Lightning Protection and Grounding Solutions for · PDF fileBogdan (Bogey) Klobassa Times...

Post on 07-Mar-2018

228 views 4 download

Transcript of Lightning Protection and Grounding Solutions for · PDF fileBogdan (Bogey) Klobassa Times...

Bogdan (Bogey) Klobassa

Times Microwave SystemsAn Amphenol Company

Lightning Protection and Grounding Solutions for Wireless Networks

Aircraft triggered return stroke

Few facts about the lightning event

• Typically, more than 2,000 thunderstorms are active throughout the world at any given moment producing on the order of 100 flashes per second. As our society becomes more dependent upon computers and information/communications networks, protection from system disruptions becomes essentials.

• During fair weather, a potential difference of 200,000 to 500,000 Volts exists between the earth surface and ionosphere. In a lightning event this potential will be responsible for lightning discharge currents of up to 100,000 Ampere.

• The average length and duration of each lightning stroke vary, but typically average about 30 microseconds producing average peak power per stroke of about 1 (one) Trillion Watts.

• The temperature along the lightning channel (flash) during the electrical discharge is in the order of 20,000 degrees Celsius (three time the temperature of the surface of the Sun)

• Wireless networks rely on communication towers for its transmission of Radio Frequency putting them statistically in a very high exposure zone. Average communication site in Florida, during thunderstorm season, will be exposed to 18 to 20 lightning strikes a year.

Annual lightning flash rate - global

The lightning event

The lower part of a thundercloud is usually negatively charged. The upward area is usually positively charged. Lightning from the negatively charged area of the cloud generally carries a negative charge to Earth and is called a negative flash. A discharge from a positively-charged area to Earth produces a positive flash

Definition of pulse wave-shape

Measured peak lightning currents

Ref: W.C. Hart, E. W. Malone, Lightning and Lightning Protection, EEC Press, 1979

Times to peak lightning currents

Ref: W. C. Hart, E. W. Malone, Lightning and Lightning Protection, EEC Press, 1979

Lightning current distribution on coaxial cable

Any Conductor is an Inductor !

Communications Radio Tower Inductance

Inductance considerations

Communication mast as voltage divider

Tower Grounding

Tower Leg Grounding (UFER vs. AWG #2)

Tower Leg Grounding

Rolling ball theory-structural protection

150’ RadiusStriking Distance(100’ for flammableliquids)

Zone of ProtectionPer ANSI/NFPA 780

Placement of air terminals

The Zone of Protection from lightning strikes can be defined using the rolling sphere model.

High rise building grounding considerations

Charge Transfer Systems and Early Streamer Emission air terminals

Be Aware!!!

Remotee Radio Heads and DAS

Application concerns and risk assessment:

•Equipment susceptibility due to the lightning exposure•High cost of repair•What is the level of protection included in the TTE against IEC, Telcordia, IEEE standards?•Are all ports for RF/Power/Data and Telemetry hardened to withstand this environment?•Dense design package of TTE vs. Dielectric withstand to EMP

Roof top mast and antennas

Grounding at bottom of the rack creates a path for surge current to traverse the rack, upsetting or destroying equipment.

Proper grounding of the equipment rack. If coax jumper cables enter at the top, ground high. If they enter low, ground low. There will be minimal current flow through the rack.

Equipment grounding with coax entering from a high mounted entry panel

Service entry bulkheads

After the fix

External view of traditional method and proposed solution

Traditional method consisting of:• High material and labor cost• Lack of provisions for other service entries• Theft exposure• Very high impedance return path to ground• High preventative maintenance

Proposed method:• Addresses theft issue• Does not require external shield grounding kits• Makes provisions for Coax/EWG/Data/DC and fiber• Minimal labor cost• All prep work performed at the shelter manufacturer

Interior view of traditional method and proposed solution

Traditional method:• Requires separate Inside MGB (IMGB)• Trapeze or other method to ground SPDs• Performance affected by long ground wires• High impedance IMGB ground conductor• Single point ground by installation• High ground loop probability

Propose method:• All RF protectors bulkhead mounted for best surge performance• Assembly accommodates different wall thickness• Provisions for grounding of all protectors to the same SPG• Low impedance ground path for lightning current • Control of MGB potential rise due to low “L” of assembly• Accommodates for additional equipment mounting

RF ProtectorsBulkhead mounted

2/0 Conductorsto ground

Ground lead considerations for installation of RF protectorsApplied surge wave-shape 6KV/3KA (8X20us)

Bulkhead mounted SPD without added ground “L”Surge return directly connected to protector ground

+25.6V, -9.2V

+

-

Su rge

Gen er ator

DUTCe nter Pin

Chass isGround

Voltage Measuredat O-scope

+

-

Surge

Generator

DUTCenter Pin

Voltag e Measured at O-sco pe

GroundInductance

Effects of 1.5 ft ground lead inductance of #1 AWG Cu wireVoltage and energy throughput drastically increases

+544V, -176V

Note: The length of the grounding conductor connected to any lightning protection device has a major effect on the protector performance as illustrated by the above test. Leadless/Bulkhead installation technique for RF lightning protection devices will eliminate this additive voltage and energy throughput to the protected equipment

True single point grounding (SPG) by design

Feed-throughLP-FT-DFDF

Blank hole plugLP-NP/DP

Lightning Protector

Installed views

Typical ground resistance values

– NFPA 70 NEC < 25 OHMS or two rods– IEEE Standard 142 Equipment Dependent– IEEE Standard 1100 < 5 OHMS– Motorola Standard R-56 < 5 OHMS– Verizon Wireless 8501 < 5 OHMS– Bell Mobility Cellular < 5 OHMS– Essilor < 3 OHMS– GE Medical Systems < 2 OHMS

When everything else fails, there is always plastic tie!

RF protection circuit topologies

Surge ProtectedA dc blocked protector uses a gas tube connected from the center pin of the “surge” connector to the protector body and a discrete component capacitor in series from the top of the gas tube to the “protected” connector center pin.

A dc blocked high pass filter has a high current rated inductor connected from the center pin of the “surge” connector to the protector body. A conductor is continued from the top of the inductor to a mechanical capacitor in series to the center pin of the “protected” connector.

The solid state dc pass/protect protector, with a dc blocking capacitorin the RF path from connector to connector, is bi-directional, and includes an RF isolated high

current bi-polar diode. The diode is RF decoupled with an inductor from each connector center pin.

Surge Protected

Bi-directional

A non-dc blocked protector (“straight-through”) will share the incoming currentwith a resistive component (RF coupling loop). The gas tube will turn on when the current through the

resistive component in the equipment input rises enough to create a voltage drop reflected back to the protector’s gas tube.

Gas Tube

Typical performance parameters for DC blocked (20-1000MHz) RF lightning protector

•DC blocked design •Multi-strike capability•Broad band performance up to 1GHz•Exceptional RF characteristics•Universal bulkhead and flange mounting•Elongated Female connectors•Weatherization gasket included •Solid Brass design / White Bronze plating•Phosphor Bronze center pin construction•Silver plated center pin•Insertion Loss: < 0.1dB•Return Loss: <-26dB•VSWR: <1.1:1 •Energy throughput: <200uJ• IP67 Weatherized

RF lightning protector surge performance examples

User voltage: 5VdcVoltage throughput: <12VpkEnergy throughput: <110uJ

Voltage throughput: <2VpkEnergy throughput: <150nJ

Passive Intermodulation (PIM) considerations

Tower

Antenna & ODU

IDU

Shelter

RF Protector

LMR400 LMR200

RF protector

LMRJumper

Broadband protection - antenna incorporated into the ODU

RF protector

Tower

Antenna

IDU

Shelter

Lightning Protector

LMR400 LMR200

Lightning Protector

LMRJumper

Broadband protection - antenna separated from ODU

Lightning Protector

ODU

LMR Jumper

Protector Grounding ???

Lightning damage to the RF protector

Images of Lightning damaged RF protector

Reflected Power Issue

LP-SPT (Surge Protector Tester)

LP-SPT Specifications:

Dimensions: 9.0” x 4.0” x 1.5”Weight: 1 pound Power: 9V battery, 2 each includedDisplay: 3.5 digit LCDTest Output: 1000V / 1mA DUT interfaces: One type-N female, one type-N maleCarrying Case: Rugged black nylonN–Alligator Clip Adaptor:Included

Thank you and Questions ???