Asset: P.S. 131 - BROOKLYN, 4305 FT HAMILTON PKWY, New York, 11219
Inspection Id Inspection Type Time In Last Edited
SA : K131 Architectural - Senior 2019-10-04 8:20 AM 2019-10-04 6:19 PM
AA : K131 Architectural - Associate 2019-10-04 8:51 AM 2019-10-04 3:21 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment Areaways 2-5, cornice, louvers, leaders/gutters/downspouts/scuppers,exterior guards, window lintels, security lights, drainage for asphalt,fences, student non-use asphalt and concrete, student use asphalt andconcrete, retaining walls, seating benches metal/wood/plastic, playingsurface-schoolyard, playgrounds southeast and southwest wereinaccessible due to scaffolding and netting at all facades.
Heating and ventilating units in the penthouses (North, South MERs)were inaccessible due to construction materials stored on top of theroof hatches
Principal(s) Information
Principal Name Stamatina Hatzimichalis
Organization P.S. 131 - Brooklyn
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal's comments are as follows: 1. Student and Staff ToiletRooms are in need of an upgrade. 2. Additional electrical power isneeded in Room 412 to support window a/c units. 3. Exterior stairs arein poor condition and need to be upgraded.
Custodian Peter Foti
Fireman Was not present
Building Square Footage 86,000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 4+B+PH+Attic
Comments on the Number of Classrooms 48
Comments on the Year Built 1901
Student Population 853
Staff Population 115
Weather Fair
Facade Photo
Corner of Fort Hamilton Parkway and 44thStreet - East view
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 1 of 52
Main Entrance Photo
Facade A - Fort Hamilton Parkway
Roof Photo
Roof 4 - Southwest view
Have any Systems/Major Building Components been upgraded? Yes
Systems: Coping, Exterior Wall, Chimney, Bulkhead and Parapetmasonry, Roofing, Flashing, Roof Drains, Roof Barriers,Skylight/Roof Vent
Year: Under Construction
Systems: Exterior Stair repairs (main entrance)
Year: 2017
Systems: Exterior Stair repairs, Limited Coping replacement
Year: 2012
Systems: Exterior Stair replacement (Original Building), LimitedParapet repairs
Year: 2010
Systems: Slate Roofing replacement, Limited Foundation Wallwaterproofing (1938 building)
Year: 2007
Systems: Aluminum Double-hung Windows and Exterior Guardsreplacement
Year: 1994
Systems: Complete Roofing replacement except Slate Roof
Year: 1991
Have there been any New Building Additions? Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 2 of 52
Comments on New Building Additions 1938 (+43,000 SF)
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? No
Are SOME floors other than the 1st floor and basement accessible through compliantmeans?
No
Do any of the following spaces exist on the First floor? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs
No
Do any of the following spaces exist in the Basement? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs
Yes
For the rooms that do exist, are SOME of them accessible in the Basement? Yes
Boys and Girls or Unisex accessible toilets exist in the Basement? No
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts No Yes
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies No Change in Elevation
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms Room 221 Yes No Not on Accessible Route
Auditorium 1st Floor Yes No Not on Accessible RouteNo Stage Access
No No
Cafeteria Basement Yes Yes Yes No
Classrooms None on Accessible Route Yes No Not on Accessible Route
Computer Rooms Room 202 Yes No Not on Accessible Route
Gymnasium 3rd Floor Yes No Not on Accessible Route Yes No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 3 of 52
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Rooms & Spaces
Library Room 212 Yes No Not on Accessible Route
Main Office Room 106 Yes No Not on Accessible Route
Multi-purpose Room No
Nurse's Room Room 201A Yes No Not on Accessible Route
Pool No
Science Lab No
Toilet Rooms (Boys) Basement Yes No Water ClosetArrangementTurning RadiusSink ArrangementNo Lever-type Hardware
Toilet Rooms (Girls) Basement Yes No No Lever-type HardwareWater ClosetArrangementTurning RadiusSink Arrangement
Toilet Rooms (Staff) Basement Yes No Water ClosetArrangementSink Arrangement
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InaccessibleInstance on AW2-AW5
Instance Quantity 4
Instance Quantity Uom EACH
InspectedInstance on AW1, AW6
Instance Condition 3 - Fair
Instance Quantity 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 4 of 52
Question Response
EXTERIOR
AREAWAY
Instance Quantity Uom EACH
Deficiency AREAWAY STAIRS: DETERIORATEDTREADS/RISERS/NOSINGS
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
AW1
Violations No violations recorded.
Deficiency AREAWAY DRAINS: DETERIORATED
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 5 of 52
Question Response
EXTERIOR
AREAWAY
Deficiency Photo1
AW1
Violations No violations recorded.
Deficiency AREAWAY SLAB: CRACKS AND SPALLING
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
AW6
Violations No violations recorded.
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Under Construction
COPING Under Construction
CORNICE Inaccessible
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 4 - Between Fair and Poor
Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 6 of 52
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade G
Violations No violations recorded.
Deficiency METAL: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 7 of 52
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Photo1
Facade C
Violations No violations recorded.
Deficiency METAL CLAD: DETERIORATED DOOR - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 3
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade L
Violations No violations recorded.
Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 8 of 52
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade K
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Does not Exist
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 50,000
Replacement Uom S.F.
Under ConstructionInstance on All Facades
Instance Quantity 50,000
Instance Quantity Uom S.F.
EXTERIOR SOFFITS Does not Exist
LOADING DOCK Does not Exist
LOUVER Inaccessible
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 11,000
Replacement Uom C.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 9 of 52
Question Response
EXTERIOR
PARAPETS Inspected
Under ConstructionInstance on All Facades
Instance Quantity 11,000
Instance Quantity Uom C.F.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 24,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inaccessible
ROOF BARRIER Under Construction
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
Under ConstructionInstance on Slate Roof: Roof 1
Instance Quantity 4,000
Instance Quantity Uom S.F.
Under ConstructionInstance on Built-Up: Roofs 2-6
Instance Quantity 19,000
Instance Quantity Uom S.F.
Under ConstructionInstance on Metal: Roof 7
Instance Quantity 1,000
Instance Quantity Uom S.F.
ROOFING DRAINS Under Construction
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 4 - Between Fair and Poor
Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED LINTELS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 10 of 52
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Deficiency Photo1
Roof 5 BH2
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOORAND FRAME
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE DOOR AND FRAME
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 5 BH2
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: GLAZED BLOCKOPEN JOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 11 of 52
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Roof Plan reference
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: PLASTERCRACKS/SPALLING
Roof Plan reference
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 4 BH1
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 12 of 52
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE DOOR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 4 BH1
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Under Construction
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 5 - Poor
Deficiency STONE: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 20
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 13 of 52
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency CAST IN PLACE CONCRETE: DETERIORATED EXPANSIONJOINT
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C1
Violations No violations recorded.
Deficiency STONE: BULGING/DISPLACED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 14 of 52
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency STONE: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 15 of 52
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency STONE: CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency STONE: DETERIORATED JOINTS AT COPING STONES
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 16 of 52
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
RAILINGS Inspected
Condition 5 - Poor
Deficiency BROKEN BRACKET
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 17 of 52
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency DAMAGED
Roof Plan reference
Deficiency Quantity 40
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency RUST - MINOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 18 of 52
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C1
Violations No violations recorded.
STAIRS/RAMPS Inspected
Condition 5 - Poor
Deficiency STONE: DETERIORATED SUBSTRATE
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE SUBSTRATE AND RESET
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 19 of 52
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency STONE: CRACKS, SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 20 of 52
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade K
Violations No violations recorded.
Deficiency STONE: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 21 of 52
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency STONE: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 12,000
Replacement Uom S.F.
EXTERIOR GUARDS Inaccessible
LINTELS Inaccessible
WINDOWS Inspected
Material Type(s) Aluminum, Steel, Solid Wood
InspectedInstance on Aluminum - Double Hung: All Facades
Instance Condition 3 - Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 22 of 52
Question Response
EXTERIOR
WINDOWS
WINDOWS
Instance Quantity 11,800
Instance Quantity Uom S.F.
Installation Year 1994
Source of Installation Custodial Staff
Deficiency ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE
Roof Plan reference
Elevation
Deficiency Quantity 80
Quantity Uom EACH
Potential Action REPLACE BALANCES
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
InspectedInstance on Steel: Facade C
Instance Condition 5 - Poor
Instance Quantity 100
Instance Quantity Uom S.F.
Installation Year 1920
Source of Installation Inspector Estimate
Deficiency STEEL: DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 23 of 52
Question Response
EXTERIOR
WINDOWS
WINDOWS
Roof Plan reference
Elevation
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE WINDOW
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C
Violations No violations recorded.
InspectedInstance on Wood: Facades B, D
Instance Condition 5 - Poor
Instance Quantity 100
Instance Quantity Uom S.F.
Installation Year 1901
Source of Installation Inspector Estimate
Deficiency WOOD: DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 24 of 52
Question Response
EXTERIOR
WINDOWS
WINDOWS
Roof Plan reference
Elevation
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE WINDOW
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency WOOD: BROKEN PANE
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 25 of 52
Question Response
EXTERIOR
WINDOWS
WINDOWS
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 3 - Fair
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED MASONRYFIREPROOFING
Deficiency Location/Instance Basement Tunnel below connector wing, Kitchen Storage Room 1901building
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 26 of 52
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Deficiency Photo1
Tunnel
Violations No violations recorded.
Deficiency CONCRETE COLUMNS/BEAMS:CRACKED/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Header beam at the Ash Hoist Vault
Violations No violations recorded.
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Basement Crawlspace, Boiler Room
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Crawlspace
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 27 of 52
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS Inspected
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Gymnasium Shower Room, Basement Boiler Room
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete, Masonry
Condition 3 - Fair
Deficiency BRICK: CRACKED/SPALLED
Deficiency Location/Instance Basement
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Kitchen Storage Room
Violations No violations recorded.
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Basement
Deficiency Quantity 80
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 28 of 52
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Slab Structure Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Vault/Ash Hoist Doors and Framing Inspected
Condition 5 - Poor
Deficiency WATER INFILTRATION
Deficiency Location/Instance Basement
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Ash Hoist Vault
Violations No violations recorded.
Deficiency DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS ANDFRAMING
Deficiency Location/Instance Basement
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 29 of 52
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Vault/Ash Hoist Doors and Framing
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade L
Violations No violations recorded.
AUDITORIUM Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed H/C Lift
Does not ExistInstance on 1st Floor
Fixed Seating
InspectedInstance on 1st Floor
Condition 1 - Good
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
InspectedInstance on 1st Floor
Stage Inspected
InspectedInstance on 1st Floor
Condition 1 - Good
Deficiency No deficiencies recorded
Stage Curtain Rigging Inspected
InspectedInstance on 1st Floor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 30 of 52
Question Response
INTERIOR
AUDITORIUM
Stage
Stage Curtain Rigging Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CAFETERIA Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on Basement
Floor Finish
InspectedInstance on Basement
Condition 4 - Between Fair and Poor
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Near windows, Center
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near windows
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 31 of 52
Question Response
INTERIOR
CAFETERIA
Floor Finish
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Center, near Stairs
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on Basement
Stage
Does not ExistInstance on Basement
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance 4th Floor bridge
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 32 of 52
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling Inspected
Deficiency Photo1
4th Floor bridge
Violations No violations recorded.
Door(s) Inspected
Condition 4 - Between Fair and Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 107,214, Main Entrance Vestibule (2), Exit Vestibule by Stair A
Deficiency Quantity 5
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 214
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Rooms 105,107,202,208, Corridor near Room 204, and others
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 33 of 52
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Room 208
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Rooms 203,204,211,304,308, and others
Deficiency Quantity 800
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 203
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance 2nd Floor bridge
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 34 of 52
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
2nd Floor bridge
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Corridor near Rooms 201,426
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 201
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Inspected
InspectedInstance on 3rd Floor
Ceiling
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 3rd Floor
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Storage Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Storage Room
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 35 of 52
Question Response
INTERIOR
GYMNASIUM
Door(s)
Violations No violations recorded.
Fixed Equipment
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Seating
InspectedInstance on 3rd Floor
Condition 3 - Fair
Deficiency DAMAGED FIXED SEATING
Deficiency Location/Instance Right Side
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Right Side
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 3rd Floor
Stage
Does not ExistInstance on 3rd Floor
Walls
InspectedInstance on 3rd Floor
Condition 3 - Fair
Deficiency SALT GLAZED BRICK: CRACKS/SPALLING
Deficiency Location/Instance Near windows
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 36 of 52
Question Response
INTERIOR
GYMNASIUM
Walls
Deficiency Photo1
Near windows
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 3rd Floor
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency DETERIORATED/TORN-OUT/MISSING
Deficiency Location/Instance Auditorium to Gymnasium Stair
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Auditorium to Gymnasium Stair
Violations No violations recorded.
KITCHEN Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 3 - Fair
Deficiency METAL PAN: DAMAGED/MISSING
Deficiency Location/Instance Near windows
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 37 of 52
Question Response
INTERIOR
KITCHEN
Ceiling
Purpose of Action LEVEL 2
Deficiency Photo1
Near windows
Violations No violations recorded.
Door(s)
InspectedInstance on Basement
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR
Deficiency Location/Instance Storage Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Storage Room
Violations No violations recorded.
Deficiency METAL: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Entrance, Mop Room
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 38 of 52
Question Response
INTERIOR
KITCHEN
Door(s)
Deficiency Photo1
Entrance
Violations No violations recorded.
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Storage Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Storage Room
Violations No violations recorded.
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Near windows
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 39 of 52
Question Response
INTERIOR
KITCHEN
Walls
Deficiency Photo1
Near windows
Violations No violations recorded.
LIBRARY Inspected
InspectedInstance on Room 212
Built-in Furnishing
InspectedInstance on Room 212
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Ceiling
InspectedInstance on Room 212
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 212
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room 212
Condition 3 - Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Near circulation desk
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near circulation desk
Violations No violations recorded.
Walls
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 40 of 52
Question Response
INTERIOR
LIBRARY Inspected
Walls
InspectedInstance on Room 212
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Inspected
InspectedInstance on 3rd Floor
Alternative use Yes
Ceiling
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 3rd Floor
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Entrance
Violations No violations recorded.
Floor Finish
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Locker Room Lockers
Does not ExistInstance on 3rd Floor
Walls
InspectedInstance on 3rd Floor
Condition 4 - Between Fair and Poor
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Near windows
Deficiency Quantity 180
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 41 of 52
Question Response
INTERIOR
LOCKER ROOM Inspected
Walls
Deficiency Photo1
Near windows
Violations No violations recorded.
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Inspected
InspectedInstance on 3rd Floor
Alternative use Yes
Ceiling
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
Does not ExistInstance on 3rd Floor
Floor Finish
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Partially
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stairs A/4,B/4, Auditorium to Gymnasium Stair
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 42 of 52
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Ceiling
Deficiency Photo1
Stair A/4
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency METAL CLAD WOOD: DETERIORATED DOOR
Deficiency Location/Instance Stairs A/3,C/Basement,D/Basement (2),1
Deficiency Quantity 4
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair D/Basement
Violations No violations recorded.
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency GLASS PANEL: DAMAGED/DETERIORATED
Deficiency Location/Instance Stair A/1,B/1,C/2,E/Basement
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 43 of 52
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Partition
Deficiency Photo1
Stair E/Basement
Violations No violations recorded.
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Stairs B/2,3, Auditorium to Gymnasium/2,3
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/2
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stair C/3
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 44 of 52
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo1
Stair C/3
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 426
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 426
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance 1st Floor by Stair E
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 45 of 52
Question Response
INTERIOR
TOILET ROOMS - STAFF
Floor Finish
Deficiency Photo1
1st Floor by Stair E
Violations No violations recorded.
Stalls Inspected
Condition 5 - Poor
Deficiency RUST - MAJOR
Deficiency Location/Instance Rooms 226,426
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 426
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Room 226
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 46 of 52
Question Response
INTERIOR
TOILET ROOMS - STAFF
Walls
Deficiency Photo1
Room 226
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 307B
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 307B
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 125,325
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 47 of 52
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Deficiency Photo1
Room 125
Violations No violations recorded.
Floor Finish Inspected
Condition 3 - Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Rooms B10,108,208,225,308, and others
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room B10
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Rooms 325,425
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 48 of 52
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Walls
Deficiency Photo1
Room 425
Violations No violations recorded.
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inaccessible
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED COVER
Deficiency Location/Instance Exit 10 Walkway
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Exit 10 Walkway
Violations No violations recorded.
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inaccessible
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 49 of 52
Question Response
SITE
PAVING
Student Non-Use Inspected
Gravel Exists? No
Asphalt Inaccessible
Concrete Inaccessible
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inaccessible
Concrete Inaccessible
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance 44th Street
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
44th Street
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency DAMAGED CURBS
Deficiency Location/Instance 43rd Street, 44th Street, Fort Hamilton Parkway
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 50 of 52
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Photo1
43rd Street
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance 43rd Street, 44th Street, Fort Hamilton Parkway
Deficiency Quantity 1,300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
43rd Street
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InaccessibleInstance on Southeast
InaccessibleInstance on Southwest
PLAYING SURFACE Inspected
Playing Field Inspected
InaccessibleInstance on Schoolyard
Running Track Does not Exist
RETAINING WALLS Inaccessible
SEATING Inspected
Benches Inspected
Concrete Does not Exist
Metal/Wood/Plastic Inaccessible
Bleachers Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131
PB/A&W Print Date: 9/14/2020Page 51 of 52
Question Response
SITE
STAIRS/RAMPS: EXTERIOR
Railings Inspected
Condition 3 - Fair
Deficiency MISSING
Deficiency Location/Instance 43rd Street
Deficiency Quantity 8
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
43rd Street
Violations No violations recorded.
Site Cheek/flank Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs/ramps Inspected
Condition 2 - Between Good and Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance 43rd Street
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
43rd Street
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K131