Schweitzer Engineering Laboratories, Inc. SEL-351R Falcon Data Sheet
SEL-351R Falcon™ Recloser ControlTake Control of Your Recloser
Major Features and BenefitsThe SEL-351R Falcon Recloser Control provides microprocessor-based features in a slim-profile housing forlong, reliable service on your distribution system.
➤ Modernize existing recloser installations to provide cost saving protection, automation, andcontrol features. Single-person-lift size and standard control cable interconnection simplifiesinstallation. Available in Lift-To-Open and Swing-Open enclosure options.
➤ Use automatic network reconfiguration for improved reliability. Patented MIRRORED BITS® communi-cations speeds protection and improves security.
➤ Customize controls by using enhanced SELOGIC® control equations for improved system operation.Configurable front-panel control labels simplify custom functions.
➤ Improve feeder loading by using built-in, high-accuracy metering functions. Use watt and var measure-ments to optimize feeder operation. Measure three-phase values with either three potential transform-ers or use “phantom” values derived from a single-phase voltage.
➤ Increase efficiency of service restoration with accurate fault location when connected with three-phase voltages.
➤ Reduce engineering costs with ACSELERATOR QuickSet® SEL-5030 Software for relay settings and logic pro-gramming. The built-in HMI provides phasor diagrams that help support commissioning and troubleshooting.
➤ Power with 120 Vac or 230 Vac (or 125 Vdc or 250 Vdc).
SEL-351R Falcon Data Sheet Schweitzer Engineering Laboratories, Inc.
2
Functional Overview
Figure 1 Functional Diagram
Functional Replacement for Traditional Recloser ControlEZ Settings for Basic Recloser FunctionsFor traditional recloser functions, the SEL-351R Falconis easy to set. Only settings such as minimum trip pickup,curve type, and reclose interval are necessary. These set-tings are made at an EZ (easy) access level. SELOGIC
control equations cannot be changed at this access level.
Control logic is preconfigured at the factory. Tocustomize the logic for advanced functions, the SELOGIC
control equations must be reprogrammed.
ReclosingThe SEL-351R Falcon can reclose as many as four (4)times. This allows as many as five (5) operations of anycombination of fast and delay curve overcurrentelements. Each reclose interval can be set for as many as999,999 cycles (more than 4.5 hours), if necessary.
After a reclose interval has timed out, the control waits auser-set time (close power wait time) for the presence ofadequate Vac power before proceeding with the autoreclose. The recloser needs either primary or secondaryvoltage to provide the closing power, depending on how
the recloser is equipped. The Vac power into theSEL-351R Falcon is an indication of the presence of thisprimary or secondary voltage. The close power wait timehas the same 999,999-cycle setting range as the recloseinterval.
The reset times are set separately for reset timing for anauto reclose and reset timing for a manual/remote closefrom lockout. Traditionally, the reset time for amanual/remote close from lockout is set for less than thereset time for an auto-reclose. The reset times have thesame 999,999-cycle setting range.
Front-panel LEDs track the CONTROL STATE forauto-reclosing: RESET, CYCLE, or LOCKOUT (see Figure 14and Table 4).
Sequence coordination logic is enabled to prevent theSEL-351R Falcon from tripping on its fast curves forfaults beyond a downstream recloser.
Customize reclosing logic by using SELOGIC controlequations. Use programmable counters, latches, logicfunctions, and analog compare functions to optimizecontrol actions.
ANSI NUMBERS/ACRONYMS AND FUNCTIONS
25 Synchronism Check*
27 Undervoltage
50N Neutral Overcurrent
50 (P, G, Q) Overcurrent (Phase, Ground, Neg. Seq.)
51N Neutral Time-Overcurrent
51 (P, G, Q) Time-Overcurrent (Phase, Ground, Neg. Seq.)
59 Overvoltage
59 (P, G, Q) Overvoltage (Phase, Ground, Neg. Seq.)
67N Directional Neutral Overcurrent*
67 (P, G, Q) Directional Overcurrent (Phase, Ground, Neg. Seq.)*
79 Autoreclosing
81 (O, U) Over-/Underfrequency
85 RIO SEL MIRRORED BITS® Communications
DFR Event Reports
HMI Operator Interface
LGC SELOGIC® Control Equations
MET High-Accuracy Metering
SER Sequential Events Recorder
ADDITIONAL FUNCTIONS
BRM Breaker Wear Monitor
LDP Load Data Profiling*
LOC Fault Locator*
* Optional Feature
51N50N
27 5979
67N
50PGQ 51
PGQ
Line
Bus
4
EIA-232EIA-485
1
IRIG-B
Residual
S
3
1
27 81OU59P
GQ
25
RECLOSER
*
*
67PGQ
85RIO
DFR HMI LGC LOC
MET SER
BRM
Schweitzer Engineering Laboratories, Inc. SEL-351R Falcon Data Sheet
3
Figure 2 Connect True Three-Phase and Synchronism-Check Voltages to the SEL-351R Falcon
Overcurrent ProtectionFast and Delay Curves Use up to five cumulative fast and delay curve operationsfor phase and ground overcurrent protection. For a nomi-nal recloser CT ratio of 1000:1, these curves can be set assensitive as 50 A and 5 A primary for phase and groundovercurrent protection, respectively.
Any fast or delay curve (phase or ground) can be set withany of the curves in Table 1. The US and IEC curvesconform to IEEE C37.112-1996 IEEE StandardInverse-Time Characteristic Equations for OvercurrentRelays.
The traditional recloser curve choices listed in Table 1use the older electronic control designations. TheSEL-351R Falcon also works with the newermicroprocessor-based control designations. For example,a given traditional recloser curve has the following twodesignations:
Traditional recloser curve A and 101 are the same curve.Use either designation in making curve settings in theSEL-351R Falcon.
Four (4) user-designed curves (created with a softwarepackage) can be downloaded to the SEL-351R Falcon.The fast and delay curves (phase or ground) can be setwith the user-designed curves or the curve choices inTable 1.
Modify fast and delay curves (including US or IEC curvechoices) with the following traditional recloser controlcurve modifiers:
➤ constant time adder—adds time to curve➤ vertical multiplier (time dial)—shifts whole curve
up or down in time➤ minimum response time—holds off curve tripping
for minimum time➤ high-current trip—instantaneous trip with optional
time delay➤ high-current lockout—high-set lockout threshold
Front-panel target LEDs indicate any overcurrent trip ingeneral (TRIP LED) and then discriminate a fast-curvetrip (FAST CURVE LED) or a high-current trip (HIGHCURRENT LED). See Figure 14 and Table 4.
Figure 3 Coordinate Overcurrent Protective Devices
Table 1 Curve Choices in the SEL-351R Falcon
Curve Type Curve Choices
All traditional recloser curves A, B, C, D, E, F, G, H, J, KP, L, M, N, P, R, T, V, W, Y, Z, 1, 2, 3, 4, 5, 6, 7, 8, 8PLUS, 9, KG, 11, 13, 14, 15, 16, 17, 18
US curves moderately inverse, inverse, very inverse, extremely inverse, short-time inverse
IEC curves class A (standard inverse), class B (very inverse), class C (extremely inverse), long-time inverse, short-time inverse
Programmable curves (user designed)
Four (4) programmable curves
Optional 3-Phase Voltage(connect to voltage channels V1, V2, and V3)• Fault Locating• Sensitive, Yet Secure, Fault Detection• Complete Metering
Connect to extravoltage channel VSfor synchronism checkand line voltage check(channel VS connectsto A-phase in this example)
Control Cable• Trip and Close• Breaker Status• IA, IB, IC, IN• 24 Vdc
120 Vac Power
120 VacClose Power (if recloser
is equipped)
LoadSource
C
B
A
RECLOSER
I1Z0 1
I2Z02
I3Z03
INZ04
12 VZ 1 7
RE
T
Z 18
BA
T+
Z 1 9
BA
T-
Z20
BA
T
3A
F01
Z 2 1
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1
Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ 10
FZ 1 1
EZ 1 2
CZ 1 3B
/DZ 14
AZ 1 5
RE
T
Z 16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A 1 1
A10
A09
A14
A 1 3
A 1 2
A23
A16
A15
A 1 7
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BSE
RIA
L P
OR
T 1
1
2
3
4
5
N/C
7
8
SER
IAL
PO
RT
2SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROL
Older electronic control designation: A
Newer microprocessor-based control designation: 101
52
t
I
FastCurves
DelayCurves
Retrofit older existingreclosers with SEL-351R Falcon
Recloser
I1Z 0 1
I2Z02
I3Z03
INZ04
12 VZ 1 7
RE
T
Z 18
BA
T+
Z 1 9
BA
T-
Z20
BA
T
3A
F01
Z 2 1
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1
Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ 10
FZ 1 1
EZ 1 2
CZ 1 3
B/DZ 14
AZ 1 5
RE
T
Z 16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A 1 1
A10
A09
A14
A 1 3
A 1 2
A23
A16
A15
A 1 7
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BSE
RIA
L P
OR
T 1
1
2
3
4
5
N/C
7
8
SER
IAL
PO
RT
2SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROLSEL-351S
SEL-351R Falcon Data Sheet Schweitzer Engineering Laboratories, Inc.
4
The SEL-351R Falcon has two reset characteristicchoices for each time-overcurrent element. One choiceresets the elements if current drops below pickup for atleast one cycle. The other choice (for US or IEC curvesonly) emulates electromechanical induction discelements, where the reset time depends on the time-dialsetting, the percentage of disc travel, and the amount ofcurrent.
Sensitive Earth Fault (SEF) ElementA sensitive earth fault (SEF) element with time delay (aslong as 16,000 cycles) can be set as sensitive as 5 A pri-mary (assuming nominal recloser CT ratio of 1000:1).Current channel IN with a 0.05 A secondary nominal rat-ing provides this sensitivity (see Figure 15).
The front-panel SEF LED indicates any SEF element trip(see Figure 14 and Table 4).
Custom Overcurrent ProtectionCustomize the overcurrent protection by reprogrammingthe corresponding SELOGIC control equations.
Metering and Monitoring
Complete Metering CapabilitiesThe SEL-351R Falcon provides extensive and accuratemetering capabilities. See Specifications on page 17 formetering and power measurement accuracies.
Metered quantities include phase voltages and currents(including demand currents); sequence voltages andcurrents; power (including demand), frequency, andenergy; and maximum/minimum logging of selectedquantities (see Table 2). The recloser control reports allmetered quantities in primary quantities (current inA primary and voltage in kV primary).
Recloser Wear MonitorReclosers suffer mechanical and electrical wear everytime they operate. The recloser wear monitor measuresunfiltered ac current at the time of trip and the number ofclose-to-open operations as a means of monitoring thiswear. Every time the recloser trips, the recloser controlrecords the magnitude of the raw current in each phase.This current information is integrated on a per-phase basis.
When the result of this integration exceeds the thresholdthe recloser wear curve establishes, the SEL-351RFalcon asserts a logic point for the affected phase. Thislogic point can be routed for alarming or to modify
reclosing (e.g., shorten the number of reclosures). Thismethod of monitoring recloser wear is based solidly onmethods of breaker rating from breaker manufacturers.
Figure 4 shows three setpoints necessary to emulate abreaker wear curve. Program the setpoints in Figure 4 tocustomize the recloser wear curve.
The SEL-351R Falcon sets setpoints automaticallyaccording to recommendations for reclosers in ANSIC37.61-1973. Only the recloser type (oil or vacuum) andthe interrupt rating are necessary settings.
Table 2 Meteringa
a If true three-phase voltage is not connected, the voltage (VA,B,C) uses phantom voltages derived from a single-phase voltage to calculate MW/MVAR, MWh/MVARh, and power factor metering values.
Quantities Description
Currents IA,B,C,N, IG Input currents, residual ground current (IG = 3I0, IA + IB + IC).
Voltages VA,B,C, VS Wye-connected voltage inputs, synchronism-check voltage input.
Power MWA,B,C,3P, MVARA,B,C,3P Single- and three-phase megawatts and megavars.
Energy MWhA,B,C,3P, MVARhA,B,C,3P Single- and three-phase megawatt-hours and megavar-hours.
Power Factor PFA,B,C,3P Single- and three-phase power factor; leading or lagging.
Sequence I1, 3I2, 3I0 Positive-, negative-, and zero-sequence currents.
Frequency, FREQ (Hz) Instantaneous power system frequency (monitored on channel VA).
Schweitzer Engineering Laboratories, Inc. SEL-351R Falcon Data Sheet
5
Figure 4 Recloser Contact Wear Curve and Settings
Fault LocatorThe SEL-351R Falcon provides an accurate estimate offault location even during periods of substantial loadflow. The fault locator uses fault type, replica line imped-ance settings, and fault conditions to develop an estimateof fault location without communications channels, spe-
cial instrument transformers, or prefault information.This feature contributes to efficient dispatch of linecrews and fast restoration of service. The fault locatorrequires three-phase voltage inputs.
AutomationFlexible Control Logic and IntegrationThe SEL-351R Falcon has three independently operatedserial ports: two EIA-232 ports and one optionalEIA-485 port on the side. The recloser control does notrequire special communications software. Use anysystem that emulates a standard terminal system.Establish communication by connecting computers,modems, protocol converters, printers, the SEL-3530RTAC, an SEL-2032, SEL-2030 or SEL-2020Communications Processor, SCADA serial port, and/orRTU for local or remote communication.
Apply an SEL-2032 as the hub of a star network, with apoint-to-point fiber or copper connection between thehub and the SEL-351R Falcon, as in Figure 5. TheSEL-2032 supports external communications links,including the public switched telephone network forengineering access to dial-out alerts and private lineconnections of the SCADA system.
Figure 5 Example Communication System
SEL manufactures a variety of standard cables forconnecting this and other IEDs to a variety of externaldevices. Consult your SEL representative for moreinformation on cable availability.
(COSP1, KASP1)
(COSP3, KASP3)
(COSP2, KASP2)
kA Interrupted (kA Axis)
Clos
e-to
-Ope
n (C
/O A
xis)
ASCII Reports Plus Interleaved Binary Data
Dial-Up ASCII Link DNP SCADA Link
I1Z 0 1
I2Z02
I3Z03
INZ04
12 VZ 1 7
RE
T
Z 18
BA
T+
Z 1 9
BA
T-
Z20
BA
T
3A
F01
Z 2 1
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1
Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ 10
FZ 1 1
EZ 1 2
CZ 1 3
B/DZ 14
AZ 1 5
RE
T
Z 16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A 1 1
A10
A09
A14
A 1 3
A 1 2
A23
A16
A15
A 1 7
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BSE
RIA
L P
OR
T 1
1
2
3
4
5
N/C
7
8
SER
IAL
PO
RT
2SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROL
I1Z0 1
I2Z02
I3Z03
INZ04
12 VZ 1 7
RE
T
Z 18
BA
T+
Z 1 9
BA
T-
Z20
BA
T
3A
F01
Z 2 1
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1
Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ 10
FZ 1 1
EZ 1 2
CZ 1 3
B/DZ 14
AZ 1 5
RE
T
Z 16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A 1 1
A10
A09
A14
A 1 3
A 1 2
A23
A16
A15
A 1 7
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BSE
RIA
L P
OR
T 1
1
2
3
4
5
N/C
7
8
SER
IAL
PO
RT
2SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROL
I1Z0 1
I2Z02
I3Z03
INZ04
12 VZ 1 7
RE
T
Z 18
BA
T+
Z 1 9
BA
T-
Z20
BA
T
3A
F01
Z 2 1
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1
Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ 10
FZ 1 1
EZ 1 2
CZ 1 3
B/DZ 14
AZ 1 5
RE
T
Z 16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A 1 1
A10
A09
A14
A 1 3
A 1 2
A23
A16
A15
A 1 7
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BSE
RIA
L P
OR
T 1
1
2
3
4
5
N/C
7
8
SER
IAL
PO
RT
2SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROL
I1Z0 1
I2Z02
I3Z03
INZ04
12 VZ 1 7
RE
T
Z 18
BA
T+
Z 1 9
BA
T-
Z20
BA
T
3A
F01
Z 2 1
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1
Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ 10
FZ 1 1
EZ 1 2
CZ 1 3
B/DZ 14
AZ 1 5
RE
T
Z 16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A 1 1
A10
A09
A14
A 1 3
A 1 2
A23
A16
A15
A 1 7
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BSE
RIA
L P
OR
T 1
1
2
3
4
5
N/C
7
8
SER
IAL
PO
RT
2SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROL
SEL-351R Falcon Data Sheet Schweitzer Engineering Laboratories, Inc.
6
ACSELERATOR QuickSet SEL-5030 and ACSELERATOR QuickSet Designer SEL-5031Use ACSELERATOR QuickSet SEL-5030 to develop set-tings off-line. The system automatically checks interre-lated settings and highlights out-of-range settings.Transfer the settings created off-line to the SEL-351RFalcon using a PC communications link. The softwareconverts event reports to oscillograms with time-coordi-nated element assertion and phasor/sequence elementdiagrams. The ACSELERATOR QuickSet interface sup-ports Microsoft® Windows® operating systems. Viewreal-time phasors via ACSELERATOR QuickSet.
ACSELERATOR QuickSet Designer® SEL-5031 Softwareadditionally allows users to create personalizedApplication Designs. Use Application Designs withinACSELERATOR QuickSet Designer to quickly implementadvanced schemes such as automatic networkreconfiguration. Application Designs hide settings youdo not want changed (e.g., SELOGIC control equations),while making visible the minimum necessary settings(e.g., timer and pickup settings) to implement thescheme. You can alias and manipulate mathematically allsettings for simple end-user interfacing. You can alsodefine custom notes and settings ranges. ApplicationDesigns enhance security by allowing access to only aspecified group of settings. Create Application Designsthat include the most commonly used relay features andsettings for your system (see Figure 6) and watchcommissioning times drop drastically.
Figure 6 Example Application Design
Table 3 Open Communications Protocols
Type Description
Simple ASCII Plain language commands for human- and simple-machine communications. Use for metering, setting, self-test status, event reporting, and other functions.
Compressed ASCII Comma-delimited ASCII data reports. Allows external devices to obtain relay data in an appropriate format for direct import into spreadsheets and database programs. Data are checksum protected.
Extended Fast Meter and Fast Operate
Binary protocol for machine-to-machine communications. Quickly updates SEL communications processors, RTUs, and other substation devices with metering information, relay element, I/O status, time-tags, open and close commands, and summary event reports. Data are checksum protected.
Binary and ASCII protocols operate simultaneously over the same communications lines so control operator metering information is not lost while a technician is transferring an event report.
Distributed Port Switch Protocol
Enables multiple SEL devices to share a common communications bus (two-character address setting range is 01–99). Use this protocol for low-cost, port-switching applications.
DNP3 Level 2 Outstation
Distributed Network Protocol with point remapping. Includes access to metering data, protection elements, contact I/O, targets, SER, relay summary event reports, and setting groups.
Schweitzer Engineering Laboratories, Inc. SEL-351R Falcon Data Sheet
7
Advanced Capabilities for Maximum ControlSelective Load Shedding for Improved System ResponseUse retrofit recloser controls to preserve critical loadswhile balancing system loading. In the example inFigure 7, the same feeder serves both Fire Departmentand Hospital as residential loads. Incorporating underfre-quency elements into the SEL-351R Falcon recloser con-
trol provides you the power to segment the feeder tomaximize load preservation while still responding to sys-tem conditions. You can set the reclosers serving the res-idential loads with as many as six levels of frequency andtime conditions to coordinate with other controls duringa loss of generation.
Figure 7 Implement Underfrequency Load Shedding With SEL-351R Falcon Recloser Controls to Preserve Critical Loads
Figure 8 Improve Service Reliability for Load With Two SEL-351R Falcon Recloser Controls Communicating Over Fiber
Dual Source for Premium ReliabilityEither Recloser 1 or Recloser 2 can serve the load inFigure 8. The respective SEL-351R Falcon detects thestate of source- and load-side voltages. The controlscommunicate via fiber-optic cable to determine whetherthe load should be transferred quickly to the other sourcein the event of an outage. MIRRORED BITS
communications technology and SEL-2815 Fiber-OpticTransceivers accomplish this communication reliablyand economically.
Automatic Network Reconfiguration for Distribution FlexibilitySystems using automatic network reconfiguration, suchas the one in Figure 9, improve service factors byremoving permanently faulted segments withoutinterrupting service from nonfaulted segments. Use theSEL-351R Falcon in a variety of possible systems, eitherwith or without communications between devices. Youcan set analog logic and counters to detect loss of voltage
1
Fire Department and Hospital
Substation
Residential
Residential
I1Z 0 1
I2Z02
I3Z03
INZ04
12 VZ 1 7
RE
T
Z 18
BA
T+
Z 1 9
BA
T-
Z20
BA
T
3A
F01
Z 2 1
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1
Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ 10
FZ 1 1
EZ 1 2
CZ 1 3
B/DZ 14
AZ 1 5
RE
T
Z 16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A 1 1
A10
A09
A14
A 1 3
A 1 2
A23
A16
A15
A 1 7
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BSE
RIA
L P
OR
T 1
1
2
3
4
5
N/C
7
8
SER
IAL
PO
RT
2SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROL
I1Z 0 1
I2Z02
I3Z03
INZ04
12 VZ 1 7
RE
T
Z 18
BA
T+
Z 1 9
BA
T-
Z20
BA
T
3A
F01
Z 2 1
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1
Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ 10
FZ 1 1
EZ 1 2
CZ 1 3
B/DZ 14
AZ 1 5
RE
T
Z 16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A 1 1
A10
A09
A14
A 1 3
A 1 2
A23
A16
A15
A 1 7
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BSE
RIA
L P
OR
T 1
1
2
3
4
5
N/C
7
8
SER
IAL
PO
RT
2SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROL
1 1
I 1
Z0
1I2
Z02I3
Z03IN
Z04
12 V
Z1 7 RET
Z18 BAT+
Z19 BAT-
Z20
BAT 3A
F01
Z2
1
N/C
Z25 GND
Z26
H
Z22
NZ23
Z24
V1
Z05V2
Z06V3
Z07N
Z08VS
Z09NS
Z10
F
Z1 1
E
Z12
C
Z13 B/D
Z14
A
Z15 RET
Z16
196-1215
ENABLED
CONTROL
TRIP
CONTROL STATE
SELECT
CANCEL
LAMP
TEST
EXIT
METER
EVENTS
STATUS
OTHER
SET
CNTRL
GROUP
TARGETRESET
GROUNDRECLOSE
ENABLEDENABLEDENABLED
REMOTE
SETTINGS
ALTERNATELOCK
(press for 3 sec)
AUX 1AUX 2
WAKE UP
CLOSED
RECLOSEROPEN
RECLOSER
TRIP
CLOSE
C
B
A
LOCKOUT
CYCLE
CURVE
FAST
TAG
HOT LINE
PROBLEM
BATTERY
SUPPLY
AC
CURRENT
HIGH
81 G
SEF
RESET
A01
A04A03
A02
A07A06
A05
A08
A1 1
A10
A09
A14
A13
A12
A23
A16
A15
A17
A18
A22
A20A
19
A21
A26A25
A24
A28A27
IRIG
-B
SERIAL P
ORT 1
1
23
45
N/C
78
SERIAL
PORT 2
SERIAL
PORT 3
OUT102
OUT101
OUT104
OUT103
OUT107
N/C
N/C
IN10
1
ALARM
IN10
3
IN10
2
N/C
N/C
IN10
4
+
_
RECLOSER CONTROL
1 3
2
3 1
1Source Source
Fiber-Optic Cable
Load
SEL-2815 TXRX
SEL-351RFalcon
SEL-351RFalcon
SEL-2815TXRX
SEL-351R Falcon Data Sheet Schweitzer Engineering Laboratories, Inc.
8
conditions indicating upstream recloser openings.Change setting groups in intermediate recloser controlsto reverse direction when the tie recloser is closed. Useeither reclose shot counting or time coordination todetermine a faulted segment.
Optional voltage elements provide three-phasemeasurements from one side of the recloser and a single-phase measurement from the other side.
Figure 9 Automatic Network Reconfiguration Showing Improved Service
Added CapabilitiesMIRRORED BITS Relay-to-Relay CommunicationsThe SEL-patented MIRRORED BITS communicationstechnology provides bidirectional relay-to-relay digitalcommunication. MIRRORED BITS can operate inde-pendently on as many as two EIA-232 serial ports on a
single SEL-351R Falcon. With MIRRORED BITS operat-ing on two serial ports, there is communication upstreamand downstream from the SEL-351R Falcon site.
This bidirectional digital communication creates eightadditional virtual outputs (transmitted MIRRORED BITS)and eight additional virtual inputs (received MIRRORED
3 1
Source
Source
Fiber-Optic CableCommunication
Fiber-Optic CableCommunication
Fiber-Optic CableCommunication
Fiber-Optic CableCommunication
1 3
Intermediate Recloser
Intermediate Recloser
Source Recloser
Source Recloser
3 1 1 3
Tie Recloser(Normally
Open)
1
3
I1Z01
I2Z02
I3Z03
INZ04
12 VZ17
RE
T
Z18
BA
T+
Z19
BA
T-
Z20
BA
T
3A
F01
Z21
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ10
FZ11
EZ12
CZ13
B/DZ14
AZ15
RE
T
Z16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A11
A10
A09
A14
A13
A12
A23
A16
A15
A17
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BS
ER
IAL
PO
RT
1
1
2
3
4
5
N/C
7
8
SE
RIA
LP
OR
T 2
SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROL
I1Z01
I2Z02
I3Z03
INZ04
12 VZ17
RE
T
Z18
BA
T+
Z19
BA
T-
Z20
BA
T
3A
F01
Z21
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ10
FZ11
EZ12
CZ13
B/DZ14
AZ15
RE
T
Z16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A11
A10
A09
A14
A13
A12
A23
A16
A15
A17
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BS
ER
IAL
PO
RT
1
1
2
3
4
5
N/C
7
8
SE
RIA
LP
OR
T 2
SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROL
I1Z01
I2Z02
I3Z03
INZ04
12 VZ17
RE
T
Z18
BA
T+
Z19
BA
T-
Z20
BA
T
3A
F01
Z21
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ10
FZ11
EZ12
CZ13
B/DZ14
AZ15
RE
T
Z16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A11
A10
A09
A14
A13
A12
A23
A16
A15
A17
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BS
ER
IAL
PO
RT
1
1
2
3
4
5
N/C
7
8
SE
RIA
LP
OR
T 2
SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROL
I1Z01
I2Z02
I3Z03
INZ04
12 VZ17
RE
T
Z18
BA
T+
Z19
BA
T-
Z20
BA
T
3A
F01
Z21
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ10
FZ11
EZ12
CZ13
B/DZ14
AZ15
RE
T
Z16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A11
A10
A09
A14
A13
A12
A23
A16
A15
A17
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BS
ER
IAL
PO
RT
1
1
2
3
4
5
N/C
7
8
SE
RIA
LP
OR
T 2
SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROL
I1Z01
I2Z02
I3Z03
INZ04
12 VZ17
RE
T
Z18
BA
T+
Z19
BA
T-
Z20
BA
T
3A
F01
Z21
N/CZ25
GN
D
Z26
H
Z22
N
Z23
Z24
V1Z05
V2Z06
V3Z07
NZ08
VSZ09
NSZ10
FZ11
EZ12
CZ13
B/DZ14
AZ15
RE
T
Z16
196-1215
ENABLEDCONTROL
TRIP
CONTROL STATE
SELECTCANCELLAMPTEST EXIT
METER EVENTS STATUS OTHER SET CNTRL GROUPTARGETRESET
GROUND
RECLOSE
ENABLED
ENABLED
ENABLEDREMOTE
SETTINGSALTERNATE
LOCK(press for 3 sec)
AUX 1
AUX 2
WAKE UP
CLOSEDRECLOSER
OPENRECLOSER
TRIP
CLOSE
CBALOCKOUTCYCLE
CURVEFAST
TAGHOT LINE
PROBLEMBATTERY
SUPPLYAC
CURRENTHIGH
81
G SEFRESET
A01
A04
A03
A02
A07
A06
A05
A08
A11
A10
A09
A14
A13
A12
A23
A16
A15
A17
A18
A22
A20
A19
A21
A26
A25
A24
A28
A27
IRIG
-BS
ER
IAL
PO
RT
1
1
2
3
4
5
N/C
7
8
SE
RIA
LP
OR
T 2
SE
RIA
LP
OR
T 3
OU
T10
2O
UT
101
OU
T10
4O
UT
103
OU
T10
7N
/CN
/CIN
101
AL
AR
MIN
103
IN10
2N
/CN
/CIN
104
+
_
RECLOSER CONTROL
Schweitzer Engineering Laboratories, Inc. SEL-351R Falcon Data Sheet
9
BITS) for each serial port operating in the MIRRORED
BITS mode (see Figure 10). Use these MIRRORED BITS totransmit/receive information between an upstream relayand a downstream recloser control to enhancecoordination and achieve faster tripping for downstreamfaults. MIRRORED BITS technology also helps reducetotal scheme operating time by eliminating the need toassert output contacts to transmit information.
Figure 10 MIRRORED BITS Transmit and Receive Bits
Advanced SELOGIC Control EquationsAdvanced SELOGIC control equations allow you toassign relay outputs to any logical combination of RelayWord elements or inputs.
Program SELOGIC control equations by combining relayelements, inputs, and outputs with SELOGIC controlequation operators. Bits in a table called the “RelayWord” reflect the state of all logical elements in therecloser control. These logical elements include all
current (50/51) and directional-level detecting elements,timer elements, SELOGIC control equation variables,inputs, outputs, and remote, local, and latched bits.
SELOGIC control equation operators include OR, AND,invert, parentheses, and rising and falling edges ofelement state changes. Analog compare functions (<, >,=, < >) are also available. These functions add controlflexibility to customize logic based on recloser shotcount or other control values.
The basic building blocks of SELOGIC control equationsare the Relay Word bits. The Relay Word bits are simpledigital quantities having a logical value of either 0 or 1.The terms “assert” or “asserted” refer to a Relay Wordbit that has a value of 1 or is changing from 0 to 1. Theterms “deassert” or “deasserted” refer to a Relay Wordbit that has a value of 0 or is changing from 1 to 0.Various elements within the recloser control assert ordeassert Relay Word bits. Use these elements in the fixedinternal logic of the recloser control to make decisions,to interpret inputs, or to drive outputs. These bits areavailable so that you can exercise flexibility in defininginputs or outputs, in specifying control variables forinternal logic, or in creating special customized logicthrough the use of SELOGIC control equations.
In addition to Boolean logic, 16 general purposeSELOGIC control equation timers eliminate externaltimers for custom protection or control schemes. Eachtimer has independent time-delay pickup and dropoutsettings. Program each timer input with any element(e.g., time qualify a voltage element) you specify. Assignthe timer output to trip logic, transfer tripcommunications, or other control scheme logic.
The SEL-351R Falcon has the same SELOGIC controlequations capability as the established SEL-351R-2.
Hardware OverviewThe convenient side-panel construction of the SEL-351RFalcon provides easy access to all controls and connec-tions.
Communications ports, contacts, and control cableconnection points are all readily available. Labeling isshown in Figure 14 (right-hand side).
Figure 11 SEL-351R Falcon Module Side Panel
SEL-351S Relay
Transmit
Receive
Transmit
Receive..
.
.
SEL-351R Falcon Recloser Control
0
0
0
1
0
0
.
.
.
.
1
0
0
0
0
0
TMB1
TMB2
TMB8
RMB1
RMB2
RMB8 RMB8
TMB1
TMB2
TMB8
.
.
.
.
.
.
RMB1
RMB2
.
.
i4422b
SEL-351R Falcon Data Sheet Schweitzer Engineering Laboratories, Inc.
10
Figure 12 SEL-351R Falcon Lift-To-Open Enclosure With Door Open (wiring not shown)
Recloser Control ConnectionsAvailable in Lift-To-Open (Figure 16) and Swing-Open(Figure 17) enclosure options.
The control cable from the recloser attaches at thebottom of the SEL-351R Falcon enclosure to a standardreceptacle. The wiring from this receptacle continuesinto the control itself, with the currents and controllanding on the side-panel terminals.
The 120 or 230 Vac power parallels voltage channel V1,as shown in the retrofit of a traditional installation inFigure 13. If you order the SEL-351R Falcon withadditional voltage channels V2, V3, and VS, connect truethree-phase voltage and synchronism-check voltage tothe side-panel terminals.
An internal battery monitor/charger provides batterycharging/discharging. Through this batterymonitor/charger the SEL-351R Falcon can monitorbattery voltage. The SEL-351R Falcon puts itself to sleepif voltage falls to a user-set threshold (or if a user-settimer times out) after an extended outage.
The SEL-351R Falcon can also be powered with125 Vdc or 250 Vdc.
Figure 13 Connections Inside the SEL-351R Falcon Enclosure
Control CableReceptacle
Batteries
NEMA Type 3R(IP32) Enclosure
RelayModule
Terminals
Mount SEL-2401 and/or SEL-3022
Mount user-supplied accessory panel
SEL-2401 orSEL-3622 orSEL-2925
SEL-351R Falcon Recloser Control (not including front panel)
As many as 7 Output
Contacts/1 Alarm
I1, I2, I3, IN
Recloser Status
Trip and Close
SCADAorOtherControl
ControlCable
120 Vac or230 Vac Power
24 VdcLead-AcidBattery
EIA-232
EIA-232
EIA-485
As many as6 Optoisolated
Inputs
V2
V3
VS (synchronism check)
V1 (also monitors frequency)
12 Vdc powerto SEL-2401 or
SEL-3622 (if installed)
Power In
12 Vdc Out
OrderingOption
OrderingOption
Close Power(if recloser
is equipped)
36 VdcPower Supply
12 VdcPower Supply
Battery Monitor/Charger
ControlPower Supply
24 or 36 Vdc Out
+ —
Schweitzer Engineering Laboratories, Inc. SEL-351R Falcon Data Sheet
11
Front-Panel InterfaceThe control panel on the SEL-351R Falcon is designed toprovide easy-to-use and flexible operation by field per-sonnel. Figure 14 shows default functions. You canchange most functions by programming to meet system
requirements (see Table 4). Use the optional configurablelabels to customize the targets and control pushbuttons tobest meet operational needs.
r See noted safety features for CLOSE and TRIP operator controls in Table 4.
Figure 14 SEL-351R Falcon Recloser Control Front-Panel Interface
Display2 x 16 liquid
crystal display (LCD)
Pushbuttons
Status and TripTarget LEDs
Operator Controls
i4301b
r
e
w
q
SEL-351R Falcon Data Sheet Schweitzer Engineering Laboratories, Inc.
12
Table 4 Factory Default Front-Panel Interface Definitions (see Figure 14)
Function Definition
➀ PUSHBUTTONS Except for TARGET RESET/LAMP TEST, the pushbuttons have dual functions (primary/secondary).
After you select a primary function (i.e., METER pushbutton), the pushbuttons operate on their secondary functions (CANCEL, SELECT, left/right arrows, up/down arrows, EXIT) so you can scroll through information, activate settings/control, etc., on the LCD.
➁ CONTROL ENABLEDa
a These indicated LEDs and the operator control have fixed functions. Programming at a higher logic level can change functions of all other LEDs and operator controls (with corresponding status LEDs).
SEL-351R Falcon Recloser Control is enabled.
AC SUPPLY Adequate Vac power is present.
BATTERY PROBLEM Indicates battery problems.
HOT LINE TAG No closing or autoreclosing can take place via the control.
TRIP Trip occurred.
FAST CURVE Fast curve overcurrent element trip.
HIGH CURRENT High-set overcurrent element trip.
81 Underfrequency trip.
RESET The control is in the reset state, ready for a reclose cycle.
CYCLE The control is actively in the trip/reclose cycle mode.
LOCKOUT All reclose attempts were unsuccessful.
A, B, C a A-, B-, or C-phase involved in fault.
G Ground involved in fault.
SEF Sensitive earth fault overcurrent element trip.
➂ GROUND ENABLED Enables/disables ground overcurrent elements.
RECLOSE ENABLED Enables/disables autoreclosing.
REMOTE ENABLED Enables/disables remote control.
ALTERNATE SETTINGS Switches active setting group between main and alternate setting groups.
LOCK (press for 3 seconds) Blocks the function of other operator controls (except WAKE UP and TRIP). Three-second delay to engage/disengage.
AUX 1 User programmable; e.g., program to Trip Test—test autoreclose logic without applying current.
AUX 2 User programmable; e.g., program to enable/disable fast-curve tripping.
WAKE UP a Wakes up the control after it has been put to sleep.
CLOSE/RECLOSER CLOSED Close recloser/recloser closed status.b
b You can set the CLOSE operator control with a delay, which allows an operator to press CLOSE and then move a safe distance away from the recloser before closing proceeds.
TRIP/RECLOSER OPEN Trip recloser (go to lockout)/recloser open status.c
c You can set the TRIP operator control with a delay, which allows an operator to press TRIP and then move a safe distance away from the recloser before tripping proceeds.
Schweitzer Engineering Laboratories, Inc. SEL-351R Falcon Data Sheet
13
Guideform SpecificationThe microprocessor-based recloser control shall provide acombination of functions including protection, monitoring,control, fault locating, and automation. Recloser controlself-checking functions shall be included. Specific opera-tional and functional requirements are as follows.
➤ Autoreclosing Control. The recloser control shallincorporate a four-shot control. It shall includefour independently set open time intervals, an inde-pendently set reset time from reclose cycle, and anindependently set reset time from lockout.
➤ Coordination With Downstream Reclosers. Therecloser control shall include 38 standard reclosertime-overcurrent curves and sequence coordinationlogic for secure and dependable operation.
➤ Phase Fault Overcurrent Protection. The reclosercontrol shall incorporate phase and negative-sequenceovercurrent elements for detection of phase faults. Foradded security, the recloser control shall provide direc-tional elements, load- encroachment logic, andtorque-control capability (internal and external).
➤ Ground Fault Overcurrent Protection. Therecloser control shall incorporate residual groundovercurrent elements for detection of groundfaults. For added security, the recloser control shallprovide directional elements and torque-controlcapability (internal and external).
➤ Phase Under- and Overvoltage Elements. Therecloser control shall incorporate undervoltage andovervoltage elements for creating protection andcontrol schemes, including but not limited to volt-age checks (e.g., hot bus/dead line) for reclosing;blown transformer high-side fuse-detection logic;and control schemes for capacitor banks.
➤ Sequence Voltage Elements. The recloser controlshall incorporate positive-, negative-, and zero-sequencevoltage elements that can be logically configured foreither under- or overvoltage applications.
➤ Under- and Overfrequency Protection. Therecloser control shall incorporate six levels ofunder- and overfrequency elements for detection ofpower system frequency disturbances. Each settinglevel shall use an independently set timer for load-shedding or generator-tripping schemes.
➤ Synchronism Check. The recloser control shallinclude two synchronism-check elements with separatemaximum angle settings (e.g., one for autoreclosingand one for manual closing). The synchronism-checkfunction shall compensate for close time and constantphase-angle differences between the two voltagesources used for synchronism check (phase-angle dif-ferences are settable in 30-degree increments).
➤ IED Communications. The recloser control shallinclude the capability for communication of inter-nal logic values to a remote relay or recloser con-trol via serial communications. These values shallbe available for use in control logic.
➤ Secure Communications. The recloser control shallinclude an optional accessory for converting anEIA-232 serial port to encrypted and authenticated
IEEE 802.11b wireless communication. Software shallbe provided with this accessory to allow a personalcomputer (PC) or personal data assistant (PDA) accessto the wireless port.
➤ Operator Controls. The recloser control shallinclude 10 operator controls on the recloser controlfront panel; these functions shall also be accessiblein the recloser control logic. Nine of the operatorcontrols shall include pushbuttons and LEDs withprogrammable functions and indications.
➤ Event Reporting and Sequential EventsRecorder (SER). The recloser control shall be capa-ble of automatically recording disturbance events of15 or 30 cycles with settable prefault duration anduser-defined triggering. Events shall be stored in non-volatile memory. The recloser control shall include anSER that stores the latest 512 entries.
➤ Status and Trip Target LEDs. The recloser con-trol shall include 16 status and trip target LEDs.
➤ Recloser Wear Monitor. The recloser controlshall include a recloser wear monitor withuser-definable wear curves, operation counter, andaccumulated interrupted currents by phase.
➤ Battery Monitor. The recloser control shall measureand report the battery voltage level. User-selectableparameters shall be provided to put the control to sleepfor low battery voltage or for a lengthy outage.
➤ Fault Locator. The recloser control shall include afault-locating algorithm to provide an accurate estimateof fault location without communications channels, spe-cial instrument transformers, or prefault information.
➤ Automation. The recloser control shall include16 local control elements, 16 remote control logicpoints, 16 latching logic points, and 16 display mes-sages in conjunction with a local display panel. Therecloser control shall have the capability to display cus-tom messages.
➤ Recloser Control Logic. The recloser control shallinclude programmable-logic functions for a wide rangeof user-configurable protection, monitoring, and controlschemes.
➤ Communication. The recloser control shallinclude two independent EIA-232 serial ports andone optional EIA-485 serial port for external com-munication. There shall be an option for DNP3Level 2 protocol with bitmapping.
➤ IRIG-B. The recloser control shall include an interfaceport for a demodulated IRIG-B time synchronizationinput signal.
➤ PC Software. The recloser control shall include com-patibility with a PC software program for use in pro-gramming control settings and logic functions, andretrieving event data. The PC software shall be included,but it is not necessary to use the recloser control.
➤ Power Supply. The recloser control shall accept120 Vac or 230 Vac (or 125 Vdc or 250 Vdc).
➤ Warranty. The relay shall have a minimum10-year worldwide warranty.
SEL-351R Falcon Data Sheet Schweitzer Engineering Laboratories, Inc.
14
Wiring Diagram
Figure 15 SEL-351R Falcon Module Inputs, Outputs, and Communications Ports
PORT 3 (SIDE)
PORT 2 (SIDE)
PORT 1 (SIDE)
ISOLATED EIA-485
+
—
+
—
Battery Monitor/Charger
12 Vdc Power Supply
I1Z01
N/C
Z02Z03Z04
Z06Z05
Z07
Z09Z08
Z10
Z11Z12Z13Z14Z15Z16Z17Z18Z19Z20Z21Z22Z23Z24Z25Z26
I2I3
IN
V1V2V3
N
NS
Chassis Ground
Note 1: Power with 120 Vac or 230 Vac (or 125 Vdc or 250 Vdc)
EIA-232
DB9
EIA-232 &IRIG-B
DB9
VS
+
—
Control Power Supply
+
—36 Vdc
Power SupplySee Note 1
Return
36 Vdc
HV FET Close
HV FET Trip
Monitored CloseCircuit Points
Monitored TripCircuit PointsB/D
C
A
EF
IRIG-B+ —
1 2 3 4 5 N/C 7 8
FRON
T-PA
NEL
OPER
ATOR
CON
TROL
S
28 Vdc24 Vdc
24 Vdc or 36 Vdc
12 Vdc
FRONT-PANEL TARGET LEDSAC
SUPPLYCONTROLENABLED
BATTERYPROBLEM
HOT LINETAG
TRIPFAST
CURVEHIGH
CURRENT81
CYCLERESET LOCKOUT A B C G SEF
CONTROL STATE FAULT TYPE
ORDERING OPTION
CURR
ENT
INPU
TSVO
LTAG
E IN
PUTS
ORDE
RING
OPT
ION * OUT107 CAN OPERATE AS EXTRA ALARM
JUMP
ER C
ONFI
GURA
BLE
OUT101 A01
PRO
GRAM
MABL
EOP
TOIS
OLAT
ED IN
PUTS
(IN10
2—IN
106
Part
of o
rder
ing
optio
ns)
OUT1
01—O
UT10
6 Pa
rt o
f ord
erin
g op
tions
)
A17IN101
IN102
IN103
IN104
IN105
IN106
A18
A19A20
A21A22
A23
A24
A25
A26A27
A28
OUT102
OUT103
OUT104
OUT105
OUT106
OUT107*
ALARM
A02
A03A04
A05
A06A07
A08
A09A10A11
A12
A13A14
A15
A16
PROG
RAMM
ABLE
OUT
PUT
CONT
ACTS
Schweitzer Engineering Laboratories, Inc. SEL-351R Falcon Data Sheet
15
Relay Mounting
Figure 16 SEL-351R Falcon Lift-To-Open Enclosure Dimensions and Mounting
SEL-351R Falcon Data Sheet Schweitzer Engineering Laboratories, Inc.
16
Figure 17 SEL-351R Falcon Swing-Open Enclosure Dimensions and Mounting
Schweitzer Engineering Laboratories, Inc. SEL-351R Falcon Data Sheet
17
Specifications
ComplianceISO 9001:2008 Certified
General
AC Current Inputs (Channels I1, I2, I3)
1 A nominal: 3 A continuous, linear to 20 A symmetrical; 100 A for 1 s
Burden: 0.13 VA @ 1 A1.31 VA @ 3 A
Sensitive Earth Fault (SEF) Channel IN Current Input
0.05 A nominal: 1.5 A continuous, linear to 1.5 A symmetrical; 20 A for 1 s
Burden: 0.0004 VA @ 0.05 A, 0.36 VA @ 1.5 A
AC Voltage Inputs
300 VL-N continuous, (connect any voltage up to 300 Vac). 600 Vac for 10 s.
Burden: 0.03 VA @ 67 V0.06 VA @ 120 V0.80 VA @ 300 V
Power Supply
Rated Range: 85–264 Vac; 100–350 Vdc
Frequency Range: 40.1–65 Hz
Burden: <30 VA
12 V Radio Supply
11–14 Vdc, 6 W continuous, 13 W for 1 s
Output Contacts (Except Trip and Close)
Make: 30 A per IEEE C37.90-1989
Carry: 6 A continuous carry at 70°C4 A continuous carry at 85°C
1 s Rating: 100 A
MOV Protection: 270 Vac / 360 Vdc; 40 J
Pickup Time: < 5 ms
Breaking Capacity (10000 operations, L/R = 40 ms):
24 V 0.75 A48 V 0.50 A
125 V 0.30 A250 V 0.20 A
Cyclic Capacity (2.5 cycle/second, L/R = 40 ms):
24 V 0.75 A48 V 0.50 A
125 V 0.30 A250 V 0.20 A
Note: Per IEC 60255-0-20:1974, using the simplified method of assessment.
Trip and Close Outputs
3 A continuous @ –40° to 40° C, 1 min @ 85°C
Make and Carry: 5 A for 0.2 s @ 1 s intervals
Optoisolated Inputs
DC Range
24 Vdc: Pickup 15.0–30 Vdc
AC Range
24 Vdc: Pickup 12.8–30 Vdc
Note: Optoisolated inputs draw approximately 4 mA of current. All current ratings are at nominal input voltages.
Frequency and Rotation
System Frequency: 50 or 60 Hz
Phase Rotation: ABC or ACB
Frequency Tracking Range: 40.1–65 Hz
Note: Voltage connected to V1 required for frequency tracking.
Communications Ports
EIA-232: 2 Side
EIA-485 (optional): 1 Side, 2100 Vdc of isolation
Baud Rate: 300–38400 baud
Time-Code Input
Recloser control accepts demodulated IRIG-B time-code input at Port 1 (optional) and Port 2. Do not connect the time-code input into both Port 1 and Port 2 at the same time. Recloser control time is synchronized to within ±5 ms of time-source input.
Operating Temperature
Relay Module: –40° to +85°C (–40° to +185°F)
Batteries: –40° to +60°C (–40° to +140°F)
Entire SEL-351R Falcon Unit: –40° to +50°C (–40° to +122°F)
Note: LCD contrast impaired for temperatures below – 20°C (–4° F). The entire SEL-351R Falcon unit was operation tested up to +70°C (+158°F). The 20°C (36°F) difference between the +50°C rating and +70°C allows for temperature rise due to sunlight.
Weight
16.7 kg (37 lbs) including batteries
Battery Specifications
Normal Capacity: 8.0 amp-hours at +25°C (+77°F)
Run Time: 20 hours at +25°C (+77°F)8 hours at –40°C (–40°F)
Estimated Life: 4 years at +25°C (+77°F)8 months at +60°C (+140°F)
Recharge Time: 55 hours at +25°C (+77°F)
Type Tests
Environmental Test
Cold: IEC 60068-2-1:1990[EN 60068-2-1:1993]Test Ad: 16 hours at –40°C
Damp Heat Cyclic: IEC 60068-2-30:1980Test Db; 55° C, 12 + 12-hour cycles, 95% humidity
Dry Heat: IEC 60068-2-2:1974[EN 60068-2-2:1993]Test Bd: Dry heat, 16 hours at +85°C
Dielectric Strength and Impulse Tests
Dielectric: IEC 60255-5:1977IEEE C37.90-19892500 Vac on analogs, contact inputs,
and contact outputs except Trip and Close; 3100 Vdc on power supply for 10 s; 2200 Vdc on EIA-485 communications port
SEL-351R Falcon Data Sheet Schweitzer Engineering Laboratories, Inc.
18
Electrostatic Discharge Test
ESD: IEC 60255-22-2:1996(8 kV contact discharge all points except serial ports, 15 kV air discharge to all other points)
RFI and Interference Tests
1 MHz Burst Disturbance: IEC 60255-22-1:1988 Level 3 (2500 V common, 1000 V differential)
Fast Transient Disturbance:
IEC 60255-22-4:1992IEC 60801-4:1998 Level 4(4000 V optional, 2000 V inputs)
Radiated EMI: IEC 60255-22-3:1989 Level 3, 10 V/mIEEE C37.90.2-1995, 35 V/m
Exception: 5.5.2(2): Performed with 200 frequency steps per octave.5.5.3: Digital Equipment Modulation Test not performed.5.5.4: Test signal off between frequency steps to simulate keying.
Surge Withstand: IEEE C37.90.1-19893.0 kV oscillatory; 5.0 kV fast transient
Vibration and Shock Tests
Sinusoidal Vibration: IEC 60255-21-1:1988 Class 1
Shock and Bump: IEC 60255-21-2:1988 Class 1
Seismic: IEC 60255-21-3:1993 Class 2
Miscellaneous
Enclosure Protection: IEC 60529:1989, IP32/NEMA 3R
Recloser Type TestsIEEE Std C37.60-2003 Clause 6.13.1, Oscillatory and fast transient
surge tests, performed in accordance with IEEE Std C37.90.1-2002 Surge Withstand Capability (SWC) for Relays and Relay Systems Associated with Electric Power Apparatus.
IEEE Std C37.60-2003 Clause 6.13.2, Simulated surge arrester operation test, performed with the following recloser.
G&W Electric Viper-S, Solid Dielectric
Model:Voltage Rating:Current Break Rating:Continuous Current
Rating:
VIP398ER-12S38 kV12.5 kA
800 A
Processing Specifications
AC Voltage and Current Inputs
16 samples per power system cycle, 3 dB low-pass filter cut-off frequency of 560 Hz.
Digital Filtering
One cycle cosine after low-pass analog filtering.Net filtering (analog plus digital) rejects dc and all harmonics greater
than the fundamental.
Protection and Control Processing
Four times per power system cycle.
Battery Monitor
Processing once per second.
Relay Elements
Instantaneous/Definite-Time Overcurrent Elements (50)
Current Pickup Range (A secondary)
1 A Nominal Channel: 0.05–20.00 A, 0.01 A steps0.20–34.00 A, 0.01 A steps for
phase-to-phase elements
SEF (0.05 A IN) Channel: 0.005–1.500 A, 0.001 A steps
Steady-State Pickup Accuracy
1 A Nominal Channel: ±0.01 A, ±3%
SEF (0.05 A IN) Channel: ±0.001 A, ±5%
Transient Overreach: ±5% of pickup
Time Delay: 0.00–16,000.00 cycles, 0.25–cycle steps
Timer Accuracy: ±0.25 cycle, ±0.1%
Time-Overcurrent Elements (51)
Current Pickup Range (A secondary)
1 A Nominal Channel: 0.05–3.2 A, 0.01 A steps
SEF (0.05 A IN) Channel: 0.005–0.160 A, 0.001 A steps
Steady-State Pickup Accuracy
1 A Nominal Channel: ±0.01 A, ±3%
SEF (0.05 A IN) Channel: ±0.001 A, ±5%
Transient Overreach: ±5% of pickup
Time Dials
US: ±0.5–15.0, 0.01 steps
IEC: 0.05–1.00, 0.01 steps
Recloser Curves: 0.10–2.00, 0.01 steps
Curve Timing Accuracy
1 A Nominal Channel: ±1.50 cycles, ±4% between 2 and 30 multiples of pickup
SEF (0.05 A IN) Channel: ±1.50 cycles, ±4%
between 2 and 30 multiples of pickup
Under- (27)/Overvoltage (59) Elements
Pickup Ranges (V secondary)
Various Elements: 0.00–300.00 V, 0.01 V steps
Phase-to-Phase Elements: 0.00–520.00 V, 0.01 V steps
Steady-State Pickup Accuracy: ±2 V, ±5%
Transient Overreach: ±5%
Synchronism-Check Elements (25)
Slip Frequency Pickup Range: 0.005–0.500 Hz, 0.001 Hz steps
Slip Frequency Pickup Accuracy: ±0.003 Hz
Phase Angle Range: 0–80°, 1° steps
Transient Accuracy: ±4°
Under-/Overfrequency Elements (81)
Frequency: 40.1–65.00 Hz, 0.01 Hz steps
Time Delays: 2.00–16,000.00 cycles, 0.25-cycle steps
Timer Accuracy: ±0.25 cycle, ±0.1%
Steady-State plus Transient Overshoot: ±0.01 Hz
Undervoltage Frequency Element Block Range: 25.00–300.00 V
Schweitzer Engineering Laboratories, Inc. SEL-351R Falcon Data Sheet
19
SELOGIC Control Equation Variable Timers
Pickup Ranges
0.00–999,999.00 cycles: 0.25-cycle steps (reclosing relay and some programmable timers)
0.00–16,000.00 cycles: 0.25-cycle steps (some programmable and other timers)
Pickup/Dropout Accuracy: ±0.25 cycle, ±0.1%
Metering Accuracy
Accuracies are specified at 20°C and at nominal system frequency unless noted otherwise.
Voltages VA, VB, VC, VS, 3V0, V1, V2: ±0.2%, (67–300.0 V; wye connected)
Currents IA, IB, IC: 1 A nominal ±3 mA, ±0.1% (0.1–20 A)
Temperature Coefficient: [(0.0002%)/(°C)2] • (__°C–20°C)2
(see example below)
Phase Angle Accuracy: ±1.0°
Currents I1, 3I0, 3I2: 1 A nominal ±0.01 A, ±3% (0.1–20.0 A)
IN (SEF): 0.05 A IN nominal ±1 mA±5% (0.01–1.5 A)
Example metering accuracy calculation for currents IA, IB, and IC due to preceding stated temperature coefficient:
For temperature of 40°C, the additional error for currents IA, IB, and IC is: [(0.0002%)/(°C)2] • (40°C–20°C)2 = 0.08%
20
© 2009–2015 by Schweitzer Engineering Laboratories, Inc. All rights reserved.
All brand or product names appearing in this document are the trademark or registeredtrademark of their respective holders. No SEL trademarks may be used without writtenpermission. SEL products appearing in this document may be covered by U.S. and Foreignpatents.
Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits afforded underfederal and international copyright and patent laws in its products, including without lim-itation software, firmware, and documentation.
The information in this document is provided for informational use only and is subject tochange without notice. Schweitzer Engineering Laboratories, Inc. has approved only theEnglish language document.
This product is covered by the standard SEL 10-year warranty. For warranty details, visitwww.selinc.com or contact your customer service representative.
*PDS351R-02*
SCHWEITZER ENGINEERING LABORATORIES2350 NE Hopkins Court • Pullman, WA 99163-5603 USAPhone: +1.509.332.1890 • Fax: +1.509.332.7990Internet: www.selinc.com • E-mail: info@selinc.com
SEL-351R Falcon Data Sheet Date Code 20150126
Notes