Overvoltage Protection for low-voltage supplies
B.1
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Class I Overvoltage Protection B.2 - B.3with sparkover gaps B.4 - B.9with high-power varistors B.10 - B.11Overvoltage Protection, combination arrester B.12 - B.15
Class II Overvoltage Protectionwith varistors B.16 - B.25
Class III Overvoltage Protectionwith varistors B.26 - B.31
Plug-in Overvoltage Protection B.32 - B.35
Mains filter B.36 - B.39
Overvoltage Protection installation instructionsClass I, II, III B.40 - B.43
Examples of applications for TN, TT and IT systems B.44 - B.45
B.2
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B
Overvoltage Protection class I with spark gap
Class I, sparkover gap
Weidmüller series PU 1 TSG and PU B(class I), PU x C (class II) plus PU D andPO D (class III) overvoltage protectiondevices lower the overvoltage protectionlevel to below the limits prescribed by theinsulation coordination to DIN VDE 0110.This means that the entire system issubjected to less interference.
The coordination of the arresters isachieved by technical means. This meansthat decoupling between classes I, II andIII is not necessary.
6.0 kV
4.0 kV
2.0 kV
1.5 kV
Electrical system
Power supply
Data interfacesBus lines
I/O lines
Design surge voltage
B.3
B
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection class I with spark gap
Varistor arresters up to 100 kA for diverse voltages PU x C
Varistor arresters up to 100 kA for diverse voltages,
with signalling contact PU x CR
Replacement varistor to suit rated voltage PU 0 C
Page B.17-24
Page B.17-24
Page B.17-24
Class I, high-power varistor Class II, varistor Class III, varistor
Sparkover gaps, triggered and enclosed, 35/50 kA PU 1 TSG
Sparkover gaps, triggered 50 kA PU 1 TSG+
Triggered sparkover gaps, 100 kA PU 1 TSG 100 kA
High-power varistors, 20/25 kA PU 3 B, PU 4 B
High-power varistors, 20/25 kA, with signalling contact PU 3 BR, PU 4 BR
Replacement arrester, high-power varistor PU 0 B
Combined overvoltage protection PU COMBI I + II
Page B.7
Page B.6
Page B.8
Page B.11
Page B.11
Page B.11
Page B.14/15
Single-phase arresters for diverse voltages,
with signalling contact PU D, PU DS
Three-phase arresters with signalling contact PU 3 D
Schuko plug-in overvoltage protector PU D ZS
Page B.27-29
Page B.30
Page B.33-35
Lightning arresters
Overvoltage arresters
Lightning arresters
for insulation coordination to IEC 664 and DIN VDE 0110
Overvoltage Protection for low-voltage supplies
B.4
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B
Weidmüller Übergabeelemente
Class I Overvoltage Protection with sparkover gaps
gap is tripped, a safety clearance of min. 100 mm must be maintained between this and any current-conductingcomponents.
The maximum permissible operating voltage Uc is 330 or 440 Vac. Decoupling from downstream class II (C) arresters for470 V is unnecessary because triggered sparkover gaps with alow sparkover voltage are used.
Please follow the installation instructions.
Checking operation, maintenance and approvals
A visual check is necessary to ensure that PU 1 TSG and PU 1TSG+ overvoltage protection components are operatingcorrectly. Besides signalling a mains power failure, the lampilluminates above 120 Vac to indicate the failure of the firingelectronics. It is advisable to check frequently during stormyweather.
The use of triggered sparkover gaps achieves a very lowprotection level of < 1.5 kV with high discharge currents.Depending on the cross-section of the line, the PU 1 TSG mustbe protected with a fuse of max. 125 A gL, the PU 1 TSG+max. 250 A gL.
The connection is designed for the following cross-sections:
– solid wire: 10...35 mm2,
– multistrand wire: 10...25 mm2.
The operating temperature range is –40 °C ... +85 °C.
The PU 1 TSG lightning arresters have UL and KEMA approvaland are hence suitable for use worldwide.
Lightning conductors with spark gap for lightingprotection equipotential bonding Overvoltage Protectionclass I (B charge eliminators)
According to the requirements of class B (DIN VDE 0675 part 6(draft 11.89)/A1: 3/96) and class I as per IEC 61643-1 (1/02),the lightning conductor at the transfer from interface 0 to 1 (as per IEC 1312-1) is used as the lightning protectionequipotential bonding. In combination with several lightningprotectors, the overvoltage protection is used in the mainsforms TN, TT and IT.
When lightning strikes, the triggered air gap protector providesthe necessary equipotential bonding between the building light-ning protection and the earthing system of the power supply.
The use of a sparkover gap satisfies the inspection require-ments for class B overvoltage protection systems according tothe VDEW (Association of German Power Stations) directive(1st ed., 1998).
Electrical connection for building installation
The PU 1 TSG 35 kA class I lightning arrester is connectedbetween the phase conductors (L1, L2, L3) and the N/PE. AWeidmüller PU 1 TS G 50 kA is used to provide the N-PEsparkover gap. The lines for this should be kept as short aspossible.
The triggered and non-blowout PU 1 TSG devices can beclipped to TS 35 rails in electrical cabinets or distributionboards. The maximum permissible operating voltage Uc is 260 Vac. Decoupling from downstream class II (C) arresters isunnecessary because triggered sparkover gaps with a lowsparkover voltage are used.
Please follow the installation instructions.
Electrical connection for industrial installations
The PU 1 TSG+ 50 kA/330 V or 440 V class I lightning arresteris connected between the phase conductors (L1, L2, L3) andthe N/PE. A Weidmüller PU 1 TSG 50 kA is used to provide theN-PE sparkover gap. The lines for this should be kept as shortas possible.
The triggered and blowout PU 1 TSG+ 50 kA devices can beclipped to TS 35 rails in electrical cabinets or distributionboards. Owing to the emissions given off when the sparkover
Dimensioned drawing PU 1 TSG+Overall width 36 mm
Accessories:QB 18-6
BZ 18L1, L2, L3, N, PE
BZ 18PE, PE, PE, PE
QB 18-4
Dimensioned drawing PU 1 TSG+Overall width 18 mm
B
Overvoltage Protection for low-voltage supplies
B.5
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
In contrast to conventional sparkover gaps, the Weidmüller PU1 TSG+ and PU 1 TSG sparkover gaps operate with electronictriggering. This fires the sparkover gap at such an early pointthat the downstream class II (Pu x C) arresters are relieved.Decoupling from downstream class II (C) arresters isunnecessary because triggered sparkover gaps with a lowsparkover voltage are used.
Protection in the TN-S-system
Protecion in the TT-system
The PU 1 TSG+ and PU 1 TSG differ in terms of the followcurrent extinction. The PU 1 TSG+ distributes the arc dropvoltage over several chambers. As soon as the total arc dropvoltage exceeds the mains voltage flowing, the follow current is extinguished. In the PU 1 TSG the follow current extinctiontakes place at the next current zero of the mains voltage.
Choke or conductor
Lightning conductor class I
Overvoltage chargeeliminator class II
Lightning conductor class I
Overvoltage chargeeliminator class II
Integrated electronic trigger component
B.6
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class I with triggered spark gap
Class I lightning arrester
• encapsulated version
• no decoupling necessary thanks to trigger elec-tronics
• suitable for networks with high short-circuit cur-rents
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
lightening test voltage imp (10/350µs)
Specific energy, per path
Short-circuit current extinction without back-up fuse
Short-circuit strength at max. back-up fuse
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals le E198315
KEMA
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 1TSG+ 50kA/0.9kV-330V
for use in industrial networks
L / NL / N
TriggerTrigger
Technical specification
330V d voltage (AC)
330V ating voltage Uc (ac), max.
Class I ment class acc. to IEC 61643-1
50 kA with 25 As charge imp (10/350µs)
625kJ/M rgy, per path
50 kA / 50 Hz current extinction without back-up fuse
25 kAeff gth at max. back-up fuse
< 150 ns me
250 A gl fuse, max.
900V ion level Up (typ.)
green LED unction indicator
black r
-40°C/85°C temp. min./Operating temp. max.
-40°C/85°C mp. min./Storage temp., max.
cURus, File E198315
KEMA
35.0 / 10.0 / 35.0
150.0 x 35 x 80.0
Type Qty. Order No.
PU1 TSG Plus 330 VAC 0,9kV 1 8561220000
Cross-connection QB 18-4 order No. 8619440000Cross-connection QB 18-6 order No. 8619450000
Designation BZ18, PE PE PE PE PE order No. 8619470000
PU 1 TSG+ 50kA/1.5kV-440V
for use in industrial networks
L / NL / N
TriggerTrigger
Technical specification
440V d voltage (AC)
440V ating voltage Uc (ac), max.
Class I ment class acc. to IEC 61643-1
50 kA with 25 As charge imp (10/350µs)
625kJ/M rgy, per path
50 kA / 50 Hz current extinction without back-up fuse
25 kAeff gth at max. back-up fuse
< 150 ns me
250 A gl fuse, max.
1500V on level Up (typ.)
green LED unction indicator
black r
-40°C/85°C temp. min./Operating temp. max.
-40°C/85°C mp. min./Storage temp., max.
cURus, File E198315
KEMA
35.0 / 10.0 / 35.0
150.0 x 35 x 80.0
Type Qty. Order No.
PU1 TSG Plus 440 VAC 1,5kV 1 8561250000
Cross-connection QB 18-4 order No. 8619440000Cross-connection QB 18-6 order No. 8619450000
DesignationBZ18, L1 L2 L3 N PE order No. 8619460000
B.7
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class I with triggered spark gap
Class I lightning arrester
• encapsulated version
• no decoupling necessary thanks to trigger elec-tronics
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
lightening test voltage imp (10/350µs)
Specific energy, per path
Short-circuit current extinction without back-up fuse
Short-circuit strength at max. back-up fuse
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals le E198315
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 1 TSG 35kA/0.9kV-260V
for use in building networks
TriggerTrigger
L / NL / N
Technical specification
230V d voltage (AC)
260V ating voltage Uc (ac), max.
Class I ment class acc. to IEC 61643-1
35 kA with 17.5As charge imp (10/350µs)
305kJ/Ω per path
3 kA / 50 Hz t current extinction without back-up fuse
25 kAeff gth at max. back-up fuse
< 1 µs time
125 A gl fuse, max.
900V ion level Up (typ.)
green LED unction indicator
grey ur
-40°C/85°C temp. min./Operating temp. max.
-40°C/85°C mp. min./Storage temp., max.
cURus, File E198315
35.0 / 10.0 / 35.0
91.0 x 18 x 63.0
Type Qty. Order No.
PU 1 TSG 35kA / 0,9kV 1 8561260000
Cross-connection QB 18-4 order No. 8619440000Cross-connection QB 18-6 order No. 8619450000
DesignationBZ18, L1 L2 L3 N PE order No. 8619460000
PU 1 TSG 50kA/1.5kV-260V
for use in building networks
TriggerTrigger
L / NL / N
Technical specification
230V d voltage (AC)
260V ating voltage Uc (ac), max.
Class I ment class acc. to IEC 61643-1
50 kA with 25 As charge imp (10/350µs)
625kJ/Ω per path
500 A / 50 Hz current extinction without back-up fuse
25 kAeff gth at max. back-up fuse
< 1 µs time
125 A gl fuse, max.
1500V on level Up (typ.)
No tical function indicator
grey ur
-40°C/85°C temp. min./Operating temp. max.
-40°C/85°C mp. min./Storage temp., max.
cURus, File E198315
35.0 / 10.0 / 35.0
91.0 x 18 x 63.0
Type Qty. Order No.
PU 1 TSG 50kA / 1,5kV 1 8561230000
Cross-connection QB 18-4 order No. 8619440000Cross-connection QB 18-6 order No. 8619450000
Designation BZ18, PE PE PE PE PE order No. 8619470000
B.8
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class I with triggered spark gap
Class I lightning arrester
• encapsulated version
• no decoupling necessary thanks to trigger elec-tronics
• suitable as N-PE arrester
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
lightening test voltage imp (10/350µs)
Specific energy, per path
Short-circuit current extinction without back-up fuse
Short-circuit strength at max. back-up fuse
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals le E198315 KEMA
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 1 TSG 100 kA
for use as N-PE arrester
TriggerTrigger
L / NL / N
Technical specification
230V d voltage (AC)
260V ating voltage Uc (ac), max.
Class I ment class acc. to IEC 61643-1
100 kA with 50 As charge imp (10/350µs)
2500kJ/Ω per path
100 A 260 V/50 Hz rent extinction without back-up fuse
Short-circuit strength at max. back-up fuse
< 1 µs time
125 A gl fuse, max.
1500V on level Up (typ.)
No tical function indicator
grey ur
-40°C/85°C temp. min./Operating temp. max.
-40°C/85°C mp. min./Storage temp., max.
cURus, File E198315 KEMA
50.0 / 6.0 / 50.0
90.0 x 36 x 63.0
Type Qty. Order No.
PU 1 TSG 100kA/1,5 kV 1 8762020000
Cross-connection QB 18-4 order No. 8619440000Cross-connection QB 18-6 order No. 8619450000
BZ18, L1 L2 L3 N PE order No. 8619460000BZ18, PE PE PE PE PE order No. 8619470000
B.9
B
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for low-voltage supplies
B.10
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B
Weidmüller overvoltage protection type PU B is designed forlightning protection equipotential bonding to DIN VDE 0185part 1 (Nov 1982). The PU B is a class I lightning arrester (B arrester) to DIN VDE 0675 part 6 (Nov 1989), IEC 61643-1(Feb 1998), ENV 61024-1 (Jan 1995) and IEC 1312-1 (Feb1995).
In the event of a lightning strike, the integral plug-in high-powervaristors create the necessary equipotential bonding betweenthe building’s lightning protection system and the earthingsystem of the power supply.
Electrical connection
The PU B class I lightning arresters are connected between the phase conductors (L1, L2, L3), or the neutral conductor,the earth of the consumer installation and – in addition – theearthing bar of the distribution board. The lines for this shouldbe kept as short as possible.
The PU B is clipped to a TS 35 rail in the switching cabinet ordistribution board. The maximum permissible operating voltageUc is 275 Vac. No inductances are required for decouplingfrom downstream class II (C) arresters.
Please follow the installation instructions.
Checking operation, maintenance and approvals
A visual check is necessary – more frequently during storms –to ensure that the PU B overvoltage protection componentsare operating correctly. This visual check is easy because thevaristor is fitted with a thermal disconnector. If this has beentripped and protection is no longer provided, the flag in thestatus window changes from green to red. A tripped arrester is easily replaced by a qualified technician without having todisconnect any wiring.
The top section of the varistor is coded according to voltageand – to distinguish it from class II overvoltage arresters (C arresters) – integrated in a black plastic housing (PA 6.6).Therefore, it is not possible to plug in a different, i.e. wrong,replacement varistor.
These plug-in high-power varistors achieve a very lowprotection level of < 2 kV with high discharge currents. Thearrester is to be fused (max. 160 A gL) to suit the cross-sectionof the line. The use of varistors means that overvoltages do notgive rise to any emissions within the installation.
The connection is to be designed to IEC 947-7-1 for thefollowing cross-sections:
– solid wire: 6...10 mm2,
– multistrand wire: 16...25 mm2,
– fine strand wire 10...25 mm2.
The operating temperature range is –40 °C ... +60 °C.
The PU B is an arrester that can be used both as a class I andalso a class II arrester.
Weidmüller PU B lightning arresters have UL approval and arehence suitable for use worldwide.
PU-B dimensionsWidth PU3B 54 mmPU3BR 72 mmPU4B 72 mmPU4BR 90 mm
Lightning arresters with varistors for lightning protectionequipotential bonding
Class I overvoltage protection (B arresters)
B.11
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class I with high-power varistors
Class I lightning arrester with high-power varis-tors, also suitable as class II arrester
• plug-in version with visual function indicator
• complete unit
• coded voltage level, diverse voltages
• high energy absorption, 7 kA 10/350 µs perdisc
• low residual voltage
• short time to sparkover
• no follow current
• thermal overcurrent protection for varistors
• no decoupling inductance required between PUB and PU C
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
lightening test voltage imp (10/350µs)
Specific energy, per path
Leakage current, max. (8/20 µs)
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator faulty, replace
Monitoring contact
Design lation housing
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
without telecomm. contact
with telecomm. contact
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 3 B/BR
PU 3 B/BR 230/400Vac
L3
U U U
L2 L1 11 12 14
OK CHANGE OK CHANGE OK CHANGE
Technical specification
230V d voltage (AC)
275V ating voltage Uc (ac), max.
Class I ment class acc. to IEC 61643-1
20 kA ening test voltage imp (10/350µs)
100kJ/M rgy, per path
100.0kA current, max. (8/20 µs)
< 25 ns ime
160 A gl fuse, max.
2000V on level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
black r
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL provals
without telecomm. contact with telecomm. contact
10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0
90.0 x 54 x 61.0 90.0 x 72 x 61.0
Type Qty. Order No.
PU 3 B 275 VAC 1 8381890000
PU 3 BR 275 VAC 1 8381900000
Plug-in spare arrester, 275 V PU 0 B 8381880000
PU 4 B/BR
PU 4 B/BR 230/400Vac
11 12 14 L3
U U U
L2 L1
OK CHANGE OK CHANGE OK CHANGE
U
OK CHANGE
N
Technical specification
230V d voltage (AC)
275V ating voltage Uc (ac), max.
Class I ment class acc. to IEC 61643-1
25 kA ening test voltage imp (10/350µs)
100kJ/Ω per path
100.0kA current, max. (8/20 µs)
< 25 ns ime
160 A gl fuse, max.
2000V on level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
black r
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL provals
without telecomm. contact with telecomm. contact
10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0
90.0 x 72 x 61.0 90.0 x 90 x 61.0
Type Qty. Order No.
PU 4 B 275 VAC 1 8147020000
PU 4 BR 275 VAC 1 8291640000
Plug-in spare arrester, 275 V PU 0 B 8381880000
The PU I+II COMBI combined overvoltage protectionincorporates triggered PU 1 TSG class I sparkover gaps, classII varistor arresters PU x C and cross-connections. This setupprotects low-voltage consumer installations and electronicdevices against overvoltages, both those caused by atmosphericdischarges (lightning) and those caused by switching operations(transients).
The PU COMBI complies with the requirements of IEC 61643-1 (Feb 1998). The PU R COMBI also has a remote signallingfunction achieved via a floating contact.
Electrical connection
The PU COMBI overvoltage protection device is connectedwith lines as short as possible between the phase conductors(L1, L2, L3), or the neutral conductor (N), and the earth of theconsumer installation. Unprotected lines (e.g. to meters) andprotected lines must not be routed together.
The PU COMBI can be supplied for a 4-conductor system withthree phases plus PEN conductor, and also for a 5-conductorsystem with three phases plus N-PE arrester.
Checking operation, maintenance and approvals
A visual check is necessary to ensure that the PU COMBIovervoltage protection components are operating correctly.This visual check is easy because the arrester is fitted with athermal disconnector. If this has been tripped and protection isno longer provided, the flag in the status window changes fromgreen to red. A tripped arrester is easily replaced by a qualifiedtechnician without having to disconnect any wiring. The topsection of the varistor is coded according to voltage. Therefore,it is not possible to plug in a different, i.e. wrong, replacementvaristor.
The cross-section of the earth line must be at least 10 mm2 orhalf the cross-sectional area of the phase conductor. The fuseprotection (max. 125 A gL) for the PU modules is chosendepending on the line cross-section and the type of wiring.
The connection is designed to IEC 947-7-1 for the followingcross-sections:
solid wire: 10...35 mm2
multistrand wire: 10...25 mm2
fine strand wire: 10...25 mm2
The operating temperature range is –40 °C ... +60 °C.
Combination arrester
Combined lightning and overvoltage protection for low-voltage consumer installations and electronics
Overvoltage Protection for low-voltage supplies
B.12
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B
B
B.13
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for low-voltage supplies
length x width x height
PU Combi I+II 4-conductor system 90 x 65 x 110 mmPU R Combi I+II 4-conductor system 90 x 65 x 126 mmPU Combi I+II 5-conductor system 90 x 65 x 148 mmPU R Combi I+II 5-conductor system 90 x 65 x 162 mm
h
B.14
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
applicable for 4-wire systems
The overvoltage protection combination consistsof the class I triggered sparkover gap PU1TSG forprotecting the phase to N of an N-PE sparkovergap and the class II PU3C. The arresters are inter-connected via 16 mm2 jumpers.
The connection to the power line is made at thePU1TSG.
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
lightening test voltage imp (10/350µs)
Specific energy, per path
Short-circuit current extinction without back-up fuse
Short-circuit strength at max. back-up fuse
Response time t;100 ns
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator faulty, replace
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU COMBI I+II 4 Wire
for use in building networks
Technical specification
230V d voltage (AC)
260V ating voltage Uc (ac), max.
I+II (combination arrester) EC 61643-1
35 kA with 17.5 As charge mp (10/350µs)
305kJ/Ω per path
3 kA / 50 Hz t current extinction without back-up fuse
25 kAeff gth at max. back-up fuse
sym/ asym: <100 ns
125 A gl fuse, max.
900V ion level Up (typ.)
green = OK; red = arrester faulty, replace
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
Approvals
35.0 / 10.0 / 35.0
91.0 x 110 x 65.0
Type Qty. Order No.
PU COMBI I+II 4 Wire 1 8729960000
Set: PU3C(R), PU1TSG, jumpers
PU R COMBI I+II 4 Wire
for use in building networks
Technical specification
230V d voltage (AC)
260V ating voltage Uc (ac), max.
I+II (combination arrester) EC 61643-1
35 kA with 17.5 As charge mp (10/350µs)
305kJ/Ω per path
3 kA / 50 Hz t current extinction without back-up fuse
25 kAeff gth at max. back-up fuse
sym/ asym: <100 ns
125 A gl fuse, max.
900V ion level Up (typ.)
green = OK; red = arrester faulty, replace
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
Approvals
35.0 / 10.0 / 35.0
90.0 x 126 x 65.0
Type Qty. Order No.
PU R COMBI I+II 4 Wire 1 8729970000
Set: PU3C(R), PU1TSG, jumpers
B.15
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
applicable for 5-wire systems
The overvoltage protection combination consistsof the class I triggered sparkover gap PU1TSG forprotecting the phase to N of an N-PE sparkovergap and the class II PU3C. The arresters are inter-connected via 16 mm2 jumpers.
The connection to the power line is made at thePU1TSG.
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
lightening test voltage imp (10/350µs)
50 kA with 25 As charge
Specific energy, per path
Short-circuit current extinction without back-up fuse
Short-circuit strength at max. back-up fuse
Response time t;100 ns
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator faulty, replace
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU COMBI I+II 5 Wire
for use in building networks
h
Technical specification
230V d voltage (AC)
260V ating voltage Uc (ac), max.
I+II (combination arrester) EC 61643-1
35 kA with 17.5 As charge mp (10/350µs)
50 kA with 25 As charge
305kJ/Ω per path
3 kA t-circuit current extinction without back-up fuse
25 kAeff gth at max. back-up fuse
sym/ asym: <100 ns
125 A gl fuse, max.
1500V on level Up (typ.)
green = OK; red = arrester faulty, replace
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
Approvals
35.0 / 10.0 / 35.0
90.0 x 148 x 65.0
Type Qty. Order No.
PU COMBI I+II 5 Wire 1 8729950000
Set: PU3C(R), PU1TSG, jumpers
PU R COMBI I+II 5 Wire
for use in building networks
h
Technical specification
230V d voltage (AC)
260V ating voltage Uc (ac), max.
I+II (combination arrester) EC 61643-1
35 kA with 17.5 As charge mp (10/350µs)
50 kA with 25 As charge
305kJ/Ω per path
3 kA t-circuit current extinction without back-up fuse
25 kAeff gth at max. back-up fuse
sym/ asym: <100 ns
125 A gl fuse, max.
1500V on level Up (typ.)
green = OK; red = arrester faulty, replace
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
Approvals
35.0 / 10.0 / 35.0
91.0 x 165 x 65.0
Type Qty. Order No.
PU R COMBI I+II 5 Wire 1 8729930000
Set: PU3C(R), PU1TSG, jumpers
B.16
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B
Weidmüller overvoltage protection type PU C protects low-voltage consumer installations and electronic devices againstovervoltages, both those caused by atmospheric discharges(lightning) and those caused by switching operations(transients). The PU C complies with the requirements of DIN VDE 0675 part 6, class C (Nov 1989), (draft) DIN VDE0675 part 6, A2 (Oct 1996), ÖVE SN 60 parts 1 and 4, andIEC 61643-1 (Feb 1998).
Electrical connection
The PU COMBI overvoltage protection device is connectedwith lines as short as possible between the phase conductors(L1, L2, L3), or the neutral conductor (N), and the earth of theconsumer installation. Unprotected lines (e.g. to meters) andprotected lines must not be routed together. PU C arresters forthe "3+1” circuit are also available.
PU C overvoltage protection is available as a compact module,3- or 4-pole, with up to 100 kA (8/20 µs), with the PEconnections of the discs already interconnected. Versions canbe supplied for the following rated voltages:
• 60 Vac,
• 115/230 Vac,
• 230/400 Vac,
• 470/600 Vac,
• for ”3+1” circuits
• special types for IT systems
Checking operation, maintenance and approvals
A visual check is necessary to ensure that the PU COMBIovervoltage protection components are operating correctly.This visual check is easy because the arrester is fitted with athermal disconnector. If this has been tripped and protection isno longer provided, the flag in the status window changes fromgreen to red. A tripped arrester is easily replaced by a qualifiedtechnician without having to disconnect any wiring.
The top section of the varistor is coded according to voltageand – to distinguish it from class I overvoltage arresters (B arresters) – integrated in a light grey plastic housing (PA 6.6).Therefore, it is not possible to plug in a different, i.e. wrong,replacement varistor.
The cross-section of the earth line must be at least 10 mm2 orhalf the cross-sectional area of the phase conductor. The fuseprotection (max. 125 A gL) for the PU modules is chosendepending on the line cross-section and the type of wiring.
Weidmüller PU C arresters have ÖVE SN 60 and UL approvaland are hence suitable for use worldwide.
The connection is designed to IEC 947-7-1 for the followingcross-sections:
– solid wire: 6...10 mm2,
– multistrand wire: 16...25 mm2,
– fine strand wire: 10...25 mm2.
The operating temperature range is –40 °C ... +60 °C.
Overvoltage Protection for low-voltage consumers andelectronic components
Low-voltage protection class II (C charge eliminators)
Overvoltage Protection for low-voltage supplies
Monitoring unit
Dimensioned drawing PU-COverall width PU1C 18 mmPU2C 36 mmPU3C 54 mmPU3CR, PU4C 72 mmPU4CR 90 mm
B.17
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class II with varistors
Class II overvoltage protection
with Uc: 280 V
• plug-in varistor top section
• coded voltage level, diverse voltages
• high energy absorption
• short time to sparkover
• no follow current
• installed in Insta distributor
• thermal and dynamic overcurrent protection
• coordination between class I with Up:< 900 V
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
Rated leakage current (8/20 µs)
Limiting leakage current (8/20 µs)
Leakage current, max. (8/20 µs)
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator faulty, replace
Monitoring contact
Design lation housing
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals N 60, SABS
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
without telecomm. contact
with telecomm. contact
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 3 C+CR 230 V
PU 3 C / PU 3 CR 230/400Vac
L3 L2 L1
OK CHANGE OK CHANGE OK CHANGE
11 12 14
U U U
Technical specification
230V d voltage (AC)
280V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
100.0kA current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
1300V on level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL, ÖVE SN 60, SABS
without telecomm. contact with telecomm. contact
10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0
90.0 x 54 x 61.0 90.0 x 72 x 61.0
Type Qty. Order No.
PU 3 C 275 VAC 1 8021490000
PU 3 CR 275 VAC 1 8021510000
Plug-in spare arrester, 275 V PU 0 B 8339510000
PU 4 C+CR 230 V
PU 4 C / PU 4 CR 230/400Vac
11 12 14 L3
U U U
L2 L1
OK CHANGE OK CHANGE OK CHANGE
U
OK CHANGE
N
Technical specification
230V d voltage (AC)
280V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
100.0kA current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
1300V on level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL, ÖVE SN 60, SABS
without telecomm. contact with telecomm. contact
10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0
90.0 x 72 x 61.0 90.0 x 91 x 61.0
Type Qty. Order No.
PU 4 C 275 VAC 1 8021500000
PU 4 CR 275 VAC 1 8021520000
Plug-in spare arrester, 275 V PU 0 B 8339510000
B.18
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class II with varistors
Class II overvoltage protection
with Uc: 280 V
• plug-in varistor top section
• coded voltage level, diverse voltages
• high energy absorption
• short time to sparkover
• no follow current
• installed in Insta distributor
• thermal and dynamic overcurrent protection
• coordination between class I with Up:< 900 V
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
Rated leakage current (8/20 µs)
Limiting leakage current (8/20 µs)
Leakage current, max. (8/20 µs)
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator faulty, replace
Monitoring contact
Design lation housing
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals N 60, SABS
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
without telecomm. contact
with telecomm. contact
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 1 C 230 V
PU 1 C
L1
OK CHANGE
U
Technical specification
230V d voltage (AC)
280V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
40.0kA e current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
1300V on level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL, ÖVE SN 60, SABS
without telecomm. contact
10.0 / 6.0 / 50.0
90.0 x 18 x 61.0
Type Qty. Order No.
PU 1 C 275 VAC 1 8102610000
Plug-in spare arrester, 275 V PU 0 B 8339510000
PU 2 C 230 V
PU 2 C
U U
L2 L1
OK CHANGE OK CHANGE
Technical specification
230V d voltage (AC)
280V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
75.0kA e current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
1300V on level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL, ÖVE SN 60, SABS
without telecomm. contact with telecomm. contact
10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0
90.0 x 36 x 61.0 90.0 x 54 x 61.0
Type Qty. Order No.
PU 2 C 275 VAC 1 8098170000
PU 2 CR 275 VAC 1 8425240000
Plug-in spare arrester, 275 V PU 0 B 8339510000
B.19
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class II with varistors
Class II overvoltage protection
with Uc: 280 V
• plug-in varistor top section
• coded voltage level, diverse voltages
• high energy absorption
• short time to sparkover
• no follow current
• installed in Insta distributor
• thermal and dynamic overcurrent protection
• coordination between class I with Up:< 900 V
• complete 3- or 4-pole modules for TN and TTsystems with 100 kA 8/20 µs discharge current
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
Rated leakage current (8/20 µs)
Limiting leakage current (8/20 µs)
Leakage current, max. (8/20 µs)
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator faulty, replace
Monitoring contact
Design lation housing
Colour range
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
without telecomm. contact
with telecomm. contact
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 3+1 C 230 V
PU 3+1 C/CR 230/400Vac
L3
U U U
L2 L1
OK CHANGE OK CHANGE OK CHANGE
PE
N
Technical specification
230V d voltage (AC)
280V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
100.0kA current, max. (8/20 µs)
< 1 µs time
125 A gl fuse, max.
1900V on level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
grey/orange
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
Approvals
without telecomm. contact with telecomm. contact
16.0 / 6.0 / 50.0 16.0 / 6.0 / 50.0
91.0 x 72 x 61.0 91.0 x 72 x 61.0
Type Qty. Order No.
PU 3+1 C 275 VAC 1 8416370000
PU 3+1 CR 275 VAC 1 8576190000
Plug-in spare arrester, 280 V PU 0 C 8339510000Plug-in spare arrester N-PE distance PU 0 C N-PE 8796160000
PU 3+1 C 385 V
PU 3+1 C 385Vac
L3
U U U
L2 L1
OK CHANGE OK CHANGE OK CHANGE
PE
N
Technical specification
230V d voltage (AC)
385V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
100.0kA current, max. (8/20 µs)
< 1 µs time
125 A gl fuse, max.
1900V on level Up (typ.)
green = OK; red = arrester faulty, replace
Monitoring contact
installation housing
grey/orange
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
Approvals
without telecomm. contact
10.0 / 6.0 / 50.0
91.0 x 72 x 61.0
Type Qty. Order No.
PU 3+1 C 385 VAC 1 8616990000
Plug-in spare arrester, 385V PU 0 C 8328670000Plug-in spare arrester N-PE distance PU 0 C N-PE 8796160000
B.20
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class II with varistors
Class II overvoltage protection
with Uc: 130 V
• plug-in varistor top section
• coded voltage level, diverse voltages
• high energy absorption
• short time to sparkover
• no follow current
• thermal and dynamic overcurrent protection
• complete 3- or 4-pole modules for TN and TTsystems with 100 kA 8/20 µs discharge current
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
Rated leakage current (8/20 µs)
Limiting leakage current (8/20 µs)
Leakage current, max. (8/20 µs)
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator faulty, replace
Monitoring contact
Design lation housing
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
without telecomm. contact
with telecomm. contact
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 3 C 115 V
PU 3 C / PU 3 CR 115/230Vac
L3 L2 L1
OK CHANGE OK CHANGE OK CHANGE
11 12 14
U U U
Technical specification
115V d voltage (AC)
130V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
100.0kA current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
800V ion level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL provals
without telecomm. contact with telecomm. contact
10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0
90.0 x 54 x 61.0 90.0 x 72 x 61.0
Type Qty. Order No.
PU 3 C 130 VAC 1 8291660000
PU 3 CR 130 VAC 1 8291680000
Plug-in spare arrester, 130 V PU 0 C 8432430000
PU 4 C 115 V
PU 4 C / PU 4 CR 115/230Vac
11 12 14 L3
U U U
L2 L1
OK CHANGE OK CHANGE OK CHANGE
U
OK CHANGE
N
Technical specification
115V d voltage (AC)
130V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
100.0kA current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
800V ion level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL provals
without telecomm. contact with telecomm. contact
10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0
90.0 x 72 x 61.0 90.0 x 90 x 61.0
Type Qty. Order No.
PU 4 C 130 VAC 1 8291670000
PU 4 CR 130 VAC 1 8291690000
Plug-in spare arrester, 130 V PU 0 C 8432430000
B.21
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class II with varistors
Class II overvoltage protection
with Uc: 130 V
• plug-in varistor top section
• coded voltage level, diverse voltages
• high energy absorption
• short time to sparkover
• no follow current
• thermal and dynamic overcurrent protection
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
Rated leakage current (8/20 µs)
Limiting leakage current (8/20 µs)
Leakage current, max. (8/20 µs)
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator faulty, replace
Monitoring contact
Design lation housing
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
without telecomm. contact
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 1 C 115 V
PU 1 C
L1
OK CHANGE
U
Technical specification
115V d voltage (AC)
130V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
40.0kA e current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
800V ion level Up (typ.)
green = OK; red = arrester faulty, replace
Monitoring contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL provals
without telecomm. contact
10.0 / 6.0 / 50.0
90.0 x 18 x 61.0
Type Qty. Order No.
PU 1 C 130 VAC 1 8215820000
Plug-in spare arrester, 130 V PU 0 C 8432430000
PU 2 C 115 V
PU 2 C
U U
L2 L1
OK CHANGE OK CHANGE
Technical specification
115V d voltage (AC)
130V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
75.0kA e current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
800V ion level Up (typ.)
green = OK; red = arrester faulty, replace
Monitoring contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL provals
without telecomm. contact
10.0 / 6.0 / 50.0
90.0 x 36 x 61.0
Type Qty. Order No.
PU 2 C 130 VAC 1 8291650000
Plug-in spare arrester, 130 V PU 0 C 8432430000
B.22
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class II with varistors
Class II overvoltage protection
with Uc: 385 V
• suitable for IT networks
• plug-in varistor top section
• coded voltage level, diverse voltages
• high energy absorption
• short time to sparkover
• no follow current
• installed in Insta distributor
• thermal and dynamic overcurrent protection
• complete 3- or 4-pole modules with 100 kA8/20 µs discharge current
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
Rated leakage current (8/20 µs)
Limiting leakage current (8/20 µs)
Leakage current, max. (8/20 µs)
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator faulty, replace
Monitoring contact
Design lation housing
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
without telecomm. contact
with telecomm. contact
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 3 C+CR 385 V
PU 3 C / PU 3 CR (to Austrian standard 8001section 18)
L3 L2 L1
OK CHANGE OK CHANGE OK CHANGE
11 12 14
U U U
Technical specification
230V d voltage (AC)
385V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
100.0kA current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
1500V on level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL provals
without telecomm. contact with telecomm. contact
10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0
90.0 x 54 x 61.0 90.0 x 72 x 61.0
Type Qty. Order No.
PU 3 C 385 VAC 1 8197930000
PU 3 CR 385 VAC 1 8380730000
Plug-in spare arrester, 385V PU 0 C 8328670000
PU 4 C+CR 385 V
PU 4 C / PU 4 CR (to Austrian standard 8001section 18)
L3
U U U
L2 L1 11 12 14
OK CHANGE OK CHANGE OK CHANGE
N
U
OK CHANGE
Technical specification
230V d voltage (AC)
385V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
100.0kA current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
1500V on level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
Approvals
without telecomm. contact with telecomm. contact
10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0
90.0 x 72 x 61.0 90.0 x 91 x 61.0
Type Qty. Order No.
PU 4 C 385 VAC 1 8601280000
PU 4 CR 385 VAC 1 8494040000
Plug-in spare arrester, 385V PU 0 C 8328670000
B.23
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class II with varistors
Class II overvoltage protection
with Uc: 550 V
• plug-in varistor top section
• coded voltage level, diverse voltages
• high energy absorption
• short time to sparkover
• no follow current
• installed in Insta distributor
• thermal and dynamic overcurrent protection
• coordination between class I with Up:< 1.5 kV
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
Rated leakage current (8/20 µs)
Limiting leakage current (8/20 µs)
Leakage current, max. (8/20 µs)
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator faulty, replace
Monitoring contact
Design lation housing
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
without telecomm. contact
with telecomm. contact
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 3 C+CR 470 V
PU 3 C / PU 3 CR 470/690Vac
L3 L2 L1
OK CHANGE OK CHANGE OK CHANGE
11 12 14
U U U
Technical specification
470V d voltage (AC)
550V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
100.0kA current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
2200V on level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL provals
without telecomm. contact with telecomm. contact
10.0 / 6.0 / 10.0 10.0 / 6.0 / 10.0
90.0 x 54 x 61.0 90.0 x 72 x 61.0
Type Qty. Order No.
PU 3 C 550 VAC 1 8451050000
PU 3 CR 550 VAC 1 8451060000
Plug-in spare arrester, 550 V PU 0 C 8451080000
PU 4 C+CR 470 V
PU 4 C / PU 4 CR 470/690Vac
L3
U U U
L2 L1 11 12 14
OK CHANGE OK CHANGE OK CHANGE
N
U
OK CHANGE
Technical specification
470V d voltage (AC)
550V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
100.0kA current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
2200V on level Up (typ.)
green = OK; red = arrester faulty, replace
250V 1A 1CO contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL provals
without telecomm. contact with telecomm. contact
10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0
90.0 x 72 x 60.0 90.0 x 90 x 60.0
Type Qty. Order No.
PU 4 C 550 VAC 1 8291720000
PU 4 CR 550 VAC 1 8451070000
Plug-in spare arrester, 550 V PU 0 C 8451080000
B.24
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class II with varistors
Class II overvoltage protection
with Uc: 550 V
• plug-in varistor top section
• coded voltage level, diverse voltages
• high energy absorption
• short time to sparkover
• no follow current
• installed in Insta distributor
• thermal and dynamic overcurrent protection
• coordination between class I with Up:< 1.5 kV
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
Rated leakage current (8/20 µs)
Limiting leakage current (8/20 µs)
Leakage current, max. (8/20 µs)
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator faulty, replace
Monitoring contact
Design lation housing
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
without telecomm. contact
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 1 C 470 V
PU 1 C
L1
OK CHANGE
U
Technical specification
470V d voltage (AC)
550V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
40.0kA e current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
2200V on level Up (typ.)
green = OK; red = arrester faulty, replace
Monitoring contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL provals
without telecomm. contact
10.0 / 6.0 / 50.0
90.0 x 18 x 61.0
Type Qty. Order No.
PU 1 C 550 VAC 1 8291700000
Plug-in spare arrester, 550 V PU 0 C 8451080000
PU 2 C 470 V
PU 2 C
U U
L2 L1
OK CHANGE OK CHANGE
Technical specification
470V d voltage (AC)
550V ating voltage Uc (ac), max.
Class II ent class acc. to IEC 61643-1
20 kA leakage current (8/20 µs)
40kA ting leakage current (8/20 µs)
75.0kA e current, max. (8/20 µs)
< 25 ns ime
125 A gl fuse, max.
2200V on level Up (typ.)
green = OK; red = arrester faulty, replace
Monitoring contact
installation housing
grey ur
-40°C/60°C temp. min./Operating temp. max.
-40°C/80°C mp. min./Storage temp., max.
UL provals
without telecomm. contact
10.0 / 6.0 / 50.0
90.0 x 36 x 61.0
Type Qty. Order No.
PU 2 C 550 VAC 1 8291710000
Plug-in spare arrester, 550 V PU 0 C 8451080000
B
B.25
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B.26
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B
Our overvoltage protection PU D protects low-voltageconsumers and electronic devices from overvoltage caused byatmospheric discharges (thunderstorm) or switchingprocedures (transients).
The PU D can be mounted in small or storey distributionboards.
PU D corresponds to the requirements of DIN VDE 0675, part6, class C, 11/89, part 6, A2 10/96 and IEC 61643-1 02/98.
Electrical connection
PU D overvoltage protection is installed after the PU C beforethe device/consumer being protected. It can protect circuits upto 16 A.
For example, an installation for a circuit in small distributionboards can be used to protect a monitor.
Functional checks and maintenance
Ageing of the varistors can cause high temperatures at the va-ristors. In low voltage systems, this can cause a fire. The integrated temperature monitoring automaticallydisconnects the varistor from the power supply. This is indicated by the glow lamp going off. Types PO DS alsoequipped with a switching contact to report this.
The back-up fuse depends on the conductor cross-sectionand type of routing. For PU D charge eliminators, the maximumpower rating is up to 16 A.
The connection is rated to IEC 947-7-1 for the following cross-sections:
solid conductor: 0,5...2,5 mm2
flexible conductor: 0,5...2,5 mm2
The operating temperature range is from –25 °C ... +55 °C, and the storage temperature range is from –40 °C ... +60 °Cbetragen.
Low-voltage consumers, small distribution boards andelectronic componentsOvervoltage protection class III (D charge eliminators)
Overvoltage Protection for low-voltage supplies
Dimensioned drawing PU DSOverall width 18 mm
B.27
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class III with varistors
Class III overvoltage arrester
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
Combined pulse Uoc
Rated discharge current per path (8/20 µs)
Leakage current, max. (8/20 µs)
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator
Monitoring contact
Design lation housing
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order data
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU DS 230Vac 16A
PU DS 230Vac 16A
Technical specification
230V d voltage (AC)
275V ating voltage Uc (ac), max.
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
Rated discharge current per path (8/20 µs)
5.0kA ge current, max. (8/20 µs)
< 150 ns me
16 A -up fuse, max.
1500V on level Up (typ.)
green LED = OK on indicator
250V 1A 1CO contact
installation housing
grey ur
-30°C/70°C temp. min./Operating temp. max.
-40°C/70°C mp. min./Storage temp., max.
Approvals
screw connection
2.5 / 0.5 / 2.5
91.0 x 18 x 61.0
Type Qty. Order No.
PU DS 230VAC 16A 1 8523740000
PU DS 115Vac/dc 16A
PU DS 115Vac/dc 16A
Technical specification
115V d voltage (AC)
130V ating voltage Uc (ac), max.
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
Rated discharge current per path (8/20 µs)
5.0kA ge current, max. (8/20 µs)
< 150 ns me
16 A -up fuse, max.
850V ion level Up (typ.)
green LED = OK on indicator
250V 1A 1CO contact
installation housing
grey ur
-30°C/70°C temp. min./Operating temp. max.
-40°C/70°C mp. min./Storage temp., max.
Approvals
screw connection
2.5 / 0.5 / 2.5
91.0 x 18 x 61.0
Type Qty. Order No.
PU DS 115VAC 16A 1 8568650000
B.28
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class III with varistors
Class III overvoltage arrester
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
Combined pulse Uoc
Rated discharge current per path (8/20 µs)
Leakage current, max. (8/20 µs)
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator
Monitoring contact
Design lation housing
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order data
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU DS 48Vac/dc 16A
PU DS 48Vac/dc 16A
Technical specification
48V ed voltage (AC)
60V rating voltage Uc (ac), max.
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
2.50kA discharge current per path (8/20 µs)
5.0kA ge current, max. (8/20 µs)
< 150 ns me
16 A -up fuse, max.
1100V on level Up (typ.)
green LED = OK on indicator
250V 1A 1CO contact
installation housing
grey ur
-30°C/70°C temp. min./Operating temp. max.
-40°C/70 temp. min./Storage temp., max.
Approvals
screw connection
2.5 / 0.5 / 2.5
91.0 x 18 x 61.0
Type Qty. Order No.
PU DS 48V 16A 1 8670740000
PU DS 24Vac/dc 16A
PU DS 24Vac/dc 16A
Technical specification
24V ed voltage (AC)
30V rating voltage Uc (ac), max.
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
1kA discharge current per path (8/20 µs)
2.0kA ge current, max. (8/20 µs)
< 150 ns me
16 A -up fuse, max.
1100V on level Up (typ.)
green LED = OK on indicator
250V 1A 1CO contact
installation housing
grey ur
-30°C/70°C temp. min./Operating temp. max.
-40°C/70°C mp. min./Storage temp., max.
Approvals
screw connection
2.5 / 0.5 / 2.5
91.0 x 18 x 61.0
Type Qty. Order No.
PU DS 24Vuc 16A 1 8682100000
B.29
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class III with varistors
Class III overvoltage arrester
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
Combined pulse Uoc
Rated discharge current per path (8/20 µs)
Leakage current, max. (8/20 µs)
Response time
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator fault
Monitoring contact
Design lation housing
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order data
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU D 230Vac 16A
PU D 230Vac 16A
OK FAULT
L L
11
12
NNPE PE
U
U
Technical specification
230V d voltage (AC)
275V ating voltage Uc (ac), max.
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
2.50kA discharge current per path (8/20 µs)
7.0kA ge current, max. (8/20 µs)
< 150 ns me
16 A -up fuse, max.
850V ion level Up (typ.)
green LED = OK; red LED = fault
250V 1A 1CO contact
installation housing
grey ur
-25°C/55°C temp. min./Operating temp. max.
-40°C/55°C mp. min./Storage temp., max.
Approvals
screw connection
2.5 / 0.5 / 2.5
91.0 x 54 x 61.0
Type Qty. Order No.
PU D 230V 16A 1 8411930000
PU D 115Vac 16A
PU D 115Vac 16A
OK FAULT
L L
11
12
NNPE PE
U
U
Technical specification
115V d voltage (AC)
130V ating voltage Uc (ac), max.
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
2.50kA discharge current per path (8/20 µs)
7.0kA ge current, max. (8/20 µs)
< 150 ns me
16 A -up fuse, max.
480V ion level Up (typ.)
green LED = OK; red LED = fault
250V 1A 1CO contact
installation housing
grey ur
-25°C/55°C temp. min./Operating temp. max.
-40°C/55°C mp. min./Storage temp., max.
Approvals
screw connection
2.5 / 0.5 / 2.5
91.0 x 54 x 61.0
Type Qty. Order No.
PU D 115Vac 16A 1 8472100000
B.30
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class III with varistors
Class III overvoltage arrester
Technical dataTechnical specification
Rated voltage (AC)
Operating voltage Uc (ac), max.
Requirement class acc. to IEC 61643-1
Combined pulse Uoc
Rated discharge current per path (8/20 µs)
Leakage current, max. (8/20 µs)
Response time t;100 ns
Back-up fuse, max.
Protection level Up (typ.)
Optical function indicator fault
Monitoring contact
Design lation housing
Colour
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
Approvals
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order data
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU 3 D 230V/400Vac 16A
PU 3 D 230V/400Vac 16A
L1L2
N N
12
11
L1L2L3L3
PE PE
FAULT
L1
FAULT
L2
FAULT
L3
Technical specification
230V d voltage (AC)
275V ating voltage Uc (ac), max.
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
6.50kA discharge current per path (8/20 µs)
18.0kA e current, max. (8/20 µs)
< 150 ns <100 ns
16 A -up fuse, max.
850V ion level Up (typ.)
green LED = OK; red LED = fault
250V 1A 1CO contact
installation housing
grey ur
-25°C/55°C temp. min./Operating temp. max.
-40°C/55°C mp. min./Storage temp., max.
Approvals
screw connection
2.5 / 0.5 / 2.5
91.0 x 54 x 61.0
Type Qty. Order No.
PU 3D 230V/400Vac 16A 1 8509130000
PO DS 230V 16A/ PO DAS 230V/16A
PO DAS 230V/16A
L
N
PE
U
FAULT
Technical specification
230V d voltage (AC)
275V ating voltage Uc (ac), max.
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
2.50kA discharge current per path (8/20 µs)
5.0kA ge current, max. (8/20 µs)
sym/ asym: <100 ns
16 A -up fuse, max.
1500V on level Up (typ.)
green LED = OK; red LED = fault
Monitoring contact
miscellaneous housing
black r
-25°C/55°C temp. min./Operating temp. max.
-40°C/60°C mp. min./Storage temp., max.
Approvals
screw connection screw connection
41.0 x 20 x 41.0 41.0 x 12 x 41.0
Type Qty. Order No.
PO D AS 1 8581830000
PO D S 1 8581840000
PO D AS with audible signal
B
B.31
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Dimensioned drawing PU D ZS
B.32
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B
The PU D ZS plug-in overvoltage protection device providesprotection against transient overvoltages for equipment pluggedinto earthed power sockets. The plug-in overvoltage protectionwith its earthed power socket is designed for 230 V/16 A, fulfilsthe requirements of class III to IEC 61643-1 and is used inconjunction with class II, the PU C protection.
The PU D ZS is fitted with components to monitor varistortemperature. In the event of an excessive temperature rise dueto pulses from the mains supply, these disconnect the unit. The integral red warning lamp indicates that protection is nolonger provided. The PU D ZS must then be replaced.
The PU D ZS analog plug-in overvoltage protection deviceprovides protection against transient overvoltages for equipmentand analogue devices plugged into earthed power sockets.Besides the use of standard telephones, an analogue installationcan also transmit data services like fault signalling systems andInternet. The fact that besides telephones other devices like faxmachines and modems are also connected to the analogue linemeans that the hazards due to transient interference phenomenalike overvoltages are on the increase.
In order to achieve protection against these overvoltages,combined overvoltage protection for analogue lines and mainsvoltages is incorporated. The basic version of this power socketadapter is protected by two-stage overvoltage protectionachieved with gas discharge tube and fast-acting suppressiondiodes.
The gas discharge tube achieves a high energy discharge; thesuppression diodes ensure a low residual voltage.
The PU D ZS digital plug-in overvoltage protection providesprotection against transient overvoltages for equipment anddigital devices plugged into earthed power sockets. This powersocket adapter is available for Uko and So interfaces.
In order to achieve protection against these overvoltages,combined overvoltage protection for digital lines and mainsvoltages is incorporated. The basic version of this power socketadapter is protected by two-stage overvoltage protectionachieved with gas discharge tube and fast-acting suppressiondiodes.
The gas discharge tube achieves a high energy discharge; thesuppression diodes ensure a low residual voltage.
In the PU D ZS with the RJ45 sockets a connecting line withRJ45 plugs at both ends is included with the product.
PU D ZS plug-in Overvoltage ProtectionClass III overvoltage protection
Overvoltage Protection for low-voltage supplies
B.33
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class III adapter plug
Class III overvoltage arrester
Technical data
Rated voltage (AC)
Operating voltage Uc (ac), max.
Operating current, Imax
According to DIN VDE 0675-6
Requirement class acc. to IEC 61643-1
Combined pulse Uoc
Leakage current, max. (8/20 µs)
Back-up fuse, max.
Response time
On output side sym., input 8/20 µs, typical
Output side unsym., input 8/20 µs, typical
Leakage current at Un
Optical function indicator fault
Pollution severity
Overvoltage category
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
General data
Input voltage max.
nominal current In, max.
Norm Signal lephone signal RJ45/RJ11/12
Rated leakage current (8/20 µs)
Total current
Response time, type
Resistance per path
Cut-off frequency fg, 600 M-System
Transistor output, positive-switching
Residual voltage at output at input pulse of 1 kV/µs
Residual voltage at output at 8/20µs and input pulse of 5kA
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU D ZS So
PU D ZS So 230V 16A
L POWER
PHONE
L
N NPE PE
1a 1a'
1b 1b'2a 2a'
2b 2b'
FAULT 230V~
230V d voltage (AC)
275V ating voltage Uc (ac), max.
16A ing current, Imax
requirement class D E 0675-6
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
5.0kA ge current, max. (8/20 µs)
16 A -up fuse, max.
< 150 ns me
600V utput side sym., input 8/20 µs, typical
1500V t side unsym., input 8/20 µs, typical
1µA e current at Un
green LED = OK; red LED = fault
2 ollution severity
III rvoltage category
0°C/60°C g temp. min./Operating temp. max.
-25°C/85°C mp. min./Storage temp., max.
General data
190V t voltage max.
0.45A al current In, max.
ISDN telephone signal RJ45/RJ11/12 1/12
4 kA d leakage current (8/20 µs)
10A al current
< 5 ns se time, type
1.1 Ω per path
80 MHz f frequency fg, 600 M-System
Transistor output, positive-switching
a/b <= 270V a-b/PE <= 270V at input pulse of 1 kV/µs
a/b<= 100V a-b/PE<= 100V ut at 8/20µs and input pulse of
5kA
Earthed contact
110.0 x 62 x 48.0
incl. conductor, RJ 11/12 both ends
Type Qty. Order No.
PU D ZS 230V~ 16A / ISDN So 1 8697560000
Conductor, RJ 45 at both ends, order no. 8697590000
PU D ZS
PU D ZS analog 230V 16A
L POWER
PHONE
L
N NPE PE
Lb(+) Lb'
LA(-) La'
FAULT 230V~
230V d voltage (AC)
275V ating voltage Uc (ac), max.
16A ing current, Imax
requirement class D E 0675-6
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
5.0kA ge current, max. (8/20 µs)
16 A -up fuse, max.
< 150 ns me
600V utput side sym., input 8/20 µs, typical
1500V t side unsym., input 8/20 µs, typical
1µA e current at Un
green LED = OK; red LED = fault
2 ollution severity
III rvoltage category
0°C/60°C g temp. min./Operating temp. max.
-25°C/85°C mp. min./Storage temp., max.
General data
190V DC oltage max.
0.45A al current In, max.
Analogue telephone signal RJ45/RJ11/12
4 kA d leakage current (8/20 µs)
10A al current
< 5 ns se time, type
1.1 Ω per path
2 MHz ff frequency fg, 600 M-System
a/b <= 270V a-b/PE <= 270V e-switching
Residual voltage at output at input pulse of 1 kV/µs
a/b<= 100V a-b/PE<= 100V ut at 8/20µs and input pulse of
5kA
Earthed contact
110.0 x 62 x 48.0
incl. conductor, RJ 11/12 both ends
Type Qty. Order No.
PU D ZS 230V~ 16A / analog a/b 1 8697600000
Conductor, RJ45 on both sides, order no. 8697590000
B.34
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class III adapter plug
Class III overvoltage arrester
Technical data
Rated voltage (AC)
Operating voltage Uc (ac), max.
Operating current, Imax
According to DIN VDE 0675-6
Requirement class acc. to IEC 61643-1
Combined pulse Uoc
Leakage current, max. (8/20 µs)
Back-up fuse, max.
Response time
On output side sym., input 8/20 µs, typical
Output side unsym., input 8/20 µs, typical
Leakage current at Un
Optical function indicator fault
Pollution severity
Overvoltage category
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
General data
Input voltage max.
nominal current In, max.
Norm Signal one signal RJ45/RJ11/12
Rated leakage current (8/20 µs)
Total current
Response time, type
Resistance per path
Cut-off frequency fg, 600 M-System
Transistor output, positive-switching
Residual voltage at output at input pulse of 1 kV/µs
Residual voltage at output at 8/20µs and input pulse of 5kA
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU D ZS Uko
PU D ZS Uko 230V 16A
L POWER
PHONE
L
N NPE PE
Lb(+) Lb'
La(-) La'
FAULT 230V~
230V d voltage (AC)
275V ating voltage Uc (ac), max.
16A ing current, Imax
requirement class D E 0675-6
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
5.0kA ge current, max. (8/20 µs)
16 A -up fuse, max.
< 150 ns me
600V utput side sym., input 8/20 µs, typical
1500V t side unsym., input 8/20 µs, typical
1µA e current at Un
green LED = OK; red LED = fault
2 ollution severity
III rvoltage category
0°C/60°C g temp. min./Operating temp. max.
-25°C/85°C mp. min./Storage temp., max.
General data
190V DC oltage max.
0.45A al current In, max.
ISDN telephone signal RJ45/RJ11/12
4 kA d leakage current (8/20 µs)
10A al current
< 5 ns se time, type
1.1 Ω per path
80 MHz f frequency fg, 600 M-System
Transistor output, positive-switching
a/b <= 270V a-b/PE <= 270V at input pulse of 1 kV/µs
a/b<= 100V a-b/PE<= 100V ut at 8/20µs and input pulse of
5kA
Earthed contact
110.0 x 62 x 48.0
incl. conductor, RJ 11/12 both ends
Type Qty. Order No.
PU D ZS Uko 230V 16A 1 8697570000
Conductor, RJ 45 at both ends, order no. 8697590000
PU D ZS 230V 16A
PU D ZS 230V 16A
LPOWER
L
N NPE PE
FAULT 230V~
230V d voltage (AC)
275V ating voltage Uc (ac), max.
16A ing current, Imax
requirement class D E 0675-6
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
5.0kA ge current, max. (8/20 µs)
16 A -up fuse, max.
< 150 ns me
600V utput side sym., input 8/20 µs, typical
1500V t side unsym., input 8/20 µs, typical
1µA e current at Un
green LED = OK; red LED = fault
2 ollution severity
III rvoltage category
0°C/60°C g temp. min./Operating temp. max.
-25°C/85°C mp. min./Storage temp., max.
General data
Input voltage max.
nominal current In, max.
ISDN telephone signal RJ45/RJ11/12
Rated leakage current (8/20 µs)
Total current
Response time, type
Resistance per path
Cut-off frequency fg, 600 M-System
Transistor output, positive-switching
Residual voltage at output at input pulse of 1 kV/µs
Residual voltage at output at 8/20µs and input pulse of 5kA
Earthed contact
110.0 x 62 x 48.0
Type Qty. Order No.
PU D ZS 230V~ 16A 1 8697580000
B.35
B
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Class III adapter plug
Class III overvoltage protection
for signals up to 1 GHz (radio/TV )
Technical data
Rated voltage (AC)
Operating voltage Uc (ac), max.
Operating current, Imax
According to DIN VDE 0675-6
Requirement class acc. to IEC 61643-1
Combined pulse Uoc
Leakage current, max. (8/20 µs)
Back-up fuse, max.
Response time
On output side sym., input 8/20 µs, typical
Output side unsym., input 8/20 µs, typical
Leakage current at Un
Optical function indicator fault
Pollution severity
Overvoltage category
Operating temp. min./Operating temp. max.
Storage temp. min./Storage temp., max.
General data
Input voltage max.
nominal current In, max.
Norm Signal trial and cable
Rated leakage current (8/20 µs)
Total current
Response time, type
Resistance per path
Cut-off frequency fg, 600 M-System
Transistor output, positive-switching
Residual voltage at output at input pulse of 1 kV/µs
Residual voltage at output at 8/20µs and input pulse of 5kA
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Information
Order dataVersion
Information
AccessoriesInformation
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Overvoltage Protection for energy distribution systems
PU D ZS TV/R
PU D ZS TV/R 230V 16A
L POWER
TV/R
L
N NPE PE
TV TV
R R
FAULT 230V~
+
+
+
230V d voltage (AC)
275V ating voltage Uc (ac), max.
16A ing current, Imax
requirement class D E 0675-6
Class III nt class acc. to IEC 61643-1
4kV ed pulse Uoc
5.0kA ge current, max. (8/20 µs)
16 A -up fuse, max.
< 150 ns me
600V utput side sym., input 8/20 µs, typical
1500V t side unsym., input 8/20 µs, typical
1µA e current at Un
green LED = OK; red LED = fault
2 ollution severity
III rvoltage category
0°C/60°C g temp. min./Operating temp. max.
-25°C/85°C mp. min./Storage temp., max.
General data
70 put voltage max.
1.50 nal current In, max.
TV/R terrestrial and cable
5 kA d leakage current (8/20 µs)
Total current
< 100 ns time, type
1.1 Ω per path
1 GHz / 75 M ncy fg, 600 M-System
Transistor output, positive-switching
600 V ual voltage at output at input pulse of 1 kV/µs
800 V ual voltage at output at 8/20µs and input pulse of 5kA
Earthed contact
110.0 x 62 x 48.0
Type Qty. Order No.
PU D ZS TV/R 1 8779230000
Coaxial cable approx. 35 cm long in each case
B.36
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B
WAVEFILTERS for simple radio interferencessuppression in the switching cabinet
The WAVEFILTER series eliminates the time-consuming needto screw in mains filters. These filters are simply clipped on tothe TS35 and connected to the device needing suppression.The two-stage WAVEFILTER with overall width 22.5 mm indesigns 1 A, 3 A, 6 A and 10 A offers high attenuation.
The WAVEFILTER with current-compensating choke is ideal forapplications in drive technology and control/automationtechnology, e.g. for suppressing continuous interference typessuch as “noise” or “ripple” from interfering radiation from othersystems or interference from frequency converters andswitched-mode power supplies. A short, low-ohm massconnection is required for the WAVEFILTER to functionperfectly. We recommend earthing all devices directly with thelargest possible cross-section to a central earthing point in theswitching cabinet.
Interference signals
We distinguish between two types of induced transient andcontinuous interference signals: Symmetrical (differential mode)and asymmetrical (common mode). The symmetricalinterference signals generate voltage between the signal leadsof the system. The asymmetrical interference voltages occurbetween the signal leads and earth.
The WAVEFILTER is suitable of attenuating both kinds ofinterference signal. In addition, WAVEFILTER 10 A also has anearthing conductor choke. This earthing conductor chokesupports both attenuation on the earthing conductor for thefilter and additional attenuation of asymmetrical interferencevoltages.
Overvoltage Protection mains filterWAVEFILTER
Overvoltage Protection for low-voltage supplies
Insertion loss
1 A WAVEFILTER
3 A WAVEFILTER
6 A WAVEFILTER
10 A WAVEFILTER
B
Overvoltage Protection for low-voltage supplies
B.37
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
,,
,,
,
,
Overvoltage Protection for low-voltage supplies
B.38
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B
Type VPE Order No.
WAVEFILTER 1A 1 8614790000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Overvoltage ProtectionMains filter
Technical dataTechnical specification
Rated voltage (AC/DC)
Rated current
Capacitance
Inductance L and L1
Leakage current at Un
Test voltage P/N-PE
Test voltage P-N
Operating temp., min./Operating temp., max.
Dimensions
Clamping range (nom./min./max) mm2
length x width x height mm
Note
Ordering dataVersion
Note
AccessoriesNote
WAVEFILTER 1 A
Wavefilter 1 A 250 V
LINE LOADL L'
N N'
Cx
Cy Cy
250V
1A
33nF
10mH
190µA
2000Vac
1700Vdc
-20°C/40°C
2.50 / 0.50 / 2.50
90 x 22.5 x 73.40
See attenuation diagram
WAVEFILTER 6 A
Wavefilter 6 A 250 V
LINE LOADL L'
N N'
Cx
Cy Cy
250V
6A
33nF Cx 22nF Cy
0.80mH
190µA
2000Vac
1700Vdc
-20°C/40°C
2.50 / 0.50 / 2.50
90 x 22.5 x 73.40
See attenuation diagram
Type VPE Order No.
WAVEFILTER 6A 1 8614800000
Overvoltage Protection for low-voltage supplies
B.39
B
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.Delivery times see page X.8
Overvoltage ProtectionMains filter
Technical dataTechnical specification
Rated voltage (AC/DC)
Rated current
Capacitance
Inductance L and L1
Leakage current at Un
Test voltage P/N-PE
Test voltage P-N
Operating temp., min./Operating temp., max.
Dimensions
Clamping range (nom./min./max) mm2
length x width x height mm
Note
Ordering dataVersion
Note
AccessoriesNote
WAVEFILTER 3 A
Wavefilter 3 A 250 V
LINE LOADL L'
N N'
Cx
Cy Cy
250V
3A
33nF
2mH
190µA
2000Vac
1700Vdc
-20°C/40°C
2.50 / 0.50 / 2.50
90 x 22.5 x 73.40
See attenuation diagram
WAVEFILTER 10 A
Wavefilter 10 A 250 V
LINE LOADL L'
N N'
Cx
Cy Cy
250V
10A
470nF Cx 4.7nF Cy
0.80mH
190µA
2000Vac
1700Vdc
-20°C/40°C
2.50 / 0.50 / 2.50
90 x 22.5 x 73.40
See attenuation diagram
Type VPE Order No.
WAVEFILTER 10A 1 8614770000
Type VPE Order No.
WAVEFILTER 3A 1 8614780000
Overvoltage Protection for low-voltage supplies
B.40
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B
The overvoltage protection may only be installed by suitablyqualified personnel.During the installation, please observe theconnection conditions specific to the country of application.
1. Application
The PU C overvoltage protection to class C (class II) protectslow-voltage consumer installations and electronic devicesagainst overvoltages that can occur as a result of atmosphericdischarges (thunderstorms) or switching operations. The PU Ccomplies with VDE 0675 part 6, class C (draft, Nov 1989), DINVDE 0675 part 6, A2 (Oct 1996), IEC 61643-1 (Feb 1998) andÖVE SN 60 parts 1 and 4. High-power metal oxide varistorsare employed as the voltage-limiting component.
The PU B is a class B (class I) lightning arrester complying withDIN VDE 0675 part 6 (Nov 1989), IEC 61643-1 (Feb 1998),ENV 61024-1 (Jan 1995) and IEC 1312-1 (Feb 1995). Theintegral varistors create the necessary equipotential bonding(lightning protection equipotential bonding according to DINVDE 0185 part 1, Nov 1982) between the building’s lightningprotection and the earthing system of the power supply duringlightning strikes.
The PU D overvoltage protection to class D (class III) protectslow-voltage consumer installations and electronic devicesagainst overvoltages and switching operations. The PU D isintegrated in addition after the PU C in small/storey distributionboards. The PU D complies with DIN VDE 0675 part 6, classD(draft, Nov 1989), DIN VDE 0675 part 6, A2 (Oct 1996) and IEC61643-1 (Feb 1998).
2. Installation specifications
2.1 Place of installationThe PU C must be incorporated in a meter cupboard ordistribution board in such a way that the connection terminalcompartment is not accessible to unauthorised
persons. The PU B is incorporated near the incoming powerlines in order to create the necessary lightning protectionequipotential bonding between the lightning protection systemand the power distribution network. All arresters must beinstalled by a qualified electrician. The installation of systemswith overvoltage protection devices is described in VDE 0100
part 534 (Apr 1999) “Selection and installation of equipment”.This draft standard should be used in conjunction with thefollowing standards:
1. IEC 60364-4-43 “Protection from overvoltage due to atmospheric influencesand switching operations”
2. IEC 61024-1 “Protection of buildings against lightning”
3. IEC 61312-1“Protection against electromagnetic lightning pulses”
2.2 Electrical connection
The lines connecting the PU C overvoltage protection and thePU B lightning arrester between the phase conductor (L1, L2,L3) or neutral conductor (N) and earth (PE) of the consumerinstallation should be kept as short as possible. The routing ofprotected and unprotected lines together must be avoided.(See diagrams on pp. 70-71 for examples of connections.)
2.2.1 Connection to phase conductor and neutralconductor
As a rule, the conductor cross-section for the connection linesto the PU C or PU B arrester is selected as for the phaseconductor (L1, L2, L3) and neutral conductor (N). If a reducedcross-section is desired, a protective device (e.g. main terminalfuse) must guarantee short-circuit protection for the connectinglines. The connection terminals on the arresters may not beused as branch terminals. The backup fuse for the PU C shouldnot exceed 125 A gL. Upstream residual-current circuit-breakers(RCD) type S (3 kA, 8/20 µs) must be able to withstand surgecurrents.The backup fuse for the PU B should not exceed 160 A gL.
Note:
Three-pole PU C devices are employed in a TN-CS system (fig. 2). If the PE and N conductors of the PEN conductor arerouted separately, a four-pole PU should be used. In a TTsystem, a four-pole PU C protector can be installed togetherwith an arrester disconnector according to DIN VDE 0100-534/A1 (Oct 1996). To avoid accidental energisation betweenPE and N and to be able to omit arrester disconnectors, thePU 4 C TT module (Part No. 8416370000) provides the bestsolution (3+1 circuit). A 385 V PU 3 C is installed in an ITsystem with 400 V phase-to-phase voltage.
2.2.2 Installation of D arrester
The PU D arrester is installed in conjunction with a PU C, in thedownstream direction. The PU D is incorporated in the line to beprotected and can protect circuits up to 16 A. The installationcan be carried out in small distribution boards for single circuitsprotecting, for example, monitors. The PO DS is suitable forincorporating in situ, directly in devices or cable ducts.
Installation specification for our PU Overvoltage Protection in power supply networks
2.2.3 Connection to earth
The earth line of the arrester is connected to the earth of theconsumer installation via the shortest route (= 0.5 m). Longer connecting lines reduce the effectiveness of theovervoltage protection. Routing the line parallel with otherelectrical cables should be avoided. In electrical consumerinstallations with equipotential bonding, an earthed equipotentialbonding rail is available as a connection point (see p. 56 ”Principles for low-voltage supplies”). A connection betweenthe arrester earth and the consumer installation earth mustalways be guaranteed. In TN systems the PEN conductor andthe arrester earth line should be connected together. The PENconductor of the power supply company may not be used asan earth. If the PE or PEN rail of a distribution board is used asan earth connection point, it is then necessary for this rail to beconnected to the consumer installation earth via a separateearth line.
Two earth connection terminals are available on the PU B. Bothterminals must be connected. One connection goes to theequipotential bonding connection of the building, the other tothe PE conductor of the installation. The cross-section for theearth line of the arrester is determined, as for lines, accordingto table 1 for the main equipotential bonding. It must be min.0.5 times the cross-section of the main protective conductor,where 25 mm2 copper is taken to be the upper limit and 10 mm2 copper the lower limit.
3. Checking the function
A visual inspection of PU overvoltage protection devices andlightning arresters is especially important during storms. If theflag in the status window or the LED is red, the overvoltageprotection device concerned must be replaced. Ageing of thevaristors can lead to high temperatures in the varistors. This situation can cause fires in low-voltage systems.Therefore, in a hazardous situation the integral temperaturemonitoring automatically disconnects the varistor from the po-wer supply. This disconnection is indicated by the warninglamp being extinguished, and in the PO DS or the PUxCR,
B
Overvoltage Protection for low-voltage supplies
B.41
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
PUxBR and PU D by a switch contact as well. The backupfuse should be selected depending on the cross-section of theline and type of installation. Backup fuses of 16 A should beused for the PU D.
3.1 Replacement
If as described under point 3 above an arrester shows a redflag or red LED, it should be replaced by a qualified electrician.The individual class I and II and arresters are plug-in units andcoded according to voltage. When performance in- sulationresistance tests to DIN VDE 0100 part 610, the varistorarresters must be removed, e.g. by lifting off the top section.The arrester must be replaced by one suitable for the ratedvoltage of the system.
4. Connecting the remote signalling
4.1 Remote signalling with monitoring module typePUxCR, PUxBR or PU D
The signalling contact of a PUxCR or PUxBR is a changeovercontact and is connected to terminals 11 and 14. In normaloperation (green flag) terminals 11/12 are closed. In this situationterminals 11/14 are open. In the case of a fault (red flag),terminals 11/14 are closed and 11/12 open. In the PU D thetriggering of the disconnection device is signalled by the openingof an irreversible thermal release. The signalling circuit isconnected with twisted lines (e.g. NYM); parallel routing with theconnecting and earth lines must be avoided here. A protectioncircuit formed by an overvoltage fine protection correspondingto the voltage level reduces interference at and in the evaluator.
4.2 Remote signalling with photoelectric barrier type PU-O/S-E
Every PU C and PU B arrester is suitable for use with remotemonitoring and this can be retrofitted at any time. The transmitter must be clipped on to the top-hat rail to the leftand the receiver to the right of the PU blocks and the devicesconnected to a 230 V supply.
Earth line Cross-section mm2)
Main protective conductor ≤ 16 25 ≤ 35– coming from current source
or protective conductor leaving
– incoming service box or – main distribution board
Phase conductor ≤ 35 50 ≥ 70
Earth line of arrester 10 26 25
Table 1
Overvoltage Protection for low-voltage supplies
B.42
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B
Afterwards, the remote signalling is connected to terminals11/14 and/or 11/12, as already described under point 4.1above. This system allows up to 40 overvoltage arresters to bemonitored simultaneously.
4.3 Approvals
PUxC(R) for 230/400 V power supply networks to ÖVE SN 60parts 1 and 4.
PU units are provided with CE and UL symbols.
Accessories
A system marker is available from LogiMark with the text“Warning! System protected by overvoltage arresters”. Lift offplug-in top section for insulation measurements. This yellowcard (Part No. 175184 1687) can be affixed with self-adhesivetape. Installation specification for PU1 TSG “Overvoltageprotection in power supply networks”.
1. Application
The arrester serves as lightning protection equipotentialbonding at the interface transition 0 to 1 (according to IEC1312-1) in accordance with the requirements of class B to DINVDE 0675 part 6 (draft, Nov 1989), A1 (Mar 1996) and therequirements of class I to IEC 61643-1 (Feb 1998).
Combinations of several overvoltage arresters are frequentlyused as an N-PE arrester in TN, TT and IT systems. The PU 1TSG 50 kA / 1.5 kV-260 V can be used in a combination circuitas a 50 kA sparkover gap between L and N in systemsdesigned for a short-circuit current of 500 A. The use of asealed sparkover gap satisfies the inspection requirements forclass B overvoltage protection systems according to the VDEWdirective (1st ed., 1998).
2. Installation instructions
2.1 Special installation conditions for metal distributionboards
The following points should be taken into consideration wheninstalling a PU x C:
1. The use of a plastic partition to separate it from adjacentmetal parts. It is recommended to incorporate a WTWpartition (Part No. 1058800000) or a WEW/2 end bracket(Part No. 1061200000).
2. The switching voltage of the PU x CR must be reduced to £ 48 V.
3. PU x C modules for Uc 550 V must always be closed withplastic covers.
2.2 Backup fuse
The overvoltage protection devices of the PU series exhibitpassive behaviour in normal operation; no current isconsumed. The necessary protection against short-circuits andoverloads is thus provided by a fuse designed for the type ofinstallation and the cross-section of the connecting lines. In addition, the products of the PU series are tested with a maximum backup fuse (refer to technical data for details).
If the fuse used in the installation is less than or equal to thisvalue, then this can be used as the line protection in theincoming supply. However, if the fuse is larger than that given in the technical specification, additional fuses to suit theconnecting line must be incorporated in the line to the PU module.
B
Overvoltage Protection for low-voltage supplies
B.43
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
2.3 Application
PU 1 TSG (+) modules provide the necessary lightningprotection equipotential bonding for existing lightningprotection systems and incoming supplies.
Enclosed PU 1 TSG modules are preferably installed in thedistribution boards of the building’s electrical installation.
Unenclosed PU 1 TSG+ modules with voltages of 330 or 440V are frequently installed in industrial applications.
3. Maintenance
According to their applications, PU 1 TSG(+) modules aredesigned for high electrical mechanical loads. Faulty arrestersmust be replaced immediately. The arresters may not beopened.
Installation specification for PU 1 TSG(+) overvoltageprotection in power supply networks. May only beinstalled by qualified personnel. During the installation,please observe the connection conditions specific to thecountry of application.
Overvoltage Protection for low-voltage supplies
B.44
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
B
Ordering data TN-C-S 230/400 V with 3+1 circuitClass I (B arrester) Type Order No. Remarks
Sparkover gap 3 x PU 1 TSG 35 kA/0.9 kA-260 V 8561260000 No decoupling necessary
+ 1 x PU 1 TSG 50 kA/0.9kA-260 V 8561230000 as N-PE sparkover gap
or High-power varistor 1 x PU 4 B 25 kA 8381890000 Install behind RCD
Class II (C arrester) Type Order No. Remarks
Varistor PU 4 C TT 3+1 circuit 8416370000
Varistor PU 4 C 8021500000 Install behind RCD
Class III (D arrester) Type Order No. Remarks
Hybrid circuit PU DS 8523740000 Install behind RCD
Hybrid circuit PU D 8411930000 Install behind RCD
Ordering data TN-C 230/400 VClass I (B arrester) Type Order No. Remarks
Sparkover gap 3 x PU 1 TSG 35 kA/0.9 kA-260 V 8561260000 No decoupling necessary
High-power varistor 1 x PU 3 B 20 kA in Summe 8381890000
Class II (C arrester) Type Order No. Remarks
Varistor PU 3 C 8021490000
Class III (D arrester Type Order No. Remarks
Hybrid circuit PU DS 8523740000 Install behind RCD
Hybrid circuit PU D 8411930000 Install behind RCD
Examples of applications in 230/400 V systems
TN-C system applications
TN-C-S system applications
TN-S system applications
B
Overvoltage Protection for low-voltage supplies
B.45
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s
Ordering data IT 230/400 V with 3+1 circuitClass I (B arrester) Type Order No. Remarks
Sparkover gap 3 x PU 1 TSG 35 kA/0.9 kA-260 V 8561260000 No decoupling necessary
+ 1 x PU 1 TSG 50 kA/0.9 kA-260 V 8561230000 as N-PE sparkover gap
High-power varistor 1 x PU 3 B 20 kA 8381890000 Install behind RCD
Class II (C arrester) Type Order No. Remarks
Varistor PU 4 C TT 3+1 circuit 8416370000
Varistor PU 4 C 8021500000 Install behind RCD
Class III (D arrester) Type Order No. Remarks
Hybrid circuit PU DS 8523740000 Install behind RCD
Hybrid circuit PU D 8411930000 Install behind RCD
Ordering data TT 230/400 V with 3+1 circuitClass I (B arrester) Type Order No. Remarks
Sparkover gap 3 x PU 1 TSG 35 kA/0.9 kA-260 V 8561260000 No decoupling necessary
+ 1 x PU 1 TSG 50 kA/0.9kA-260 V 8561230000 as N-PE sparkover gap
High-power varistor 1 x PU 3 B 20 kA + 1 x PU 1 TSG 8381890000 Install behind RCD
Class II (C arrester) Type Order No. Remarks
Varistor PU 4 C TT 3+1 circuit 8416370000
Varistor PU 4 C 8021500000 Install behind RCD
Class III (D arrester) Type Order No. Remarks
Hybrid circuit PU DS 8523740000 Install behind RCD
Hybrid circuit PU D 8411930000 Install behind RCD
Examples of applications in 230/400 V systems
TT system applications
IT system applications
B.46
Ove
rvo
ltag
e P
rote
ctio
n fo
r lo
w-v
olt
age
sup
plie
s