One-way Joist Part 3

Post on 11-Nov-2015

218 views 0 download

description

One way joist construction part 3

Transcript of One-way Joist Part 3

  • that all pans may require diaphragms to resist lateralpressures. However, 14-gauge pans with a depth of16 inches or greater should always be installed withinternal bracing. The soffits of all steel pans shouldbe strengthened with some type of permanentlyattached internal brace, the most common of whichis a welded sheet metal angle at least of the samegauge as the body of the pan. Because the steel lappan system is characterized by offsets, fins andprotrusions as well as chips and dings that resultfrom the removal of the pan sections, the contractdocuments should include guidance and informationon acceptable tolerances for formed surfaces.

    It should be pointed out that care must be takenwith the installation of any embedded items ormechanical inserts or fixtures. If the attachment ofthese items is not considered in relationship to thestripping of these forms they may act as anchorspreventing the removal of the pan forms.Therefore, itis recommended that only center pin soft rivets beused. The center pin of the rivet will remain exposedon the underside of the pan form and can beremoved prior to stripping. This will allow the body ofthe rivet to close as the pan is stripped, permittingthe easy removal of the forms.

    TOLERANCESTolerance guidance can be found in several ACI

    standards and reports. ACI 117, StandardTolerances for Concrete Construction and Materials;ACI 301, Specifications for Structural Concrete; andACI 347R, Guide to Formwork for Concrete, provideinformation on finished surfaces, but do not addresspan joist surfaces specifically. ACI 117 and ACI347R limit offsets and other irregularities based onClass of surface finish. See Table 2. The ACI 117standard might be regarded as the mostauthoritative. The mandatory specification checklistin ACI 117 requires the Architect/Engineer todesignate the intended Class of surface finish andthereby establish the tolerance for form offsets. ACI301 addresses the finishing of formed surfaces inChapter 2 and differentiates between rough formfinishes (those not exposed to public view) andsmooth finishes (exposed to public view). ACI 301requires: Patch tie holes and defects. Remove allfins completely. for smooth formed finishes, butpermits up to 1/4 inch fins for rough finishes. As adefault, Article 5.3.3.5 of ACI 301 calls for the finishto be based on exposure to public view wheresurface finish is not designated in the contractdocuments.

    TABLE 2 Surface Finish Class

    ACI Committee 347 notes that revisions of the347R report are in progress to change the limit forabrupt offsets within Class C finish to 1/2 inch,consistent with ACI 117. Although ACI 347R cautionsagainst using pry bars directly against concrete toremove formwork, this is common practice in manyareas of the country.

    CONCLUSIONSurface irregularities should be expected in pan

    joist construction. It is difficult to patch surface spallssuccessfully. The patch may be more noticeable thanthe spall. The continuing use of the steel lap pan joistform system remains a proven and excellent methodof forming site cast reinforced concrete floor systemsin non-critically exposed applications.

    Figure 2 Lap Pan Shapes

    Figure 3 Setting Lap Pans

    Type ofIrregularity

    Class of Surface Finish(Size of Permissible Defects in Inches)

    Gradual(ACI 347R)

    Abrupt(ACI 117)(ACI 347R)

    For surfaces prominently exposed to public view whereappearance is of special importance.Coarse-textured concrete-formed surfaces intended toreceive plaster, stucco, or wainscoting.

    General standard for permanently exposed surfaces whereother finishes are not specified.

    Minimum-quality surface where roughness is not objectionable,usually applied where surfaces will be concealed.

    A

    1/8

    1/81/8

    B

    1/4

    1/41/4

    C

    1/2

    1/21/4

    D

    1

    11

    Class A:

    Class B:

    Class C:

    Class D: