HVAC Noise & Vibration ControlHVAC Noise & Vibration Control

Specifications & Best PracticesSpecifications & Best Practices

Presented By

Noise & Vibration Control, Inc.610-863-6300

www.brd-nonoise.com

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 2/93

2

☺ Brief Intro to Acoustics

☺ Specification Best Practice

☺ Treatment Best Practices

TopicsTopics

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 3/93

3

Why Acoustics Matter!Why Acoustics Matter!

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 4/93

4

Important Acoustic Terminology 

• Loudness vs. Pitch

• Decibels: Sound Power vs. Sound

Pressure

• Decibel Weighting Networks• Tonal Content

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 5/93

5

A 1K Hz tone at 60 dB would require a

102 dB tone at 20 Hz to sound as loud tothe human ear.

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 6/93

6

Common Municipal Code defines tone as:

“any sound which can be distinctly heard as a single pitch or set of single pitches…. and shall exist

of the one-third octave band sound pressure level in the band when the tone exceeds the arithmetic

average of the sound levels of the two contiguous one-third octave bands by five dB for frequencies

of 500 Hz and above, eight dB for frequencies between 160-400 Hz, and by 15 dB for frequencies

less than or equal to 125 Hz.”

Tonal Noise

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 7/93

7

PWL vs. SPLSound Power vs. Sound Pressure

Cause vs. Effect

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 8/93

8

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 9/93

9

What is the overall dBA level?

Octave Center Unweighted A-weighting A-weighted Overall

Band Frequency Sound factor (dB) Sound Resultant

Pressure (dB) Pressure (dBA) Level

1 63 94 -26 68

2 125 86 -16 70

3 250 85 -9 76

4 500 89 -3 86 91 dBA5 1,000 89 0 89

6 2,000 77 1 78

7 4,000 75 1 76

8 8,000 76 0 76

86

89

Decibel

 Addition

72

86

89

79

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 10/93

10

(Sound Levels 270 ton Air Cooled Chiller)

-37-37-37-37-37-37-37-37-37Loss100’

1008185929497999890Lw

634448555760626153Lp

A8K4K2K1K50025012563Freq (Hz)

1. Where are we now?

2. Where do we need to be?

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 11/93

11

13182022171410----Needed

Attenuation

502628334046526167Ordinance

634448555760626153Chiller 

A8K4K2K1K50025012563Freq (Hz)

3. How much noise reduction is required?

4. What needs to be done to achieve compliance?

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 12/93

12

☺ Common SpecificationStrategies

☺ Specifications Types

☺ Specification Best

Practices

Sub TopicsSub Topics

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 13/93

13

 A Specification Should Provide“Just the Right Prescription”

• Accountability

• Cost Control

• Predictable Performance

• Review of subjective and objective noise

criteria

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 14/93

14

Common SpecificationCommon SpecificationStrategiesStrategies

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 15/93

15

Common Spec Strategies on NoiseSensitive Projects

• Specify sound data for lowest rated model asequipment basis of design

• Specify all available OEM equipment low noiseoptions

• Specify an equipment model that is not tonal• Specify the same treatment used on the last

noise sensitive project

• Retain an acoustical consultant to write thespecification

• Specify base equipment and address any

noise problems at start-up

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 16/93

16

Published Sound Power Data

(No OEM Sound Kit Options)

OverallA-Wtd

63 125 250 500 1000 2000 4000 8000 (dBA)

1 97 94 92 97 90 88 84 82 97

2 102 103 99 99 98 94 87 84 102

3 67 70 79 83 89 91 88 80 95

4 93 99 97 100 97 91 88 80 105

Sound Power Levels (dB)Octave Band Center Frequency (Hz)

4 Different

Manufacturers &

Chiller Models

(Screw and Scroll

Designs)

Published Sound Pressure Data at 30’ Away

(No OEM Sound Kit Options)Overall

A-Wtd

63 125 250 500 1000 2000 4000 8000 (dBA)1 70 67 65 70 63 61 57 55 70

2 75 76 72 72 71 67 60 57 75

3 40 43 52 56 62 64 61 53 68

4 66 72 70 73 70 64 61 53 74

Octave Band Center Frequency (Hz)

Sound Pressure Levels 5 (dB) @ 30'

4 Different Chiller Manufacturers &

Models (Screw and

Scroll Designs)

Common Specification Strategies:

Specify sound data for lowest rated model as equipment basis of design

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 17/93

17

Sound Pressure Data for property line 80’ away

(No OEM Sound Kit Options)Overall

A-Wtd

63 125 250 500 1000 2000 4000 8000 (dBA)

1 61 58 56 61 54 52 48 46 61

2 66 67 63 63 62 58 51 48 66

3 31 34 43 47 53 55 52 44 60

4 57 63 61 64 61 55 52 44 66

Sound Pressure Levels 5 (dB) @ 80'

Octave Band Center Frequency (Hz)4 Different Chiller 

Manufacturers &

Models (Screw

and Scroll

Designs)

Sound Pressure Data for property line 80’ away(with factory OEM options)

Overall

A-Wtd

63 125 250 500 1000 2000 4000 8000 (dBA)

63 57 57 59 54 48 44 42 6052 60 61 59 56 54 46 41 62

31 33 43 46 49 51 48 42 56

57 63 61 61 60 55 52 42 64

Sound Pressure Levels 5 (dB) @ 80'

Octave Band Center Frequency (Hz)

4 Different Chiller 

Manufacturers & Models(Screw and Scroll

Designs)

None of the chillers will comply with typical nighttime

noise ordinance values of 50 to 55 dBA.

Common Specification Strategies:

Specify sound data for lowest rated model as equipment basis of design

Specify all available OEM equipment low noise options

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 18/93

18

Scroll Chiller SoundPressure Levels

 

     Z C A     1     2

     1     6

     2     0

     2     5

     3     2

     4     0

     5     0

     6     3

     8     0

     1     0     0

     1     2     5

     1     6     0

     2     0     0

     2     5     0

     3     1     5

     4     0     0

     5     0     0

     6     3     0

     8     0     0

     1     k

     1     k     2     5

     1     k     6

     2     k

     2     k     5

     3     k     1     5

     4     k

     5     k

     6     k     3

     8     k

     1     0     k

     1     2     k     5

     1     6     k

     2     0     k Hz

30

40

50

60

70

80

90

100dB

Screw Chiller Sound

Pressure Levels

Common Specification Strategies:

Specify an equipment model that is not tonal

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 19/93

19

☺ Performance

☺ Design

☺ Allowance

Specification TypesSpecification Types

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 20/93

20

Performance Specifications

• Typical performance descriptors – Sound Power and/or Sound Pressure

 – Octave band and/or overall dB and/or dBA levels

 – NC or RC levels• Relies on the acoustical credibility of the equipment

manufacturer  – May or may not have the capabilities needed

 – Commonly will take an exception

• Spec is difficult to enforce – AHRI 370, AHRI 575, AHRI 260, etc...

• Spec is often not based on project target levels atreceiver positions

• Performance spec may or may not address equipmentintegration issues (operating performance, maintenance,etc…)

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 21/93

21

Performance Specification Example

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 22/93

22

Performance Specification Example

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 23/93

23

Contradictory Performance Specification

Sound attenuation solution quiet

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 24/93

24

Contradictory Performance Specification

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 25/93

25

Design Specifications = “Just Right Prescription”

• Evaluates noise sensitive location(s) to provide

 – Predictable Performance

 – Accountability

 – Cost Control

• Right amount of attenuation

• Accounted for in the budget

• Describes, provides performance, and/or 

illustrates (schematic details) the materials andproducts needed

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 26/93

26

Design Specification

Schematic Design

Detail

ABC model JJJ

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 27/93

27

SchematicDesign Detail

Design

Specification

ABC solution/model

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 28/93

28

“Loose” Design Specification

ABC . . . . . . . . . . . . . . .

Result of a “Loose/Generic” spec

What is criteria for approving or rejecting?

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 29/93

29

“Better” Design Specification

 ABC model and manufactured by ABC company or equivalent.

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 30/93

30

“Detailed” Design Specification

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 31/93

31

“Best” Design Specification

 Attenuation

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 32/93

32

“Best” Design Specification Cont’d

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 33/93

33

 Allowance Specifications

• Equivalent advantages of pre-

purchased equipment – Provides the right material that is

wanted on the project

• Assures needed design will be built• Levels the playing field for bidders

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 34/93

34

Allowance Specification

 ABC Acoustic Attenuation DEF Company.

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 35/93

35

Specification BestSpecification BestPracticesPractices

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 36/93

36

Best Practices

 Acoustic Design• Answer 4 design questions

1. Where are we now?

2. Where do we need to be?

3. What needs to be done to get there?

4. How much will that cost?

• Use 3-5 dBA safety factor • Cursory review on every project, in depth review when

warranted

• Assess site ambient noise levels• Evaluate airborne and structure-borne transmission

• System problems require system solutions

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 37/93

37

Best Practices

Specifications• Job specific combined design/performance specs

preferred over generic performance specs

• Evaluate project specific objective and subjective criteria

 – Indoor criteria: NC, RC, NCB, RC Mark II

 – Outdoor criteria: Zoning and ordinance criteria

• Place in Division 15/23 with equipment

• Specify single source for system acoustic performance

• Specify turnkey where installation critical

• Require submission for approval as “or equal” 10 days before bid date

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 38/93

38

Take Away

• Location specific performance is “king”

and drives the design spec• Design specs provide “just the right”

knowledge of costs that can get into

the budget• Acoustic treatments/solutions need to

be in the equipment spec to ensurepredictable performance,acceptability, and accountability

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 39/93

39

☺ Construction Trends

☺ Specifications

☺ Vibration Isolation☺ Chiller Noise Treatments

☺ Roof Mounted Treatments

☺ Duct Work & Silencers

☺ Rooftop Unit Treatments

Sub TopicsSub Topics

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 40/93

40

Construction Trends• Less mass in building

• Less space between floors• Curb mounted equipment

• Drop ceilings

• Premium for rentable/usable space• Value Engineering

• Heightened sensitivity of owners

• ANSI S12.60• LEED

B t P ti

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 41/93

41

Best Practices

• Thickened slab above and

below

• Floating floors

• Pneumatic isolation systems

• 6 sided enclosures• Stay away from midpoints of 

column spans

• Buffer from noise sensitive

spaces• Source & path acoustic

treatments

Indoor Chillers

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 42/93

42

Source Treatments

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 43/93

43

Source Treatments

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 44/93

44

Critical Design Factors• Broadband Performance

• Tonal Performance

• Aerodynamic Performance

• Operating Efficiency• Operating Costs

“S ft” E l P th T t t

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 45/93

45

“Soft” Enclosure Path Treatments

“Hard” Enclosure Path Treatments

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 46/93

46

Hard Enclosure Path Treatments

B t P ti

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 47/93

47

Best Practices

Outdoor Chillers• Thickened slab for 

rooftop

• Evaluate loudness and

tonal content

• Special consideration for 

remote evap piping• Evaluate building and

property line noise

• Optimize aerodynamicand acoustic performance

• Source and path acoustic

treatment

C S T t t

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 48/93

48

Compressor Source Treatments

Sound Blankets

• Treat all accessible compressor circuit

components• 3 to 4 lb. surface density

• Fit/refit attachment features must be “user 

friendly”

• UL 764C Listed

T ti C Ci it

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 49/93

49

Treating Compressor Circuits

Result of “generic” spec

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 50/93

50

Result of generic spec

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 51/93

51

 Air Intake Source Treatments

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 52/93

52

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 53/93

53

Condenser Fan Source Treatments

• Acoustical plenums

• Plenum with baffles

• Plenum with silencer bank

• Individual stack silencers

Open Plenums

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 54/93

54

Open Plenums

Plenum with Baffles

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 55/93

55

Plenum with Baffles

Plenum with Silencer Bank

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 56/93

56

Plenum with Silencer Bank

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 57/93

57

Not Recommended by OEMs

“Dedicated” Stack Silencers

Path Treatments

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 58/93

58

Wall and Fence Liners

Turnkey Acoustical Barrier Walls

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 59/93

59

y

20+ dBA Attenuation Systems

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 60/93

60

20 dBA Attenuation Systems

Best Practices

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 61/93

61

• Integral vibration/seismic

curb

• Lock down internal

isolation

• Add mass inside curbs

• Seal (acoustic) duct

drops

• Dissipate supply breakoutnoise above deck

• Plenum style acoustic

curbs

Rooftop CurbMounted AHU

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 62/93

62

Poor “Best Practice”

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 63/93

63

Poor Best PracticeThis is a seismic job!

In-Curb Treatment

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 64/93

64

Best Practices

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 65/93

65

RTU Configurations• Increase plenum liner thickness

• Utilize RTU discharge plenums on the supplyside

• Avoid vane type flow modulation devices. VFD

controllers are preferred• Slower fan speeds = lower noise levels

• Evaluate fan wheel types. Backward inclined (BI)

and aerofoil (AF) wheels are preferred over forward curved models (FC)

Integrated Sound Attenuators

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 66/93

66

External

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 67/93

67

External

 Acoustic Duct

Lagging

7 - 9 dB reduction in first 3

octave bands

Rooftop Unit Condenser Section

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 68/93

68

Treatments

Best Practices

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 69/93

69

Roof Mounted Equipment onDunnage Steel

• Restrained isolators if spring• UV compatible shear mounts

• 3” to 4” thickened slab 8’ to 10’ around unit

perimeter 

• Locate over utility space

• Keep away from skylights and operablewindows

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 70/93

70

Cooling Towers• Similar to Chiller strategies

• Restrained spring isolators• Condenser fan discharge

treatment

• Path treatments

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 71/93

71

Best Practices

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 72/93

72

Vibration Isolation• Follow ASHRAE guidelines for static deflection

• Review actual deflections• Isolate pipes and ducts at riser and wall

penetrations

• Avoid suspended piping in mechanical roomsbelow noise sensitive space

• Avoid cantilevered loads

• Proper adjustment of isolator lockdowns

and snubbers

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 73/93

73

Acoustical Sealant

in ½” Gap Acoustical Batt Mineral Fiber

Packing

Pipe and Duct Penetrations

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 74/93

74

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 75/93

75

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 76/93

76

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 77/93

77

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 78/93

78

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 79/93

79

Best Practices

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 80/93

80

• Concrete inertia bases

• Support elbows on base

• Open springs

• Seismic snubbers for 

base• Molded neoprene flexes

• Vibration isolationhangers for 50’ or entiremechanical room

• Acoustic treatment rarelyneeded

Pumps

Best Practices

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 81/93

81

• Avoid high pressure

drop models

• Evaluate self 

generated noise

• Apply ∆p correction

factors

• Stay 3 equivalent ductdiameters away from

fittings

 AHU Duct Silencers

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 82/93

82

Guidelines for Sound Trap PlacementNear Fans and Duct Fittings

Best Practices

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 83/93

83

 Avoiding Respirable Fibers

• Fiber free reactive duct silencers

(packless)

• Media wrap of packed silencers

with spacers• Closed cell thermal insulation

• Open cell melamine foams

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 84/93

84

Best Practices

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 85/93

85

Duct Design

• Follow ASHRAE guidelines

• Follow SMACNA guidelines• Control ductwork aspect ratios

• Increase gauge and stiffening near units

• Double wall duct

• Duct shape

• Target velocities consistent with targetNC goals

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 86/93

86

Turbulence = Regenerated Noise

Regenerated Noise at Fittings

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 87/93

87

Recommended maximum airflow

velocities for various installations

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 88/93

88

Duct

Shapes

Best Practices

R Diff

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 89/93

89

• Select diffusers for 6 to 8NC points below roomtarget NC

• Long radius 90° flexes todiffusers add 1 to 3 NCpoints

• “Kinked” flexes add 7 to 9

NC points• Balancing dampers

should be located threeequivalent duct diameters

away from diffusers andfittings

• Open plenum returngrilles may require linedelbow

Room Diffusers

Best Practices

VAV B

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 90/93

90

VAV Boxes

• Lined discharge 10’ to 15’

• First take-off minimum 3’ from discharge

• Single duct VAV 1500 – 1700 CFM

• Fan powered VAV 1100 – 1200 CFM• External wraps for casing radiated noise

Recommended VAV Detail

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 91/93

91

Removable Wraps Reduce

R di t d N i

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 92/93

92

Radiated Noise

7/29/2019 HVAC Noise and Vibration Control

http://slidepdf.com/reader/full/hvac-noise-and-vibration-control 93/93