IPES-IR3 Flame Sensor
By Tim Quine
ENGR 518
Purpose • Detect fires in industrial applications such
as refineries, paint productions, oil and gas boilers.
• Send alarm signals to user’s receiving devices or alarm systems.
• This is done via closed loop current signals.
Device Characteristics
• Enclosure Material – Stainless Steel Grade 316 or Aluminum 6061
• Weight – Stainless Steel 11 lbs. or
Aluminum 5.5 lbs.• Cable – 6,200 ft. (18 AWG)
Device Components
IR Detectors
LED Status Lights
Explosive ProofCasing
Differential Signaling Lesson
RS232 RS423 RS422 RS485
Differential no no yes yes
Max number of drivers 1 1 1 32
Max number of receivers 1 10 10 32
Modes of operation half duplexfull duplex
half duplex half duplex half duplex
Network topology point-to-point multidrop multidrop multipoint
Max distance (acc. standard) 15 m 1200 m 1200 m 1200 m
Max speed at 12 m 20 kbs 100 kbs 10 Mbs 35 Mbs
Max speed at 1200 m (1 kbs) 1 kbs 100 kbs 100 kbs
Max slew rate 30 V/μs adjustable n/a n/a
Receiver input resistance 3..7 kΩ ≧ 4 kΩ ≧ 4 kΩ ≧ 12 kΩ
Driver load impedance 3..7 kΩ ≧ 450 Ω 100 Ω 54 Ω
Receiver input sensitivity ±3 V ±200 mV ±200 mV ±200 mV
Receiver input range ±15 V ±12 V ±10 V –7..12 V
Max driver output voltage ±25 V ±6 V ±6 V –7..12 V
Min driver output voltage (with load) ±5 V ±3.6 V ±2.0 V ±1.5 V
Device Specifications
• Detection type – optical via multiple spectrum IR Source.
• Spectral Range – three points in the
4.0 to 5.0 micrometer range.• Power – 24 VDC nominal (3 Watts)• Operating Temp Range (-40 to 185 )• Impact Resistance – 1.9 Joules• field of vision
Square Law and Wavelengths
Signaling• Outputs – Industry Standard 4-20 mA +/-
0.1 mA, 2 alarm relays, digital and analog.State IR3 Status
Fire Relay State Fault Relay Status
Output signal, mA
LED Status ConditionNormally open
when energizedNormally closed when
energized
1No power supply
voltage Open Open 0 Off
2
After switching on during 45 sec.
Open Open 2
Continuous green LED light for first 10 sec, then flashing
green LED
3Fault or optical
interference (dust) Open Open 2Alternate flashing of the
yellow and green LED lights
4Normal (no faults or fire
during operation) Open Closed 4Continuous lighting of the
green LED light
5 Fire Closed Closed 18 Continuous red LED light
6Fire & Fault
Closed Open 8Alternate flashing of the
yellow and green LED light
7Test mode (magnetic
collar is on) Open Open 2Magnetic collar is on. Fire
relay is blocked
SensitivityFuel Distance Fire Size Avg. Time
N-Heptane 211 1 ft x 1 ft 9 sec
Methanol 151 1 ft x 1 ft 9 sec
Ethanol 151 1 ft x 1 ft 11 sec
Diesel 151 1 ft x 1 ft 15 sec
Diesel 151 2 ft x 2 ft 10 sec
Gasoline 175 1 ft x 1 ft 10 sec
JP-4 201 1 ft x 1 ft 10 sec
JP-4 206 2 ft x 2 ft 10 sec
Methane 151 3/8’’ x 3‘ 10 sec
Source Distance
1.5 kW Heater 3 ft
Arc Welder, 200A. 3/16’’ – 7018 electrode
9 ft
Fluorescent (2) 20W (6000 Lux)
0 ft
Halogen, 500W 3 ft
Incandescent, 100 W 2000 LUX
1 ft
Direct Sunlight No alarm
Indirect Sunlight No alarm
Stimuli modulated at 1.5 Hz and also un-modulated
Field of vision
Probability Review
• Times recorded previous slide• • Range for 50 % of future
measurement would fall in
eqn: Range between 9.16 and 11.72 seconds
Times
9 sec
9 sec
11 sec
15 sec
10 sec
10 sec
10 sec
10 sec
10 sec
False Alarms
• Cost industries money due to down time .• Must know difference or the result
could be catastrophic.• Uses microprocessor,
algorithms, multiple
sensors and wavelength
range settings.
Competitors Technologies
• Bimetal thermal switches• Computer Imaging Programs• Smoke detectors• SAFE air sample analysis
My Future Uses
• Compressed Air Foam System• Small scale flame sensors• Detecting all fires
References
• http://www.espsafetyinc.com/esp/cms/userfiles/files/IPES-IR3rep-WEB-100512.pdf
• http://www.espsafetyinc.com/cms/userfiles/files/IPES%20IR3%2003_28_2012.pdf
• http://www.espsafetyinc.com/IPES-IR3-multi-spectral-flame-detector.php
**All images in powerpoint are from Google Images**
Questions?