Post on 14-Dec-2018
CIVIL
PRINTED ON RECYCLED PAPER
ARCHITECT + ENGINEER PUBLIC SCHOOLS OF PETOSKEY
GMB ARCHITECTURE + ENGINEERING
85 EAST EIGHTH STREET, SUITE 200, HOLLAND, MI 49423
P. 616.796.0200 F. 616.796.0201 www.gmb.com
VICINITY MAP
PETOSKEY HIGH SCHOOL
CAMPUS IMPROVEMENTS
PUBLIC SCHOOLS OF PETOSKEY
1500 HILL STREET
PETOSKEY, MI 49770
NEW STADIUM AND CAMPUS IMPROVEMENTS
BIDS & CONSTRUCTION
02.09.2015
PROJECT 5-3211
1130 HOWARD STREET
PETOSKEY, MI 49770
PH: 231.348.2100
C0.00 OVERALL EXISTING SITE SURVEY
C0.01 NORTH DEMOLITION PLAN
C0.02 HIGH SCHOOL PARKING DEMOLITION PLAN
C0.03 STADIUM DEMOLITION PLAN
C0.04 SOUTH PARKING LOT AND WEST NORTHMEN DEMOLITION PLANS
C0.05 MIDDLE SCHOOL PARKING LOT AND ATHLETIC FIELD DEMOLITION PLANS
C0.06 NORTH PARKING LOT DEMOLITION PLAN
C0.07 MCDOUGAL EXTENSION DEMOLITION PLANS
C0.08 NORTH NORTHMEN DRIVE DEMOLITION PLAN
C1.00 OVERALL SITE PLAN
C1.01 NORTH SITE PLAN
C1.02 HIGH SCHOOL PARKING SITE PLAN
C1.03 STADIUM SITE PLAN
C1.04 SOUTH PARKING LOT AND WEST NORTHMEN SITE PLAN
C1.05 MIDDLE SCHOOL PARKING LOT AND ATHLETIC FIELDS PLANS
C1.06 NORTH PARKING LOT PLAN
C1.07 MCDOUGAL EXTENSION SITE PLAN
C1.08 NORTH NORTHMEN DRIVE SITE PLAN
C1.09 STADIUM PLAZA ENLARGEMENT PLAN
C2.01 NORTHMEN DRIVE PROFILE STA. 0+00 TO 10+00
C2.02 NORTHMEN DRIVE PROFILE STA. 10+00 TO 20+00
C2-03 NORTHMEN DRIVE PROFILE STA. 20+00 TO 30+00
C2.04 NORTHMEN DRIVE PROFILE STA. 30+00 TO 40+00
C2.05 NORTHMEN DRIVE PROFILE STA. 40+00 TO 43+00
C2.06 McDOUGAL EXTENSION PROFILE STA. 0+00 TO 10+00
C2.07 McDOUGAL EXTENSION PROFILE STA. 10+00 TO 14+50
C3.00 OVERALL GRADING PLAN
C3.01 NORTH GRADING PLAN
C3.02 HIGH SCHOOL PARKING GRADING PLAN
C3.03 STADIUM GRADING PLAN
C3.04 SOUTH PARKING LOT AND WEST NORTHMEN GRADING PLAN
C3.05 MIDDLE SCHOOL PARKING LOT AND ATHLETIC FIELDS GRADING PLANS
C3.06 NORTH PARKING LOT GRADING PLAN
C3.07 MCDOUGAL EXTENSION GRADING PLAN
C3.08 NORTH NORTHMEN DRIVE GRADING PLAN
C4.00 OVERALL UTILITY PLAN
C4.01 NORTH UTILITY PLAN
C4.02 HIGH SCHOOL PARKING UTILITY PLAN
C4.03 STADIUM UTILITY PLAN
C4.04 SOUTH PARKING LOT AND WEST NORTHMEN UTILITY PLAN
C4.05 MIDDLE SCHOOL PARKING LOT AND ATHLETIC FIELDS UTILITY PLAN
C4.06 NORTH PARKING LOT UTILITY PLAN
C4.07 MCDOUGAL EXTENSION UTILITY PLAN
C4.08 NORTH NORTHMEN DRIVE UTILITY PLAN
C5.01 ENLARGED TURF PLAN AND DETAILS
C5.02 TURF DRAINAGE PLAN AND DETAILS
C5.03 TURF FIELD LAYOUT PLANS AND DETAILS
C5.04 TRACK AND FIELD DETAILS
C6.00 OVERALL LANDSCAPE PLAN
C6.01 NORTH LANDSCAPE PLAN
C6.02 HIGH SCHOOL PARKING LANDSCAPE PLAN
C6.03 STADIUM LANDSCAPE PLAN
C6.04 SOUTH PARKING LOT AND WEST NORTHMEN LANDSCAPE PLAN
C6.05 MIDDLE SCHOOL PARKING LOT AND ATHLETIC FIELDS LANDSCAPE PLAN
C6.06 NORTH PARKING LOT LANDSCAPE PLAN
C6.07 MCDOUGAL EXTENSION LANDSCAPE PLAN
C6.08 NORTH NORTHMEN DRIVE LANDSCAPE PLAN
C7.03 STADIUM IRRIGATION PLAN
C7.04 SOUTH PARKING LOT IRRIGATION PLAN
C7.05 IRRIGATION PLAN ENLARGEMENTS
C7.06 IRRIGATION DETAILS
C8.01 SITE DETAILS
C8.02 SITE DETAILS
C8.03 SITE DETAILS
C8.04 SITE DETAILS
C8.05 SITE DETAILS
C9.01 TRAFFIC CONTROL PLAN
SITE ELECTRICAL
DESIGN ARCHITECT
BECKETT RAEDER
616 PETOSKEY STREET, PETOSKEY, MI 49770
P. 231.347.2523 F. 231.347.2524 www.bria2.com
LOCKER ROOMS
STRUCTURAL
S1.10 LOCKER ROOM STRUCTURAL PLANS & DETAILS
S1.20 STRUCTURAL DETAILS
ARCHITECTURAL
A1.10 LOCKER ROOM PLANS, DETAILS & ENLARGED PLANS
A1.20 LOCKER ROOM EXTERIOR ELEVATIONS, BUILDING
SECTIONS, ROOF PLAN & DOOR SCHEDULE
A1.30 LOCKER ROOM WALL SECTIONS & DETAILS
A1.90 LOCKER ROOM ADDITION FINISH PLAN & LEGEND
PLUMBING
P1.10 LOCKER ROOM ADDITION PLUMBING PLAN
FIRE PROTECTION
FP1.10 LOCKER ROOM ADDITION FIRE PROTECTION PLAN
FP1.20 EXISTING FIRE PROTECTION PLAN
MECHANICAL
M1.20 LOCKER ROOMS HVAC PLAN
M1.30 LOCKER ROOMS HYDRONIC PLAN
ELECTRICAL
E1.10 LOCKER ROOM ADDITION ELECTRICAL PLANS
CONCESSION & TEAM ROOM
BUILDING
STRUCTURAL
S2.10 CONCESSIONS STRUCTURAL PLAN & NOTES
S2.20 STRUCTURAL DETAILS
ARCHITECTURAL
A2.10 CONCESSIONS & TEAMROOM PLANS & NOTES
A2.11 CONCESSION & TEAMROOM TUNNEL PLANS, SECTIONS, &
DETAILS
A2.12 CONCESSION & TEAMROOM ENLARGED PLANS & NOTES
A2.20 CONCESSIONS & TEAMROOM DOOR AND FRAME
SCHEDULE, WALL SECTIONS & DETAILS
A2.30 CONCESSIONS & TEAMROOM EXTERIOR ELEVATIONS &
BUILDING SECTIONS
A2.40 CONCESSION & TEAMROOM DETAILS
A2.80 CONCESSION & TEAMROOM INTERIOR ELEVATIONS
A2.90 CONCESSIONS BUILDING FINISH PLANS & INTERIOR
ELEVATIONS
PLUMBING
P2.10 CONCESSION PLUMBING PLANS
P2.20 ENLARGED PLUMBING PLANS
MECHANICAL
M2.20 CONCESSIONS AND LOCKER ROOMS HVAC PLANS
ELECTRICAL
E2.10 CONCESSIONS BUILDING POWER & COMMUNICATIONS PLAN
E2.20 CONCESSIONS BUILDING LIGHTING PLANS
E6.01 ELECTRICAL ONE-LINE DIAGRAM
E7.01 ELECTRICAL SYMBOL LEGENDS
E7.02 ELECTRICAL DETAILS
E7.03 ELECTRICAL SCHEDULES
TICKET BOOTHS
STRUCTURAL
S3.10 FOUNDATION PLAN, ROOF PLAN & NOTES
ARCHITECTURAL
A3.10 TICKET BOOTH PLANS & NOTES
A3.20 EXTERIOR ELEVATIONS, SECTIONS & DETAILS
ELECTRICAL
E3.10 TICKET BOOTH ELECTRICAL PLANS
PRESS BOX
ARCHITECTURAL
A4.01 OVERALL STADIUM PLAN
A4.10 PRESS BOX PLANS & NOTES
A4.11 BLEACHER ENLARGED PLANS
A4.20 EXTERIOR ELEVATIONS & BUILDING SECTIONS
A4.30 STADIUM SECTIONS AND DETAILS
A4.31 PRESS BOX SECTION AND DETAILS
A4.91 PRESS BOX INTERIOR ELEVATIONS, FINISH PLAN & LEGEND
MECHANICAL
M4.20 PRESSBOX HVAC PLANS
ELECTRICAL
E4.10 PRESSBOX ELECTRICAL PLANS
STORAGE BUILDING &
DUGOUTS
ARCHITECTURAL
A5.10 STORAGE BUILDING / DUGOUT PLANS & DETAILS
A5.20 SECTIONS & DETAILS
MECHANICAL
M5.20 STORAGE BUILDING HVAC AND PLUMBING PLANS
ELECTIRCAL
E5.10 STORAGE BUILDING & DUGOUT ELECTRICAL PLANS
E1.01 NORTH ELECTRICAL SITE PLAN
E1.02 WEST ELECTRICAL SITE PLAN
E1.03 EAST ELECTRICAL SITE PLAN
E1.04 SOUTH ELECTRICAL SITE PLAN
E1.05 DISTRICT FIBER OPTIC PLAN
E1 UNDERGROUND ELECTRIC LAYOUT - NORTHMEN DRIVE (NORTH)
E2 UNDERGROUND ELECTRIC LAYOUT - NORTHMEN DRIVE (WEST)
E3 UNDERGROUND ELECTRIC LAYOUT - NORTHMEN DRIVE (EAST)
E4 UNDERGROUND ELECTRIC LAYOUT - McDOUGAL DRIVE
ISSUED FOR REFERENCE
PROJECT LOCATION
E-1320 CFM
E-1
320 CFM
E-1
400 CFM
E-1
400 CFM
HC-15.13100 CFM
HC-15.23100 CFM
24"x24"ACCESSPANEL
S-1700 CFM
S-2
175 CFM
S-2
175 CFM S-1700 CFM
14"x14" SA
8"ø SA 8"ø SA
12"ø SA
14"x14" SA
12"ø SA
30"x14" SA
44"x18" SA30"x14" SA
20"x14" SA
12"ø SA
S-1700 CFM
E-2
175 CFM
E-2
175 CFM
E-2
125 CFM
E-2
125 CFM
8"x8" EA8"x8" EA
14"x14" EA
10"x10" EA
S-1
700 CFM
18"x14" SA
18"x14" SA
12"ø SA
S-1700 CFM
10"x14" SA
S-1
700 CFM
12"ø SA
10"x10" EA
14"x14" EA
30"x14" EA
30"x14" EA
14"x14" EA
10"x10" EA
S-1
700 CFM
12"ø SA
10"x14" SA
S-1700 CFM
12"ø SA
18"x14" SA
14"x14" EA
10"x10" EA
CH-15.11.8 GPM
CH-15.21.8 GPM
12"ø SASEE DETAIL 1/M1.10 (TYP.)
S-2
125 CFM
S-2
125 CFM8"ø SA 8"ø SA
8"x8" EA8"x8" EA
20"x14" EA
TOILET / SHOWER103
TOILET / SHOWER110
OFFICE111
OFFICE102
TOILET107
TOILET106
WOMENS LOCKERROOM
104MENS LOCKER ROOM
109
CORRIDOR112
CORRIDOR101
SD
SD
SD
SD
30"x14" EA
24"x24"ACCESS
PANEL
24"x24"ACCESS
PANEL 24"x24"ACCESSPANEL
E-31040 CFM
E-31040 CFM
E-31040 CFM
E-31040 CFM
ALL EXHAUST DUCTWORK TOBE ALUMINUM CONSTRUCTION
ERU-15.1 (ON ROOF)6000 CFMSEE DETAIL 2/M1.20
COORDINATE LOCATIONWITH STRUCTURAL.
SHOWER ROOM105
SHOWER ROOM108
16"x14" EA
16"x14" EA
16"x14" EA
16"x14" EA
44"x18" SA22"x18" SA
22"x18" SA
24"x18" EA
24"x18" EA
25"x25" SA DROP.CONNECT TO UNIT
DUCT SIZE.
26"x26" EA DROP.CONNECT TO UNITDUCT SIZE.
1. ACTUAL LOCATION OF GRILLES AND DIFFUSERS SHALL BE COORDINATED WITHREFLECTED CEILING PLAN. IF THERE ARE ANY DISCREPANCIES VERIFY FINALLOCATION WITH ARCHITECT/ENGINEER.
2. INSTALL ALL THERMOSTATS/SENSORS AT 48" A.F.F. TO TOP OFTHERMOSTATS/SENSORS, UNLESS NOTED OTHERWISE. ALLTHERMOSTATS/SENSORS INSTALLED SHALL HAVE INSULATED BACKPLATES.
3. CONTRACTOR SHALL FIELD VERIFY MECHANICAL EQUIPMENT CONDITIONS PRIOR TOFABRICATION AND CONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS.
4. IN AREAS OF ACOUSTICALLY LINED AND DOUBLE WALL DUCTWORK, THE DIMENSIONSLISTED ARE THE FREE AREA WITHIN THE DUCT LINER.
5. IN AREAS WHERE DUCTWORK IS EXPOSED, ROUTE DUCTWORK AS HIGH AS POSSIBLEUNLESS NOTED OTHERWISE ON DRAWINGS.
6. CONTRACTOR SHALL REFER TO CODE COMPLIANCE DRAWING FOR INFORMATION ONRATINGS OF FIRE/SMOKE DAMPERS.
7. PAINT INTERIOR OF DUCT AT RETURN AND EXHAUST DIFFUSERS/GRILLES FLAT BLACK.
8. FLEXIBLE DUCTWORK CORE SHALL BE CLAMPED AND TAPED AT ALL CONNECTIONSAND JOINTS (i.e. AT CONNECTION TO BRANCH DUCTWORK, DIFFUSERS, ETC.). TAPESHALL MEET REQUIREMENTS OF UL181B-FX. IN ADDITION, FLEXIBLE DUCTWORKJACKET SHALL BE TAPED AT ALL CONNECTIONS AND JOINTS WITH TAPE MEETINGTHE ABOVE STATED REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONALINFORMATION.
9. ALL SUPPLY AND RETURN AIR DUCTWORK SHOWN WITH DASHES SHALL BEINTERNALLY LINED DOUBLE WALL DUCTWORK WITH 1" THICK DUCT LINER FOR ROUNDAND RECTANGULAR SUPPLY & RETURN. ALL EXHAUST DUCTWORK SHOWN WITHDASHES SHALL BE ACOUSTICALLY LINED SINGLE WALL DUCTWORK.
10.SEAL ALL JOINTS AIRTIGHT WHERE NEW DUCTWORK CONNECTS TO EXISTING,TYPICAL.
GENERAL HVAC NOTES:
HUMIDISTAT
PARALLEL BLADE DAMPER
OPPOSED BLADE DAMPER
VOLUME DAMPER
FIRE DAMPER (THRU FLOOR)-
FIRE DAMPER (THRU WALL)-
(DYNAMIC)D
(DYNAMIC)
SMOKE DETECTOR
SMOKE DAMPER (THRU FLOOR)-
SMOKE DAMPER (THRU WALL)-
RADIANT FLOOR THERMOSTATR
MOTOR OPERATED DAMPER
MANOMETER
BACK-DRAFT DAMPER
D
SD
M
THERMOSTAT / SENSOR
SD
SD
F/SD
F/SD
COMBINATION FIRE/SMOKE DAMPER(THRU FLOOR)
COMBINATION FIRE/SMOKE DAMPER(THRU WALL)
FIRE DAMPER (THRU FLOOR)-
FIRE DAMPER (THRU WALL)-
(STATIC)
(STATIC)
SUPPLY AIR INDICATOR
RETURN AIR INDICATOR
EXHAUST AIR INDICATOR
HVAC SCHEMATIC SYMBOLS
H
T
ST
THE FLEXIBLE DUCTWORK CORE SHALL BE CLAMPED(ZIP-STRIPS CAN ALSO BE USED) AND TAPED AT ALLCONNECTIONS. ALSO, THE FLEXIBLE DUCTWORKJACKET/INSULATION SHALL BE TAPED AT ALL CONNECTIONS.TAPE SHALL MEET REQUIREMENTS OF UL181B-FX. REFER TOSPECIFICATIONS FOR ADDITIONAL INFORMATION.
ACCEPTABLE INSTALLATION
ACCEPTABLE INSTALLATION BOTTOM TAKE OFF (ACCEPTABLE)
ACCEPTABLE INSTALLATION
NOTE:
1. FLEXIBLE DUCTWORK SHALL NOT EXCEED 3'-0" IN LENGTH.
2.
SUPPLY AIR DUCT,REFER TO PLANS FORSIZE (TYP.).
LO-LOSS FITTING (TYP.)
VOLUME DAMPER (TYP.)
LOW PRESSUREFLEXIBLE DUCT (TYP.)
SUPPLY AIR DIFFUSER, REFERTO EQUIPMENT SCHEDULE (TYP.)
PROVIDE DUCT TRANSITION ATDIFFUSER IF REQUIRED. (TYP.)
1.5 DIAMETER BEND RADIUSPREFERRED, BUT 1.0 DIAMETERBEND RADIUS EXCEPTED WHERESPACE RESTRICTIONS EXIST (TYP.)
PROVIDE HANGERS (TYP.)
PROVIDE SADDLESFOR FLEX (TYP.)
UNSUPPORTED AND UNCONSTRAINEDBENDS OR TURNS LESS THAN TWODIAMETERS, OR ALLOWANCE OF ANYSAGGING, IS NOT ACCEPTED.
MIN. OF 2 DUCT DIAMETERS
1.5 DIAMETER BEND RADIUSPREFERRED, BUT 1.0 DIAMETERBEND RADIUS EXCEPTED WHERESPACE RESTRICTIONS EXIST (TYP.)
3. ALL DUCT TAKE-OFFS FROM SUPPLY AND RETURN DUCTMAINS SHALL BE 45" DEGREE LO-LOSS TYPE.
ABBREVIATIONS
AFFBFWBODBOG
CABOP
CHCONVCOCWDCWDHWDHWREAEFFCOFDFPGHWRHWSOAPIVRECIRCRWR
RARWS
SANSTSASWTODTOGTOPVVDVTRUHWWCOWH
ABOVE FINISHED FLOORBOILER FEED WATERBOTTOM OF DUCTBOTTOM OF GRILLEBOTTOM OF PIPECOMPRESSED AIRCHILLED GLYCOL RETURNCHILLED GLYCOL SUPPLYCABINET HEATERCONVECTORCLEAN-OUT
DOMESTIC COLD WATERDOMESTIC COLD WATER
DOMESTIC HOT WATERDOMESTIC HOT WATER RETURNEXHAUST AIREXHAUST FANFLOOR CLEAN-OUTFLOOR DRAINFIRE PROTECTIONNATURAL GASHOT WATER RETURN (HEATING)HOT WATER SUPPLY (HEATING)OUTSIDE AIRPOST INDICATOR VALVEDOMESTIC HOT WATER RETURNRADIANT WATER RETURN
RETURN AIRSANITARY WASTESTORM WATERSUPPLY AIRSOFTWATERTOP OF DUCTTOP OF GRILLETOP OF PIPEVENTVOLUME DAMPERVENT THRU ROOFUNIT HEATERWASTEWALL CLEAN-OUTWALL HYDRANT
RADIANT WATER SUPPLY
CGRCGS
CABINET HEATERS
CH-15.1Cabinet Heater, Locker Corridor 101: Trane force-flow cabinet heater, Model FFEB040, horizontal recessed, stamped front inlet and outlet, Size 04, nominal 320 CFM, standard 0.13 hp motor, 120/1/60, 2.75 min.circuit ampacity, 15A max circuit breaker, disconnect switch, 4H hot water coil, 144 FPF, 27.6 MBH, 160F EWT, 30 deg. F WTD, 1.8 GPM, 5.8 ft. WPD, high speed fan operation, 1" throwaway filters, factoryinstalled fan speed switch (Off-Hi-Med-Lo), disconnect located in the unit and access door. Controlled by the BMS/ATC Contractor.
CH-15.2Cabinet Heater, Locker Corridor 112: Same as CH-15.2.
ENERGY RECOVERY UNIT
ERU-15.1
Energy Recovery Unit, Locker Room: SEMCO Preconditioning Unit, Model FV-7500V, utilizing a total energy wheel. Unit shall be located on roof and shall have outdoor air and exhaust air hoods and vertical exhaustair inlet and outdoor air discharge ductwork connections. Install smoke detectors in outside/supply air and exhaust air duct, refer to specification. Provide with 16 high roof curb, factory insulated, hinged accessdoors for filter, wheel and fan motor, and with two (2) sets of filters.
Air volume information: Supply air; 6,000 CFM @ 1.0" ESP, Return/Exhaust air; 6,100 CFM @ 1.0" ESP. Filters: 1” thick permanent aluminum washable filters for outside air, 2” pleated MERV 8 for return air, 0.50“ wheel PD, 71% TE effectiveness
Performance:Outdoor conditions: 91EDB/73.6 EWB summer, 0 EDB winter.Indoor conditions: 75 DB / 64 WB summer, 70 DB / 54 WB winter.Supply air: 79.6 DB / 67.0 WB summer, 49.7 DB winter.
Electrical Data: Supply Fan; 5.0 HP w/ VFD provided with the unit, Exhaust Fan; 7.5 HP w/ VFD provided with the unit, Enthalpy Wheel 1/2 HP, control transformer, airflow monitor, 480/3/60, 23.5 MCA, 30 MOP.Provide unit with NEMA 3R electrical panel, individual motor contactors, non-fused disconnect, HOA switch, motorized intake damper with operator, motorized exhaust damper, indoor filter assembly and thermostatwheel frost protection.
HEATING COILS
HC-15.1Heating Coil, ERU-15.1: Trane duct coil, 44" width x 18" height, type W coil, 4 rows, Fin Type PH, 100 FPF, with turbulators, 45 EAT, 130 EWT, 95.0 LAT, 158.4 MBH, 10.6 GPM, 30 WTD, 3,100 CFM, 0.33 APD,0.91 ft. WPD. BMS/ATC shall control with three-way valve.
HC-15.2Heating Coil, ERU-15.1: Same as HC-2. BMS/ATC shall control with three-way valve.
PLUMBING EQUIPMENT
DWH-1Domestic Water Heater, HS Locker: Lochinvar electric water heater, Standard Hi-Power model HSX30-080, 80 gallon capacity, (3) heating elements, 13.5 total watts, 36.1 amps, surface mounted thermostat, 60.1/4”H x 25.1/2” Dia., 480/3/60, 1.1/4” water connections.
ET-1Expansion Tank, DWH-1: Amtrol Thermal Expansion Absorber, ST series, model ST-8, horizontal, 200F maximum system temperature, 150 psi maximum operating pressure, 3.2 gallon tank volume, 15" long x 9"dia., 3/4" NPT connection size, diaphragm-type, pre-pressurized tank (40 psi), steel shell, heavy duty butylene.
PP-1Domestic Hot Water Recirculation Pump: Bell & Gossett bronze circulator rated for potable water use, Series PL30, 2 GPM at 23 ft TDH, 1/12 HP, 3/4” NPT flanged connection, 2650 RPM, 120/1/60.
GRILLES/REGISTERS/DIFFUSERS
S-1Supply Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 30 deg. fixed deflection, one set of blades parallel to the long dimension, size 16”W x 16”H, white finish, with opposedblade damper.
S-2Supply Air Grille: Titus rectangular supply grille, model 300FS, 8"x8" duct size, double deflection, 3/4" blade spacing, aluminum construction, surface mount, white finish.
E-1Exhaust Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 30 deg. fixed deflection, one set of blades parallel to the long dimension, size 12”W x 12”H, white finish, with opposedblade damper.
E-2Exhaust Air Grille: Titus return grille, Model 350FL, 3/4" blade spacing, 35 deg. fixed blade deflection, aluminum construction, surface mount, white finish and 8" x 8" neck size.
E-3Exhaust Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 30 deg. fixed deflection, one set of blades parallel to the long dimension, size 20”W x 20”H, white finish, with opposedblade damper.
EQUIPMENT SCHEDULE:
EQUIPMENT FLASHING
ROOF CURB (SIZEAS REQUIRED FOREQUIPMENT)
OPENING IN ROOF
FLASH CURB INTO ROOF
ROOF STRUCTURE
ROOF OPENINGFRAMING ANGLES (SEEPLANS FOR SIZE)3.1/2"x5"x1/4" MIN.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2014 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616.796.0201
Holland, Michigan 49423
www.gmb.com
02.09.15 BIDS & CONSTRUCTION
C:\L
OC
AL P
RO
JEC
TS\5
-321
1M_L
OC
KER
RO
OM
_CE
NTR
AL_
JeffT
.rvt
M1.20
5-3211
LOCKER ROOMS HVAC PLAN
RS/JT
NE
W S
TA
DIU
M &
CA
MP
US
IMP
RO
VE
ME
NT
S
PU
BLI
C S
CH
OO
LS O
F P
ETO
SK
EY
PE
TO
SK
EY
, M
ICH
IGA
N
NORTH
1/4" = 1'-0"LOCKER ROOMS HVAC
NOT TO SCALEM1.201 Ceiling Diffuser Flex Connection
NOT TO SCALEM1.202 Roof Curb Detail
HC-15.110.6 GPM
HC-15.210.6 GPM
CH-15.11.8 GPM
CH-15.21.8 GPM
1 1/4" HWS 1 1/4" HWR 1 1/4" HWS1 1/4" HWR
2" HWS 2" HWR
3/4" HWR
3/4" HWS
2" HWR
2" HWS
3/4" HWS 3/4" HWR 2 1/2" HWR
2 1/2" HWS
SEE DETAIL 1/M1.30 (TYP.)
SEE DETAIL 2/M1.30
SEE DETAIL 4 (TYP.)
S
S
S
S
EXIST C-11.0 GPM
EXIST C-11.0 GPM
EXIST C-11.0 GPM
EXIST. FT-11.0 GPM
EXIST. FT-11.0 GPM
EXIST. BC-1B1.2 GPM
EXIST. BC-2B1.2 GPM
EXIST. BC-3B3.1 GPM
EXIST. BC-4B1.1 GPM
EXIST. BC-5B2.4 GPM
EXIST. BC-6B1.2 GPM
EXIST. BC-7B1.6 GPM
EXIST. C-11.0 GPM
REBALANCE EXISTING EQUIPMENT AS SHOWN
EXIST. CUH-43.8 GPM
EXIST. CUH-11.0 GPM
EXIST. FT1.0 GPM
EXIST. FT1.0 GPM
EXIST. FT1.0 GPM
ROUTE PIPING THRU BACK RIGHT CORNER OFCLOSET IN B0-105. CONFIRM ROUTE WITH OWNERAND ENGINEER PRIOR TO INSTALLATION. PIPERUNS FROM LEVEL B00, THROUGH B0, TO B1. SEEUPPER HYDRONIC PLAN FOR CONTINUATION.
PENETRATIONS AT ALL FLOOR/DECKPENETRATIONS SHALL BE FIRE CAULKED.
SEE DETAIL 3/M1.30
2 1/2" HWR
2 1/2" HWS
2" HWR 2" HWS
VALVE AND CAPFOR FUTURE
TOILET / SHOWER103
SHOWER ROOM105
SHOWER ROOM108
TOILET / SHOWER110
OFFICE111
OFFICE102
TOILET107
TOILET106
WOMENS LOCKERROOM
104MENS LOCKER ROOM
109
CORRIDOR112
CORRIDOR101
HOT WATER RETURN
HOT WATER SUPPLY
CABINET HEATERABOVE CEILING
FILTER
COIL
NOTE: DRAIN & VENTS SHALLBE 3/4" BOILER DRAIN COCKSWITH CAPS, TYPICAL.
VENT
B&G CIRCUIT SETTERPLUS COMBINATION BALANCE/ISOLATION VALVE.
NOTE: UNIONS SHOWNFOR STEEL PIPE ONLY
THERMOSTAT
STRAINER W/ BLOWDOWN VALVEDRAIN
T
PIPE INSULATIONPER SPECIFICATIONS
PIPE INSULATION INSERTPER SPECIFICATIONS
ADJUSTABLE CLEVISHANGER
ROD SIZE ANDSPACING PERSPECIFICATIONS
PIPE INSULATIONSHIELD PER SPECS.
S
T
OR
OR
VALVE SYMBOLS
GATE VALVE
BALL VALVE
GLOBE VALVE
BUTTERFLY VALVE
SWING CHECK VALVE
TRIPLE-DUTY VALVE
PLUG VALVE
DIAPHRAM VALVE
NEEDLE VALVE
ANGLE VALVE
THREE-WAY VALVE
SELF CONTAINED PRESS. RED'G VALVE
EXT. PRESSURE RED'G VALVE
CHECK VALVE
RELIEF / SAFETY VALVE
SOLENOID VALVE
HOSE BIBB
CIRCUIT SETTER
TEMPERATURE CONTROL VALVE
3-WAY TEMPERATURE CONTROL
SELF OPERATED VALVE
BACKFLOW PREVENTERWITH DRIP PAN
INDICATES VALVE IS FLANGED (TYP)
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING PIPE ROUTING WITH DUCTWORKAND ELECTRICAL TRADES.
INSTALL THERMOSTATS/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/ SENSORS, UNLESSNOTED OTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVEINSULATED BACKPLATES.
CONTRACTOR SHALL FIELD VERIFY MECHANICAL EQUIPMENT CONDITIONS PRIOR TOFABRICATION AND CONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. CONTRACTORSHALL BE RESPONSIBLE FOR THE COORDINATION OF PIPE ROUTING WITH DUCTWORK ANDELECTRICAL TRADES. REFER TO DETAIL SHEETS M7.01 AND M7.02 FOR TYPICAL COIL,EQUIPMENT, VALVE AND PIPING INFORMATION.
CORE HOLES IN WALLS AND FLOORS FOR PIPES, PROVIDE SLEEVES, AND FIRE STOP TOMAINTAIN WALL/FLOOR RATING. SEE CODE COMPLIANCE PLANS FOR RATINGS.
ALL PIPING BRANCHES SHALL HAVE ISOLATION VALVES LOCATED ABOVE THE CEILING(INCORRIDORS) OR MECHANICAL ROOMS AND/0R CLOSETS AT AN ACCESSIBLE LOCATION ANDHEIGHT. INTENT OF DESIGN IS FOR ALL DUCTWORK TO BE LOCATED HIGH AS POSSIBLE WHEREPIPING AND DUCTWORK CROSS OR INHABIT SAME LOCATIONS, ALL HYDRONIC PIPING SHALL BELOCATED UNDER DUCTWORK. COORDINATE INSTALLATION WITH MECHANICAL/HVACCONTRACTOR.
PATCH AND REPAIR ALL EXISTING PIPE INSULATION WHERE NEW HOT WATER HEATING SUPPLYAND RETURN PIPING CONNECTS TO EXISTING PIPING, TYPICAL.
COORDINATE PIPING AND THERMOSTATS WITH APPROPRIATE TRADES TO AVOIDINTERFERENCES.
GENERAL HYDRONIC PIPING NOTES:1.
2.
3.
4.
5.
6.
7.
ABBREVIATIONS
AFFBFWBODBOG
CABOP
CHCONVCOCWDCWDHWDHWREAEFFCOFDFPGHWRHWSOAPIVRECIRCRWR
RARWS
SANSTSASWTODTOGTOPVVDVTRUHWWCOWH
ABOVE FINISHED FLOORBOILER FEED WATERBOTTOM OF DUCTBOTTOM OF GRILLEBOTTOM OF PIPECOMPRESSED AIRCHILLED GLYCOL RETURNCHILLED GLYCOL SUPPLYCABINET HEATERCONVECTORCLEAN-OUT
DOMESTIC COLD WATERDOMESTIC COLD WATER
DOMESTIC HOT WATERDOMESTIC HOT WATER RETURNEXHAUST AIREXHAUST FANFLOOR CLEAN-OUTFLOOR DRAINFIRE PROTECTIONNATURAL GASHOT WATER RETURN (HEATING)HOT WATER SUPPLY (HEATING)OUTSIDE AIRPOST INDICATOR VALVEDOMESTIC HOT WATER RETURNRADIANT WATER RETURN
RETURN AIRSANITARY WASTESTORM WATERSUPPLY AIRSOFTWATERTOP OF DUCTTOP OF GRILLETOP OF PIPEVENTVOLUME DAMPERVENT THRU ROOFUNIT HEATERWASTEWALL CLEAN-OUTWALL HYDRANT
RADIANT WATER SUPPLY
CGRCGS
EX. AHU-1B93.2 GPM
EX. AHU-2B93.2 GPM
EX. AHU-3B23.2 GPM
EX. AHU-4B
EX. AHU-5B10.5 GPMUH-4
4.7 GPM
UH-44.7 GPM
REBALANCE EXISTINGEQUIPMENT AS SHOWN
PIPING CONTINUED ON LOWERLEVEL HYDRONIC PLAN.
2 1/2" HWS2 1/2" HWR
FIRE STOP AROUND FLOOR AND WALL PENETRATIONS (TYP.)
FAN ROOMB1-101
EXIST. 6" HWS&R
EXIST. 4" HWS&RNEW 2-1/2" HWS&R
EXIST. 2-1/2" HWS&R
EXIST. 2-1/2" HWS&R(BELOW 6" HWS&R)
NEW 6" HWS&R(ABOVE 2-1/2" HWS&R)
NEW 4" HWS&R(ABOVE 2-1/2" HWS&R)
NOTE: REPLACE PORTION OF 4" HWS&R WITH 6" HWS&R AFTER EXIST.2-1/2" HWS&R TEES. CONNECT NEW 2-1/2" HWS&R INTO NEW 6"HWS&R. RECONNECT EXISTING 4" HWS&R INTO NEW 6" HWS&R.CONTRACTOR TO FIELD VERIFY SIZES AND LOCATIONS. MAINTAINEXISTING ISOLATION AND BALANCING VALVE ON 2-1/2" AND 4" PIPING.
SET TO 24.8 GPM
REHEAT COIL
ACCESS DOOR
ADJUST DUCT SIZEAS REQUIRED FORREHEAT COIL
NOTE: DRAIN & VENTS SHALLBE 3/4" BOILER DRAIN COCKSWITH CAPS, TYPICAL.
BALL VALVE
HOT WATER SUPPLY
SUPPLY MAIN DUCT.REFER TO PLANSFOR SIZE.
HOT WATER RETURN
CIRCUIT SETTER
PIPE REDUCER, TYPICAL.
TEMPERATURE CONTROLVALVE. SEE MECH. EQUIP.SCHED. FOR VALVE TYPE.
VENT
ACCESS DOOR
REHEAT COIL
ACCESS DOOR
ADJUST DUCT SIZEAS REQUIRED FORREHEAT COIL
NOTE: DRAIN & VENTS SHALLBE 3/4" BOILER DRAIN COCKSWITH CAPS, TYPICAL.
BALL VALVE
HOT WATER SUPPLY
SUPPLY MAIN DUCT.REFER TO PLANSFOR SIZE.
HOT WATER RETURN
CIRCUIT SETTER
PIPE REDUCER, TYPICAL.
TEMPERATURE CONTROLVALVE. SEE MECH. EQUIP.SCHED. FOR VALVE TYPE.
VENT
ACCESS DOOR
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2014 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616.796.0201
Holland, Michigan 49423
www.gmb.com
02.09.15 BIDS & CONSTRUCTION
C:\L
OC
AL P
RO
JEC
TS\5
-321
1M_L
OC
KER
RO
OM
_CE
NTR
AL_
JeffT
.rvt
M1.30
5-3211
LOCKER ROOMS HYDRONICPLAN
NE
W S
TA
DIU
M &
CA
MP
US
IMP
RO
VE
ME
NT
S
PU
BLI
C S
CH
OO
LS O
F P
ETO
SK
EY
PE
TO
SK
EY
, M
ICH
IGA
N
NORTH
1/8" = 1'-0"LOCKER ROOMS HYDRONIC PLAN
NOT TO SCALEM1.301 Cabinet Heater Piping - Horizontal
NOT TO SCALEM1.304 Chilled & Hot Water Heating Hanger Detail
NORTH
1/8" = 1'-0"LOCKER ROOMS UPPER HYDRONIC PLAN
NOT TO SCALEM1.302 Reheat Coil Piping Detail / 2-way
NOT TO SCALEM1.303 Reheat Coil Piping Detail / 3-way
T
WH-15.2
S-4
125 CFM
S-5
200 CFM
E-5200 CFM
E-5200 CFM
E-6
125 CFM
S
S
SS
S-1
950 CFM
E-1
850 CFM
S-1
950 CFM
E-1
850 CFM
CH-15.8
E-4
125 CFM
E-1
850 CFM
S-3
500 CFM
UH-15.1
16"x12" EA
38"x12" EA 46"x12" EA
48"x14" EA
12"x12" EA
24"x12" SA
24"x12" SA 36"x12" SA 40"x12" SA
60"x14" SA
40"x12" SA 18"x12" SA
18"x12" SA
8"x8" SA 8"x8" SA 18"x10" EA
24"x12" EA
S-3
400 CFM18"x12" SA 14"x12" EA
14"x12" SA
8"x8" EA 8"x8" EA
8"x8" EA
10"x12" EA
8"x8" EA
18"x12" EA
FT-15.3
S-1
950 CFM
E-1
850 CFM
S-1
950 CFM
18"x12" SA 14"x12" EA8"ø SA
14"x12" EA 14"x12" EA 18"x12" SA
CH-15.10
CH-15.11
CH-15.9
INSTALL TEAM ROOM GRILLESAT 9'-8" BOG AFF (TYP.)
6"x6" EA
SA DUCT CT'D ON UPPER LEVEL PLAN EA DUCT CT'D ON UPPER LEVEL PLAN
S-6
270 CFM
E-7270 CFM
10"x10" EA
INSTALL AT 7'BOT. OF FT
6"x6" EAE-675 CFM
14"x14" DOWN TO S-3 WITH VD
14"x14" DOWN TO S-3 WITH VD
CORRIDOR205
COACH TOILET /SHOWER
207
TOILET208
TOILET206
TRAINING203
OFFICIALS ROOM202
CUSTODIAN204
UTILITY211
TEAM ROOM201
TEAM ROOM209
STORAGE212
STORAGE210
E-6
100 CFMT
E-2
500 CFME-2
300 CFM
WH-15.1FT-15.1
38"x26" SA 22"x18" SA 18"x18" SA 10"x18" SA
8"x8" EA
18"x16" EA6"x8" EA
T
S
S
S
S
S S
S
$
6 HR. TWIST TIMER(EF-15.1) PROVIDED ANDINSTALLED BY THEELECTRICAL CONTRACTOR
S-475 CFM
E-475 CFM
6"ø EA
E-475 CFM
6"ø EA
E-4
95 CFM
E-3680 CFM
E-475 CFM
S-475 CFM
E-475 CFM
6"ø EA
6"ø SA
S-475 CFM
6"ø SA 6"ø EA6"ø EA
12"x12" EA
14"ø EA 14"ø EA CH-15.7
16"ø SA
16"ø SA
6"ø SA
E-4
75 CFM
6"ø EA
CH15.4
60"x14" SA
48"x14" EA
14"ø SA
14"ø SA
S-7475 CFM
S-7
475 CFM 6"ø EA
E-4100 CFM
FT-15.2
T
S-2685 CFM
S-4
75 CFM
CH-15.5
CH-15.6
CH-15.3CH-15.2
CH-15.1S-2
685 CFM
S-2735 CFM
E-9685 CFM
E-9685 CFM
E-9735 CFM
E-9
735 CFM
S-2
735 CFM
SA DUCT CT'D ON LOWER LEVEL PLAN EA DUCT CT'D ON LOWER LEVEL PLAN
42"x30" SA
L-15.24600 CFM
18" DEEP PLENUM. SLOPE THE BOTTOM OF THEPLENUM TOWARD THE LOUVER TO ALLOW FOR
DRAINAGE. LOUVER SHALL BE SEALED WATERTIGHT AND SHALL BE PAINTED FLAT BLACK.
REFER TO SHEETS A2.30 AND A2.40 FORELEVATION, SIZE AND SHAPE OF LOUVER.
12"x20" DUCT ACCESS DOOR (TYP.)
EF-15.19385 CFM
24"x24" ACCESS PANEL
L-15.14600 CFM
18" DEEP PLENUM. SLOPE THE BOTTOM OF THEPLENUM TOWARD THE LOUVER TO ALLOW FORDRAINAGE. LOUVER SHALL BE SEALED WATERTIGHT AND SHALL BE PAINTED FLAT BLACK.
REFER TO SHEETS A2.30 AND 2.40 FORELEVATION, SIZE AND SHAPE OF LOUVER.
12"x20" ACCESS DOOR (TYP.)
12"ø SA24"x16" EA
48"x30" EA W/ A.L. (UPPER)48"x14" EA (LOWER)
FLEX DUCT
48"x20" EA (UPPER)48"x14" EA (LOWER)
42"x26" SA
42"x30" SA
96"x20" PLENUM
28"x14" SA
28"x14" SA
I-1
2400 CFM
I-12400 CFM
96"x20" PLENUM
GENERAL STORAGE255
FAMILY TOILET256
MENS257
UTILITY254
CUST252
STORAGE253
CONCESSIONS250
WOMENS258
SECURE STORAGE251
CUST259
14"x14" EA12"x14" EA
20"x26" EA
E-104800 CFM
12"ø SA
INTERLOCK DAMPER W/ EF15.1
24"x24" ACCESS PANEL
6"ø SAINTERLOCK DAMPER W/ EF-15.1
EXCESS DAMPER AREA SHALL BEBLANKED OFF, SEALED WATER TIGHTAND PAINTED FLAT BLACK (TYP.)
FOR SIZE AND LOCATION OF LOUVERFIELD VERIFY DIMENSION PRIOR TOORDERING/FABRICATION.
42"x20" SA
48"x20" EA
INSTALL AT 7'BOT. OF FT
INSTALL AT 7'BOT. OF FT
14"ø EA
14"ø EA
EXCESS DAMPER AREA SHALL BEBLANKED OFF, SEALED WATER TIGHT
AND PAINTED FLAT BLACK (TYP.)
34"x16" EA W/ A.L.
1. ACTUAL LOCATION OF GRILLES AND DIFFUSERS SHALL BE COORDINATED WITH REFLECTED CEILING PLAN.IF THERE ARE ANY DISCREPANCIES VERIFY FINAL LOCATION WITH ARCHITECT/ENGINEER.
2. INSTALL ALL THERMOSTATS/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/SENSORS, UNLESS NOTEDOTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED SHALL HAVE INSULATED BACKPLATES.
3. CONTRACTOR SHALL FIELD VERIFY MECHANICAL EQUIPMENT CONDITIONS PRIOR TO FABRICATION ANDCONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS.
4. IN AREAS OF ACOUSTICALLY LINED AND DOUBLE WALL DUCTWORK, THE DIMENSIONS LISTED ARE THE FREEAREA WITHIN THE DUCT LINER.
5. IN AREAS WHERE DUCTWORK IS EXPOSED, ROUTE DUCTWORK AS HIGH AS POSSIBLE UNLESS NOTEDOTHERWISE ON DRAWINGS.
6. CONTRACTOR SHALL REFER TO CODE COMPLIANCE DRAWING FOR INFORMATION ON RATINGS OFFIRE/SMOKE DAMPERS.
7. PAINT INTERIOR OF DUCT AT RETURN AND EXHAUST DIFFUSERS/GRILLES FLAT BLACK.
8. FLEXIBLE DUCTWORK CORE SHALL BE CLAMPED AND TAPED AT ALL CONNECTIONS AND JOINTS (i.e. ATCONNECTION TO BRANCH DUCTWORK, DIFFUSERS, ETC.). TAPE SHALL MEET REQUIREMENTS OF UL181B-FX.IN ADDITION, FLEXIBLE DUCTWORK JACKET SHALL BE TAPED AT ALL CONNECTIONS AND JOINTS WITH TAPEMEETING THE ABOVE STATED REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
9. ALL SUPPLY AND RETURN AIR DUCTWORK SHOWN WITH DASHES SHALL BE INTERNALLY LINED DOUBLEWALL DUCTWORK WITH 1" THICK DUCT LINER FOR ROUND AND RECTANGULAR SUPPLY & RETURN. ALLEXHAUST DUCTWORK SHOWN WITH DASHES SHALL BE ACOUSTICALLY LINED SINGLE WALL DUCTWORK.
10. SEAL ALL JOINTS AIRTIGHT WHERE NEW DUCTWORK CONNECTS TO EXISTING, TYPICAL.
GENERAL HVAC NOTES:
HUMIDISTAT
PARALLEL BLADE DAMPER
OPPOSED BLADE DAMPER
VOLUME DAMPER
FIRE DAMPER (THRU FLOOR)-
FIRE DAMPER (THRU WALL)-
(DYNAMIC)D
(DYNAMIC)
SMOKE DETECTOR
SMOKE DAMPER (THRU FLOOR)-
SMOKE DAMPER (THRU WALL)-
RADIANT FLOOR THERMOSTATR
MOTOR OPERATED DAMPER
MANOMETER
BACK-DRAFT DAMPER
D
SD
M
THERMOSTAT / SENSOR
SD
SD
F/SD
F/SD
COMBINATION FIRE/SMOKE DAMPER(THRU FLOOR)
COMBINATION FIRE/SMOKE DAMPER(THRU WALL)
FIRE DAMPER (THRU FLOOR)-
FIRE DAMPER (THRU WALL)-
(STATIC)
(STATIC)
SUPPLY AIR INDICATOR
RETURN AIR INDICATOR
EXHAUST AIR INDICATOR
HVAC SCHEMATIC SYMBOLS
H
T
ST
ABBREVIATIONS
AFFBFWBODBOG
CABOP
CHCONVCOCWDCWDHWDHWREAEFFCOFDFPGHWRHWSOAPIVRECIRCRWR
RARWS
SANSTSASWTODTOGTOPVVDVTRUHWWCOWH
ABOVE FINISHED FLOORBOILER FEED WATERBOTTOM OF DUCTBOTTOM OF GRILLEBOTTOM OF PIPECOMPRESSED AIRCHILLED GLYCOL RETURNCHILLED GLYCOL SUPPLYCABINET HEATERCONVECTORCLEAN-OUT
DOMESTIC COLD WATERDOMESTIC COLD WATER
DOMESTIC HOT WATERDOMESTIC HOT WATER RETURNEXHAUST AIREXHAUST FANFLOOR CLEAN-OUTFLOOR DRAINFIRE PROTECTIONNATURAL GASHOT WATER RETURN (HEATING)HOT WATER SUPPLY (HEATING)OUTSIDE AIRPOST INDICATOR VALVEDOMESTIC HOT WATER RETURNRADIANT WATER RETURN
RETURN AIRSANITARY WASTESTORM WATERSUPPLY AIRSOFTWATERTOP OF DUCTTOP OF GRILLETOP OF PIPEVENTVOLUME DAMPERVENT THRU ROOFUNIT HEATERWASTEWALL CLEAN-OUTWALL HYDRANT
RADIANT WATER SUPPLY
CGRCGS
DUCT, REFER TO PLAN FOR SIZE.
RATED WALL
BREAKAWAY CONNECTION PERSMACNA RECOMMENDATIONS.
APPLY FIRE-STOP CAULKINGPER SPECIFICATIONS, TYP.
CLEARANCE: 1/8" PER FOOTOF DAMPER WIDTH OR HEIGHT,MIN. 1/4" / MAX. 1.1/2".
FIRE DAMPER, REFERTO SPECIFICATIONSFOR TYPE.
NOTE: PROVIDE ACCESS DOOR,REFER TO SPECIFICATIONS.LOCATE DOOR PER DAMPERMFG. RECOMMENDATIONS.
6" MAX./3" MIN., TYPICAL.
DAMPER SLEEVE, GAUGE PER MFG.RECOMMENDATIONS, 10 GAUGE MAX.
RETAINING ANGLES SHALL BE 14 GAUGESTEEL (MIN.) WITH MIN. 1.1/2" X 1.1/2" LEGS,TYPICAL. ATTACH TO SLEEVE PER MFG.RECOMMENDATIONS. DO NOT ANCHOR TOWALL. ANGLES SHOULD SANDWICH WALLTO ALLOW FOR EXPANSION AND OVERLAPOPENING A MIN. OF 1"+ CLEARANCE.
RETAINING ANGLES (10 GAUGE MIN.)
CABINET HEATERS
CH-15.1Cabinet Heater, Concessions Room 250: Trane electric horizontal recessed cabinet heater, Model FFEB03, size 03, 280 CFM, 2 stage, 208/3/60, 0.13 hp, 2.0 kW first stage, 4.4kW total capacity, 17.4 MCA, 20.0 MOP, wall mounted speed switch/thermostat provided with the unit and wired by the Electrical Contractor. Cabinet Heater shall be provided with aunit mounted disconnect switch.
CH-15.2Cabinet Heater, Concessions Room 250: Same as CH-1.
CH-15.3Cabinet Heater, Concessions Room 250: Same as CH-1.
CH-15.4Cabinet Heater, Men’s Toilet 257: Trane electric horizontal cabinet heater, Model FFDB02, size 02, 222 CFM, back stamped louver inlet, bottom stamped louver outlet, 2 stage,208/3/60, 0.13 hp, 1.0 kW first stage, 2.2 kW total capacity, 9.57 MCA, 15.0 MOP, wall mounted speed switch/thermostat provided with the unit and wired by the ElectricalContractor. Cabinet Heater shall be provided with a unit mounted disconnect switch.
CH-15.5Cabinet Heater, Men’s Toilet 257: Same as CH-4.
CH-15.6Cabinet Heater, Women’s Toilet 258: Same as CH-4.
CH-15.7Cabinet Heater, Women’s Toilet 258: Same as CH-4.
CH-15.8Cabinet Heater, Toilet 206: Same as CH-4.
CH-15.9Cabinet Heater, Toilet 208: Same as CH-4.
CH-15.10Cabinet Heater, Official’s 202: Same as CH-4.
CH-15.11Cabinet Heater, Training 203: Same as CH-4.
EXHAUST FANS
EF-15.1Exhaust Fan, Concessions/Team Building: Centrifugal centrifugal square blower, model 300 SQNB, belt drive, 9,385 CFM, 1.0" SP, 5 HP, 755 RPM, 16.1 sones, U.L. listed,480/3/60, factory wired disconnect, insulated housing, ducted inlet and discharge, backdraft damper. Controlled by 6 hour twist timer provided and installed by the ElectricalContractor. Interlock operation of fan with dampers. Dampers shall prove open prior to energizing fan.
FINNED TUBE
FT-15.1Electric Finned Tube, Custodial 259: Q-Mark Commercial Baseboard Heater, QMKC2513W Series, 750 watts, 120/1/60, 6.3 amps, 3’-0” length, with wall mounted line voltagethermostat provided with the unit and wired by the Electrical Contractor.
FT-15.2Electric Finned Tube, Custodial 252: Same as FT-1.
FT-15.3Electric Finned Tube, Custodian 204: Same as FT-1.
LOUVERS
L-15.1Exhaust Air Louver, EF-15.1: Ruskin extruded aluminum drainable blade louver, 4" depth, model ELT375DX with 37-1/2 deg. blade angle, bird screen, standard flanged frame, andcustom Kynar 500 finish selected by Architect. Refer to architectural drawing for dimensional information (nominal dimensions 16’-0” base x 3’-4” height, triangular shape).Contractor shall field verify dimensions prior to ordering/fabrication.
L-15.2Intake Air Louver, EF-15.1: Same as L-15.1.
PLUMBING EQUIPMENT
DWH-1Domestic Water Heater, Concessions Building: Lochinvar electric water heater, Standard Hi-Power model HSX18-080, 80 gallon capacity, (3) heating elements, 18 total watts, 21.7amps, surface mounted thermostat, 60.1.1/4” H x 25.1/2” Dia., 480/3/60, 1.1/4” water connections.
ET-1Expansion Tank, DWH-1: Amtrol Thermal Expansion Absorber, ST series, model ST-8, horizontal, 200F maximum system temperature, 150 psi maximum operating pressure, 2.0gallon tank volume, 15" long x 9" dia., 3/4" NPT connection size, diaphragm-type, pre-pressurized tank (40 psi), steel shell, heavy duty butylene.
PEQ-1Ice-Maker Water Box: Guy Gray model BIM875, 18 gauge G90 hot dip galvanized steel box with 20 gauge front, unpainted, angle valve with 1/2” FIP inlet, 1/4” compression outlet.
PP-1Domestic Hot Water Recirculation Pump: Bell & Gossett bronze circulator rated for potable water use, Series PL30, 2 GPM at 23 ft TDH, 1/12 HP, 3/4” NPT flanged connection,2650 RPM, 120/1/60.
PP-2Sanitary Sewage Ejector: ITT/Goulds Model 3886, Size WS0311B, 1/3 HP, 120/1/60, 20 gpm @ 17 ft. head, 1750 RPM, 4.69” impeller diameter, 2” NPT discharge, 2” maximumsolids handling capability. Furnish factory simplex control panel with NEMA 1 enclosure, single pump operation, pump run light and HOA switch, local visual and audible alarm, highlevel alarm circuit with manual reset, auxiliary dry alarm contacts for BMS/ATC interface, factory starter and disconnect switch. Provide mechanically activated float switches for levelcontrol and control wiring.
Provide with polyethylene vault equal to Goulds Poly Basin, Simplex A7-2401S, 24” dia. and 36” deep, 2” Schedule 40 PVC discharge pipe and valves, 2” PVC check valve at top ofriser, sealed polyethylene cover with 2” vent, 2” discharge pipe opening and opening for electrical feeder (coordinate with Electrical Contractor for installation of conduit feed) withpipe grommet to seal each opening.
UNIT HEATER
UH-15.1
Unit Heater, Utility 211: Q-Mark Unit Heater, CMUH0371 Series, 3000 watts, 277/1/60, 11.0 amps, wall bracket, fan delay switch, line voltage thermostat provided with the unit andwired by the Electrical Contractor.
WALL HEATERS
WH-15.1Electric Wall Heater, Family Toilet 256: Q-Mark Commercial Fan Forced Wall Heater, CWH3150F Series, 1500 watts, 120/1/60, 12.5 amps, built-in disconnect switch, fan delayswitch, integral thermostat.
WH-15.2Electric Wall Heater, Coach/Toiler Shower 207: Same as WH-15.1.
GRILLES/REGISTERS/DIFFUSERS
S-1Supply Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 38 deg. fixed deflection, one set of blades parallel to the long dimension, size 28”W x16”H, white finish.
S-2Supply Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 38 deg. fixed deflection, one set of blades parallel to the long dimension, size 16”W x16”H, white finish, with opposed blade damper.
S-3Supply Air Grille: Titus heavy duty rectangular supply grille, model 300HDFS, 14"x14" duct size, double deflection, 3/4" blade spacing, aluminum construction, surface mount, whitefinish.
S-4Supply Air Grille: Titus heavy duty rectangular supply grille, model 300HDFS, 8"x8" duct size, double deflection, 3/4" blade spacing, aluminum construction, surface mount, whitefinish.
S-5Supply Air Grille: Titus heavy duty rectangular supply grille, model 300HDFS, 10"x10" duct size, double deflection, 3/4" blade spacing, aluminum construction, surface mount, whitefinish.
S-6Supply Air Diffuser: Titus square ceiling diffuser, Model TMSA-AA, 24" x 24" face size, adjustable discharge pattern, Type 3 lay-in frame, white finish, aluminum construction, and 8"dia. neck size.
S-7Supply Air Diffuser: Titus square ceiling diffuser, Model TMSA-AA, 24" x 24" face size, adjustable discharge pattern, Type 3 lay-in frame, white finish, aluminum construction, 12"dia. neck size, and opposed blade damper.
E-1Exhaust Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 30 deg. fixed deflection, one set of blades parallel to the long dimension, size 28”Wx 16”H, white finish.
E-2Exhaust Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 30 deg. fixed deflection, one set of blades parallel to the long dimension, size 22”Wx 8”H, white finish.
E-3Exhaust Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 30 deg. fixed deflection, one set of blades parallel to the long dimension, size 18”Wx 18”H, white finish, with opposed blade damper.
E-4Exhaust Air Grille: Titus heavy duty bar grille, model 630FL, aluminum construction, 1/2" spacing, 30 deg. fixed deflection, one set of blades parallel to the long dimension, size 8”Wx 8”H, white finish, with opposed blade damper.
E-5Exhaust Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 30 deg. fixed deflection, one set of blades parallel to the long dimension, size 10”Wx 10”H, white finish, with opposed blade damper.E-6Exhaust Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 30 deg. fixed deflection, one set of blades parallel to the long dimension, size 8”W x8”H, white finish.
E-7Exhaust Air Grille: Titus perforated exhaust grille, Model PAR-AA, 24" x 24" face size, white finish, Type 3 lay-in frame and 10"x10” neck size. Paint ductwork flat black behind grille.
E-8Not Used.
E-9Exhaust Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 38 deg. fixed deflection, one set of blades parallel to the long dimension, size 16”Wx 16”H, white finish, with opposed blade damper.
E-10Exhaust Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 38 deg. fixed deflection, one set of blades parallel to the long dimension, size 74”Wx 20”H, white finish.
I-1Intake Air Grille: Titus heavy duty bar grille, model 63FL, aluminum construction, 1/2" spacing, 38 deg. fixed deflection, one set of blades parallel to the long dimension, size 30”W x30”H, white finish.
EQUIPMENT SCHEDULE:
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2014 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616.796.0201
Holland, Michigan 49423
www.gmb.com
02.09.15 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-3
211M
_CO
NC
ESS
ION
S_C
EN
TRA
L_Je
ffT.rv
t
M2.20
5-3211
CONCESSIONS AND TEAMROOMS HVAC PLANS
RS/JT
NE
W S
TA
DIU
M &
CA
MP
US
IMP
RO
VE
ME
NT
S
PU
BLI
C S
CH
OO
LS O
F P
ETO
SK
EY
PE
TO
SK
EY
, M
ICH
IGA
N
NORT
H
1/4" = 1'-0"CONCESSIONS/TEAM ROOMS LOWER LEVEL PLAN
NORT
H
1/4" = 1'-0"CONCESSIONS/TEAM ROOMS UPPER LEVEL PLAN
NOT TO SCALEM2.201 Vertical Fire Damper
FT-15.1 FT-15.2
T T T T T
VIEWING405
VISITOR VIEWING407
MEDIA VIEWING409
MEDIA VIEWING401
HOME VIEWING403
FT-15.3
FT-15.5FT-15.4
1. ACTUAL LOCATION OF GRILLES AND DIFFUSERS SHALL BE COORDINATED WITHREFLECTED CEILING PLAN. IF THERE ARE ANY DISCREPANCIES VERIFY FINALLOCATION WITH ARCHITECT/ENGINEER.
2. INSTALL ALL THERMOSTATS/SENSORS AT 48" A.F.F. TO TOP OFTHERMOSTATS/SENSORS, UNLESS NOTED OTHERWISE. ALL THERMOSTATS/SENSORSINSTALLED SHALL HAVE INSULATED BACKPLATES.
3. CONTRACTOR SHALL FIELD VERIFY MECHANICAL EQUIPMENT CONDITIONS PRIOR TOFABRICATION AND CONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS.
4. IN AREAS OF ACOUSTICALLY LINED AND DOUBLE WALL DUCTWORK, THE DIMENSIONSLISTED ARE THE FREE AREA WITHIN THE DUCT LINER.
5. IN AREAS WHERE DUCTWORK IS EXPOSED, ROUTE DUCTWORK AS HIGH AS POSSIBLEUNLESS NOTED OTHERWISE ON DRAWINGS.
6. CONTRACTOR SHALL REFER TO CODE COMPLIANCE DRAWING FOR INFORMATION ONRATINGS OF FIRE/SMOKE DAMPERS.
7. PAINT INTERIOR OF DUCT AT RETURN AND EXHAUST DIFFUSERS/GRILLES FLAT BLACK.
8. FLEXIBLE DUCTWORK CORE SHALL BE CLAMPED AND TAPED AT ALL CONNECTIONSAND JOINTS (i.e. AT CONNECTION TO BRANCH DUCTWORK, DIFFUSERS, ETC.). TAPESHALL MEET REQUIREMENTS OF UL181B-FX. IN ADDITION, FLEXIBLE DUCTWORKJACKET SHALL BE TAPED AT ALL CONNECTIONS AND JOINTS WITH TAPE MEETING THEABOVE STATED REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONALINFORMATION.
9. ALL SUPPLY AND RETURN AIR DUCTWORK SHOWN WITH DASHES SHALL BEINTERNALLY LINED DOUBLE WALL DUCTWORK WITH 1" THICK DUCT LINER FOR ROUNDAND RECTANGULAR SUPPLY & RETURN. ALL EXHAUST DUCTWORK SHOWN WITHDASHES SHALL BE ACOUSTICALLY LINED SINGLE WALL DUCTWORK.
10.SEAL ALL JOINTS AIRTIGHT WHERE NEW DUCTWORK CONNECTS TO EXISTING,TYPICAL.
GENERAL HVAC NOTES:
HUMIDISTAT
PARALLEL BLADE DAMPER
OPPOSED BLADE DAMPER
VOLUME DAMPER
FIRE DAMPER (THRU FLOOR)-
FIRE DAMPER (THRU WALL)-
(DYNAMIC)D
(DYNAMIC)
SMOKE DETECTOR
SMOKE DAMPER (THRU FLOOR)-
SMOKE DAMPER (THRU WALL)-
RADIANT FLOOR THERMOSTATR
MOTOR OPERATED DAMPER
MANOMETER
BACK-DRAFT DAMPER
D
SD
M
THERMOSTAT / SENSOR
SD
SD
F/SD
F/SD
COMBINATION FIRE/SMOKE DAMPER(THRU FLOOR)
COMBINATION FIRE/SMOKE DAMPER(THRU WALL)
FIRE DAMPER (THRU FLOOR)-
FIRE DAMPER (THRU WALL)-
(STATIC)
(STATIC)
SUPPLY AIR INDICATOR
RETURN AIR INDICATOR
EXHAUST AIR INDICATOR
HVAC SCHEMATIC SYMBOLS
H
T
ST
ABBREVIATIONS
AFFBFWBODBOG
CABOP
CHCONVCOCWDCWDHWDHWREAEFFCOFDFPGHWRHWSOAPIVRECIRCRWR
RARWS
SANSTSASWTODTOGTOPVVDVTRUHWWCOWH
ABOVE FINISHED FLOORBOILER FEED WATERBOTTOM OF DUCTBOTTOM OF GRILLEBOTTOM OF PIPECOMPRESSED AIRCHILLED GLYCOL RETURNCHILLED GLYCOL SUPPLYCABINET HEATERCONVECTORCLEAN-OUT
DOMESTIC COLD WATERDOMESTIC COLD WATER
DOMESTIC HOT WATERDOMESTIC HOT WATER RETURNEXHAUST AIREXHAUST FANFLOOR CLEAN-OUTFLOOR DRAINFIRE PROTECTIONNATURAL GASHOT WATER RETURN (HEATING)HOT WATER SUPPLY (HEATING)OUTSIDE AIRPOST INDICATOR VALVEDOMESTIC HOT WATER RETURNRADIANT WATER RETURN
RETURN AIRSANITARY WASTESTORM WATERSUPPLY AIRSOFTWATERTOP OF DUCTTOP OF GRILLETOP OF PIPEVENTVOLUME DAMPERVENT THRU ROOFUNIT HEATERWASTEWALL CLEAN-OUTWALL HYDRANT
RADIANT WATER SUPPLY
CGRCGS
FINNED TUBE
FT-15.1Electric Finned Tube, Pressbox 401: Q-Mark Commercial Baseboard Heater, QMKC2515WSeries, 1250 watts, 120/1/60, 10.4 amps, 5’-0” length, with wall mounted line voltage thermostatprovided with the unit and wired by the Electrical Contractor.
FT-15.2Electric Finned Tube, Pressbox 403: Same as FT-15.1.
FT-15.3Electric Finned Tube, Pressbox 405: Q-Mark Commercial Baseboard Heater, QMKC25008WSeries, 2500 watts, 208/1/60, 12.0 amps, 8’-0” length, with wall mounted line voltage thermostatprovided with the unit and wired by the Electrical Contractor.
FT-15.4Electric Finned Tube, Pressbox 407: Same as FT-15.1.
FT-15.5Electric Finned Tube, Pressbox 409: Same as FT-15.1.
EQUIPMENT SCHEDULE:
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2014 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616.796.0201
Holland, Michigan 49423
www.gmb.com
02.09.15 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
3211
M_P
RE
SS
BOX
_CE
NTR
AL_
alan
m.rv
t
M4.20
5-3211
PRESSBOX HVAC PLANS
RS/JT
NE
W S
TA
DIU
M &
CA
MP
US
IMP
RO
VE
ME
NT
S
PU
BLI
C S
CH
OO
LS O
F P
ETO
SK
EY
PE
TO
SK
EY
, M
ICH
IGA
N
NORTH
1/4" = 1'-0"PRESS BOX HVAC PLAN
1. ACTUAL LOCATION OF GRILLES AND DIFFUSERS SHALL BE COORDINATED WITHREFLECTED CEILING PLAN. IF THERE ARE ANY DISCREPANCIES VERIFY FINALLOCATION WITH ARCHITECT/ENGINEER.
2. INSTALL ALL THERMOSTATS/SENSORS AT 48" A.F.F. TO TOP OFTHERMOSTATS/SENSORS, UNLESS NOTED OTHERWISE. ALLTHERMOSTATS/SENSORS INSTALLED SHALL HAVE INSULATED BACKPLATES.
3. CONTRACTOR SHALL FIELD VERIFY MECHANICAL EQUIPMENT CONDITIONS PRIORTO FABRICATION AND CONNECTION OF HYDRONIC AND DUCTWORKCOMPONENTS.
4. IN AREAS OF ACOUSTICALLY LINED AND DOUBLE WALL DUCTWORK, THEDIMENSIONS LISTED ARE THE FREE AREA WITHIN THE DUCT LINER.
5. IN AREAS WHERE DUCTWORK IS EXPOSED, ROUTE DUCTWORK AS HIGH ASPOSSIBLE UNLESS NOTED OTHERWISE ON DRAWINGS.
6. CONTRACTOR SHALL REFER TO CODE COMPLIANCE DRAWING FOR INFORMATIONON RATINGS OF FIRE/SMOKE DAMPERS.
7. PAINT INTERIOR OF DUCT AT RETURN AND EXHAUST DIFFUSERS/GRILLES FLATBLACK.
8. FLEXIBLE DUCTWORK CORE SHALL BE CLAMPED AND TAPED AT ALLCONNECTIONS AND JOINTS (i.e. AT CONNECTION TO BRANCH DUCTWORK,DIFFUSERS, ETC.). TAPE SHALL MEET REQUIREMENTS OF UL181B-FX. IN ADDITION,FLEXIBLE DUCTWORK JACKET SHALL BE TAPED AT ALL CONNECTIONS AND JOINTSWITH TAPE MEETING THE ABOVE STATED REQUIREMENTS. REFER TOSPECIFICATIONS FOR ADDITIONAL INFORMATION.
9. ALL SUPPLY AND RETURN AIR DUCTWORK SHOWN WITH DASHES SHALL BEINTERNALLY LINED DOUBLE WALL DUCTWORK WITH 1" THICK DUCT LINER FORROUND AND RECTANGULAR SUPPLY & RETURN. ALL EXHAUST DUCTWORK SHOWNWITH DASHES SHALL BE ACOUSTICALLY LINED SINGLE WALL DUCTWORK.
10.SEAL ALL JOINTS AIRTIGHT WHERE NEW DUCTWORK CONNECTS TO EXISTING,TYPICAL.
GENERAL HVAC NOTES:
EXHAUST FAN
EF-15.1Exhaust Fan, Storage Building: Cook sidewall propeller exhaust fan, model 24EW620D08, 3,500CFM @ 0.25” S.P., 1/4 HP, 14.2 sones, direct drive, motor side wire guard, disconnect switch,120/1/60, heavy duty aluminum shutter backdraft damper. Interlock intake air damper operation toprove open prior to energizing fan. Energize with 6 hour twist timer, provided and installed byElectrical Contractor.
FINNED TUBE
FT-15.1Electric Finned Tube, Storage Building: Q-Mark Commercial Baseboard Heater, QMKC2573WSeries, 750 watts, 120/1/60, 6.3 amps, 3’-0” length, with wall mounted line voltage thermostatprovided with the unit and wired by the Electrical Contractor.
LOUVERS
L-15.1Intake Air Louver, EF-15.1: Ruskin extruded aluminum drainable blade louver, 48”x42”, 4" depth,model ELF375DX with 37-1/2 deg. blade angle, bird screen, standard recessed frame with sillextension, and custom Kynar 500 finish selected by Architect, with 120v damper. Refer toDrawing A5.10 for dimensional information.
L-15.2Exhaust Air Louver, EF-15.1: Same as L-15.1.
EQUIPMENT SCHEDULE:
IRRIGATIONMETER
PI
PI
2" CW
PIPE STAND, TYP(HSS 2"x2"x1/4" POSTWITH 4"x4"x3/8" TOP AND BASE PLATES)
BYPASS
PRESSUREGAUGE, TYP
GATE VALVE, TYP
2"
FLOOR DRAIN, REFERTO PLUMBING PLANS
FINISH FLOOR
DOMESTICMETER
PI
2" IRRIGATION
3/4", THREADED CAP TERMINATE 16" A.F.F.FOR BLOWDOWN. REFER TO FLOOR PLANFOR LOCATION
HUMIDISTAT
PARALLEL BLADE DAMPER
OPPOSED BLADE DAMPER
VOLUME DAMPER
FIRE DAMPER (THRU FLOOR)-
FIRE DAMPER (THRU WALL)-
(DYNAMIC)D
(DYNAMIC)
SMOKE DETECTOR
SMOKE DAMPER (THRU FLOOR)-
SMOKE DAMPER (THRU WALL)-
RADIANT FLOOR THERMOSTATR
MOTOR OPERATED DAMPER
MANOMETER
BACK-DRAFT DAMPER
D
SD
M
THERMOSTAT / SENSOR
SD
SD
F/SD
F/SD
COMBINATION FIRE/SMOKE DAMPER(THRU FLOOR)
COMBINATION FIRE/SMOKE DAMPER(THRU WALL)
FIRE DAMPER (THRU FLOOR)-
FIRE DAMPER (THRU WALL)-
(STATIC)
(STATIC)
SUPPLY AIR INDICATOR
RETURN AIR INDICATOR
EXHAUST AIR INDICATOR
HVAC SCHEMATIC SYMBOLS
H
T
STABBREVIATIONS
AFFBFWBODBOG
CABOP
CHCONVCOCWDCWDHWDHWREAEFFCOFDFPGHWRHWSOAPIVRECIRCRWR
RARWS
SANSTSASWTODTOGTOPVVDVTRUHWWCOWH
ABOVE FINISHED FLOORBOILER FEED WATERBOTTOM OF DUCTBOTTOM OF GRILLEBOTTOM OF PIPECOMPRESSED AIRCHILLED GLYCOL RETURNCHILLED GLYCOL SUPPLYCABINET HEATERCONVECTORCLEAN-OUT
DOMESTIC COLD WATERDOMESTIC COLD WATER
DOMESTIC HOT WATERDOMESTIC HOT WATER RETURNEXHAUST AIREXHAUST FANFLOOR CLEAN-OUTFLOOR DRAINFIRE PROTECTIONNATURAL GASHOT WATER RETURN (HEATING)HOT WATER SUPPLY (HEATING)OUTSIDE AIRPOST INDICATOR VALVEDOMESTIC HOT WATER RETURNRADIANT WATER RETURN
RETURN AIRSANITARY WASTESTORM WATERSUPPLY AIRSOFTWATERTOP OF DUCTTOP OF GRILLETOP OF PIPEVENTVOLUME DAMPERVENT THRU ROOFUNIT HEATERWASTEWALL CLEAN-OUTWALL HYDRANT
RADIANT WATER SUPPLY
CGRCGS
METER ROOM502
FT-15.1
48"x42"L-15.1
$
48"x42"L-15.2
NEW 6 HR TWIST TIMER PROVIDEDAND INSTALLED BY THE ELECTRICALCONTRACTOR. COORDINATE WITHOTHER ELECTRICAL DEVICES.
22"x22" SA
T
EF-15.13500 CFM
12"x20" ACCESS DOOR
CONTRACTOR SHALL SLOPE THEBOTTOM OF THE PLENUM TOWARDTHE LOUVER TO ALLOW FORDRAINAGE. LOUVER PLENUM SHALLBE SEALED WATER TIGHT ANDSHALL BE PAINTED FLAT BLACK.(TYP.)
FLEX CONNECTOR
12"x20" ACCESS DOOR120v ZERO LEAKAGE DAMPER W/ ACTUATOR
STORAGE BUILDING501
2" CW TO 1'-0" A.F.F., REFER TO SITEUTILITY PLAN FOR CONTINUATION
2" IRRIGATION TO 5'-0" FROM OUTSIDE OF BUILDING,REFER TO SITE UTILITY PLAN FOR CONTINUATION
WH-1
WH-1
3/4" CW
3/4" CW
SHUTOFF & BLOWDOWN VALVE
SHUTOFF & BLOWDOWN VALVE
INSTALL FT-15.1 6" ABVMETER ASSEMBLY
2" VALVE & BOX
3/4" BLOWOUT TO 1'-0"A.F.F. & CAP
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2014 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616.796.0201
Holland, Michigan 49423
www.gmb.com
02.09.15 BIDS & CONSTRUCTION
C:\L
OC
AL
PRO
JEC
TS\5
-321
1M_S
TOR
AG
E-D
UG
OU
TS_C
EN
TRA
L_Je
ffT.rv
t
M5.20
5-3211
STORAGE BUILDING HVACAND PLUMBING PLAN
RS/JT
NE
W S
TA
DIU
M &
CA
MP
US
IMP
RO
VE
ME
NT
S
PU
BLI
C S
CH
OO
LS O
F P
ETO
SK
EY
PE
TO
SK
EY
, M
ICH
IGA
N
M5.20 1" = 1'-0"
1 WATER METER DETAIL
NORTH 1/4" = 1'-0"STORAGE BUILDING HVAC & PLUMBING PLAN
BF
BF
BF
BF BFBF
BF
BF
BF BF
1. CONNECT TO EXTERIOR POTABLE WATER SERVICES. ROUTE PIPING TO 1'-0"A.F.F.
2. COORDINATE ROUTING OF PLUMBING PIPING WITH ALL TRADES. ALLSANITARY PIPING TO BE INSTALLED & VENTED PER ALL APPLICABLE STATE &LOCAL CODES.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALLPIPE SLEEVES THRU FOUNDATION WALLS AS NECESSARY.
4. PROVIDE STOPS AT ALL FIXTURES, ROUTE HW & CW PIPING UP & DOWN ASREQUIRED IN WALLS TO ELEVATION FOR PIPING CONNECTION TO FIXTURES
5. PROVIDE CLEAN-OUTS AT ALL SANITARY BRANCH RISERS IN BASE OF WALL.PLACE CLEAN-OUTS MINIMUM OF 10" A.F.F.
6. GAS PIPING SHALL CONFORM TO FIRE MARSHALL REQUIREMENTS AND NFPA54
7. PROVIDE CIRCUIT SETTER BALANCING VALVES AT DOMESTIC HOT WATERRETURN LINE JUNCTIONS TO ALLOW CONTRACTOR TO BALANCE RETIRNWATER FLOW.
8. ROUTE CONDENSATE DOWN WALL TO FLOOR DRAIN OR SS-1, UNLESSNOTED OTHERWISE. PROVIDE AIR GAP, COORDINATE ROUTING WITH OTHERTRADES.
9. SLOPE CONDENSATE DRAIN PIPING 1/4"/FT WHEN POSSIBLE, 1/8"/FTMINIMUM.
GENERAL PLUMBING NOTES:
LEGENDS & ABBREVIATIONS
HW PIPING
VENT PIPINGV
DOMESTIC COLD WATERDOMESTIC HOT WATERDOMESTIC HOT WATER RETURN
DN. DOWNWH-1 WALL HYDRANTWC-1 WATER CLOSETS-1 SINKLAV-1 LAVATORYEQ. EQUIPMENTTYP. TYPICAL
CW PIPING
CLEAN OUTWALL CLEAN OUT
C.O.W.C.O.I.E.FDSAN.
V.T.R.
INVERT ELEVATIONFLOOR DRAINSANITARY
VENT THRU ROOF
G NATURAL GAS (ABOVE GROUND)
G NATURAL GAS
U/G UNDERGROUND
STORM PIPING (ABOVE GROUND)
SANITARY PIPING (UNDERGROUND)RECIRC. PIPING
CWHWRECIRC.
WALL HYDRANT/HOSE BIBB
A.W. ACID WASTE
TEMPERED WATERT.W.GV GAS SLEEVE VENT
FIXTURE
MINIMUM SIZE CONNECTION
CW HW SAN VENT
WATER CLOSET(FLUSH VALVE)
URINAL (FLUSH VALVE)
LAVATORY
SINK
SHOWER
MOP SERVICE BASIN
WASHING MACHINE OUTLETBOX (WITH STANDPIPE)
ICE MAKER OUTLET BOX
WALL HYDRANT/ HOSE BIBB
ELECTRIC WATER COOLER
DRINKING FOUNTAIN
FLOOR DRAIN
FLOOR DRAIN(MECHANICAL ROOM)
1-1/4" ---- 4" 2"
3/4" ---- 2" 1-1/2"
1-1/4"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
----
----
1-1/4"
1-1/4"
1-1/2"
2"4"--------
1/2" 1/2" 1-1/4"
1/2" 1/2" 1-1/2"
2"1/2" 1/2"
3/4" 3/4" 3"
3/4" 3/4" 3" (TRAP)
1/2" --------
3/4" --------
1/2" ----
1/2" ----
1-1/4"
1-1/4"
3"--------
NOTE:CONTRACTOR SHALL INSTALL WATER HEATER PERMANUFACTURER'S RECOMMENDATIONS. SCHEMATICIS GENERAL IN NATURE AND MAY OR MAY NOTREFLECT ACTUAL INSTALLATION REQUIREMENTS.
ET-1, EXPANSIONTANK
1.1/2" CW & 1.1/2" HW(140°), SEE PLUMBINGPLAN THIS DRAWING FORCONTINUATION
PP-1, RECIRC.PUMP
ROUTE T/P RELIEFDOWN TO F.D.
WATER HEATERCAPACITY (GAL.)
EXPANSION TANKCAPACITY (GAL.)
NOTE:
1. BASED ON STATE INDUSTRIES EXPANSION TANK
2. EXPANSION TANK CAPACITIES ARE BASED ON A MINIMUM GALLON REQUIREMENT
30 40 50 65 70 80 100
2 2 2 2.6 3 3.2 4
NOTE: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOWPREVENTER, CHECK VALVE OR WATER METER WITH CHECKVALVE, PROVIDE AND INSTALL EXPANSION TANK AND 100PSI RELIEF VALVE IN COLD WATER LINE TO WATER HEATER
EXPANSION TANK SIZING SCHEDULE
DWH-1, WATERHEATER
4" HOUSEKEEPINGPAD
2.1/2" CW, 1.1/2" HW& 1/2" RECIRC.
1.1/2" H&C
1.1/2" H&C
WC-2AWC-2A
1.1/2" CW
LAV-1ALAV-1A
SH-3A
SH-3
SH-2ASH-2
SH-1A
SH-1A
WC-2A WC-2A
WC-2 U-1A
LAV-1A LAV-1A
LAV-1 LAV-1
WH-1
3/4" CW
3/4" CWROUTE 3/4" H&C DOWN IN CHASE TO 1'-6" A.F.F. WITH1/2" H&C STUB FOR EACH LAV. PIPE MIXING VALVEPER MANFACTURER'S RECOMMENDATION. w/1.1/2"SAN IN WALL TO 1'-6" A.F.F. EXTEND 1.1/2" VENTTO ABOVE CEILING AS SHOWN(TYP.)
ROUTE 2" CW DOWN IN CHASEWITH 1" CW STUB TO EACH WC& 3/4" CW STUB TO U-1A
ROUTE 3/4" H&C DOWN IN CHASE TO 1'-6" A.F.F.WITH 1/2" H&C STUB FOR EACH LAV. PIPE MIXINGVALVE PER MANFACTURER'S RECOMMENDATION.w/1.1/2" SAN IN WALL TO 1'-6" A.F.F. EXTEND 1.1/2"VENT TO ABOVE CEILING AS SHOWN(TYP.)
ROUTE 1.1/2" CW DOWN IN CHASEWITH 1" CW STUB TO EACH WC
3/4" CW, 3/4" HW& 1/2" RECIRC.
2" CW, 1.1/4" HW& 1/2" RECIRC.
WH-2WH-2
LOCKER ROOM26
TOILET / SHOWER20
PE OFFICE21
TOILET22
SHOWER23
LOCKER ROOM24 LOCKER ROOM
43
OFFICIALS ROOM41
CUST25
CUST42
PE OFFICE45
TOILET38
SHOWER39
STORAGE47
LOCKER ROOM44
TOILET / SHOWER46
CORRIDOR112
CORRIDOR101
OFFICE111
OFFICE102
TOILET / SHOWER103
TOILET / SHOWER110
MENS LOCKER ROOM109SHOWER ROOM
105
SHOWER ROOM108
TOILET106
TOILET107
WOMENS LOCKERROOM
104
3"FD-3
3"FD-3
3"FD-3
3"FD-3
3"FD-33"FD-3
4" SANITARY, CONNECT TO 4" SANITARY 5'-0" FROMOUTSIDE OF BUILDING. REFER TO SITE UTILITY PLANFOR CONTINUATION
C.O. w/FROST SLEEVE
INV. EL. 755.35'
3"SAN.
3/4" CW
2"CW
W.C.O.3" SAN.3" SAN.
4" SAN.
3" SAN.
W.C.O.
3" SAN.
3" SAN.3" SAN.
3" SAN.3" SAN. W.C.O.
3"FD-1 3"FD-1
W.C.O.
3" SAN.
3" SAN.
3" SAN.3/4" H&C
3" SAN.
DWH-1
3" SAN.
EXIST'G x" CW
NEW 2" CW
CONNECT TO EXIST'G CW MAIN. CONTRACTORSHALL FIELD VERIFY SIZE & LOCATION
SS-1
3/4" H&C
1/2" H&C
4" SAN.
3/4"H&C
1/2" H&C
3" SAN.
C.O.
4" SAN. W.C.O.
3" SAN.
4" SAN.
1" H&C
1" H&C
3" SAN.
3"FD-3
3" SAN.
4" SAN.
2"V-3"VTR
4"RD
4"RD
4" STORM(C.I.), ROUTE ASHIGH AS POSSIBLE
4" STORM(C.I.),ROUTE AS HIGHAS POSSIBLE
6" STORM, CONNECT TO 6" STORM 5'-0" FROMOUTSIDE OF BUILDING. REFER TO SITE UTILITYPLAN FOR CONTINUATION
INV. EL. 7
55.35'
6" STORM RISERw/W.C.O. AT BASE
2"V
2"V
3"RD
3" STORM(C.I.), ROUTE ASHIGH AS POSSIBLE
PP-3
1.1/2" CW & 3/4" HW1.1/2" CW & 3/4" HW
1.1/2" CW, 1.1/2" HW& 1/2" RECIRC. REFERTO DET. 1/P1.10
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2014 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616.796.0201
Holland, Michigan 49423
www.gmb.com
02.09.15 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
3211
P_L
OC
KE
R R
OO
M_C
EN
TRA
L_do
nald
g.rv
t
P1.10
5-3211
LOCKER ROOM ADDITIONPLUMBING PLAN
NE
W S
TA
DIU
M &
CA
MP
US
IMP
RO
VE
ME
NT
S
PU
BLI
C S
CH
OO
LS O
F P
ETO
SK
EY
PE
TO
SK
EY
, M
ICH
IGA
N
NOT TO SCALEP1.101 WATER HEATER
NORT
H
1/8" = 1'-0"FIRST FLOOR LOCKER ROOM ADDITION PLUMBING PLAN
BF BF
BF
BFBF BF
BF
BF
DN
BFBF
BF
BF
BFBF
BF
DWH-1 PP-2
ROUTE 1/2" H&C DOWN IN WALL TO 2'-0" A.F.F. FORLAV. PIPE MIXING VALVE PER MANFACTURER'SRECOMMENDATION. w/1.1/2" SAN IN WALL TO 1'-6"A.F.F. EXTEND 1.1/2" VENT TO ABOVE CEILING ASSHOWN (TYP.)
STORAGE210
STORAGE212
TEAM ROOM209
TRAINING203
OFFICIALS ROOM202
CORRIDOR205
COACH TOILET /SHOWER
207
TOILET206
TOILET208
ELECTRICAL211
C.O.
C.O.
C.O.
C.O.
S-1A
DF-1ADF-1ASS-1
SH-1A
LAV-1A
WC-1A WC-1WC-1AWC-1A
U-1ALAV-1ALAV-1A
3"FD-3
3" FD-3A
WH-3
6"PD6"PD
6"PD
2"SAN
2" FORCED SAN, REFER TO CONCESSIONS -SECOND FLOOR PLUMBING PLAN, THIS SHEETFOR CONTINUATION
3" SAN
4" SAN
4" V
2" VENT UP, REFER TO CONCESSIONS -SECOND FLOOR PLUMBING PLAN, THISSHEET, FOR CONT.
V
V V
V
V
VV
WATERMETER
8" STORM, CONNECT TO 8" STORM 5'-0"FROM OUTSIDE OF BUILDING. REFER TOSITE UTILITY PLAN FOR CONTINUATION
4" CW, CONNECT TO 4" CW 5'-0" FROMOUTSIDE OF BUILDING. REFER TO SITEUTILITY PLAN FOR CONTINUATION
C.O. w/ FROST SLEEVE
I.E. = 759.00'
3" CW, 1.1/2" HW,& 3/4" RECIRC.
2.1/2" CW, 1.1/4" HW,& 3/4" RECIRC.
1.1/2" CW1/2" HW
1" CW
4" SAN
4" SAN
3" SAN1.1/2" V
1.1/2" V
2" V
2" V
4" SAN 4" SAN
2" V
1.1/2" V
3" CW, 1.1/2" HW,& 3/4" RECIRC.
3" CW, 1.1/2" HW, & 3/4" RECIRC. UP.REFER TO CONCESSIONS - SECONDFLOOR PLUMBING PLAN, DRAWINGP2.20 FOR CONTINUATION
3" SAN
2" SAN4" SAN
1.1/2" CW& 1/2" HW
3"FD-3 3"FD-33"FD-3 1.1/2" CW, 1/2" HW,
& 3/4" RECIRC.
1.1/4" CW & 4" SANTO WC. (TYP.)
8" STORM
6" STORM 6" STORM
REFER TODETAIL 1/P2.10.
1/2" CW DN TOICE MACHINE.
1.1/4" CW CONNECT TO 1.1/4" CW 5'-0"FROM BUILDING.REFER TO SITE UTILITYPLANS FOR CONTINUATION. 1.1/4" CW
I.E. = 759.50'
DF-2ADF-2A W.C.O.
W.C.O.
3"1/2" CW1/2" CW
1/2" CW
3/4"H&C
3" SAN.
4" VALVE & BOXTHREADED CAP,TERMINATE 16" A.F.F.
3/4"
SECURE STORAGE251
CONCESSIONS250
STORAGE253CUST
252
UTILITY254
GENERAL STORAGE255
MENS257
WOMENS258
CUST259
WC-1A
LAV-1A
LAV-1A
S-2A
SS-1
WH-1
C.O.
6"PD 6"PD 6"PD
REFER TO P2.20 FORWORK IN THIS AREA.
REFER TO P2.20 FORWORK IN THIS AREA.
2" FORCED SAN, REFER TO TEAMROOM - FIRST FLOOR PLUMBING PLAN,THIS SHEET, FOR CONTINUATION
2" VENT DOWN, REFER TO TEAMROOM - FIRST FLOOR PLUMBINGPLAN, THIS SHEET, FOR CONT.
ROUTE 1/2" H&C DOWN IN WALL TO 2'-0" A.F.F. FORSINK. PIPE MIXING VALVE PER MANFACTURER'SRECOMMENDATION. w/1.1/2" SAN IN WALL TO 1'-6"A.F.F. EXTEND 2" VENT TO 3" V.T.R.
ROUTE 1/2" H&C DOWN IN WALL TO 2'-0" A.F.F. FORLAV. PIPE MIXING VALVE PER MANFACTURER'SRECOMMENDATION. w/1.1/2" SAN IN WALL TO 1'-6"A.F.F. EXTEND 1.1/2" VENT TO ABOVE CEILING ASSHOWN (TYP.)
1.1/4" CW & 4" SAN TO WC.
ROUTE 1/2" H&C DOWN IN WALL TO 2'-0" A.F.F. FORLAV PIPE MIXING VALVE PER MANFACTURER'SRECOMMENDATION. w/1.1/2" SAN IN WALL TO 1'-6"A.F.F. EXTEND 1.1/2" VENT TO ABOVE CEILING ASSHOWN (TYP.)
C.O.
3" FD-33" FD-3
4" SAN.
4" SAN.
3" SAN3" SAN
2" FORCED SAN
4" SANITARY, CONNECT TO 4" SANITARY 5'-0" FROM OUTSIDE OF BUILDING. REFER TOSITE UTILITY PLAN FOR CONTINUATION
C.O. w/ FROST SLEEVE
I.E. = 773.5'
V
2" V, 4" SAN, 1.1/2" CW, 1" HW, 3/4" RECIRC.REFER TO P2.20 FOR CONT.
4" SAN.1.1/2" CW1/2" HW
1" CW, 1" HW,& 3/4" RECIRC.
3/4" CW
3/4" H&C
2"SAN
1/2"H&C
1.1/2"V-3"VTR
3/4" HW DOWNTO POT FILLER
3/4"HW
2" FORCED SAN
1. CONNECT TO EXTERIOR POTABLE WATER SERVICES. ROUTE PIPING TO 1'-0"A.F.F.
2. COORDINATE ROUTING OF PLUMBING PIPING WITH ALL TRADES. ALLSANITARY PIPING TO BE INSTALLED & VENTED PER ALL APPLICABLE STATE &LOCAL CODES.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALLPIPE SLEEVES THRU FOUNDATION WALLS AS NECESSARY.
4. PROVIDE STOPS AT ALL FIXTURES, ROUTE HW & CW PIPING UP & DOWN ASREQUIRED IN WALLS TO ELEVATION FOR PIPING CONNECTION TO FIXTURES
5. PROVIDE CLEAN-OUTS AT ALL SANITARY BRANCH RISERS IN BASE OF WALL.PLACE CLEAN-OUTS MINIMUM OF 10" A.F.F.
6. GAS PIPING SHALL CONFORM TO FIRE MARSHALL REQUIREMENTS AND NFPA54
7. PROVIDE CIRCUIT SETTER BALANCING VALVES AT DOMESTIC HOT WATERRETURN LINE JUNCTIONS TO ALLOW CONTRACTOR TO BALANCE RETIRNWATER FLOW.
8. ROUTE CONDENSATE DOWN WALL TO FLOOR DRAIN OR SS-1, UNLESSNOTED OTHERWISE. PROVIDE AIR GAP, COORDINATE ROUTING WITH OTHERTRADES.
9. SLOPE CONDENSATE DRAIN PIPING 1/4"/FT WHEN POSSIBLE, 1/8"/FTMINIMUM.
GENERAL PLUMBING NOTES:
LEGENDS & ABBREVIATIONS
HW PIPING
VENT PIPINGV
DOMESTIC COLD WATERDOMESTIC HOT WATERDOMESTIC HOT WATER RETURN
DN. DOWNWH-1 WALL HYDRANTWC-1 WATER CLOSETS-1 SINKLAV-1 LAVATORYEQ. EQUIPMENTTYP. TYPICAL
CW PIPING
CLEAN OUTWALL CLEAN OUT
C.O.W.C.O.I.E.FDSAN.
V.T.R.
INVERT ELEVATIONFLOOR DRAINSANITARY
VENT THRU ROOF
G NATURAL GAS (ABOVE GROUND)
G NATURAL GAS
U/G UNDERGROUND
STORM PIPING (ABOVE GROUND)
SANITARY PIPING (UNDERGROUND)RECIRC. PIPING
CWHWRECIRC.
WALL HYDRANT/HOSE BIBB
A.W. ACID WASTE
TEMPERED WATERT.W.GV GAS SLEEVE VENT
FIXTURE
MINIMUM SIZE CONNECTION
CW HW SAN VENT
WATER CLOSET(FLUSH VALVE)
URINAL (FLUSH VALVE)
LAVATORY
SINK
SHOWER
MOP SERVICE BASIN
ICE MAKER OUTLET BOX
WALL HYDRANT/ HOSE BIBB
DRINKING FOUNTAIN
FLOOR DRAIN
1-1/4" ---- 4" 2"
3/4" ---- 2" 1-1/2"
1-1/4"
1-1/2"
1-1/2"
1-1/2"
----
----
1-1/4"
1-1/2"
1/2" 1/2" 1-1/4"
1/2" 1/2" 1-1/2"
2"1/2" 1/2"
3/4" 3/4" 3"
1/2" --------
3/4" --------
1/2" ---- 1-1/4"
3"--------
NOTE:CONTRACTOR SHALL INSTALL WATER HEATER PERMANUFACTURER'S RECOMMENDATIONS. SCHEMATICIS GENERAL IN NATURE AND MAY OR MAY NOTREFLECT ACTUAL INSTALLATION REQUIREMENTS.
ET-1, EXPANSIONTANK
1" CW & 1" HW(140°),SEE PLUMBING PLANTHIS DRAWING FORCONTINUATION
PP-1,RECIRC.PUMP
ROUTE T/P RELIEFDOWN TO F.D.
WATER HEATERCAPACITY (GAL.)
EXPANSION TANKCAPACITY (GAL.)
NOTE:
1. BASED ON STATE INDUSTRIES EXPANSION TANK
2. EXPANSION TANK CAPACITIES ARE BASED ON A MINIMUM GALLON REQUIREMENT
30 40 50 65 70 80 100
2 2 2 2.6 3 3.2 4
NOTE: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOWPREVENTER, CHECK VALVE OR WATER METER WITH CHECKVALVE, PROVIDE AND INSTALL EXPANSION TANK AND 100PSI RELIEF VALVE IN COLD WATER LINE TO WATER HEATER
EXPANSION TANK SIZING SCHEDULE
DWH-1,WATER HEATER
4" HOUSEKEEPING PAD
IRRIGATIONMETER
PI
PI
4" CW
PIPE STAND, TYP(HSS 2"x2"x1/4" POSTWITH 4"x4"x3/8" TOP AND BASE PLATES)
BYPASS
PRESSUREGAUGE, TYP
GATE VALVE, TYP
3" CW
FLOOR DRAIN, REFERTO PLUMBING PLANS
FINISH FLOOR
REFER TO DWG P2.10
DOMESTICMETER
PI
1.1/4" IRRIGATION
3/4", THREADED CAP TERMINATE 16" A.F.F.FOR BLOWDOWN. REFER TO FLOOR PLANFOR LOCATION
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2014 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616.796.0201
Holland, Michigan 49423
www.gmb.com
02.09.15 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
3211
P_C
ON
CE
SS
ION
S_C
EN
TRA
L_do
nald
g.rv
t
P2.10
5-3211
CONCESSION PLUMBINGPLANS
RLS / TWS
NE
W S
TA
DIU
M &
CA
MP
US
IMP
RO
VE
ME
NT
S
PU
BLI
C S
CH
OO
LS O
F P
ETO
SK
EY
PE
TO
SK
EY
, M
ICH
IGA
N
NORT
H
1/8" = 1'-0"TEAM ROOM - FIRST FLOOR PLUMBING PLAN
NORT
H
1/8" = 1'-0"CONCESSIONS - SECOND FLOOR PLUMBING PLAN
NOT TO SCALEP2.101 WATER HEATER DETAIL
NOT TO SCALEP2.102 WATER METER DETAIL
BFBF
BF
BFBFBF
BFBF
BF
MENS257
WOMENS258
W.C.O.
C.O.
C.O.
C.O.
W.C.O.
W.C.O.
DF-3 DF-3A
SS-1
WC-1A
WC-1
WC-1
WC-1
WC-1
WC-1
WC-1
U-1
U-1
U-1
U-1
U-1A
LAV-1A
WC-1 WC-1
WC-1A
WC-1
WH-1
WH-2
WH-2
2.1/2" CW
2.1/2" CW
LAV-1A
LAV-1
LAV-1 LAV-1
LAV-1
LAV-1LAV-1
LAV-1LAV-1
WC-1 WC-1
WC-1 WC-1
WC-1 WC-1
WC-1
WC-1
WC-1
WC-1
WC-1
3" FD-3
2" V, 4" SAN, 1.1/2" CW, 1" HW, 3/4" RECIRC.REFER TO P2.10 FOR CONT.
6" SANITARY, CONNECT TO 6" SANITARY 5'-0"FROM OUTSIDE OF BUILDING. REFER TO SITEUTILITY PLAN FOR CONTINUATION
C.O. w/ FROST SLEEVE
I.E. = 773.50'
1" CW & 4" SAN TOWC (TYP.)
1" CW & 4" SANTO WC (TYP.)
1" CW & 4" SANTO WC (TYP.)
6" SAN
4" SAN 4" SAN
4" SAN
4" SAN
4" SAN3" SAN2" SAN
4" SAN
3" FD-3
2" V
V V
V
V
VVV
V
V
2" CW
3/4" CW AND 2" SAN. TOURNALS. EXTEND 1.1/2"VENT TO ABOVE CEILINGAS SHOWN. (TYP.)
2" CW
1.1/2" CW
3/4" CW
2" V
2" V
2" V
2" V
2" SAN
1" CW & HW HEADERS DN TO LAVATORIES AND WALLHYDRANTS. PROVIDE AND INSTALL SHUTOFF VALVESAND ACCESS PANEL IN DROP.
ROUTE 1/2" H&C FROM 1" HEADERS TO 2'-0" A.F.F. FORLAV. PIPE MIXING VALVE PER MANFACTURER'SRECOMMENDATION. w/1.1/2" SAN IN WALL TO 1'-6"A.F.F. EXTEND 1.1/2" VENT TO ABOVE CEILING ASSHOWN (TYP.)
3/4" CW TOWALL HYDRANT(TYP.)
2"V-3"VTR
3" CW, 1.1/2" HW, & 3/4" RECIRC. DOWN.REFER TO TEAM ROOM, DRAWING P2.10FOR CONTINUATION
2" V
2" V
2" V
3" SAN
3" SAN
1.1/2" V2" V
4" SAN
3" FD-3
3" SAN
4" SAN
4" SAN
4" SAN
4" SAN
3" FD-3
3" SAN
4" SAN
2.1/2" CW
2" CW
2" CW
2.1/2" CW
2" CW
2" CW
2" CW
2" CW
2.1/2" CW
3" CW, 1.1/2" HW,& 3/4" RECIRC.
2.1/2" CW, 1.1/2" HW,& 3/4" RECIRC.
1" CW3/4" HW
1" CW3/4" HW
3/4" CW
2.1/2" CW, 1" HW,& 3/4" RECIRC.
LAV-1A LAV-1A
1/2" CW2" SAN.
2"SAN.
4"
4"
4"
4"
4"
4"
4"
1. CONNECT TO EXTERIOR POTABLE WATER SERVICES. ROUTE PIPING TO 1'-0"A.F.F.
2. COORDINATE ROUTING OF PLUMBING PIPING WITH ALL TRADES. ALLSANITARY PIPING TO BE INSTALLED & VENTED PER ALL APPLICABLE STATE &LOCAL CODES.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALLPIPE SLEEVES THRU FOUNDATION WALLS AS NECESSARY.
4. PROVIDE STOPS AT ALL FIXTURES, ROUTE HW & CW PIPING UP & DOWN ASREQUIRED IN WALLS TO ELEVATION FOR PIPING CONNECTION TO FIXTURES
5. PROVIDE CLEAN-OUTS AT ALL SANITARY BRANCH RISERS IN BASE OF WALL.PLACE CLEAN-OUTS MINIMUM OF 10" A.F.F.
6. GAS PIPING SHALL CONFORM TO FIRE MARSHALL REQUIREMENTS AND NFPA54
7. PROVIDE CIRCUIT SETTER BALANCING VALVES AT DOMESTIC HOT WATERRETURN LINE JUNCTIONS TO ALLOW CONTRACTOR TO BALANCE RETIRNWATER FLOW.
8. ROUTE CONDENSATE DOWN WALL TO FLOOR DRAIN OR SS-1, UNLESSNOTED OTHERWISE. PROVIDE AIR GAP, COORDINATE ROUTING WITH OTHERTRADES.
9. SLOPE CONDENSATE DRAIN PIPING 1/4"/FT WHEN POSSIBLE, 1/8"/FTMINIMUM.
GENERAL PLUMBING NOTES:
LEGENDS & ABBREVIATIONS
HW PIPING
VENT PIPINGV
DOMESTIC COLD WATERDOMESTIC HOT WATERDOMESTIC HOT WATER RETURN
DN. DOWNWH-1 WALL HYDRANTWC-1 WATER CLOSETS-1 SINKLAV-1 LAVATORYEQ. EQUIPMENTTYP. TYPICAL
CW PIPING
CLEAN OUTWALL CLEAN OUT
C.O.W.C.O.I.E.FDSAN.
V.T.R.
INVERT ELEVATIONFLOOR DRAINSANITARY
VENT THRU ROOF
G NATURAL GAS (ABOVE GROUND)
G NATURAL GAS
U/G UNDERGROUND
STORM PIPING (ABOVE GROUND)
SANITARY PIPING (UNDERGROUND)RECIRC. PIPING
CWHWRECIRC.
WALL HYDRANT/HOSE BIBB
A.W. ACID WASTE
TEMPERED WATERT.W.GV GAS SLEEVE VENT
FIXTURE
MINIMUM SIZE CONNECTION
CW HW SAN VENT
WATER CLOSET(FLUSH VALVE)
URINAL (FLUSH VALVE)
LAVATORY
SINK
SHOWER
MOP SERVICE BASIN
ICE MAKER OUTLET BOX
WALL HYDRANT/ HOSE BIBB
DRINKING FOUNTAIN
FLOOR DRAIN
1-1/4" ---- 4" 2"
3/4" ---- 2" 1-1/2"
1-1/4"
1-1/2"
1-1/2"
1-1/2"
----
----
1-1/4"
1-1/2"
1/2" 1/2" 1-1/4"
1/2" 1/2" 1-1/2"
2"1/2" 1/2"
3/4" 3/4" 3"
1/2" --------
3/4" --------
1/2" ---- 1-1/4"
3"--------
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2014 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616.796.0201
Holland, Michigan 49423
www.gmb.com
02.09.15 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
3211
P_C
ON
CE
SS
ION
S_C
EN
TRA
L_do
nald
g.rv
t
P2.20
5-3211
ENLARGED PLUMBING PLANS
NE
W S
TA
DIU
M &
CA
MP
US
IMP
RO
VE
ME
NT
S
PU
BLI
C S
CH
OO
LS O
F P
ETO
SK
EY
PE
TO
SK
EY
, M
ICH
IGA
N
NORT
H
1/4" = 1'-0"ENLARGED CONCESSIONS - SECOND FLOOR PLUMBING PLAN