Post on 17-May-2020
4/19/2012
1
HVAC BASICSAND
HVAC SYSTEM EFFICIENCYIMPROVEMENT
SECTION O
INTRODUCTION
HVAC systems – or Heating, Ventilating and Air-Conditioning systems – control the environment for people and equipment in our
Section
Oenvironment for people and equipment in our facilities.
HVAC use in an office building might be as high as 30 – 50% in some climates.
HVAC systems and chillers are also significant energy consumers in many manufacturing
O -
2
energy consumers in many manufacturing facilities.
4/19/2012
2
FUNCTIONS OF HVAC SYSTEMS
The purpose of a Heating, Ventilating and Air
Section
OVentilating and Air Conditioning (HVAC) system is to provide and maintaina comfortable and safe environment within a building forthe occupants or for the
O -
3
pprocess being conducted.
Many HVAC systems were not designed with energy efficiency as one of the design factors
ENVIRONMENTAL CONTROL FACTORSAn HVAC system functions to provide an
environment in which these three factors are maintained within desired ranges. Typical
Section
Og ypdesign conditions are:
23 degrees C temperature (dry bulb) 40 - 60% relative humidityASHRAE 62 – 1999, 2001 and 62.1 – 2004, 2007
Ventilation Standard
O -
4
10 LPS outside air per person, or CO2 less than 1000 PPM
4/19/2012
3
COMFORT ZONE ON PSYCHROMETRIC
CHARTS
ection OO
-5
TEMPERATURE CONTROL STRATEGIES
Vary the temperature of the supply air to the space while keeping the air flow rate constant.
Section
Op p gThis is the constant volume, variable temperature approach.
Vary the air flow rate while keeping the supply air temperature constant. This is the variable volume, constant temperature approach. VAV – variable air volume system.
O -
6
volume system.
Vary the supply air temperature and the flow rate, as in a variable volume reheat system.
4/19/2012
4
RELATIVE HUMIDITY CONTROL Humidification - The air is too dry and water vapor
must be added for comfort.
Section
O
Dehumidification - The air is too wet and water vapor must be removed for comfort.
AC systems typically over-cool the air to remove water vapor, and then may have to heat the air back up - this is called reheat, and
O -
7
heat the air back up this is called reheat, and requires additional energy.
Either way, energy required is around 2300 kJ per kg of water.
SENSIBLE AND LATENT HEAT
Sensible heat - The heat associated with a temperature change of a substance at a constant
Section
Otemperature change of a substance at a constant moisture level.
Latent heat - The heat associated with the phase change of a substance.
Enthalpy - Total heat content of a substance, i l di b th ibl h t l l t t h t
O -
8
including both sensible heat plus latent heat.
4/19/2012
5
PRIMARY EQUIPMENT Chillers
Direct expansion (DX) systems
Section
O Direct expansion (DX) systems
Boilers
Furnaces
O -
9
SECONDARY SYSTEMS Single duct, single zone system
Single duct, terminal reheat system
Section
O
Multizone system
Dual duct system
Single duct, variable air volume system This is the most common system going in to large
i l b ildi
O -
10
commercial buildings
Fan coil system
4/19/2012
6
HVAC SYSTEMS
The summary below illustrates the types of systems frequently encountered in heating and air-conditioning systems.
11
12
4/19/2012
7
13
VAV HVAC SYSTEMS Most common new system going in to large commercial
buildings.
High efficiency because of use of variable speed drive
Section
O
High efficiency because of use of variable speed drive on the supply air fan. For example, cutting air flow from full rate to 80% of full rate, cuts the fan power almost in half!
Fan is controlled most often to keep a constant static pressure in the supply duct. Temperature is controlled b l l t i l b i th
O -
14
by a local terminal box in the zone.
4/19/2012
8
POWER AND ENERGY IN AIRCONDITIONING
One kW of A/C = 3600 kJ/h
A kW is a measure of A/C power, and is used when sizing
Section
Op , gsystems, or when determining electrical demand.
One kWh of A/C = 3600 kJ
A kWh is a measure of A/C energy, and is used when sizing storage tanks for thermal energy storage (TES) systems, or when determining electrical energy consumption.
O -
15
VAPOR COMPRESSION CYCLE
Section
O
OUTSIDE AIR
CONDENSER O -
16
INSIDE AIR
OUTSIDE AIR
CONDENSER
COMPRESSOR
EXPANSION VALVE
INSIDE AIR
EVAPORATOR
4/19/2012
9
DIAGRAM OF A TYPICAL CHILLER
Section
OCondenser
Condenser Water29o C 35o C
O -
17
Condenser
CompressorMotor
Expansion Valve High Pressure
SideLow Pressure Side
Chilled Water
Evaporator
12o C6o C
HRU – DESUPERHEATER Adding a small plate and frame heat exchanger into
this system allows heat recovery from the 85 degree C hot refrigerant gas coming out of the compressor. Cold
Section
Ohot refrigerant gas coming out of the compressor. Cold water (10 -20 degrees) goes through the other side of the HRU, and is heated to 55 to 65 degrees C.
The amount of heat recovery is about 800 kJ/h per kW of capacity of the AC unit or air cooled chiller.
O -
18
4/19/2012
10
HVAC SYSTEM PERFORMANCE MEASURES
Energy Efficiency Ratio (EER)
EER = kJ of cooling output
Section
OEER = kJ of cooling outputWh of electric input
= kJ/h of cooling outputW of electric power input
Coefficient of Performance (COP)
O -
19
COP = Energy or heat output (total)Energy or heat input (external only)
= EER / 3.6 kJ/Wh
SOME MAGIC NUMBERS FOR EER AND COP
EER = kJ/h of cooling outputW of electric power input
Section
OW of electric power input
COP = EER /3.6 kJ/Wh
kWin = 3.6 = 1.0kWcool EER COP
O -
20
4/19/2012
11
EXAMPLES
1. A 30 kW cooling roof top A/C unit has an EER of 7.2. What is its COP?
Section
Oof 7.2. What is its COP?
2. A 30 kW cooling roof top A/C unit has an EER of 7.2. What is its kW input load at full capacity?
3. A 30 kW cooling roof top A/C unit has an EER f 8 5 Wh t i it COP?
O -
21
of 8.5. What is its COP?
4. A 30 kW cooling roof top A/C unit has an EER of 8.5. What is its kW input load at full capacity?
HEATING SEASONAL PERFORMANCE
FACTOR
For heating with an electric heat pump, the test is conducted at a different temperature than for
Section
Ois conducted at a different temperature than for the SEER, and this performance measure is called the HSPF – the Heating Seasonal Performance Factor. For heating, there is also the heating COP, measured at different temperatures than the cooling COP.
O -
22
4/19/2012
12
SYSTEM IMPROVEMENT OPTIONSMake building envelope improvements to reduce
HVAC load insulation high performance windows and roofs
Section
O insulation, high performance windows and roofs
Replace old HVAC units and chillers with more efficient models
Possibly downsize units and chiller Energy Star (US) and ASHRAE say chillers are
i d i US
O -
23
oversized 60% in US.
Consider multiple chillers
Consider a chiller with a variable speed drive
Consider installing a small chiller or separate
Section
OConsider installing a small chiller or separate HVAC system for 24/7 loads
Use VSDs on pumps, cooling towers
Replace constant volume systems with VAV -i bl i l
O -
24
variable air volume systems
4/19/2012
13
USE HEATPIPE FOR DEHUMIDIFICATIONS
ection OO
-25
Consider adding a gas engine driven chiller with heat recovery for hot water
Retrofit to DDC controls
Section
O
Use cooling towers where possible
O -
26
4/19/2012
14
USE VARIABLE REFRIGERANT VOLUME
SYSTEMS
The term variable refrigerant flow (VRF) refers to the ability of the system to control the amount of
Section
Oability of the system to control the amount of refrigerant flowing to each of the evaporators, enabling the use of many evaporators of different capacities and configurations, individualized comfort control, simultaneous heating and cooling in different zones, and heat recovery from one zone to another.
Current era technology using electronically
O -
27
gy g ycommutated motors, inverter driven scroll compressors, multiple compressors, versatile configurations, and complex refrigerant and oil circuitry, returns, and controls, can permit as many as 60 are more indoor units to operate off one outdoor unit.
ENERGY EFFICIENCY
The energy efficiency of VRF systems derives from several factors:
Section
O
The VRF system essentially eliminates duct losses, which are often estimated at 10% to 20% of total air flow. But, there must be a separate ventilation system.
The VRF systems typically include 2 – 3 compressors, one of which is variable speed in each condensing unit enabling wide capacity modulation
O -
28
condensing unit, enabling wide capacity modulation, and high part-load efficiency.
HVAC systems typically operate between 40 – 80% of full load most of the time.
4/19/2012
15
ABSORPTION CHILLERS Absorption chillers can produce large quantities of chilled
water using very little electric power and energy. Their prime energy source is heat from hot water or steam.
Section
Oprime energy source is heat from hot water or steam.
Absorption chillers have no CFCs. Most absorption cycles use either ammonia and water or lithium bromide and water.
Absorption chillers are not very efficient
O -
29
Absorption chillers are not very efficient. Single stage -- COPs about 0.6 - 0.8 Two-stage -- COPs about 1.0 - 1.2
GAS DRIVEN CHILLERS Gas engine driven chillers offer significant
electric demand savings, and good part-load performance
Section
Operformance. Most applications are in areas with high demand
rates and low or moderate gas rates. In many cases, heat recovery and beneficial use
of the heat is necessary for this approach to be cost-effective.D l d i hill il bl ( l t i d
O -
30
Dual drive chillers are available (electric and gas).
PowerCold Corp, Alturdyne Corp, Jenbacher
4/19/2012
16
CEM REVIEW PROBLEMS
1. In a vapor compression cycle air conditioner, the refrigerant is always in the vapor state.
Section
O
A) True B) False
2. A roof top air conditioner has an EER of 9.2. What is its COP?
O -
31
3. Reheat may still be needed in an HVAC system even if the outside temperature is very high.
A) True B) False
4. A roof top air conditioner has an EER of 13.5. What is its kWin per kWcool rating?
5. How many kWh electric input is used to provide 120 illi kWh f i diti i ith t h i
Section
O
million kWh of air conditioning with a system having a COP of 3.0?
5. How many kWh electric input is used to provide 100 million kJ of heat removal (air conditioning) with a system having a COP of 5.0?
O -
32
4/19/2012
17
HVAC SYSTEMS APPENDIX
Section O - 33
LATEST RESULTS ONCHILLED WATER PUMPING
Study just out from the Air-Conditioning and Refrigeration Technology Institute (2004) on
Section
ORefrigeration Technology Institute (2004) on “Variable Primary Flow Chilled Water Systems: Potential Benefits and Application Issues.”
To measure energy use and savings of VPFCWS, ARTI conducted an extensive study that compared these systems’ energy use with that of other common systems,
O -
34
that of other common systems, including: Constant flow/primary-only
CWS
4/19/2012
18
ARTI CWS STUDY (CONTINUED)– Constant primary flow/variable secondary flow
CWS– Primary/secondary CWS
Section
OPrimary/secondary CWS– Primary/secondary CWS with a check valve
installed in the decouplerAccording to the ARTI study, the VPFCWS:
– reduced energy use 3 - 5%– reduced first cost by 4 - 8%– Reduced life cycle cost by 3 - 5%
O -
35
Reduced life cycle cost by 3 5%compared to conventional constant primary flow/variable secondary flow CWS.
Section
O
HVAC TESTING AND BALANCING
The systems that distribute air and water for space conditioning throughout a facility may need to be balanced and cleaned as part f th t i i i ff t
O -
36
of the retrocommissioning effort. In a process known as testing, adjusting, and balancing (TAB),
HVAC system components are adjusted so that air and water flows match load requirements.
The process begins with testing to evaluate the performance of the equipment in its current state. Adjustments to flow rates of air or water are then made for the purpose of balancing the system and matching the loads throughout a building.
Indications that TAB is needed include frequent complaints from occupants about hot or cold spots in a building, the renovation of spaces for different uses and occupancy, and the need for frequent adjustments of HVAC components to maintain comfort.
4/19/2012
19
Section
OHVAC TESTING
Typical HVAC system investigations include: Air system flow rates, including supply, return, exhaust, and O
-37outside airflow (flows go through main ducts, branches, and
supply diffusers that lead to specific spaces in a building) Water system flow rates for chillers, condensers, boilers, and
primary and secondary heating and cooling coils Temperatures of heating and cooling delivery systems (air side
and water side)P i i d f i i f fl l d i f i d Positions and functioning of flow-control devices for air and water delivery systems
Control settings and operation Fan and pump speeds and pressures
Section
O
HVAC TESTING
The savings associated with TAB come from the reductions in the energy used by the heating and O
-38
gy y gcooling system and can range up to 10 percent of costs.
The heat exchange equipment that cools and heats the air that ultimately reaches building spaces should also be inspected and cleaned if necessary. This consists of heating and cooling coils installed in air handlers, fan coil terminal units, or baseboard radiators. These units are typically supplied with chilled water and hot waterare typically supplied with chilled water and hot water.
The heating and cooling coils can also be part of a packaged unit such as a rooftop air-conditioning unit.
4/19/2012
20
Section
OHVAC MAINTENANCE
All surfaces and filters should be clean—dirty surfaces reduce heat transfer and increase pressure loss, which serves to increase energy use O
-39
use.
For air-side heating and cooling coils, whether in an air handler or in a rooftop unit, the methods for cleaning include compressed air, dust rags or brushes, and power washes. Any of these techniques will reduce deposit buildup. In addition, check baseboard heating systems for dust buildup, and clean them if necessary.
The water side of heating and cooling systems is generally inaccessible for mechanical cleaning. Chemical treatments are often the best solution for cleaning these surfaces. Ongoing water treatment and filtering of the water side are recommended to reduce dirt, biological, and mineral-scale buildup. Filters for both air-side and water-side systems should be cleaned and replaced as necessary.
Section
O
HVAC MAINTENANCE
In addition, make sure that terminal fan coil units and baseboards are not blocked or covered with books, O
-40
baseboards are not blocked or covered with books, boxes, or file cabinets. Besides creating a fire hazard (in the case of radiators), blocking the units prevents proper air circulation and renders heating and cooling inefficient.
In general, the cleaner the heat transfer surfaces, the greater the savings In addition cleaning coils and greater the savings. In addition, cleaning coils and filters may reduce the pressure drop across the coil and reduce fan or pump energy consumption. Savings can range up to 10 percent.
4/19/2012
21
Section
OCHILLER PLANT SAVINGS
O -
41S
ection O
CHILLER PLANT SAVINGS
Use controls to properly sequence chillers. Monitor the capacity of all chillers in the plant and turn chillers on or off so O
-42that each one is loaded enough to keep it in its most efficient zone
Monitor outdoor conditions and reset the chilled-water temperature accordingly. This strategy can help match chiller output to the actual load.
Monitor outdoor conditions and reset the condenser-water temperature accordingly. Higher condenser-water temperatures decrease cooling tower fan power but increase temperatures decrease cooling tower fan power but increase chiller power. The optimum operating temperature occurs at the point where these two opposing trends combine to produce the lowest total power use.
4/19/2012
22
Section
OCHILLER PLANT SAVINGS
Take full advantage of available cooling towers. Most chilled-water plants have excess capacity, with one or more O
-43cooling towers not operating during low-load periods. To make the
most of existing cooling towers, simply run condenser water over as many towers as possible, at the lowest possible fan speed.
Inspect tubes annually and clean as needed, or use automatic tube-cleaning equipment. As a chiller runs, water may leave behind scale, algae, or slime on the inside of the condenser tubes
Prevent scale formation in cooling towers. Scaling, corrosion, and biological growth all impede tower efficiency and increase maintenance costs from the resultant condenser fouling and loss of heat transfer.
Section
O
CHILLER WATER SAVINGS
Replace standard valves with low-friction units to reduce flow resistance for the chilled water. This measure reduces
d t l h t t th hill
O -
44
pump energy use and returns less heat to the chiller.
Insulate chilled-water pipes. Insulation helps ensure that the chilled water only absorbs heat from the spaces where it is intended to do so.
Replace standard-efficiency or oversized pumps with highly efficient units sized for the newly reduced loads.Most induction motors that drive pumps reach peak efficiency when about 75 percent loaded and are less efficient when fully when about 75 percent loaded, and are less efficient when fully loaded. Thus, wherever possible, size pumps so that much of their operating time is spent at or close to their most efficient part-load factor. If a pump is oversized, then it likely operates at an inefficient loading factor.
4/19/2012
23
Section
OCHILLER WATER SAVINGS
Control chilled-water pumps with variable-speed drives (VSDs). VSDs can ensure that pumps are performing at maximum efficiency at part-load conditions As with fan O
-45
maximum efficiency at part-load conditions. As with fan systems, the power required to operate a pump motor is proportional to the cube of its speed. For example, in a pump system with a VSD, a load reduction that results in a 10 percent reduction in motor speed reduces energy consumption by 27 percent: 1 – (0.9)3 = 0.27. However, it is necessary to ensure that flow rates through chillers are maintained at safe levels.
Upgrade the chiller compressor For a centrifugal Upgrade the chiller compressor. For a centrifugal compressor, install a VSD. This will allow the chiller to run at lower speeds under part-load conditions.
For reciprocating and screw chillers, replace with one that uses new magnetic bearing technology. These achieve
better efficiency.
Section
O
CHILLER WATER SAVINGS
For chillers without a VSD, use low-voltage soft starters.The motor windings of constant-speed compressors experience O
-46great stress when the chiller is first started due to the high
inrush of current.
Replace an old or oversized standard-efficiency chiller with a properly sized high-efficiency water-cooled unit.
When replacing an existing chiller, select one that will be most efficient under the conditions it is likely to experience.
Install water-side economizers to allow cooling towers to produce chilled water when weather conditions permit.
4/19/2012
24
Section
OEFFICIENT PACKAGED A/C UNITS
O -
47S
ection O
HVAC CONTROLS
The EMS and controls within a building play a crucial role in providing a comfortable building environment. O
-48
p g g Over time, temperature sensors or thermostats may drift
out of tune. Wall thermostats are frequently adjusted by occupants,
throwing off controls and causing unintended energy consumption within a building.
Poorly calibrated sensors can increase heating and cooling loads and lead to occupant discomfort.
Occupants are likely to take matters into their own hands if they consistently experience heating or cooling problems!
4/19/2012
25
Section
OTUNING UP THE CONTROLS
Calibrate the indoor and outdoor building sensors.Calibration of room thermostats, duct thermostats, humidistats, O
-49and pressure and temperature sensors should be in accordance
with the original design specifications. Calibrating these controls may require specialized skills or equipment and may call for outside expertise.
Inspect damper and valve controls to make sure they are functioning properly. Check pneumatically controlled dampers for leaks in the compressed-air hoses. Also examine dampers to
th t th d l l Stiff d ensure that they open and close properly. Stiff dampers can cause improper modulation of the amount of outside air being used in the supply airstream. In some cases, dampers may actually be wired in a single position or disconnected, violating minimum outside air requirements.
Section
O
TUNING UP THE CONTROLS
Review building operating schedules. HVAC controls must be adjusted to heat and cool the building properly during occupied hours. Occupancy schedules can change frequently over the life of a building, O
-50
and control schedules should be adjusted accordingly. Operating schedules should also be adjusted to reflect daylight saving time. When the building is unoccupied, set the temperature back to save some heating or cooling energy, but keep in mind that some minimum heating and cooling may be required when the building is unoccupied.
Review the utility rate schedule. Utilities typically charge on-peak and off-peak times within a rate, which can dramatically affect the amount of electric bills. If possible, equipment should run during the l i ff k h less expensive off-peak hours.
Savings from these control tune-up measures can range up to 30 percent of annual heating and cooling costs.
4/19/2012
26
Section
OCOOL SAVINGS
Chilled-water and condenser-water reset. In facilities with a central chiller system, the operating efficiency can be increased O
-51through a practice known as chilled-water reset—modifying the
chilled-water temperature and/or condenser-water temperature in order to reduce chiller energy consumption.
Chiller tube cleaning and water treatment. Cleaning chiller tubes and improving water treatment can also improve performance of a chiller system by providing cleaner surfaces for heat transfer on both the refrigerant and water sides of the chiller tubes
Section
O
COOL SAVINGS
Reciprocating compressor unloading. For smaller chiller systems that use reciprocating compressors with multiple pistons part-load performance can be improved by making O
-52
pistons, part-load performance can be improved by making sure the system properly unloads pistons as the load decreases. If not, the system may cycle unnecessarily during low cooling loads. Increased cycling can lead to compressor and/or electrical failures. Unloading is typically controlled by a pressure sensor that is set for a specific evaporator pressure. This sensor, and the controls dependent upon it, can fall out of calibration or fail.
Chiller tube cleaning and water treatment Cleaning Chiller tube cleaning and water treatment. Cleaning chiller tubes and improving water treatment can also improve performance of a chiller system by providing cleaner surfaces for heat transfer on both the refrigerant and water sides of the chiller tubes.