrofittable modules for electronic releasesModularityisoneofthemainfeaturesofthenewSENTRON3WLcircuitbreakers.SpecialLCDs,ground-faultmodules,ratedcurrentmodulesandcommunicationmodulesfortheelectronicreleasesareavailableforfastandeasyretrofittingandadaptationtochangingrequirements.
CommunicationTheuseofmoderncommunication-capablecircuitbreakersopensupcompletelynewpossibilitiesintermsofstart-up,parameterization,diagnostics,maintenanceandoperation.Thisallowsmanydifferentwaysofreducingcostsandimprovingproductivityinindustrialplants,buildingsandinfrastructureprojectstobeachieved.
FlexibilityThe3WLhasasecondparametersetthatcanbeselected.Ifthelinesupplyconditionschangeeg.whenchangingovertogeneratoroperation,the3WLautomaticallychangesovertothesecondparametersetinbesttime,optimallyadaptingthetripunitcharacteristicstothenewsituation.
Partial Load ProtectionThe3WLoptimallyprotectsyourplantorsystemevenunderpartialloadconditionsusingaRatedCurrentModulethecircuitbreakercanbesetinjustsecondstomatchtheratedcurrent.
International standards and approvals•IEC60947-2
•DINVDE0690Part1
•Climate-proofacc.toDINIEC68Part30-2
•CCC,Gost
•Shipbuilding,e.g.:GL,ABS,LRS,PRS.DesignsaccordingtoUL489arealsoavailableforinternationaluse.3WLaircircuitbreakers/non-automaticaircircuitbreakersaccordingtoUL489upto5000A.
Figure1:3WLaircircuitbreaker,withdrawable Figure2:3WLaircircuitbreaker,fixedmounting
your link to the worlds best products www.ramelec.com.au 3
Air Circuit BreakersTechnical Specifications
Standard-- Not available
Optional1) ETU15B cannot be used with 3WL circuit breakers, size III.
3WL air circuit breakers/non-automatic air circuit breakers according to UL 489 up to 5000 A, see Catalog LV 16. SENTRON transfer switching control unit for ATSE, see chapter "Monitoring devices".
Air circuit breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC)
3WL non-automatic air circuit breakers up to 4000 A (DC)
Size I, II, III II
Rated current In A 630, 800, 1000, 1250, 1600, 2000, 2500, 3200, 4000, 5000, 6300
1000, 2000, 4000
Number of poles 3-pole, 4-pole 3-pole, 4-pole
Rated operationalvoltage Ue
V ACV DC
... 690/1000/1150--
--... 1000
Rated ultimateshort-circuit breaking capacity at 500 V AC
kA
Size I
55/66
Size II
66/80/100
Size III
100/150 (3-pole), 130 (4-pole)
30/25/20 (at 300/600/1000 V DC)
Endurance Operating cycles
20000 15000 10000 15000
Mounting position
Degree of protectionWith cover IP55 IP55Without cover (with door sealing frame)
IP41 IP41
Dimensions 3-/4-pole
W mm 320/410 460/590 704/914 460/590
Fixed mounting
H mm 434 434 434 434D mm 291 291 291 291
Withdraw-able
H mm 465,5 465,5 465,5 465,5D mm 471 471 471 471
Type ETU15B 1) ETU25B ETU27B ETU45B ETU76BElectronic releases for SENTRON 3WL circuit breakersOverload protection
Short-time delayed short-circuit protection
--
Instantaneous short-circuit protection
Neutral conductor protection -- --
Ground-fault protection -- --
Zone Selective Interlocking -- -- --
LCD, 4-line -- -- -- --
LCD, graphic -- -- -- --
Communication throughPROFIBUS DP
-- -- --
Measurement function Plus -- -- --
Selectable parameter sets -- -- -- --
Parameters freely programmable -- -- -- --
CubicleBUS -- -- --
Size IIISize IISize I
NSE0_00061a
30° 30°
NSE0_00062a
30° 30°
NSE0_00061a
30° 30°
NSE0_00062a
30° 30°
NSS0_00535
H
B T
NS
E0_
0110
6a
NS
E0_
0110
7a
NS
E0_
0110
8a
NS
E0_
0110
9a Rating Plug
NS
E0_
0111
1a
W D
your link to the worlds best products www.ramelec.com.au 4
Air Circuit BreakersSwitching Capacity
1) Size II with In max ��2500 A. 2) Size II with In max = 3200 A and In max = 4000 A. 3) At a rated voltage of �� 690 V the Icw value of the circuit breaker cannot be
greater than the Icu or Ics value at 690 V. 4) Rated operational voltage Ue = 1150 V. 5) At Ue = 220 V DC. 6) At Ue = 300 V DC. 7) At Ue = 600 V DC. 8) At Ue = 1000 V DC.
Size I II III
Type 3WL11 3WL12 3WL13
Switching capacity class N
S
N
S
H
H
C3-pole
C4-pole
Short-circuit breaking capacityRated operational voltage Ue up to 415 V AC
Icu kA 55 66 66 80 100 100 150 130
Ics kA 55 66 66 80 100 100 150 130
Icm kA 121 145 145 176 220 220 330 286
Rated operational voltage Ue up to 500 V AC
Icu kA 55 66 66 80 100 100 150 130
Ics kA 55 66 66 80 100 100 150 130
Icm kA 121 145 145 176 220 220 330 286
Rated operational voltage Ue up to 690 V AC
Icu kA 42 50 50 75 85 85 150 130
Ics kA 42 50 50 75 85 85 150 130
Icm kA 88 105 105 165 187 187 330 286
Rated operational voltage Ue up to 1000 V/1150 V AC
Icu kA -- -- -- -- 50 50 704) 704)
Ics kA -- -- -- -- 50 50 704) 704)
Icm kA -- -- -- -- 105 105 154 4) 154 4)
Rated short-time withstand current I cw of the circuit breakers3)
0.5 s kA 55 66 66 80 100 100 100 100Aks 1 42 50 55 66 80 100 100 100Aks 2 29,5 35 39 46 651)/702) 80 80 80
3 s kA 24 29 32 37 501)/652) 65 65 65Short-circuit breaking capacity I cc of the non-automatic air circuit breakersUp to 500 V AC kA 55 66 66 80 100 100 100 100
AkCA V 096 ot pU 42 50 50 75 85 85 100 100
Up to 1,000 V /1150 V AC kA -- -- -- -- 504) 504) 704) 704)
Size II
Type 3WL12
Switching capacity class DCShort-circuit breaking capacityUp to 220 V DCUp to 300 V DCUp to 600 V DCUp to 1000 V DC
Icc Icc Icc Icc
kAkAkAkA
35302520
Rated short-time withstand current I cw0.5 s1 s2 s3 s
kAkAkAkA
--355)/306)/257)/208) ----
N S N S H H C C
DC
Circuit breaker with ECO switching capacity N
Circuit breaker with standard switching capacity S
Circuit breaker with high switching capacity H
Circuit breakers with very high switching capacity C
Non-automatic air circuit breakers with DC switching capacity
N
S
H
C
DC
your link to the worlds best products www.ramelec.com.au
Available for most brands
By installing the SIEMENS complete ACB and retrofit kit inside an existing cradle you can minimize costs
and shut down times.
SIEMENSretrofitkitshavebeendesignedandmanufacturedinAustraliabyKentanEngineering.
WiththeageingofmanyACB’sinstalledthroughoutthecountry,oftenreplacementpartsarenolongeravailable
orsparepartshaveexorbitantcosts.
TheSiemens3WLACBfittedinaNilsenNABcradle
ShowingtheuppersetofextensionbarsconnectedtotheACB
SIEMENS AIR CIRCUIT BREAKERRETRO FIT KITS
your link to the worlds best products www.ramelec.com.au
Each application has the kit manufactured to order. Each kit contains all the necessary extension bars,
supports, bolts etc and a complete set of instructions showing step by step how to fit the ACB’s together.
ExtensionbarsconnectingtheACBtotheexistingcradle.
TheSiemenscradleandACBmountedinsidetheNilsencradle
Contact Ramelec for details on 3WL Retro Fit kits.
INSTALLATION
INSTRUCTIONS
_________________
SIEMENS3WL1AIR
CIRCUITBREAKER
RETROFITKIT
-FOR-
NILSENNAB1/D16AIR
CIRCUITBREAKER
Ramelec (SA) Pty Ltd13-15 Shepley AvenuePanorama SA 5041Tel: 08 8374 2100Fax: 08 8299 0770
Ramelec (QLD) Pty Ltd2/5 Breene PlaceMorningside QLD 4170Tel: 07 3899 1322Fax: 07 3899 1422
Ramelec (NSW) Pty LtdP1 10 – 16 South StRydalmere NSW 2116Tel: 02 9684 6700Fax: 02 9684 6722
Ramelec (VIC) Pty Ltd8 Enterprise CourtMulgrave VIC 3171Tel: 03 9808 9800Fax: 03 9808 9855
Ramelec (WA) Pty Ltd56 Millrose DriveMalaga WA 6090Tel: 08 9249 9155Fax: 08 9249 9418
Ramelec Electronics Pty Ltd13-15 Shepley AvenuePanorama SA 5041Tel: 1300 309 150Fax: 1300 309 152
NewcastleEnvironmental Controls & Instrumentation171 Main RdSpeers Point NSW 2284Tel: (02) 4958 9977Fax: (02) 4958 9400
Darwin (NT)Ramelec Pty LtdTel: 1300 309 303Fax: 1300 309 308
Ramelec Electronics (H.K.) CO.5/F, East Asia Textiles Industrial Building, 2 Ho Tin Street, Tuen Mun, N.T. Hong Kong
Ramelec Main Offi ces:
Ramelec Regional Offi ces:
Your link to the worlds best products www.ramelec.com.au
TEL: 1300 309 303 FAX: 1300 309 308Enquiries sales@ramelec.com.au
Visit us www.ramelec.com.au
CONTACT US
Sensors & Controls
McDonnell & MillerTheinformationprovidedinthisbrochurecontainsmerelygeneraldescriptionsorcharacteristicsofperformancewhichinactualcaseofusedonotalwaysapplyasdescribedorwhichmaychangeasaresultoffurtherdevelopmentoftheproducts.Anobligationtoprovidetherespectivecharacteristicsshallonlyexistifexpresslyagreedinthetermsofcontract.AllproductdesignationsmaybetrademarksorproductnamesofRamelecPtyLtdorsuppliercompanieswhoseusebythirdpartiesfortheirownpurposescouldviolatetherightsoftheowners. RE
F-85
8v2 G
IANT
GRA
PHICS
08 81
11 51
30