Light is the solution ENCELIUM® EXTEND Networked Light Management System Wireless System Installation Manual
Light is OSRAM
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page ii of 35
Table of Contents
TABLE OF CONTENTS ......................................................................................................................................................................... II
THE ENCELIUM® EXTEND WIRELESS SYSTEM .................................................................................................................................. 4
OVERVIEW .................................................................................................................................................................................. 4
ENCELIUM® EXTEND LMS WIRELESS COMPONENTS – CAD LEGENDS ........................................................................................... 5
ENCELIUM® EXTEND WIRELESS SYSTEM RISER DIAGRAM .............................................................................................................. 6
LABOR ESTIMATES FOR ENCELIUM® WIRELESS DEVICES INSTALLATION ...................................................................................... 7
WIRELESS CONTROL MODULE (WCM) .............................................................................................................................................. 8
WCM INSTALLATION METHODS...................................................................................................................................................... 8 Fixture Mounting .................................................................................................................................................................. 8 Junction Box Mounting ........................................................................................................................................................ 8
WIRING DIAGRAMS............................................................................................................................................................................. 9
WCM WIRING DIAGRAMS ............................................................................................................................................................. 9 WCM to Dimming Ballast/LED Driver Wiring ......................................................................................................................... 9 WCM to Non-Dimming Ballast/LED Driver Wiring .................................................................................................................. 9 WCM to OCS Wiring .......................................................................................................................................................... 10
WCM/GB II INTEGRATION - WIRING DIAGRAMS .............................................................................................................................. 11 WCM to OCS Wiring via SIM .............................................................................................................................................. 11 WCM to PHS Wiring via SIM .............................................................................................................................................. 11
UL924 COMPLIANCE – WIRING DIAGRAMS .................................................................................................................................... 12 LCM Sense ........................................................................................................................................................................ 12
ENCELIUM® EXTEND WIRELESS SENSORS ..................................................................................................................................... 13
INSTALLATION METHODS ............................................................................................................................................................. 13 Ceiling Tile Installation ........................................................................................................................................................ 14 Drywall Installation .............................................................................................................................................................. 16 Metal Surface Installation .................................................................................................................................................... 16 Installing the Mask .............................................................................................................................................................. 17
INSTALLATION METHODS USING THE ACCESSORIES .......................................................................................................................... 18 Junction Box Installation ..................................................................................................................................................... 18 Knock-out Mounting .......................................................................................................................................................... 20
ENCELIUM EXTEND WIRELESS WALLSTATIONS ............................................................................................................................. 21
INSTALLATION DETAILS – WALL MOUNT ......................................................................................................................................... 21 Installation with Decorator or Multi Gang Wall Plate ............................................................................................................ 23
INSTALLATION DETAILS - SURFACE MOUNT ..................................................................................................................................... 26
ENCELIUM EXTEND WIRELESS MANAGER (WM) ............................................................................................................................. 28
INSTALLATION DETAILS ................................................................................................................................................................ 28 Ceiling Tile Mount ............................................................................................................................................................... 28 Wall Mount ......................................................................................................................................................................... 30
SYSTEM SUPPORT UNIT (SSU)......................................................................................................................................................... 31
ETHERNET SWITCH .......................................................................................................................................................................... 31
INSTALLATION DETAILS ................................................................................................................................................................ 31
APPENDIX ......................................................................................................................................................................................... 32
LUMINAIRE CONTROL MODULE (LCM) ........................................................................................................................................... 32 SENSOR INTERFACE MODULE (SIM) .............................................................................................................................................. 32 CONTACT CLOSURE USING SIM & WIRE TABLE ............................................................................................................................... 32 LCM WIRING DIAGRAMS............................................................................................................................................................. 33
LCM to Fixed Output Ballast/LED Driver Connection .......................................................................................................... 33 LCM to Dimming Ballast/LED Driver Connection ................................................................................................................. 33
ALC WIRING DIAGRAM ............................................................................................................................................................... 33 SIM to OCS Connection ..................................................................................................................................................... 34 SIM to Photo Sensor Connection ....................................................................................................................................... 34 SIM/Photo Sensor Mounting Detail ..................................................................................................................................... 34
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page iv of 35
The ENCELIUM® EXTEND Wireless System Overview
The ENCELIUM® EXTEND Networked Light Management System (LMS) is a computer network-based system that allows smart control of lighting fixtures and lighting-related devices wirelessly. Each component is individually addressed. The main components of this system include:
• System Support Unit (SSU): Server
• Wireless Manager (WM): Control Unit/Device Controller
• Wireless Control Module (WCM)
• Wireless Wallstation
• Wireless Control Module (WCM)
• Wireless Sensor
Note: SIM (Sensor Interface Module) & LCM (Luminaire Control Module) are ENCELIUM control devices typically used in ENCELIUM GreenBus II® architecture. These devices can be used in ENCELIUM wireless installations if the project design warrants the use of these devices.
ENCELIUM wireless control network connects all field devices such as WCM and wireless wallstations with wireless managers. The ENCELIUM wireless system has the following characteristics:
• Automatic assignment node addresses
• Automatic recovery of lost nodes
• Wireless managers are networked together with the via a dedicated LAN (CAT-5, Ethernet cabling), or via the existing tenant network
ENCELIUM Wireless System installation work consists of:
• Installing wireless control modules (WCMs), wireless managers (WMs), wireless sensors & wireless wallstations
• Installing the SSU in appropriate equipment closets
• Installing Sensor Interface Module (SIM), Luminaire Control Module (LCM), etc. if low voltage device connectivity is indicated
• Interconnecting SSU and WMs via CAT-5 data cabling or tenant network
When installing ENCELIUM wireless components, safety precautions, wiring diagrams and installation details shipped with each ENCELIUM LMS component should be followed. Refer to the Product information bulletins and wiring diagrams available on the ENCELIUM website at www.encelium.com/en/technical-information for additional component specific information.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 4 of 35
Conceptual view of ENCELIUM® EXTEND LMS Wireless System is shown below:
Note: Router (that implements the necessary forwarding and firewall rules) allows only the ENCELIUM management traffic to pass. All other communication between the two networks are blocked.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 5 of 35
ENCELIUM® EXTEND LMS Wireless Components – CAD Legends
Symbol Description
Wireless Control Module (WCM)
Wireless Sensor – SCPPH-450 (Coverage 450 sq. ft.); SCPPH-1500 (Coverage 1500 sq. ft.)
Wireless Wallstation
Wireless Manager (WM)
SSU (System Support Unit), 1SSU required per building. Requires 120 VAC normal power.
Ethernet Switch, 16 –Port 10/100, Rack Mount (1U); Use PoE injectors to connect WMs or use PoE enabled switches. Ethernet network cables that are used to connect WMs, SSU and switch are limited to a maximum length of 300 ft. (Ethernet Limitation)
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 6 of 35
ENCELIUM® EXTEND Wireless System Riser Diagram
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 7 of 35
Labor Estimates for ENCELIUM® Wireless Devices Installation
Labor Task Installation Details No. Of Wire Connections due to ENCELIUM devices
Est. Labor Per
Install WCM to an existing fixture
• Secure WCM using knockout and retainer nut in fixture/junction box
• Connect line voltage AC power to WCM and fixture • Connect 0-10V dimming conductors if applicable
n/a 3 2
15 minutes
Retrofit existing fluorescent fixture ballast and install WCM
• Remove existing ballast • Install new ballast • Secure WCM using knockout and retainer nut in fixture/junction
box • Connect line voltage AC power to WCM and ballast • Connect 0-10V dimming conductors if applicable
n/a n/a n/a 3 2
20 minutes
Install wireless sensor • Mounting to ceiling tile or metal surface n/a
1 minute
Install wireless wallstation • Surface mount n/a
<5 minutes
Install wireless wallstation • JBox mount n/a <5minutes
Install ceiling/wall mount (low-voltage) occupancy sensor or photo sensor
• Install SIM onto junction box using knockout and retainer nut • Install sensor onto junction box • Connect SIM to sensor
n/a n/a 3
15 minutes
WM • Wall Mount • Ceiling Mount
n/a n/a
5 minutes 10 minutes
Note: GBII component installation details are discussed in ENCELIUM EXTEND GBII Installation Manual.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 8 of 35
Wireless Control Module (WCM) The OSRAM WCM provides both dimming and switching functions. The WCM connects to the following devices to be controlled by the ENCELIUM® EXTEND
Wireless System:
• Luminaires – Switching, 0 -10V dimming and DALI
• Low-voltage sensors – Connected directly or via SIM
The WCM has an additional GreenBus II® port to facilitate communication with GBII components. The GBII channel can be run a maximum of 20 ft. from the WCM to the compatible GBII equipment. Only one GBII device can be connected a WCM. See WCM Wiring Diagrams and WCM Installation Methods.
WCM Installation Methods
WCM can be mounted on the fixture or Junction Box.
Fixture Mounting
Junction Box Mounting
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 9 of 35
Wiring Diagrams WCM Wiring Diagrams
WCM to Dimming Ballast/LED Driver Wiring
WCM to Non-Dimming Ballast/LED Driver Wiring
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 10 of 35
WCM to DALI Ballast/LED Driver Wiring
WCM to OCS Wiring
The configuration shown below (WCM being used to connect an OCS) does not the allow the use of WCM GBII port.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 11 of 35
WCM/GB II Integration - Wiring Diagrams
WCM to OCS Wiring via SIM
WCM to PHS Wiring via SIM
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 12 of 35
WCM to ALC Wiring
UL924 Compliance – Wiring Diagrams
LCM Sense
In this scenario, LCM is acting as the sensing device.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 13 of 35
ENCELIUM® EXTEND Wireless Sensors The ENCELIUM EXTEND Wireless System utilize ENCELIUM wireless sensors. These sensors require no wiring.
These sensors have both occupancy sensing and daylight measurement capabilities.
Note: ENCELIUM EXTEND Wireless System does allow 24V sensor (low-voltage) connectivity. These sensors can be either connected directly to the WCM or via SIM as shown in the wiring diagram.
Refer to ENCELIUM product information bulletins for Sensors, WCM and SIM, wiring diagrams and ENCELIUM project-specific component layout. Product information bulletins and wiring diagrams are available on the ENCELIUM website at www.osram.us/encelium
Typical occupancy sensors used in ENCELIUM installations are shown below:
ENCELIUM EXTEND Wireless Sensor(s)
Installation Methods
ENCELIUM EXTEND Wireless Sensor Front & Rear Views are shown below:
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 14 of 35
Ceiling Tile Installation
1. Remove the mounting plate. Twist counter clockwise using your fingers and lift.
Upon removing the mounting plate the sensor rear view will look as shown below exposing the case bottom of the sensor.
2. Place the sensor base flush to the ceiling tile. Insert the supplied helical and/or thumb screws to secure the sensor mounting plate to the ceiling tile. Helical screws are suggested for ceiling and thumb screws are suggested for drywall mounting.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 15 of 35
3. Install the supplied batteries as per polarity signs indicated within the battery compartment.
4. Install the main sensor assembly to the mounting plate that has been already attached to the ceiling tile (step 2 above).
5. Slightly rotate the sensor clockwise until it snaps in with the mounting plate.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 16 of 35
Drywall Installation
Except step 4, all steps outlined in Ceiling Tile Installation apply. Drill a 3/16” hole on the drywall and install the anchor first as shown below.
Metal Surface Installation
Make sure nickel plated magnets are attached to the ceiling grid or to any other metal surfaces such as a Junction Box.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 17 of 35
Installing the Mask
Masks can be used to create specific patterns of sensor coverage.
ENCELIUM provides three different masking options:
Note: Use an X-Acto knife when removing plastics from the customizable mask.
1. Remove the ring (lens surround) from the sensor assembly. This can be achived by using your thump and rotating the ring counter clockwise.
2. Place the supplied mask (Hallway Mask is chosen for illustration) as shown and slightly rotate clockwise until it latches.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 18 of 35
Installation Methods using the Accessories
Additional mounting methods are possible by using the ENCELIUM Sensor Accessory kit. The ENCELIUM Sensor Accessory Kit is a separate package (i.e. they are NOT part of the ENCELIUM Wireless Sensor package) and contain the following components:
1. Cover Ring – Junction Box Installation 2. Cross Bar – Junction Box Installation 3. Nut – used for knock-out Mounting 4. Knock-out Mount
Junction Box Installation
1. Install the cross bar to the octogonal junction box.
Note: As shown below, the side of the cross bar with extrusion should be facing the JBox base.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 19 of 35
2. Position the cover ring on the junction box and turn slightly until the it latches. You may need to push the latching mechanism slightly downwards.
3. Remove the mounting plate from the sensor assembly. Twist counter clockwise using your fingers and lift.
4. Place the sensor assembly (from Step 3 above) and turn slightly until it latches with the cover ring.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 20 of 35
Knock-out Mounting
Use the nut and the knock-out mount supplied with ENCELIUM Sensor accessory for knoct-out mounting puposes.
1. Scew in the knock-out mount through the ceiling tile as shown below and install the nut.
2. Remove the mounting plate from the sensor assembly. Twist counter clockwise using your fingers and lift.
3. Place the sensor assembly (from Step 2. above) on top of knock-out mount (from Step 1. above) and twist slightly until the sensor assembly latches with the knock-out mount.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 21 of 35
ENCELIUM EXTEND Wireless Wall Stations
The ENCELIUM® EXTEND Wireless System utilize ENCELIUM wireless wallstations. These wallstations require no wiring.
Note: ENCELIUM EXTEND Wireless System does allow ENCELIUM EXTEND GreenBus II® wallstations (low-voltage). These wallstations can be connected directly to the WCM.
Refer to ENCELIUM product information bulletin for Wireless Wallstations, wiring diagrams and ENCELIUM project-specific component layout.
Product information bulletins (PIBs) and wiring diagrams are available on the ENCELIUM website at www.osram.us/encelium
Installation Details – Wall Mount
Shown below are ENCELIUM EXTEND Wireless Wallstation Front and Rear Views:
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 22 of 35
1. Install the mounting bracket using the supplied screws. Ensure that the ENCELIUM logo and SINGLE GANG labels are facing up.
2. Install the supplied (2) AA batteries to the wallstation assembly. Pay attention to the battery polarity indicators.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 23 of 35
3. Place the wallstation assembly into the mounting plate and push gently until ‘clicks’ are heard. This confirms that the pieces are secured.
Installation with Decorator or Multi Gang Wall Plate
The ENCELIUM EXTEND Wallstation can also be installed with a off the shelf Decorator style wall plate. Multi gang wallstation installations require multi gang decorator wall plate.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 24 of 35
1. Remove the button assembly from the ENCELIUM Wall Plate. This can be achieved by pressing the wall plate with your thumbs near the button assembly.
2. Install the supplied wall strips to the wallstation until they snap in.
3. Install the supplied batteries as shown in Installation Details – Wall Mount, Step 2. 4. Orient the mounting bracket such that the DECORATOR and MULTI GANG labels are facing up. Insert the wallstation
button assembly into the mounting plate until ‘clicks’ are heard. Clicks confirm that the pieces are secured.When installed properly wall switch buttons will not be sticking out of the mounting bracket.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 25 of 35
5. Install the switch assembly (with mounting bracket) to the JBox using the supplied screws.
6. Using dry wall screws, screw in the decorator face plate.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 26 of 35
Installation Details - Surface Mount
ENCELIUM EXTEND Wall Station Surface Mount Kit is required for this installation type.
1. Screw in the surface mount kit to the wall or use adhesive tape.
Note: Screws and adhesive tape are NOT included in the ENCELIUM EXTEND Wallstation Surface Mount Kit.
2. Install the supplied (4) AAA batteries. Pay attention to the battery polarity indicators.
3. Separate the battery housing from the main wallstation assembly. Use a small screw driver and gently lift the latches from the wallstation assembly. Switch assembly implies the wall mountable ENCELIUM Wallstation.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 27 of 35
4. Push the wallstation assembly (from Step 3 above) into the faceplate frame until multiple clicks are heard. This confirms that the pieces are secured.
5. Attach the wallstation assembly (from Step 4 above) to the surface mount kit until it snaps in.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 28 of 35
ENCELIUM EXTEND Wireless Manager (WM) The ENCELIUM EXTEND Wireless Manager establishes wireless connection and processes data to and from lighting control devices. Each ENCELIUM EXTEND Wireless Manager must be connected to an Ethernet (PoE) Network Switch using standard CAT-5 or greater Ethernet data cabling. In large installations there may be multiple WMs, which can be distributed around the controlled space, such as individual floors of an office building. Each WM must be connected to an Ethernet Network. The WMs are also powered using Power Over Ethernet (PoE). A PoE Network Switch can be used, otherwise a PoE injector must be placed after the network switch.
The WM supports two mounting methods, Ceiling Tile Mount and Wall/Junction Box Mount.
Installation Details Ceiling Tile Mount
ENCELIUM EXTEND Wireless Manager with ceiling mount accessories.
1. Cut a hole on the ceiling using the ENCELIUM supplied template.
Note: Use the cardboard cutout used to hold the ceiling mount barckets for template.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 29 of 35
2. Assemble the WM and the ceiling mount bracket together. Push the ceiling mount bracket until the lock snaps into the groove.
3. Push the assembled WM through the ceiling tile as shown below.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 30 of 35
4. Place the upper bracket on to the WM (above the ceiling tile from the plenum area) until it locks with lower bracket installed in Step 2.
Wall Mount
1. Align the WM screw holes with the screws on the Junction Box (Switch wall box) as shown below and slide slightly to secure it with the junction box.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 31 of 35
System Support Unit (SSU) The OSRAM SSU is the ENCELIUM EXTEND LMS server, which must be interconnected to every ENCELIUM EXTEND Manager. It stores all ENCELIUM LMS configuration data. It downloads system configuration
data to the ENCELIUM EXTEND Manager and stores data received from the ENCELIUM EXTEND Manager. It is typically installed in an IT or communications closet. It requires power from a 120VAC receptacle and one or two CAT-5 data connections. The SSU can be directly connected to a single ENCELIUM EXTEND Manager using a crossover cable or connected to multiple ENCELIUM EXTEND Managers through an Ethernet Switch or the tenant network.
Ethernet Switch An Ethernet data switch is optionally provided based on the ENCELIUM LMS design. An Ethernet switch is required if there are multiple ENCELIUM EXTEND Managers and the tenant network is not going to be used, which is typical.
The maximum recommended cable length is 300’ for the connection between the ENCELIUM EXTEND Manager and Ethernet switch as well as the connection between the SSU and Ethernet switch.
A bracket is provided for mounting the SSU, an ENCELIUM EXTEND Manager and Ethernet switch as required.
Refer to ENCELIUM product information bulletins, wiring diagrams and ENCELIUM project-specific component layout and GreenBus II wiring drawings for wiring details. Product information bulletins and wiring diagrams are available on the ENCELIUM website at www.encelium.com/en/technical-information.
Installation Details
• When installing ENCELIUM® EXTEND LMS components, safety precautions, wiring diagrams and installation details shipped with each ENCELIUM EXTEND LMS component should be followed.
• The SSU requires connection to a 120 VAC receptacle on backup power if available.
• SSU require 1 or 2 CAT-5 data connections.
• If an Ethernet data switch is required, it can be mounted in the same bracket as the SSU.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 32 of 35
Appendix LCM & SIM are ENCELIUM® EXTEND GreenBus II® devices. These devices will be used with ENCELIUM EXTEND Wireless System if warranted by system design.
Luminaire Control Module (LCM) The OSRAM LCM provides both dimming and switching functions. The LCM connects to the following devices to be controlled by the ENCELIUM EXTEND Wireless System:
• Light fixtures via switching and 0-10V dimming if applicable
A single LCM can be connected to WCM using either of the two GBII ports on the LCM. See WCM Installation Methods for LCM installation and LCM Wiring Diagrams.
Sensor Interface Module (SIM) The OSRAM SIM connects to low-voltage occupancy sensors, photo sensors and contact closures to be controlled by the ENCELIUM EXTEND Wireless System.
A single SIM ca be connected to a WCM using either of the two GBII ports on the SIM. See SIM JBox installation methods and SIM Wiring Diagrams.
Contact Closure using SIM & Wire Table
ENCELIUM LMS can accept dry contact signals from push button or Single Pole, Single Throw (SPST) switches. Signals from these devices can be used to control the status of light zones.
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 33 of 35
LCM Wiring Diagrams
LCM to Fixed Output Ballast/LED Driver Connection
LCM to Dimming Ballast/LED Driver Connection
ALC Wiring Diagram
ENCELIUM EXTEND Networked Light Management System – Wireless System Installation Manual
Page 34 of 35
SIM Wiring Diagrams
SIM to OCS Connection
SIM to Photo Sensor Connection
SIM/Photo Sensor Mounting Detail
SIM/Low-Voltage photo sensor installation using JBox is shown below:
200 Ballardvale Street
Wilmington, MA 01887
Phone 1-800-531-7573
www.osram.us/ds