Nexans Euromold Bushings, Oil Insulated 24kV 1250A 672T1 Interface D

Post on 10-Feb-2017

156 views 3 download

Transcript of Nexans Euromold Bushings, Oil Insulated 24kV 1250A 672T1 Interface D

8

05/2

015

672T1INTERFACE D

EQUIPMENT BUSHING

Up to 24 kV - 1250 A

Equipmentbushing

type

VoltageUm (kV)

CurrentIr

(A)

672T1

K672T1

12

24

1250

1250

ApplicationFor use in equipment insulated with oil fluid, typically for transformers, switchgear, capacitors...

6/10 (12) kV6.35/11 (12) kV

8.7/15 (17.5) kV12/20 (24) kV

12.7/22 (24) kV

DesignThe equipment bushing is amoulded epoxy insulated part inaccordance with CENELEC EN50180.

Technical characteristics Each bushing is tested forAC withstand and partial discharge prior to leavingthe factory.

Ordering instructionsTo order the equipment bushing, specify the type.For use in potentially explosive atmospheres (for 12 kV max.). Order: -/ATEX.

Specifications and standardsThe bolted type equipment bushings 672T1 meet the requirements of IEC 60137.

Dia. 76

M16

1.5

Dia. 114

221

350

Dia.32

32

stainless steel flange

M16

Minimum oil level: -12 kV: 40 mm -24 kV: 50 mm

In mm.

Natalie Lundie
Power stamp

9

672T1 bushing

In mm.

140

170

60°

60°

10

equipmentconnection

fixing studs andnuts M10

sealing gasket

equipment

fixing flangetype : MK600-1(antimagnetic)

bushing interface

FIXINGS FOR EQUIPMENT BUSHINGS

Bushing fixing flangeTo order the bushing fixing flange, simply specify MK600-1.

Natalie Lundie
Power stamp