Catalog HA 41.21 · 2007
The products and systems described in this catalogare manufactured and sold according to a certifiedquality and environmental management system(acc. to ISO 9001 and ISO 14001).(DQS Certificate Reg. No. DQS 003473 QM UM).The certificate is accepted in all IQNet countries.
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 20072
Pages
Application, Requirements
Typical uses, features 2 and 3
Technical Data
Electrical data, pressure values,temperature 4 and 5Switchgear installation 6Shipping data 7
Product Range
Product range overview, equipmentfeatures 8 and 9Panels 10 to 15
Design
Panel design 16 and 17
Components
3AH vacuum circuit-breakers 18 to 20Three-position switches 21Busbars, HV HRC fuse assembly 22 and 23Operating mechanisms 24Indicating and measuring equipment 25 to 27Interlocking systems and locking devices 28Transformers 29 to 31Cable connection 32 and 33Low-voltage equipment 34
Dimensions
Panels 35 to 41Floor openings, fixing points 42
Standards
Standards, specifications, guidelines, 43 to 46classification
Notes
46
Supersedes: Catalog HA 41.21 · 2005
Example4-panel transfer switchgear withintegrated low-voltage niche
R-HA
41-0
82ep
s
R-HA
41-0
55ep
s
Utilities transfer substationfor industrial plants
Typical uses
�������� � �������
© Siemens AG 2007
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 3
� �������� "�#���$����
Reliability
• Type and routine-tested *
• Standardized and manu-factured using numericallycontrolled machines
• Quality management systemaccording to DIN EN ISO 9001
• More than 450,000 switchgearcomponents in operationworldwide for many years
• No cross-insulation betweenphases
Personal safety
• All switching operations canbe performed with closedpanel front
• Metal-enclosed LSC 2 A orLSC 2 B panels
• HV HRC fuses and cable seal-ing ends are only accessiblewhen the outgoing feeders areearthed
• Logical mechanical interlocking
• Capacitive voltage detectionsystem for verification of safeisolation from supply
• Earthing of outgoing feedersby means of make-proofearthing switches
Security of operation
• Components, e.g. operatingmechanisms, three-positionswitches, vacuum circuit-breakers proven for years
• LSC 2 B panels (metal com-partmentalization betweenbusbar and switching deviceand between switching deviceand cable connection compart-ment)
• LSC 2 A panels with metalcompartmentalizationbetween switching deviceand busbar compartment
• Three-position switch metal-enclosed with gas-insulatedswitching functions
– Welded sealed-for-lifeswitchgear vessel
– No cross-insulation betweenphases
– With welded-in bushings forcable connection, busbar andoperating mechanism
• Switch operating mechanismsoutside switchgear vessel
• Maintenance-free operatingmechanism parts (IEC 60 694/VDE 0670-1000 *)
SIMOSEC switchgear is afactory-assembled, type-tested, three-phase, metal-enclosed, indoor switchgearaccording to IEC 62 271-200 *for single busbars.
Typical uses
SIMOSEC switchgear isused for power distribution indistribution systems withfeeder currents up to 1250 A.
Modular space-saving designallows use in
• Substations, customer trans-fer substations, distributionsubstations and switchingsubstations of power supplyand public utilities
• Public buildings, such ashigh-rise buildings, railwaystations, hospitals
• Industrial plants
Typical examples
• Wind power stations
• High-rise buildings
• Airports
• Underground railway stations
• Sewage treatment plants
• Port facilities
• Traction power supplysystems
• Automobile industry
• Petroleum industry
• Chemical industry
• Unit-type heating powerstations
• Textile, paper andfood industry
• Emergency power supplyinstallations
Modular design
• Individual panels, for freecombination and extension
• Option: Low-voltage com-partments can be supplied intwo overall heights
Technical features
• Air-insulated indoorswitchgear
• Gas-insulated, maintenance-free switching functions forthe three-position switch
• Partition class: PM(metallic partition)
• Three-pole primary enclosure
• Phases arranged one behindthe other
• No cross-insulation betweenphases
• Busbar system at the top
• Air-insulated busbar and cableconnection system
• Three-position switch, metal-enclosed, with air-insulatedprimary terminals and gas-insulated switching functions
• Vacuum circuit-breaker 3AH5,metal-enclosed, up to 630 A,fixed-mounted in gas-insulatedswitchgear vessel
• Vacuum circuit-breaker 3AH6,air-insulated, up to 1250 A,easy to remove after looseningthe fixing bolts
• Hermetically-sealed bywelding, stainless-steelswitchgear vessel,
– For switching devices– With welded-in bushings
(for electrical connections andmechanical components)
– With insulating gas SF6
• LSC 2 A or LSC 2 B panels
• Pressure relief– To the rear and upwards– Separately for each
compartment
• Air-insulated cable connectionsystem for conventional cablesealing ends
• Three-phase current trans-former, factory-assembled onthe feeder bushings
• Integrated low-voltage niche(standard) for installationof, e.g.
– Terminals, MCBs, push-buttons
– Protection devices
• Option: Top-mounted low-voltage compartment
• Option: Panel heating forsevere ambient conditions,e.g. condensation
• Mechanical switch positionindications integrated inmimic diagram
• Switchgear interlockingsystem with logicalmechanical interlocks
Reavailability
• Three-position switch discon-nector with gas-insulated,maintenance-free quenchingprinciple
• Metal compartmentalizationbetween busbar compart-ment, switching devices andcable connection compart-ment
• Separate pressure relief foreach compartment
• Cable testing without theneed to isolate the busbar
• Mounting location of three-phase current transformer forselective disconnection ofcircuit-breaker feeders
Cost-efficiency
Extremely low life-cycle costsand extremely high availabilitythroughout the entire productservice life cycle as a result of:
• Three-position switch withgas-insulated quenchingprinciple
• 3AH vacuum circuit-breaker
• Minimum space requirement
• Easy switchgear extension
• Standard protection relays,e.g. multifunction protectionSIPROTEC 4
Electrical features
• Rated voltages up to 24 kV
• Rated short-time withstandcurrent up to 25 kA
• Rated normal current offeeders
– Up to 630 A, e.g. forring-main, metering andcircuit-breaker panels
– Up to 1250 A, forcircuit-breaker and bussectionalizer panels
• Rated normal current ofbusbar up to 1250 A
* Standards see page 43
Features
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 20074
Electrical data of panels, pressure values, temperature
1) The rated normal currents apply to ambient tempera-tures of 40 °C. The 24-hour-mean value is max. 35 °C(according to IEC 60 694 / VDE 0670-1000)
2) Pressure values for SF6-insulated vessels
* Type designationof the vacuumcircuit-breaker
Common details on electrical data, filling pressure and temperature
Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24
Rated short-dur. power-freq. withstand voltage Ud kV 20 28 36 38 50Rated lightning impulse withstand voltage Up kV 60 75 95 95 125
Rated frequency fr 50/60 HzRated normal current Ir 1)
of busbarStandard 630 AOption 1250 A
Rated short-timewithstand current Ik
for switchgear with tk = 1 s up to kA 20 25 20 25 16 20 25 16 20 25 16 20for switchgear with tk = 3 s up to kA 20 – 20 – – 20 – – 20 – – 20
Rated peak withstand current Ip up to kA 50 63 50 63 40 50 63 40 50 63 40 50Rated filling pressure pre 2) for insulation 1500 hPa (absolute) at 20 °CMinimum operating pressure pme 2) for insulation 1300 hPa (absolute) at 20 °CAmbient temperature T for panels without secondary equipment on request: Class “Minus 25 indoor” (– 25 °C to +55 °C)
for panels with secondary equipment Class “Minus 5 indoor” (– 5 °C to +55 °C)
Ring-main panel type RK and cable connection panel type K, K-E
Rated normal current Ir 1) for feeder and transfer, panel type RK 630 A (standard), 400 A (on request)for feeder, panel type K, K-E 630 A (standard), 400 A (on request)for feeder, panel type K1, K1-E 630 A (standard), 1250 A
Rated short-circuit making current Ima up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Transformer panel type TR
Rated normal current Ir 1) for feeder 3) 200 ARated peak withstand current Ip 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50Rated short-circuit making current Ima 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50Reference dimension “e“ for HV HRC fuse links mm 292 4) 292 442 442 442
Circuit-breaker panel type LS
Rated normal current Ir 1) f. panel type LS1 and LS1-U 3AH5 * 630 Af. panel type LS11 and LS11-U 3AH6 * 630 Af. panel type LS31, LS32 and LS31-U 3AH6 * 1250 A
Rated short-circuit making current Ima up to kA 50 63 50 63 40 50 63 40 50 63 40 50Rated short-circuit breaking current Isc for 3AH vacuum circuit-breaker up to kA 20 25 20 25 16 20 25 16 20 25 16 20
Busbar earthing panel type SE
Rated short-circuit making current Ima up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Busbar voltage metering panels type ME3 and type ME31-F
Rated peak withstand current Ip 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50Rated short-circuit making current Ima 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50Reference dim. “e“ in panel type ME31-F for HV HRC fuse links 292 mm
Billing metering panels type ME1
Rated normal current Ir 1) for transfer, panel types ME1 and ME1-H 630 A, 1250 Afor feeder as cable-connection panel type ME1-K 630 A, 1250 Afor busbar connection, panel type ME1-S 630 A, 1250 Afor bus riser panel type HF 630 A, 1250 A
Bus sectionalizer panels type LT
Rated normal current Ir 1) for panel types LT10 and HF, with 3AH5 * 630 Afor panel type LT1, with 3AH5 *: On request 630 Afor panel types LT11 and HF, with 3AH6 * 630 Afor panel types LT2 and LT22 630 Afor panel types LT31 and HF, with 3AH6 * 1250 A
Rated short-circuit making current Ima up to kA 50 63 50 63 40 50 63 40 50 63 40 50Rated short-circuit breaking current Isc for 3AH vacuum circuit-breaker up to kA 20 25 20 25 16 20 25 16 20 25 16 20Electrical service life for 3AH vacuum circuit-breaker:
at rated normal current Ir 1) 10,000 operating cyclesat rated short-circuit breaking current Isc 50 breaking operations, 35 breaking operations on
3AH6 * with 25 kA
for feeder for transfer with
3) For panel types TR and ME31-F depending on the max.cut-off current of the HV HRC fuse link (ID w 25 kA)
4) With reference dimension e = 192 mm, an extension tube(100 mm long) is additionally required for fuse mounting 292 mm
�������� %�
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 5
1) Depending on the HV HRCfuse links
* Higher values of electrical data available on request
** Indications in parenthesis acc. to previous standards
Electrical data * of the switching devices
�������� %�
Make-proof earth-ing function ofthe three-positionswitch-disconnectorMake-proof earth-ing function in fee-der of panels LS11,LS31 and LS32Earthing functionof the three-positiondisconnector
HA41
-29a
eps
Three-position switch-disconnector
Rated insulationlevel
Rated voltage Ur kV 7.2 12 15 17.5 24
Rated short-duration power-frequency withstand volt. Ud kV 20 28 36 38 50
Rated lightning impulse withstand voltage Up kV 60 75 95 95 125
Rated frequency fr Hz 50/60 50/60 50/60 50/60 50/60
Rated normalcurrent for
ring-main feeders Ir A 400, 630 400, 630 400, 630 400, 630 400, 630
transformer feeders 1) Ir A 200 200 200 200 200
Rated short-timewithstand current
for switchgear with tk = 1 s Ik up to kA 25 25 25 25 20
for switchgear with tk = 3 s Ik kA 20 20 20 20 20
Rated peak withstand current Ip up to kA 63 63 63 63 50
Rated short-circuitmaking current for
transformer feeders 2) Ima kA 25 25 25 25 25
ring-main feeders Ima up to kA 63 63 63 63 50
Mechanical stability (class M1) No. of operating cycles 1000 1000 1000 1000 1000
Switching capacity of general-purpose switches (class E3) according to IEC 60 265-1 / VDE 0670 Part 301 (Standards see page 43)
Test duty 1 Rated mainly active for 100 switching operations I1 A 630 630 630 630 630load breaking current for 20 switching operations I1 A 31.5 31.5 31.5 31.5 31.5
Test duty 2a Rated closed-loop breaking current I2a A 630 630 630 630 630
Test duty 3 Rated transformer breaking current I3 A 40 40 40 40 40
Test duty 4a Rated cable-charging breaking current I4a (IC or I6)** A 68 68 68 68 68
Test duty 4b Rated line-charging breaking current I4b A 68 68 68 68 68
Test duty 5 Rated short-circuit making current Ima up to kA 63 63 63 63 50
Test duty 6a Rated earth-fault breaking current I6a (Ie)** A 60 60 60 60 60
Test duty 6b Rated cable-charging breaking current and line- I6b Acharging breaking current under earth-fault conditions (HJ3 v ICL)**
35 35 35 35 35
– Cable-charging breaking current under IL + HJ3 v ICL Aearth-fault conditions with superimposed load current
630+50 630+50 630+50 630+50 630+50
Switching capacity of switch-disconnector/fuse combination (Standards see page 43)
Rated transfer current I4 A 1150 1150 830 830 830
Earthing switch
Rated voltage Ur kV 7.2 12 15 17.5 24
Rated short-circuit making current Ima up to kA 63 63 63 63 50
Rated short-time withstand current Ik up to kA 25 25 25 25 20
Rated short-circuit making current Ima up to kA 63 63 63 63 50
Rated short-time withstand current Ik up to kA 25 25 25 25 20
Rated short-time withstand current Ik up to kA 25 25 25 25 20
3AH5 and 3AH6 vacuum circuit-breakers
Rated insulationlevel
Rated voltage Ur kV 7.2 12 15 17.5 24
Rated short-duration power-frequency withstand volt. Ud kV 20 28 36 38 50
Rated lightning impulse withstand voltage Up kV 60 75 95 95 125
Rated frequency fr Hz 50/60 50/60 50/60 50/60 50/60
Rated normal current of feeders for 3AH5 Ir A 400, 630 400, 630 400, 630 400, 630 400, 630
for 3AH6 Ir A 630, 1250 630, 1250 630, 1250 630, 1250 630,1250
Rated short-time withstand current Ik up to kA 25 25 25 25 20
Rated short-circuit duration tk s 3 3 3 3 3
Rated peak withstand current Ip up to kA 63 63 63 63 50
Rated short-circuit breaking current Isc up to kA 25 25 25 25 20
Rated short-circuit making current Ima up to kA 63 63 63 63 50
Electrical service life at rated normal current – – 10,000 operating cycles
2) Corresponds to the max. permissiblecut-off current of the HV HRC fuse
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 20076
������������������������������������������������������� ��
��
���� ������
�����
����
���
� �
��
��
���������������������������������������������������� � ������������������������������������������������������������������������������� � ������������������������������ � ����������� � �� ����� ���������� ������� �����
�����
���
� ���
��
� ���
����
� � ����
���
����
����� ��
��
�
�
�
�
�
��
��
��
��
��
�
��
�
�
�
��
��
�
�������� %�Switchgear installation
Room planning
Switchgear installation
Wall-standing arrangement,free-standing arrangement– Single row– Double row (for face-to-face
arrangement)
Room dimensions
See opposite dimensiondrawings
Door dimensions
The door dimensionsdepend on the– Number of panels in a
transport unit– Design with or without
low-voltage compartment
Switchgear fastening
• For floor openings andfixing points of the switch-gear, see page 42
• Foundations:– Steel structure– Steel-reinforced concrete
Panel dimensions
See pages 35 to 41
Weight
The weight of a panel dependson the extent to which it isequipped (e.g. with motoroperating mechanism, voltagetransformer). For details,please refer to page 7.
1 Relief opening
2 Direction of pressure relief
3 Pressure relief of switchgear
4 Room height
5 Individual panel depth
6 Panel depth including end wall
7 Depending on national requirements:Control aisle ≥ 1000 mm recommended(in Germany ≥ 800 mm). When extendingor replacing panels, it might be necessary –depending on the room dimensions – todisassemble the respective neighbouringpanels.
8 Option: Floor cover
9 Cable
10 Foundation
11 Height of cable basement corresponding tocable bending radius
12 Wall distance
13 Side wall distance
14 Installation flush with rear wall
15 Panel width
16 End wall
17 Depth of pressure relief duct
18 Option: For free-standing arrangementpressure relief duct for each panel for ratedshort-time withstand current Ik w 20 kA
19 Option: Front cover
20 Option: Low-voltage compartment
21 Option: High end wall
Room planning
Plan view Plan view
Wall-standing arrangement (side view) Free-standing arrangement (side view)
Cable basement Cable basement
Switchgear room Switchgear room
* Switchgear height 2100 mmif height of low-voltagecompartment 350 mm;switchgear height 2300 mmif height of low-voltagecompartment 550 mm
** Depending on bending radius ofcable
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 7
������������
� ��
�
�
�
���
��
����
������
�
��
�
��
��
�
�
�
�
�
�
�
�
Transport unitsfor shipping (plan view)
1) The net weight and the grossweight depend on the extentto which the panel is equipped(e.g. current transformers, motoroperating mechanisms) and aretherefore given as mean value
* Low-voltage compartment,350 mm high, weight approx.60 kg depending on thepanel type and on the extentto which it is equipped, oroptionally 550 mm high
With individual panel
With combinations of differentindividual panels
1 T1 = Depth of individual panel
2 Individual paneldimension B1 x T1
3 Transport unit,dimension B2 x T2
4 B3 = Overall width ofcombination of differentindividual panels
5 B2 = Width of thetransport unit
Shipping data
2) Sum of thenet weights ofindividual panels
Individual panelor combinationsthereof for standard switchgear(without pressure relief duct)
Paneltype
Panel or panelcombination
Transport unit (including packing)for standard panels (without pressure relief duct)
WidthB1mm
Netweight 1)
approx. kgwith- / withoutLVC*/LVC*
WidthB2m
Height
mwith- / withoutLVC*/LVC*
DepthT2m
Volume
m3
with- / withoutLVC*/LVC*
Grossweight 1)
approx. kgwith- / withoutLVC*/LVC*
Transport of individual panels
Ring-main panel RKRK1
375500
190 / 250210 / 270
1.081.08
1.95 / 2.3 1.40 2.95 / 3.48 250 / 310270 / 330
Ring-main panel for panel combinations RK-U 375 260 / 320 1.08 320 / 380
Cable panel K, K-EK1, K1-E
375500
190 / 250190 / 250
1.081.08
250 / 310250 / 310
Transformer panel TRTR1
375500
210 / 270230 / 290
1.081.08
270 / 330290 / 350
Circuit-breaker panel 630 A LS1, -ULS11, -U
750750
340 / 400340 / 400
1.081.08
410 / 460410 / 460
Circuit-breaker panel 1250 A– For connection of max. 2 cables– For connection of 3 cables
LS31LS32
750875
400 / 460460 / 520
1.081.08
470 / 520530 / 580
Bus sectionalizer panel 1250 A LT31 750 450 / 510 1.08 520 / 570
Bus sectionalizer panel 630 Awith vacuum circuit-breaker
LT10LT11
750750
320 / 380320 / 380
1.081.08
390 / 440390 / 440
Bus sectionalizer panel with1 three-position switch-disconnector
LT2LT2-W
750750
250 / 310310 / 370
1.081.08
320 / 370380 / 430
Bus sectionalizer panel with2 three-position switch-disconnectors
LT22LT22-W
750750
290 / 350350 / 410
1.081.08
360 / 410420 / 470
Billing metering panel ME1....ME1-H
750750
270 / 330330 / 390
1.081.08
340 / 390400 / 450
Busbarvoltage metering panel
ME3ME31-F
375500
210 / 270270 / 330
1.081.08
270 / 330330 / 390
Bus riser without transformerspanel with transformers
HF 375 170 / 230 1.08 230 / 290
HF 375 260 / 320 1.08 320 / 380
Busbarearthing panel
SE1SE2
375500
190 / 250270 / 330
1.081.08
250 / 310330 / 390
For individual panel Panelwidthmm
Additionalweightapprox. kg
Pressure relief ductfor free-standing arrangementof switchgear
375 30
500 40
750 60
875 70
Transport of combinations of different individual panels
Transport unit:–Standard: As individual panels arrangedside by side and not screwed together
–Option: As multi-panel transport unit,panels screwed together
Standard packing for:– Truck– Seaworthy crate, air freight
Overall width B3On request
B20.70 1.95 / 2.3
T21.40 1.91 / 2.25
w 875 mm 1.08 1.95 / 2.3 1.40 2.95 / 3.48 2) + 70 **w 1000 mm *** 1.20 1.95 / 2.3 1.40 3.28 / 3.86 2) + 80 **w 1500 mm 1.78 1.95 / 2.3 1.40 4.64 / 5.47 2) + 100 **w 2125 mm 2.33 1.95 / 2.3 1.40 6.36 / 7.50 2) + 120 **
Container packing, standard(other dimensions on request)
w 875 mm 1.10 1.95 / 2.3 1.40 3.00 / 3.50 2) + 80 **w 2000 mm 2.20 1.95 / 2.3 1.40 6.00 / 7.10 2) + 120 **
Packing, transport (examples)
Packing Version For supply Transport
Panels mounted on wooden floorand covered with PE protection sheeting
Open In Europe Rail, truck
For container Overseas Ship + truck
�������� %�
** Packingweight
*** w 1125 mmon request
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 20078
Product range overview
1) Panels type LSC2B2) With additional make-proof earthing switch3) Type designation of vacuum circuit-breaker4) With 1 three-position switch-disconnector5) With 2 three-position switch-disconnectors6) With voltage transformer for busbar metering
&����� "���
Paneltype
Panelwidth
RKRK1
375 mm500 mm
RK-U 375 mm
TRTR1
375 mm500 mm
KK1
375 mm500 mm
K-EK1-E
375 mm500 mm
LS1 750 mm
LS1-U 750 mm
LS11 750 mm
LS11-U 750 mm
LS31LS32
750 mm875 mm
LS31-U 750 mm
LT10 750 mm
LT11 750 mm
LT31 750 mm
LT2LT2-W
750 mm750 mm
LT22LT22-W
750 mm750 mm
ME1ME1-S
750 mm750 mm
ME1-KME1-KS
750 mm750 mm
ME1-H 750 mm
ME3ME31-F
375 mm500 mm
SE1 375 mm
SE2 500 mm
HF 375 mm
Panel designation
Ring-mainpanel 1)
asfeederastransfer
Transformerpanel 1)
asfeeder
Cable panel asfeeder
Cable panel 1) 2) asfeeder
Circuit-breaker panel 630 A 1)
with 3AH5 3)asfeederastransfer
Circuit-breaker panel 630 Awith 3AH6 3)
asfeederastransfer
Circuit-breaker panel 1250 Awith 3AH6 3)
asfeederastransfer
Bus sectionalizer panel 630 A 1)
with 3AH5 3), for panel type HFBus sectionalizer panel 630 Awith 3AH6 3), for panel type HFBus sectionalizer panel 1250 Awith 3AH6 3), for panel type HFBus sectionalizer panel 630 A 1) 4)
5)
Billing meteringpanel
Standard
asend panel
Billing metering panelfor additional current transformerBusbar voltage meteringpanel 1)
Busbar earthingpanel 1)
6)
Bus riser panel
Standard panels
Ring-main paneltype RK
Circuit-breaker paneltype LS1
Transformer paneltype TR
Circuit-breaker paneltype LS11
Cable paneltype K
Billing metering paneltype ME1
R-HA
41-0
73ep
s
R-HA
41-0
76ep
s
R-HA
41-0
74ep
s
R-HA
41-0
77ep
s
R-HA
41-0
75ep
s
R-HA
41-0
78ep
s
Column No.
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 9
&����� "���
6)
6)
–
7)
7)
7)
• Basic equipment
° Additional equipment (option),further additionalequipment on request
– Not available
Equipment features
• • – • • – ° ° ° ° ° – – ° – ° ° – – ° ° ° ° ° ° RKRK1
• • – – • – ° ° ° ° ° – – ° – – ° – – ° – ° • ° – RK-U
• • – • • ° ° ° ° ° ° – – – ° • ° – – ° – ° ° ° ° TRTR1
• – • • • – – – – – – – – – – ° ° – – – ° ° ° ° ° KK1
– • – • • – ° ° ° ° ° – – – – ° ° – – ° ° ° ° ° ° K-EK1-E
• • – • • – ° ° ° ° ° ° – ° – ° ° ° ° ° ° ° ° ° ° LS1
• • – – • ° ° ° ° ° ° ° – ° – – ° ° ° ° – ° • ° – LS1-U
• • – • • ° ° ° ° ° ° ° ° 5) ° – ° 6) ° ° ° ° ° ° ° ° ° LS11
• • – – • ° ° ° ° ° ° ° ° ° – – ° ° ° ° – ° • ° – LS11-U
• • – • • ° ° ° ° ° ° • • 5)
° – ° 6) ° ° ° ° ° ° ° ° ° LS31LS32
• • – – • ° ° ° ° ° ° • • ° – – ° ° ° ° – ° • ° – LS31-U
• • – – • ° ° ° ° ° ° ° ° ° – – ° ° ° ° – ° • ° – LT10
• • – – • ° ° ° ° ° ° ° • ° – – ° ° ° ° – ° • ° – LT11
• • – – • ° ° ° ° ° ° • • ° – – ° ° ° ° – ° • ° – LT31
• • • – • – ° ° ° ° ° – – ° – – ° – – ° – ° • ° – LT2LT2-W
• • – – • – ° ° ° ° ° – – ° – – ° – – ° – ° • ° – LT22LT22-W
– – • – • – – – – – – – – – – ° ° – – – – ° • ° – ME1ME1-S
– – • • • – – – – – – – – – – ° ° – – – – ° ° ° ° ME1-KME1-KS
– – • – • – – – – – – – – – – ° ° – – – – ° • ° – ME1-H
• • – – • – ° ° ° ° ° – – – ° ° ° – – ° – ° • ° – ME3ME31-F
• • – – • – ° ° ° – – – – – – – ° – – ° – ° • ° – SE1
• • – – • – ° ° ° – – – – – ° – ° – – ° – ° • ° – SE2
– – • – • – – – – – – – – – – – ° – – – – ° • ° – HF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Panel type
5) Not to be applied for versions with separate feeder earthing switch inpanel types LS11, LS31 and LS32
6) Inspection window is a standard equipment in panel types LS11, LS31and LS32 for versions with separate earthing switch
7) Panel heating: wired on terminal (standard).Option: version with thermostat.
1) Three-position switch as three-position switch-disconnector2) Three-position switch as three-position disconnector in panel
types LS31, LS31-U, LS32 and LT313) Type designation of the vacuum circuit-breaker4) In special cases, deeper floor cover for panels
with cable feeder required
–
Man
ual o
perat
ingm
echa
nism
forthr
ee-po
sition
switc
h1)
2)
Interl
ock for
cable
compa
rtmen
t cov
er
Cable
compa
rtmen
t cov
erloc
ked in
place
C-rail a
s cable
brack
et
Low-vo
ltage
niche
aster
minal c
ompa
rtmen
t
Releas
e assh
unt r
eleas
e
Mec
hanic
alrea
dy-fo
r-serv
iceind
icator
forthr
ee-po
sition
switc
h
Signall
ingsw
itch (1N
O) for r
emote
electr
ical
ready
-for-s
ervice
indica
tion for
three
-posit
ionsw
itch1)
2)
Aux. s
witch f. t
hree-p
ositio
n switc
h and mak
e-proo
f eart
hing sw
itch
Switc
h-disc
onne
ctor a
ndEA
RTHIN
G: f.CLO
SED
andOPE
N2N
O+2NC
each
Moto
r ope
rating
mecha
nism
forthr
ee-po
sition
switc
h1)
2)
Loca
l remote
switc
h formoto
r ope
rat. m
ech.
ofthr
ee-po
sition
switc
h1)
2)2 )
Interl
ock in
circu
it-brea
ker p
anel
betw
een
three
-posit
ionsw
itch1)
2) and
3AH...
vacu
umcir
cuit-b
reake
r
Lock
ingde
vice for
switc
h posit
ion“C
LOSED“ of
3AH6 va
cuum
circu
it-brea
ker w
ithea
rthed
three
-posit
ionsw
itch1)
2)
Closing
lock-o
utfor
three
-posit
ionsw
itch1)
2)
De-eart
hing loc
k-out
form
ake-p
roof e
arthin
g switc
h
Inspe
ction
window
inthe
conn
ectio
n/cab
leco
mpartm
ent c
over
Low-vo
ltage
compa
rtmen
t or c
over
Moto
r ope
rating
mec
hanis
mfor
vacu
umcir
cuit-b
reake
r
Releas
e asc.t
.-ope
rated
relea
sein
3AH
3)
Lock
ingde
vice for
three
-posit
ionsw
itch1)
2)
Short-
circu
it or e
arth-f
ault i
ndica
tor
– Secon
dary
equip
ment
– Floor
cove
r4)
– Panel
heati
ng7)
Mou
nted ca
ble
clamps
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200710
���� ������
��
���������
������������
������
������
��
��
��
��
�� �
������ �����
������
������
���������
���������
������
������
������
���� �������
��
��
���������
������
��������
������
��������
��������
Ring-main panels
Type RK-U375 mm wide
Ring-main panelsas feeder panels
either:Version withtransformers
Type RK375 mm wide
Type RK1500 mm wide
����
����
���
����
��
��
��
��
��
�� ��
����������
���������
������
������
������
������
������
������
���������
������
Type LT10750 mm wide
Type RK1500 mm wide
���� �� ����
��
������
������
Ring-main panelas transfer panel for attachmentto panel types ME1... or ME1-H
or:Version withconnectionfittings
For other panel combinations
Type RK-U375 mm wide
With3AH5vacuumcircuit-breaker,fixed-mounted
With3AH6vacuumcircuit-breaker,remov-able
Bus sectionalizer panel type LT10 withring-main transfer panel type RK-U
Type RK-U375 mm wide
Type LT11750 mm wideBus sectionalizer panel type LT11 withring-main transfer panel type RK-U(non-interchangeable arrangement)
������������
�
��
��
!�
!
��
����
���������
������
������
������
������
������
������
Standard:transferto theright
Option:transferto theleft
The ring-main transfer panelRK-U can be attached on theleft or right of the bussectionalizer panel LT10
&����� "���
* On request up to 12 kV
P1 and P2are terminaldesignationsof the currenttransformer
** On request:only 1 set of voltagetransformers possible
��
��
��
��
��
�
HA41
-239
0cep
s
Capacitivevoltage detectionsystem
Voltage transformere.g. 4MR, 1-pole,cast-resin insulated
Cable (notincluded in thescope of supply)
2nd cable (notincluded in thescope of supply)
Surgearrester
Block-typecurrent transformer4MA,cast-resin insulated
Cable-typecurrent transformere.g. 4MC703 . . .
Three-phasecurrent transformer4MC63 . . .
3AH5 vacuumcircuit-breaker
Three-positionswitch-disconnector
3AH6 vacuumcircuit-breaker
Voltage transformere.g. 4MR, 2-pole,cast-resin insulated
On request:voltage transformere.g. 4MR, 2-pole,cast-resin insulated,only up to 17.5 kV
�
��
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 11
��
��
���� � ����
��
������
��������
������
Transformer panelsas feeder panels
��
�� �
�"����
��
��
������
������
������
������
������ ���������
Cable panelsas feeder panels, 630 A
���� ��"����
��
���������
������
���������
���������
���������
������
Transformer and cable panels
Type K375 mm wide
Type TR375 mm wide
���� �� ����
��
������
��������
������
Type TR1500 mm wide
Cable panelsas feeder panels, 630 A, withmake-proof earthing switch
���� �������
��
��
���������
������
������
���������
���������
�����
� #
������
Type K-E375 mm wide
��
�� �
������
��
��
��
������
������
���������
������
������
���������
������
Type K1500 mm wide
Type K1-E500 mm wide
��
����
������
��
������
������ ���������
������
������
������
��
����
������
��
��
������������
���������
���������
������
������
either:Version withtransformers
or:Version withconnectionfittings
either:Version withtransformers
or:Version withconnectionfittings
HV HRC fuse
Capacitivevoltage detectionsystem
Make-proofearthing switch
Earthingswitch
Three-positionswitch-disconnector
Fixedearthing point
Cable-typecurrent transformer,e.g. 4MC703 . . .
Block-typecurrent transformer4MA,cast-resin insulated
Three-phasecurrent transformer4MC63 . . .
Voltage transformere.g. 4MR, 1-pole,cast-resin insulated
Cable (notincluded in thescope of supply)
2nd cable (notincluded in thescope of supply)
Surgearrester HA
41-2
390c
eps
Type K1500 mm wide
Type K1-E500 mm wide
as feeder panels630 A and 1250 A
&����� "���
* Current transformerlocated partlyunderneath the panel
** On request up to 12 kV
��
as feeder panels630 A and 1250 A
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200712
�
��
�� �
������
��
��
��
��
���������
���������
���������
������ ������
������ ���������
������ ������
������������
������
��
���� �������
��
��
��
!
!�
����������
���������
������ ������
������������ ��������
�������
������
Circuit-breaker panels
Circuit-breaker panels 630 Aas feeder panels
as transfer panels for attachmentto panel types ME1... or ME1-H
Type LS1750 mm wide
Type LS1-U750 mm wide
* On request
** Standard: Feeder earthingvia the 3AH6 vacuum circuit-breakerwith interlocks (without earthing switch)
B Mounting position of the currenttransformer with terminal P1 at the top only
P1 and P2 are terminal designationsof the current transformer
With 3AH5 vacuum circuit-breaker,fixed-mounted
Voltage transformere.g. 4MR, 1-pole,cast-resin insulated
Three-phasecurrent transformer4MC63 . . .
�
��
����
�"����
��
��
��
��
������ ������
������ ���������
������ ������
������������
���������
���������
���������
������
Type LS31750 mm wide
With 3AH6vacuum circuit-breaker,removable
Type LS11750 mm wide
��
���� �"����
��
��
!
!�
����
������ ������
������ ������
������
With 3AH5 vacuum circuit-breaker,fixed-mounted
With 3AH6 vacuum circuit-breaker,removable
Type LS11-U750 mm wide
as transfer panel for attachmentto panel types ME1... or ME1-H
�
���� ��$����
��
��
!
!�
��
������ ������
�������� ������
������
���������
With 3AH6 vacuum circuit-breaker,removable
Type LS31-U750 mm wide
Standard:transferto theright
Option:transferto theleft
Transferpossibleonly tothe right
3AH5 vacuumcircuit-breaker
Three-positionswitch-disconnector
Three-positiondisconnector
3AH6 vacuumcircuit-breaker
Cable-typecurrent transformere.g. 4MC703 . . .
Block-typecurrent transformer4MA,cast-resin insulated
���� � �����
���
��
!
!�
��
������ ������
�������� ������
������
���������
Transferpossibleonly tothe right
Circuit-breaker panels 1250 Aas feeder panels
forconnectionof max.2 cables
�
������������
��
��
��
��
��
������ ������
������ ���������
������ ������
������������
���������
���������
������
���������
With 3AH6vacuum circuit-breaker, removable
forconnectionof max.3 cables(4 cables *)
With 3AH6vacuum circuit-breaker,removable
Type LS32875 mm wide
&����� "���
Cable (notincluded in thescope of supply)
Addit. cables (notincluded in thescope of supply)
Surge arrester
Capacitive voltagedetection system
Fixedearthing point HA
41-2
390c
eps
Make-proofearthing switch
Voltage transformere.g. 4MR, 2-pole,cast-resin insulated
�
��
�
��
��
��
��
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 13
���� �������
��
��
��
!�
!
����
������
������
������
���������
������
������
������
��
�� �
����
������ ������
������
���� �������
��
��
!�
!
����
������
������
������
������
������
������
��
�� �
����
������ ������
���� �������
��
��
��
��
!�
!
!
!�
���� ����
������ ������
������
���������
������
������
������
������
������
Bus sectionalizer panels 630 Ain combination with bus riser panel
���� �������
��
��
��
��
!
!�
!�
!
���� ����
������ ������
������
���������
������
������
������
������
������
Type HF375 mm
Type LT10750 mm wide
Type HF375 mm wide
Type LT10750 mm wide
�
���� �������
��
��
!�
!
����
������
������
������
������
������
������
������
Type HF375 mm wide
Type LT11750 mm wide
Type LT2750 mm wide
Bus sectionalizer panels 630 Awith 1 three-position switch-disconnector
Type LT2-W750 mm wide
with 2 three-position switch-disconnectors
Type LT22750 mm wide
Type LT22-W750 mm wide
Pane
ltyp
eH
Fat
tach
edon
the
right
Bus sectionalizer panels
With3AH5vacuumcircuit-breaker,
fixed-mounted
corresponds to type RK-Uwith type HF
Type HF375 mm wide
Type LT31750 mm wide
�
���� ��"����
��
!�
!
��
����
������
������
������
������
������
������
������
corresponds to type RK-Uwith type RK-U
corresponds to type RK-Uwith type RK-U
corresponds to type RK-Uwith type HF
With3AH5vacuumcircuit-breaker,
fixed-mounted
With3AH6vacuumcircuit-breaker
remov-able
Bus sectionalizer panel 1250 Ain combination with bus riser panel
Pane
ltyp
eH
Fat
tach
edon
the
left
Pane
ltyp
eH
Fca
non
lybe
atta
ched
onth
erig
htPa
nelt
ype
HF
can
only
beat
tach
edon
the
right
P1 and P2are terminaldesignationsof the currenttransformer
With3AH6vacuumcircuit-breaker
remov-able
&����� "���
3AH5 vacuumcircuit-breaker
Three-positionswitch-disconnector
3AH6 vacuumcircuit-breaker
Three-positiondisconnector
Voltage transformere.g. 4MR, 1-pole,cast-resin insulated
Block-typecurrent transformer4MA,cast-resin insulated
Three-phasecurrent transformer4MC63 . . .
Capacitivevoltage detectionsystem
Fixedearthing point HA
41-2
390c
eps
��
��
��
�
��
Voltage transformere.g. 4MR, 2-pole,cast-resin insulated
�
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200714
����
���
�����
����
��
��
��
������
������
������
������
�����������
��
��
����
����
�
!
!�
������
������
����
���
�����
����
��
��
��
������
������
������
������
�����������
��
��
����
����
�
!
!�
������
������
��
����
���
�����
��
������
������
������
������
������ ���������
��
����
���
�����
��
��
��
��
������
������
������
������ ���������
��
����
���
����
��
��
��
��
������
������
������
������ ���������
��
����
���
�����
��
����
��
������
������
������
������ ���������
��
��
����
����
�
!�
!
������
������
��
��
����
����
�
!�
!
������
������
����
���
�����
����
��
��
��
������
������
������
������
�����������
����
���
�����
����
��
��
��
������
������
������
������
�����������
�� ��
Billing metering panels
Billing metering panels630 A and 1250 AStandard
Type ME1750 mm wide
Standard **:Transfer to the right
Type ME1-S750 mm wide
Billing metering panels630 A and 1250 Afor busbar connection
Type ME1750 mm wide
Type ME1-S750 mm wide
Type ME1750 mm wide
Type ME1-S750 mm wide
Type ME1750 mm wide
Type ME1-S750 mm wide
Type ME1-H750 mm wide
Type ME1-H750 mm wide
Billing metering panels630 A and 1250 Afor additional transformer
HA41
-239
0cep
s
Capacitivevoltage detectionsystem
Block-typecurrent transformer4MA,cast-resin insulated
Fixedearthing point
Fixed earthingpoint forbusbar earthing
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Type ME1-H750 mm wide
Type ME1-H750 mm wide
Standard **:Transfer to the right
Voltage transformer,e.g. 4MR,1- or 2-pole,cast-resin insulated
Scheme 1 Scheme 1 Scheme 1
Scheme 2 *** Scheme 2 *** Scheme 2 ***
Scheme 3 Scheme 3 Scheme 3
Scheme 4 *** Scheme 4 *** Scheme 4 ***** Option:
Transferto the left
*** Transformerterminalsinterchanged
P1 and P2are terminaldesignationsof the currenttransformer
&����� "���
��
Voltage transformer,e.g. 4MR, 1-pole,cast-resin insulated,or on request:
Voltage transformer,e.g. 4MR, 1-pole,cast-resin insulated,mit HV HRC fuse,instead of a2nd set of currentor voltagetransformers
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 15
Make-proofearthing switch
Three-positionswitch-disconnector
HA41
-239
0cep
s
Capacitivevoltage detectionsystem
Fixedearthing point
Voltage transformer,e.g. 4MR,1- or 2-pole,cast-resin insulated
Billing metering panels,busbar voltage metering panels, busbar earthing panels and bus riser panels
HV HRC fuse
* On requestup to 12 kV
** Connectionfor 3 cablespossible
B Option:Transferto the left
BB Forattachmentto left orrightring-mainpanelstype RK-U
��
�� �
� ����
������
������%����&'���(
��
�� �
����
������
��
��
�� �
� ����
!
!�
������
��������
��
�� �
� ����
!
!�
������
������
��
��
�� �
����
!
!�
������
������
��
��
�� �
� ����
!
!�
������
������
��
��
�� �
� ����
!�
!
������
������
��
��
�� �
� ����
!�
!
������
������
Billing metering panels630 A and 1250 A **for cable connection
Type ME1-K750 mm wide
Standard B):Transfer to the right
Type ME1-KS750 mm wide
Billing metering panels630 A and 1250 A **for busbar connection
��
��
�� �
� ����
!�
!
������
������
Type ME1-K750 mm wide
��
��
�� �
� ����
!�
!
������
������
Type ME1-KS750 mm wide
Type ME1-K750 mm wide
Type ME1-KS750 mm wide
Type ME1-K750 mm wide
Type ME1-KS750 mm wide
Type ME31-F500 mm wide
Type ME3375 mm wide
Busbar voltagemetering panels
Standard B):Transfer to the right
Standard B):Transfer to the right
Standard B):Transfer to the right
Type SE1375 mm wide
Type SE2500 mm wide
Bus riser panels630 A and 1250 A
Type HF BB)375 mm wide
�����������
��
!�
!
������
��������
������
������
Transformerterminalsinterchanged
Transformerterminalsinterchanged
Type HF BB)375 mm wide
Type HF BB)375 mm wide
Busbarearthing panels
Type HF BB)375 mm wide
Earthing switch
Make-proofearthing switch
Transformerterminalsinterchanged
Transformerterminalsinterchanged
Scheme 1 Scheme 1 Scheme 1
��
�� �
� ����
��
�� �
� ����
������
�����������
��
!�
!
������
��������
������
�������
����������
��
!
!�
������
��������
������
������
����������
��
!
!�
������
��������
������
������
Scheme 2 Scheme 2 Scheme 2
Scheme 3 Scheme 3 Scheme 3
Scheme 4 Scheme 4 Scheme 4
P1 and P2are terminaldesignationsof the currenttransformer
as right or leftend panel
as right or leftend panel
as right or leftend panel
as right or leftend panel
Block-typecurrent transformer4MA,cast-resin insulated
��
&����� "���
Voltage transformer,e.g. 4MR, 1-polecast-resin insulated
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200716
Panel design (examples)
����
���
����
�
������
��
���������������
�
���
��
�
��
��
��
�
��
�
��
��
��
��
��
��
�
��
�
��
��
��
Ring-main panel as feeder Transformer panel as feeder
Billing metering panel Legend for pages 16 and 17
1 Option: Low-voltage compartment
2 Niche for optional low-voltage equipment,cover can be unscrewed
3 Option: CAPDIS voltage detection system
4 Option: Short-circuit /earth-fault indicator
5 Option: Ready-for-service indicatorfor switching device
6 Switch position indication for load-breakfunction “CLOSED – OPEN“
7 Switch position indication for earthingfunction “OPEN – EARTHED“
8 Feeder designation label
9 Mimic diagram
10 Option: Sockets for capacitive voltage detection system(depending on arrangement)
11 Option: Momentary-contact rotary control switch“CLOSED – OPEN“ for motor operating mechanismwith local-remote switchfor three-position switch-disconnector
12 Option: Locking device for three-positionswitch-disconnector
13 Pressure relief device for switching device
14 Manual operation for the mechanism ofthe earthing function
15 Manual operation for the mechanism ofthe load-break function
16 Rating and type plate
17 Gas-insulated vessel for switching device
18 Interlocking of the cable compartment cover
19 Bushing-type insulator for busbar
20 Bushing-type insulator for feeder
����
���
����
�
�
���
��
���������������
��
�
��
��
��
��
��
��
��
��
��
��
��
��
�
���
����
��
�
��
��
��
����
���
����
�
��
�
��
�
��
��
��
��
�
��
��
�
�
�
����
��
��
��
��
Type RK Type TR
Type ME1
Section Section
Section
%�����
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 17
����
���
����
��
��
�
�
��
�
����������������
��
��
��
��
�
��
��
��
��
��
��
��
������
�
��
��
��
����������
��
��
��
��
��
�
��
��
��
��
��
�
��
��
��
����
���
�����
�
�
��
�����
��
��
��������
��������
��
��
��
��
��
�
�
��
��
��
��
����
��
�
��
��
�
��
�
��
��
��
�
��
��
��
��
Panel design (examples)
Circuit-breaker panel (with 3AH5 vacuum circuit-breaker) 21 Insulating sleeve (e.g. for Up > 95 kV)
22 Cable bracket with clamps (option) for fastening cables
23 Busbar
24 Insulating cap * on busbar
25 Spring-operated mechanism forthree-position switch-disconnector
26 Spring-operated/stored-energy mechanism forthree-position switch-disconnector
27 Three-position switch-disconnector
28 Cable connection
29 Cable compartment cover
30 Earthing connection (for location see dimension drawings)
31 Earthing switch for cable connection
32 Inspection window
33 Post insulator
34 Insulating sleeve
35 Option: HV HRC fuse link
36 Option only for panel types LS11 ... and LT11 ...:Logical mechanical interlocking between circuit-breaker“OPEN“ and three-position switch-disconnector andlocking device for three-position switch-disconnector
37 Option: ME1- fuse box for voltage transformer
38 Cover, screwed on
39 4MR voltage transformer
40 4MA7 block-type current transformer
Vacuum circuit-breaker:
41 3AH5 vacuum circuit-breaker, fixed-mounted
42 3AH6 vacuum circuit-breaker, removable
43 Operating mechanism box
44 Manual operation– for closing with manual operating mechanism– for emergency operation with motor operating
mechanism
45 Mechanical “OFF“ pushbutton
46 Mechanical “ON“ pushbutton(not supplied with spring-operated mechanism)
47 “Spring charged“ indicator
48 Operating cycle counter
49 Switch position indication
50 Option: Three-phase current transformer 4MC63 53
51 Option: Overcurrent-time protection relaySIPROTEC easy 7SJ45
52 Option: Multifunction protection relay SIPROTEC 4 7SJ62
53 Cover * for screwed gland of cable connections
54 Insulating cap * on bushing-type insulator
55 Option: Wiring duct, removable,for control cables and/or bus wires
56 Logical mechanical interlocking for three-position switch
57 Earthing busbar
58 Metal compartmentalization of busbar compartment
59 Metal compartmentalization of cableconnection compartment
60 Busbar compartment cover for panel extension
61 Cable sealing end (not included in scope of supply)
62 Option: Feeder earthing via make-proof earthing switch
63 or feeder earthing via vacuum circuit-breaker (= lockingdevice for feeder earthed when circuit-breaker “CLOSED“)
64 Interlocking of cable compartment cover incircuit-breaker panels
65 Cover for transformer connection compartment
* For example for Up W 95 kV, Ur W 15 kV
Type LS11 Section
Circuit-breaker panel (with 3AH6 vacuum circuit-breaker)
Type LS1 Section
%�����
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200718
Common features
• Circuit-breakers withvacuum interrupters
• Stored-energy spring-operated mechanism for10,000 operating cycles
• Maintenance-free for in-door installation accordingto IEC 60 694 /VDE 0670 -1000, sub-sequently IEC 62 271-1*
• Individual secondaryequipment
Switching duties andoperating mechanisms
The switching duties of thevacuum circuit-breaker aredependent, among otherfactors, on its type of oper-ating mechanism. Threeoperating mechanismversions are available:
• Motor operating stored-energy mechanism
– For auto-reclosure (K),– For synchronization and
rapid load transfer (U)
• Manual operating stored-energy mechanism
– For auto-reclosure (K)
• Manual spring-operatedmechanism(= spring CLOSED,stored-energy OPEN)
– Not for auto-reclosure (K)– For normal closing and– For storage of one
opening
Trip-free mechanism
• The vacuum circuit-breakers are fitted with atrip-free mechanismaccording toIEC 62 271-100 /VDE 0671-100
3AH5 and 3AH6 vacuum circuit-breakers
3AH5 vacuum circuit-breaker
• Metal-enclosed
• Up to 630 A
• Pole parts with vacuuminterrupters fixed-mountedin hermetically welded,gas-filled switchgear vessel
• System-conforming usewith three-position switchin gas-insulated switchgearvessel
• Operating mechanismarranged outside theswitchgear vessel andbehind the control board
• Air-insulated primaryterminals
Installation in metal-cladpanels
• Feeder panels type LS1,panel width 750 mm
• Transfer panels type LS1-U,panel width 750 mm
• Bus sectionalizer panelstype LT10 (for adjacent busriser panel type HF),panel width 750 mm
3AH6 vacuum circuit-breaker
• Removable 1) lateral-mechanism circuit-breaker,air-insulated
• Up to 1250 A
• Circuit-breaker polesarranged one behind theother
• Operating mechanism inseparate box behind lowerpanel cover
• Logical mechanical inter-locking between 3AH6vacuum circuit-breaker andthree-position switch
• Installation in:– Feeder panel type LS11,
panel width 750 mm– Transfer panel type LS11-U,
panel width 750 mm– Bus sectionalizer panels
type LT11 and LT31 (foradjacent bus riser paneltype HF), panel width750 mm
– Feeder panel type LS31(for connection ofmax. 2 cables),panel width 750 mm
– Feeder panel type LS32(for connection of 3 cables;4 cables on request),panel width 875 mm
3AH5vacuum circuit-breaker(operating mechanism box open)
Abbreviations for switchingduties and applications:
U = Synchronization andrapid load transfer(make time w 90 ms)
K = Auto-reclosure
R-HA
41-0
66ep
s
1
2
3
4
5
* Standards see page 43
1) Removable after looseningthe respective contactconnections and fixing bolts
1 Operating mechanism box
2 Bushing-type insulator for busbar
3 Switchgear vessel, gas-filled, with3AH5 vacuum circuit-breaker andthree-position switch-disconnector
R-HA
41-0
68ep
s 9
8
7
3AH6vacuum circuit-breaker
6
4 Spring-operated mechanism ofthree-position switch-disconnector
5 Bushing-type insulator for feeder
6 Location for three-phase currenttransformer (option)
For further details, please referalso to Catalog HG 11.11“3AH Vacuum Circuit-Breakers“
11
10
7 Operating mechanism boxwith control elements
8 Circuit-breaker poles withvacuum interrupters
9 Truck
10 Locking device (standardwhen earthing the feeder withclosed 3AH6 vacuum circuit-breaker)for the 3AH6 vacuum circuit-breakerin switch position “CLOSED”with three-position switchin switch position “EARTHED“
11 Logical mechanical interlockingbetween vacuum circuit-breakerand three-position switch(prevents switching of all threeswitch positions).Option for 630 A panel types with:3AH5: LS1, LS1-U, LT103AH6: LS11, LS11-U, LT11Standard for 1250 A panel types with:3AH6: LS31, LS31-U,
LS32 and LT31.
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 19
3AH5 and 3AH6 vacuum circuit-breakers
Operating mechanismelements of the3AH6 vacuum circuit-breaker
Operating mechanism elements
1 Gear
2 Coupling on gear for operationwith hand crank– For closing with manual
spring-operated mechanism– For charging the closing
spring with stored-energymechanism
3 Closing spring
4 Motor (M1 *)
5 “Closing spring charged” indicator
6 Circuit-breaker “OPEN”
7 Circuit-breaker “CLOSED”
8 Operating rod
Operating mechanismfunctions
Motor operating mechanism 1)
(M1 *)
In the case of the motor operat-ing mechanism, the closingspring is charged by means ofa motor and latched in thecharged position (the “springcharged” indication is visible).Closing is effected either bymeans of an ON pushbutton ora closing solenoid. The closingspring is recharged automati-cally (for auto-reclosure).
Manual operating stored-energy mechanism
The closing spring is chargedby means of the supplied handcrank until latching of theclosing latch is indicated(= “spring charged” indication).
Subsequently the vacuumcircuit-breaker can be closedeither manually or electrically.The closing spring can be re-charged manually. The “possibil-ity to close” is thus stored oncemore (for auto-reclosure).
Manual spring-operatedmechanism(= spring CLOSED,stored-energy OPEN)
The closing spring of the vacuumcircuit-breaker is charged bymeans of the supplied handcrank until the vacuum circuit-breaker closes. Subsequentlyeither manual or electrical open-ing is possible.
Vacuum circuit-breakers withspring-operated mechanism arenot suitable for auto-reclosure.
1) Motor rating at24 V to 220 V DC: 350 W110 V and 220 V AC: 400 VA
2) With closing solenoid
* Equipment code
Abbreviations:
O = OPEN operation
CO = CLOSE operation with subse-quent OPEN operation at theshortest internal close-open timeof the vacuum circuit-breaker
t = Dead time 0.3 s
t ‘ = Dead time 3 min
Operating mechanismelements of the3AH5 vacuum circuit-breaker
6
4
3
1R-
HA41
-080
eps
2
8
7
R-HA
41-0
69ep
s
2
1
3
47
8
6
Differences between the vacuum circuit-breakers depending on the operating mechanism version
Operatingmechanism version
Motor operatingstored-energy mechanism
Manual operatingstored-energy mechanism
Manual spring-operatedmechanism
Typical uses Utility substationsand industrial plants
Classic transfer substationsand substations withoutauxiliary voltage supply
Simple utility substations(circuit-breaker astransformer switch)
Mechanismfunction
Stored-energy CLOSED,stored-energy OPEN
Stored-energy CLOSED,stored-energy OPEN
Spring CLOSED,stored-energy OPEN
Mechanismoperation
With motor 1), manual(emergency) operationat the panel includinganti-pumping
With handcrank
With handcrank
Closing thevacuumcircuit-breaker
Electrically 2) ormechanically at the panelwith pushbutton
Mechanically at the panelwith pushbutton, option:electrically 2)
Mechanically at the panelwith hand crank(charging process)
Closing solenoid,e.g. for remoteelectrical closing
Always provided, withelectrical signal“closing spring charged”
Option Without
Rated switchingsequence
O-t-CO orO-t-CO-t’-CO
O-t-CO O or CO
Auto-reclosure (K)
Suitable (multipleauto-reclosure possible)
Suitable (only with closingsolenoid)
–For further details, please refer also toCatalog HG 11.11 “3AH VacuumCircuit-Breakers“
5
5
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200720
Secondary equipment of the 3AH5 and 3AH6 vacuum circuit-breakers
The scope of the secondaryequipment of the 3AH vacu-um circuit-breaker dependson the type of applicationand offers a wide range ofvariations, thus allowingeven the highest require-ments to be satisfied.
Closening solenoid
• Type 3AY15 10 (Y9 *)
• For electrical closing
Shunt releases
• Types:– Standard: 3AY15 10 (Y1 *)– Option: 3AX11 01 (Y2 *),
with energy store
• Tripping by protection re-lay or electrical operation
Current transformer-operated release
• Type 3AX11 04 (Y6 *) fortripping pulse W 0.1 Ws inconjunction with suitableprotection systems, e.g.7SJ4 protection relay,SEG relay (other designson request)
• Used where no externalauxiliary voltage is avail-able, tripping by protec-tion relay
Undervoltage release
• Type 3AX11 03 (Y7 *)
• Comprising:– Energy store and
unlatching mechanism– Electromagnetic system,
to which voltage ispermanently applied inthe CLOSED position ofthe vacuum circuit-breaker;tripping is initiated whenthis voltage drops
• Connection to voltagetransformer possible
Position switch
• Type 3SE4 (S4 *)
• For signalling “closingspring charged“
• Only in conjunction withstored-energy mechanisms
Secondary equipment of the 3AH6vacuum circuit-breaker (typical example)
Anti-pumping (standard)(mechanical and electrical)
• Function: If CLOSE andOPEN commands are ap-plied simultaneously andcontinuously to the vacuumcircuit-breaker, this revertsto its OPEN position afterclosing. The circuit-breakerremains in this position untilthe OPEN command is eli-minated and a new CLOSEcommand is given. Thuscontinuous closing and ope-ning (= pumping) is avoided.
Breaker tripping signal(standard)
• For electrical signalling(as pulse > 10 ms), e.g. toremote control systems,in the case of automatictripping (e.g. protection)
• Via NO contact (S6 *)and cut-out switch (S7 *)
Varistor module
• As overvoltage protectionfor protection devices inconjunction with inductivedevices in the vacuumcircuit-breaker (limiting toapprox. 500 V)
• Recommended for auxil-iary voltages W 60 V DC
Auxiliary switch
• Type 3SV9 (S1 *)
• Standard: 6NO+6NC,of which 2NO+2NC+2 changeover contactsare free 1)
• Option: 12NO+12NC, ofwhich 7NO+4NC+2 change-over contacts are free 1)
Mechanical interlocking
• Dependent on the typeof operating mechanism:
– Spring-operatedmechanism or
– Stored-energy mechanism
• Option:Switchgear interlockingwith the three-positionswitch-disconnector
For further details concer-ning interlocking functions,refer to page 28.
For further details, please refer also toCatalog HG 11.11 “3AH Vacuum Circuit-Breakers“
1) For utilizationby thecustomer
Abbreviations:NO = normally-open contactNC = normally-closed contact
* Equipmentcode
Basic equipment
1 Auxiliary switch 6NO+6NC (S1 *),option: 12NO+12NC
2 1st release (Y1 *)
Additional equipment
3 Position switch (S4 *)
4 Closing solenoid (Y9 *)
5 Operating cycle counter
6 2nd release(e.g. Y2 *, Y6 * and Y7 *)
7 Mechanical interlockingwith interrogationof the three-positionswitch-disconnector
1
1
2
5
6
2
7
4
3
5
R-HA
41-0
80ep
s
4
3
R-HA
41-0
46ep
s
Secondary equipment of the 3AH5vacuum circuit-breaker (typical example)
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 21
����� ������
�
Three-position switches as three-position switch-disconnectors or disconnectors
Common features
• Metal-enclosed
• Located in agas-insulatedswitchgear vessel
• Switch positions:CLOSED-OPEN-EARTHED
• No cross insulationbetween phases
• Three-position switchwith air-insulatedprimary connectionsfor busbar and feeder
• Operation via agas-tight welded-in me-tal bellows in the frontof the switchgearvessel
Mode of operation
The switch shaft with themoving contact piecesrotates inside the cham-ber containing the fixedcontact pieces.
Compression vanes,which rotate in conjunc-tion with the switchshaft, divide the arcingchamber into two sub-chambers each of whichchanges in conjunctionwith the rotation.
During the switchingmovement, the compres-sion vanes generate apressure difference be-tween the subchambers.The SF6 gas flowsthrough a nozzle, causesa directional blow-out ofthe breaking arc andquenches it rapidly.
Interlocking is not neces-sary as the “CLOSED”and “EARTHED” func-tions cannot be imple-mented simultaneously.
1 Bushing-type insulator for busbar
2 Switchgear vessel for gas insulation
3 Three-position switch-disconnector
4 Bushing-type insulator for feeder
5 Spring-operated mechanism with detachable lever
6 Mounting location for three-phase current transformer (option)
Detachable lever mechanismwith three-position switch-disconnector
Three-positionswitch-disconnector630 A
R-HA
41-0
57ep
s
1
2
3
4
7 Detachable lever, inserted
Three-positionswitch-disconnector 630 A
• Up to 630 A
• With gas-insulated,maintenance-free quench-ing principle
Operating mechanism
• Spring-operated mechanismwith detachable lever
• Manual operation with theaid of a detachable lever
• Options:– Mechanical ready-for-
service indication– Auxiliary switch– Motor operating mechanism
for switch-disconnector– Locking device
• Spring-operated/stored-energy mechanism fortransformer panel types TR,TR1 and ME31-F
Interlocks
• Opening of lower panelcover or cable compartmentcover only in “EARTHED“position
• Option: Logical mechanicalinterlocking of three-positionswitch-disconnector withvacuum circuit-breaker
Three-positiondisconnector 1250 A
• Up to 1250 A, for paneltypes LS31, LS31-U, LS32and LT31
• Metal-enclosed
Operating mechanism
• Spring-operated mechanismwith detachable lever
• Manual operation with theaid of a detachable lever
• Options:– Mechanical ready-for-
service indication– Auxiliary switch– Motor operating mecha-
nism for disconnector– Locking device
Interlocks
• Opening of lower panelcover or cable compartmentcover only in “EARTHED”position
• Logical mechanicalinterlocking with vacuumcircuit-breaker
Switch positions:
EARTHED
OPEN
CLOSED
5
6
Switching functions of thethree-position switch-disconnector630 A
• Switching and disconnecting underload
• Switching function as general purposeswitch-disconnector (class E3 and M1)according to
– IEC 60 265-1– VDE 0670-301– IEC 62 271-102– VDE 0671-102
• Make-proof earthing function
Switching functions of thethree-position disconnector1250 A
• Disconnecting
• Switching functions according to– IEC 62 271-102– VDE 0671-102
• Earthing function
• For panel types LS31, LS31-U,LS32 and LT31
Note: Standards see page 43
asthree-positionswitch-disconnector630 A
asthree-positiondisconnector1250 A
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200722
Busbars, HV HRC fuse assembly
Busbar compartment extending over 3 panels (example)Side view
R-HA
41-0
61ep
s
Busbars
• Safe-to-touch due tometallic enclosure
• Metal-clad busbarcompartment
• Three-pole design,bolted from panel topanel
• Easy switchgearextension
• Made of copper:– Fl E-Cu for w 630 A– Rd E-Cu for > 630 A to
1250 A
• Versions:– 630 A, > 12 kV:
With insulating shrink-onsleeve
– 1250 A, up to 24 kV:Rd E-Cu bare
HV HRC fuse assembly
• For transformer paneltypes TR and TR1
• For busbar voltage meter-ing panel type ME31-F
• HV HRC fuse linksacc. to DIN 43 625 (maindimensions) with strikerpin; version “medium”acc. to IEC 60 282/VDE 0670-4 *
– As short-circuit protec-tion before transformers
– With selectivity (depend-ing on correct selection)to upstream and down-stream connected equip-ment
• Requirements fulfilled asHV alternating currentswitch fuse combination
• Selection of HV HRCfuses for transformers
• Fuse replacement possi-ble only when feeder isearthed
• Option: Shunt release onoperating mechanism ofthree-position switch-disconnector
• Option: “Tripped indica-tion” of three-positionswitch-disconnector intransformer feeder (trans-former switch) for remoteelectrical indication withone normally-open con-tact (1NO)
“HV HRC fuse tripped”
Following the tripping of anHV HRC fuse link, the me-chanism for charging thespring must be set to the“OPEN” position
Subsequently, earthing canbe implemented by meansof the three-positionswitch-disconnector ande.g. the fuse can bereplaced.
Replacement of HV HRCfuse links
• Isolating and earthing ofthe transformer feeder
• Subsequent manualreplacement of theHV HRC fuse link
2
3
1
1 Busbar
2 Insulating cap (e.g.for Ur > 17.5 kV) onbusbar
3 Bushing-typeinsulator for busbar
Busbars
HV HRC fuse assembly
6
4
5
8
R-HA
41-0
52ep
s
4 Insulating sleeve
5 HV HRC fuse(not included in thescope of supply)
6 Earthing switch (ratedshort-circuit makingcurrent Ima = 4 kA)for cable connection
7 Cover for boltedcable lug connection(e.g. for rated voltageUr = 24 kV)
8 Cable sealing end(not included in thescope of supply)
HV HRC fuses in transformer panel type TRSide view
7
R-HA
41-0
71ep
s
Control board of a transformer feeder
“CLOSED“ indi-cation, manual ormotor operation
Indication “HVHRC fuse tripped”or “shuntrelease tripped”
“OPEN” indication
* Standards see page 43
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 23
Allocation of HV HRC fuses and transformers
The table opposite shows therecommended 3GD HV HRCfuse links (electrical data validfor ambient temperatures of upto 40 oC) for the fuse pro-tection of transformers
Recommendation
The three-position switch-disconnector in the trans-former feeder (transformerswitch) was combined withSiemens HV HRC fuse linksof type 3GD and tested *.
Standards
HV HRC fuse links withstriker pin, “medium“ versionaccording to
• IEC 60 282-1 */ VDE 0670-4 *
• IEC 60 787 / VDE 0670-402
• DIN 43 625 main dimensions
* Standards see page 43
Ratedsystemvoltage
kV
TransformerRating SN
kVA
Relativeimpedancevoltage uk
%
Ratedcurrent I1
A
Rated normal current of the HV HRC fuse
Lowest Highestvalue value
A A
6 to 7.2 5075
100
444
4.87.29.6
161620
161625
125160200
444
12.015.419.2
253240
253240
250315400
444
24.030.338.4
505063
5063
100
500630800
445 to 6
48.061.077.1
6380on request
100100on request
10 to 12 5075
100
444
2.94.35.8
101016
101016
125160200
444
7.29.3
11.5
162025
162025
250315400
444
14.518.323.1
253240
324050
500630800
445 to 6
29.036.446.2
506363
638080
100012501600
5 to 65 to 65 to 6
58.072.392.5
80100125
100100125
13.8 5075
100
444
2.13.24.2
61010
61010
125160200
444
5.36.78.4
161616
161620
250315400
444
10.513.216.8
202532
253232
500630800
445 to 6
21.026.433.5
405050
505050
10001250
5 to 65 to 6
41.952.4
6380
6380
15 to 17.5 5075
100
444
1.92.93.9
61010
61010
125160200
444
4.86.27.7
101616
101620
250315400
444
9.712.215.5
202532
252532
500630800
445 to 6
19.324.330.9
324050
405050
10001250
5 to 65 to 6
38.548.2
6363
6380
20 to 24 5075
100
444
1.52.22.9
66
10
66
10
125160200
444
3.64.75.8
101016
101016
250315400
444
7.39.2
11.6
162020
162025
500630800
445 to 6
14.518.223.1
253232
324032
100012501600
5 to 65 to 65 to 6
29.036.046.5
405063
405080
2000 5 to 6 57.8 80 80
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200724
Manual operatingmechanism
• Standard:As detachable levermechanism
• Option: Different operatinghandles 1) for the operatingmechanisms of the switch-disconnector and make-proof earthing switch
• Spring-operated mecha-nism
– For ring-main paneltypes RK and RK1
– For all three-positionswitches (except in paneltypes TR and TR1)
• Spring-operated /stored-energy mechanismFor transformer paneltypes TR and TR1 as wellas for busbar voltage me-tering panel type ME31-F
The three-position switch isoperated via a rocker withmetal bellows which isgas-tight and welded at theswitchgear vessel.
Motor operatingmechanism (option)
The manual operating me-chanisms can be equippedwith motor operating mecha-nisms both for the three-position switch-disconnectorand for the three-positiondisconnector.
Operating voltages for motoroperating mechanisms:– 24, 48, 60, 110, 220 V DC– 50/60 Hz 110 and 230 V AC
Electrical operation:
• Standard: Remote opera-tion (applied to terminal)
• Option: Local operationby momentary-contactrotary control switch
Shunt release (option)
Spring-operated/stored-en-ergy mechanisms can beequipped with a shunt re-lease. Remote electricaltripping of the three-positionswitch-disconnector is possi-ble via the magnetic coilof the shunt release, e.g.transformer overtemperaturetripping.
To avoid thermal overloadingof the shunt release in theevent of a continuous signalthat may be applied, theshunt release is switched offvia an auxiliary switch whichis mechanically coupled withthe three-position switch-disconnector.
Auxiliary switch (option)
Each operating mechanismof the three-position switch-disconnector can be option-ally equipped with an auxil-iary switch for the switchposition indication:– Function switch-discon-
nector or disconnector:CLOSED and OPEN:2NO + 2NC
– Function earthingswitch at thethree-position switch:CLOSED and OPEN:2NO + 2NC
– Separate earthing switch(at the feeder):CLOSED and OPEN:2NO + 2NC
Operating mechanisms for three-position switches
Operating mechanisms (examples)
Detachable lever mechanismas spring-operated mechanismfor ring-main feeders
R-HA
41-0
79ep
s
1 Terminal strip locatedin the low-voltageniche (optionally inthe low-voltagecompartment)
2 M.c.b. (option)in the low-voltageniche
3 Local-remote switch(option)
4 Actuation for themotor operatingmechanism of thethree-positionswitch-disconnector
5 Auxiliary contactorsof the motor operatingmechanism for lockingthe motor
6 Auxiliary switch
7 Switch positionindicator for thethree-positionswitch-disconnector
8 Locking device(standard for motoroperating mechanism)
9 Operating mechanismfor the three-positionswitch-disconnectorcoupled with the motoroperating mechanism
10 Shunt release (option)
11 Motor operatingmechanism
R-HA
41-0
70ep
s
Operating mechanism parts intransformer feeder
6
8
7
9
10
11
5
4
3
2
1
Abbreviations:
NO = normally-open contactNC = normally-closed contact
1) According toVDN*/ VDEW**recommendation
* Association of Germannetwork operatorsVDN e.V. in Germany(as of 2003)
** Association ofGerman Power Stations –VDEW e.V.(until 2003)
Technical data of the auxiliary switch
Breaking capacity
AC operation at40 Hz to 60 Hz
Operating Normalvoltage current
V A
DC operation
Operating Normal currentvoltage resistive inductive:
T=20 msV A A
up to 230 10 24 10 1048 10 960 9 7
110 5 4240 2.5 2
Rated insulationvoltage250 V AC/DC
Insulation groupC to VDE 0110
Continuous current10 A
Making capacity50 A
Rated switching capacity
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 25
Indicating and measuring equipment
Voltage detection systemsacc. to IEC 61243-5 orVDE 0682-415
• To verify safe isolation fromsupply
• Detection systems– Standard: HR system with
plug-in indicator– Option: LRM system with
plug-in indicator– LRM system with integrated
indicator type VOIS+,VOIS R+
– LRM system with integratedindicator, with integratedrepeat test of the interface,with integrated function testtype CAPDIS-S1+
– LRM system with integratedindicator, with integratedrepeat test of the interface,with integrated function test,with integrated signallingrelay type CAPDIS-S2+
HR system, LRM system
• Verification of safe isolationfrom supply phase by phaseby insertion in each socket pair
• Indicator suitable forcontinuous operation
• Safe-to-touch
• Routine-tested
• Measuring system and volt-age indicator can be tested
• Voltage indicator flasheswhen high voltage is present
VOIS+, VOIS R+
• Integrated display, withoutauxiliary power
• With indication “A1” to “A3”,(see legend)
• Maintenance-free; repeattest required
• With integrated 3-phase testsocket for phase comparison(also suitable for plug-in volt-age indicator)
• Degree of protection IP 67,temperature range –25 °C to+55 °C
• With integrated signallingrelay (only VOIS R+):
– “M1”: Voltage present atleast at one phase L1, L2 orL3
– “M2”: Voltage not present atL1, L2 and L3
plugged-involtageindicator
Voltage indicationwith capacitive voltage divider (principle)
– C1 Capacity integrated into bushing
– C2 Capacity of the connection leads andof the voltage indicator to earth
R-HA
40-1
03ep
sR-
HA40
-102
aep
s
Plug-in voltage indicatorper phase atthe panel front
Integrated voltage detection systemCAPDIS-S1+, -S2+
� ���� �����
���
��� ��� ��
����
��
mountedCAPDIS/VOIS
Voltage indicators and detection systems
R-HA
40-1
04ep
s
Integrated voltage indicatorVOIS+
A0
A1
A2
A3
A4
A5
A6
A0 CAPDIS-S2+: Operating voltagenot present
A1 Operating voltage present
A2 – Operating voltage not present– For CAPDIS-S2+:
Auxiliary power not present
A3 Failure in phase L1, operating voltageat L2 and L3 (for CAPDIS-Sx+ alsoindication: Earth fault)
A4 Voltage (not operating voltage)present
A5 Indication “Device-Function-Test”passed
A6 Indication “ERROR”, e.g. in case ofmissing auxiliary voltage(see: “error indication M4“)
Symbols shown
VOIS+,VOIS R+ CAPDIS-S1+ CAPDIS-S2+
���� �� ���� ��
�����
���� ��
���
�� �
����
CAPDIS-Sx+
Common features
• Maintenance-free
• Integrated display, withoutauxiliary power
• Integrated repeat test of theinterfaces (self-testing)
• With integrated function test(without auxiliary power) bypressing the “Device-Func-tion-Test” pushbutton
• With integrated 3-phase testsocket for phase comparison(also suitable for plug-involtage indicator)
• Degree of protection IP 54,temperature range –25 °C to+55 °C
• With circuit capacity
• With ready-for-servicemonitoring (external auxiliarypower required)
• With integrated signalling re-lay for signalling “M1” to “M4”(auxiliary power required):
– “M1”: Voltage present atphases L1, L2, L3
– “M2”: Voltage not present atL1, L2 and L3 (= active zeroindication)
– “M3”: Earth fault or voltagefailure, e.g. in one phase
– “M4”: External auxiliarypower missing (operatingvoltage present or not)
Features of CAPDIS-S1+
• Without auxiliary power
• With indication “A1” to “A5”(see legend)
• Without ready-for-servicemonitoring
• Without signalling relay (thuswithout auxiliary contacts)
Features of CAPDIS-S2+
• With indication “A0” to “A6”(see legend)
• Only by pressing the“Device-Function-Test”pushbutton: “ERROR” indica-tion (A6), e.g. in case ofmissing auxiliary voltage
ULE= UN / 3 during rated operationin the three-phase system
U2 = UA = Voltage at the capacitive interfaceof the switchgear or at the voltage indicator
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200726
Indicating and measuring equipment
Short-circuit/earth-faultindicators (option)
All ring-main feeders can beoptionally equipped with a 3-phaseshort-circuit or earth-fault indicator.
Characteristics
• Use depends on network conditions
• Optical signal when a preselectedpickup value is exceeded
• Depending on the type, reset– Manually– Automatically after a preset time
(e.g. 2 hours)
• With ring-type sensors
• Display panel, withdrawable housing,depending on the type
• Response values settable(depending on the type of device)
• Options:Remote electrical indication viacontact (1 NO + 1 NC) dependingon the type of device settable aspassing contact (W) or maintainedcontact (D).
Short-circuit indicator ALPHA M Short-circuit indicator ALPHA E
Short-circuit /earth-fault indicator EKA-3
R-HA
40-0
96ep
s
R-HA
40-0
97ep
s
R-HA
40-0
98ep
s
R-HA
40-0
95ep
s Red indication:Short-circuit indicatorhas picked up
Selection of short-circuit and earth-fault indicators
Indicator type 1) Reset
Ma- Automaticalnual after
Remote reset:A:by aux. voltageB:via NO contact(floating)
Automatical resetafter return ofpower supply
Response values
Short-circuit currentIK (A)Standard, othervalues on request
Response values
Earth-fault currentIE (A)Standard, othervalues on request
Opt.: Remote indicat. as
W (passing contact= standard)
D (maintained contact= option)
Short-circuit indicator
ALPHA M 5) x – – – 400, 600, 800, 1000 – W, D
ALPHA E 5) x 2 h or 4 h A (12-60 V AC/DC) – 400, 600, 800, 1000 – W, D
GAMMA 5.0 2)5) x • 4 s after returnof power supply
• 2 h or 4 h
– x (230 V AC, 50 Hz) 400, 600, 800, 1000 – W, D
ALPHA –automatic 5)
x 3 h A (12-60 V AC/DC) – self-adjusting,change of current with150 A w D i w 300 A,response time: t w 20 ms
– W, D
KA-Opto F 3) 5)
with 3 LEDindications
x after 2 h or 4 h B (1NO) – 400, 600, 800, 1000 – W, D
IKI-10 V2 SP 6) x after 2 h or 4 h B (1NO) – 400, 600, 800, 1000 – W, D
IKI-10 V2 L 6) x after 2 h or 4 h B (1NO) x (110-230 V AC, 50/60 Hz) 400, 600, 800, 1000 – W, D
Earth-fault/short-circuit indicator
EKA-3 4) 5) – – – x (230 V AC, 50 Hz) 450 40, 80, 160 W, D
DELTA M 5) x – – – 400, 600, 800, 1000 200 W, D
DELTA E 5) x after 2 h or 4 h A (12-60 V AC/DC) – 400, 600, 800, 1000 200 W, D
KA-Opto F+E 5) x after 2 h or 4 h B (1NO) – 400, 600, 800, 1000 40, 60, 80 W, D
IKI-10 V2 SP/ES 6) 7) x after 2 h or 4 h B (1NO) – 400, 600, 800, 1000 10% or 25% of IK W, D
IKI-10 V2 L/ES 6) 7) x after 2 h or 4 h B (1NO) x (110-230 V AC, 50/60 Hz) 400, 600, 800, 1000 10% or 25% of IK W, D
Earth-fault indicator
EKA-3/1 4) 5) – – – x (230 V AC, 50 Hz) – 40, 80, 160 W, D
IKI-10 V2 L/ES 6) 7) x after 2 h or 4 h B (1NO) x (110-230 V AC, 50/60 Hz) – 30, 55, 80, 100 W, D
Short-circuit/earth-fault indicators(examples)
Earth-fault indicator EKA-3/1
R-HA
40-0
94a
eps
Short-circuit indicator IKI-10 V2 SPR-
HA40
-100
eps
R-HA
40-0
99ep
s
Short-circuit indicator Opto F
1) Further types and other makesavailable on request
2) External auxiliary voltage required(120 V AC or 240 V AC)
3) Power supply required for the LED indications(indication by means of an integrated batteryor 12 V AC to 60 V AC voltage)
4) External auxiliary voltage required(230 V AC, 50 Hz), device with integrated battery
5) Make: Horstmann
6) Make: Kries Energietechnik
7) Ring-type sensor: d = 110 mm
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 27
Ready-for-service indicator
Characteristics
• Self-monitoring; easy to read
• Independent of temperatureand pressure variations
• Independent of site altitude
• Only responds to changes ingas density
• Option: Alarm switch“1 NO contact” for remoteelectrical indication
Mode of operation
For the ready-for-service indica-tor, a gas-tight measurementbox is installed on the inside ofthe switchgear vessel.
A coupling magnet, which isfitted to the bottom end of themeasurement box, transmitsits position to an outside arma-ture through the stainless steelswitchgear vessel. This arma-ture moves the ready-for-ser-vice indicator of the switchgear.
While changes in the gasdensity during the loss of gas,which are decisive for theinsulating capacity, are dis-played, temperature-depen-dent changes in the gaspressure are not. The gas inthe measurement box has thesame temperature as that inthe switchgear.
The temperature effect iscompensated via the samepressure change in both gasvolumes.
Verification of correctterminal-phase connections
• Possible by means of aphase comparison test unit(can be ordered separately)
• Safe-to-touch handling of thephase comparison test unit byinserting it into the capacitivetaps (socket pairs) of theswitchgear or the feeders.
3 Measurement box
4 Magnetic coupling5 Red indication:
Not ready for service6 Green indication:
Ready for service
Principle of operationof gas monitoringwith ready-for-service indicator
�������������
�
��
Stainless-steel vesselfilled with SF6 gas,gauge pressure500 hPa at 20 °C
Ready-for-serviceindicator
Ready-for-service indicator
Gas monitoring
Indicating and measuring equipment
Phase comparison test units
R-HA
40-0
59ep
s
Make: Pfisterer, type EPV– For plug-in voltage detection systems– For integrated voltage detection systems
(CAPDIS-S1+, -S2+)
R-HA
40-0
89ep
s
Make: Horstmann, type ORION 3.0combined test unit for– Phase comparison– Interface testing at switchgear– Voltage detection for
HR and LRM systems andCAPDIS-S1+, -S2+
R-HA
35-1
24ep
s
Make: Kries, type CAP-Phaseas combined test unit (HR and LRM)for:– Voltage detection– Repeat test– Phase comparison– Phase sequence test– Self-testThe unit doesn’t require any battery
or other makes
R-HA
41-1
14ep
s
Control board of a ring-main panel (example)
1
Indicator on control board:Ready for service
1 Ready-for-serviceindicator (option)
2 Indicator green:Ready for service(indicator red:Not ready forservice)
R-HA
41-1
13ep
s
2
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200728
Interlocking systems and locking devices
Interlocking of connectioncompartment
Ring-main andcircuit-breaker panel
• Access to the cable con-nection compartment(e.g. for cable testing) isonly possible providedthat the feeder is isolatedand earthed (three-posi-tion switch-disconnectorin “EARTHED” position)
• Option: Closing lock-outThis prevents the three-position switch-discon-nector from beingswitched from “OPEN” to“CLOSED” position,when the cable compart-ment cover is removed
Transformer panel
• Access to the cable con-nection compartment andto the HV HRC fuse com-partment (e.g. for replace-ment of HV HRC fuselinks) is only possible pro-vided that the feeder isisolated and earthed(three-position switch-disconnector in“EARTHED” position)
• Option: De-earthinglock-outThis prevents thethree-position switch-disconnector from beingswitched from position“EARTHED” to “OPEN”.
Switchgear interlocking
• Dependent on the va-cuum circuit-breaker oper-ating mechanism with
– Spring-operated or– Stored-energy mechanism
• Option: Switchgear-sidemechanical interlockingwith three-positionswitch-disconnector
• Vacuum circuit-breakercannot be closed whenthree-position switch-disconnector is in the“OPEN” position:
– Spring-operated mecha-nism: Hand crank openingis blocked
– Stored-energy mechanismwith closing solenoid3AY15 10: Pushbutton(S12) operated by mecha-nical interlock preventscontinuous command toclosing solenoid
Interlocking in circuit-breaker panel types LS1,LS1-U and LT10 (with 3AH5fixed-mounted vacuumcircuit-breaker)
• Option: Logical mechanicalinterlocking with three-po-sition switch-disconnector
• Earthing of feeder viathree-position switch-disconnector in“EARTHED” position
Interlocking in circuit-breaker panels (with 3AH6removable vacuum circuit-breaker)
• Option: For 630 A paneltypes LS11, LS11-U andLT11: Logical mechanicalinterlocking with three-po-sition switch-disconnector
• Standard: For 1250 Apanel types LS31, LS31-U,LS32 and LT31: Logicalmechanical interlockingwith three-positiondisconnector
• Logical mechan. interlock-ing of cable compartmentcover: Opening of cablecompartment cover onlypossible provided that thefeeder is earthed
Feeder earthing
• Standard: For panel typesLS11, LS11-U, LT11, LS31,LS31-U and LS32:Earthing by switching ofvacuum circuit-breaker3AH6 1) in position“CLOSED” and of three-position switch 2) inposition “EARTHED”
• Option: For circuit-breakerpanel types LS11, LS31and LS32: Earthing bymeans of an additionalmake-proof earthingswitch at the feeder withinspection window in thecable compartment cover
Locking devices
The three-position switch-disconnector can be lockedon the operating mechanismside in any position (option).
Interlocking systems
Locking device (option)
R-HA
41-0
64ce
psR-
HA41
-081
eps
Interlocking for cable compartment cover
Removed cable compartment coverwith earthed bus sectionalizer panel
Locking device of the detachable lever mechanisme.g. for padlock
1) With additional locking device –optionally with signalling switch – forsecuring the “CLOSED” position ofthe vacuum circuit-breaker for feeder“EARTHED”
2) Three-position switch as– Switch-disconnector in panel
types LS11, LS11-U and LT11– Disconnector in panel types
LS31, LS31-U, LS32 and LT31
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 29
4MC63 three-phase current transformers for panel types LS ... and LT ...
Application
• For circuit-breaker panelstype LS ...
• For bus sectionalizer panelstype LT ...
• Option: For ring-main panelstype RK ...
Features
• According to IEC 60 044-1/VDE 0414-1
• Designed as a three-polering-core currenttransformer
• Free of dielectricallystressed cast-resin parts (dueto design)
• Insulation class E
• Inductive type
• Climate-independent
• Secondary connection bymeans of a terminal stripinside the panel
Installation
• Arranged outside the switch-gear vessel on the bushings
• Factory-assembled
Other designs(option)
Three-phase current transfor-mers for protection equipmentbased on c.t. operation:
• 7SJ45 protection relay asdefinite-time overcurrentprotection
• Definite-time overcurrentprotection relay,make SEG, type WIP 1,WIC 1
Technical data 4MC63 53 three-phase current transformer
for IN < 150 Afor ID = 630 A
for IN < 400 Afor ID = 630 A
for IN < 1000 Afor ID = 1250 A
Primary data
Max. equipment operatingvoltage Um
0.72 kV 0.72 kV 0.72 kV
Rated current IN A 150 100 75 50 400 300 200 1000 750 600 500
Rated short-durationpower-frequencywithstand voltage(winding test)
3 kV 3 kV 3 kV
Rated thermal short-timewithstand current Ith
25 kA 25 kA 25 kA
Rated continuous thermalcurrent ID
630 A 630 A 1250 A
Transient overloadcurrent
1.5 x ID / 1 h 2 x ID / 0.5 h 1.5 x ID / 1 h
Rated peak withstandcurrent Idyn
unlimited unlimited unlimited
Secondary data
Rated current A 1 0.67 0.5 0.33 1 0.75 0.5 1 0.75 0.6 0.5
Rating VA 5 3.33 2.5 1.67 5 3.75 2.5 5 3.75 3 2.5
Rated current (option) 5 A 5 A 5 A
Current at ID 4.2 A 1.575 A 1.25 A
Protec-tioncore
Class 10 P 10 P 10 P
Overcurrent factor 10 10 10
Other values available on request
R-HA
41-0
48ep
s
4MC63 53 three-phasecurrent transformer
4MC63 53 three-phase current transformeron the bushings of the three-positionswitch-disconnector
R-HA
41-0
44ep
s
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200730
4MC70 33 cable-type current transformerson the cable at the panel connection
Application
• For circuit-breaker panelstype LS ...
• For ring-main panelstype RK ...
• For transformer panelstype TR ...
Features
• According to IEC 60 044-1/VDE 0414-1
• Designed as a single-polering-core current transformer
• Only for shielded cables
• Climate-independent
• Free of dielectricallystressed cast-resin parts (dueto design)
• Insulation class E
• Inductive type
• Secondary connection bymeans of a terminal stripinside the panel
Installation
• 4MC70 33 cable-type currenttransformer for panel typesLS ...
• 4MC70 31 cable-type currenttransformer: e.g. for paneltypes RK ..., K ... and TR ...
• Arranged on the cable atthe panel connection
• Transformers mounted on asupporting plate at ourfactory; final assembly onthe cables on site
* Depending on the core data
** Available installation heightinside panel types RK or RK1:Approx. 285 mm, depending onmake, type and cross-section ofsealing end Other values available on request
R-HA
41-0
49a
eps
R-HA
41-0
25ep
s
4MC70 31 cable-typecurrent transformerH
4MC70 33 cable-typecurrent transformer,4 different overall heights
4MC70 33 and 4MC70 31 cable-type current transformers
Technical data 4MC70 33 cable-typecurrent transformer
4MC70 31 cable-typecurrent transformer
Primary data
Max. equipment operatingvoltage Um
0.72 kV 0.72 kV
Rated current IN 30 A to 600 A 50 A to 600 A
Rated short-durationpower-frequencywithstand voltage(winding test)
3 kV 3 kV
Rated thermal short-timewithstand current Ith
25 kA 25 kA
Rated continuous thermalcurrent ID
1.0 x INoption: 1.2 x IN
1.0 x INoption: 1.2 x IN
Transient overloadcurrent
1.5 x ID / 1 h or 2 x ID / 0.5 h 1.5 x ID / 1 h or 2 x ID / 0.5 h
Rated peak withstandcurrent Idyn
unlimited unlimited
Secondary data
Rated current 1 A (option: 5 A) 1 A (option: 5 A)
Meas-uringcore
Class 0.2 0.5 1 1
Overcurrent factor FS10 (option: FS5) FS5 (option: FS10)
Rating 2.5 VA to 10 VA 2.5 VA to 10 VA
Pro-tectioncore
Class 10 P 5 P –
Overcurrent factor 10 10 –
Rating 2.5 VA to 10 VA –
Option: Secondary tap 1 : 2 (e.g. 150 A – 300 A) 1 : 2
Dimensions
Overall height H ** mm 50* 100* 170* 285* 89
Outside diameter Ø 145 mm 85 mm x 114 mm
Inside diameter Ø 55 mm Ø 40 mm
For cable diameter Ø 50 mm Ø 36 mm
H
RHA4
1-02
4aep
s
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 31
4MA7 block-type current transformers and 4MR voltage transformers
Application
• For billing metering panelstype ME1 ...
• For bus riser paneltype HF …
• For mounting at thefeeder
Features
4MA7 current transformer
• According to IEC 60 044-1/VDE 0414-1
• Dimensions according toDIN 42600-8
• Designed as a single-poleindoor block-type currenttransformer
• Cast-resin insulated
• Insulation class E
• Secondary connection bymeans of screw-typeterminals
4MR voltage transformer
• According to IEC 60 044-2/VDE 0414-2
• Dimensions according toDIN 42600-9 (smallmodel)
• Designed as an indoorvoltage transformer:
– Type 4MR, single-pole– Option: Type 4MR, two-pole
• Cast-resin insulated
• Insulation class E
• Secondary connection bymeans of screw-typeterminals
R-HA
41-0
60a
eps
4MA7 block-type currenttransformer,single-pole
4MR14 voltagetransformer,single-pole
4MR voltage transformer and4MA7 block-type current transformer installed inbilling metering panel type ME1
R-HA
41-0
29a
eps
R-HA
41-0
30a
eps
Technical data
4MA7 single-pole block-type current transformer (other values on request)Primary data
Max. equipment operating voltage Um kV 3.6 7.2 12 17.5 24
Rated short-durat. power-freq. withstand volt. Ud kV 10 20 28 38 50Rated lightning impulse withstand voltage Up kV 20 60 75 95 125Rated current IN A 20 to 1250Rated thermal short-time withstand current Ith kA up to 25Rated continuous thermal current ID up to 1.0 x In (option: 1.2 x In)Rated peak withstand current Idyn max. 2.5 x Ith
Secondary data
Rated current A 1 or 5Measuring Class 0.2; 0.5; 1core Overcurrent factor FS5 or FS10
Rating VA 10 to 15Protection Class 5 P or 10 Pcore Overcurrent factor 10
Rating VA 5 to 15
4MR single-pole voltage transformer (other values on request)Primary data
Max. equipment operating voltage Um (= 1.2 x UN) kV 3.6 7.2 12 17.5 24
Rated short-durat. power-freq. withstand volt. Ud kV 10 20 28 38 50Rated lightning impulse withstand voltage Up kV 20 60 75 95 125Rated voltage UN kV 3.3/ 3 3.6/ 3
4.8/ 35.0/ 36.0/ 36.6/ 3
7.2/ 310.0/ 311.0/ 3
13.8/ 315.0/ 3
17.5/ 320.0/ 322.0/ 3
Rated voltage factor (8h) 1.9 x UN
Secondary data
Rated voltage V 100/ 3110/ 3 (option)120/ 3 (option)
Rated voltage for auxiliary winding (option) V 100/3110/3 (option)120/3 (option)
Rating VA 20 50 100Class 0.2 0.5 1.0
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200732
Cable connection
General features
• Connecting lugs for sealing endsarranged one behind the other
• Uniform cable connection heightfor the respective panel types
• With cable bracket, e.g. type C40according to DIN EN 50 024
• Access to the cable connectioncompartment only if feeder hasbeen isolated and earthed
Special features
– In ring-main panels– In circuit-breaker panels– In cable panels
• For thermoplastic-insulated cables
• For paper-insulated mass-impregnated cables withadapter systems
• For connection cross-sections up to 300 mm2
• Cable routing downwards
– In transformer panels:
• For thermoplastic-insulated cables
• For connection cross-sections up to 120 mm2:Cable lug max. 32 mm wide
• For rated normal currentsof 200 A
For options see figures
Cable cross-sections
Note
Cable sealing ends and cable clampsare not included in the scope of supply
Cable connection (examples)
Cable connection compartment with cablesealing ends (options: A, B, C 1) and D 1), see below)
Ring-main panel type RKCable connection compartment as delivered
L3 L2 L1 L1L2L3
Transformer panel type TRCable connection compartment as delivered
Cable connection compartment with cablesealing ends (option: A 2), see below)
L3L2L1
R-HA
41-0
50ep
s
R-HA
41-0
51ep
s
R-HA
41-0
53ep
s
R-HA
41-0
52ep
s
R-HA
41-0
55ep
s
R-HA
41-0
67ep
s
L3L2L1
Cable connection compartment with cablesealing ends (options: A, B, C and D, see below)
Circuit-breaker panel type LS11Cable connection compartment as delivered
Options A Mounted cable clamps 2)
B Short-circuit / earth-fault indicator
C Double cable connection
D Suitable for connection of surge arresters 3)
5
1
4
3
7
8
14
10 13
12
2
6
L1L2
L3
9
11
1) Only with ring-main panel type RK1
2) Cable clamps with transformerpanels type TR ... partly mountedunderneath the panel in the cablebasement
3) Make Siemens, type 3EK7,other makes on request
Panel type Connectable cables xconnection cross-section
No. x mm2
for rated voltage
12 kV 17.5 kV 24 kV
K Standard
On request
1x 300 1x 300 1x 300
2x 300 – –
K1 2x 400 2x 400 2x 400
RK, Standard 1x 300 1x 300 1x 300K-E
On request 2x 300 – –
RK1, K1-E 2x 300 2x 300 2x 300
LS1 2x 300 2x 300 2x 300
LS11, LS31 2x 400 2x 400 2x 300
LS32 Standard
Option
On request
3x 400 3x 400 3x 300
4x 300 4x 300 –
– – 4x 300
ME1-K, ME1-KS 3x 400 3x 400 3x 300
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 33
1) Transformer panel types TR ...:– Lower edge of sealing end below panel– Cable lugs of sealing ends up to 32 mm width– Owing to the various sealing end lengths, some of
the mounted cable clamps are underneath the panel
2) Circuit-breaker panel types LS11, LS31 and LS32:– Lower edge of sealing end below panel
Selection data for various cable sealing ends
1 As-delivered condition,e.g. for Up w 95 kV, preparedfor cable sealing end
2 As-delivered condition,e.g. for Up > 95 kV, additionally withinsulating sleeve, preparedfor cable sealing end
3 Phase L1:Make Lovink-EnertechType IAEM 20, 240 mm2 (20 kV)
4 Phase L2:Make Tyco ElectronicsType EPKT 24 C / 1X,185 mm2 (24 kV),as shrink-on sealing end,for severe ambient conditions
5 Phase L3:Make Prysmian Kabel und Systeme(Pirelli Elektrik)Type ELTI mb-1C-2h-C-T3,240 mm2 (24 kV)
6 As-delivered condition, preparedfor cable sealing end
7 Phase L1:Make Lovink-EnertechType IAEM 20,95 mm2 (20 kV)
8 Phase L2:Make Tyco ElectronicsType TFTI/5131,95 mm2 (24 kV),as push-on sealing end
9 Phase L3:Make EuromoldType AIN, 95 mm2 (24 kV)
10 As-delivered condition,e.g. for Up < 95 kV, preparedfor cable sealing end
11 As-delivered condition,e.g. for Up W 95 kV, additionally withinsulating cap, prepared forcable sealing end
12 Phase L1:Make Lovink-EnertechType IAES 20,240 mm2 (20 kV)
13 Phase L2:Make Prysmian Kabel und Systeme(Pirelli Elektrik)Type ELTI 1C-24-D-T3,240 mm2 (24 kV),as indoor sealing end,for severe ambient conditions
14 Phase L3:Make EuromoldType AIN 20,240 mm2 (24 kV)
Connection height **of cables abovefloor or abovelower edge of panel:
Cable sealing ends(examples)
Note
Depending on make andtype, the termination of thecable sealing end (= shieldearth) for the 3-core thermo-plastic-insulated cable andthe fitted cable clamp (option)may be located underneath thepanel in the cable basement.This must be taken intoaccount in panels withfloor cover (option).
3) Cable sealingend type withinsulation shields
* On request:Max. connectioncross-section ofcable sealing endtypes
**Due to the installation of4MA cast-resin insulatedblock-type current trans-formers in panels RK1and LS1, the connectionheight of the cables isreduced to 380 mm
Panel type TR …
Dimension a~ 530 mm at 12 kV~ 380 mm at 24 kV
����� ������
�����
�����
��
���
�����
��
���
� ����
���
����� ������
Panel type LS1 ...
Panel type RK ...
Panel type LS11 ...
Single-core thermoplastic-insulated cables for < 12 kV (6/10 kV)
Euromold AIN 10 25–300 (500*)35 MSC35 MSC (option 3))
16–300 (500*)25–300 (500*)
ITK-212 50–300 (400*)Prysmian Kabel undSysteme (Pirelli Elektrik)
ELTI mb-1C-12 35–240ELTI-1C-12 25–300
Tyco Electronics IXSU-F 16–300 (500*)TFTI 25–300 (400*)EPKT 1) 16–300
Lovink-Enertech IAEM 10 25–300IAES 10 25–300 (500*)
3M Germany 92-EB 6x-1 35–300 (400*)Südkabel SEHDI 10.2 35–300 (500*)
SEI 12 70–300nkt cables TI 12 25–240
AV 10 C 25–300 (500*)AV 10 E 25–300 (500*)
Single-core thermoplastic-insulated cables for > 12 kV to < 24 kV (12/20 kV)
Euromold AIN 20 25–300 (630*)35 MSC35 MSC (option 3))
25–7025–185
36 MSC 2)
36 MSC (option 3))95–300 (500*)95–300 (500*)
ITK-224 25–240Prysmian Kabel undSysteme (Pirelli Elektrik)
ELTI mb-1C-24 35–240ELTI-1C-24 25–300
Tyco Electronics IXSU-F 25–300 (500*)TFTI 25–300 (400*)EPKT 16–300 (500*)
Lovink-Enertech IAEM 20 25–300IAES 20 25–300 (500*)
3M Germany 93-EB 6x-1 50–300 (400*)Südkabel SEHDI 20.2 35–300 (500*)
SEI 24 25–240nkt cables TI 24 25–240
AV 20 E 25–300 (500*)AV 10 E 25–300 (500*)
Three-core thermoplastic-insulated cables for < 12 kV (6/10 kV)
Euromold AIN 10 25–300 (500*)SR-DI 12 35–300 (500*)
Prysmian Kabel undSysteme (Pirelli Elektrik)
ELTI-3C-12 25–300
Tyco Electronics IXSU-F 16–300 (500*)Lovink-Enertech IAES 10 25–300
GHKI 16–300 (400*)
Three-core thermoplastic-insulated cables for > 12 kV to < 24 kV (12/10 kV)
Euromold SR-DI 24 2) 35–300 (500*)Lovink-Enertech GHKI 25–300 (500*)
Cable sealing end, e.g. for panel types RK..., LS1..., LS11..., LS31..., LS32and TR ...1) (for connection heights of cables see opposite dimension drawings)
Make Type Cross-section in mm2
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200734
Low-voltage equipment
Low-voltage niche(standard)
• Screwed-on cover as– Cover (available mounting
depth behind ofapprox. 184 mm)
– Frame cover, approx.46 mm deeper version(available mountingdepth behind ofapprox. 230 mm)
• For accommodation ofterminals and standardprotection devices, e.g.in circuit-breaker panelscombined with framecover for panels
– Type LS1: Protectionrelays (with max. 75 mmwide mounting frame), e.g.– Type 7SJ45, 7SJ46– Make SEG, type WICOn request:– 7SJ60– Make SEG, WIP1
– Type LS11, LS31 and LS32:Protection relays (withmax. 75 mm widemounting frame), e.g.type 7SJ45, 7SJ46,7SJ60.On request:– 7SJ61/62 (150 mm wide)– Make SEG, WIP1
• For bus wires and/or con-trol cables; niche open atthe side to the adjacentpanel
• Safe-to-touch, separatedfrom high-voltage part ofthe panel
• Degree of protectionIP 3X (standard)
Low-voltage compartment(option)
• Overall heights:350 mm, 550 mm
• Available mounting depth:442 mm
• Overall widths:375 mm, 500 mm, 750 mm
• For mounting on the panel
• Dependent on the panel-specific scope of thesecondary equipment
• For accommodation of pro-tection, control, measuringand metering equipment,e.g. multifunction protec-tion relay SIPROTEC 47SJ61/62/63 or othermakes of protection relays
• Compartment 750 mmwide for panel type LS32
1 LED indications
2 LCD
3 Navigation keys
4 Function keys
5 Option:Short-circuit/earth-faultindicator
6 Frame cover oflow-voltage niche(can be unscrewed)
7 Momentary-contactrotary control switchON-OFF for motoroperating mechanismof the three-positionswitch-disconnector
8 Local-remote switchfor three-positionswitch-disconnector
9 Control board
10 Low-voltage nicheopen
11 Option:Installed equipment
12 Panel front
13 Option:Multifunctionprotection relaySIPROTEC 4 7SJ61on swing-out frame
14 Option:Protection devicemake SEG,type WIC
Electronic functions
Multifunction protectionrelay SIPROTEC 4 7SJ62or 7SJ63 with the followingfeatures:
1 User-programmable LEDswith application-specificlabel, for displaying anydesired process andequipment data
2 LCD for process andequipment data, e.g. for:
– Measuring and meteringvalues
– Binary information on thestatus of switching pointand device
– Protection data– General indications– Alarms
3 Keys for navigation inmenus and for enteringvalues
4 Four user-programmablefunction keys forfrequently performedactions
Low-voltage cables
• Control cables of thepanel to the low-voltagecompartment are con-nected via multi-pole,coded module plugconnectors
• Option: Plug-in bus wiresfrom panel to panel insidethe low-voltage niches,optionally in separatecable duct on the panel
Low-voltage niche (examples)
SIPROTEC 47SJ61:
1 LED indications
2 LCD
3 Navigation keys
4 Function keys
Low-voltage compartment (option)
R-HA
41-0
62a
eps
R-HA
41-0
83ep
sR-
HA41
-059
aep
s
In bus sectionalizer panel type LT11(low-voltage niche closed)
In circuit-breaker panel type LS1(low-voltage niche open)
In billing metering panel type ME1(low-voltage niche open)
On circuit-breaker panel type LS1for additional low-voltage equipment
6
5
7
8
9
3
2
2
1
4
3
10
R-HA
41-0
58ep
s
11
9
10
11
12
1
4
14
13
��$ ������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 35
Ring-main panels, transformer panels�������������������������
�� ����� �� ��������
������
�� ���
)����
��*�
��
������
���
���
��*�
�������������������������
���
�� ��������
��
)����
��
��������������������������
�� ����� �� ��������
) ��
��
)����
��*�
��
���
���
��*�
� �
1) Location of voltage transformerin left-hand panel,e.g. in panel typeLT10 or LT11
* Option:Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment
*** For panel type RK1 the cableconnection height is reducedto approx. 380 mm for panelversion with 4MA block-typecurrent transformer
Ring-mainpanels
Ring-main panelfor panel combinations
Transformerpanels
Type RK Type RK1
Type RK-U
Type TR1Type TR
%�$�������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200736
Cable panels�������������������� ���
������ �
���
�� ����� �� ��������
���
��
)����
��*�
��
���
���
��*�
������������������������
�� ����� �� ��������
���
��
)����
��*�
��
���
���
��*�
� �
Type K Type K1
Type K1-EType K-E
Cable panels
Cable panels(with additional make-proofearthing switch)
* Option:Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment
%�$�������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 37
Circuit-breaker panels��������������� ��������
��� ����� �� ��������
������
�� �
��
)����
��
������
���*�
)� �������������������"�����
���
��� ����� �� ��������
���
��
)���� �
�
�� �
�
���
���
�� �
)� ���
��
1) Type designation of thevacuum circuit-breaker
2) Option: Inspection window
3) Option: With make-proofearthing switch
* Option: Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment– Approx. 184 mm with cover– Approx. 230 mm with extended
frame cover
*** The cable connection height isreduced to approx. 380 mm forpanel version with 4MA block-typecurrent transformer
Circuit-breaker panel630 Awith 3AH5 1)
Type LS1
Type LS11 (with make-proof earthing switch)
Circuit-breaker panels630 Awith 3AH6 1)
Type LS11 (withoutearthing switch)�����������������������
���
��� ����� �� ��������
���
��
)����
��
�� �
�
���
���
�� �
)� ���
�
�����
Type LS31 3) (for connectionof max. 2 cables)
Type LS32 3) (for connectionof 3 cables)
Circuit-breaker panels1250 Awith 3AH6 1)
%�$�������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200738
Bus sectionalizer panels with bus riser panel��������������������� ���������
���
�� ��������
��
)����
��
)� �������������������������
���
�� ��������
��
)����
��
)� ���
Type LT10 + type HF
Type LT11 + type HF
Bus sectionalizer panel630 Awith 3AH5 1)
Bus sectionalizer panel630 Awith 3AH6 1)
1) Type designation of thevacuum circuit-breaker
* Option:Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment– Approx. 184 mm
with cover– Approx. 230 mm
with extended frame cover
Bus sectionalizer panel1250 Awith 3AH6 1)���������������� �����
���
�� ��������
��
)����
��
)� ���
Type LT31 + type HF
%�$�������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 39
Bus sectionalizer panels������������������������
��� ��������
�� ���
)����
��
������
���
���
�
��������������������������
��� ��������
��
)����
��
�
���
���
Type LT2(� type RK-U with type HF)
Type LT2-W
* Option:Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment
Bus sectionalizer panelswithout transformers
Bus sectionalizer panelswith transformers
Type LT22(� type RK-U with type RK-U)
Type LT22-W
%�$�������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200740
Billing metering panels������������������������
��� ��������
�� �
�� �
�
������
)����
��������������������������
��� ��������
�� �
�
)����
������ �������������������
��� ��������
�� �
�
)����
* Option:Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment
Billing metering panel(standard)
Billing metering panelsfor busbar and cableconnection
Billing meteringpanel for2nd current transformer set
Type ME1
Type ME1-S(for busbar connection)
Type ME1-H
��������������������� �� �
���
��� ��������
�� �
�
)����
��� ��� ���
���
Type ME1-K(for cable connection)
%�$�������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 41
Busbar voltage metering panels, busbar earthing panels, bus riser panels
�������������������������
�� ��������
��
)����
��
���
���
)��
�
���������
Busbarvoltage meteringpanels
Type ME3 Type ME31-Fwith fuses
1) Location of voltagetransformer inleft-hand panel
* Option:Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment
��������������������������
�� ��������
��
)����
��
Busbarearthingpanels
Type SE1without transformers
�����������������������
���
��� ��������
��
)����
��
Type SE2with voltage transformers
��������������������������
�� ��������
�� �
�
)����
Busriserpanels
Type HFwithout transformers
�������������������������
���
�� ��������
�� �
�
)����
Type HFwith transformers
%�$�������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200742
Floor openings (dimensions in red) and fixing points
Fo
rp
an
elw
idth
375
mm
�����*��
��
�����
���
��
��
��*�
��
�� ���
��
�� �
����
�
��+���
���+��
���
������
��
��
��
���
�
��*�
�
�
�
�
������*��
��
���
���
��
��
��*�
��
�� ���
��
�� �
����
�
��+���
���+��
���
������
��
��
�
������ ��
��
���
���
���
��
��
���
��
�� ��
��
����
����
�
��+���
���+��
���
������
��
��
��
���
�
��*�
�
�
�
�
������ ��
���
���
���
��
��
���
��
�� ��
��
����
���
�
��+���
���+��
���
������
��
��
�
��������*��
��
���
���
���
��
��
��*�
��
�� � �
��
����
����
�
��+���
���+��
���
������
��
��
��
���
�
��
��
�
�
�
�
�������
��
����
����
��
���
��
��
�
�
With cable connection
1 Wall distance
2 Fixing frame (base)of an individual panel or panel block
3 Floor opening for high-voltage cables and,where applicable, control cables; in paneltypes LS11, LS31 and LS31-K: floor openingalso possible below floor cover
4 Position of the led-in cables for the feeder
5 Fixing points
6 Floor opening if required for panelswithout cable connection�����
��*��
���
���
���
��
��
��*�
��
�� � �
��
����
����
�
��+���
���+��
���
������
��
��
�
��
��
�
Without cable connection
Fo
rp
an
elw
idth
500
mm
Without cable connectionWith cable connection
Fo
rp
an
elw
idth
750
mm
With double cable connection
For dimensions not shownsee illustration on the left
Without cable connection
For pa-nel type
RKKK-ETR
For pa-nel type
RK-UME3HFSE1
For pa-nel type
RK1K1+K1-ETR1
For pa-nel type
RK1-UME31-FSE2
For pa-nel type
LS1(Dim. a= 562.5)
ME1-K(Dim. a= 375)
ME1-KS(Dim. a= 375)
For pa-nel type
LS1-ULS11-ULT10LT11LT2LT2-WLT22LT22-WME1ME1-SME1-H
LS31-ULT31
For pa-nel type
LS11
LS31
For pa-nel type
LS32
With cable connection
Fo
rp
an
elw
idth
875
mm
With cable connection��������*��
���
���
���
��
��
��*�
��
�� ���
��
����
� ����
��+���
���+��
���
������
��
��
�
���
���
��
��
���
��
��
� �
�
�
�
�
�
%�$�������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 43
Altitude correction factor Ka
For site altitudesabove 1000 m, thealtitude correctionfactor Ka is recom-mended, depend-ing on the actualsite altitude abovesea level.
Rated short-dur. power-freq. withstand volt. for site altitudes > 1000 m to be selected
W Rated short-duration power-frequency withstand voltage up to w 1000 m · Ka
Rated lightning impulse withstand voltage for site altitudes > 1000 m to be selected
W Rated lightning impulse withstand voltage up to w 1000 m · Ka
Example:
3000 m site altitude above sea level17.5 kV switchgear rated voltage95.0 kV rated lightning impulse withstand voltage
Rated lightning impulse95 kV · 1.28 = 122 kVwithstand volt. to be selected
Standards, specifications, guidelines, classification
Standards
The SIMOSEC switchgearcomplies with the relevantstandards and specificationsapplicable at the time oftype tests.
In accordance with the harmo-nization agreement reached bythe countries of the EuropeanCommunity, their nationalspecifications conform to theIEC standard.
� ������� ������
�� �
����
����
����
�������� � �� ����
�
����
�����
��
����
����
������
�
Alti
tude
corr
ectio
nfa
ctor
Site altitude in m above sea level
Type of service location
SIMOSEC switchgear can beused as an indoor installation inaccordance with IEC 61 936(Power installations exceeding1 kV AC) and VDE 0101
• Outside lockable electricalservice locations at placeswhich are not accessible tothe public. Enclosures ofswitchgear can only beremoved with tools.
• Inside lockable electricalservice locations. A lockableelectrical service location isa place outdoors or indoorsthat is reserved exclusively forhousing electrical equipmentand which is kept under lockand key. Access is restrictedto authorized personnel andpersons who have beenproperly instructed in electri-cal engineering.Untrained or unskilled per-sons may only enter underthe supervision of authorizedpersonnel or properly instruc-ted persons.
Terms
“Make-proof earthing switches”are earthing switches withshort-circuit making capacityaccording to– IEC 62 271-102
and– VDE 0671-102
Colour of panel front
Siemens standard (SN)47 030 G1,colour no. 700 / light basic(similar to RAL 7047 / grey)
Insulating capacity
• The insulating capacity is veri-fied by testing the switchgearwith rated values of short-duration power-frequencywithstand voltage and light-ning impulse withstand volt-age according to IEC 60 694/VDE 0670-1000 (seetable “Insulating capacity”).
• The rated values are referredto sea level and to normalatmospheric conditions(1013 hPa, 20 °C, 11 g/m3
humidity in accordance withIEC 60 071 and VDE 0111).
• The insulating capacitydecreases with increasingaltitude.For site altitudes above1000 m (above sea level)the standards do not provideany guidelines for the insula-tion rating. Instead, specialregulations apply to thesealtitudes.
• Site altitude– As the altitude increases, the
insulating capacity of insula-tion in air decreases due tothe decreasing air density.This reduction is permitted upto a site altitude of 1000 maccording to IEC and VDE.
– For site altitudes above1000 m a higher insulationlevel must be selected. Itresults from the multiplica-tion of the rated insulationlevel for 0 to 1000 m with thealtitude correction factor Ka.
Result:
According to the abovetable, a switchgear for arated voltage of 24 kV witha rated lightning impulsewithstand voltage of125 kV is to be selected.
Table – Insulating capacity
Rated voltage (rms value) kV 7.2 12 15 17.5 24
Rated short-duration power-frequency withstand voltage (rms value)
– Across isolating distances kV 23 32 39 45 60
– Between phases and to earth kV 20 28 36 38 50
Rated lightning impulse withstand voltage (peak value)
– Across isolating distances kV 70 85 105 110 145
– Between phases and to earth kV 60 75 95 95 125
Overview of standards (August 2007)
IEC standard VDE standard EN standard
Switchgear SIMOSEC IEC 60 694 VDE 0670-1000 EN 60 694
IEC 62 271-200 VDE 0671-200 EN 62 271-200
Devices Circuit-breaker IEC 62 271-100 VDE 0671-100 EN 62 271-100
Disconnector and earthingswitch
IEC 62 271-102 VDE 0671-102 EN 62 271-102
Switch-disconnector IEC 60 265-1 VDE 0670-301 EN 60 265-1
Switch-disconnector /fuse combination
IEC 62 271-105 VDE 0671-105 EN 62 271-105
HV HRC fuses IEC 60 282-1 VDE 0670-4 EN 60 282
Voltage detection system IEC 61 243-5 VDE 0682-415 EN 61 243-5
Degree ofprotection
– IEC 60 529 VDE 0470-1 EN 60 529
Insulation – IEC 60 071 VDE 0111 EN 60 071
Transformers Current transformer IEC 60 044-1 VDE 0414-1 EN 60 044-1
Voltage transformer IEC 60 044-2 VDE 0414-2 EN 60 044-2
Installation – IEC 61 936-1 VDE 0101 –
������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200744
Standards, specifications, guidelines, classification
Internal arc classification(option)
• Safety of operating personnelensured by tests to verify in-ternal arc classification
• The possibility of arc faultsin SIMOSEC switchgear ismuch less due to:
– Metal-enclosed and gas-insulated switching functions(e.g. of three-position switch-disconnector and 3AH5vacuum circuit-breaker)
– Logical arrangement ofoperating mechanismelements and mechanicalinterlocks
– Short-circuit-proof feederearthing by means of thethree-position switch-disconnector
• The internal arc fault testsmust be performed in accord-ance with IEC 62 271-200 /VDE 0671-200 *
Criteria for internal arc faults
• Criteria according toIEC 62 271-200 /VDE 0671-200 * with respectto the behaviour in case ofinternal arc faults
• Definitions of criteria:– Acceptance criterion 1
Covers and doors remainclosed. Limited deformationsare accepted.
– Acceptance criterion 2No fragmentation of theenclosure. No projection ofsmall parts above 60 gweight.
– Acceptance criterion 3No holes in the accessiblesides up to a height of 2 m.
– Acceptance criterion 4Indicators do not ignite dueto the effect of hot gases.
– Acceptance criterion 5The enclosure remainsconnected to its earthingparts.
• For cable testing– the installation and
operating instructions ofthe switchgear
– the standardsIEC 62 271-200 /VDE 0671-200Section 5.105 *
– the information on manu-facturer-dependent cablesealing ends
– the cable version(e.g. paper-insulated mass-impregnated cables, PVCcables or XLPE cables)
must be observed.
1) VLF = very low frequency
2) Referred to: U0 /U (Um = 6.35/11 (12) kV)
* Standards see page 43
Cable testing
• For circuit-breaker andswitch-disconnector feeders
• DC voltage test
before the test:
Remove or disconnect anyvoltage transformers at thecable connection inSIMOSEC switchgear.
SIMOSEC switchgear forrated voltages up to 24 kVcan be subjected to cabletests at a max. DC testvoltage of 72 kV or accordingto VDE at 70 kV, 15 min.The voltage at the busbarmay be 24 kV in this case.
Test voltages:
Ratedvoltage
U0 /U (Um) Max. test voltageapplied to cable
VLF 1), 0.1 Hz acc. to IEC VDE 0278
3 x U0 6 x U0, 15 min.ULF U = max. U =
Ur (kV) (kV) AC (kV) DC (kV) DC (kV)
12 6 / 10 (12) 19 24 38 2)
24 12 / 20 (24) 38 48 70
Climate and ambientconditions
SIMOSEC switchgear may beused, subject to possible addi-tional measures – e.g. panelheaters or floor covers –under the following ambientconditions and climate classes:
• Ambient conditions– Natural foreign materials– Chemically active pollutants– Small animals
• Climate classesThe climate classes areclassified according toIEC 60 721-3-3
SIMOSEC switchgear is largelyinsensitive to climate andambient conditions by virtue ofthe following features:
• No cross insulation forisolating distances betweenphases
• Metal enclosure of switchingdevices (e.g. three-positionswitch) in gas-filled stainless-steel switchgear vessel
• Dry-type bearings inoperating mechanism
• Essential parts of the operat-ing mechanism made ofcorrosion-proof materials
• Use of climate-independentthree-phase current trans-formers
������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 2007 45
Standards, specifications, guidelines, classification
Classification of the SIMOSEC switchgear according to IEC 62 271-200
Internal arc classification (option)
Class– Free-standing arrangement– Wall-standing arrangement
7.2 kV to 24 kVIAC A FLR 20 kA, 1 sIAC A FL 20 kA, 1 s
Degree of accessibility A
– F– L– R
Switchgear in closed electrical service location, access only forproperly instructed personnelFrontLateralRear (for free-standing arrangement)
Test current 20 kA
Test duration 1 s
Construction and design
Partition class PM
Loss of service continuity category 1)
Panels– Without HV HRC fuses, and for panel types
without removable circuit-breakers type 3AH6– With HV HRC fuses, and for panel types
with removable circuit-breakers type 3AH6– In a SIMOSEC switchgear, panel types ME1 or
HF are also part of the busbar. According toIEC 62 271-200 a category is not applicable
LSC 2B
LSC 2A
–
Accessibility to compartments– Busbar compartment– Switching-device compartment– Switching-device compartment with
circuit-breakers type 3AH6 (removable)– Low-voltage compartment– Cable connection compartment
– Without HV HRC fuses– With HV HRC fuses
Tool-basedNot accessibleAccessible and interlock-based
Tool-based
Tool-basedInterlock-based and tool-based
1) The loss of service continuity cate-gory always refers to the completeswitchgear, i.e. the panel with thelowest category determines theloss of service continuity categoryof the complete switchgear.
������
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.21· 200746
Standards, specifications, guidelines, classification
IEC 60 529 and EN 60 529:
Responsible for
Technical contents:Bernd SchüpferlingSiemens AG, Dept. PTD M 2 PPMErlangen
General editing:Gabriele PollokSiemens AG, Dept. PTD CC MErlangen
* Standards see page 43
** For explanationssee adjacent table
Type of protection Degree of protection
I P 2Xss
Protection against solid foreign bodiesProtected against the penetrationof solid foreign bodies, diameter W 12.5 mm
Protection against electric shockProtected against access to dangerous partsby means of a finger (the distance betweena test finger with a diameter of 12 mmto dangerous parts must be sufficient)
Protection against the ingress of waterNo definition
I P 3Xss
Protection against solid foreign bodiesProtected against the penetrationof solid foreign bodies, diameter W 2.5 mm
Protection against electric shockProtected against access to dangerous partsby means of a wire (the distance between a testrod with a diameter of 2.5 mm and a length of100 mm to dangerous parts must be sufficient)
Protection against the ingress of waterNo definition
I P 3 X Dsss
Protection against solid foreign bodiesProtected against the penetrationof solid foreign bodies, diameter W 2.5 mm
Protection against the ingress of waterNo definition
Protection against electric shockProtected against access to dangerous partsby means of a wire (the distance between a testrod with a diameter of 1 mm and a length of100 mm to dangerous parts must be sufficient)
I P 6 5ss
Protection against solid foreign bodiesDust-proof: no penetration of dust
Protection against electric shockProtected against access to dangerous partsby means of a wire (test probe with a diameter of 1 mmmay not penetrate)
Protection against the ingress of waterProtected against water jets,water which is directed towardsthe enclosure from any directionmay not have a damaging effect
Protection against solidforeign bodies, electric shockand ingress of water
SIMOSEC switchgear fulfillsacc. to the standards *
the following degrees ofprotection **:
Degree ofprotection
Type ofprotection
IP 2X(standard)
Enclosure of liveparts underhigh-voltage
Compartments
IP 3X(option)
Enclosure of liveparts under high-voltage inswitchgear withlocking device
IP 3XD(onrequest)
Enclosure of liveparts under high-voltage inswitchgear withlocking device
IP 65 Metal enclosureof gas-filledswitchgear vessels
IEC 60 694 VDE 0670-1000EN 60 694
IEC 62 271-200 VDE 0671-200
IEC 60 529 EN 60 529
If not stated otherwise on theindividual pages of this catalog,we reserve the right to includemodifications, especiallyregarding the stated values,dimensions and weights.
Drawings are not binding.
All product designations usedare trademarks or productnames of Siemens AG or othersuppliers.
If not stated otherwise, alldimensions in this catalog aregiven in mm.
Notes
������
The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.The required features should therefore be specified in each individual case at the time of closing the contract.