Martin StoesslR&D Manager

Siemens Transformers Austria - Weiz

1892

1979

2007

2

Transformer reliability

Ability to

• perform its required functions

• under stated conditions

• for a specified period of time

Failure

• termination of the ability

It is often reported as a probability

3

Transformer Reliability - based on ANSI C57. 117 (1986)

Definitions:• Population:

Transformers that have given common specific characteristics

• Failure:

Termination of a transformer to perform its specific functions

• Failure with forced outage:

Failure of a transformer that requires its immediate removal from the system for more than 1 day in conjunction with internal measures

• Failure Rate FR [%] = (nF / SY) 100

The ration of the number of failures with forced outage of a given population over a given period of time to the number of accumulated service years for all transformers in that period of time

• Mean Time Between Failures MTBF [years] = 1 / FR

Mean Time between failures (MTBF) = 1 / FR (years)

N: Number of units in service within evaluation period (floating 10 years)

SY: Number of service years accumulated with [N] units in service

nF: Number of failures with forced outage of a population within the evolution period

4

Transformer Reliability - based on ANSI C57. 117 (1986)

FRe and MTBF as a degree of Reliability:Failure rate and reliability are related in the following way:

R = e-λt

t ... time in year

λ … failure rate in failures per transformer-years of service (λ=nF/SY)

e ... 2.718

• MTBF is considered to be the reciprocal of failure rate for purpose of estimating reliability:

MTB = 1 / λ

• MTBF and reliability are related in the following way:

R = e-t/MTBF

• Example:

Given a constant MTBF of 500 years

The reliability R of a transformer surviving t years of service without a failure would be shown as below: λ = 0.002

t R

1 0.9980

5 0.9900

10 0.9802

20 0.9608

30 0.9418

For a given MTBF of 500 years the probability of a transformer surviving 20 years of service without failure is 96.08%

5

CIGRE activities related toTransformer Reliability

SC A2 Reliability Advisory Group 2006

• “Bathtub” curve

• Reliability databases

WG A2.37: Reliability Surveys

• difficult to get reliable data

WG A2.43: TR Bushing reliability (Um≥72,5 kV)

• Started in June 2010

Plans to work on topics like post mortem and end of life decision.

6

Reliability of main accessories

A2 session papers in Paris 2010 showed that

• accessories cause a significant proportion of the power transformer major failures.

• new bushing and tap-changer technologies were introduced recently

• these technologies and their impact on maintenance have to be reviewed

Future task of CIGRE Study Committee A2

7

Operation conditions

Thermal

stress

Electrical

stress

Ambient

stress

Mechanical

stress

Transformer

operating stress

of the electrical insulation system

8

Electrical insulation system

transformer insulation life [1]

total time between initial state (new) and the final state when due to normal service

• thermal ageing

• dielectric stress

• short-circuit stress

• mechanical movement

could result in a high risk of electrical failure

[1] IEC 60076-7 Loading guide for oil-immersed power transformers

9

Operation conditions

Thermal

stress

Electrical

stress

Ambient

stress

Mechanical

stress

Transformer

operating stress

of the electrical insulation system

10

Thermal stresses and ageing

Caused by the heating due to no-load and load losses

• Chemical

• Polymerization

• Depolymerization

• Physical

• Diffusion

• Expansion/contraction

11

Thermal ageing retardation

Control possibilities

• Reduce temp. rises by new cooling stage control (overall loss of life optimization)

• Hot spot factor determination and control

• Proper material selection

• Initial moisture content

• Air sealing

• Forced cooling

• Design know how

[1] IEC 60076-7 Loading guide for oil-immersed power transformers

[1]

12

Manufacturer activities

• Continue verification cooling calculations

• Interfaces for dynamic calculation

• Cooling calculation for alternative insulation fluids

• Repair experience

• Post mortem analysis

• Material tests

• Supplier control

13

Operation conditions

Thermal

stress

Electrical

stress

Ambient

stress

Mechanical

stress

Transformer

operating stress

of the electrical insulation system

14

Electrical stresses and ageing

Caused by the electrical field and the interaction within the insulation system

• Increased local temperatures

• Partial Discharge

• X-Wax

• Leakage current

• Creeping distance

• Electrical treeing

• Static electrification

could appear

15

Electrical ageing retardation

Control possibilities

• Proper material selection

• Supplier quality control

• “PD free” transformers

• Design and processingknow how

• Calculation possibilities

16

Manufacturer activities

• Continuous adaptation of the transients package to needs of design departments, and to customer

• Testing and evaluation of new insulation components and materials

• Basic reproducible test and comparative investigations

• Optimize technology to ease production and deliver PD-free products

17

Operation conditions

Thermal

stress

Electrical

stress

Ambient

stress

Mechanical

stress

Transformer

operating stress

of the electrical insulation system

18

Ambient stress

Caused by different ambient stresses the inner & outer systems of a Transformer could be damaged

• Humidity

• High/extreme low ambient temperature

• Altitude

• Pollution

• Wind

• Earthquake

19

Operation conditions

Thermal

stress

Electrical

stress

Ambient

stress

Mechanical

stress

Transformer

operating stress

of the electrical insulation system

20

Mechanical stress

Caused by acceleration during

• Transport

• Installation

• Operation

inner & outer systemsof a Transformer might be damaged

21

Operation conditions

• Real case studies shows a combination of stresses as well as interactions

Thermal

stress

Electrical

stress

Ambient

stress

Mechanical

stress

Transformer

operating stress

of the electrical insulation system

22

Real case study #1

Sealed GSU Transformer

Manufactured in 1952

Power: 8 MVA

Rating: 115,5 / 5,25 kV

Measurement of Degree of Polymerization (DP-value)in 1982 (after 30 years!!!)

• Phase 1: HV-winding, shielding ring: DP = 884

• Phase 2: HV-winding, leads: DP = 902

• Phase 3: HV-winding, winding insulation: DP = 721

23

#1: Actual Investigations 2011 (after around 60 years of operation)

• HV leads ~ 300

• LV leads ~ 100

• DP-distribution over winding height

• DP average = 300 – 400

24

Real case study #2

Sealed GSU Transformer

Manufactured in 1966Power:103 //51,5 / 51,5 MVA

Rating:403// 16 / 16 kV

Measurement of

T1Q: 642 T1R: 449

T1S: 449 T1T: 704

• Samples were taken from LV – flexible connector

• Tests were performed according ISO 14453:1997

25

#2: Refurbishment Result in 2006

Measurement of De-polymerization (DP – value)

• We expect a transformer rest – life time of >13 years under the used load – conditions for all 4 transformers.

• This assessment is based on the results of the performed measurements, the

fact that the transformers are

new sealed and that the

insulation oil is purified.

26