Post on 22-Aug-2020
Tranquility® 30 (TT) SeriesTranquility® 20 (TS) Series
Residential Horizontal & VerticalPackaged Geothermal Heat Pumps
Installation, Operation &Maintenance Instructions
97B0113N01Rev.:January 30, 2017
H&V Products
Table of ContentsModel Nomenclature 3Storage 4Pre-Installation 4Horizontal Installation 5-6Horizontal Service Access 7Field Conversion of Air Discharge 8Duct System Installation 9Condensate Piping Installation 9Vertical Installation Clearances 10Vertical Installation 11-12Water Connection Installation 13Ground Loop Applications 13-14Open Loop - Ground Water Systems 15-16Water Quality Standards 17Hot Water Generator 18-20Electrical - Line Voltage 21-22Electrical - Low Voltage Wiring 23Accessory Connections 24Electrical - Thermostat Wiring 25
ECM Blower Control 26-27Blower Data 28-30CXM Controls 31Safety Features – CXM Control 32-34Unit Commissioning And Operating Conditions 35Unit Start-Up and Operating Conditions 36Unit Start-Up Procedure 37Coax Pressure Drop Tables 38Unit Operating Conditions 39-43Performance Data 44-63Preventive Maintenance 64Troubleshooting 65CXM Process Flow Chart 66Functional & Performance Troubleshooting 67-68Troubleshooting Form 69Refrigerant Circuit Diagram 69Warranty 70Revision History 72
This page was intentionally left blank.
3
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Model Nomenclature: General Overview
WARNING!
WARNING!
CAUTION!WARNING! To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by technicians who meet local, state, and federal pro ciency requirements.
CAUTION! To avoid equipment damage, DO NOT use these units as a source of heating or cooling during the construction process. The mechanical components and lters will quickly become clogged with construction dirt and debris, which may cause system damage.
WARNING! All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants. If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed.
SafetyWarnings, cautions and notices appear throughout this manual. Read these items carefully before attempting any installation, service, or troubleshooting of the equipment.
DANGER: Indicates an immediate hazardous situation, which if not avoided will result in death or serious injury. DANGER labels on unit access panels must be observed.
WARNING: Indicates a potentially hazardous situation, which if not avoided could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation or an unsafe practice, which if not avoided could result in minor or moderate injury or product or property damage.
NOTICE: Noti cation of installation, operation or maintenance information, which is important, but which is not hazard-related.
WARNING!
NOTE: Above model nomenclature is a general reference. Consult individual speci cation sections for detailed information.
WARNING! The EarthPure® Application and Service Manual should be read and understood before attempting to service refrigerant circuits with HFC-410A.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
4 G e o t h e r m a l H e a t i n g a n d C o o l i n g
General Information
CAUTION! DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can signi cantly reduce performance, reliability, and service life. Always move and store units in an upright position. Tilting units on their sides may cause equipment damage.
CAUTION!
CAUTION!
Pre Installation
CAUTION! CUT HAZARD - Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing heat pumps.
Inspection Upon receipt of the equipment, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the packaging of each unit, and inspect each unit for damage. Insure that the carrier makes proper notation of any shortages or damage on all copies of the freight bill and completes a common carrier inspection report. Concealed damage not discovered during unloading must be reported to the carrier within 15 days of receipt of shipment. If not led within 15 days, the freight company can deny the claim without recourse. Note: It is the responsibility of the purchaser to le all necessary claims with the carrier. Notify your equipment supplier of all damage within fteen (15) days of shipment.
Storage Equipment should be stored in its original packaging in a clean, dry area. Store units in an upright position at all times. Stack units a maximum of 3 units high.
Unit Protection Cover units on the job site with either the original packaging or an equivalent protective covering. Cap the open ends of pipes stored on the job site. In areas where painting, plastering, and/or spraying has not been completed, all due precautions must be taken to avoid physical damage to the units and contamination by foreign material. Physical damage and contamination may prevent proper start-up and may result in costly equipment clean-up.
Examine all pipes, ttings, and valves before installing any of the system components. Remove any dirt or debris found in or on these components.
Pre-Installation Installation, Operation, and Maintenance instructions are provided with each unit. Horizontal equipment is designed for installation above false ceiling or in a ceiling plenum. Other unit con gurations are typically installed in a mechanical room. The installation site chosen should include adequate service clearance around the unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check the system before operation.
Prepare units for installation as follows: 1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the correct unit has been shipped.
2. Keep the cabinet covered with the original packaging until installation is complete and all plastering, painting, etc. is nished.
3. Verify refrigerant tubing is free of kinks or dents and that it does not touch other unit components.
4. Inspect all electrical connections. Connections must be clean and tight at the terminals.
5. Remove any blower support packaging (water-to-air units only).
6. Loosen compressor bolts on units equipped with compressor grommet vibration isolation until the compressor rides freely on the grommets.
7. Locate and verify any hot water generator (HWG), hanger, or other accessory kit located in the compressor section or blower section.
5
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Horizontal Installation
Mounting Horizontal UnitsHorizontal units have hanger kits pre-installed from the factory as shown in Figure 1. Figure 3 shows a typical horizontal unit installation.
Horizontal heat pumps are typically suspended above a ceiling or within a soffi t using fi eld supplied, threaded rods sized to support the weight of the unit.
Use four (4) fi eld supplied threaded rods and factory provided vibration isolators to suspend the unit. Hang the unit clear of the fl oor slab above and support the unit by the mounting bracket assemblies only. DO NOT attach the unit fl ush with the fl oor slab above.
Pitch the unit toward the drain as shown in Figure 2 to improve the condensate drainage. On small units (less than 8.8kW) ensure that unit pitch does not cause condensate leaks inside the cabinet.
Drain Connection
1/4” (6.4mm) pitchtoward drain for drainage
Figure 1: Hanger Bracket
Figure 2: Horizontal Unit Pitch
Horizontal Unit LocationUnits are not designed for outdoor installation. Locate the unit in an INDOOR area that allows enough space for service personnel to perform typical maintenance or repairs without removing unit from the ceiling. Horizontal units are typically installed above a false ceiling or in a ceiling plenum. Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air). Consideration should be given to access for easy removal of the fi lter and access panels. Provide suffi cient room to make water, electrical, and duct connection(s).
If the unit is located in a confi ned space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be diffi cult to remove after the unit is installed should be removed prior to setting the unit. Refer to Figure 3 for an illustration of a typical installation. Refer to unit specifi cations catalog for dimensional data.
Conform to the following guidelines when selecting unit location:1. Provide a hinged access door in concealed-spline or
plaster ceilings. Provide removable ceiling tiles in T-bar or lay-in ceilings. Refer to horizontal unit dimensions for specifi c series and model in unit specifi cations catalog. Size the access opening to accommodate the service technician during the removal or replacement of the compressor and the removal or installation of the unit itself.
2. Provide access to hanger brackets, water valves and fi ttings. Provide screwdriver clearance to access panels, discharge collars and all electrical connections.
3. DO NOT obstruct the space beneath the unit with piping, electrical cables and other items that prohibit future removal of components or the unit itself.
4. Use a manual portable jack/lift to lift and support the weight of the unit during installation and servicing.
The installation of water source heat pump units and all associated components, parts and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
6 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Horizontal Installation
Figure 3: Typical Horizontal Unit Installation
Air Coil - To obtain maximum performance, the air coil should be cleaned before start-up. A 10% solution of dishwasher detergent and water is recommended for both sides of the coil. A thorough water rinse should follow.
7
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Horizontal Service Access
Left Return Back Discharge Right Return Back Discharge
Supply Air Flow
Supply Air Flow
Return Air Flow
Return Air Flow
Air C
oil
Air C
oil
Air C
oil
Air C
oil
Front Front
Front Front
BSP BSP
ASPASP ASP ASP
ASP ASP ASPASP
CCP CCP
CCP CCP
BSP BSP
Return Air Flow
Return Air Flow
Supply Air Flow
Supply Air Flow
Left Return Straight Discharge Right Return Straight Discharge
= mandatory 2 service access
= (optional) additional 2 service access
Notes:1. While clear access to all removable panels is not required,
installer should take care to comply with all building codes and allow adequate clearance for future fi eld service.
2. CCP and BSP requires 2’ service access.3. Blower service access is through back panel on straight
discharge units or through panel opposite air coil on back, discharge units.
4. ASP are removable panels that provide additional access to the units interior. Clear access to ASP panels is not required and they are not to be used in place of the mandatory CC and BSP panels.
Legend:CCP = Control/Compressor Access Panel BSP = Blower Service PanelASP = Additional Service Panel (not required)
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
8 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Water Connection End
Return Air
Remove Screws
Water Connection End
Return Air
Rotate
Move to Side
Side Discharge
Return Air
Water Connection End
Discharge Air
Drain
Back Discharge
Replace Screws
WaterConnection End
Supply Duct
Return Air
WaterConnection End
Drain
Return Air
Discharge Air
Side Discharge
Back Discharge
Field Conversion of Air Discharge
Figure 5: Right Return Side to Back
Figure 4: Left Return Side to BackOverview - Horizontal units can be fi eld converted between side (straight) and back (end) discharge using the instructions below.
Note: It is not possible to fi eld convert return air between left or right return models due to the necessity of refrigeration copper piping changes.
Preparation - It is best to fi eld convert the unit on the ground before hanging. If the unit is already hung it should be taken down for the fi eld conversion.
Side to Back Discharge Conversion1. Place unit in well lit area. Remove the screws as shown in
Figure 4 to free top panel and discharge panel.2. Lift out the access panel and set aside. Lift and rotate
the discharge panel to the other position as shown, being careful with the blower wiring.
3. Check blower wire routing and connections for tension or contact with sheet metal edges. Reroute if necessary.
4. Check refrigerant tubing for contact with other components.
5. Reinstall top panel and screws noting that the location for some screws will have changed.
6. Manually spin the fan wheel to ensure that the wheel is not rubbing or obstructed.
7. Replace access panels.
Back to Side Discharge Conversion - If the discharge is changed from back to side, use above instruction noting that illustrations will be reversed.
Left vs. Right Return - It is not possible to fi eld convert return air between left or right return models due to the necessity of refrigeration copper piping changes. However, the conversion process of side to back or back to side discharge for either right or left return confi guration is the same. In some cases, it may be possible to rotate the entire unit 180 degrees if the return air connection needs to be on the opposite side. Note that rotating the unit will move the piping to the other end of the unit.
9
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Figure 6: Horizontal Condensate Connection
Horizontal Installation
Condensate Piping – Horizontal UnitsPitch the unit toward the drain as shown in Figure 2 to improve the condensate drainage. On small units (less than 2.5 tons/8.8 kW), insure that unit pitch does not cause condensate leaks inside the cabinet.
Install condensate trap at each unit with the top of the trap positioned below the unit condensate drain connection as shown in Figure 6. Design the depth of the trap (water-seal) based upon the amount of ESP capability of the blower (where 2 inches [51mm] of ESP capability requires 2 inches [51mm] of trap depth). As a general rule, 1-1/2 inch [38mm] trap depth is the minimum.
Each unit must be installed with its own individual trap and connection to the condensate line (main) or riser. Provide a means to fl ush or blow out the condensate line. DO NOT install units with a common trap and/or vent.
Always vent the condensate line when dirt or air can collect in the line or a long horizontal drain line is required. Also vent when large units are working against higher external static pressure than other units connected to the same condensate main since this may cause poor drainage for all units on the line. WHEN A VENT IS INSTALLED IN THE DRAIN LINE, IT MUST BE LOCATED AFTER THE TRAP IN THE DIRECTION OF THE CONDENSATE FLOW.
CAUTION!
Duct System InstallationThe duct system should be sized to handle the design airfl ow quietly. Refer to Figure 3 for horizontal duct system details or fi gure 8 for vertical duct system details. A fl exible connector is recommended for both discharge and return air duct connections on metal duct systems to eliminate the transfer of vibration to the duct system. To maximize sound attenuation of the unit blower, the supply and return plenums should include internal fi berglass duct liner or be constructed from ductboard for the fi rst few feet. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended, as the unit’s performance will be adversely aff ected.
At least one 90° elbow should be included in the supply duct to reduce air noise. If air noise or excessive air fl ow is a problem, the blower speed can be changed. For airfl ow charts, consult specifi cations catalog for the series and model of the specifi c unit.
If the unit is connected to existing ductwork, a previous check should have been made to insure that the ductwork has the capacity to handle the airfl ow required for the unit. If ducting is too small, as in the replacement of a heating only system, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired as necessary.
DUCT SYSTEM INSTALLATION
CAUTION! Ensure condensate line is pitched toward drain 1/8 inch per ft [11mm per m] of run.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
10 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Vertical Installation Clearances
Air Coil Side
Front
‡ † 1”
1”1”
6”
*Recommended Minimum Installation Clearances for Vertical Units*
1”Back of unit
Side opposite return air
6” Front if hard piped
Return Air Side
1”
Ducted return
- ‡ *Add for duct width
- † Add 2” for 1” fi lter frame/rail or 3” for 2” fi lter frame/rail
Free (open) return - calculate required dimension for a maximum velocity of 600 fpm
*Field installed accessories (hoses, air cleaners, etc.) and factory WSE option willrequire additional space. Top supply air is shown, the same clearances apply to bottom supply air units.
urn
ASPASP
Air C
oil
Front
CCP and BSP
Supply Air Opening
Notes:1. While clear access to all removable
panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future fi eld service.
2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available.
3. ASP are removable panels that provide additional access to the units interior. Clear access to ASP panels is not required and they are not to be used in place of the mandatory CCPand BSP panels.
4. Top supply air is shown, the same clearances apply to bottom supply air units.
Legend:CCP = Control/Compressor Access Panel BSP = Blower Service PanelASP = Additional Service Panel (not required)
urn
ASPASP
Air C
oil
Front
CCP and BSP
Supply Air Opening
11
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Vertical Installation
Figure 7: Vertical Unit Mounting
Figure 8: Typical Vertical Unit Installation Using Ducted Return Air
Flexible canvas ductconnector to reducenoise and vibration
Use turning vanes insupply transition
Internally insulate supplyduct for first 1.2 m each wayto reduce noise
Internally insulate returntransition duct to reduce noise Rev.: 2/13
Rounded returntransition
Remove supply ductflanges from inside blowercompartment and installon supply air opening ofunit. Do not use a supplyair plenum/duct smaller than the size of the supply duct flanges.
Vertical Unit LocationUnits are not designed for outdoor installation. Locate the unit in an INDOOR area that allows enough space for service personnel to perform typical maintenance or repairs without removing unit from the mechanical room/closet. Vertical units are typically installed in a mechanical room or closet. Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air). Consideration should be given to access for easy removal of the fi lter and access panels. Provide suffi cient room to make water, electrical, and duct connection(s).
If the unit is located in a confi ned space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be diffi cult to remove after the unit is installed should be removed prior to setting the unit. Refer to Figures 7 and 8 for typical installation illustrations. Refer to unit specifi cations catalog for dimensional data.1. Install the unit on a piece of rubber, neoprene or other
mounting pad material for sound isolation. The pad should be at least 3/8” [10mm] to 1/2” [13mm] in thickness. Extend the pad beyond all four edges of the unit.
2. Provide adequate clearance for fi lter replacement and drain pan cleaning. Do not block fi lter access with piping, conduit or other materials. Refer to unit specifi cations for dimensional data.
3. Provide access for fan and fan motor maintenance and for servicing the compressor and coils without removing the unit.
4. Provide an unobstructed path to the unit within the closet or mechanical room. Space should be suffi cient to allow removal of the unit, if necessary.
5. Provide access to water valves and fi ttings and screwdriver access to the unit side panels, discharge collar and all electrical connections.
Downfl ow units may be installed directly on the fl oor. The optional internal electric heat is rated for zero clearance to combustible materials.
The installation of water source heat pump units and all associated components, parts and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
12 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Vertical Installation
Return Air Inlet
Figure 9: Vertical Sound Attenuation
Vent
*3/4" FPT
3/4" PVC
AlternateCondensate
Location
WaterConnections
1/8" per footslope to drain
Figure 10a: Vertical Unit with Internal Condensate Trap
Figure 10c: Vertical Internal Condensate Trap
Condensate Piping for Vertical Units - Some units utilize a condensate hose inside the cabinet as a trapping loop; therefore an external trap is not necessary, other units require an external condensate trap. Observe the condensate drain connection to determine if a fi eld provided trap is necessary. Units with a PVC socket connection are internally trapped, units with stainless steel MPT connection require an external trap. Figures 10a and b show typical condensate connections. Figure 10c illustrates the internal trap that is present in some units. Each unit must be installed with its own individual trap and connection to the condensate line (main) or riser. Provide a means to fl ush or blow out the condensate line. DO NOT install units with a common trap and/or vent. Always vent the condensate line when dirt or air can collect in the line or a long horizontal drain line is required. Also vent when large units are working against higher external static pressure than other units connected to the same condensate main since this may cause poor drainage for all units on the line. WHEN A VENT IS INSTALLED IN THE DRAIN LINE, IT MUST BE LOCATED AFTER THE TRAP IN THE DIRECTION OF THE CONDENSATE FLOW. Install the external condensate trap with the top of the trap positioned below the unit condensate drain connection as shown in fi gure 10b. Design the depth of the trap (water-seal) based upon the amount of the ESP capability of the blower (ex. 2 inches (51mm) of ESP capability requires 2 inches (51mm) of trap depth). As a general rule, 1-1/2 inch (38mm) trap depth is the minimum.
Sound Attenuation for Vertical Units - Sound attenuation is achieved by enclosing the unit within a small mechanical room or a closet. Additional measures for sound control include the following:1. Mount the unit so that the return air inlet is 90° to the
return air grille. Refer to Figure 9. Install a sound baffl e as illustrated to reduce line-of sight sound transmitted through return air grilles.
2. Mount the unit on a Tranquility Unit Isolation Pad to minimize vibration transmission to the building structure. For more information on Tranquility Unit Isolation Pads, contact your distributor.
Figure 10b: Vertical Unit with External Condensate Trap
CAUTION! CAUTION! Ensure condensate line is pitched toward drain 1/8 inch per ft [11mm per m] of run.
13
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Water Connection Installation
External Flow Controller MountingThe Flow Controller can be mounted beside the unit as shown in Figure 12. Review the Flow Controller installation manual for more details.
Gasket
Swivel Nut
Stainless steel snap ring
Brass Adaptor
Hand Tighten Only!
Do Not Overtighten!
Figure 11: Water Connections
Pre-InstallationPrior to installation, locate and mark all existing underground utilities, piping, etc. Install loops for new construction before sidewalks, patios, driveways, and other construction has begun. During construction, accurately mark all ground loop piping on the plot plan as an aid in avoiding potential future damage to the installation.
Piping InstallationThe typical closed loop ground source system is shown in Figure 12. All earth loop piping materials should be limited to polyethylene fusion only for in-ground sections of the loop. Galvanized or steel fi ttings should not be used at any time due to their tendency to corrode. All plastic to metal threaded fi ttings should be avoided due to their potential to leak in earth coupled applications. A fl anged fi tting should be substituted. P/T plugs should be used so that fl ow can be measured using the pressure drop of the unit heat exchanger. Earth loop temperatures can range between 25 and 110°F [-4 to 43°C]. Flow rates between 2.25 and 3 gpm per ton [2.41 to 3.23 l/m per kW] of cooling capacity is recommended in these applications.
Test individual horizontal loop circuits before backfi lling. Test vertical U-bends and pond loop assemblies prior to installation. Pressures of at least 100 psi [689 kPa] should be used when testing. Do not exceed the pipe pressure rating. Test entire system when all loops are assembled.
Flushing the Earth LoopOnce piping is completed between the unit, Flow Controller and the ground loop (Figure 12), the loop is ready for fi nal purging and charging. A fl ush cart with at least a 1.5 hp [1.1 kW] pump is required to achieve enough fl uid velocity in the loop piping system to purge air and dirt particles. An
GROUND-LOOP HEAT PUMP APPLICATIONS
CAUTION!
High and Low Voltage Knockouts
Vibration Isolation Pad
To Thermostat
Figure 12: Typical Ground-Loop Application
CAUTION! The following instructions represent industry accepted installation practices for closed loop earth coupled heat pump systems. Instructions are provided to assist the contractor in installing trouble free ground loops. These instructions are recommendations only. State/provincial and local codes MUST be followed and installation MUST conform to ALL applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
Water ConnectionsResidential models utilize swivel piping fi ttings for water connections that are rated for 450 psi (3101 kPa) operating pressure. The connections have a rubber gasket seal similar to a garden hose gasket, which when mated to the fl ush end of most 1” threaded male pipe fi ttings provides a leak-free seal without the need for thread sealing tape or joint compound. Check for burrs and ensure that the rubber seal is in the swivel connector prior to attempting any connection (rubber seals are shipped attached to the swivel connector). DO NOT OVER TIGHTEN or leaks may occur.
The female locking ring is threaded onto the pipe threads which holds the male pipe end against the rubber gasket, and seals the joint. HAND TIGHTEN ONLY! DO NOT OVERTIGHTEN!
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
14 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Ground-Loop Heat Pump Applications
antifreeze solution is used in most areas to prevent freezing. All air and debris must be removed from the earth loop piping before operation. Flush the loop with a high volume of water at a minimum velocity of 2 fps (0.6 m/s) in all piping. The steps below must be followed for proper fl ushing. 1. Fill loop with water from a garden hose through the fl ush
cart before using the fl ush cart pump to insure an even fi ll. 2. Once full, the fl ushing process can begin. Do not allow
the water level in the fl ush cart tank to drop below the pump inlet line to avoid air being pumped back out to the earth loop.
3. Try to maintain a fl uid level in the tank above the return tee so that air cannot be continuously mixed back into the fl uid. Surges of 50 psi (345 kPa) can be used to help purge air pockets by simply shutting off the return valve going into the fl ush cart reservoir. This “dead heads” the pump to 50 psi (345 kPa). To purge, dead head the pump until maximum pumping pressure is reached. Open the return valve and a pressure surge will be sent through the loop to help purge air pockets from the piping system.
4. Notice the drop in fl uid level in the fl ush cart tank when the return valve is shut off . If air is adequately purged from the system, the level will drop only 1-2 inches (2.5 - 5 cm) in a 10” (25 cm) diameter PVC fl ush tank (about a half gallon [2.3 liters]), since liquids are incompressible. If the level drops more than this, fl ushing should continue since air is still being compressed in the loop fl uid. Perform the “dead head” procedure a number of times. Note: This fl uid level drop is your only indication of air in the loop.
5. Consult ClimaDry AOM for fl ushing instructions for units equipped with ClimaDry Whole House Dehumidifi cation option.
Antifreeze may be added before, during or after the fl ushing procedure. However, depending upon which time is chosen, antifreeze could be wasted when emptying the fl ush cart tank. See antifreeze section for more details.
Loop static pressure will fl uctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fl uctuation is normal and should be considered when charging the system initially. Run the unit in either heating or cooling for a number of minutes to condition the loop to a homogenous temperature. This is a good time for tool cleanup, piping insulation, etc. Then, perform fi nal fl ush and pressurize the loop to a static pressure of 50-75 psi [345-517 kPa] (winter) or 35-40 psi [241-276 kPa] (summer). After pressurization, be sure to loosen the plug at the end of the Grundfos loop pump motor(s) to allow trapped air to be discharged and to insure the motor housing has been fl ooded. This is not required for Taco circulators. Insure that the Flow Controller provides adequate fl ow through the unit by checking pressure drop across the heat exchanger and compare to the pressure drop tables at the back of the manual.
AntifreezeIn areas where minimum entering loop temperatures drop below 40°F [5°C] or where piping will be routed through areas subject to freezing, antifreeze is required. Alcohols and glycols are commonly used as antifreeze; however your local sales manager should be consulted for the antifreeze best suited to your area. Low temperature protection should be maintained to 15°F [9°C] below the lowest expected entering loop temperature. For example, if 30°F [-1°C] is the minimum expected entering loop temperature, the leaving loop temperature would be 25 to 22°F [-4 to -6°C] and low temperature protection should be at 15°F [-10°C]. Calculation is as follows:30°F - 15°F = 15°F [-1°C - 9°C = -10°C].
All alcohols should be premixed and pumped from a reservoir outside of the building when possible or introduced under the water level to prevent fumes. Calculate the total volume of fl uid in the piping system. Then use the percentage by volume shown in Table 2 for the amount of antifreeze needed. Antifreeze concentration should be checked from a well mixed sample using a hydrometer to measure specifi c gravity.
Table 1: Approximate Fluid Volume (gal.) per 100' of Pipe
Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)Pipe Size Volume (gal) [liters]
Copper
1” 4.1 [15.3]
1.25” 6.4 [23.8]
2.5” 9.2 [34.3]
Rubber Hose 1” 3.9 [14.6]
Polyethylene
3/4” IPS SDR11 2.8 [10.4]
1” iPS SDR11 4.5 [16.7]
1.25” IPS SDR11 8.0 [29.8]
1.5” IPS SDR11 10.9 [40.7]
2” IPS SDR11 18.0 [67.0]
1.25” IPS SCH40 8.3 [30.9]
1.5” IPS SCH40 10.9 [40.7]
2” IPS SCH40 17.0 [63.4]
Unit Heat Exchanger Typical 1.0 [3.8]
Flush Cart Tank 10” Dia x 3ft tall[254mm x 91.4cm tall] 10 [37.9]
Low Water Temperature Cutout Setting - CXM ControlWhen antifreeze is selected, the FP1 jumper (JW3) should be clipped to select the low temperature (antifreeze 10°F [-12.2°C]) set point and avoid nuisance faults (see “Low Water Temperature Cutout Selection” in this manual). Note: Low water temperature operation requires extended range equipment.
15
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Table 2: Antifreeze Percentages by Volume
Ground-Loop Heat Pump Applications
GROUND-WATER HEAT PUMP APPLICATIONSOpen Loop - Ground Water SystemsTypical open loop piping is shown in Figure 13. Shut off valves should be included for ease of servicing. Boiler drains or other valves should be “tee’d” into the lines to allow acid fl ushing of the heat exchanger. Shut off valves should be positioned to allow fl ow through the coax via the boiler drains without allowing fl ow into the piping system. P/T plugs should be used so that pressure drop and temperature can be measured. Supply and return water piping should be limited to copper, HPDE, or other acceptable high temperature material. Note that PVC or CPVC material is not recommended as they are not compatible with the polyolester oil used in HFC-410A products.
Water quantity should be plentiful and of good quality. Consult table 3 for water quality guidelines. The unit can be ordered with either a copper or cupro-nickel water heat exchanger. Consult table 3 for recommendations. Copper is recommended for closed loop systems and open loop ground water systems that are not high in mineral content or corrosiveness. In conditions anticipating heavy scale formation or in brackish water, a cupro-nickel heat exchanger is recommended. In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, an open loop system is not recommended. Heat exchanger coils may over time lose heat exchange capabilities due to build up of mineral deposits. Heat exchangers must only be serviced by a qualifi ed technician, as acid and special pumping equipment is required. Desuperheater coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional acid fl ushing. In some cases, the desuperheater option should not be recommended due to hard water conditions and additional maintenance required.
Water Quality StandardsTable 3 should be consulted for water quality requirements. Scaling potential should be assessed using the pH/Calcium hardness method. If the pH <7.5 and the Calcium hardness is less than 100 ppm, scaling potential is low. If this method yields numbers out of range of those listed, the Ryznar Stability and Langelier Saturation indecies should be calculated. Use the appropriate scaling surface temperature for the application, 150°F [66°C] for direct use (well water/
open loop) and DHW (desuperheater); 90°F [32°F] for indirect use. A monitoring plan should be implemented in these probable scaling situations. Other water quality issues such as iron fouling, corrosion prevention and erosion and clogging should be referenced in Table 3.
Pressure Tank and PumpUse a closed, bladder-type pressure tank to minimize mineral formation due to air exposure. The pressure tank should be sized to provide at least one minute continuous run time of the pump using its drawdown capacity rating to prevent pump short cycling. Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local building codes (e.g. recharge well, storm sewer, drain fi eld, adjacent stream or pond, etc.). Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning department to assure compliance in your area. The pump should be sized to handle the home’s domestic water load (typically 5-9 gpm [23-41 l/m]) plus the fl ow rate required for the heat pump. Pump sizing and expansion tank must be chosen as complimentary items. For example, an expansion tank that is too small can causing premature pump failure due to short cycling. Variable speed pumping applications should be considered for the inherent energy savings and smaller pressure tank requirements.
Water Control ValveNote the placement of the water control valve in fi gure 13. Always maintain water pressure in the heat exchanger by placing the water control valve(s) on the discharge line to prevent mineral precipitation during the off -cycle. Pilot operated slow closing valves are recommended to reduce water hammer. If water hammer persists, a mini-expansion tank can be mounted on the piping to help absorb the excess hammer shock. Insure that the total ‘VA’ draw of the valve can be supplied by the unit transformer. For instance, a slow closing valve can draw up to 35VA. This can overload smaller 40 or 50 VA transformers depending on the other controls in the circuit. A typical pilot operated solenoid valve draws approximately 15VA (see Figure 22). Note the special wiring diagrams for slow closing valves (Figures 23 & 24).
Flow RegulationFlow regulation can be accomplished by two methods. One method of fl ow regulation involves simply adjusting the ball
Type
Minimum Temperature for Low Temperature Protection
10°F [-12.2°C]
15°F [-9.4°C]
20°F [-6.7°C]
25°F [-3.9°C]
MethanolPropylene GlycolEthanol*
21%29%23%
17%24%20%
13%18%16%
8%12%11%
* Must not be denatured with any petroleum based product
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
16 G e o t h e r m a l H e a t i n g a n d C o o l i n g
VibrationIsolation Pad
Unit PowerDisconnect
High and lowvoltage knockouts
PressureTank
Shut-OffValve
BoilerDrains
FlowRegulator
Water InWater Out
WaterControlValve
OptionalFilter
P/T Plugs
To Thermostat
Figure 13: Typical Open Loop/Well Application
Ground-Water Heat Pump Applications
valve or water control valve on the discharge line. Measure the pressure drop through the unit heat exchanger, and determine fl ow rate from tables 9a through 9c. Since the pressure is constantly varying, two pressure gauges may be needed. Adjust the valve until the desired fl ow of 1.5 to 2 gpm per ton [2.0 to 2.6 l/m per kW] is achieved. A second method of fl ow control requires a fl ow control device mounted on the outlet of the water control valve. The device is typically a brass fi tting with an orifi ce of rubber or plastic material that is designed to allow a specifi ed fl ow rate. On occasion, fl ow control devices may produce velocity noise that can be reduced by applying some back pressure from the ball valve located on the discharge line. Slightly closing the valve will spread the pressure drop over both devices, lessening the velocity noise. NOTE: When EWT is below 50°F [10°C], a minimum of 2 gpm per ton (2.6 l/m per kW) is required.
Water Coil Low Temperature Limit SettingFor all open loop systems the 30°F [-1.1°C] FP1 setting (factory setting-water) should be used to avoid freeze damage to the unit. See “Low Water Temperature Cutout Selection” in this manual for details on the low limit setting.
CAUTION! CAUTION! Refrigerant pressure activated water regulating valves should never be used with this equipment.
WARNING! WARNING! Polyolester Oil, commonly known as POE oil, is a synthetic oil used in many refrigeration systems including those with HFC-410A refrigerant. POE oil, if it ever comes in contact with PVC or CPVC piping, may cause failure of the PVC/CPVC. PVC/CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC-410A as system failures and property damage may result.
17
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Water QualityParameter
HXMaterial
ClosedRecirculating Open Loop and Recirculating Well
Scaling Potential - Primary Measurement
pH/Calcium HardnessAll
-pH < 7.5 and Ca Hardness <100ppm
Method
Index Limits for Probable Scaling Situations - (Operation outside these limits is not recommended)
RyznarAll
- 6.0 - 7.5Stability Index If >7.5 minimize steel pipe use.
Langelier All- -0.5 to +0.5
Saturation Index If <-0.5 minimize steel pipe use. Based upon 66°C HWG andDirect well, 29°C Indirect Well HX
Iron FoulingIron Fe 2+ (Ferrous) All
- <0.2 ppm (Ferrous)(Bacterial Iron potential) If Fe2+ (ferrous)>0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.
Iron Fouling All- <0.5 ppm of Oxygen
Above this level deposition will occur .
Corrosion Prevention
pH All6 - 8.5 6 - 8.5
Monitor/treat asneeded Minimize steel pipe below 7 and no open tanks with pH <8
Hydrogen Sulfide (H2S) All- <0.5 ppm
At H2S>0.2 ppm, avoid use of copper and copper nickel piping or HX's.Rotten egg smell appears at 0.5 ppm level.
Copper alloy (bronze or brass) cast components are OK to <0.5 ppm.Ammonia ion as hydroxide, chloride, nitrate and sulfate compounds All - <0.5 ppm
Maximum
Maximum Allowable at maximum water temperature.
Chloride Levels
10 C 24 C 38 CCopper
Cupronickel- <20ppm NR NR- <150 ppm NR NR
304 SS - <400 ppm <250 ppm <150 ppm316 SS - <1000 ppm <550 ppm < 375 ppm
Titanium - >1000 ppm >550 ppm >375 ppm
Erosion and Clogging
Particulate Size andErosion
All
<10 ppm of particlesand a maximumvelocity of 1.8 m/sFiltered for maximum841 micron [0.84 mm,20 mesh] size.
<10 ppm (<1 ppm "sandfree” for reinjection) of particles and a maximum velocity of 1.8 m/s. Filtered for maximum 841 micron 0.84 mm,20 mesh] size. Any particulate that is not removed can potentiallyclog components.
Notes:
Rev.: 5/6/2014 S
• NR - Application not recommended.• "-" No design Maximum.
• Closed Recirculating system is identified by a closed pressurized piping system.• Recirculating open wells should observe the open recirculating design considerations.
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below
Scaling indexes should be calculated at 66°C for direct use and HWG applications, and at 32°C for indirect HX use. A monitoring plan should be implemented.
The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. The water should be evaluated by an independent testing facility comparing to this Table and when properties are outside of these requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water. Failure to do so will void the warranty for the coaxial heat exchanger and any other components damaged by a leak.
Water Quality Standards
Table 3: Water Quality Standards
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
18 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Electric water heaters are recommended. If a gas, propane, or oil water heater is used, a second preheat tank must be installed (Figure 15). If the electric water heater has only a single center element, the dual tank system is recommended to insure a usable entering water temperature for the HWG.
Typically a single tank of at least 52 gallons (235 liters) is used to limit installation costs and space. However, a dual tank, as shown in Figure 15, is the most effi cient system, providing the maximum storage and temperate source water to the HWG.
It is always advisable to use water softening equipment on domestic water systems to reduce the scaling potential and lengthen equipment life. In extreme water conditions, it may be necessary to avoid the use of the HWG option since the potential cost of frequent maintenance may off set or exceed any savings. Consult Table 3 for scaling potential tests.
Hot Water Generator
The HWG (Hot Water Generator) or desuperheater option provides considerable operating cost savings by utilizing excess heat energy from the heat pump to help satisfy domestic hot water requirements. The HWG is active throughout the year, providing virtually free hot water when the heat pump operates in the cooling mode or hot water at the COP of the heat pump during operation in the heating mode. Actual HWG water heating capacities are provided in the appropriate heat pump performance data.
Heat pumps equipped with the HWG option include a built-in water to refrigerant heat exchanger that eliminates the need to tie into the heat pump refrigerant circuit in the fi eld. The control circuit and pump are also built in for residential equipment. Figure 14 shows a typical example of HWG water piping connections on a unit with built-in circulating pump. This piping layout reduces scaling potential.
The temperature set point of the HWG is fi eld selectable to 125°F or 150°F . The 150°F set point allows more heat storage from the HWG. For example, consider the amount of heat that can be generated by the HWG when using the 125°F set point, versus the amount of heat that can be generated by the HWG when using the 150°F set point.
In a typical 50 gallon two-element electric water heater the lower element should be turned down to 100°F, or the lowest setting, to get the most from the HWG. The tank will eventually stratify so that the lower 80% of the tank, or 40 gallons, becomes 100°F (controlled by the lower element). The upper 20% of the tank, or 10 gallons, will be maintained at 125°F (controlled by the upper element).
Using a 125°F set point, the HWG can heat the lower 40 gallons of water from 100°F to 125°F, providing up to 8,330 btu’s of heat. Using the 150°F set point, the HWG can heat the same 40 gallons of water from 100°F to 150°F and the remaining 10 gallons of water from 125°F to 150°F, providing a total of up to 18,743 btu’s of heat, or more than twice as much heat as when using the 125°F set point.
This example ignored standby losses of the tank. When those losses are considered the additional savings are even greater.
Figure 14: Typical HWG Installation
Figure 15: HWG Double Tank In stal la tion
WARNING! WARNING! A 150°F SETPOINT MAY LEAD TO SCALDING OR BURNS. THE 150°F SET POINT MUST ONLY BE USED ON SYSTEMS THAT EMPLOY AN APPROVED ANTI-SCALD VALVE.
Hot Outletto home
Insulated water lines - 5/8” OD, 50 ft maximum (one way)[16mm OD, 15 meters maximum]
PoweredWaterHeater
Upperelement to120 - 130°F[49 - 54°C]
Lowerelement to
100 - 110°F[38 - 43°C]
Shut-offValve #3
Shut Off Valve #2
Field supplied 3/4’ brass nipple and ‘T’
ColdInlet
Shut Off Valve #4
Shut Off Valve #1
Insulated water lines - 5/8” OD, 50 ft maximum (one way)
[16mm OD, 15 meters maximum]
Upper element to 130°F [54°C]
(or owner preference)
Cold Inlet
Hot Outlet tohouse
Powered
Water Heater
Cold Inlet fromDomestic supply
Hot Outlet
Unpowered
Water Heater
Field Supplied 3/4” brass nipple and “T”
Lower element to 120°F [49°C]
Shut-offValve #1
Shut-offValve #4
Shut-offValve #3
Shut Off Valve #2
19
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Hot Water Generator
The microprocessor control monitors the refrigerant and water temperatures to determine when to operate the HWG. The HWG will operate any time the refrigerant temperature is suf ciently above the water temperature. Once the HWG has satis ed the water heating demand during a heat pump run cycle, the controller will cycle the pump at regular Intervals to determine if an additional HWG cycle can be utilized. The microprocessor control Includes 3 DIP switches, SW10 (HWG PUMP TEST), SW11 (HWG TEMP), and SW12 (HWG STATUS).
SW10 HWG PUMP TEST. When this switch is in the “ON” position, the HWG pump is forced to operate even if there is no call for the HWG. This mode may be bene cial to assist in purging the system of air during Initial start up. When SW10 is in the “OFF” position, the HWG will operate normally. This switch is shipped from the factory in the “OFF” (normal) position. NOTE; If left in the “On” position for 5 minutes, the pump control will revert to normal operation.
SW11 HWG TEMP. The control setpoint of the HWG can be set to either of two temperatures, 125°F or 150°F. When SW11 is in the “ON” position the HWG setpoint is 150°F. When SW11 is in the “OFF” position the HWG setpoint is
WARNING!
WARNING!
WARNING! UNDER NO CIRCUMSTANCES SHOULD THE SENSORS BE DISCONNECTED OR REMOVED AS FULL LOAD CONDITIONS CAN DRIVE HOT WATER TANK TEMPERATURES FAR ABOVE SAFE TEMPERATURE LEVELS IF SENSORS HAVE BEEN DISCONNECTED OR REMOVED.
WARNING! USING A 150°F SETPOINT ON THE HWG WILL RESULT IN WATER TEMPERATURES SUFFICIENT TO CAUSE SEVERE PHYSICAL INJURY IN THE FORM OF SCALDING OR BURNS, EVEN WHEN THE HOT WATER TANK TEMPERATURE SETTING IS VISIBLY SET BELOW 150°F. THE 150°F HWG SETPOINT MUST ONLY BE USED ON SYSTEMS THAT EMPLOY AN APPROVED ANTI-SCALD VALVE (PART NUMBER AVAS4) AT THE HOT WATER STORAGE TANK WITH SUCH VALVE PROPERLY SET TO CONTROL WATER TEMPERATURES DISTRIBUTED TO ALL HOT WATER OUTLETS AT A TEMPERATURE LEVEL THAT PREVENTS SCALDING OR BURNS!
125°F. This switch Is shipped from the factory in the “OFF” (125°F) position.
SW12 HWG STATUS. This switch controls operation of the HWG. When SW12 is in the “ON” position the HWG is disabled and will not operate. When SW12 is in the “OFF” position the HWG is in the enabled mode and will operate normally. This switch is shipped from the factory in the “ON” (disabled) position. CAUTION: DO NOT PLACE THIS SWITCH IN THE ENABLED POSITION UNITL THE HWG PIPING IS CONNECTED, FILLED WITH WATER, AND PURGED OR PUMP DAMAGE WILL OCCUR.
When the control is powered and the HWG pump output is not active, the status LED (AN1) will be “On”. When the HWG pump output is active for water temperature sampling or HWG operation, the status LED will slowly ash (On 1 second, Off 1 second).
If the control has detected a fault, the status LED will ash a numeric fault code as follows:
Hot Water Sensor Fault 1 ash Compressor Discharge sensor fault 2 ashes High Water Temperature (>160ºF) 3 ashes Control Logic Error 4 ashes
Fault code ashes have a duration of 0.4 seconds with a 3 second pause between fault codes. For example, a “Compressor Discharge sensor fault” will be four ashes 0.4 seconds long, then a 3 second pause, then four ashes again, etc.
C
H
M
WATER HEATER
CHECK VALVE
8” M
AX
HOT WATERTO HOUSE
ANTI-SCALDVALVE
ANTI-SCALDVALVE PIPINGCONNECTIONS
COLD WATERSUPPLY
InstallationThe HWG is controlled by two sensors and a microprocessor control. One sensor is located on the compressor discharge line to sense the discharge refrigerant temperature. The other sensor is located on the HWG heat exchanger’s “Water In” line to sense the potable water temperature.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
20 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Warning! The HWG pump Is fully wired from the factory. Use extreme caution when working around the microprocessor control as it contains line voltage connections that presents a shock hazard that can cause severe injury or death!
The heat pump, water piping, pump, and hot water tank should be located where the ambient temperature does not fall below 50°F [10°C]. Keep water piping lengths at a minimum. DO NOT use a one way length greater than 50 ft. (one way) [15 m]. See Table 7 for recommended piping sizes and maximum lengths.
All installations must be in accordance with local codes. The installer is responsible for knowing the local requirements, and for performing the installation accordingly. DO NOT connect the pump wiring until “Initial Start-Up” section, below. Powering the pump before all installation steps are completed may damage the pump.
Water Tank Preparation1. Turn off power or fuel supply to the hot water tank.2. Connect a hose to the drain valve on the water tank.3. Shut off the cold water supply to the water tank.4. Open the drain valve and open the pressure relief valve
or a hot water faucet to drain tank.5. When using an existing tank, it should be fl ushed with
cold water after it is drained until the water leaving the drain hose is clear and free of sediment.
6. Close all valves and remove the drain hose.7. Install HWG water piping.
HWG Water Piping1. Using at least 5/8” [16mm] O.D. copper, route and install
the water piping and valves as shown in Figures 14 or 15. Install an approved anti-scald valve if the 150°F HWG setpoint is or will be selected. An appropriate method must be employed to purge air from the HWG piping. This may be accomplished by fl ushing water through the HWG (as In Figures 14 and 15) or by Installing an air vent at the high point of the HWG piping system.
2. Insulate all HWG water piping with no less than 3/8” [10mm] wall closed cell insulation.
3. Open both shut off valves and make sure the tank drain valve is closed.
Water Tank Refi ll 1. Close valve #4. Ensure that the HWG valves (valves #2
and #3) are open. Open the cold water supply (valve #1) to fi ll the tank through the HWG piping. This will purge air from the HWG piping.
2. Open a hot water faucet to vent air from the system until water fl ows from faucet; turn off faucet. Open valve #4.
3. Depress the hot water tank pressure relief valve handle to ensure that there is no air remaining in the tank.
4. Inspect all work for leaks.
5. Before restoring power or fuel supply to the water heater, adjust the temperature setting on the tank thermostat(s) to insure maximum utilization of the heat available from the refrigeration system and conserve the most energy. On tanks with both upper and lower elements and thermostats, the lower element should be turned down to 100°F [38°C] or the lowest setting; the upper element should be adjusted to 120-130°F [49-54°C]. Depending upon the specifi c needs of the customer, you may want to adjust the upper element diff erently. On tanks with a single thermostat, a preheat tank should be used (Fig 15).
6. Replace access cover(s) and restore power or fuel supply.
Initial Start-Up1. Make sure all valves in the HWG water circuit are
fully open.2. Turn on the heat pump and allow it to run for
10-15 minutes.3. Set SW12 to the “OFF” position (enabled) to engage the
HWG.4. The HWG pump should not run if the compressor is not
running.5. The temperature diff erence between the water entering
and leaving the HWG coil should be approximately 5-10°F [3-6°C].
6. Allow the unit to operate for 20 to 30 minutes to insure that it is functioning properly.
Hot Water Generator
Table 7: HWG Water Piping Sizes and Length
Unit Nominal Tonnage
Nominal HWG Flow
(gpm)
1/2" Copper (max length*)
3/4" Copper (max length*)
1.5 0.6 50 -
2.0 0.8 50 -
2.5 1.0 50 -
3.0 1.2 50 -
3.5 1.4 50 -
4.0 1.6 45 50
5.0 2.0 25 50
6.0 2.4 10 50
*Maximum length is equivalent length (in feet) one way of type L
copper.
CAUTION! CAUTION! Use only copper piping for HWG piping due to the potential of high water temperatures for water that has been in the HWG heat exchanger during periods of no-fl ow conditions (HWG pump not energized). Piping other than copper may rupture due to high water temperature and potable water pressure.
21
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Electrical - Line Voltage
WARNING! CAUTION! WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.
CAUTION! Use only copper conductors for fi eld installed electrical wiring. Unit terminals are not designed to accept other types of conductors.
Standard TS Unit
Model
Compressor HWGPumpFLA
Ext Loop Pump FLA
FanMotorFLA
TotalUnitFLA
MinCircuitAmps
MaxFuse/HACR
(2)RLA LRA Qty
PSC Electrical Data
018 9.0 48.0 1 0.40 4.0 1.0 14.4 16.7 25
024 13.5 58.3 1 0.50 4.0 1.6 19.6 22.9 35
030 12.8 64.0 1 0.50 4.0 1.8 19.1 22.3 35
036 16.0 77.0 1 0.50 4.0 1.8 22.3 26.3 40
042 16.7 79.0 1 0.50 4.0 2.2 23.4 27.5 40
048 21.8 117.0 1 0.50 4.0 2.7 29.0 34.4 50
060 26.4 134.0 1 0.50 4.0 3.8 34.7 41.3 60
ECM Electrical Data
018 9.0 48.0 1 0.40 4.0 3.9 17.3 19.6 25
024 13.5 58.3 1 0.50 4.0 3.9 21.9 25.2 35
030 12.8 64.0 1 0.50 4.0 3.9 21.2 24.4 35
036 16.0 77.0 1 0.50 4.0 3.9 24.4 28.4 40
042 16.7 79.0 1 0.50 4.0 3.9 25.1 29.2 45
048 21.8 117.0 1 0.50 4.0 6.9 33.2 38.6 60
060 26.4 134.0 1 0.50 4.0 6.9 37.8 44.4 70
070 30.8 178.0 1 0.50 4.0 6.9 42.2 49.9 80
Table 4a: Tranquility® 30 (TT) Series Electrical Data
Table 4b: Tranquility® 20 (TS) Series Electrical Data
Rated Voltage of 208-230/60/1 Min/Max Voltage of 197/254HACR circuit breaker in USA only All fuses Class RK-5Wire length based on one way measurement with 2% voltage drop Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.
All TT Units with Emerson ECM Fan Motor TT Units (ECM) Standard TT Units (ECM) with ClimaDry
Model
Compressor HWGPumpFLA
Ext Loop Pump FLA
FanMotorFLA
TotalUnitFLA
MinCircuitAmps
MaxFuse/HACR
(2)
ClimaDryPumpFLA
TotalUnitFLA
MinCircuitAmps
Max/Fuse
HACR(2)RLA LRA Qty
026 11.7 58.3 1 0.5 4.0 3.9 20.1 23.0 30 0.8 20.9 23.8 35
038 15.3 83.0 1 0.5 4.0 3.9 23.7 27.5 40 0.8 24.5 28.3 40
049 21.2 104.0 1 0.5 4.0 6.9 32.6 37.9 50 1.1 33.7 39.0 60
064 27.1 152.9 1 0.5 4.0 6.9 38.5 45.2 70 1.1 39.6 46.3 70
072 29.7 179.2 1 0.5 4.0 6.9 41.1 48.5 70 1.1 42.2 49.6 70
Rated Voltage of 208-230/60/1 Min/Max Voltage of 197/254HACR circuit breaker in USA only All fuses Class RK-5
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
22 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Electrical - Line Voltage
Electrical - Line VoltageAll fi eld installed wiring, including electrical ground, must comply with the National Electrical Code as well as all applicable local codes. Refer to the unit electrical data for fuse sizes. Consult wiring diagram for fi eld connections that must be made by the installing (or electrical) contractor.
All fi nal electrical connections must be made with a length of fl exible conduit to minimize vibration and sound transmission to the building.
General Line Voltage WiringBe sure the available power is the same voltage and phase shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
WARNING!
CAUTION!
Unit Power Supply(see electrical table for wire
and breaker size)
Connect the blue wire to:H for High speed fanM for Medium speed fanL for Low speed fanMedium is factory setting
Fan Motor
Figure 17: PSC Motor Speed Selection
WARNING! Disconnect electrical power source to prevent injury or death from electrical shock.
CAUTION! Use only copper conductors for fi eld installed electrical wiring. Unit terminals are not designed to accept other types of conductors.
Blower Speed Selection – Units with PSC MotorPSC (Permanent Split Capacitor) blower fan speed can be changed by moving the blue wire on the fan motor terminal block to the desired speed as shown in Figure 17. Optional ECM motor speeds are set via low voltage controls (see “ECM Blower Control”). Most units are shipped on the medium speed tap. Consult specifi cations catalog for specifi c unit airfl ow tables. Typical unit design delivers rated airfl ow at nominal static (0.15 in. w.g. [37Pa]) on medium speed and rated airfl ow at a higher static (0.4 to 0.5 in. w.g. [100 to 125 Pa]) on high speed for applications where higher static is required. Low speed will deliver approximately 85% of rated airfl ow at 0.10 in. w.g. [25 Pa].
Power Connection Line voltage connection is made by connecting the incoming line voltage wires to the “L” side of the contactor as shown in Figure 16. Consult Tables 4a through 4b for correct fuse size.
208 Volt OperationAll residential 208-230 Volt units are factory wired for 230 Volt operation. The transformer may be switched to the 208V tap as illustrated on the wiring diagram by switching the red (208V) and the orange (230V) wires at the contactor terminal.
Special Note for AHRI Testing: To achieve rated airfl ow for AHRI testing purposes on all PSC products, it is necessary to change the fan speed to “HI” speed. When the heat pump has experienced less than 100 operational hours and the coil has not had suffi cient time to be “seasoned”, it is necessary to clean the coil with a mild surfactant such as Calgon to remove the oils left by manufacturing processes and enable the condensate to properly “sheet” off of the coil.
HWG Wiring (Split Units Only)The hot water generator pump power wiring is disabled at the factory to prevent operating the HWG pump “dry.” After all HWG piping is completed and air purged from the water piping, the pump power wires should be applied to terminals on the HWG power block PB2 as shown in the unit wiring diagram. This connection can also serve as a HWG disable when servicing the unit.
Figure 16: TT/TS Single Phase Line VoltageField Wiring
23
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Electrical - Low Voltage Wiring
Low voltage eld wiring for units with ECM fan
Low voltage eld wiring for units with PSC FAN (ECM board will not be present)
Figure 19: FP1 Limit Setting
CXM PCB
JW3-FP1jumper should be clipped for
low temperature operation
Figure 18: TT/TS Low Voltage Field Wiring
Low Water Temperature Cutout SelectionThe CXM control allows the eld selection of low water (or water-antifreeze solution) temperature limit by clipping jumper JW3, which changes the sensing temperature associated with thermistor FP1. Note that the FP1 thermistor is located on the refrigerant line between the coaxial heat exchanger and expansion device (TXV). Therefore, FP1 is sensing refrigerant temperature, not water temperature, which is a better indication of how water ow rate/temperature is affecting the refrigeration circuit.
The factory setting for FP1 is for systems using water (30°F [-1.1°C] refrigerant temperature). In low water temperature (extended range) applications with antifreeze (most ground loops), jumper JW3 should be clipped as shown in Figure 19 to change the setting to 10°F [-12.2°C] refrigerant temperature, a more suitable temperature when using an antifreeze solution. All residential units include water/refrigerant circuit insulation to prevent internal condensation, which is required when operating with entering water temperatures below 59°F [15°C].
Thermostat ConnectionsThe thermostat should be wired directly to the CXM board (units with PSC fan). Units with optional ECM motor include factory wiring from the CXM board to the ECM interface board. Thermostat wiring for these units should be connected to the ECM interface board. Figure 18 shows wiring for TT/TS units with PSC or optional ECM motor. See “Electrical – Thermostat” for speci c terminal connections.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
24 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Electrical - Low Voltage Wiring
Figure 20: Accessory WiringFigure 21: AVM Valve Wiring
CC
Thermostat
Y1
12
3
Y1
AVMTaco ValveHeater Switch
Figure 22: Taco SBV Valve Wiring
From Water SourceIN
OUT
NOTE: Shut-off valves, strainers andother required components not shown.
SolenoidValve Flow
Regulator
To DischargeStage 1
Stage 2
Figure 23: Two-Stage Piping
Water Solenoid Valves An external solenoid valve(s) should be used on ground water installations to shut off ow to the unit when the compressor is not operating. A slow closing valve may be required to help reduce water hammer. Figure 20 shows typical wiring for a 24VAC external solenoid valve. Figures 21 and 22 illustrate typical slow closing water control valve wiring for Taco 500 series (ClimateMaster P/N AVM…) and Taco SBV series valves. Slow closing valves take approximately 60 seconds to open (very little water will ow before 45 seconds). Once fully open, an end switch allows the compressor to be energized. Only relay or triac based electronic thermostats should be used with slow closing valves. When wired as shown, the slow closing valve will operate properly with the following notations:
1. The valve will remain open during a unit lockout.2. The valve will draw approximately 25-35 VA through the
“Y” signal of the thermostat.Note: This valve can overheat the anticipator of anelectromechanical thermostat. Therefore, only relay ortriac based thermostats should be used.
Two-stage UnitsTranquility 27™ (TT) two-stage units should be designed with two parallel valves for ground water applications to limit water use during rst stage operation. For example, at 1.5 gpm/ton [2.0 l/m per kW], an 049 unit requires 6 gpm [23 l/m] for full load (2nd stage) operation, but only 4 gpm [15 l/m] during 1st stage operation. Since the unit will operate on rst stage 80-90% of the time, signi cant water savings can be realizedby using two parallel solenoid valves with two ow regulators. In the example above, stage one solenoid would be installed with a 4 gpm [15 l/m] ow regulator on the outlet, while stage two would utilize a 2 gpm [8 l/m] ow regulator. When stage one is operating, the second solenoid valve will be closed. When stage two is operating, both valves will be open, allowing full load ow rate.
Figure 23 illustrates piping for two-stage solenoid valves. Review gures 20-22 for wiring of stage one valve. Stage two valve should be wired between terminal “Y2” (ECM board) and terminal “C.”
Note: When EWT is below 50°F [10°C], a minimum of 2 gpm per ton (2.6 l/m per kW) is required.
Accessory ConnectionsA terminal paralleling the compressor contactor coil has been provided on the CXM control. Terminal “A” is designed to control accessory devices, such as water valves. Note: This terminal should be used only with 24 Volt signals and not line voltage. Terminal “A” is energized with the compressor contactor. See Figure 20 or the speci c unit wiring diagram for details.
25
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Electrical - Thermostat Wiring
Figure 24: Units With Optional ECM Fan.
Figure 25: Typical Thermostat 2 Heat/1 Cool (PSC Fan)
Thermostat InstallationThe thermostat should be located on an interior wall in a larger room, away from supply duct drafts. DO NOT locate the thermostat in areas subject to sunlight, drafts or on external walls. The wire access hole behind the thermostat may in certain cases need to be sealed to prevent erroneous temperature measurement. Position the thermostat back plate against the wall so that it appears level and so the thermostat wires protrude through the middle of the back plate. Mark the position of the back plate mounting holes and drill holes with a 3/16” (5mm) bit. Install supplied anchors and secure plate to the wall. Thermostat wire must be 18 AWG wire. Wire the appropriate thermostat as shown in Figures 24 and 25 to the low voltage terminal strip on the CXM (units with PSC motor) or ECM control board (units with ECM motor). Practically any heat pump thermostat will work with these units, provided it has the correct number of heating and cooling stages.
ATP32U04 Thermostat
Connection to ECM Control
CompressorCompressor Stage 2
Reversing ValveFan
24Vac Hot24Vac Common
Fault LED
ECMBoard
Y1
Y2
W
DH
O
G
R
C
AL1
Y1
Y2
W
DH
O
G
R
CL
Dehumidification
Units with CXM or DXM board and ECM fan motor, utilizing ECM dehumidificationmode (without ClimaDry option)
Notes:1) Units with whole house dehumidification option have slightly different
thermostat wiring.Terminal DH at the thermostat is connected to terminal H atthe DXM board
2) ECM dehumidification mode slows down fan speed in the cooling mode whendehumidification output from thermostat is active. Normal heating and cooling fanspeeds are not affected.
3) ECM board DIP switch SW9 must be in dehumid. mode forECM dehumidification mode.
Auxiliary Heat
ATM21U01 Thermostat
Connection to CXM Control
CompressorHeating Stage 2Reversing Valve
Fan24Vac Hot
24Vac CommonFault LED
Y
Y2/W
O
G
R
C
L
Y
W
O
G
R
C
AL1
CXM
NOTICE: Units with ClimaDry whole house dehumidi cation option require a separate humidistat or thermostat part number ATP32U04 (See ClimaDry AOM for more details).
CAUTION!
CAUTION!CAUTION! Refrigerant pressure activated water regulating valves should never be used with ClimateMaster equipment.
CAUTION! Many units are installed with a factory or eld supplied manual or electric shut-off valve. DAMAGEWILL OCCUR if shut-off valve is closed during unit operation. A high pressure switch must be installed on the heat pump side of any eld provided shut-off valves and connected to the heat pump controls in series with the built-in refrigerant circuit high pressure switch to disable compressor operation if water pressure exceeds pressure switch setting. The eld installed high pressure switch shall have a cut-out pressure of 300 psig and a cut-in pressure of 250 psig. This pressure switch can be ordered from ClimateMaster with a 1/4” internal are connection as part number 39B0005N02.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
26 G e o t h e r m a l H e a t i n g a n d C o o l i n g
ECM Blower Control
The ECM fan is controlled by an interface board that converts thermostat inputs and fi eld selectable CFM settings to signals used by the ECM motor controller. Units manufactured before July 2005 have version I (P/N 69243707). Units manufactured after July 2005 have version II (P/N 17B0019N01). Fan speeds are selected with jumpers for version I or via a nine position DIP switch for version II. To take full advantage of the ECM motor features, a multi-stage thermostat should be used (2-stage heat/2-stage cool or 3-stage heat/2-stage cool).
HFC-410A packaged units built after May 2009 have ECM controller version III (P/N 17B0034N01). This controller includes logic and a relay to control the HWG functions.
Note: Power must be off to the unit for at least three seconds before the ECM motor will recognize a speed change. The motor will recognize a change in the CFM Adjust or dehumidifi cation mode settings while the unit is powered.
There are four different airfl ow settings from lowest airfl ow rate (speed tap 1) to the highest airfl ow rate (speed tap 4). The charts below indicate settings for both versions of the ECM interface board, followed by detailed information for each setting.
Cooling Settings: The cooling setting determines the cooling (normal) CFM for all units with ECM motor. Cooling (normal) setting is used when the unit is not in dehumidifi cation mode. Tap 1 is the lowest CFM setting, while tap 4 is the highest CFM setting. To avoid air coil freeze-up, tap 1 may not
be used if the dehumidifi cation mode is selected. Consult submittal data or specifi cations catalog for the specifi c unit series and model to correlate speed tap setting to airfl ow in CFM.
Heating Settings: The heating setting determines the heating
CFM for Tranquility® 30 (TT) and Tranquility® 20 (TS) units. Tap 1 is the lowest CFM setting, while tap 4 is the highest CFM setting. Consult submittal data or specifi cations catalog for the specifi c unit series and model to correlate speed tap setting to airfl ow in CFM.
Auxiliary/Emergency Heat Settings: The auxiliary/emergency heat setting determines the CFM when the unit is in auxiliary heat or emergency heat mode. This setting is used for residential units with internal electric heat. When auxiliary electric heat is energized (i.e. compressor and electric heat), the greater of the auxiliary/emergency or heating setting
will be used. A “G” (fan) signal must be present from the thermostat for electric heat to operate. Consult the submittal data or specifi cations catalog for the specifi c unit series and model to correlate speed tap setting to airfl ow in CFM.
CFM Adjust Settings: The CFM adjust setting allows four selections. The NORM setting is the factory default position. The + or – settings adjust the airfl ow by +/- 15%. The +/- settings are used to “fi ne tune” airfl ow adjustments. The
TEST setting runs the ECM motor at 70% torque, which causes the motor to operate like a standard PSC motor, and disables the CFM counter.
Dehumidifi cation Mode Settings: The dehumidifi cation mode setting provides fi eld selection of humidity control. When operating in the normal mode, the cooling airfl ow settings are determined by the cooling tap setting above. When dehumidifi cation is enabled there is a reduction in airfl ow
in cooling to increase the moisture removal of the heat pump. Consult submittal data or specifi cations catalog for the specifi c unit series and model to correlate speed tap to airfl ow in CFM. The dehumidifi cation mode can be enabled in two ways.
1. Constant Dehumidifi cation Mode: When the dehumidifi cation mode is selected (via DIP switch or jumper setting), the ECM motor will operate with a multiplier applied to the cooling CFM settings (approx. 20-25% lower airfl ow). Any time the unit is running in the cooling mode, it will operate at the lower airfl ow to improve latent capacity. The “DEHUM” LED will be illuminated at all times. Heating airfl ow is not affected. NOTE: Do not select dehumidifi cation mode if cooling setting is tap 1.
2. Automatic (Humidistat-controlled) Dehumidifi cation Mode: When the dehumidifi cation mode is selected (via DIP switch or jumper setting) AND a humidistat is connected to terminal DH (version II) or HUM (version I), the cooling airfl ow will only be reduced when the humidistat senses that additional dehumidifi cation is required. The DH (or HUM) terminal is reverse logic. Therefore, a humidistat (not dehumidistat) is required. The “DEHUM” LED will be illuminated only when the humidistat is calling for dehumidifi cation mode. Heating airfl ow is not affected. NOTE: Do not select dehumidifi cation mode if cooling setting is tap 1.
27
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
ECM Blower Control
Table 5: ECM Board Tap Settings
Y
G G G G R
WOY2Y1GRC
Y2Y1
GO
WC
RDH
AL1A
AAL1
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
SW9O
FFO
N
G
DEHUM
CFM
TB1
J1S1
ThermostatInput LEDs
CFM Counter1 flash per 100 CFM
ECM MotorLow VoltageConnector
1/4" SpadeConnections
to CXM orDXM Board
ThermostatConnections
DehumidificationLED
Fan Speed Selection DIP Switch
J01
AL
AL
A
G Y1 Y2 O W1 EM C R
GY1
Y2O
W1
EMN
CC
RH
um
32
14
321 433 2122
1
4 321 4
56
78
910
L
LED's
TB01
CFM
Dehum
id
Norm
Norm
Test(–)(+)
CFM
Adjust
AuxC
FMH
PC
FM
Delay
1/4" SpadeConnectionsto CXM orDXM Board
ThermostatInput LEDs
CFM Counter1 flash per 100CF
ECM MotorLow VoltageConnector
DehumidificationLED
Fan Speed Selection Jumpers
ThermostatConnections
Figure 26a: ECM Version II Interface Layout Figure 26b: ECM Version I Interface Layout
Figure 26c: ECM Version III Interface Layout
Cooling settings: TT, TS Units Heating settings: TT, TS Units Aux/Emerg Heat settings: TT, TS Units*
*Residential Units
Version I Version I Version I69243707 69243707 69243707
Tap HP CFM Tap DELAY Tap AUX CFMSetting Jumper SW1 SW2 Setting Jumper SW3 SW4 Setting Jumper SW5 SW6
1 1 ON ON 1 1 ON ON 1 1 ON ON2 2 ON OFF 2 2 ON OFF 2 2 ON OFF3 3 OFF ON 3 3 OFF ON 3 3 OFF ON4 4 OFF OFF 4 4 OFF OFF 4 4 OFF OFF
CFM Adjust settings: TT, TS Units Dehum Mode settings: TT, TS UnitsVersion I Version I69243707 69243707
Tap CFM Adj Tap DehumidSetting Jumper SW7 SW8 Setting JumperTEST 1 ON ON NORM pins 1,2
- 2 ON OFF Dehumid pins 2,3+ 3 OFF ON
NORM 4 OFF OFF
DIP Switch
Version II and III(17B0019N01 & 17B0034N01)
DIP Switch DIP Switch
ONOFF
DIP Switch DIP SwitchSW9
Version II and III(17B0019N01 & 17B0034N01)
Version II and III(17B0019N01 & 17B0034N01)
Version II and III(17B0019N01 & 17B0034N01)
Version II and III(17B0019N01 & 17B0034N01)
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
28 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Tranquility® 30 (TT) Series ECM Blower Performance Data
Airfl ow in CFM with wet coil and clean air fi lter
ResidentialUnits Only
ModelMax ESP
(in. wg)
Fan Motor (hp)
TapSetting
Cooling Mode Dehumid Mode Heating ModeAUX CFM
Aux/ EmergModeStg 1 Stg 2 Fan Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan
026
0.50 1/2 4 810 950 475 630 740 475 920 1060 475 4 1060
0.50 1/2 3 725 850 425 560 660 425 825 950 425 3 950
0.50 1/2 2 620 730 370 490 570 370 710 820 370 2 820
0.50 1/2 1 520 610 300 600 690 300 1 690
038
0.50 1/2 4 1120 1400 700 870 1090 700 1120 1400 700 4 1400
0.50 1/2 3 1000 1250 630 780 980 630 1000 1250 630 3 1350
0.50 1/2 2 860 1080 540 670 840 540 860 1080 540 2 1350
0.50 1/2 1 730 900 450 730 900 450 1 1350
049
0.75 1 4 1460 1730 870 1140 1350 870 1560 1850 870 4 1850
0.75 1 3 1300 1550 780 1020 1210 780 1400 1650 780 3 1660
0.75 1 2 1120 1330 670 870 1040 670 1200 1430 670 2 1430
0.75 1 1 940 1120 560 1010 1200 560 1 1350
064
0.75 1 4 1670 2050 1020 1300 1600 1020 1860 2280 1020 4 2280
0.75 1 3 1500 1825 920 1160 1430 920 1650 2050 920 3 2040
0.75 1 2 1280 1580 790 1000 1230 790 1430 1750 790 2 1750
0.75 1 1 1080 1320 660 1200 1470 660 1 1470
072
0.75 1 4 1620 2190 1050 1270 1650 1050 1690 2230 1050 4 2230
0.75 1 3 1500 1950 980 1170 1520 980 1600 2100 980 3 2100
0.75 1 2 1400 1830 910 1100 1420 910 1400 1850 910 2 1870
0.75 1 1 1320 1700 850 1240 1620 850 1 1670
Factory shipped on Tap Setting 2During Auxiliary operation (residential units only) the CFM will run at the higher if the heating (delay jumper) or AUX settingsAirfl ow is controlled within +/- 5% up to Max ESP shown with wet coil and standard 1” fi berglass fi lterDo not select Dehumidifi cation mode if HP CFM is on setting 1All units AHRI/ISO/ASHRAE 13256-1 rated HP (Cooling) Delay (Heating) CFM Setting 3
29
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Airfl ow in CFM with wet coil and clean air fi lter
Tranquility® 20 (TS) Series PSC Blower Performance Data
Model FanSpeed
RatedAirfl ow
Min CFM
Airfl ow (cfm) at External Static Pressure (in. wg)0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
018
HI
600 450
704 711 693 690 675 640 598 515
MED 602 599 581 585 573 547 492
LO 531 527 517 506 495 462
024
HI
950 655
1111 1105 1066 1006 934 854 765 662 635
MED 890 879 854 818 770 708 686 623
LO 759 745 730 704 662 627
030
HI
1000 685
1374 1351 1296 1228 1159 1090 1016 919 775
MED 1146 1151 1128 1091 1047 997 934 844 705
LO 1011 1015 999 945 911 863 785
036
HI
1200 825
1375 1387 1377 1350 1307 1251 1182 1099 1003 890
MED 992 1013 1013 1002 986 967 941 900 832 719
LO 887 900 897 886 872 853 826 785
042
HI
1400 960
1808 1759 1723 1680 1617 1524 1399 1247 1075
MED 1537 1518 1494 1459 1408 1338 1247 1134 1001
LO 1323 1309 1284 1246 1192 1122 1036 936 824
060
HI
1950 1500
2311 2300 2279 2257 2209 2140 2088 1990 1901 1856 1752
MED 2058 2039 2016 1983 1949 1920 1874 1807 1750 1670 1582
LO 1868 1858 1858 1838 1806 1792 1749 1699 1636 1570
Black areas denote ESP where operation is not recommended.Units factory shipped on medium speed. Other speeds require fi eld selection.All airfl ow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for 208-230V units.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
30 G e o t h e r m a l H e a t i n g a n d C o o l i n g
ResidentialUnits Only
ModelMax ESP
(in. wg)
Fan Motor (hp)
TapSetting
Cooling Mode Dehumid Mode Heating ModeAUX CFM
Aux/ EmergModeStg 1 Stg 2 Fan Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan
018 1.0 1/2
4 640 800 400 500 620 400 640 800 400 4 800
3 600 750 375 470 590 375 600 750 375 3 750
2 525 650 330 400 500 330 525 650 330 2 650
1 450 550 280 450 550 280 1 650
024 1.0 1/2
4 900 1100 470 610 740 470 900 1100 470 4 1100
3 780 950 420 540 660 420 780 950 420 3 950
2 670 825 360 490 600 360 670 825 390 2 820
1 550 675 300 550 675 340 1 690
030 1.0 1/2
4 920 1130 560 720 880 560 1000 1230 560 4 1230
3 820 1000 500 640 780 500 900 1100 500 3 1100
2 740 900 450 580 700 450 800 950 450 2 950
1 660 800 400 640 780 400 1 780
036 0.90 1/2
4 1150 1400 700 900 1090 700 1150 1400 700 4 1400
3 1020 1250 630 800 980 630 1020 1250 630 3 1350
2 890 1080 540 690 840 540 890 1080 540 2 1350
1 740 900 450 750 920 450 1 1350
042 0.90 1/2
4 1290 1580 790 1010 1230 790 1290 1580 790 4 1580
3 1150 1400 700 900 1090 700 1150 1400 700 3 1400
2 1050 1280 640 820 1000 640 1020 1240 640 2 1350
1 920 1120 560 900 1080 560 1 1350
048 1.0 1
4 1420 1730 870 1110 1350 870 1520 1850 865 4 1850
3 1270 1550 780 990 1210 780 1350 1650 775 3 1650
2 1180 1440 720 920 1120 720 1110 1350 720 2 1350
1 1050 1280 640 980 1250 640 1 1200
060 0.75 1
4 1680 2050 1030 1310 1600 1030 1870 2280 1030 4 2280
3 1500 1830 910 1170 1420 910 1680 2050 910 3 2050
2 1400 1700 850 1090 1330 850 1480 1800 850 2 1800
1 1300 1580 790 1270 1550 790 1 1550
070 0.75 1
4 1830 2230 1100 1420 1740 1100 1830 2230 1100 4 2230
3 1600 1950 980 1250 1520 980 1720 2100 980 3 2100
2 1440 1750 880 1120 1360 880 1670 1950 880 2 1950
1 1200 1580 790 1460 1780 790 1 1780
See ECM control section for details on setting taps.Bold numbers indicate factory settings. During Auxiliary operation the CFM will run at the higher of the Heating (Delay jumper) or AUX settings.Airfl ow is controlled within 5% up to the Max ESP shown with wet coil.Do not select Dehumidifi cation mode if HP CFM is on setting 1.All units AHRI/ISO/ASHRAE 13256-1 rated HP CFM Setting 3.ClimaDry units are factory wired to operate in stage 2 airfl ow.
Tranquility® 20 (TS) Series ECM Blower Performance Data
Airfl ow in CFM with wet coil and clean air fi lter
31
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
CXM ControlFor detailed control information, see CXM Application, Operation and Maintenance (AOM) manual (part #97B0003N12).
Field Selectable InputsTest mode: Test mode allows the service technician to check the operation of the control in a timely manner. By momentarily shorting the test terminals, the CXM control enters a 20 minute test mode period in which all time delays are sped up 15 times. Upon entering test mode, the status LED will fl ash a code representing the last fault. For diagnostic ease at the thermostat, the alarm relay will also cycle during test mode. The alarm relay will cycle on and off similar to the status LED to indicate a code representing the last fault, at the thermostat. Test mode can be exited by shorting the test terminals for 3 seconds.Retry Mode: If the control is attempting a retry of a fault, the status LED will slow fl ash (slow fl ash = one fl ash every 2 seconds) to indicate the control is in the process of retrying.
Field Confi guration OptionsNote: In the following fi eld confi guration options, jumper wires should be clipped ONLY when power is removed from the CXM control.
Water coil low temperature limit setting: Jumper 3 (JW3-FP1 Low Temp) provides fi eld selection of temperature limit setting for FP1 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature).Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].Air coil low temperature limit setting: Jumper 2 (JW2-FP2 Low Temp) provides fi eld selection of temperature limit setting for FP2 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature). Note: This jumper should only be clipped under extenuating circumstances, as recommended by the factory.Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides fi eld selection of the alarm relay terminal AL2 to be jumpered to 24VAC or to be a dry contact (no connection).Not Clipped = AL2 connected to R. Clipped = AL2 dry contact (no connection).
DIP SwitchesNote: In the following fi eld confi guration options, DIP switches should only be changed when power is removed from the CXM control.DIP switch 1: Unit Performance Sentinel Disable - provides fi eld selection to disable the UPS feature.On = Enabled. Off = Disabled.DIP switch 2: Stage 2 Selection - provides selection of whether compressor has an “on” delay. If set to stage 2, the compressor will have a 3 second delay before energizing. Also, if set for stage 2, the alarm relay will NOT cycle during test mode.On = Stage 1. Off = Stage 2DIP switch 3: Not Used.DIP switch 4: DDC Output at EH2 - provides selection for
DDC operation. If set to “DDC Output at EH2,” the EH2 terminal will continuously output the last fault code of the controller. If set to “EH2 normal,” EH2 will operate as standard electric heat output.On = EH2 Normal. Off = DDC Output at EH2.NOTE: Some CXM controls only have a 2 position DIP switch package. If this is the case, this option can be selected by clipping the jumper which is in position 4 of SW1.Jumper not clipped = EH2 Normal. Jumper clipped = DDC Output at EH2.DIP switch 5: Factory Setting - Normal position is “On.” Do not change selection unless instructed to do so by the factory.
-Flash code 2 = 2 quick fl ashes, 10 second pause, 2 quick fl ashes, 10 second pause, etc.
-On pulse 1/3 second; off pulse 1/3 second
CXM Controls
Short test pins together to enter Test Mode and speed-up timing and delays for 20 minutes.
Figure 27: Test Mode Pins
LT1LT2
Table 6a: CXM LED And Alarm Relay OperationsDescription of Operation LED Alarm Relay
Normal Mode On OpenNormal Mode with UPS Warning On Cycle (closed 5 sec., Open 25 sec.)CXM is non-functional Off OpenFault Retry Slow Flash OpenLockout Fast Flash ClosedOver/Under Voltage Shutdown Slow Flash Open (Closed after 15 minutes)Test Mode - No fault in memory Flashing Code 1 Cycling Code 1
Test Mode - HP Fault in memory Flashing Code 2 Cycling Code 2
Test Mode - LP Fault in memory Flashing Code 3 Cycling Code 3
Test Mode - LT1 Fault in memory Flashing Code 4 Cycling Code 4
Test Mode - LT2 Fault in memory Flashing Code 5 Cycling Code 5
Test Mode - CO Fault in memory Flashing Code 6 Cycling Code 6Test Mode - Over/Undershutdown in memory Flashing Code 7 Cycling Code 7
Test Mode - UPS in memory Flashing Code 8 Cycling Code 8
Test Mode - Swapped Thermistor Flashing Code 9 Cycling Code 9
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
32 G e o t h e r m a l H e a t i n g a n d C o o l i n g
CXM Controls
Safety Features – CXM ControlThe safety features below are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions.Anti-short cycle protection: The control features a 5 minute anti-short cycle protection for the compressor.Note: The 5 minute anti-short cycle also occurs at power up.Random start: The control features a random start upon power up of 5-80 seconds.Fault Retry: In Fault Retry mode, the Status LED begins slowly fl ashing to signal that the control is trying to recover from a fault input. The control will stage off the outputs and then “try again” to satisfy the thermostat input call. Once the thermostat input call is satisfi ed, the control will continue on as if no fault occurred. If 3 consecutive faults occur without satisfying the thermostat input call, the control will go into “lockout” mode. The last fault causing the lockout will be stored in memory and can be viewed by going into test mode. Note: FP1/FP2 faults are factory set at only one try.Lockout: In lockout mode, the status LED will begin fast fl ashing. The compressor relay is turned off immediately. Lockout mode can be “soft” reset by turning off the thermostat (or satisfying the call). A “soft” reset keeps the fault in memory but resets the control. A “hard” reset (disconnecting power to the control) resets the control and erases fault memory.Lockout with emergency heat: While in lockout mode, if W becomes active (CXM), emergency heat mode will occur. High pressure switch: When the high pressure switch opens due to high refrigerant pressures, the compressor relay is de-energized immediately since the high pressure switch is in series with the compressor contactor coil. The high pressure fault recognition is immediate (does not delay for 30 continuous seconds before de-energizing the compressor).High pressure lockout code = 2Example: 2 quick fl ashes, 10 sec pause, 2 quick fl ashes, 10 sec. pause, etc.Low pressure switch: The low pressure switch must be open and remain open for 30 continuous seconds during “on” cycle to be recognized as a low pressure fault. If the low pressure switch is open for 30 seconds prior to compressor power up it will be considered a low pressure (loss of charge) fault. The low pressure switch input is bypassed for the initial 60 seconds of a compressor run cycle.Low pressure lockout code = 3Water coil low temperature (FP1): The FP1 thermistor temperature must be below the selected low temperature limit setting for 30 continuous seconds during a compressor run cycle to be recognized as a FP1 fault. The FP1 input is bypassed for the initial 120 seconds of a compressor run cycle. FP1 is set at the factory for one try. Therefore, the control will go into lockout mode once the FP1 fault has occurred.FP1 lockout code = 4
Air coil low temperature (FP2): The FP2 thermistor temperature must be below the selected low temperature limit setting for 30 continuous seconds during a compressor run cycle to be recognized as a FP2 fault. The FP2 input is bypassed for the initial 120 seconds of a compressor run cycle. FP2 is set at the factory for one try. Therefore, the control will go into lockout mode once the FP2 fault has occurred.FP2 lockout code = 5Condensate overfl ow: The condensate overfl ow sensor must sense overfl ow level for 30 continuous seconds to be recognized as a CO fault. Condensate overfl ow will be monitored at all times.CO lockout code = 6Over/under voltage shutdown: An over/under voltage condition exists when the control voltage is outside the range of 18VAC to 31.5VAC. Over/under voltage shut down is a self-resetting safety. If the voltage comes back within range for at least 0.5 seconds, normal operation is restored. This is not considered a fault or lockout. If the CXM is in over/under voltage shutdown for 15 minutes, the alarm relay will close.Over/under voltage shut down code = 7Unit Performance Sentinel-UPS (patent pending): The UPS feature indicates when the heat pump is operating ineffi ciently. A UPS condition exists when:a) In heating mode with compressor energized, FP2 is
greater than 125°F [52°C] for 30 continuous seconds, or:b) In cooling mode with compressor energized, FP1 is
greater than 125°F [52°C] for 30 continuous seconds, or:c) In cooling mode with compressor energized, FP2 is less
than 40°F [4.5°C] for 30 continuous seconds. If a UPS condition occurs, the control will immediately go to UPS warning. The status LED will remain on as if the control is in normal mode. Outputs of the control, excluding LED and alarm relay, will NOT be aff ected by UPS. The UPS condition cannot occur during a compressor off cycle. During UPS warning, the alarm relay will cycle on and off . The cycle rate will be “on” for 5 seconds, “off ” for 25 seconds, “on” for 5 seconds, “off ” for 25 seconds, etc.
UPS warning code = 8Swapped FP1/FP2 thermistors: During test mode, the control monitors to see if the FP1 and FP2 thermistors are in the appropriate places. If the control is in test mode, the control will lockout, with code 9, after 30 seconds if:a) The compressor is on in the cooling mode and the FP1
sensor is colder than the FP2 sensor, or:b) The compressor is on in the heating mode and the FP2
sensor is colder than the FP1 sensor.Swapped FP1/FP2 thermistor code = 9.
Diagnostic FeaturesThe LED on the CXM board advises the technician of the current status of the CXM control. The LED can display either the current CXM mode or the last fault in memory if in test mode. If there is no fault in memory, the LED will fl ash Code 1 (when in test mode).
33
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
CXM Control Start-up OperationThe control will not operate until all inputs and safety controls are checked for normal conditions. The compressor will have a 5 minute anti-short cycle delay at power-up. The fi rst time after power-up that there is a call for compressor, the compressor will follow a 5 to 80 second random start delay. After the random start delay and anti-short cycle delay, the compressor relay will be energized. On all subsequent compressor calls, the random start delay is omitted.
Table 6b: Unit Operation
CXM Controls
T-stat signalTT TS TS
ECM fan ECM fan PSC fanG Fan only Fan only Fan only
G, Y or Y1 Stage 1 heating1 Stage 1 heating3 Stage 1 heating5
G, Y1, Y2 Stage 2 heating1 Stage 2 heating3 Stage 2 heating5
G, Y1, Y2, W Stage 3 heating1 Stage 3 heating3 N/AG, W Emergency heat Emergency heat Emergency heat
G, Y or Y1, O Stage 1 cooling2 Stage 1 cooling4 Cooling6
G, Y1, Y2, O Stage 2 cooling2 Stage 2 cooling4 N/A
1 Stage 1 = 1st stage compressor, 1st stage fan operation Stage 2 = 2nd stage compressor, 2nd stage fan operation Stage 3 = 2nd stage compressor, auxiliary electric heat, 2nd or 3rd stage fan operation (depending on fan settings)2 Stage 1 = 1st stage compressor, 1st stage fan operation, reversing valve Stage 2 = 2nd stage compressor, 2nd stage fan operation, reversing valve3 Stage 1 = compressor, 1st stage fan operation Stage 2 = compressor, 2nd stage fan operation Stage 3 = compressor, auxiliary electric heat, 2nd or 3rd stage fan operation (depending on fan settings)4 Stage 1 = compressor, 1st stage fan operation, reversing valve Stage 2 = compressor, 2nd stage fan operation, reversing valve5 Stage 1 = compressor, fan Stage 2 = compressor, auxiliary electric heat, fan6 Cooling = compressor, fan, reversing valve
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
34 G e o t h e r m a l H e a t i n g a n d C o o l i n g
CXM Controls
CXM Thermostat DetailsThermostat Compatibility - Most all heat pump thermostats can be used with the CXM control. However Heat/Cool stats are NOT compatible with the CXM.
Anticipation Leakage Current - Maximum leakage current for "Y" is 50 mA and for "W" is 20mA. Triacs can be used if leakage current is less than above. Thermostats with anticipators can be used if anticipation current is less than that specifi ed above.
Thermostat Signals - • "Y" and "W" have a 1 second recognition time when being activated or being removed.• "O" and "G" are direct pass through signals but are monitored by the micro processor.• "R" and "C" are from the transformer.• "AL1" and "AL2" originate from the alarm relay.• "A" is paralleled with the compressor output for use with well water solenoid valves.• The "Y" 1/4" quick connect is a connection point to the "Y" input terminal P1 for factory use. This "Y" terminal can be used to drive panel mounted relays such as the loop pump relay.
Table 7: Nominal resistance at various temperatures
Safety Features – CXM Control
Temp (ºC) Temp (ºF)Resistance
(kOhm)Temp (ºC) Temp (ºF)
Resistance (kOhm)
-17.8 0.0 85.34 55 131.0 2.99-17.5 0.5 84.00 56 132.8 2.88-16.9 1.5 81.38 57 134.6 2.77-12 10.4 61.70 58 136.4 2.67-11 12.2 58.40 59 138.2 2.58-10 14.0 55.30 60 140.0 2.49-9 15.8 52.38 61 141.8 2.40-8 17.6 49.64 62 143.6 2.32-7 19.4 47.05 63 145.4 2.23-6 21.2 44.61 64 147.2 2.16-5 23.0 42.32 65 149.0 2.08-4 24.8 40.15 66 150.8 2.01-3 26.6 38.11 67 152.6 1.94-2 28.4 36.18 68 154.4 1.88-1 30.2 34.37 69 156.2 1.810 32.0 32.65 70 158.0 1.751 33.8 31.03 71 159.8 1.692 35.6 29.50 72 161.6 1.643 37.4 28.05 73 163.4 1.584 39.2 26.69 74 165.2 1.535 41.0 25.39 75 167.0 1.486 42.8 24.17 76 168.8 1.437 44.6 23.02 77 170.6 1.398 46.4 21.92 78 172.4 1.349 48.2 20.88 79 174.2 1.30
10 50.0 19.90 80 176.0 1.2611 51.8 18.97 81 177.8 1.2212 53.6 18.09 82 179.6 1.1813 55.4 17.26 83 181.4 1.1414 57.2 16.46 84 183.2 1.1015 59.0 15.71 85 185.0 1.0716 60.8 15.00 86 186.8 1.0417 62.6 14.32 87 188.6 1.0118 64.4 13.68 88 190.4 0.9719 66.2 13.07 89 192.2 0.9420 68.0 12.49 90 194.0 0.9221 69.8 11.94 91 195.8 0.8922 71.6 11.42 92 197.6 0.8623 73.4 10.92 93 199.4 0.8424 75.2 10.45 94 201.2 0.8125 77.0 10.00 95 203.0 0.7926 78.8 9.57 96 204.8 0.7627 80.6 9.16 97 206.6 0.7428 82.4 8.78 98 208.4 0.7229 84.2 8.41 99 210.2 0.7030 86.0 8.06 100 212.0 0.6831 87.8 7.72 101 213.8 0.6632 89.6 7.40 102 215.6 0.6433 91.4 7.10 103 217.4 0.6234 93.2 6.81 104 219.2 0.6035 95.0 6.53 105 221.0 0.5936 96.8 6.27 106 222.8 0.5737 98.6 6.01 107 224.6 0.5538 100.4 5.77 108 226.4 0.5439 102.2 5.54 109 228.2 0.5240 104.0 5.33 110 230.0 0.5141 105.8 5.12 111 231.8 0.5042 107.6 4.92 112 233.6 0.4843 109.4 4.72 113 235.4 0.4744 111.2 4.54 114 237.2 0.4645 113.0 4.37 115 239.0 0.4446 114.8 4.20 116 240.8 0.4347 116.6 4.04 117 242.6 0.4248 118.4 3.89 118 244.4 0.4149 120.2 3.74 119 246.2 0.4050 122.0 3.60 120 248.0 0.3951 123.8 3.47 121 249.8 0.3852 125.6 3.34 122 251.6 0.3753 127.4 3.22 123 253.4 0.3654 129.2 3.10
35
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Unit Commissioning And Operating Conditions
Table 8a: Building Operating Limits
Operating LimitsEnvironment – Units are designed for indoor installation only. Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air). Power Supply – A voltage variation of +/– 10% of nameplate utilization voltage is acceptable.
Determination of operating limits is dependent primarily upon three factors: 1) return air temperature. 2) water temperature, and 3) ambient temperature. When any one of these factors is at minimum or maximum levels, the other two factors should be at normal levels to insure proper unit operation. Extreme variations in temperature and humidity and/or corrosive water or air will adversely affect unit performance, reliability, and service life. Consult Table 8a for operating limits.
Commissioning ConditionsConsult Table 8b for the particular model. Starting conditions vary depending upon model and are based upon the following notes:
Notes:1. Conditions in Table 8b are not normal or continuous operating conditions. Minimum/maximum limits are start-up conditions
to bring the building space up to occupancy temperatures. Units are not designed to operate under these conditions on a regular basis.
2. Voltage utilization range complies with AHRI Standard 110.
Table 8b: Building Commissioning Limits
Cooling HeatingAir LimitsMin. ambient air, DB 45ºF [7ºC] 39ºF [4ºC]Rated ambient air, DB 80.6ºF [27ºC] 68ºF [20ºC]Max. ambient air, DB 130ºF [54ºC] 85ºF [29ºC]Min. entering air, DB/WB *50/45ºF [10/7ºC] 40ºF [4.5ºC]Rated entering air, DB/WB 80.6/66.2ºF [27/19ºC] 68ºF [20ºC]Max. entering air, DB/WB 110/83ºF [43/28ºC] 80ºF [27ºC]Water LimitsMin. entering water 30ºF [-1ºC] 20ºF [-6.7ºC]Normal entering water 50-110ºF [10-43ºC] 30-70ºF [-1 to 21ºC]Max. entering water 120ºF [49ºC] 90ºF [32ºC]
UnitCommissioning Limits
Normal Water Flow 1.5 to 3.0 gpm / ton[1.6 to 3.2 l/m per kW]
TT/TS
Cooling Heating Cooling Heatingmitsmbient air, DB 45ºF [7ºC] 39ºF [4ºC] 45ºF [7ºC] 39ºF [4ºCambient air, DB 80.6ºF [27ºC] 68ºF [20ºC] 80.6ºF [27ºC] 68ºF [20ºCmbient air, DB 130ºF [54ºC] 85ºF [29ºC] 130ºF [54ºC] 85ºF [29ºC]tering air, DB/WB 60/45ºF [16/7ºC] 40ºF [4.4ºC] *60/50ºF [16/10ºC] 45ºF [7ºC]
entering air, DB/WB 80.6/66.2ºF [27/19ºC] 68ºF [20ºC] 80.6/66.2ºF [27/19ºC] 68ºF [20ºCntering air, DB/WB 100/75ºF [38/24ºC] 80ºF [27ºC] 95/75ºF [35/24ºC] 80ºF [27ºC]Limitstering water 30ºF [-1ºC] 20ºF [-6.7ºC] 30ºF [-1ºC] 20ºF [-6.7ºC]entering water 50-110ºF [10-43ºC] 30-70ºF [-1 to 21ºC] 50-110ºF [10-43ºC] 30-70ºF [-1 to 21ºC]
ntering water 120ºF [49ºC] 90ºF [32ºC] 120ºF [49ºC] 90ºF [32ºC]
TSTTperating Limits
l Water Flow 1.5 to 3.0 gpm / ton[1.6 to 3.2 l/m per kW]
1.5 to 3.0 gpm / ton[1.6 to 3.2 l/m per kW]
Rev.: 4 June, 2013B
Cooling HeatingAir LimitsMin. ambient air, DB 45ºF [7ºC] 39ºF [4ºC]Rated ambient air, DB 80.6ºF [27ºC] 68ºF [20ºC]Max. ambient air, DB 130ºF [54ºC] 85ºF [29ºC]Min. entering air, DB/WB *60/45ºF [16/7ºC] 40ºF [4.4ºC]
Rated entering air, DB/WB 80.6/66.2ºF [27/19ºC] 68ºF [20ºC]Max. entering air, DB/WB 100/75ºF [38/24ºC] 80ºF [27ºC]Water LimitsMin. entering water 30ºF [-1ºC] 20ºF [-6.7ºC]Normal entering water 50-110ºF [10-43ºC] 30-70ºF [-1 to 21ºC]Max. entering water 120ºF [49ºC] 90ºF [32ºC]
UnitOperating Limits
Normal Water Flow 1.5 to 3.0 gpm / ton[1.6 to 3.2 l/m per kW]
TT
*If with ClimaDry, 65/55°F (18/13°C)
*If with ClimaDry, 65/55°F (18/13°C)
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
36 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Unit Start-Up and Operating Conditions
Unit and System CheckoutBEFORE POWERING SYSTEM, please check the following:
UNIT CHECKOUT Balancing/shutoff valves: Insure that all isolation valves
are open and water control valves are wired. Line voltage and wiring: Verify that voltage is within
an acceptable range for the unit and wiring and fuses/breakers are properly sized. Verify that low voltage wiring is complete.
Unit control transformer: Insure that transformer has the properly selected voltage tap. Residential 208-230V units are factory wired for 230V operation unless specifi ed otherwise.
Loop/water piping is complete and purged of air. Water/piping is clean.
Antifreeze has been added if necessary. Entering water and air: Insure that entering water and air
temperatures are within operating limits of Table 8. Low water temperature cutout: Verify that low water
temperature cut-out on the CXM/CXM control is properly set.
Unit fan: Manually rotate fan to verify free rotation and insure that blower wheel is secured to the motor shaft. Be sure to remove any shipping supports if needed. DO NOT oil motors upon start-up. Fan motors are pre-oiled at the factory. Check unit fan speed selection and compare to design requirements.
Condensate line: Verify that condensate line is open and properly pitched toward drain.
HWG pump is disconnected unless piping is completed and air has been purged from the system.
Water fl ow balancing: Record inlet and outlet water temperatures for each heat pump upon startup. This check can eliminate nuisance trip outs and high velocity water fl ow that could erode heat exchangers.
Unit air coil and fi lters: Insure that fi lter is clean and accessible. Clean air coil of all manufacturing oils.
Unit controls: Verify that CXM fi eld selection options are properly set. Low voltage wiring is complete.
Blower speed is set. Service/access panels are in place.
SYSTEM CHECKOUT System water temperature: Check water temperature
for proper range and also verify heating and cooling set points for proper operation.
System pH: Check and adjust water pH if necessary to maintain a level between 6 and 8.5. Proper pH promotes longevity of hoses and fi ttings (see Table 3).
System fl ushing: Verify that all air is purged from the system. Air in the system can cause poor operation or system corrosion. Water used in the system must be potable quality initially and clean of dirt, piping slag, and strong chemical cleaning agents. Some antifreeze solutions may require distilled water.
Flow Controller pump(s): Verify that the pump(s) is wired, purged of air, and in operating condition.
System controls: Verify that system controls function and
operate in the proper sequence. Low water temperature cutout: Verify that low water
temperature cut-out controls are set properly (FP1 - JW3).
Miscellaneous: Note any questionable aspects of the installation.
Unit Start-up Procedure1. Turn the thermostat fan position to “ON.” Blower
should start.2. Balance air fl ow at registers.3. Adjust all valves to their full open position. Turn on the
line power to all heat pump units.4. Room temperature should be within the minimum-
maximum ranges of Table 8b. During start-up checks, loop water temperature entering the heat pump should be between 30°F [-1°C] and 95°F [35°C].
5. Two factors determine the operating limits of water source heat pumps, (a) return air temperature, and (b) water temperature. When any one of these factors is at a minimum or maximum level, the other factor must be at normal level to insure proper unit operation.a. Adjust the unit thermostat to the warmest setting.
Place the thermostat mode switch in the “COOL” position. Slowly reduce thermostat setting until the compressor activates.
b. Check for cool air delivery at the unit grille within a few minutes after the unit has begun to operate.
Note: Units have a fi ve minute time delay in the control circuit that can be bypassed on the CXM/CXM control board as shown below in Figure 27. See controls description for details.
c. Verify that the compressor is on and that the water fl ow rate is correct by measuring pressure drop through the heat exchanger using the P/T plugs and comparing to Tables 9a through 9b.
d. Check the elevation and cleanliness of the condensate lines. Dripping may be a sign of a blocked line. Check that the condensate trap is fi lled to provide a water seal.
CAUTION!
CAUTION!
CAUTION! Verify that ALL water control valves are open and allow water fl ow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump.
CAUTION! To avoid equipment damage, DO NOT leave system fi lled in a building without heat during the winter unless antifreeze is added to the water loop. Heat exchangers never fully drain by themselves and will freeze unless winterized with antifreeze.
37
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Unit Start-Up Procedure
e. Refer to Table 10. Check the temperature of both entering and leaving water. If temperature is within range, proceed with the test. If temperature is outside of the operating range, check refrigerant pressures and compare to Tables 11 through 12. Verify correct water fl ow by comparing unit pressure drop across the heat exchanger versus the data in Tables 9a through 9b. Heat of rejection (HR) can be calculated and compared to catalog data capacity pages. The formula for HR for systems with water is as follows:HR = TD x GPM x 500, where TD is the temperature diff erence between the entering and leaving water, and GPM is the fl ow rate in U.S. GPM, determined by comparing the pressure drop across the heat exchanger to Tables 9a through 9b.
f. Check air temperature drop across the air coil when compressor is operating. Air temperature drop should be between 15°F and 25°F [8°C and 14°C].
g. Turn thermostat to “OFF” position. A hissing noise indicates proper functioning of the reversing valve.
6. Allow fi ve (5) minutes between tests for pressure to equalize before beginning heating test.a. Adjust the thermostat to the lowest setting. Place the
thermostat mode switch in the “HEAT” position.b. Slowly raise the thermostat to a higher temperature
until the compressor activates.c. Check for warm air delivery within a few minutes after
the unit has begun to operate.d. Refer to Table 10. Check the temperature of both
entering and leaving water. If temperature is within range, proceed with the test. If temperature is outside of the operating range, check refrigerant pressures and compare to Tables 11 through 12. Verify correct water fl ow by comparing unit pressure drop across the heat exchanger versus the data in Tables 9a through 9b. Heat of extraction (HE) can be calculated and compared to submittal data capacity pages. The formula for HE for systems with water is as follows:
HE = TD x GPM x 500, where TD is the temperature diff erence between the entering and leaving water, and GPM is the fl ow rate in U.S. GPM, determined by comparing the pressure drop across the heat exchanger to Tables 9a through 9b.
e. Check air temperature rise across the air coil when compressor is operating. Air temperature rise should be between 20°F and 30°F [11°C and 17°C].
f. Check for vibration, noise, and water leaks.7. If unit fails to operate, perform troubleshooting analysis
(see troubleshooting section). If the check described fails to reveal the problem and the unit still does not operate, contact a trained service technician to insure proper diagnosis and repair of the equipment.
8. When testing is complete, set system to maintain desired comfort level.
9. BE CERTAIN TO FILL OUT AND RETURN ALL WARRANTY REGISTRATION PAPERWORK.
Note: If performance during any mode appears abnormal, refer to the CXM section or troubleshooting section of this
WARNING!
CAUTION!
WARNING! When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise caution when working with energized equipment.
CAUTION! Verify that ALL water control valves are open and allow water fl ow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump.
manual. To obtain maximum performance, the air coil should be cleaned before start-up. A 10% solution of dishwasher detergent and water is recommended.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
38 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Unit Operating Conditions
Table 10: Water Temperature Change Through Heat Exchanger
Model GPMPressure Drop (psi)
30°F 50°F 70°F 90°F
0182.84.15.5
0.72.13.5
0.51.72.8
0.31.42.4
0.21.12.0
0243.04.56.0
1.21.92.0
0.31.01.4
0.20.71.2
0.10.51.0
0303.85.67.5
0.91.62.5
0.81.42.2
0.81.32.1
0.71.32.0
0364.56.89.0
1.22.44.0
0.81.93.2
0.91.83.0
0.81.72.8
0425.58.311.0
1.02.23.8
0.91.93.4
0.81.83.2
0.81.83.1
0486.09.0
12.0
1.12.33.9
0.91.83.2
0.71.83.2
0.81.83.0
0607.511.315.0
1.33.56.1
0.62.54.7
0.52.14.1
0.52.03.9
0709.0
13.518.0
2.75.28.1
1.73.86.4
1.53.35.7
1.63.25.5
Antifreeze Type Antifreeze %
CoolingWPD
Corr. Fct.EWT 40°F
EWT 40°F
Total Cap
Sens Cap Power
Propylene Glycol15 0.968 0.968 0.990 1.21025 0.947 0.947 0.983 1.360
Methanol15 0.968 0.968 0.990 1.16025 0.949 0.949 0.984 1.220
Ethanol15 0.944 0.944 0.983 1.30025 0.917 0.917 0.974 1.360
Ethylene Glycol15 0.980 0.980 0.994 1.12025 0.966 0.966 0.990 1.200
Antifreeze Correction Table
Model GPMPressure Drop (psi)
30°F 50°F 70°F 90°F
026
2.33.03.44.56.0
0.71.11.32.03.1
0.40.70.91.42.3
0.40.60.81.21.9
0.50.70.81.21.8
038
3.04.56.06.89.0
1.52.63.84.56.9
0.91.72.73.25.2
0.81.52.32.74.4
0.91.52.22.64.1
049
4.56.06.89.0
12.0
1.52.63.84.56.9
0.61.11.42.54.2
0.51.01.32.33.8
0.30.91.22.23.5
064
6.07.59.0
11.312.015.0
0.91.72.53.74.16.1
0.20.91.52.63.04.7
0.20.71.32.32.64.1
0.30.81.42.32.64.0
072
7.08.5
10.512.814.017.0
1.42.23.34.65.47.6
0.71.32.23.44.16.0
0.51.11.93.03.65.4
0.71.22.02.93.55.2
Table 9a: TT Coax Water Pressure Drop Table 9b: TS Coax Water Pressure Drop
39
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Unit Operating Conditions
TE026 Full Load Cooling - without HWG active Full Load Heating - without HWG active
Entering Water Temp
°F
Water Flow
GPM/ton
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Rise°F
Air TempDrop °F
DB
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Drop
°F
Air Temp
Rise °F DB
30*1.5
2.253
72-8375-8578-88
273-293275-295277-297
6-116-116-11
3-83-83-8
5.9-7.94.2-6.22.7-4.7
16-2217-2318-24
501.5
2.253
128-138128-138128-138
186-206172-192158-178
18-2318-2318-23
8-136-116-11
16.3-18.312.1-14.1
7.8-9.8
19-2520-2620-26
102-112106-116110-120
302-322303-323305-325
8-128-128-12
6-116-116-11
8.9-10.96.7-8.74.5-6.5
22-2823-2923-29
701.5
2.253
136-146136-146136-146
281-301267-287253-273
7-127-127-12
7-125-104-9
15.7-17.711.6-13.67.6-9.6
19-2519-2519-25
128-138134-144141-151
330-350332-352334-354
10-1510-1510-15
8-138-138-13
11.3-13.38.5-10.55.8-7.8
27-3428-3528-35
901.5
2.253
139-149139-149139-149
368-388354-374340-360
6-116-116-11
7-125-105-10
14.9-16.911-13
7.2-9.2
18-2418-2418-24
162-172166-176171-181
367-387372-392377-397
14-1915-2017-22
10-1510-1510-15
14.4-16.410.8-12.8
7.1-9.1
33-4134-4234-42
1101.5
2.253
143-153143-153143-153
465-485450-470433-453
6-116-116-11
7-125-105-10
13.9-15.910.2-12.2
6.5-8.5
17-2317-2317-23
*Based on 15% Methanol antifreeze solution
TT026
TE038 Full Load Cooling - without HWG active Full Load Heating - without HWG active
Entering Water Temp
°F
Water Flow
GPM/ton
Suction Pressure
PSIG
Discharge Pressure
PSIGSuperheat Subcooling
Water Temp Rise °F
Air Temp Drop °F
DB
Suction Pressure
PSIG
Discharge Pressure
PSIGSuperheat Subcooling
Water Temp Drop
°F
Air Temp
Rise °F DB
30*1.5
2.253
69-7973-8376-86
293-313297-317300-320
7-127-127-12
14-1914-1914-19
8.9-10.96.7-8.74.5-6.5
17-2318-2419-25
501.5
2.253
129-139128-138128-138
225-245211-231197-217
15-2015-2015-20
10-159-149-14
21.9-23.916.1-18.110.3-12.3
18-2419-2519-25
96-106100-110105-115
322-342326-346331-351
10-1510-1510-15
17-2217-2217-22
12.2-14.29.3-11.36.4-8.4
23-2924-3024-30
701.5
2.253
136-146135-145135-145
302-322283-303265-285
9-149-149-14
13-1812-1712-17
21.5-23.515.8-17.8
10-12
18-2419-2519-25
123-133129-139135-145
352-372358-378364-384
11-1611-1611-16
19-2419-2419-24
15-1711.6-13.68.2-10.2
28-3529-3630-37
901.5
2.253
140-150140-150140-150
390-410369-389349-369
7-128-138-13
13-188-138-13
20.5-22.514.9-16.99.3-11.3
17-2317-2317-23
157-167169-179181-191
390-410399-419408-428
13-1813-1814-19
18-2316.5-21.5
15-20
21-2315.5-17.510.5-12.5
36-4437-4539-47
1101.5
2.253
145-155145-155145-155
488-508467-487447-467
7-128-138-13
13-188-138-13
19-2114-169-11
17-2317-2317-23
*Based on 15% Methanol antifreeze solution
TT038
TE049 Full Load Cooling - without HWG active Full Load Heating - without HWG active
Entering Water Temp
°F
Water Flow
GPM/ton
Suction Pressure
PSIG
Discharge Pressure
PSIGSuperheat Subcooling
Water Temp Rise °F
Air Temp Drop °F
DB
Suction Pressure
PSIG
Discharge Pressure
PSIGSuperheat Subcooling
Water Temp Drop
°F
Air Temp
Rise °F DB
30*1.5
2.253
66-7669-7972-82
286-306289-309292-312
7-127-127-12
8-139-149-14
8-106-84-6
18-2419-2519-25
501.5
2.253
125-135123-133122-132
242-262224-244205-225
13-1813-1814-19
10-159-147-12
20.9-22.915.6-17.610.2-12.2
19-2519-2519-25
93-10398-108103-113
314-334320-340326-346
8-138-138-13
10-1510-1510-15
11.5-13.58.7-10.75.9-7.9
23-2924-3025-31
701.5
2.253
133-143132-142131-141
310-330290-310270-290
8-138-139-14
8-137-125-10
20.5-22.515.2-17.29.9-11.9
19-2519-2519-25
123-133130-140137-147
344-364354-374361-381
9-149-149-14
9-149-149-14
15-1711.5-13.57.9-9.9
28-3529-3630-37
901.5
2.253
138-148137-147136-146
396-416374-394352-372
7-127-127-12
7-126-114-9
19.2-21.214.3-16.39.3-11.3
18-2418-2418-24
165-175175-185185-195
390-410401-421413-433
13-1815-2017-22
8-138-138-13
19.6-21.615-17
10.3-12.3
37-4538-4639-47
1101.5
2.253
144-154143-153142-152
497-517472-492447-467
7-127-127-12
5-104-93-8
18-2013.3-15.38.5-10.5
17-2317-2317-23
*Based on 15% Methanol antifreeze solution
TT049
Table 11: TT Series Typical Unit Operating Pressures and Temperatures
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
40 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Unit Operating Conditions
018 Full Load Cooling - without HWG active Full Load Heating - without HWG activeEntering
Water Temp °F
WaterFlow
GPM/ton
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Rise
°F
Air TempDrop °F
DB
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Drop
°F
Air TempRise °F DB
30*1.5
2.253
120-130120-130120-130
155-175142-162128-148
27-3227-3227-32
11-169-149-14
16.9-19.912.5-14.58.1-10.1
16-2217-2317-23
73-8375-8578-88
268-288270-290272-292
8-138-138-13
4-94-94-9
6.1-8.14.4-6.42.9-4.9
15-2116-2216-22
501.5
2.253
137-147137-147137-147
220-240206-226192-212
16-2116-2116-21
10-158-138-13
17-1912.6-14.68.4-10.4
16-2217-2317-23
102-112106-116110-120
295-315297-317299-319
8-138-138-13
8-138-138-13
9.1-11.16.9-8.94.7-6.7
20-2621-2721-27
701.5
2.253
142-152142-152142-152
287-307273-239259-279
7-127-127-12
10-158-138-13
15.9-17.911.8-13.87.8-9.8
16-2217-2317-23
131-141137-147144-154
324-344326-346328-348
9-149-149-14
10-1510-1510-15
12.1-14.19.3-11.36.6-8.6
25-3326-3426-34
901.5
2.253
146-156146-156146-156
375-395361-381347-367
6-116-116-11
10-158-138-13
14.9-16.911-13
7.2-9.2
16-2217-2317-23
174-184180-190187-197
360-380367-387374-394
10-1511-1612-17
12-1712-1712-17
15.8-17.811.9-13.9
8-10
32-4033-4133-41
1101.5
2.253
154-164154-164154-164
478-498461-481445-465
6-116-116-11
10-158-138-13
14-1610.2-12.2
6.5-8.5
16-2216-2216-22
*Based on 15% Methanol antifreeze solution
TE064 Full Load Cooling - without HWG active Full Load Heating - without HWG activeEntering
Water Temp
°F
WaterFlow
GPM/ton
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Rise°F
Air TempDrop °F
DB
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Drop
°F
Air Temp
Rise °F DB
30*1.5
2.253
66-7669-7972-82
282-302285-305289-309
10-1610-1610-16
9-149-14
10-15
8-106-84-6
19-2519-2520-26
501.5
2.253
128-138126-136125-135
238-258222-242205-225
16-2121-2626-31
14-1913-1812-17
20.5-22.514.9-16.99.2-11.2
21-2721-2721-27
90-10095-10599-109
310-330313-333316-336
11-1711-1711-17
12-1712-1712-17
11.3-13.38.5-10.55.7-7.7
24-3025-3126-32
701.5
2.253
135-145134-144133-143
315-335296-316276-296
10-1512-1715-20
14-1913-1811-16
21-2315.5-17.5
10-12
22-2822-2822-28
115-125120-130126-136
337-357341-361345-365
12-1812-1812-18
14-1914-1915-20
14-1610.6-12.6
7.3-9.3
28-3529-3630-37
901.5
2.253
139-149138-148138-148
408-428386-406364-384
10-1510-1510-15
15-2013-1811-16
20.1-22.114.8-16.89.5-11.5
21-2721-2721-27
157-167161-171166-176
390-410394-414398-418
15-2015-2015-20
14-1914-1915-20
18.2-20.213.9-15.99.6-11.6
37-4538-4639-47
1101.5
2.253
144-154143-153142-152
515-535493-513469-489
8-138-138-13
14-1913-1812-17
19-2114-169-11
20-2620-2620-26
*Based on 15% Methanol antifreeze solution
TT064
TE072 Full Load Cooling - without HWG active Full Load Heating - without HWG active
Entering Water Temp
°F
WaterFlowGPM/ton
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Rise°F
Air Temp
Drop °F DB
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Drop
°F
Air TempRise
°F DB
30*1.5
2.253
61-7165-7568-78
292-312296-316300-320
11-1611-1610-15
13-1814-1915-20
7.2-9.25.4-7.43.5-5.5
19-2520-2621-27
501.5
2.253
131-141130-140129-139
210-230205-225200-220
10-1511-1613-18
12-1712-1712-17
18.5-20.514-16
9.5-11.5
22-2823-2924-30
89-9998-108106-116
327-347337-357348-368
10-1510-1510-15
19-2414-199-14
10.9-12.98.3-10.35.7-7.7
26-3228-3430-36
701.5
2.253
135-145131-141128-138
300-320295-315290-310
10-1511-1613-18
15-2014-1914-19
17.6-19.613.8-15.8
10-12
23-2923-2923-29
119-129132-142144-154
365-385380-400395-415
10-1510-1510-15
21-2616-2111-16
14.7-16.711.3-13.37.9-9.9
33-3936-4238-44
901.5
2.253
139-149137-147135-145
390-410370-390350-370
10-1510-1510-15
16-2114-1913-18
16.7-18.712.6-14.68.5-10.5
22-2822-2822-28
162-172172-182182-192
418-438430-450444-464
10-1510-1511-16
19-2419-2419-24
19.4-21.414.7-16.710.1-12.1
43-4945-5147-53
1101.5
2.253
145-155145-155144-154
490-510470-490452-472
10-1510-159-14
16-2114-1913-18
15.9-17.911.7-13.7
7.4-9
20-2720-2720-27
*Based on 15% Methanol antifreeze solution
TT072
Table 12: TS Series Typical Unit Operating Pressures and Temperatures
Table 11: TT Series Typical Unit Operating Pressures and Temperatures: Continued
41
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Unit Operating Conditions
024 Full Load Cooling - without HWG active Full Load Heating - without HWG activeEntering
Water Temp °F
WaterFlow
GPM/ton
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Rise
°F
Air TempDrop °F
DB
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Drop
°F
Air TempRise °F DB
30*1.5
2.253
115-125115-125115-125
154-174141-161127-147
40-4540-4540-45
8-136-116-11
16.5-18.512.1-14.177.7-9.7
19-2520-2620-26
73-8375-8578-88
283-303285-305287-307
8-128-128-12
6-116-116-11
5.9-7.94.2-6.22.7-4.7
16-2217-2318-24
501.5
2.253
115-120115-120115-120
209-229195-215181-201
24-2924-2924-29
10-158-138-13
15.7-17.711.6-13.67.6-9.6
18-2418-2418-24
102-112106-116110-120
313-333314-334316-336
8-128-128-12
8-138-138-13
8.9-10.96.7-8.74.5-6.5
22-2823-2923-29
701.5
2.253
136-146136-146136-146
275-295261-281247-267
6-116-116-11
6-115-104-9
15.7-17.711.6-13.67.6-9.6
18-2418-2418-24
128-138134-144141-151
340-360342-362344-364
9-149-149-14
9-149-149-14
11.3-13.38.5-10.55.8-7.8
27-3428-3528-35
901.5
2.253
140-150140-150140-150
361-381347-367333-353
6-116-116-11
6-115-104-9
14.9-16.911-13
7.2-9.2
18-2418-2418-24
162-172166-176171-181
370-390376-396383-403
14-1915-2016-21
9-149-149-14
14.4-16.410.8-12.8
7.1-9.1
32-4034-4234-42
1101.5
2.253
144-154144-154144-154
460-480445-465428-448
6-116-116-11
6-114-94-9
13.9-15.910.2-12.2
6.5-8.5
17-2317-2317-23
*Based on 15% Methanol antifreeze solution
030 Full Load Cooling - without HWG active Full Load Heating - without HWG activeEntering
Water Temp °F
WaterFlow
GPM/ton
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Rise
°F
Air TempDrop °F
DB
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Drop
°F
Air TempRise °F
DB
30*1.5
2.253
116-126115-125115-125
146-166138-158128-148
27-3227-3227-32
7-136-116-11
19.6-21.614.3-16.3
8-10
16-2217-2317-23
69-7973-8376-86
275-295277-297279-299
7-127-127-12
6-116-116-11
7.2-9.25.4-7.43.5-5.5
16-2217-2317-23
501.5
2.253
129-139128-138128-138
217-237203-223189-209
12-1712-1712-17
6-115-105-10
20.8-22.815-17
9.2-11.2
17-2318-2418-24
96-106100-110105-115
300-320304-324309-329
10-1510-1510-15
9-149-149-14
10.5-12.57.6-9.64.8-6.8
21-2722-2822-28
701.5
2.253
132-142131-141131-141
293-313274-294256-276
9-149-149-14
6-115-105-10
20.1-22.114.4-16.48.6-10.6
17-2318-2418-24
123-133129-139135-145
327-347333-353339-359
11-1611-1611-16
11-1611-1611-16
13.2-15.29.8-11.86.4-8.4
25-3226-3327-34
901.5
2.253
137-147137-147137-147
383-403362-382342-362
7-127-127-12
5-105-105-10
19.4-21.413.8-15.88.2-10.2
16-2216-2216-22
155-165162-172169-179
355-375362-382369-389
13-1814-1916-21
11-1611-1611-16
16.8-18.812.7-14.78.6-10.6
30-3831-3932-40
1101.5
2.253
143-153143-153143-153
475-495457-477439-459
6-116-116-11
9-146-116-11
18.2-20.213-147.7-9.7
16-2216-2216-22
*Based on 15% Methanol antifreeze solution
036 Full Load Cooling - without HWG active Full Load Heating - without HWG activeEntering
Water Temp °F
WaterFlow
GPM/ton
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Rise
°F
Air TempDrop °F
DB
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Drop
°F
Air TempRise °F
DB
30*1.5
2.253
117-127116-126116-126
142-162134-154124-144
33-3833-3833-38
8-147-127-12
19.1-21.113.8-15.8
7.4-9.4
15-2215-2215-22
69-7973-8376-86
276-296278-298280-300
10-1510-1510-15
10-1510-1510-15
7.2-9.25.3-7.33.5-5.5
17-2318-2418-24
501.5
2.253
136-146136-146136-146
211-231197-217183-203
11-1611-1611-16
6-115-105-10
20.6-22.614.8-16.8
9-11
17-2317-2317-23
99-109103-113108-118
302-322306-326311-331
10-1510-1510-15
13-1813-1813-18
10.6-12.67.7-9.7
5-7
22-2823-2923-29
701.5
2.253
137-147137-147137-147
275-295260-280245-265
9-149-149-14
10-159-149-14
19-2113.8-15.8
8-10
18-2419-2519-25
127-137133-143139-149
332-352338-358344-364
10-1510-1510-15
15-2015-2015-20
13.5-15.510.1-12.1
6.7-8.7
27-3428-3529-36
901.5
2.253
142-152142-152142-152
373-393352-372332-352
7-128-138-13
10-156-116-11
19.5-21.513.9-15.98.3-10.3
17-2317-2317-23
164-174172-182181-191
365-385372-392379-399
11-1611-1612-17
15-2015-2015-20
17.4-19.413.2-15.2
9-11
34-4235-4336-44
1101.5
2.253
147-157147-157147-157
467-487448-468430-450
6-116-116-11
10-158-137-12
16.2-18.211.9-13.97.6-9.6
16-2216-2216-22
*Based on 15% Methanol antifreeze solution
Table 12: TS Series Typical Unit Operating Pressures and Temperatures: Continued
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
42 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Unit Operating Conditions
042 Full Load Cooling - without HWG active Full Load Heating - without HWG activeEntering
Water Temp °F
WaterFlow
GPM/ton
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Rise
°F
Air TempDrop °F
DB
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Drop
°F
Air TempRise °F
DB
30*1.5
2.253
114-124113-123113-123
170-190150-170131-151
27-3227-3227-32
10-159-147-12
17.2-19.212.7-14.78.2-10.2
17-2317-2317-23
69-7972-8275-85
286-306289-309292-312
5-105-106-11
5-106-116-11
4.5-6.53.9-5.93.2-5.2
16-2217-2318-24
501.5
2.253
130-140129-139129-139
226-246208-228190-210
10-1510-1510-15
6-115-104-9
17.8-19.813.3-15.38.8-10.8
20-2620-2620-26
100-110105-115110-120
315-335322-342330-350
7-128-13
10-15
6-116-117-12
9-117-95-7
22-2823-2924-30
701.5
2.253
132-142131-141131-141
290-310273-293255-275
6-116-116-11
6-115-104-9
17.3-19.312.8-14.88.3-10.3
19-2519-2519-25
131-141138-148145-155
347-367358-378369-389
11-1613-1816-21
6-118-139-14
13.4-15.410-126.9-8.9
29-3530-3631-37
901.5
2.253
136-146135-145135-145
370-390350-370330-350
6-116-116-11
6-115-104-9
16-1811.8-13.87.6-9.6
17-2317-2317-23
175-185177-187180-190
393-413401-421409-429
19-2420-2522-27
7-129-14
12-17
17.6-19.613.2-15.28.7-10.7
36-4237-4338-44
1101.5
2.253
143-153142-152141-151
469-489448-468427-447
6-116-116-11
6-115-104-9
14-1611-137-9
16-2216-2216-22
*Based on 15% Methanol antifreeze solution
048 Full Load Cooling - without HWG active Full Load Heating - without HWG activeEntering
Water Temp °F
WaterFlow
GPM/ton
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Rise
°F
Air TempDrop °F
DB
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Drop
°F
Air TempRise °F
DB
30*1.5
2.253
108-118107-117107-117
180-200161-181142-162
27-3228-3329-34
12-1710-159-14
19.8-21.814.8-16.89.8-11.8
19-2519-2519-25
65-7568-7872-82
293-313297-217301-321
7-128-139-14
9-149-149-14
8.2-10.26.2-8.24.2-6.2
17-2318-2419-25
501.5
2.253
123-133122-132122-132
236-256218-238200-220
16-2117-2217-22
8-137-126-11
20.2-22.215.2-18.210.2-12.2
21-2721-2721-27
92-102100-110108-118
321-341330-350340-360
10-1511-1612-17
11-1611-1611-16
11.6-13.68.9-10.9
6-8
23-2924-3026-32
701.5
2.253
130-140129-139129-139
305-325285-305265-285
10-1511-1611-16
8-136-115-10
20-2215-1710-12
20-2620-2620-26
122-132133-143144-154
353-373365-385378-398
12-1714-1916-21
11-1611-1611-16
15-1711.5-13.5
8-10
29-3531-3733-39
901.52.25
3
133-143132-142132-142
390-410368-388345-365
8-139-149-14
8-136-115-10
19-2114-169-11
19-2519-2519-25
166-176173-183181-191
397-417407-727417-437
16-2118-2319-24
9-149-14
10-15
19.5-21.514.7-16.79.9-11.9
37-4338-4440-46
1101.5
2.253
141-151140-150140-150
497-517472-492447-467
6-117-128-13
8-136-115-10
18-2013.5-15.58.7-10.7
18-2418-2418-24
*Based on 15% Methanol antifreeze solution
060 Full Load Cooling - without HWG active Full Load Heating - without HWG activeEntering
Water Temp °F
WaterFlow
GPM/ton
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Rise
°F
Air TempDrop °F
DB
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Drop
°F
Air TempRise °F DB
30*1.5
2.253
98-10897-10796-106
160-180149-169137-157
40-4541-4642-48
12-1712-1711-16
20-2214.3-16.38.5-10.5
19-2519-2520-26
62-7266-7670-80
276-296280-300284-304
6-116-117-12
6-116-116-11
8-106-84-6
17-2318-2419-25
501.5
2.253
118-128117-127115-125
225-245210-230195-215
36-4137-4238-43
11-1610-159-14
21.2-23.215.7-17.710.2-12.2
19-2520-2621-27
88-9894-104100-110
306-326311-331317-337
10-1510-1511-16
8-138-139-14
11-138.3-10.35.5-7.5
23-2924-3025-31
701.5
2.253
135-145133-143132-142
300-320285-305270-290
12-1714-1916-21
9-148-137-12
20.3-22.315-1710-12
21-2721-2722-28
112-122122-132130-140
333-353342-362351-371
12-1714-1915-20
10-1510-1511-16
14-1610.5-12.5
7.3-9.3
28-3430-3632-38
901.5
2.253
139-149138-148138-148
390-410370-390350-370
8-138-138-13
7-126-116-11
19.3-21.314.3-16.39.3-11.3
20-2621-2721-27
147-157154-164160-170
369-389377-397385-405
15-2018-2319-24
10-1510-1511-16
17.7-19.713.4-15.4
9-11
36-4237-4338-44
1101.5
2.253
144-154143-153142-152
488-508468-488448-468
8-137-127-12
8-136-115-10
18.4-20.413.6-15.68.8-10.8
21-2721-2721-27
*Based on 15% Methanol antifreeze solution
Table 12: TS Series Typical Unit Operating Pressures and Temperatures: Continued
43
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Unit Operating Conditions
070 Full Load Cooling - without HWG active Full Load Heating - without HWG active
Entering Water
Temp °F
WaterFlow
GPM/ton
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Rise°F
Air TempDrop °F
DB
SuctionPressure
PSIG
DischargePressure
PSIGSuperheat Subcooling
WaterTemp Drop
°F
Air TempRise °F
DB
30*1.5
2.253
110-120109-119107-117
177-197162-182147-167
36-4137-4238-43
15-2013-1811-16
20.2-22.215-17
9.7-11.7
21-2721-2722-28
61-7165-7568-78
290-310292-312296-316
12-1812-1812-18
9-1410-1510-15
8-106-84-6
19-2520-2621-27
501.5
2.253
128-138128-138127-137
246-266228-248210-230
18-2319-2420-25
11-169-146-11
21-2315.6-17.610.2-12.2
22-2823-2924-30
88-9896-106105-115
320-340330-350338-358
11-1711-1711-17
13-1811-169-14
11.7-13.79-116-8
26-3227-3329-35
701.5
2.253
134-144133-143131-141
305-325289-309273-293
9-149-149-14
11-169-146-11
20.8-22.815.4-17.4
10-12
23-2923-2923-29
118-128130-140141-151
355-375368-388380-400
10-1612-1815-21
14-1913-1811-16
15.2-17.211.7-13.7
8-10
33-3935-4137-43
901.5
2.253
140-150139-149138-148
390-410373-393355-375
10-1510-1510-15
11-169-146-11
19.6-21.614.5-16.59.3-11.3
22-2822-2822-28
158-168168-178178-188
401-421412-432423-443
9-1510-1612-18
13-1812-1712-17
19.5-21.514.8-16.8
10-12
41-4743-4945-51
1101.5
2.253
144-154143-153142-152
488-508468-488448-468
10-1510-159-14
9-146-115-10
18.4-20.413.6-15.68.8-10.8
20-2720-2720-27
*Based on 15% Methanol antifreeze solution
Table 12: TS Series Typical Unit Operating Pressures and Temperatures: Continued
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
44 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Performance Data — Tranquility® 30 Model 026 - Full Load
850 CFM Nominal (ISO Rated) Airfl ow Cooling, 950 CFM Nominal (ISO Rated) Airfl ow Heating Performance capacities shown in thousands of Btuh
EWT°F
Cooling - EAT 80/67°F Heating - EAT 70°F
GPMWPD
CFM TC SC kW EER HR HWC GPMWPD
CFM HC kW COP HE LAT HWCPSI FT PSI FT
20 Operation not recommended 6.0 3.7 8.6 820 16.4 1.49 3.2 11.3 88.5 1.66.0 3.7 8.6 950 16.6 1.44 3.4 11.7 86.2 1.5
30
3.0 1.1 2.5 730 30.2 20.2 0.95 31.9 33.4 0.8 3.0 1.1 2.5 820 17.8 1.51 3.5 12.7 90.1 1.83.0 1.1 2.5 850 30.7 21.8 0.98 31.3 34.0 0.8 3.0 1.1 2.5 950 18.1 1.47 3.6 13.1 87.6 1.84.5 2.0 4.6 730 30.2 20.2 0.88 34.2 33.2 0.7 4.5 2.0 4.6 820 18.6 1.53 3.6 13.4 91.0 1.94.5 2.0 4.6 850 30.7 21.7 0.92 33.6 33.9 0.7 4.5 2.0 4.6 950 18.9 1.48 3.7 13.8 88.4 1.96.0 3.1 7.1 730 30.1 20.1 0.86 35.2 33.0 0.6 6.0 3.1 7.1 820 19.0 1.53 3.6 13.8 91.5 2.06.0 3.1 7.1 850 30.7 21.6 0.89 34.6 33.7 0.7 6.0 3.1 7.1 950 19.3 1.49 3.8 14.2 88.8 1.9
40
3.0 0.9 2.0 730 29.6 20.1 1.04 28.4 33.2 1.1 3.0 0.9 2.0 820 20.4 1.56 3.8 15.0 93.0 2.23.0 0.9 2.0 850 30.1 21.6 1.08 27.9 33.8 1.1 3.0 0.9 2.0 950 20.7 1.51 4.0 15.5 90.1 2.14.5 1.6 3.8 730 30.1 20.2 0.97 31.0 33.4 0.9 4.5 1.6 3.8 820 21.3 1.57 4.0 16.0 94.1 2.34.5 1.6 3.8 850 30.6 21.8 1.00 30.5 34.0 0.9 4.5 1.6 3.8 950 21.7 1.53 4.2 16.5 91.1 2.36.0 2.6 6.0 730 30.2 20.2 0.93 32.3 33.4 0.8 6.0 2.6 6.0 820 21.9 1.58 4.0 16.5 94.7 2.46.0 2.6 6.0 850 30.7 21.8 0.97 31.7 34.0 0.8 6.0 2.6 6.0 950 22.2 1.53 4.2 17.0 91.6 2.3
50
3.0 0.7 1.6 730 28.7 19.7 1.15 24.9 32.7 1.4 3.0 0.7 1.6 820 23.1 1.60 4.2 17.6 96.0 2.63.0 0.7 1.6 850 29.2 21.2 1.20 24.4 33.3 1.5 3.0 0.7 1.6 950 23.4 1.55 4.4 18.1 92.8 2.54.5 1.4 3.2 730 29.4 20.0 1.07 27.5 33.1 1.2 4.5 1.4 3.2 820 24.3 1.62 4.4 18.7 97.4 2.74.5 1.4 3.2 850 29.9 21.5 1.11 27.0 33.7 1.2 4.5 1.4 3.2 950 24.6 1.57 4.6 19.3 94.0 2.66.0 2.3 5.2 730 29.7 20.1 1.03 28.9 33.2 1.0 6.0 2.3 5.2 820 24.9 1.64 4.5 19.3 98.1 2.86.0 2.3 5.2 850 30.2 21.6 1.07 28.3 33.9 1.1 6.0 2.3 5.2 950 25.3 1.59 4.7 19.9 94.7 2.7
60
3.0 0.7 1.5 730 27.5 19.2 1.28 21.5 31.9 1.9 3.0 0.7 1.5 820 25.9 1.65 4.6 20.2 99.2 2.93.0 0.7 1.5 850 28.0 20.7 1.33 21.1 32.5 1.9 3.0 0.7 1.5 950 26.3 1.60 4.8 20.8 95.6 2.84.5 1.3 2.9 730 28.4 19.6 1.19 24.0 32.5 1.5 4.5 1.3 2.9 820 27.3 1.68 4.8 21.6 100.8 3.14.5 1.3 2.9 850 28.9 21.1 1.23 23.5 33.1 1.6 4.5 1.3 2.9 950 27.7 1.63 5.0 22.2 97.0 3.06.0 2.0 4.7 730 28.8 19.8 1.14 25.3 32.7 1.4 6.0 2.0 4.7 820 28.1 1.69 4.9 22.3 101.7 3.26.0 2.0 4.7 850 29.3 21.3 1.18 24.8 33.4 1.4 6.0 2.0 4.7 950 28.5 1.64 5.1 22.9 97.8 3.1
70
3.0 0.6 1.5 730 26.1 18.7 1.42 18.4 31.0 2.4 3.0 0.6 1.5 820 28.8 1.70 4.9 22.9 102.5 3.33.0 0.6 1.5 850 26.6 20.1 1.47 18.0 31.6 2.4 3.0 0.6 1.5 950 29.2 1.65 5.2 23.6 98.5 3.24.5 1.2 2.7 730 27.1 19.1 1.32 20.6 31.6 2.0 4.5 1.2 2.7 820 30.4 1.73 5.1 24.4 104.3 3.54.5 1.2 2.7 850 27.6 20.5 1.37 20.2 32.3 2.0 4.5 1.2 2.7 950 30.8 1.68 5.4 25.1 100.0 3.46.0 1.9 4.4 730 27.6 19.3 1.27 21.8 32.0 1.8 6.0 1.9 4.4 820 31.2 1.75 5.2 25.3 105.3 3.66.0 1.9 4.4 850 28.1 20.7 1.31 21.4 32.6 1.9 6.0 1.9 4.4 950 31.7 1.70 5.5 25.9 100.9 3.5
80
3.0 0.7 1.5 730 24.6 18.0 1.58 15.6 30.0 3.0 3.0 0.7 1.5 820 31.6 1.76 5.3 25.6 105.7 3.63.0 0.7 1.5 850 25.0 19.4 1.64 15.3 30.6 3.0 3.0 0.7 1.5 950 32.1 1.70 5.5 26.3 101.3 3.54.5 1.2 2.7 730 25.7 18.5 1.47 17.5 30.7 2.5 4.5 1.2 2.7 820 33.4 1.79 5.5 27.3 107.7 3.84.5 1.2 2.7 850 26.1 19.9 1.52 17.2 31.3 2.6 4.5 1.2 2.7 950 33.9 1.74 5.7 28.0 103.0 3.76.0 1.8 4.2 730 26.2 18.7 1.41 18.5 31.0 2.3 6.0 1.8 4.2 820 34.3 1.81 5.6 28.2 108.8 3.96.0 1.8 4.2 850 26.7 20.1 1.46 18.2 31.7 2.4 6.0 1.8 4.2 950 34.9 1.76 5.8 28.9 104.0 3.8
90
3.0 0.7 1.6 730 23.0 17.4 1.76 13.1 29.0 3.6 3.0 0.7 1.6 820 34.4 1.81 5.6 28.2 108.9 3.93.0 0.7 1.6 850 24.5 19.2 1.70 14.5 30.3 3.3 3.0 0.7 1.6 950 35.0 1.76 5.8 29.0 104.1 3.84.5 1.2 2.7 730 24.1 17.8 1.64 14.7 29.7 3.2 4.5 1.2 2.7 820 36.3 1.86 5.7 30.0 111.0 4.24.5 1.2 2.7 850 24.5 19.2 1.70 14.5 30.3 3.3 4.5 1.2 2.7 950 36.9 1.80 6.0 30.7 105.9 4.06.0 1.8 4.1 730 24.6 18.0 1.58 15.6 30.0 3.0 6.0 1.8 4.1 820 37.3 1.88 5.8 30.9 112.1 4.36.0 1.8 4.1 850 25.1 19.4 1.63 15.3 30.6 3.0 6.0 1.8 4.1 950 37.9 1.82 6.1 31.6 106.9 4.2
100
3.0 0.7 1.6 730 21.5 16.9 1.95 11.0 28.1 4.4
Operation not recommended
3.0 0.7 1.6 850 21.8 18.1 2.02 10.8 28.7 4.54.5 1.2 2.7 730 22.5 17.2 1.82 12.3 28.7 3.94.5 1.2 2.7 850 22.9 18.5 1.89 12.1 29.3 4.06.0 1.8 4.1 730 23.0 17.4 1.76 13.1 29.0 3.76.0 1.8 4.1 850 23.4 18.7 1.82 12.8 29.6 3.7
110
3.0 0.7 1.5 730 20.0 16.4 2.17 9.2 27.4 5.33.0 0.7 1.5 850 20.3 17.7 2.25 9.0 28.0 5.44.5 1.1 2.6 730 20.9 16.7 2.03 10.3 27.8 4.74.5 1.1 2.6 850 21.3 17.9 2.10 10.1 28.5 4.86.0 1.7 4.0 730 21.4 16.8 1.96 10.9 28.1 4.56.0 1.7 4.0 850 21.8 18.1 2.03 10.7 28.7 4.5
120
3.0 0.5 1.2 730 18.7 16.2 2.41 7.7 26.9 6.33.0 0.5 1.2 850 19.0 17.4 2.50 7.6 27.5 6.44.5 1.0 2.4 730 19.5 16.3 2.26 8.6 27.2 5.64.5 1.0 2.4 850 19.8 17.5 2.34 8.5 27.8 5.86.0 1.7 3.9 730 19.9 16.4 2.18 9.1 27.3 5.36.0 1.7 3.9 850 20.2 17.6 2.26 8.9 28.0 5.5
Interpolation is permissible; extrapolation is not. Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. See performance correction tables for operating conditions other than those listed above.Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. For operation in the shaded areas, please see the Performance Data Selection Notes.All performance is based upon the lower voltage of dual voltage rated units.
45
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Performance Data — Tranquility® 30 Model 038 - Full Load
Operation not recommended
1250 CFM Nominal (ISO Rated) Airfl ow Cooling, 1250 CFM Nominal (ISO Rated) Airfl ow Heating Performance capacities shown in thousands of Btuh
EWT°F
Cooling - EAT 80/67°F Heating - EAT 70°F
GPMWPD
CFM TC SC kW EER HR HWC GPMWPD
CFM HC kW COP HE LAT HWCPSI FT PSI FT
20 Operation not recommended 9.0 8.3 19.1 1080 25.6 2.09 3.6 18.5 91.9 2.19.0 8.3 19.1 1250 26.0 2.02 3.8 19.1 89.2 2.1
30
4.5 2.6 6.0 1080 44.8 27.6 1.44 31.1 49.7 1.1 4.5 2.6 6.0 1080 27.9 2.12 3.9 20.7 93.9 2.44.5 2.6 6.0 1250 45.6 29.7 1.49 30.5 50.6 1.1 4.5 2.6 6.0 1250 28.3 2.05 4.0 21.3 91.0 2.46.8 4.5 10.5 1080 44.2 27.4 1.39 31.8 48.9 0.9 6.8 4.5 10.5 1080 29.2 2.14 4.0 21.9 95.1 2.66.8 4.5 10.5 1250 44.9 29.5 1.44 31.2 49.9 0.9 6.8 4.5 10.5 1250 29.7 2.07 4.2 22.6 92.0 2.59.0 6.9 16.0 1080 43.6 27.3 1.38 31.7 48.3 0.8 9.0 6.9 16.0 1080 30.0 2.15 4.1 22.6 95.7 2.79.0 6.9 16.0 1250 44.4 29.3 1.43 31.1 49.3 0.8 9.0 6.9 16.0 1250 30.4 2.08 4.3 23.3 92.5 2.6
40
4.5 2.0 4.7 1080 44.7 27.6 1.54 28.9 49.9 1.4 4.5 2.0 4.7 1080 31.9 2.18 4.3 24.4 97.3 2.94.5 2.0 4.7 1250 45.4 29.6 1.60 28.4 50.9 1.5 4.5 2.0 4.7 1250 32.4 2.12 4.5 25.2 94.0 2.96.8 3.8 8.7 1080 44.8 27.6 1.46 30.7 49.8 1.1 6.8 3.8 8.7 1080 33.5 2.22 4.4 25.9 98.7 3.16.8 3.8 8.7 1250 45.6 29.7 1.51 30.1 50.8 1.2 6.8 3.8 8.7 1250 34.0 2.15 4.6 26.7 95.2 3.09.0 5.9 13.6 1080 44.7 27.6 1.43 31.3 49.6 1.0 9.0 5.9 13.6 1080 34.4 2.23 4.5 26.7 99.5 3.29.0 5.9 13.6 1250 45.5 29.7 1.48 30.7 50.5 1.0 9.0 5.9 13.6 1250 34.9 2.16 4.7 27.5 95.8 3.2
50
4.5 1.7 3.9 1080 43.7 27.3 1.68 26.0 49.5 1.9 4.5 1.7 3.9 1080 35.9 2.27 4.6 28.2 100.8 3.44.5 1.7 3.9 1250 44.5 29.3 1.75 25.5 50.4 2.0 4.5 1.7 3.9 1250 36.5 2.20 4.9 29.0 97.0 3.36.8 3.2 7.5 1080 44.5 27.5 1.57 28.3 49.9 1.5 6.8 3.2 7.5 1080 37.8 2.31 4.8 29.9 102.4 3.76.8 3.2 7.5 1250 45.3 29.6 1.63 27.7 50.8 1.6 6.8 3.2 7.5 1250 38.4 2.24 5.0 30.7 98.4 3.69.0 5.2 11.9 1080 44.7 27.6 1.53 29.3 49.9 1.4 9.0 5.2 11.9 1080 38.8 2.33 4.9 30.8 103.3 3.89.0 5.2 11.9 1250 45.5 29.7 1.58 28.8 50.9 1.4 9.0 5.2 11.9 1250 39.4 2.26 5.1 31.7 99.2 3.7
60
4.5 1.5 3.5 1080 42.2 26.8 1.86 22.7 48.5 2.6 4.5 1.5 3.5 1080 40.0 2.36 5.0 31.9 104.3 3.94.5 1.5 3.5 1250 42.9 28.8 1.93 22.3 49.5 2.7 4.5 1.5 3.5 1250 40.6 2.29 5.2 32.8 100.1 3.86.8 2.9 6.7 1080 43.4 27.2 1.73 25.1 49.3 2.1 6.8 2.9 6.7 1080 42.1 2.42 5.1 33.9 106.1 4.26.8 2.9 6.7 1250 44.1 29.2 1.79 24.7 50.2 2.1 6.8 2.9 6.7 1250 42.8 2.34 5.4 34.8 101.7 4.19.0 4.7 10.8 1080 43.9 27.3 1.67 26.3 49.6 1.9 9.0 4.7 10.8 1080 43.3 2.44 5.2 34.9 107.1 4.39.0 4.7 10.8 1250 44.6 29.4 1.73 25.9 50.5 1.9 9.0 4.7 10.8 1250 43.9 2.37 5.4 35.8 102.5 4.2
70
4.5 1.5 3.4 1080 40.2 26.0 2.06 19.5 47.3 3.4 4.5 1.5 3.4 1080 44.1 2.47 5.2 35.7 107.8 4.44.5 1.5 3.4 1250 40.9 28.0 2.14 19.2 48.2 3.5 4.5 1.5 3.4 1250 44.8 2.39 5.5 36.6 103.2 4.36.8 2.7 6.3 1080 41.7 26.6 1.91 21.8 48.2 2.8 6.8 2.7 6.3 1080 46.5 2.53 5.4 37.8 109.8 4.76.8 2.7 6.3 1250 42.4 28.6 1.98 21.4 49.2 2.9 6.8 2.7 6.3 1250 47.2 2.45 5.6 38.8 104.9 4.59.0 4.4 10.1 1080 42.4 26.8 1.84 23.0 48.6 2.5 9.0 4.4 10.1 1080 47.8 2.56 5.5 39.0 111.0 4.89.0 4.4 10.1 1250 43.1 28.8 1.91 22.6 49.6 2.6 9.0 4.4 10.1 1250 48.5 2.48 5.7 40.0 105.9 4.7
80
4.5 1.5 3.4 1080 38.0 25.2 2.29 16.6 45.8 4.3 4.5 1.5 3.4 1080 48.2 2.58 5.5 39.4 111.3 4.94.5 1.5 3.4 1250 38.6 27.1 2.37 16.3 46.7 4.4 4.5 1.5 3.4 1250 49.0 2.50 5.7 40.4 106.3 4.76.8 2.7 6.2 1080 39.6 25.8 2.13 18.6 46.8 3.6 6.8 2.7 6.2 1080 50.9 2.65 5.6 41.8 113.6 5.26.8 2.7 6.2 1250 40.3 27.7 2.20 18.3 47.8 3.7 6.8 2.7 6.2 1250 51.6 2.56 5.9 42.9 108.2 5.09.0 4.2 9.7 1080 40.4 26.1 2.05 19.7 47.4 3.3 9.0 4.2 9.7 1080 52.3 2.69 5.7 43.1 114.8 5.39.0 4.2 9.7 1250 41.1 28.1 2.12 19.4 48.3 3.4 9.0 4.2 9.7 1250 53.1 2.60 6.0 44.2 109.3 5.2
90
4.5 1.5 3.5 1080 35.6 24.1 2.54 14.0 44.3 5.3 4.5 1.5 3.5 1080 52.4 2.69 5.7 43.2 114.9 5.34.5 1.5 3.5 1250 37.9 26.7 2.45 15.4 46.2 4.7 4.5 1.5 3.5 1250 53.2 2.60 6.0 44.3 109.4 5.26.8 2.6 6.1 1080 37.2 24.9 2.37 15.7 45.3 4.6 6.8 2.6 6.1 1080 55.3 2.76 5.9 45.8 117.4 5.66.8 2.6 6.1 1250 37.9 26.7 2.45 15.4 46.2 4.7 6.8 2.6 6.1 1250 56.1 2.68 6.1 47.0 111.6 5.59.0 4.1 9.5 1080 38.1 25.2 2.28 16.7 45.9 4.3 9.0 4.1 9.5 1080 56.8 2.81 5.9 47.3 118.7 5.89.0 4.1 9.5 1250 38.7 27.1 2.36 16.4 46.8 4.3 9.0 4.1 9.5 1250 57.7 2.72 6.2 48.4 112.7 5.6
100
4.5 1.5 3.5 1080 33.2 23.0 2.82 11.8 42.8 6.5
Operation not recommended
4.5 1.5 3.5 1250 33.7 24.8 2.92 11.6 43.7 6.76.8 2.6 6.1 1080 34.8 23.8 2.63 13.2 43.7 5.76.8 2.6 6.1 1250 35.4 25.6 2.73 13.0 44.7 5.89.0 4.1 9.4 1080 35.6 24.1 2.54 14.0 44.3 5.39.0 4.1 9.4 1250 36.2 26.0 2.63 13.7 45.2 5.4
110
4.5 1.4 3.2 1080 30.8 21.9 3.11 9.9 41.5 7.94.5 1.4 3.2 1250 31.4 23.5 3.23 9.7 42.4 8.06.8 2.5 5.9 1080 32.3 22.6 2.92 11.1 42.3 7.06.8 2.5 5.9 1250 32.9 24.3 3.03 10.9 43.2 7.19.0 4.0 9.2 1080 33.1 23.0 2.83 11.7 42.7 6.69.0 4.0 9.2 1250 33.7 24.7 2.93 11.5 43.6 6.7
120
4.5 1.1 2.6 1080 28.7 20.8 3.43 8.4 40.4 9.44.5 1.1 2.6 1250 29.2 22.3 3.55 8.2 41.4 9.66.8 2.4 5.4 1080 30.0 21.4 3.23 9.3 41.0 8.46.8 2.4 5.4 1250 30.5 23.1 3.35 9.1 41.9 8.69.0 3.9 8.9 1080 30.7 21.8 3.13 9.8 41.4 7.99.0 3.9 8.9 1250 31.2 23.4 3.25 9.6 42.3 8.1
Interpolation is permissible; extrapolation is not. Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. See performance correction tables for operating conditions other than those listed above.Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. For operation in the shaded areas, please see the Performance Data Selection Notes.All performance is based upon the lower voltage of dual voltage rated units.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
46 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Performance Data — Tranquility® 30 Model 049 - Full Load
1550 CFM Nominal (ISO Rated) Airfl ow Cooling, 1650 CFM Nominal (ISO Rated) Airfl ow Heating Performance capacities shown in thousands of Btuh
EWT°F
Cooling - EAT 80/67°F Heating - EAT 70°F
GPMWPD
CFM TC SC kW EER HR HWC GPMWPD
CFM HC kW COP HE LAT HWCPSI FT PSI FT
20 Operation not recommended 12.0 5.2 12.1 1430 33.0 2.94 3.3 23.0 91.4 3.412.0 5.2 12.1 1650 33.5 2.85 3.4 23.8 88.8 3.3
30
6.0 1.2 2.8 1330 58.6 39.7 1.89 31.0 65.0 1.8 6.0 1.2 2.8 1430 35.6 3.03 3.4 25.2 93.0 3.66.0 1.2 2.8 1550 59.6 42.6 1.96 30.4 66.3 1.8 6.0 1.2 2.8 1650 36.1 2.94 3.6 26.1 90.3 3.59.0 2.7 6.4 1330 58.4 40.7 1.78 32.8 64.5 1.8 9.0 2.7 6.4 1430 36.9 3.07 3.5 26.5 93.9 3.69.0 2.7 6.4 1550 59.4 43.8 1.85 32.2 65.7 1.8 9.0 2.7 6.4 1650 37.5 2.98 3.7 27.3 91.0 3.5
12.0 4.7 10.8 1330 58.0 41.3 1.73 33.5 64.0 1.8 12.0 4.7 10.8 1430 37.7 3.10 3.6 27.1 94.4 3.712.0 4.7 10.8 1550 59.0 44.4 1.80 32.9 65.2 1.9 12.0 4.7 10.8 1650 38.3 3.00 3.7 28.1 91.5 3.6
40
6.0 1.0 2.3 1330 57.8 38.4 2.06 28.1 64.8 2.0 6.0 1.0 2.3 1430 40.3 3.17 3.7 29.5 96.1 3.86.0 1.0 2.3 1550 58.8 41.3 2.13 27.6 66.1 2.0 6.0 1.0 2.3 1650 40.9 3.07 3.9 30.4 93.0 3.79.0 2.4 5.6 1330 58.5 39.3 1.93 30.3 65.1 1.8 9.0 2.4 5.6 1430 42.1 3.21 3.8 31.2 97.3 3.99.0 2.4 5.6 1550 59.5 42.3 2.00 29.7 66.3 1.9 9.0 2.4 5.6 1650 42.8 3.11 4.0 32.1 94.0 3.8
12.0 4.2 9.7 1330 58.6 39.8 1.87 31.3 65.0 1.8 12.0 4.2 9.7 1430 43.1 3.24 3.9 32.1 97.9 4.012.0 4.2 9.7 1550 59.6 42.8 1.94 30.7 66.2 1.8 12.0 4.2 9.7 1650 43.8 3.14 4.1 33.1 94.6 3.9
50
6.0 0.9 2.0 1330 56.1 37.4 2.25 24.9 63.8 2.3 6.0 0.9 2.0 1430 45.5 3.30 4.0 34.3 99.5 4.16.0 0.9 2.0 1550 57.1 40.2 2.33 24.4 65.0 2.4 6.0 0.9 2.0 1650 46.2 3.20 4.2 35.3 95.9 4.09.0 2.2 5.1 1330 57.4 38.1 2.11 27.2 64.6 2.0 9.0 2.2 5.1 1430 47.8 3.35 4.2 36.4 101.0 4.39.0 2.2 5.1 1550 58.4 41.0 2.18 26.7 65.9 2.1 9.0 2.2 5.1 1650 48.5 3.25 4.4 37.5 97.2 4.1
12.0 3.9 9.0 1330 57.9 38.5 2.04 28.4 64.9 1.9 12.0 3.9 9.0 1430 49.1 3.38 4.3 37.5 101.8 4.312.0 3.9 9.0 1550 58.9 41.4 2.11 27.9 66.1 2.0 12.0 3.9 9.0 1650 49.8 3.28 4.5 38.7 98.0 4.2
60
6.0 0.8 1.9 1330 53.7 36.5 2.48 21.7 62.2 2.9 6.0 0.8 1.9 1430 51.1 3.43 4.4 39.4 103.1 4.56.0 0.8 1.9 1550 54.7 39.2 2.57 21.3 63.4 2.9 6.0 0.8 1.9 1650 51.9 3.33 4.6 40.5 99.1 4.39.0 2.0 4.7 1330 55.5 37.1 2.31 24.0 63.4 2.5 9.0 2.0 4.7 1430 53.8 3.50 4.5 41.9 104.9 4.79.0 2.0 4.7 1550 56.4 39.9 2.40 23.6 64.6 2.5 9.0 2.0 4.7 1650 54.7 3.39 4.7 43.1 100.7 4.5
12.0 3.6 8.4 1330 56.3 37.5 2.24 25.2 63.9 2.3 12.0 3.6 8.4 1430 55.4 3.54 4.6 43.3 105.9 4.812.0 3.6 8.4 1550 57.2 40.3 2.32 24.7 65.1 2.3 12.0 3.6 8.4 1650 56.2 3.43 4.8 44.5 101.5 4.6
70
6.0 0.8 1.8 1330 51.0 35.6 2.73 18.7 60.3 3.6 6.0 0.8 1.8 1430 56.9 3.57 4.7 44.7 106.8 4.96.0 0.8 1.8 1550 51.8 38.2 2.83 18.3 61.5 3.7 6.0 0.8 1.8 1650 57.7 3.46 4.9 45.9 102.4 4.79.0 2.0 4.5 1330 52.9 36.2 2.55 20.8 61.6 3.1 9.0 2.0 4.5 1430 60.0 3.66 4.8 47.6 108.9 5.19.0 2.0 4.5 1550 53.9 38.9 2.64 20.4 62.9 3.1 9.0 2.0 4.5 1650 61.0 3.54 5.0 48.9 104.2 5.0
12.0 3.5 8.1 1330 53.9 36.5 2.46 21.9 62.3 2.8 12.0 3.5 8.1 1430 61.8 3.71 4.9 49.1 110.0 5.212.0 3.5 8.1 1550 54.8 39.3 2.55 21.5 63.5 2.9 12.0 3.5 8.1 1650 62.7 3.59 5.1 50.5 105.2 5.1
80
6.0 0.8 1.8 1330 47.9 34.6 3.02 15.8 58.2 4.5 6.0 0.8 1.8 1430 62.7 3.73 4.9 50.0 110.6 5.36.0 0.8 1.8 1550 48.7 37.2 3.13 15.5 59.4 4.5 6.0 0.8 1.8 1650 63.7 3.62 5.2 51.3 105.7 5.29.0 1.9 4.4 1330 50.0 35.3 2.82 17.7 59.6 3.8 9.0 1.9 4.4 1430 66.2 3.84 5.1 53.1 112.9 5.69.0 1.9 4.4 1550 50.8 37.9 2.92 17.4 60.8 3.9 9.0 1.9 4.4 1650 67.2 3.72 5.3 54.5 107.7 5.4
12.0 3.4 7.8 1330 51.0 35.6 2.72 18.7 60.3 3.6 12.0 3.4 7.8 1430 68.1 3.90 5.1 54.8 114.1 5.812.0 3.4 7.8 1550 51.9 38.3 2.82 18.4 61.5 3.6 12.0 3.4 7.8 1650 69.2 3.78 5.4 56.3 108.8 5.6
90
6.0 0.8 1.9 1330 44.7 33.4 3.36 13.3 56.2 5.5 6.0 0.8 1.9 1430 68.5 3.91 5.1 55.1 114.3 5.86.0 0.8 1.9 1550 47.6 36.8 3.25 14.6 58.7 4.9 6.0 0.8 1.9 1650 69.5 3.79 5.4 56.6 109.0 5.69.0 1.9 4.4 1330 46.8 34.2 3.14 14.9 57.5 4.8 9.0 1.9 4.4 1430 72.2 4.05 5.2 58.4 116.8 6.29.0 1.9 4.4 1550 47.6 36.8 3.25 14.6 58.7 4.9 9.0 1.9 4.4 1650 73.3 3.92 5.5 60.0 111.2 6.0
12.0 3.3 7.7 1330 47.9 34.6 3.03 15.8 58.2 4.5 12.0 3.3 7.7 1430 74.2 4.13 5.3 60.1 118.1 6.412.0 3.3 7.7 1550 48.7 37.2 3.14 15.5 59.4 4.6 12.0 3.3 7.7 1650 75.4 4.00 5.5 61.7 112.3 6.2
100
6.0 0.8 1.9 1330 41.6 32.2 3.75 11.1 54.4 6.7
Operation not recommended
6.0 0.8 1.9 1550 42.4 34.6 3.88 10.9 55.6 6.99.0 1.9 4.3 1330 43.6 33.0 3.50 12.5 55.5 5.99.0 1.9 4.3 1550 44.3 35.5 3.62 12.2 56.7 6.1
12.0 3.3 7.6 1330 44.6 33.4 3.38 13.2 56.1 5.612.0 3.3 7.6 1550 45.4 35.9 3.50 13.0 57.3 5.7
110
6.0 0.8 1.8 1330 38.8 30.9 4.19 9.2 53.1 8.26.0 0.8 1.8 1550 39.5 33.2 4.35 9.1 54.3 8.49.0 1.8 4.3 1330 40.5 31.7 3.91 10.3 53.8 7.39.0 1.8 4.3 1550 41.2 34.1 4.06 10.2 55.0 7.4
12.0 3.3 7.5 1330 41.4 32.1 3.78 11.0 54.3 6.812.0 3.3 7.5 1550 42.1 34.5 3.92 10.8 55.5 7.0
120
6.0 0.7 1.6 1330 36.4 29.6 4.71 7.7 52.5 9.96.0 0.7 1.6 1550 37.0 31.8 4.88 7.6 53.7 10.19.0 1.8 4.1 1330 37.8 30.4 4.39 8.6 52.7 8.89.0 1.8 4.1 1550 38.4 32.6 4.55 8.4 53.9 9.0
12.0 3.2 7.4 1330 38.5 30.8 4.24 9.1 53.0 8.312.0 3.2 7.4 1550 39.2 33.1 4.39 8.9 54.2 8.5
Interpolation is permissible; extrapolation is not. Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. See performance correction tables for operating conditions other than those listed above.Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. For operation in the shaded areas, please see the Performance Data Selection Notes.All performance is based upon the lower voltage of dual voltage rated units.
47
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Performance Data — Tranquility® 30 Model 064 - Full Load
1825 CFM Nominal (ISO Rated) Airfl ow Cooling, 2050 CFM Nominal (ISO Rated) Airfl ow Heating Performance capacities shown in thousands of Btuh
EWT°F
Cooling - EAT 80/67°F Heating - EAT 70°F
GPMWPD
CFM TC SC kW EER HR HWC GPMWPD
CFM HC kW COP HE LAT HWCPSI FT PSI FT
20 Operation not recommended15.0 7.3 16.8 1750 42.8 3.89 3.2 29.5 92.6 4.015.0 7.3 16.8 2050 43.4 3.77 3.4 30.6 89.6 3.8
30
7.5 1.7 3.9 1590 75.3 49.7 2.68 28.1 84.4 1.9 7.5 1.7 3.9 1750 46.9 3.95 3.5 33.4 94.8 4.17.5 1.7 3.9 1850 76.6 53.4 2.78 27.5 86.1 2.0 7.5 1.7 3.9 2050 47.6 3.82 3.6 34.5 91.5 4.011.3 3.7 8.6 1590 74.9 50.3 2.57 29.1 83.6 1.8 11.3 3.7 8.6 1750 49.1 3.98 3.6 35.6 96.0 4.211.3 3.7 8.6 1850 76.2 54.0 2.67 28.5 85.3 1.8 11.3 3.7 8.6 2050 49.9 3.86 3.8 36.7 92.5 4.115.0 6.1 14.1 1590 74.2 50.5 2.53 29.3 82.9 1.8 15.0 6.1 14.1 1750 50.4 4.00 3.7 36.7 96.7 4.215.0 6.1 14.1 1850 75.5 54.3 2.62 28.8 84.5 1.8 15.0 6.1 14.1 2050 51.2 3.88 3.9 37.9 93.1 4.1
40
7.5 1.2 2.7 1590 74.4 48.8 2.86 26.0 84.2 2.3 7.5 1.2 2.7 1750 53.9 4.06 3.9 40.0 98.5 4.47.5 1.2 2.7 1850 75.7 52.5 2.97 25.5 85.8 2.3 7.5 1.2 2.7 2050 54.7 3.94 4.1 41.3 94.7 4.211.3 3.0 7.0 1590 75.2 49.5 2.72 27.6 84.5 2.0 11.3 3.0 7.0 1750 56.7 4.12 4.0 42.7 100.0 4.511.3 3.0 7.0 1850 76.5 53.2 2.82 27.1 86.1 2.0 11.3 3.0 7.0 2050 57.6 3.99 4.2 44.0 96.0 4.415.0 5.3 12.2 1590 75.3 49.8 2.66 28.3 84.3 1.9 15.0 5.3 12.2 1750 58.3 4.15 4.1 44.1 100.8 4.615.0 5.3 12.2 1850 76.6 53.6 2.76 27.8 86.0 1.9 15.0 5.3 12.2 2050 59.2 4.02 4.3 45.5 96.7 4.4
50
7.5 0.9 2.0 1590 72.4 47.8 3.08 23.5 82.9 2.8 7.5 0.9 2.0 1750 61.1 4.21 4.3 46.8 102.4 4.77.5 0.9 2.0 1850 73.6 51.4 3.20 23.0 84.5 2.9 7.5 0.9 2.0 2050 62.1 4.08 4.5 48.2 98.0 4.611.3 2.6 6.0 1590 74.0 48.6 2.91 25.4 84.0 2.4 11.3 2.6 6.0 1750 64.5 4.28 4.4 49.9 104.1 4.911.3 2.6 6.0 1850 75.3 52.2 3.02 25.0 85.6 2.5 11.3 2.6 6.0 2050 65.5 4.15 4.6 51.3 99.6 4.715.0 4.7 10.8 1590 74.6 48.9 2.83 26.3 84.3 2.2 15.0 4.7 10.8 1750 66.3 4.32 4.5 51.6 105.1 5.015.0 4.7 10.8 1850 75.9 52.6 2.94 25.9 85.9 2.3 15.0 4.7 10.8 2050 67.3 4.19 4.7 53.0 100.4 4.8
60
7.5 0.7 1.7 1590 69.5 46.7 3.35 20.7 81.0 3.5 7.5 0.7 1.7 1750 68.5 4.37 4.6 53.6 106.2 5.17.5 0.7 1.7 1850 70.7 50.3 3.47 20.4 82.6 3.6 7.5 0.7 1.7 2050 69.5 4.24 4.8 55.1 101.4 5.011.3 2.4 5.4 1590 71.7 47.6 3.15 22.8 82.5 3.0 11.3 2.4 5.4 1750 72.3 4.46 4.7 57.1 108.3 5.311.3 2.4 5.4 1850 73.0 51.1 3.26 22.4 84.1 3.1 11.3 2.4 5.4 2050 73.4 4.33 5.0 58.6 103.2 5.215.0 4.3 10.0 1590 72.7 48.0 3.05 23.8 83.1 2.8 15.0 4.3 10.0 1750 74.4 4.52 4.8 59.0 109.4 5.515.0 4.3 10.0 1850 74.0 51.6 3.16 23.4 84.8 2.8 15.0 4.3 10.0 2050 75.5 4.38 5.1 60.6 104.1 5.3
70
7.5 0.7 1.7 1590 66.1 45.5 3.67 18.0 78.7 4.4 7.5 0.7 1.7 1750 75.8 4.55 4.9 60.3 110.1 5.67.5 0.7 1.7 1850 67.3 48.9 3.81 17.7 80.3 4.5 7.5 0.7 1.7 2050 77.0 4.41 5.1 61.9 104.8 5.411.3 2.3 5.2 1590 68.6 46.4 3.43 20.0 80.4 3.8 11.3 2.3 5.2 1750 80.1 4.67 5.0 64.2 112.4 5.811.3 2.3 5.2 1850 69.8 49.9 3.56 19.6 82.0 3.8 11.3 2.3 5.2 2050 81.3 4.52 5.3 65.9 106.7 5.715.0 4.1 9.5 1590 69.9 46.9 3.32 21.0 81.2 3.5 15.0 4.1 9.5 1750 82.4 4.73 5.1 66.3 113.6 6.015.0 4.1 9.5 1850 71.1 50.4 3.44 20.6 82.8 3.5 15.0 4.1 9.5 2050 83.7 4.59 5.3 68.0 107.8 5.8
80
7.5 0.8 1.8 1590 62.5 44.1 4.05 15.4 76.3 5.5 7.5 0.8 1.8 1750 83.1 4.75 5.1 66.9 114.0 6.17.5 0.8 1.8 1850 63.5 47.5 4.19 15.1 77.8 5.6 7.5 0.8 1.8 2050 84.4 4.61 5.4 68.7 108.1 5.911.3 2.2 5.2 1590 65.1 45.1 3.78 17.2 78.0 4.7 11.3 2.2 5.2 1750 87.8 4.89 5.3 71.1 116.4 6.411.3 2.2 5.2 1850 66.2 48.5 3.91 16.9 79.6 4.8 11.3 2.2 5.2 2050 89.1 4.74 5.5 73.0 110.3 6.215.0 4.1 9.4 1590 66.4 45.6 3.65 18.2 78.8 4.3 15.0 4.1 9.4 1750 90.3 4.97 5.3 73.4 117.8 6.615.0 4.1 9.4 1850 67.5 49.0 3.78 17.9 80.4 4.4 15.0 4.1 9.4 2050 91.7 4.81 5.6 75.3 111.4 6.4
90
7.5 0.8 2.0 1590 58.7 42.6 4.49 13.1 74.0 6.7 7.5 0.8 2.0 1750 90.3 4.97 5.3 73.3 117.8 6.67.5 0.8 2.0 1850 62.3 47.0 4.33 14.4 77.1 5.9 7.5 0.8 2.0 2050 91.7 4.81 5.6 75.2 111.4 6.411.3 2.3 5.2 1590 61.3 43.7 4.18 14.7 75.5 5.8 11.3 2.3 5.2 1750 95.2 5.12 5.4 77.8 120.4 7.111.3 2.3 5.2 1850 62.3 47.0 4.33 14.4 77.1 5.9 11.3 2.3 5.2 2050 96.7 4.96 5.7 79.7 113.7 6.915.0 4.0 9.3 1590 62.6 44.2 4.03 15.5 76.4 5.4 15.0 4.0 9.3 1750 97.9 5.21 5.5 80.1 121.8 7.315.0 4.0 9.3 1850 63.7 47.5 4.18 15.2 77.9 5.5 15.0 4.0 9.3 2050 99.4 5.05 5.8 82.1 114.9 7.1
100
7.5 0.9 2.0 1590 55.2 41.1 5.00 11.0 72.3 8.1
Operation not recommended
7.5 0.9 2.0 1850 56.2 44.2 5.18 10.8 73.9 8.311.3 2.3 5.2 1590 57.5 42.1 4.65 12.4 73.4 7.111.3 2.3 5.2 1850 58.5 45.3 4.82 12.1 75.0 7.315.0 4.0 9.3 1590 58.8 42.6 4.48 13.1 74.1 6.715.0 4.0 9.3 1850 59.8 45.9 4.65 12.9 75.6 6.8
110
7.5 0.8 1.8 1590 52.2 39.6 5.60 9.3 71.3 9.87.5 0.8 1.8 1850 53.1 42.6 5.80 9.2 72.9 10.011.3 2.2 5.1 1590 54.1 40.6 5.20 10.4 71.8 8.711.3 2.2 5.1 1850 55.0 43.6 5.39 10.2 73.4 8.815.0 4.0 9.2 1590 55.2 41.1 5.01 11.0 72.3 8.215.0 4.0 9.2 1850 56.1 44.2 5.19 10.8 73.8 8.3
120
7.5 0.6 1.3 1590 50.0 38.5 6.30 7.9 71.5 11.77.5 0.6 1.3 1850 50.8 41.4 6.53 7.8 73.1 11.911.3 2.0 4.7 1590 51.3 39.2 5.83 8.8 71.2 10.411.3 2.0 4.7 1850 52.2 42.1 6.04 8.6 72.8 10.615.0 3.8 8.8 1590 52.1 39.6 5.62 9.3 71.3 9.815.0 3.8 8.8 1850 53.0 42.6 5.82 9.1 72.9 10.0
Interpolation is permissible; extrapolation is not. Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. See performance correction tables for operating conditions other than those listed above.Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. For operation in the shaded areas, please see the Performance Data Selection Notes.All performance is based upon the lower voltage of dual voltage rated units.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
48 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Performance Data — Tranquility® 30 Model 072 - Full Load
1950 CFM Nominal (Rated) Airfl ow Cooling, 2100 CFM Nominal (Rated) Airfl ow Heating Performance capacities shown in thousands of Btuh
EWT°F
Cooling - EAT 80/67°F Heating - EAT 70°F
GPMWPD
CFM TC SC kW EER HR HWC GPMWPD
CFM HC kW COP HE LAT HWCPSI FT PSI FT
20 Operation not recommended17.0 8.9 20.6 1750 46.6 4.66 2.9 30.7 94.7 5.217.0 8.9 20.6 2050 47.3 4.52 3.1 31.9 91.4 5.0
30
8.5 2.2 5.1 1590 82.4 50.1 3.04 27.1 92.8 3.6 8.5 2.2 5.1 1750 51.6 4.77 3.2 35.3 97.3 5.48.5 2.2 5.1 1850 83.8 53.9 3.15 26.6 94.6 3.7 8.5 2.2 5.1 2050 52.4 4.63 3.3 36.6 93.7 5.2
12.8 4.6 10.6 1590 82.3 50.0 2.90 28.4 92.2 3.6 12.8 4.6 10.6 1750 54.0 4.83 3.3 37.5 98.6 5.512.8 4.6 10.6 1850 83.7 53.8 3.00 27.9 93.9 3.7 12.8 4.6 10.6 2050 54.8 4.68 3.4 38.8 94.8 5.417.0 7.6 17.6 1590 81.9 49.8 2.84 28.9 91.6 3.6 17.0 7.6 17.6 1750 55.3 4.86 3.3 38.7 99.2 5.617.0 7.6 17.6 1850 83.3 53.5 2.94 28.3 93.3 3.7 17.0 7.6 17.6 2050 56.1 4.71 3.5 40.1 95.3 5.5
40
8.5 1.6 3.8 1590 81.3 49.8 3.27 24.9 92.4 3.9 8.5 1.6 3.8 1750 59.4 4.96 3.5 42.4 101.4 5.98.5 1.6 3.8 1850 82.7 53.5 3.39 24.4 94.3 4.0 8.5 1.6 3.8 2050 60.3 4.80 3.7 43.9 97.2 5.7
12.8 3.9 8.9 1590 82.2 50.1 3.09 26.6 92.8 3.6 12.8 3.9 8.9 1750 62.1 5.02 3.6 45.0 102.9 6.112.8 3.9 8.9 1850 83.6 53.9 3.21 26.1 94.6 3.7 12.8 3.9 8.9 2050 63.1 4.87 3.8 46.5 98.5 5.917.0 6.7 15.5 1590 82.4 50.1 3.02 27.3 92.7 3.6 17.0 6.7 15.5 1750 63.6 5.06 3.7 46.4 103.7 6.217.0 6.7 15.5 1850 83.8 53.9 3.13 26.8 94.5 3.7 17.0 6.7 15.5 2050 64.6 4.90 3.9 47.9 99.2 6.1
50
8.5 1.3 3.0 1590 79.1 49.0 3.54 22.3 91.2 4.5 8.5 1.3 3.0 1750 66.9 5.14 3.8 49.4 105.4 6.58.5 1.3 3.0 1850 80.5 52.6 3.67 21.9 93.0 4.6 8.5 1.3 3.0 2050 67.9 4.99 4.0 50.9 100.7 6.3
12.8 3.4 7.8 1590 80.8 49.6 3.34 24.2 92.2 4.0 12.8 3.4 7.8 1750 70.1 5.23 3.9 52.3 107.1 6.812.8 3.4 7.8 1850 82.2 53.3 3.46 23.8 94.0 4.1 12.8 3.4 7.8 2050 71.2 5.07 4.1 53.9 102.1 6.617.0 6.0 13.9 1590 81.5 49.8 3.24 25.1 92.5 3.8 17.0 6.0 13.9 1750 71.8 5.27 4.0 53.8 108.0 7.017.0 6.0 13.9 1850 82.9 53.6 3.36 24.7 94.3 3.9 17.0 6.0 13.9 2050 72.9 5.11 4.2 55.5 102.9 6.8
60
8.5 1.2 2.7 1590 76.1 47.8 3.87 19.6 89.3 5.4 8.5 1.2 2.7 1750 74.4 5.34 4.1 56.2 109.4 7.38.5 1.2 2.7 1850 77.4 51.4 4.01 19.3 91.1 5.6 8.5 1.2 2.7 2050 75.5 5.18 4.3 57.9 104.1 7.1
12.8 3.1 7.1 1590 78.3 48.7 3.63 21.6 90.7 4.7 12.8 3.1 7.1 1750 78.0 5.44 4.2 59.4 111.3 7.712.8 3.1 7.1 1850 79.7 52.3 3.76 21.2 92.5 4.8 12.8 3.1 7.1 2050 79.2 5.28 4.4 61.2 105.8 7.417.0 5.6 13.0 1590 79.3 49.1 3.52 22.6 91.3 4.4 17.0 5.6 13.0 1750 80.0 5.50 4.3 61.2 112.3 7.917.0 5.6 13.0 1850 80.7 52.7 3.64 22.2 93.1 4.5 17.0 5.6 13.0 2050 81.2 5.33 4.5 63.0 106.7 7.7
70
8.5 1.1 2.6 1590 72.4 46.3 4.26 17.0 87.0 6.7 8.5 1.1 2.6 1750 81.9 5.56 4.3 62.9 113.3 8.18.5 1.1 2.6 1850 73.7 49.8 4.42 16.7 88.7 6.8 8.5 1.1 2.6 2050 83.2 5.38 4.5 64.8 107.6 7.9
12.8 3.0 6.8 1590 75.0 47.4 3.98 18.9 88.6 5.8 12.8 3.0 6.8 1750 86.0 5.68 4.4 66.6 115.5 8.612.8 3.0 6.8 1850 76.3 50.9 4.12 18.5 90.4 5.9 12.8 3.0 6.8 2050 87.3 5.50 4.6 68.5 109.4 8.417.0 5.4 12.4 1590 76.3 47.9 3.85 19.8 89.4 5.4 17.0 5.4 12.4 1750 88.2 5.75 4.5 68.6 116.7 8.917.0 5.4 12.4 1850 77.6 51.5 3.99 19.5 91.2 5.5 17.0 5.4 12.4 2050 89.5 5.57 4.7 70.5 110.4 8.7
80
8.5 1.2 2.7 1590 68.4 44.7 4.72 14.5 84.5 8.2 8.5 1.2 2.7 1750 89.5 5.79 4.5 69.8 117.4 9.18.5 1.2 2.7 1850 69.5 48.1 4.89 14.2 86.2 8.4 8.5 1.2 2.7 2050 90.9 5.61 4.7 71.7 111.0 8.8
12.8 2.9 6.7 1590 71.2 45.8 4.40 16.2 86.2 7.1 12.8 2.9 6.7 1750 94.1 5.93 4.6 73.9 119.8 9.812.8 2.9 6.7 1850 72.4 49.3 4.56 15.9 88.0 7.3 12.8 2.9 6.7 2050 95.5 5.75 4.9 75.9 113.2 9.517.0 5.2 12.1 1590 72.6 46.4 4.24 17.1 87.1 6.6 17.0 5.2 12.1 1750 96.7 6.02 4.7 76.1 121.1 10.117.0 5.2 12.1 1850 73.8 49.9 4.40 16.8 88.8 6.7 17.0 5.2 12.1 2050 98.1 5.83 4.9 78.2 114.3 9.8
90
8.5 1.2 2.8 1590 64.1 43.0 5.26 12.2 82.0 10.0 8.5 1.2 2.8 1750 97.3 6.04 4.7 76.7 121.5 10.28.5 1.2 2.8 1850 68.1 47.4 5.07 13.4 85.4 9.0 8.5 1.2 2.8 2050 98.8 5.85 4.9 78.8 114.6 9.9
12.8 2.9 6.7 1590 67.0 44.1 4.89 13.7 83.6 8.8 12.8 2.9 6.7 1750 102.6 6.22 4.8 81.3 124.3 11.012.8 2.9 6.7 1850 68.1 47.4 5.07 13.4 85.4 9.0 12.8 2.9 6.7 2050 104.1 6.03 5.1 83.6 117.0 10.717.0 5.2 12.0 1590 68.4 44.7 4.71 14.5 84.5 8.2 17.0 5.2 12.0 1750 105.5 6.32 4.9 83.9 125.8 11.417.0 5.2 12.0 1850 69.6 48.1 4.88 14.2 86.3 8.4 17.0 5.2 12.0 2050 107.1 6.12 5.1 86.2 118.4 11.1
100
8.5 1.2 2.8 1590 59.8 41.2 5.88 10.2 79.9 12.2
Operation not recommended
8.5 1.2 2.8 1850 60.9 44.3 6.09 10.0 81.6 12.512.8 2.9 6.7 1590 62.6 42.3 5.46 11.5 81.2 10.812.8 2.9 6.7 1850 63.7 45.5 5.66 11.2 83.0 11.017.0 5.2 12.0 1590 64.0 42.9 5.27 12.2 82.0 10.117.0 5.2 12.0 1850 65.1 46.2 5.46 11.9 83.8 10.3
110
8.5 1.1 2.6 1590 55.7 39.5 6.61 8.4 78.2 14.78.5 1.1 2.6 1850 56.7 42.5 6.85 8.3 80.0 15.0
12.8 2.9 6.6 1590 58.3 40.6 6.13 9.5 79.2 13.112.8 2.9 6.6 1850 59.3 43.6 6.36 9.3 81.0 13.417.0 5.1 11.8 1590 59.6 41.1 5.91 10.1 79.8 12.317.0 5.1 11.8 1850 60.7 44.2 6.12 9.9 81.6 12.6
120
8.5 0.9 2.1 1590 52.0 38.1 7.45 7.0 77.4 17.68.5 0.9 2.1 1850 52.9 41.0 7.72 6.8 79.2 18.0
12.8 2.7 6.2 1590 54.2 39.0 6.91 7.8 77.8 15.812.8 2.7 6.2 1850 55.2 41.9 7.16 7.7 79.6 16.117.0 5.0 11.5 1590 55.5 39.4 6.65 8.3 78.2 14.917.0 5.0 11.5 1850 56.4 42.4 6.90 8.2 80.0 15.2
Interpolation is permissible; extrapolation is not. Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. See performance correction tables for operating conditions other than those listed above.Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. For operation in the shaded areas, please see the Performance Data Selection Notes.All performance is based upon the lower voltage of dual voltage rated units.
49
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Performance Data — Tranquility® 20 Model 018 - PSC Blower
Operation not recommended
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
205.5 3.9 9.0
Operation not recommended450 12.2 1.36 7.8 95.0 2.6 1.4
5.5 3.9 9.0 600 12.5 1.24 8.3 89.3 2.9 1.5
30
2.8 0.7 1.6 450 20.7 16.8 0.78 23.3 26.6 0.6 450 13.7 1.40 9.2 98.1 2.9 1.72.8 0.7 1.6 600 21.5 14.0 0.80 24.3 26.8 0.6 600 14.0 1.28 9.7 91.7 3.2 1.74.1 2.1 4.9 450 21.0 16.8 0.74 23.5 28.4 0.5 450 14.2 1.41 9.6 99.3 2.9 1.84.1 2.1 4.9 600 21.8 14.1 0.76 24.4 28.6 0.6 600 14.6 1.29 10.2 92.5 3.3 1.85.5 3.5 8.1 450 21.2 16.8 0.72 23.6 29.3 0.5 450 14.5 1.42 9.9 99.9 3.0 1.85.5 3.5 8.1 600 22.0 14.1 0.75 24.6 29.6 0.5 600 14.9 1.30 10.5 93.0 3.4 1.9
40
2.8 0.6 1.4 450 20.8 17.2 0.85 23.7 24.5 0.9 450 15.8 1.44 11.1 102.6 3.2 1.92.8 0.6 1.4 600 21.7 14.4 0.88 24.6 24.7 1.0 600 16.3 1.32 11.8 95.1 3.6 2.04.1 2.0 4.6 450 21.0 17.2 0.81 23.7 26.0 0.9 450 16.5 1.45 11.7 103.9 3.3 2.04.1 2.0 4.6 600 21.8 14.4 0.83 24.7 26.2 0.9 600 16.9 1.33 12.4 96.1 3.7 2.15.5 3.2 7.4 450 21.2 17.3 0.79 23.9 26.9 0.8 450 16.8 1.46 12.0 104.7 3.4 2.15.5 3.2 7.4 600 22.1 14.5 0.81 24.8 27.1 0.8 600 17.3 1.33 12.8 96.7 3.8 2.1
50
2.8 0.5 1.2 450 20.6 17.3 0.95 23.9 21.8 1.5 450 18.0 1.47 13.1 107.0 3.6 2.22.8 0.5 1.2 600 21.5 14.5 0.98 24.8 22.0 1.5 600 18.5 1.35 13.9 98.5 4.0 2.34.1 1.7 3.9 450 21.0 17.5 0.89 24.0 23.5 1.3 450 18.7 1.48 13.8 108.6 3.7 2.34.1 1.7 3.9 600 21.8 14.6 0.92 25.0 23.7 1.4 600 19.2 1.35 14.6 99.7 4.2 2.45.5 2.8 6.5 450 21.1 17.5 0.86 24.0 24.4 1.2 450 19.2 1.49 14.2 109.4 3.8 2.45.5 2.8 6.5 600 21.9 14.6 0.89 25.0 24.6 1.3 600 19.7 1.36 15.1 100.4 4.2 2.4
60
2.8 0.3 0.7 450 19.9 16.8 1.05 23.5 18.9 2.0 450 20.1 1.50 15.1 111.4 3.9 2.52.8 0.3 0.7 600 20.7 14.1 1.09 24.4 19.1 2.1 600 20.7 1.37 16.0 101.9 4.4 2.64.1 1.5 3.5 450 20.4 17.2 0.99 23.7 20.6 1.8 450 21.0 1.51 15.9 113.3 4.1 2.64.1 1.5 3.5 600 21.2 14.3 1.02 24.7 20.8 1.9 600 21.6 1.38 16.9 103.3 4.6 2.65.5 2.6 6.0 450 20.6 17.3 0.96 23.8 21.5 1.6 450 21.5 1.52 16.4 114.3 4.1 2.75.5 2.6 6.0 600 21.4 14.4 0.99 24.8 21.7 1.7 600 22.1 1.39 17.4 104.1 4.7 2.7
70
2.8 0.3 0.7 450 18.9 16.2 1.17 22.9 16.1 2.7 450 22.3 1.54 17.1 115.9 4.3 2.82.8 0.3 0.7 600 19.7 13.5 1.21 23.8 16.2 2.8 600 22.9 1.40 18.1 105.4 4.8 2.84.1 1.4 3.2 450 19.5 16.6 1.10 23.2 17.7 2.4 450 23.4 1.56 18.0 118.1 4.4 2.94.1 1.4 3.2 600 20.3 13.8 1.14 24.2 17.9 2.5 600 24.0 1.43 19.1 107.0 4.9 2.95.5 2.4 5.5 450 19.8 16.8 1.07 23.4 18.6 2.1 450 23.9 1.57 18.5 119.3 4.5 3.05.5 2.4 5.5 600 20.6 14.0 1.10 24.3 18.7 2.2 600 24.6 1.44 19.7 107.9 5.0 3.1
80
2.8 0.2 0.5 450 17.7 15.4 1.31 22.2 13.6 3.2 450 24.6 1.59 19.1 120.6 4.5 3.02.8 0.2 0.5 600 18.5 12.9 1.35 23.1 13.7 3.3 600 25.2 1.46 20.3 108.9 5.1 3.14.1 1.2 2.8 450 18.4 15.9 1.23 22.6 15.0 3.0 450 25.8 1.63 20.2 123.1 4.6 3.14.1 1.2 2.8 600 19.2 13.2 1.27 23.5 15.1 3.1 600 26.5 1.49 21.4 110.9 5.2 3.25.5 2.2 5.1 450 18.7 16.1 1.19 22.8 15.7 2.7 450 26.5 1.66 20.7 124.5 4.7 3.25.5 2.2 5.1 600 19.5 13.4 1.23 23.7 15.9 2.9 600 27.2 1.52 22.0 111.9 5.3 3.3
85
2.8 0.2 0.5 450 17.1 15.0 1.39 21.9 12.4 3.6 450 25.8 1.63 20.1 123.0 4.6 3.12.8 0.2 0.5 600 17.8 12.6 1.43 22.7 12.5 3.7 600 26.4 1.49 21.3 110.8 5.2 3.24.1 1.2 2.7 450 17.8 15.5 1.30 22.2 13.7 3.3 450 27.1 1.69 21.2 125.7 4.7 3.34.1 1.2 2.7 600 18.5 12.9 1.35 23.1 13.8 3.5 600 27.8 1.54 22.5 112.9 5.3 3.35.5 2.1 4.9 450 18.1 15.7 1.26 22.4 14.4 3.1 450 27.8 1.72 21.8 127.2 4.7 3.45.5 2.1 4.9 600 18.9 13.1 1.30 23.3 14.6 3.2 600 28.6 1.58 23.2 114.1 5.3 3.5
90
2.8 0.2 0.5 450 16.5 14.7 1.46 21.5 11.3 4.1 450 26.9 1.68 21.1 125.4 4.7 3.32.8 0.2 0.5 600 17.2 12.3 1.51 22.4 11.4 4.3 600 27.7 1.53 22.4 112.7 5.3 3.44.1 1.1 2.5 450 17.2 15.1 1.38 21.9 12.5 3.8 450 28.4 1.74 22.3 128.3 4.8 3.44.1 1.1 2.5 600 17.9 12.6 1.42 22.8 12.6 3.9 600 29.1 1.60 23.6 114.9 5.3 3.55.5 2.0 4.6 450 17.5 15.3 1.33 22.1 13.1 3.5 450 29.1 1.79 22.9 130.0 4.8 3.55.5 2.0 4.6 600 18.3 12.8 1.38 23.0 13.2 3.6 600 29.9 1.63 24.3 116.2 5.4 3.6
100
2.8 0.2 0.5 450 15.2 14.0 1.64 20.8 9.3 4.5 680
Operation not recommended
2.8 0.2 0.5 600 15.9 11.7 1.69 21.7 9.4 4.6 9504.1 1.1 2.5 450 15.9 14.3 1.54 21.2 10.3 4.3 6804.1 1.1 2.5 600 16.6 12.0 1.59 22.0 10.4 4.4 9505.5 1.9 4.4 450 16.3 14.5 1.50 21.4 10.9 4.2 6805.5 1.9 4.4 600 16.9 12.1 1.55 22.2 10.9 4.3 950
110
2.8 0.1 0.2 450 14.0 13.4 1.84 20.3 7.6 5.3 6802.8 0.1 0.2 600 14.6 11.2 1.90 21.1 7.7 5.4 9504.1 0.9 2.1 450 14.6 13.7 1.73 20.5 8.4 5.2 6804.1 0.9 2.1 600 15.2 11.4 1.79 21.4 8.5 5.3 9505.5 1.7 3.9 450 15.0 13.8 1.68 20.7 8.9 5.0 6805.5 1.7 3.9 600 15.6 11.6 1.74 21.5 9.0 5.1 950
120
2.8 0.1 0.2 450 12.9 13.1 2.06 19.9 6.2 6.3 6802.8 0.1 0.2 600 13.4 10.9 2.13 20.7 6.3 6.4 9504.1 0.8 1.8 450 13.4 13.2 1.94 20.1 6.9 6.1 6804.1 0.8 1.8 600 14.0 11.0 2.01 20.8 7.0 6.2 9505.5 1.6 3.7 450 13.7 13.3 1.89 20.2 7.3 5.9 6805.5 1.6 3.7 600 14.3 11.1 1.95 21.0 7.3 6.0 950
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
Performance capacities shown in thousands of Btuh600 CFM Nominal (Rated) Airfl ow Cooling, 600 CFM Nominal (Rated) Airfl ow Heating
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
50 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Performance Data — Tranquility® 20 Model 018 - ECM Blower
Operation not recommended
Operation not recommended
EWT°F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFM TC SC kW HR EER HWCAirfl ow
CFM HC kW HE LAT COP HWC
205.5 3.9 9.0
Operation not recommended550 11.9 1.25 7.9 90.0 2.8 1.4
5.5 3.9 9.0 750 12.3 1.16 8.4 85.1 3.1 1.5
30
2.8 0.7 1.6 550 20.3 12.4 0.75 22.8 27.3 0.6 550 13.2 1.29 9.0 92.3 3.0 1.72.8 0.7 1.6 750 21.1 14.5 0.79 23.8 26.8 0.6 750 13.6 1.20 9.6 86.8 3.3 1.74.1 2.1 4.9 550 20.7 12.6 0.71 23.1 29.1 0.5 550 13.7 1.31 9.5 93.1 3.1 1.84.1 2.1 4.9 750 21.5 14.7 0.75 24.1 28.6 0.6 750 14.1 1.21 10.1 87.5 3.4 1.85.5 3.5 8.1 550 21.3 12.9 0.70 23.6 30.5 0.5 550 14.0 1.31 9.7 93.6 3.1 1.85.5 3.5 8.1 750 22.1 15.0 0.74 24.6 30.0 0.5 750 14.4 1.21 10.3 87.8 3.5 1.9
40
2.8 0.6 1.4 550 20.8 12.9 0.81 23.5 25.5 0.9 550 15.3 1.33 10.9 95.8 3.4 1.92.8 0.6 1.4 750 21.6 15.0 0.86 24.5 25.1 1.0 750 15.8 1.23 11.6 89.5 3.8 2.04.1 2 4.6 550 21.3 13.1 0.77 23.9 27.6 0.9 550 16.0 1.34 11.5 96.9 3.5 2.04.1 2 4.6 750 22.1 15.2 0.81 24.9 27.2 0.9 750 16.5 1.24 12.3 90.3 3.9 2.15.5 3.2 7.4 550 21.5 13.2 0.75 24.0 28.6 0.8 550 16.3 1.34 11.9 97.5 3.6 2.15.5 3.2 7.4 750 22.4 15.3 0.79 25.1 28.1 0.8 750 16.8 1.24 12.6 90.8 4.0 2.1
50
2.8 0.5 1.2 550 21.3 13.5 0.90 24.3 23.7 1.5 550 17.5 1.35 13.0 99.5 3.8 2.22.8 0.5 1.2 750 22.1 15.7 0.95 25.3 23.3 1.5 750 18.1 1.25 13.8 92.3 4.2 2.34.1 1.7 3.9 550 21.5 13.5 0.84 24.3 25.5 1.3 550 18.4 1.36 13.8 100.9 4.0 2.34.1 1.7 3.9 750 22.3 15.7 0.89 25.4 25.1 1.4 750 18.9 1.26 14.6 93.4 4.4 2.45.5 2.8 6.5 550 21.6 13.5 0.82 24.4 26.4 1.2 550 18.8 1.36 14.2 101.7 4.0 2.45.5 2.8 6.5 750 22.5 15.7 0.87 25.4 26.0 1.3 750 19.4 1.26 15.1 93.9 4.5 2.4
60
2.8 0.3 0.7 550 20.6 13.6 0.99 24.0 20.8 2.0 550 19.8 1.37 15.2 103.4 4.2 2.52.8 0.3 0.7 750 21.5 15.8 1.05 25.0 20.4 2.1 750 20.4 1.27 16.1 95.2 4.7 2.64.1 1.5 3.5 550 21.1 13.6 0.93 24.3 22.7 1.8 550 20.8 1.38 16.1 105.0 4.4 2.64.1 1.5 3.5 750 22.0 15.9 0.99 25.3 22.3 1.9 750 21.4 1.28 17.1 96.5 4.9 2.65.5 2.6 6.0 550 21.3 13.6 0.90 24.4 23.6 1.6 550 21.3 1.39 16.6 105.9 4.5 2.75.5 2.6 6.0 750 22.2 15.9 0.96 25.4 23.2 1.7 750 22.0 1.28 17.6 97.1 5.0 2.7
70
2.8 0.3 0.7 550 19.6 13.4 1.11 23.4 17.7 2.7 550 22.1 1.40 17.3 107.2 4.6 2.82.8 0.3 0.7 750 20.4 15.6 1.17 24.4 17.4 2.8 750 22.8 1.29 18.4 98.2 5.2 2.84.1 1.4 3.2 550 20.3 13.5 1.04 23.8 19.5 2.4 550 23.2 1.42 18.3 109.0 4.8 2.94.1 1.4 3.2 750 21.1 15.7 1.10 24.8 19.2 2.5 750 23.9 1.31 19.4 99.5 5.3 2.95.5 2.4 5.5 550 20.6 13.6 1.00 24.0 20.5 2.1 550 23.8 1.43 18.8 110.0 4.9 3.05.5 2.4 5.5 750 21.4 15.8 1.06 25.0 20.1 2.2 750 24.5 1.32 20.0 100.2 5.4 3.1
80
2.8 0.2 0.5 550 18.4 13.1 1.24 22.7 14.8 3.2 550 24.3 1.45 19.3 111.0 4.9 3.02.8 0.2 0.5 750 19.2 15.2 1.31 23.6 14.6 3.3 750 25.1 1.34 20.5 101.0 5.5 3.14.1 1.2 2.8 550 19.1 13.3 1.16 23.1 16.5 3.0 550 25.5 1.49 20.3 112.9 5.0 3.14.1 1.2 2.8 750 19.9 15.4 1.23 24.1 16.2 3.1 750 26.3 1.38 21.5 102.4 5.6 3.25.5 2.2 5.1 550 19.5 13.4 1.12 23.3 17.3 2.7 550 26.0 1.52 20.7 113.8 5.0 3.25.5 2.2 5.1 750 20.3 15.5 1.19 24.3 17.0 2.9 750 26.8 1.40 22.0 103.1 5.6 3.3
85
2.8 0.2 0.5 550 17.8 12.9 1.32 22.3 13.5 3.6 550 25.4 1.49 20.2 112.7 5.0 3.12.8 0.2 0.5 750 18.5 15.0 1.40 23.3 13.3 3.7 750 26.2 1.38 21.4 102.3 5.6 3.24.1 1.15 2.7 550 18.5 13.1 1.24 22.7 15.1 3.3 550 26.5 1.55 21.1 114.6 5.0 3.34.1 1.15 2.7 750 19.2 15.2 1.31 23.7 14.8 3.5 750 27.3 1.43 22.4 103.7 5.6 3.35.5 2.1 4.9 550 18.9 13.2 1.20 22.9 15.9 3.1 550 27.0 1.59 21.5 115.5 5.0 3.45.5 2.1 4.9 750 19.6 15.3 1.26 23.9 15.6 3.2 750 27.9 1.47 22.8 104.4 5.6 3.5
90
2.8 0.2 0.5 550 17.2 12.7 1.40 21.9 12.3 4.1 550 26.4 1.54 21.0 114.5 5.0 3.32.8 0.2 0.5 750 17.8 14.8 1.48 22.9 12.1 4.3 750 27.2 1.42 22.4 103.6 5.6 3.44.1 1.1 2.5 550 17.9 12.9 1.31 22.3 13.7 3.8 550 27.5 1.61 21.9 116.3 5.0 3.44.1 1.1 2.5 750 18.6 15.0 1.38 23.3 13.4 3.9 750 28.4 1.49 23.2 105.0 5.6 3.55.5 2 4.6 550 18.2 13.0 1.27 22.6 14.4 3.5 550 28.0 1.66 22.3 117.2 5.0 3.55.5 2 4.6 750 19.0 15.2 1.34 23.5 14.2 3.6 750 28.9 1.53 23.6 105.7 5.5 3.6
100
2.8 0.2 0.5 550 15.9 12.3 1.58 21.3 10.1 4.5
Operation not recommended
2.8 0.2 0.5 750 16.5 14.3 1.67 22.2 9.9 4.64.1 1.1 2.5 550 16.6 12.5 1.48 21.6 11.2 4.34.1 1.1 2.5 750 17.2 14.6 1.56 22.6 11.0 4.45.5 1.9 4.4 550 16.9 12.6 1.43 21.8 11.8 4.25.5 1.9 4.4 750 17.6 14.7 1.51 22.8 11.6 4.3
110
2.8 0.1 0.2 550 14.7 12.0 1.79 20.9 8.3 5.32.8 0.1 0.2 750 15.3 13.9 1.89 21.8 8.1 5.44.1 0.9 2.1 550 15.3 12.1 1.67 21.1 9.2 5.24.1 0.9 2.1 750 15.9 14.1 1.77 22.0 9.0 5.35.5 1.7 3.9 550 15.6 12.2 1.62 21.2 9.7 5.05.5 1.7 3.9 750 16.3 14.2 1.71 22.1 9.5 5.1
120
2.8 0.1 0.2 550 13.8 11.5 2.03 20.8 6.8 6.32.8 0.1 0.2 750 14.4 13.4 2.14 21.7 6.7 6.44.1 0.8 1.8 550 14.3 11.8 1.90 20.8 7.5 6.14.1 0.8 1.8 750 14.8 13.7 2.01 21.7 7.4 6.25.5 1.6 3.7 750 15.1 13.9 1.94 21.7 7.8 5.95.5 1.6 3.7 550 14.5 11.9 1.83 20.8 7.9 6.0
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
Performance capacities shown in thousands of Btuh750 CFM Nominal (Rated) Airfl ow Cooling, 750 CFM Nominal (Rated) Airfl ow Heating
51
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Performance Data — Tranquility® 20 Model 024 - PSC Blower
Performance capacities shown in thousands of Btuh950 CFM Nominal (Rated) Airfl ow Cooling, 950 CFM Nominal (Rated) Airfl ow Heating
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
206.0 1.9 4.4 Operation not recommended 680 15.7 1.69 10.7 91.4 2.7 1.76.0 1.9 4.4 950 16.4 1.50 11.3 86.0 3.2 1.5
30
3.0 0.9 2.1 680 28.1 16.5 0.89 32.0 31.5 0.8 680 17.4 1.69 12.3 93.7 3.0 2.03.0 0.9 2.1 950 30.4 19.4 0.94 33.6 32.4 0.8 950 18.2 1.50 13.1 87.8 3.6 1.84.5 1.2 2.7 680 27.5 15.6 0.83 31.0 33.2 0.7 680 18.3 1.70 13.2 94.9 3.2 2.14.5 1.2 2.7 950 29.7 18.3 0.87 32.7 34.1 0.7 950 19.1 1.51 14.0 88.6 3.7 1.96.0 1.7 4.0 680 26.9 14.9 0.80 30.3 33.7 0.6 680 18.8 1.70 13.6 95.6 3.2 2.16.0 1.7 4.0 950 29.1 17.6 0.84 31.9 34.6 0.6 950 19.6 1.51 14.5 89.1 3.8 1.9
40
3.0 0.7 1.5 680 28.1 17.1 1.00 32.3 28.2 1.0 680 20.2 1.71 15.0 97.5 3.5 2.43.0 0.7 1.5 950 30.4 20.2 1.05 34.0 29.0 1.1 950 21.1 1.52 15.9 90.6 4.1 2.14.5 1.0 2.4 680 28.2 16.7 0.92 32.1 30.6 0.9 680 21.2 1.71 16.0 98.9 3.6 2.64.5 1.0 2.4 950 30.5 19.7 0.97 33.8 31.5 0.9 950 22.2 1.52 17.0 91.6 4.3 2.36.0 1.6 3.6 680 28.1 16.4 0.88 31.9 31.7 0.8 680 21.8 1.71 16.6 99.7 3.7 2.66.0 1.6 3.6 950 30.4 19.3 0.93 33.5 32.6 0.8 950 22.8 1.52 17.6 92.2 4.4 2.3
50
3.0 0.5 1.2 680 27.4 17.2 1.10 31.9 24.8 1.4 680 22.9 1.72 17.7 101.2 3.9 2.83.0 0.5 1.2 950 29.6 20.2 1.16 33.6 25.5 1.5 950 24.0 1.53 18.8 93.4 4.6 2.54.5 0.9 2.1 680 28.0 17.2 1.02 32.3 27.5 1.1 680 24.2 1.73 18.9 102.9 4.1 2.94.5 0.9 2.1 950 30.3 20.2 1.07 34.0 28.3 1.2 950 25.3 1.54 20.0 94.6 4.8 2.66.0 1.5 3.3 680 28.2 17.1 0.98 32.3 28.8 1.0 680 24.9 1.73 19.5 103.9 4.2 3.06.0 1.5 3.3 950 30.5 20.1 1.03 34.0 29.6 1.1 950 26.0 1.54 20.7 95.3 4.9 2.7
60
3.0 0.4 0.9 680 26.2 16.8 1.23 31.0 21.3 1.8 680 25.7 1.74 20.4 105.0 4.3 3.13.0 0.4 0.9 950 28.3 19.7 1.29 32.7 21.9 1.9 950 26.9 1.55 21.6 96.2 5.1 2.84.5 0.8 1.8 680 27.1 17.1 1.13 31.7 24.0 1.5 680 27.2 1.75 21.7 107.0 4.5 3.44.5 0.8 1.8 950 29.3 20.1 1.19 33.4 24.6 1.6 950 28.4 1.56 23.1 97.7 5.3 3.06.0 1.4 3.1 680 27.5 17.2 1.09 32.0 25.2 1.3 680 28.0 1.75 22.5 108.1 4.7 3.56.0 1.4 3.1 950 29.8 20.2 1.15 33.7 25.9 1.4 950 29.2 1.56 23.9 98.5 5.5 3.1
70
3.0 0.3 0.6 680 24.6 16.1 1.36 29.9 18.1 2.3 680 28.6 1.76 23.1 108.9 4.7 3.63.0 0.3 0.6 950 26.6 19.0 1.43 31.5 18.6 2.4 950 29.8 1.57 24.5 99.1 5.6 3.24.5 0.7 1.7 680 25.7 16.6 1.26 30.7 20.4 1.9 680 30.2 1.79 24.7 111.2 5.0 3.84.5 0.7 1.7 950 27.8 19.5 1.33 32.4 20.9 2.0 950 31.6 1.59 26.2 100.8 5.8 3.46.0 1.3 2.9 680 26.3 16.8 1.22 31.1 21.6 1.8 680 31.2 1.80 25.5 112.4 5.1 3.96.0 1.3 2.9 950 28.4 19.8 1.28 32.8 22.2 1.9 950 32.6 1.60 27.1 101.7 6.0 3.5
80
3.0 0.2 0.5 680 22.8 15.3 1.51 28.6 15.1 2.9 680 31.4 1.80 25.8 112.8 5.1 3.93.0 0.2 0.5 950 24.7 18.1 1.59 30.1 15.5 3.0 950 32.9 1.60 27.4 102.0 6.0 3.54.5 0.7 1.5 680 24.0 15.9 1.41 29.5 17.1 2.5 680 33.4 1.83 27.6 115.5 5.3 4.24.5 0.7 1.5 950 26.0 18.7 1.48 31.0 17.6 2.6 950 34.9 1.63 29.3 104.0 6.3 3.76.0 1.2 2.7 680 24.7 16.2 1.36 30.0 18.1 2.3 680 34.5 1.85 28.6 116.9 5.4 4.36.0 1.2 2.7 950 26.7 19.0 1.43 31.5 18.6 2.4 950 36.0 1.65 30.4 105.1 6.4 3.8
85
3.0 0.2 0.4 680 21.9 14.9 1.6 27.9 13.8 3.2 680 32.9 1.83 27.2 114.9 5.3 4.13.0 0.2 0.4 950 23.7 17.6 1.68 29.4 14.2 3.4 950 34.4 1.6 28.9 103.5 6.2 3.74.5 0.6 1.5 680 23.1 15.5 1.49 28.8 15.6 2.8 680 35.0 1.9 29.1 117.7 5.5 4.34.5 0.6 1.5 950 25.0 18.2 1.57 30.3 16.0 2.9 950 36.6 1.7 30.9 105.7 6.5 3.96.0 1.1 2.6 680 23.7 15.8 1.44 29.3 16.6 2.6 680 36.2 1.9 30.2 119.3 5.6 4.46.0 1.1 2.6 950 25.7 18.5 1.51 30.8 17.1 2.7 950 37.8 1.7 32.1 106.9 6.6 4.0
90
3.0 0.1 0.3 680 21.0 14.5 1.68 27.3 12.4 3.5 680 34.4 1.85 28.6 116.9 5.4 4.33.0 0.1 0.3 950 22.7 17.1 1.77 28.7 12.8 3.7 950 36.0 1.65 30.4 105.1 6.4 3.84.5 0.6 1.4 680 22.2 15.1 1.57 28.1 14.1 3.0 680 36.6 1.90 30.6 119.9 5.7 4.54.5 0.6 1.4 950 24.0 17.7 1.65 29.6 14.5 3.2 950 38.3 1.69 32.5 107.3 6.6 4.06.0 1.1 2.5 680 22.8 15.4 1.51 28.6 15.1 2.9 680 37.9 1.92 31.8 121.6 5.8 4.66.0 1.1 2.5 950 24.7 18.1 1.59 30.1 15.5 3.0 950 39.6 1.71 33.8 108.6 6.8 4.1
100
3.0 0.1 0.2 680 19.1 13.8 1.88 26.1 10.2 4.2
Operation not recommended
3.0 0.1 0.2 950 20.7 16.2 1.98 27.4 10.5 4.44.5 0.5 1.2 680 20.3 14.2 1.76 26.8 11.5 3.74.5 0.5 1.2 950 21.9 16.7 1.85 28.2 11.8 3.96.0 1.0 2.2 680 20.9 14.5 1.69 27.2 12.3 3.56.0 1.0 2.2 950 22.6 17.1 1.78 28.6 12.7 3.7
110
3.0 0.0 0.1 680 17.5 13.2 2.10 25.1 8.3 5.03.0 0.0 0.1 950 18.9 15.5 2.21 26.5 8.6 5.34.5 0.5 1.0 680 18.5 13.5 1.97 25.7 9.4 4.64.5 0.5 1.0 950 20.0 15.9 2.07 27.0 9.6 4.86.0 0.8 1.9 680 19.0 13.7 1.90 26.0 10.0 4.36.0 0.8 1.9 950 20.5 16.1 2.00 27.3 10.3 4.5
120
3.0 0.0 0.0 680 16.2 12.9 2.36 24.7 6.9 6.03.0 0.0 0.0 950 17.5 15.1 2.48 26.0 7.1 6.34.5 0.3 0.8 680 16.9 13.0 2.21 24.9 7.7 5.44.5 0.3 0.8 950 18.3 15.3 2.32 26.2 7.9 5.76.0 0.6 1.5 680 17.3 13.1 2.13 25.1 8.1 5.16.0 0.6 1.5 950 18.7 15.4 2.24 26.4 8.4 5.4
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
52 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Performance Data — Tranquility® 20 Model 024 - ECM Blower
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
Performance capacities shown in thousands of Btuh950 CFM Nominal (Rated) Airfl ow Cooling, 950 CFM Nominal (Rated) Airfl ow Heating
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
206.0 1.9 4.4 680
Operation not recommended680 15.4 1.64 10.4 90.9 2.7 1.7
6.0 1.9 4.4 950 950 16.1 1.46 11.1 85.7 3.2 1.5
30
3.0 0.9 2.1 680 28.1 16.5 0.87 31.8 32.5 0.8 680 17.1 1.65 12.1 93.3 3.0 2.03.0 0.9 2.1 950 30.4 19.4 0.91 33.5 33.4 0.8 950 17.8 1.47 12.8 87.4 3.6 1.84.5 1.2 2.7 680 27.5 15.6 0.80 30.9 34.4 0.7 680 17.9 1.65 12.9 94.4 3.2 2.14.5 1.2 2.7 950 29.7 18.3 0.84 32.5 35.3 0.7 950 18.7 1.47 13.7 88.2 3.7 1.96.0 1.7 4.0 680 26.9 14.9 0.77 30.2 34.9 0.6 680 18.4 1.65 13.3 95.0 3.3 2.16.0 1.7 4.0 950 29.1 17.6 0.81 31.8 35.9 0.6 950 19.2 1.47 14.2 88.7 3.8 1.9
40
3.0 0.7 1.5 680 28.1 17.1 0.96 32.2 29.3 1.0 680 19.8 1.66 14.7 96.9 3.5 2.43.0 0.7 1.5 950 30.4 20.2 1.01 33.9 30.1 1.1 950 20.7 1.48 15.6 90.1 4.1 2.14.5 1.0 2.4 680 28.2 16.7 0.88 32.0 31.9 0.9 680 20.8 1.66 15.7 98.3 3.7 2.64.5 1.0 2.4 950 30.5 19.7 0.93 33.7 32.8 0.9 950 21.7 1.48 16.7 91.2 4.3 2.36.0 1.6 3.6 680 28.1 16.4 0.86 31.7 32.8 0.8 680 21.3 1.67 16.2 99.0 3.7 2.66.0 1.6 3.6 950 30.4 19.3 0.90 33.4 33.7 0.8 950 22.3 1.49 17.2 91.7 4.4 2.3
50
3.0 0.5 1.2 680 27.4 17.2 1.07 31.8 25.5 1.4 680 22.5 1.67 17.3 100.6 3.9 2.83.0 0.5 1.2 950 29.6 20.2 1.13 33.5 26.2 1.5 950 23.5 1.49 18.4 92.9 4.6 2.54.5 0.9 2.1 680 28.0 17.2 0.99 32.2 28.3 1.1 680 23.7 1.69 18.5 102.2 4.1 2.94.5 0.9 2.1 950 30.3 20.2 1.04 33.8 29.1 1.2 950 24.7 1.50 19.6 94.1 4.8 2.66.0 1.5 3.3 680 28.2 17.1 0.95 32.2 29.6 1.0 680 24.3 1.69 19.1 103.1 4.2 3.06.0 1.5 3.3 950 30.5 20.1 1.00 33.9 30.5 1.1 950 25.4 1.50 20.3 94.8 5.0 2.7
60
3.0 0.4 0.9 680 26.2 16.8 1.20 30.9 21.8 1.8 680 25.2 1.70 20.0 104.3 4.4 3.13.0 0.4 0.9 950 28.3 19.7 1.26 32.6 22.5 1.9 950 26.4 1.51 21.2 95.7 5.1 2.84.5 0.8 1.8 680 27.1 17.1 1.10 31.6 24.6 1.5 680 26.6 1.71 21.3 106.2 4.6 3.44.5 0.8 1.8 950 29.3 20.1 1.16 33.3 25.3 1.6 950 27.8 1.52 22.6 97.1 5.4 3.06.0 1.4 3.1 680 27.5 17.2 1.06 31.9 26.1 1.3 680 27.4 1.72 22.0 107.3 4.7 3.56.0 1.4 3.1 950 29.8 20.2 1.11 33.6 26.8 1.4 950 28.6 1.53 23.4 97.9 5.5 3.1
70
3.0 0.3 0.6 680 24.6 16.1 1.33 29.8 18.5 2.3 680 28.0 1.72 22.6 108.1 4.8 3.63.0 0.3 0.6 950 26.6 19.0 1.40 31.4 19.0 2.4 950 29.3 1.53 24.0 98.5 5.6 3.24.5 0.7 1.7 680 25.8 16.6 1.23 30.6 21.0 1.9 680 29.6 1.74 24.2 110.3 5.0 3.84.5 0.7 1.7 950 27.8 19.5 1.29 32.3 21.6 2.0 950 31.0 1.55 25.7 100.2 5.9 3.46.0 1.3 2.9 680 26.3 16.8 1.18 31.0 22.3 1.8 680 30.5 1.75 25.0 111.6 5.1 3.96.0 1.3 2.9 950 28.4 19.8 1.24 32.7 22.9 1.9 950 31.9 1.56 26.6 101.1 6.0 3.5
80
3.0 0.2 0.5 680 22.8 15.4 1.48 28.5 15.4 2.9 680 30.9 1.76 25.3 112.0 5.1 3.93.0 0.2 0.5 950 24.7 18.1 1.56 30.0 15.8 3.0 950 32.2 1.57 26.9 101.4 6.0 3.54.5 0.7 1.5 680 24.1 15.9 1.38 29.4 17.4 2.5 680 32.7 1.80 27.1 114.6 5.3 4.24.5 0.7 1.5 950 26.0 18.7 1.45 30.9 17.9 2.6 950 34.2 1.60 28.8 103.3 6.3 3.76.0 1.2 2.7 680 24.7 16.2 1.32 29.8 18.7 2.3 680 33.8 1.81 28.1 116.0 5.5 4.36.0 1.2 2.7 950 26.7 19.0 1.39 31.4 19.2 2.4 950 35.3 1.61 29.8 104.4 6.4 3.8
85
3.0 0.2 0.4 680 21.9 14.9 1.6 27.8 14.0 3.2 680 32.3 1.79 26.7 114.0 5.3 4.13.0 0.2 0.4 950 23.7 17.6 1.65 29.3 14.4 3.4 950 33.8 1.6 28.4 102.9 6.2 3.74.5 0.6 1.5 680 23.1 15.5 1.46 28.7 15.9 2.8 680 34.4 1.8 28.6 116.8 5.5 4.34.5 0.6 1.5 950 25.0 18.2 1.54 30.2 16.4 2.9 950 35.9 1.6 30.4 105.0 6.5 3.96.0 1.1 2.6 680 23.7 15.8 1.40 29.2 17.0 2.6 680 35.5 1.8 29.6 118.3 5.6 4.46.0 1.1 2.6 950 25.7 18.5 1.48 30.7 17.5 2.7 950 37.1 1.6 31.5 106.1 6.6 4.0
90
3.0 0.1 0.3 680 21.0 14.5 1.65 27.2 12.7 3.5 680 33.8 1.81 28.1 116.0 5.5 4.33.0 0.1 0.3 950 22.7 17.1 1.74 28.6 13.0 3.7 950 35.3 1.61 29.8 104.4 6.4 3.84.5 0.6 1.4 680 22.2 15.1 1.54 28.0 14.4 3.0 680 36.0 1.85 30.1 119.0 5.7 4.54.5 0.6 1.4 950 24.0 17.7 1.62 29.5 14.8 3.2 950 37.6 1.65 31.9 106.6 6.7 4.06.0 1.1 2.5 680 22.8 15.4 1.48 28.5 15.4 2.9 680 37.2 1.89 31.2 120.7 5.8 4.66.0 1.1 2.5 950 24.7 18.1 1.56 30.0 15.8 3.0 950 38.9 1.68 33.1 107.9 6.8 4.1
100
3.0 0.1 0.2 680 19.2 13.8 1.84 26.0 10.4 4.2 680
Operation not recommended
3.0 0.1 0.2 950 20.7 16.2 1.94 27.3 10.7 4.4 9504.5 0.5 1.2 680 20.3 14.2 1.72 26.7 11.8 3.7 6804.5 0.5 1.2 950 21.9 16.7 1.81 28.1 12.1 3.9 9506.0 1.0 2.2 680 20.9 14.5 1.66 27.1 12.5 3.5 6806.0 1.0 2.2 950 22.6 17.1 1.75 28.5 12.9 3.7 950
110
3.0 0.0 0.1 680 17.5 13.2 2.07 25.0 8.5 5.0 6803.0 0.0 0.1 950 18.9 15.5 2.18 26.4 8.7 5.3 9504.5 0.5 1.0 680 18.5 13.5 1.93 25.6 9.6 4.6 6804.5 0.5 1.0 950 20.0 15.9 2.03 26.9 9.8 4.8 9506.0 0.8 1.9 680 19.0 13.7 1.86 25.9 10.2 4.3 6806.0 0.8 1.9 950 20.5 16.1 1.96 27.2 10.5 4.5 950
120
3.0 0.0 0.0 680 16.2 12.9 2.32 24.6 7.0 6.0 6803.0 0.0 0.0 950 17.5 15.1 2.44 25.8 7.2 6.3 9504.5 0.3 0.8 680 16.9 13.0 2.17 24.8 7.8 5.4 6804.5 0.3 0.8 950 18.3 15.3 2.28 26.1 8.0 5.7 9506.0 0.6 1.5 680 17.3 13.1 2.10 25.0 8.2 5.1 6806.0 0.6 1.5 950 18.7 15.4 2.21 26.3 8.5 5.4 950
53
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Performance Data — Tranquility® 20 Model 030 - PSC Blower
Performance capacities shown in thousands of Btuh1000 CFM Nominal (Rated) Airfl ow Cooling,1000 CFM Nominal (Rated) Airfl ow Heating
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
207.5 2.7 6.2 720
Operation not recommended720 18.6 2.06 12.4 93.9 2.6 1.7
7.5 2.7 6.2 1000 1000 19.4 1.83 13.2 88.0 3.1 1.5
30
3.8 0.9 2.0 720 31.8 18.2 1.14 36.6 27.9 0.8 720 20.7 2.10 14.3 96.6 2.9 1.93.8 0.9 2.0 1000 34.4 21.4 1.20 38.5 28.7 0.8 1000 21.6 1.87 15.2 90.0 3.4 1.75.6 1.6 3.6 720 30.9 17.3 1.07 35.4 28.7 0.7 720 21.6 2.11 15.2 97.8 3.0 2.05.6 1.6 3.6 1000 33.4 20.4 1.13 37.2 29.5 0.7 1000 22.6 1.88 16.2 90.9 3.5 1.87.5 2.5 5.7 720 30.2 16.7 1.05 34.6 28.9 0.6 720 22.1 2.12 15.7 98.4 3.1 2.17.5 2.5 5.7 1000 32.6 19.7 1.10 36.4 29.7 0.6 1000 23.1 1.89 16.7 91.4 3.6 1.9
40
3.8 0.8 1.8 720 32.1 18.8 1.26 37.3 25.6 1.0 720 23.9 2.15 17.4 100.8 3.3 2.23.8 0.8 1.8 1000 34.7 22.1 1.32 39.2 26.3 1.1 1000 25.0 1.91 18.5 93.1 3.8 2.05.6 1.5 3.4 720 32.0 18.4 1.18 36.9 27.2 0.9 720 25.1 2.16 18.5 102.2 3.4 2.55.6 1.5 3.4 1000 34.6 21.7 1.24 38.9 27.9 0.9 1000 26.2 1.92 19.6 94.2 4.0 2.27.5 2.3 5.3 720 31.8 18.1 1.14 36.5 27.9 0.8 720 25.7 2.17 19.1 103.0 3.5 2.67.5 2.3 5.3 1000 34.4 21.3 1.20 38.5 28.6 0.8 1000 26.8 1.93 20.3 94.9 4.1 2.3
50
3.8 0.8 1.8 720 31.5 18.8 1.39 37.1 22.7 1.3 720 27.2 2.18 20.5 105.0 3.7 2.73.8 0.8 1.8 1000 34.0 22.1 1.46 39.0 23.3 1.4 1000 28.4 1.94 21.8 96.3 4.3 2.45.6 1.4 3.2 720 32.0 18.8 1.29 37.3 24.7 1.1 720 28.5 2.20 21.8 106.7 3.8 2.95.6 1.4 3.2 1000 34.6 22.2 1.36 39.3 25.4 1.2 1000 29.8 1.96 23.1 97.6 4.5 2.67.5 2.2 5.0 720 32.1 18.8 1.26 37.3 25.6 1.0 720 29.3 2.20 22.5 107.6 3.9 3.07.5 2.2 5.0 1000 34.7 22.1 1.32 39.2 26.3 1.0 1000 30.6 1.96 23.9 98.3 4.6 2.7
60
3.8 0.7 1.7 720 30.2 18.4 1.52 36.2 19.8 1.7 720 30.4 2.21 23.6 109.1 4.0 3.03.8 0.7 1.7 1000 32.6 21.6 1.60 38.1 20.4 1.8 1000 31.8 1.97 25.1 99.5 4.7 2.75.6 1.3 3.1 720 31.1 18.7 1.43 36.8 21.8 1.4 720 32.0 2.24 25.1 111.1 4.2 3.35.6 1.3 3.1 1000 33.7 22.0 1.50 38.8 22.4 1.5 1000 33.4 1.99 26.6 100.9 4.9 2.97.5 2.1 4.8 720 31.5 18.8 1.38 37.1 22.9 1.3 720 32.8 2.25 25.9 112.2 4.3 3.47.5 2.1 4.8 1000 34.1 22.1 1.45 39.0 23.5 1.4 1000 34.3 2.00 27.5 101.8 5.0 3.0
70
3.8 0.7 1.7 720 28.5 17.7 1.68 35.0 16.9 2.2 720 33.7 2.26 26.7 113.3 4.4 3.43.8 0.7 1.7 1000 30.8 20.9 1.77 36.8 17.4 2.3 1000 35.2 2.01 28.4 102.6 5.1 3.05.6 1.3 3.0 720 29.7 18.2 1.58 35.9 18.8 1.9 720 35.4 2.28 28.3 115.5 4.5 3.75.6 1.3 3.0 1000 32.1 21.4 1.66 37.7 19.3 2.0 1000 37.0 2.03 30.1 104.3 5.3 3.37.5 2.0 4.7 720 30.2 18.4 1.52 36.2 19.9 1.7 720 36.4 2.29 29.2 116.8 4.6 3.87.5 2.0 4.7 1000 32.7 21.7 1.60 38.1 20.4 1.8 1000 38.0 2.04 31.0 105.2 5.5 3.4
80
3.8 0.7 1.7 720 26.5 16.9 1.86 33.6 14.2 2.8 720 36.9 2.30 29.8 117.5 4.7 3.83.8 0.7 1.7 1000 28.7 19.9 1.96 35.4 14.6 2.9 1000 38.6 2.05 31.6 105.7 5.5 3.45.6 1.3 3.0 720 27.8 17.5 1.74 34.5 16.0 2.4 720 38.8 2.34 31.5 119.9 4.9 4.05.6 1.3 3.0 1000 30.1 20.5 1.83 36.3 16.4 2.5 1000 40.6 2.08 33.5 107.6 5.7 3.67.5 2.0 4.6 720 28.5 17.7 1.68 35.0 16.9 2.2 720 39.9 2.36 32.5 121.3 4.9 4.27.5 2.0 4.6 1000 30.8 20.9 1.77 36.8 17.4 2.3 1000 41.7 2.10 34.5 108.6 5.8 3.7
85
3.8 0.7 1.7 720 25.5 16.5 2.0 32.9 13.1 3.1 720 38.5 2.33 31.2 119.5 4.8 4.03.8 0.7 1.7 1000 27.6 19.4 2.07 34.6 13.4 3.3 1000 40.2 2.1 33.2 107.3 5.7 3.65.6 1.3 2.9 720 26.8 17.0 1.84 33.8 14.7 2.7 720 40.5 2.4 33.1 122.1 5.0 4.25.6 1.3 2.9 1000 29.0 20.0 1.93 35.6 15.1 2.9 1000 42.3 2.1 35.1 109.2 5.9 3.87.5 2.0 4.6 720 27.4 17.3 1.78 34.3 15.5 2.5 720 41.6 2.4 34.1 123.5 5.1 4.47.5 2.0 4.6 1000 29.7 20.4 1.87 36.1 15.9 2.7 1000 43.5 2.1 36.2 110.2 6.0 3.9
90
3.8 0.7 1.7 720 24.5 16.1 2.06 32.2 11.9 3.4 720 40.1 2.36 32.7 121.6 5.0 4.23.8 0.7 1.7 1000 26.5 18.9 2.17 33.9 12.2 3.6 1000 41.9 2.10 34.7 108.8 5.9 3.75.6 1.3 2.9 720 25.8 16.6 1.93 33.1 13.3 3.0 720 42.2 2.42 34.6 124.3 5.1 4.45.6 1.3 2.9 1000 27.9 19.5 2.03 34.8 13.7 3.2 1000 44.1 2.15 36.8 110.8 6.0 3.97.5 2.0 4.5 720 26.4 16.9 1.87 33.5 14.1 2.9 720 43.3 2.45 35.6 125.7 5.2 4.67.5 2.0 4.5 1000 28.6 19.9 1.97 35.3 14.5 3.0 1000 45.3 2.18 37.8 111.9 6.1 4.1
100
3.8 0.7 1.7 720 22.5 15.3 2.28 30.9 9.9 4.1 720
Operation not recommended
3.8 0.7 1.7 1000 24.3 18.0 2.40 32.5 10.1 4.3 10005.6 1.3 2.9 720 23.7 15.8 2.15 31.6 11.0 3.7 7205.6 1.3 2.9 1000 25.6 18.5 2.26 33.3 11.3 3.9 10007.5 1.9 4.5 720 24.3 16.0 2.08 32.0 11.7 3.5 7207.5 1.9 4.5 1000 26.3 18.8 2.19 33.7 12.0 3.7 1000
110
3.8 0.7 1.7 720 20.7 14.7 2.55 29.9 8.1 4.9 7203.8 0.7 1.7 1000 22.4 17.3 2.68 31.5 8.4 5.2 10005.6 1.2 2.8 720 21.7 15.0 2.40 30.4 9.1 4.5 7205.6 1.2 2.8 1000 23.5 17.7 2.52 32.0 9.3 4.7 10007.5 1.9 4.4 720 22.2 15.2 2.32 30.7 9.6 4.3 7207.5 1.9 4.4 1000 24.0 17.9 2.44 32.4 9.9 4.5 1000
120
3.8 0.7 1.6 720 19.3 14.4 2.84 29.5 6.8 5.9 7203.8 0.7 1.6 1000 20.9 17.0 2.99 31.1 7.0 6.2 10005.6 1.2 2.8 720 20.0 14.5 2.67 29.7 7.5 5.3 7205.6 1.2 2.8 1000 21.7 17.1 2.81 31.2 7.7 5.6 10007.5 1.9 4.3 720 20.5 14.6 2.60 29.8 7.9 5.1 7207.5 1.9 4.3 1000 22.1 17.2 2.73 31.4 8.1 5.4 1000
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
54 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Performance Data — Tranquility® 20 Model 030 - ECM Blower
Performance capacities shown in thousands of Btuh1,000 CFM Nominal (Rated) Airfl ow Cooling, 1,100 CFM Nominal (Rated) Airfl ow Heating
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
207.5 2.7 6.2 720
Operation not recommended790 18.8 2.09 12.6 92.1 2.6 1.7
7.5 2.7 6.2 1000 1100 19.7 1.86 13.3 86.6 3.1 1.5
30
3.8 0.9 2.0 720 31.8 18.2 1.10 36.4 28.8 0.8 790 20.9 2.12 14.5 94.5 2.9 1.93.8 0.9 2.0 1000 34.4 21.4 1.16 38.4 29.6 0.8 1100 21.9 1.89 15.4 88.4 3.4 1.75.6 1.6 3.6 720 30.9 17.3 1.04 35.2 29.8 0.7 790 21.9 2.15 15.4 95.7 3.0 2.05.6 1.6 3.6 1000 33.4 20.3 1.09 37.1 30.6 0.7 1100 22.9 1.91 16.4 89.3 3.5 1.87.5 2.5 5.7 720 30.2 16.7 1.01 34.4 29.9 0.6 790 22.4 2.15 15.9 96.3 3.1 2.17.5 2.5 5.7 1000 32.6 19.7 1.06 36.2 30.8 0.6 1100 23.4 1.91 16.9 89.7 3.6 1.9
40
3.8 0.8 1.8 720 32.1 18.8 1.22 37.2 26.4 1.0 790 24.2 2.18 17.6 98.4 3.3 2.23.8 0.8 1.8 1000 34.7 22.1 1.28 39.1 27.1 1.1 1100 25.3 1.94 18.7 91.3 3.8 2.05.6 1.5 3.4 720 32.0 18.4 1.14 36.8 28.1 0.9 790 25.4 2.19 18.7 99.7 3.4 2.55.6 1.5 3.4 1000 34.6 21.7 1.20 38.7 28.9 0.9 1100 26.5 1.95 19.9 92.3 4.0 2.27.5 2.3 5.3 720 31.8 18.1 1.10 36.4 28.8 0.8 790 26.0 2.20 19.3 100.5 3.5 2.67.5 2.3 5.3 1000 34.4 21.3 1.16 38.3 29.6 0.8 1100 27.2 1.96 20.5 92.9 4.1 2.3
50
3.8 0.8 1.8 720 31.5 18.8 1.35 36.9 23.3 1.3 790 27.5 2.21 20.7 102.2 3.6 2.73.8 0.8 1.8 1000 34.0 22.1 1.42 38.9 24.0 1.4 1100 28.7 1.97 22.0 94.2 4.3 2.45.6 1.4 3.2 720 32.0 18.8 1.26 37.2 25.5 1.1 790 28.9 2.23 22.1 103.8 3.8 2.95.6 1.4 3.2 1000 34.6 22.2 1.32 39.1 26.2 1.2 1100 30.2 1.98 23.4 95.4 4.5 2.67.5 2.2 5.0 720 32.1 18.8 1.22 37.1 26.4 1.0 790 29.6 2.24 22.8 104.7 3.9 3.07.5 2.2 5.0 1000 34.7 22.1 1.28 39.1 27.1 1.0 1100 31.0 1.99 24.2 96.1 4.6 2.7
60
3.8 0.7 1.7 720 30.2 18.4 1.48 36.1 20.4 1.7 790 30.8 2.25 23.9 106.1 4.0 3.03.8 0.7 1.7 1000 32.7 21.6 1.56 38.0 20.9 1.8 1100 32.2 2.00 25.4 97.1 4.7 2.75.6 1.3 3.1 720 31.1 18.7 1.39 36.7 22.4 1.4 790 32.4 2.27 25.4 107.9 4.2 3.35.6 1.3 3.1 1000 33.7 22.0 1.46 38.7 23.1 1.5 1100 33.8 2.02 26.9 98.5 4.9 2.97.5 2.1 4.8 720 31.5 18.8 1.34 36.9 23.5 1.3 790 33.2 2.27 26.2 108.9 4.3 3.47.5 2.1 4.8 1000 34.1 22.1 1.41 38.9 24.2 1.4 1100 34.7 2.02 27.8 99.2 5.0 3.0
70
3.8 0.7 1.7 720 28.5 17.7 1.65 34.9 17.3 2.2 790 34.1 2.28 27.0 109.9 4.4 3.43.8 0.7 1.7 1000 30.8 20.9 1.73 36.7 17.8 2.3 1100 35.6 2.03 28.7 100.0 5.1 3.05.6 1.3 3.0 720 29.7 18.2 1.54 35.7 19.3 1.9 790 35.8 2.30 28.7 112.0 4.6 3.75.6 1.3 3.0 1000 32.1 21.4 1.62 37.6 19.8 2.0 1100 37.4 2.05 30.4 101.5 5.4 3.37.5 2.0 4.7 720 30.2 18.4 1.48 36.1 20.4 1.7 790 36.8 2.33 29.6 113.1 4.6 3.87.5 2.0 4.7 1000 32.7 21.7 1.56 38.0 21.0 1.8 1100 38.5 2.07 31.4 102.4 5.4 3.4
80
3.8 0.7 1.7 720 26.6 16.9 1.82 33.5 14.6 2.8 790 37.3 2.33 30.1 113.8 4.7 3.83.8 0.7 1.7 1000 28.7 19.9 1.91 35.2 15.0 2.9 1100 39.0 2.07 31.9 102.8 5.5 3.45.6 1.3 3.0 720 27.8 17.5 1.70 34.4 16.4 2.4 790 39.3 2.37 31.9 116.0 4.9 4.05.6 1.3 3.0 1000 30.1 20.6 1.79 36.2 16.8 2.5 1100 41.0 2.11 33.9 104.5 5.7 3.67.5 2.0 4.6 720 28.5 17.7 1.65 34.9 17.3 2.2 790 40.3 2.39 32.9 117.3 4.9 4.27.5 2.0 4.6 1000 30.8 20.9 1.73 36.7 17.8 2.3 1100 42.1 2.13 34.9 105.5 5.8 3.7
85
3.8 0.7 1.7 720 25.5 16.5 1.9 32.8 13.4 3.1 790 38.9 2.36 31.6 115.6 4.8 4.03.8 0.7 1.7 1000 27.6 19.4 2.02 34.5 13.8 3.3 1100 40.7 2.1 33.5 104.3 5.7 3.65.6 1.3 2.9 720 26.8 17.0 1.80 33.7 15.0 2.7 790 41.0 2.4 33.4 118.0 5.0 4.25.6 1.3 2.9 1000 29.0 20.1 1.89 35.4 15.4 2.9 1100 42.8 2.1 35.5 106.0 5.9 3.87.5 2.0 4.6 720 27.5 17.3 1.74 34.1 15.9 2.5 790 42.1 2.4 34.5 119.3 5.1 4.47.5 2.0 4.6 1000 29.7 20.4 1.83 35.9 16.3 2.7 1100 44.0 2.2 36.6 107.0 5.9 3.9
90
3.8 0.7 1.7 720 24.5 16.1 2.02 32.1 12.2 3.4 790 40.6 2.39 33.1 117.5 5.0 4.23.8 0.7 1.7 1000 26.5 18.9 2.12 33.8 12.5 3.6 1100 42.4 2.13 35.1 105.7 5.8 3.75.6 1.3 2.9 720 25.8 16.6 1.89 32.9 13.6 3.0 790 42.7 2.45 35.0 120.0 5.1 4.45.6 1.3 2.9 1000 27.9 19.6 1.99 34.7 14.0 3.2 1100 44.6 2.18 37.2 107.5 6.0 3.97.5 2.0 4.5 720 26.4 16.9 1.84 33.4 14.4 2.9 790 43.8 2.48 36.0 121.3 5.2 4.67.5 2.0 4.5 1000 28.6 19.9 1.93 35.2 14.8 3.0 1100 45.8 2.21 38.2 108.5 6.1 4.1
100
3.8 0.7 1.7 720 22.5 15.3 2.24 30.8 10.0 4.1 790
Operation not recommended
3.8 0.7 1.7 1000 24.3 18.0 2.36 32.4 10.3 4.3 11005.6 1.3 2.9 720 23.7 15.8 2.11 31.5 11.2 3.7 7905.6 1.3 2.9 1000 25.6 18.5 2.22 33.2 11.5 3.9 11007.5 1.9 4.5 720 24.3 16.0 2.04 31.9 11.9 3.5 7907.5 1.9 4.5 1000 26.3 18.8 2.15 33.6 12.2 3.7 1100
110
3.8 0.7 1.7 720 20.7 14.7 2.51 29.8 8.3 4.9 7903.8 0.7 1.7 1000 22.4 17.3 2.64 31.4 8.5 5.2 11005.6 1.2 2.8 720 21.7 15.0 2.36 30.3 9.2 4.5 7905.6 1.2 2.8 1000 23.5 17.7 2.48 31.9 9.5 4.7 11007.5 1.9 4.4 720 22.2 15.2 2.28 30.6 9.7 4.3 7907.5 1.9 4.4 1000 24.1 17.9 2.40 32.2 10.0 4.5 1100
120
3.8 0.7 1.6 720 19.3 14.4 2.81 29.4 6.9 5.9 7903.8 0.7 1.6 1000 20.9 17.0 2.95 31.0 7.1 6.2 11005.6 1.2 2.8 720 20.0 14.5 2.63 29.6 7.6 5.3 7905.6 1.2 2.8 1000 21.7 17.1 2.77 31.1 7.8 5.6 11007.5 1.9 4.3 720 20.5 14.6 2.55 29.7 8.0 5.1 7907.5 1.9 4.3 1000 22.1 17.2 2.68 31.3 8.3 5.4 1100
55
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Performance Data — Tranquility® 20 Model 036 - PSC Blower
Performance capacities shown in thousands of Btuh1,200 CFM Nominal (Rated) Airfl ow Cooling, 1,200 CFM Nominal (Rated) Airfl ow Heating
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
209.0 4.3 9.9 860
Operation not recommended860 22.3 2.37 15.2 94.0 2.8 2.4
9.0 4.3 9.9 1200 1200 23.3 2.11 16.1 88.0 3.2 2.1
30
4.5 1.2 2.8 860 33.1 18.6 1.31 38.5 25.2 1.0 860 24.4 2.38 17.2 96.2 3.0 2.74.5 1.2 2.8 1200 35.8 21.9 1.38 40.5 25.9 1.0 1200 25.5 2.12 18.2 89.7 3.5 2.46.8 2.4 5.5 860 31.2 17.2 1.26 36.3 24.8 0.8 860 25.3 2.39 18.1 97.3 3.1 2.96.8 2.4 5.5 1200 33.7 20.2 1.32 38.2 25.5 0.8 1200 26.5 2.13 19.2 90.4 3.6 2.69.0 3.8 8.8 860 30.0 16.5 1.23 35.0 24.5 0.8 860 25.9 2.41 18.6 97.9 3.2 3.09.0 3.8 8.8 1200 32.5 19.4 1.29 36.9 25.2 0.8 1200 27.1 2.14 19.8 90.9 3.7 2.7
40
4.5 1.0 2.3 860 34.9 20.3 1.44 40.8 24.3 1.2 860 27.9 2.43 20.5 100.1 3.4 3.34.5 1.0 2.3 1200 37.8 23.9 1.51 42.9 25.0 1.3 1200 29.2 2.16 21.8 92.5 4.0 2.96.8 2.1 4.8 860 34.0 19.4 1.36 39.6 25.0 1.0 860 29.2 2.45 21.8 101.5 3.5 3.56.8 2.1 4.8 1200 36.8 22.8 1.43 41.6 25.7 1.1 1200 30.5 2.18 23.1 93.6 4.1 3.19.0 3.4 7.9 860 33.3 18.8 1.32 38.8 25.2 1.0 860 29.9 2.46 22.4 102.2 3.6 3.69.0 3.4 7.9 1200 36.0 22.1 1.39 40.8 25.9 1.0 1200 31.3 2.19 23.8 94.1 4.2 3.2
50
4.5 0.9 2.0 860 35.4 21.3 1.59 41.8 22.3 1.7 860 31.8 2.48 24.1 104.2 3.7 3.84.5 0.9 2.0 1200 38.3 25.0 1.67 44.0 22.9 1.8 1200 33.2 2.21 25.6 95.6 4.4 3.46.8 1.9 4.4 860 35.2 20.7 1.49 41.3 23.6 1.4 860 33.3 2.52 25.6 105.9 3.9 4.06.8 1.9 4.4 1200 38.1 24.4 1.57 43.4 24.3 1.5 1200 34.8 2.24 27.2 96.9 4.6 3.69.0 3.2 7.3 860 35.0 20.4 1.45 40.9 24.2 1.2 860 34.2 2.53 26.5 106.8 4.0 4.29.0 3.2 7.3 1200 37.8 24.0 1.52 43.0 24.9 1.3 1200 35.8 2.25 28.1 97.6 4.7 3.7
60
4.5 0.8 1.8 860 34.8 21.6 1.76 41.8 19.8 2.4 860 35.7 2.55 27.8 108.5 4.1 4.44.5 0.8 1.8 1200 37.7 25.4 1.85 44.0 20.4 2.5 1200 37.3 2.27 29.6 98.8 4.8 3.96.8 1.8 4.1 860 35.3 21.5 1.65 41.8 21.5 1.9 860 37.6 2.59 29.6 110.4 4.3 4.66.8 1.8 4.1 1200 38.2 25.2 1.73 44.1 22.1 2.0 1200 39.2 2.30 31.4 100.3 5.0 4.19.0 3.0 6.9 860 35.4 21.3 1.59 41.8 22.3 1.7 860 38.6 2.61 30.5 111.5 4.3 4.79.0 3.0 6.9 1200 38.3 25.0 1.67 44.0 22.9 1.8 1200 40.3 2.32 32.4 101.1 5.1 4.2
70
4.5 0.8 1.8 860 33.6 21.5 1.94 41.1 17.3 3.1 860 39.6 2.63 31.5 112.7 4.4 4.94.5 0.8 1.8 1200 36.3 25.3 2.04 43.3 17.8 3.3 1200 41.4 2.34 33.5 102.0 5.2 4.46.8 1.7 3.9 860 34.5 21.6 1.82 41.6 19.0 2.6 860 41.6 2.66 33.4 114.8 4.6 5.26.8 1.7 3.9 1200 37.3 25.5 1.91 43.8 19.5 2.7 1200 43.5 2.37 35.4 103.6 5.4 4.69.0 2.9 6.6 860 34.8 21.6 1.76 41.8 19.8 2.4 860 42.7 2.69 34.4 116.0 4.7 5.39.0 2.9 6.6 1200 37.6 25.4 1.85 44.0 20.3 2.5 1200 44.6 2.39 36.5 104.4 5.5 4.7
80
4.5 0.8 1.8 860 31.9 21.0 2.15 40.1 14.8 4.0 860 43.4 2.70 35.0 116.7 4.7 5.44.5 0.8 1.8 1200 34.5 24.7 2.26 42.2 15.3 4.2 1200 45.3 2.40 37.1 105.0 5.5 4.86.8 1.7 3.8 860 33.0 21.4 2.02 40.8 16.4 3.4 860 45.4 2.74 36.9 118.9 4.9 5.76.8 1.7 3.8 1200 35.7 25.1 2.12 42.9 16.8 3.6 1200 47.5 2.44 39.1 106.6 5.7 5.19.0 2.8 6.4 860 33.5 21.5 1.95 41.1 17.2 3.1 860 46.4 2.77 37.8 120.0 4.9 5.89.0 2.8 6.4 1200 36.3 25.3 2.05 43.3 17.7 3.3 1200 48.5 2.46 40.1 107.4 5.8 5.2
85
4.5 0.8 1.8 860 30.9 20.6 2.3 39.4 13.7 4.5 860 45.1 2.74 36.6 118.5 4.8 5.74.5 0.8 1.8 1200 33.4 24.2 2.38 41.5 14.1 4.7 1200 47.1 2.4 38.8 106.4 5.7 5.16.8 1.6 3.8 860 32.1 21.0 2.13 40.2 15.2 3.9 860 47.0 2.8 38.4 120.6 5.0 6.06.8 1.6 3.8 1200 34.7 24.8 2.24 42.3 15.6 4.1 1200 49.1 2.5 40.7 107.9 5.8 5.39.0 2.8 6.4 860 32.6 21.2 2.06 40.5 15.9 3.6 860 48.0 2.8 39.2 121.7 5.0 6.19.0 2.8 6.4 1200 35.3 25.0 2.17 42.7 16.4 3.8 1200 50.1 2.5 41.6 108.7 5.9 5.5
90
4.5 0.8 1.8 860 29.9 20.2 2.38 38.8 12.6 4.9 860 46.8 2.78 38.1 120.4 4.9 6.04.5 0.8 1.8 1200 32.3 23.8 2.50 40.8 12.9 5.2 1200 48.9 2.47 40.5 107.7 5.8 5.36.8 1.6 3.8 860 31.1 20.7 2.23 39.6 13.9 4.4 860 48.6 2.81 39.8 122.4 5.1 6.26.8 1.6 3.8 1200 33.7 24.4 2.35 41.7 14.3 4.6 1200 50.8 2.50 42.3 109.2 6.0 5.59.0 2.7 6.3 860 31.8 21.0 2.17 40.0 14.6 4.0 860 49.5 2.83 40.7 123.3 5.1 6.49.0 2.7 6.3 1200 34.3 24.7 2.28 42.1 15.1 4.2 1200 51.8 2.52 43.2 109.9 6.0 5.7
100
4.5 0.8 1.8 860 27.7 19.2 2.62 37.4 10.6 6.1 860
Operation not recommended
4.5 0.8 1.8 1200 30.0 22.6 2.76 39.4 10.9 6.4 12006.8 1.6 3.7 860 29.0 19.8 2.47 38.2 11.7 5.4 8606.8 1.6 3.7 1200 31.4 23.3 2.60 40.2 12.1 5.7 12009.0 2.7 6.2 860 29.7 20.1 2.40 38.6 12.4 5.0 8609.0 2.7 6.2 1200 32.1 23.7 2.52 40.7 12.7 5.3 1200
110
4.5 0.7 1.7 860 25.6 18.0 2.90 36.2 8.8 7.3 8604.5 0.7 1.7 1200 27.6 21.2 3.05 38.1 9.1 7.7 12006.8 1.6 3.6 860 26.8 18.7 2.74 36.9 9.8 6.7 8606.8 1.6 3.6 1200 29.0 22.0 2.88 38.8 10.1 7.0 12009.0 2.6 6.1 860 27.4 19.0 2.66 37.2 10.3 6.3 8609.0 2.6 6.1 1200 29.7 22.4 2.80 39.2 10.6 6.6 1200
120
4.5 0.6 1.5 860 23.6 16.9 3.20 35.2 7.4 8.7 8604.5 0.6 1.5 1200 25.5 19.9 3.37 37.0 7.6 9.2 12006.8 1.5 3.3 860 24.7 17.5 3.03 35.7 8.1 8.0 8606.8 1.5 3.3 1200 26.6 20.6 3.19 37.5 8.4 8.4 12009.0 2.5 5.8 860 25.2 17.9 2.95 36.0 8.6 7.6 8609.0 2.5 5.8 1200 27.3 21.0 3.10 37.9 8.8 8.0 1200
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
56 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Performance Data — Tranquility® 20 Model 036 - ECM Blower
Performance capacities shown in thousands of Btuh1,200 CFM Nominal (Rated) Airfl ow Cooling, 1,200 CFM Nominal (Rated) Airfl ow Heating
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
209.0 4.3 9.9 860
Operation not recommended860 21.7 2.08 15.4 93.4 3.1 2.4
9.0 4.3 9.9 1200 1200 22.7 1.85 16.3 87.5 3.6 2.1
30
4.5 1.2 2.8 860 34.1 19.3 1.08 38.7 31.5 1.0 860 23.7 2.10 17.4 95.6 3.3 2.74.5 1.2 2.8 1200 36.9 22.7 1.14 40.8 32.4 1.0 1200 24.8 1.87 18.4 89.1 3.9 2.46.8 2.4 5.5 860 32.2 17.5 1.01 36.5 31.9 0.8 860 24.7 2.11 18.3 96.6 3.4 2.96.8 2.4 5.5 1200 34.8 20.6 1.06 38.4 32.8 0.8 1200 25.8 1.88 19.4 89.9 4.0 2.69.0 3.8 8.8 860 31.0 16.5 0.98 35.2 31.7 0.8 860 25.3 2.12 18.8 97.2 3.5 3.09.0 3.8 8.8 1200 33.5 19.5 1.03 37.0 32.5 0.8 1200 26.4 1.89 20.0 90.4 4.1 2.7
40
4.5 1.0 2.3 860 36.0 21.5 1.22 41.1 29.6 1.2 860 27.3 2.15 20.7 99.4 3.7 3.34.5 1.0 2.3 1200 39.0 25.3 1.28 43.3 30.4 1.3 1200 28.5 1.91 22.0 92.0 4.4 2.96.8 2.1 4.8 860 35.1 20.3 1.13 39.9 31.0 1.0 860 28.6 2.16 21.9 100.8 3.9 3.56.8 2.1 4.8 1200 37.9 23.9 1.19 41.9 31.8 1.1 1200 29.9 1.92 23.3 93.0 4.6 3.19.0 3.4 7.9 860 34.4 19.6 1.09 39.0 31.4 1.0 860 29.3 2.17 22.6 101.5 4.0 3.69.0 3.4 7.9 1200 37.2 23.0 1.15 41.1 32.3 1.0 1200 30.6 1.93 24.0 93.6 4.6 3.2
50
4.5 0.9 2.0 860 36.5 22.7 1.37 42.1 26.6 1.7 860 31.1 2.20 24.3 103.5 4.1 3.84.5 0.9 2.0 1200 39.4 26.7 1.44 44.3 27.4 1.8 1200 32.5 1.96 25.8 95.1 4.9 3.46.8 1.9 4.4 860 36.3 22.0 1.26 41.6 28.7 1.4 860 32.7 2.23 25.8 105.2 4.3 4.06.8 1.9 4.4 1200 39.3 25.9 1.33 43.8 29.5 1.5 1200 34.1 1.98 27.4 96.3 5.1 3.69.0 3.2 7.3 860 36.1 21.6 1.22 41.2 29.6 1.2 860 33.5 2.24 26.6 106.1 4.4 4.29.0 3.2 7.3 1200 39.0 25.4 1.28 43.4 30.5 1.3 1200 35.0 1.99 28.2 97.0 5.2 3.7
60
4.5 0.8 1.8 860 35.9 23.1 1.53 42.1 23.5 2.4 860 35.0 2.26 28.0 107.7 4.5 4.44.5 0.8 1.8 1200 38.9 27.2 1.61 44.3 24.1 2.5 1200 36.6 2.01 29.7 98.2 5.3 3.96.8 1.8 4.1 860 36.4 22.9 1.42 42.2 25.7 1.9 860 36.8 2.29 29.7 109.6 4.7 4.66.8 1.8 4.1 1200 39.3 27.0 1.49 44.4 26.4 2.0 1200 38.5 2.04 31.5 99.7 5.5 4.19.0 3.0 6.9 860 36.5 22.7 1.37 42.1 26.6 1.7 860 37.8 2.32 30.6 110.7 4.8 4.79.0 3.0 6.9 1200 39.4 26.7 1.44 44.4 27.4 1.8 1200 39.5 2.06 32.5 100.5 5.6 4.2
70
4.5 0.8 1.8 860 34.7 22.9 1.72 41.5 20.1 3.1 860 38.9 2.33 31.6 111.9 4.9 4.94.5 0.8 1.8 1200 37.5 27.0 1.81 43.6 20.7 3.3 1200 40.6 2.07 33.5 101.3 5.8 4.46.8 1.7 3.9 860 35.6 23.1 1.60 42.0 22.3 2.6 860 40.9 2.37 33.5 114.0 5.0 5.26.8 1.7 3.9 1200 38.5 27.2 1.68 44.2 22.9 2.7 1200 42.7 2.11 35.5 102.9 5.9 4.69.0 2.9 6.6 860 35.9 23.1 1.53 42.1 23.5 2.4 860 41.9 2.38 34.4 115.1 5.2 5.39.0 2.9 6.6 1200 38.8 27.2 1.61 44.3 24.1 2.5 1200 43.8 2.12 36.6 103.8 6.1 4.7
80
4.5 0.8 1.8 860 32.9 22.3 1.92 40.3 17.1 4.0 860 42.6 2.41 35.1 115.9 5.2 5.44.5 0.8 1.8 1200 35.6 26.3 2.02 42.5 17.6 4.2 1200 44.5 2.14 37.2 104.3 6.1 4.86.8 1.7 3.8 860 34.1 22.8 1.79 41.1 19.1 3.4 860 44.6 2.44 37.0 118.1 5.4 5.76.8 1.7 3.8 1200 36.8 26.8 1.88 43.3 19.6 3.6 1200 46.6 2.17 39.2 106.0 6.3 5.19.0 2.8 6.4 860 34.6 22.9 1.72 41.4 20.1 3.1 860 45.7 2.46 37.9 119.2 5.4 5.89.0 2.8 6.4 1200 37.4 27.0 1.81 43.6 20.7 3.3 1200 47.7 2.19 40.3 106.8 6.4 5.2
85
4.5 0.8 1.8 860 31.9 21.9 2.0 39.7 15.7 4.5 860 44.3 2.43 36.7 117.7 5.3 5.74.5 0.8 1.8 1200 34.4 25.7 2.14 41.7 16.2 4.7 1200 46.3 2.2 38.9 105.7 6.3 5.16.8 1.6 3.8 860 33.1 22.4 1.90 40.5 17.5 3.9 860 46.3 2.5 38.5 119.8 5.5 6.06.8 1.6 3.8 1200 35.8 26.3 2.00 42.6 18.0 4.1 1200 48.4 2.2 40.9 107.3 6.4 5.39.0 2.8 6.4 860 33.7 22.6 1.83 40.8 18.5 3.6 860 47.3 2.5 39.4 120.9 5.6 6.19.0 2.8 6.4 1200 36.4 26.6 1.92 43.0 19.1 3.8 1200 49.4 2.2 41.8 108.1 6.5 5.5
90
4.5 0.8 1.8 860 30.8 21.4 2.15 39.0 14.3 4.9 860 46.0 2.46 38.2 119.5 5.5 6.04.5 0.8 1.8 1200 33.3 25.2 2.26 41.0 14.7 5.2 1200 48.1 2.19 40.6 107.1 6.4 5.36.8 1.6 3.8 860 32.1 22.0 2.01 39.8 16.0 4.4 860 47.9 2.51 40.0 121.6 5.6 6.26.8 1.6 3.8 1200 34.7 25.9 2.11 41.9 16.5 4.6 1200 50.1 2.23 42.5 108.6 6.6 5.59.0 2.7 6.3 860 32.8 22.3 1.93 40.3 17.0 4.0 860 48.9 2.53 40.9 122.6 5.7 6.49.0 2.7 6.3 1200 35.4 26.2 2.03 42.4 17.5 4.2 1200 51.0 2.25 43.4 109.4 6.6 5.7
100
4.5 0.8 1.8 860 28.6 20.4 2.40 37.5 11.9 6.1 860
Operation not recommended
4.5 0.8 1.8 1200 30.9 24.0 2.52 39.5 12.3 6.4 12006.8 1.6 3.7 860 29.9 21.0 2.24 38.4 13.3 5.4 8606.8 1.6 3.7 1200 32.4 24.7 2.36 40.4 13.7 5.7 12009.0 2.7 6.2 860 30.6 21.3 2.17 38.8 14.1 5.0 8609.0 2.7 6.2 1200 33.1 25.1 2.28 40.9 14.5 5.3 1200
110
4.5 0.7 1.7 860 26.3 19.2 2.67 36.1 9.8 7.3 8604.5 0.7 1.7 1200 28.4 22.6 2.81 38.0 10.1 7.7 12006.8 1.6 3.6 860 27.6 19.9 2.51 36.9 11.0 6.7 8606.8 1.6 3.6 1200 29.8 23.4 2.64 38.8 11.3 7.0 12009.0 2.6 6.1 860 28.3 20.2 2.43 37.3 11.7 6.3 8609.0 2.6 6.1 1200 30.6 23.8 2.55 39.3 12.0 6.6 1200
120
4.5 0.6 1.5 860 24.1 18.2 2.98 34.9 8.1 8.7 8604.5 0.6 1.5 1200 26.1 21.4 3.13 36.8 8.3 9.2 12006.8 1.5 3.3 860 25.3 18.8 2.81 35.5 9.0 8.0 8606.8 1.5 3.3 1200 27.3 22.1 2.95 37.4 9.3 8.4 12009.0 2.5 5.8 860 25.9 19.1 2.72 35.9 9.5 7.6 8609.0 2.5 5.8 1200 28.0 22.4 2.86 37.8 9.8 8.0 1200
57
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Performance Data — Tranquility® 20 Model 042 - PSC Blower
Performance capacities shown in thousands of Btuh1,400 CFM Nominal (Rated) Airfl ow Cooling, 1,400 CFM Nominal (Rated) Airfl ow Heating
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
2010.5 3.7 8.5 1000
Operation not recommended1000 26.1 2.77 17.7 94.1 2.8 3.7
10.5 3.7 8.5 1400 1400 27.2 2.46 18.8 88.0 3.2 3.3
30
5.3 1.0 2.3 1000 39.5 23.0 1.35 45.2 29.3 1.7 1000 28.7 2.75 20.4 96.6 3.1 3.95.3 1.0 2.3 1400 42.7 27.1 1.42 47.6 30.1 1.8 1400 30.0 2.45 21.6 89.8 3.6 3.57.9 2.0 4.6 1000 36.4 20.1 1.26 41.7 28.8 1.8 1000 29.9 2.74 21.6 97.7 3.2 4.07.9 2.0 4.6 1400 39.4 23.7 1.33 43.9 29.6 1.9 1400 31.3 2.44 23.0 90.7 3.8 3.6
10.5 3.4 7.9 1000 34.6 18.6 1.24 39.7 28.0 1.8 1000 30.6 2.74 22.3 98.4 3.3 4.010.5 3.4 7.9 1400 37.4 21.8 1.30 41.8 28.7 1.9 1400 32.0 2.44 23.7 91.2 3.8 3.6
40
5.3 0.9 2.0 1000 42.3 26.1 1.50 48.6 28.1 1.8 1000 33.0 2.74 24.7 100.6 3.5 4.35.3 0.9 2.0 1400 45.7 30.7 1.58 51.1 28.9 1.9 1400 34.5 2.44 26.2 92.8 4.1 3.87.9 1.9 4.3 1000 40.9 24.5 1.41 46.8 29.1 1.7 1000 34.6 2.74 26.2 102.0 3.7 4.37.9 1.9 4.3 1400 44.2 28.8 1.48 49.3 29.9 1.8 1400 36.1 2.44 27.8 93.9 4.3 3.8
10.5 3.2 7.5 1000 39.9 23.4 1.36 45.6 29.3 1.7 1000 35.5 2.74 27.1 102.8 3.8 4.410.5 3.2 7.5 1400 43.1 27.5 1.43 48.0 30.2 1.8 1400 37.1 2.44 28.7 94.5 4.5 3.9
50
5.3 0.8 1.8 1000 42.7 27.2 1.66 49.6 25.7 2.2 1000 37.5 2.75 29.1 104.7 4.0 4.65.3 0.8 1.8 1400 46.2 32.0 1.75 52.2 26.4 2.3 1400 39.2 2.45 30.9 95.9 4.7 4.17.9 1.7 4.0 1000 42.7 26.7 1.56 49.1 27.3 1.9 1000 39.4 2.77 30.9 106.5 4.2 4.77.9 1.7 4.0 1400 46.1 31.4 1.64 51.7 28.1 2.0 1400 41.2 2.46 32.8 97.3 4.9 4.2
10.5 3.1 7.1 1000 42.3 26.1 1.50 48.6 28.2 1.9 1000 40.5 2.77 31.9 107.5 4.3 4.710.5 3.1 7.1 1400 45.8 30.8 1.58 51.2 29.0 2.0 1400 42.3 2.46 33.9 98.0 5.0 4.2
60
5.3 0.8 1.8 1000 41.7 27.1 1.84 49.1 22.7 2.7 1000 42.2 2.79 33.5 109.0 4.4 4.95.3 0.8 1.8 1400 45.1 31.9 1.93 51.7 23.4 2.8 1400 44.1 2.48 35.6 99.1 5.2 4.47.9 1.7 3.9 1000 42.5 27.3 1.72 49.5 24.7 2.4 1000 44.4 2.81 35.7 111.1 4.6 5.27.9 1.7 3.9 1400 46.0 32.1 1.81 52.1 25.4 2.5 1400 46.4 2.50 37.9 100.7 5.4 4.6
10.5 3.0 6.9 1000 42.7 27.2 1.66 49.6 25.7 2.2 1000 45.7 2.83 36.9 112.3 4.7 5.310.5 3.0 6.9 1400 46.2 32.0 1.75 52.2 26.4 2.3 1400 47.7 2.52 39.2 101.6 5.6 4.7
70
5.3 0.8 1.7 1000 39.8 26.2 2.04 47.8 19.6 3.3 1000 46.9 2.84 38.0 113.4 4.8 5.45.3 0.8 1.7 1400 43.0 30.8 2.14 50.3 20.1 3.5 1400 49.0 2.53 40.4 102.4 5.7 4.87.9 1.6 3.8 1000 41.1 26.8 1.90 48.7 21.6 2.9 1000 49.5 2.89 40.5 115.9 5.0 5.67.9 1.6 3.8 1400 44.5 31.6 2.00 51.3 22.2 3.1 1400 51.8 2.57 43.0 104.2 5.9 5.0
10.5 2.9 6.7 1000 41.7 27.1 1.84 49.1 22.6 2.7 1000 51.0 2.92 41.8 117.2 5.1 5.710.5 2.9 6.7 1400 45.1 31.9 1.94 51.7 23.2 2.8 1400 53.3 2.60 44.4 105.2 6.0 5.1
80
5.3 0.8 1.8 1000 37.3 24.8 2.25 46.0 16.6 4.2 1000 51.7 2.93 42.5 117.9 5.2 6.05.3 0.8 1.8 1400 40.4 29.2 2.37 48.5 17.0 4.4 1400 54.0 2.61 45.1 105.7 6.1 5.37.9 1.6 3.7 1000 38.9 25.7 2.11 47.2 18.4 3.6 1000 54.7 3.01 45.2 120.6 5.3 6.27.9 1.6 3.7 1400 42.1 30.2 2.22 49.7 19.0 3.8 1400 57.1 2.68 48.0 107.8 6.2 5.5
10.5 2.9 6.7 1000 39.7 26.1 2.04 47.7 19.4 3.4 1000 56.3 3.06 46.7 122.1 5.4 6.410.5 2.9 6.7 1400 42.9 30.7 2.15 50.3 20.0 3.6 1400 58.8 2.72 49.6 108.9 6.3 5.7
85
5.3 0.8 1.8 1000 36.0 24.0 2.4 45.1 15.2 4.7 1000 54.1 3.00 44.7 120.1 5.3 6.25.3 0.8 1.8 1400 38.9 28.3 2.51 47.5 15.6 4.9 1400 56.6 2.7 47.5 107.4 6.2 5.67.9 1.6 3.7 1000 37.6 25.0 2.23 46.2 16.9 4.1 1000 57.2 3.1 47.5 123.0 5.4 6.57.9 1.6 3.7 1400 40.7 29.4 2.35 48.7 17.4 4.3 1400 59.8 2.7 50.5 109.6 6.4 5.8
10.5 2.9 6.6 1000 38.4 25.4 2.16 46.8 17.9 3.8 1000 58.9 3.1 49.1 124.6 5.5 6.710.5 2.9 6.6 1400 41.5 29.9 2.27 49.3 18.4 4.1 1400 61.6 2.8 52.1 110.7 6.5 6.0
90
5.3 0.8 1.8 1000 34.6 23.3 2.51 44.1 13.8 5.1 1000 56.6 3.06 46.9 122.4 5.4 6.55.3 0.8 1.8 1400 37.5 27.4 2.64 46.5 14.2 5.4 1400 59.1 2.72 49.8 109.1 6.4 5.87.9 1.6 3.7 1000 36.3 24.2 2.35 45.3 15.4 4.6 1000 59.8 3.16 49.8 125.4 5.6 6.97.9 1.6 3.7 1400 39.2 28.5 2.47 47.7 15.9 4.8 1400 62.5 2.81 52.9 111.3 6.5 6.1
10.5 2.9 6.6 1000 37.1 24.7 2.27 45.9 16.3 4.3 1000 61.6 3.23 51.4 127.0 5.6 7.110.5 2.9 6.6 1400 40.1 29.0 2.39 48.3 16.8 4.5 1400 64.4 2.87 54.6 112.6 6.6 6.3
100
5.3 0.8 1.8 1000 32.0 21.9 2.80 42.4 11.5 6.4 1000
Operation not recommended
5.3 0.8 1.8 1400 34.6 25.8 2.94 44.6 11.8 6.7 14007.9 1.6 3.6 1000 33.5 22.7 2.62 43.4 12.8 5.6 10007.9 1.6 3.6 1400 36.2 26.7 2.76 45.7 13.1 5.9 1400
10.5 2.8 6.5 1000 34.3 23.1 2.54 43.9 13.5 5.3 100010.5 2.8 6.5 1400 37.1 27.2 2.67 46.2 13.9 5.6 1400
110
5.3 0.8 1.7 1000 29.8 20.9 3.13 41.2 9.5 7.7 10005.3 0.8 1.7 1400 32.2 24.6 3.29 43.4 9.8 8.1 14007.9 1.6 3.6 1000 31.0 21.4 2.94 41.8 10.5 6.9 10007.9 1.6 3.6 1400 33.5 25.2 3.09 44.0 10.8 7.3 1400
10.5 2.8 6.4 1000 31.6 21.7 2.84 42.2 11.1 6.6 100010.5 2.8 6.4 1400 34.2 25.5 2.99 44.4 11.4 6.9 1400
120
5.3 0.7 1.6 1000 28.2 20.6 3.52 41.0 8.0 9.3 10005.3 0.7 1.6 1400 30.5 24.3 3.70 43.1 8.2 9.8 14007.9 1.5 3.5 1000 28.9 20.7 3.30 41.0 8.8 8.4 10007.9 1.5 3.5 1400 31.3 24.3 3.47 43.1 9.0 8.8 1400
10.5 2.7 6.3 1000 29.4 20.8 3.20 41.1 9.2 8.0 100010.5 2.7 6.3 1400 31.8 24.4 3.36 43.2 9.5 8.4 1400
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
58 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Performance Data — Tranquility® 20 Model 042 - ECM Blower
Performance capacities shown in thousands of Btuh1,400 CFM Nominal (Rated) Airfl ow Cooling, 1,400 CFM Nominal (Rated) Airfl ow Heating
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
2010.5 3.7 8.5 1000
Operation not recommended1000 24.5 2.59 16.7 92.6 2.8 3.7
10.5 3.7 8.5 1400 1400 25.6 2.30 17.7 86.9 3.3 3.3
30
5.3 1.0 2.3 1000 39.4 22.9 1.20 44.6 32.9 1.7 1000 27.0 2.57 19.3 95.0 3.1 3.95.3 1.0 2.3 1400 42.6 27.0 1.26 47.0 33.8 1.8 1400 28.3 2.29 20.5 88.7 3.6 3.57.9 2.0 4.6 1000 36.3 20.1 1.12 41.1 32.4 1.8 1000 28.1 2.56 20.4 96.1 3.2 4.07.9 2.0 4.6 1400 39.3 23.6 1.18 43.3 33.3 1.9 1400 29.4 2.28 21.6 89.4 3.8 3.6
10.5 3.4 7.9 1000 34.5 18.5 1.08 39.1 31.8 1.8 1000 28.7 2.56 21.0 96.6 3.3 4.010.5 3.4 7.9 1400 37.3 21.8 1.14 41.2 32.7 1.9 1400 30.0 2.28 22.3 89.9 3.9 3.6
40
5.3 0.9 2.0 1000 42.3 26.1 1.35 48.0 31.3 1.8 1000 31.1 2.56 23.3 98.8 3.6 4.35.3 0.9 2.0 1400 45.7 30.7 1.42 50.5 32.2 1.9 1400 32.5 2.28 24.8 91.5 4.2 3.87.9 1.9 4.3 1000 40.9 24.4 1.26 46.3 32.6 1.7 1000 32.5 2.56 24.7 100.1 3.7 4.37.9 1.9 4.3 1400 44.2 28.7 1.32 48.7 33.5 1.8 1400 34.0 2.28 26.2 92.5 4.4 3.8
10.5 3.2 7.5 1000 39.9 23.4 1.22 45.1 32.7 1.7 1000 33.3 2.56 25.5 100.8 3.8 4.410.5 3.2 7.5 1400 43.1 27.5 1.28 47.5 33.7 1.8 1400 34.8 2.28 27.0 93.0 4.5 3.9
50
5.3 0.8 1.8 1000 42.7 27.2 1.51 49.1 28.3 2.2 1000 35.4 2.57 27.5 102.8 4.0 4.65.3 0.8 1.8 1400 46.2 32.0 1.59 51.6 29.1 2.3 1400 37.0 2.29 29.2 94.5 4.7 4.17.9 1.7 4.0 1000 42.6 26.6 1.41 48.6 30.3 1.9 1000 37.1 2.59 29.2 104.4 4.2 4.77.9 1.7 4.0 1400 46.1 31.4 1.48 51.2 31.1 2.0 1400 38.8 2.30 31.0 95.7 4.9 4.2
10.5 3.1 7.1 1000 42.3 26.1 1.36 48.1 31.1 1.9 1000 38.1 2.60 30.1 105.3 4.3 4.710.5 3.1 7.1 1400 45.7 30.7 1.43 50.6 32.0 2.0 1400 39.8 2.31 31.9 96.3 5.0 4.2
60
5.3 0.8 1.8 1000 41.7 27.1 1.69 48.6 24.7 2.7 1000 39.8 2.61 31.7 106.9 4.5 4.95.3 0.8 1.8 1400 45.1 31.9 1.78 51.2 25.4 2.8 1400 41.6 2.32 33.7 97.5 5.3 4.47.9 1.7 3.9 1000 42.5 27.3 1.57 49.0 27.1 2.4 1000 41.9 2.63 33.7 108.8 4.7 5.27.9 1.7 3.9 1400 46.0 32.1 1.65 51.6 27.9 2.5 1400 43.8 2.34 35.8 98.9 5.5 4.6
10.5 3.0 6.9 1000 42.7 27.2 1.52 49.1 28.1 2.2 1000 43.0 2.65 34.8 109.8 4.8 5.310.5 3.0 6.9 1400 46.2 32.0 1.60 51.6 28.9 2.3 1400 45.0 2.36 36.9 99.7 5.6 4.7
70
5.3 0.8 1.7 1000 39.8 26.2 1.88 47.3 21.2 3.3 1000 44.4 2.68 36.1 111.1 4.9 5.45.3 0.8 1.7 1400 43.1 30.8 1.98 49.8 21.8 3.5 1400 46.4 2.38 38.3 100.7 5.7 4.87.9 1.6 3.8 1000 41.2 26.8 1.76 48.3 23.4 2.9 1000 46.8 2.72 38.3 113.3 5.0 5.67.9 1.6 3.8 1400 44.5 31.6 1.85 50.8 24.0 3.1 1400 48.9 2.42 40.6 102.3 5.9 5.0
10.5 2.9 6.7 1000 41.7 27.1 1.69 48.6 24.6 2.7 1000 48.1 2.74 39.5 114.5 5.1 5.710.5 2.9 6.7 1400 45.1 31.9 1.78 51.2 25.3 2.8 1400 50.3 2.44 41.9 103.2 6.0 5.1
80
5.3 0.8 1.8 1000 37.4 24.8 2.11 45.6 17.7 4.2 1000 49.0 2.77 40.4 115.4 5.2 6.05.3 0.8 1.8 1400 40.4 29.2 2.22 48.0 18.2 4.4 1400 51.3 2.46 42.8 103.9 6.1 5.37.9 1.6 3.7 1000 39.0 25.7 1.97 46.7 19.8 3.6 1000 51.8 2.83 42.8 117.9 5.4 6.27.9 1.6 3.7 1400 42.1 30.2 2.07 49.2 20.3 3.8 1400 54.1 2.52 45.5 105.8 6.3 5.5
10.5 2.9 6.7 1000 39.7 26.1 1.90 47.3 20.9 3.4 1000 53.3 2.88 44.2 119.3 5.4 6.410.5 2.9 6.7 1400 42.9 30.7 2.00 49.7 21.5 3.6 1400 55.7 2.56 46.9 106.8 6.4 5.7
85
5.3 0.8 1.8 1000 36.0 24.1 2.2 44.6 16.2 4.7 1000 51.4 2.83 42.5 117.6 5.3 6.25.3 0.8 1.8 1400 39.0 28.3 2.35 47.0 16.7 4.9 1400 53.7 2.5 45.1 105.5 6.2 5.67.9 1.6 3.7 1000 37.6 25.0 2.09 45.8 18.1 4.1 1000 54.3 2.9 45.1 120.3 5.5 6.57.9 1.6 3.7 1400 40.7 29.4 2.20 48.2 18.6 4.3 1400 56.7 2.6 47.9 107.5 6.4 5.8
10.5 2.9 6.6 1000 38.4 25.4 2.02 46.3 19.2 3.8 1000 55.9 3.0 46.5 121.7 5.5 6.710.5 2.9 6.6 1400 41.6 29.9 2.12 48.8 19.7 4.1 1400 58.4 2.6 49.4 108.6 6.5 6.0
90
5.3 0.8 1.8 1000 34.7 23.3 2.36 43.7 14.7 5.1 1000 53.8 2.90 44.6 119.8 5.4 6.55.3 0.8 1.8 1400 37.5 27.4 2.48 46.0 15.1 5.4 1400 56.2 2.58 47.4 107.2 6.4 5.87.9 1.6 3.7 1000 36.3 24.2 2.21 44.8 16.5 4.6 1000 56.8 2.99 47.4 122.6 5.6 6.97.9 1.6 3.7 1400 39.3 28.5 2.32 47.2 16.9 4.8 1400 59.4 2.66 50.3 109.3 6.5 6.1
10.5 2.9 6.6 1000 37.1 24.7 2.13 45.4 17.4 4.3 1000 58.5 3.06 48.8 124.1 5.6 7.110.5 2.9 6.6 1400 40.2 29.1 2.24 47.8 17.9 4.5 1400 61.1 2.72 51.8 110.4 6.6 6.3
100
5.3 0.8 1.8 1000 32.1 21.9 2.64 41.9 12.1 6.3 1000
Operation not recommended
5.3 0.8 1.8 1400 34.7 25.8 2.78 44.2 12.5 6.6 14007.9 1.6 3.6 1000 33.6 22.7 2.47 42.9 13.6 5.6 10007.9 1.6 3.6 1400 36.3 26.7 2.60 45.2 14.0 5.9 1400
10.5 2.8 6.5 1000 34.4 23.1 2.40 43.4 14.3 5.3 100010.5 2.8 6.5 1400 37.1 27.2 2.52 45.7 14.7 5.6 1400
110
5.3 0.8 1.7 1000 29.8 20.9 2.98 40.7 10.0 7.7 10005.3 0.8 1.7 1400 32.2 24.6 3.13 42.9 10.3 8.1 14007.9 1.6 3.6 1000 31.0 21.4 2.79 41.3 11.1 6.9 10007.9 1.6 3.6 1400 33.5 25.2 2.93 43.5 11.4 7.3 1400
10.5 2.8 6.4 1000 31.7 21.7 2.69 41.7 11.8 6.6 100010.5 2.8 6.4 1400 34.2 25.6 2.83 43.9 12.1 6.9 1400
120
5.3 0.7 1.6 1000 28.2 20.6 3.37 40.5 8.4 9.3 10005.3 0.7 1.6 1400 30.5 24.2 3.54 42.6 8.6 9.8 14007.9 1.5 3.5 1000 29.0 20.7 3.15 40.5 9.2 8.4 10007.9 1.5 3.5 1400 31.3 24.3 3.31 42.6 9.5 8.8 1400
10.5 2.7 6.3 1000 29.4 20.8 3.04 40.6 9.7 8.0 100010.5 2.7 6.3 1400 31.8 24.5 3.20 42.7 9.9 8.4 1400
59
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Performance Data — Tranquility® 20 Model 048 - PSC Blower
Performance capacities shown in thousands of Btuh1,600 CFM Nominal (Rated) Airfl ow Cooling, 1,600 CFM Nominal (Rated) Airfl ow Heating
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
2012.0 4.2 9.6 1150
Operation not recommended1150 34.6 3.78 23.2 97.8 2.7 3.7
12.0 4.2 9.6 1600 1600 36.1 3.36 24.6 90.9 3.2 3.3
30
6.0 1.1 2.6 1150 47.8 26.4 2.01 56.0 23.8 1.7 1150 37.3 3.78 26.0 100.1 2.9 3.96.0 1.1 2.6 1600 51.7 31.0 2.11 58.9 24.5 1.8 1600 39.0 3.36 27.6 92.6 3.4 3.59.0 2.3 5.3 1150 44.4 23.5 1.85 52.0 24.0 1.8 1150 38.9 3.79 27.5 101.3 3.0 3.99.0 2.3 5.3 1600 48.0 27.7 1.95 54.7 24.6 1.9 1600 40.7 3.37 29.2 93.5 3.5 3.5
12.0 3.8 8.7 1150 42.4 22.0 1.79 49.7 23.7 1.8 1150 39.8 3.80 28.3 102.1 3.1 4.012.0 3.8 8.7 1600 45.9 25.9 1.88 52.3 24.4 1.9 1600 41.6 3.38 30.1 94.1 3.6 3.6
40
6.0 0.9 2.1 1150 50.7 29.3 2.23 59.7 22.7 1.9 1150 42.3 3.82 30.8 104.1 3.2 4.26.0 0.9 2.1 1600 54.8 34.5 2.35 62.8 23.3 2.0 1600 44.2 3.40 32.7 95.6 3.8 3.79.0 2.1 4.8 1150 49.1 27.6 2.08 57.5 23.6 1.7 1150 44.3 3.84 32.6 105.7 3.4 4.39.0 2.1 4.8 1600 53.1 32.4 2.19 60.5 24.2 1.8 1600 46.3 3.42 34.7 96.8 4.0 3.8
12.0 3.5 8.0 1150 47.9 26.5 2.01 56.0 23.9 1.7 1150 45.4 3.86 33.7 106.6 3.5 4.412.0 3.5 8.0 1600 51.8 31.1 2.11 59.0 24.5 1.8 1600 47.5 3.43 35.8 97.5 4.1 3.9
50
6.0 0.8 1.9 1150 51.3 30.6 2.46 61.1 20.8 2.3 1150 47.6 3.89 35.7 108.3 3.6 4.56.0 0.8 1.9 1600 55.4 36.0 2.59 64.3 21.4 2.4 1600 49.7 3.46 37.9 98.8 4.2 4.09.0 1.9 4.4 1150 51.0 29.8 2.30 60.3 22.2 2.0 1150 50.0 3.93 37.9 110.2 3.7 4.69.0 1.9 4.4 1600 55.2 35.1 2.42 63.5 22.8 2.1 1600 52.2 3.50 40.3 100.2 4.4 4.1
12.0 3.3 7.6 1150 50.6 29.2 2.23 59.6 22.7 1.9 1150 51.3 3.96 39.2 111.3 3.8 4.712.0 3.3 7.6 1600 54.7 34.4 2.34 62.7 23.4 2.0 1600 53.6 3.52 41.6 101.0 4.5 4.2
60
6.0 0.8 1.8 1150 50.3 30.8 2.71 60.9 18.6 2.8 1150 52.9 3.99 40.7 112.6 3.9 4.86.0 0.8 1.8 1600 54.4 36.3 2.85 64.1 19.1 2.9 1600 55.3 3.55 43.2 102.0 4.6 4.39.0 1.8 4.2 1150 51.1 30.8 2.54 61.1 20.1 2.4 1150 55.7 4.05 43.3 114.9 4.0 5.19.0 1.8 4.2 1600 55.3 36.2 2.67 64.4 20.7 2.5 1600 58.2 3.60 45.9 103.7 4.7 4.5
12.0 3.1 7.3 1150 51.3 30.6 2.45 61.0 20.9 2.2 1150 57.2 4.08 44.7 116.1 4.1 5.212.0 3.1 7.3 1600 55.4 36.0 2.58 64.2 21.5 2.3 1600 59.8 3.63 47.4 104.6 4.8 4.6
70
6.0 0.8 1.7 1150 48.4 30.2 2.98 59.8 16.2 3.5 1150 58.4 4.11 45.7 117.0 4.2 5.36.0 0.8 1.7 1600 52.3 35.6 3.13 63.0 16.7 3.7 1600 61.0 3.66 48.5 105.3 4.9 4.79.0 1.8 4.1 1150 49.8 30.7 2.79 60.7 17.9 2.9 1150 61.5 4.18 48.5 119.5 4.3 5.69.0 1.8 4.1 1600 53.9 36.1 2.93 63.9 18.4 3.1 1600 64.2 3.72 51.5 107.2 5.1 5.0
12.0 3.1 7.1 1150 50.4 30.8 2.69 61.0 18.7 2.8 1150 63.2 4.23 50.1 120.9 4.4 5.712.0 3.1 7.1 1600 54.5 36.3 2.83 64.2 19.3 2.9 1600 66.0 3.76 53.2 108.2 5.1 5.1
80
6.0 0.8 1.7 1150 45.7 29.2 3.27 58.1 14.0 4.4 1150 63.8 4.24 50.6 121.3 4.4 5.86.0 0.8 1.7 1600 49.4 34.3 3.44 61.2 14.4 4.6 1600 66.6 3.77 53.8 108.6 5.2 5.29.0 1.7 4.0 1150 47.6 29.9 3.06 59.4 15.5 3.7 1150 67.1 4.33 53.7 124.0 4.5 6.29.0 1.7 4.0 1600 51.5 35.2 3.22 62.5 16.0 3.9 1600 70.1 3.85 57.0 110.6 5.3 5.5
12.0 3.0 7.0 1150 48.5 30.3 2.97 59.9 16.3 3.4 1150 68.9 4.37 55.4 125.5 4.6 6.312.0 3.0 7.0 1600 52.4 35.6 3.12 63.0 16.8 3.6 1600 72.0 3.89 58.8 111.7 5.4 5.6
85
6.0 0.8 1.7 1150 44.2 28.5 3.4 57.1 12.9 4.9 1150 66.4 4.30 53.0 123.5 4.5 6.16.0 0.8 1.7 1600 47.8 33.5 3.62 60.2 13.3 5.2 1600 69.4 3.8 56.3 110.2 5.3 5.59.0 1.7 4.0 1150 46.2 29.3 3.22 58.4 14.4 4.2 1150 69.8 4.4 56.2 126.2 4.7 6.59.0 1.7 4.0 1600 49.9 34.5 3.39 61.5 14.8 4.4 1600 73.0 3.9 59.6 112.2 5.5 5.8
12.0 3.0 6.9 1150 47.1 29.7 3.11 59.0 15.2 3.9 1150 71.7 4.4 57.9 127.7 4.7 6.612.0 3.0 6.9 1600 51.0 35.0 3.28 62.1 15.6 4.1 1600 74.9 4.0 61.4 113.3 5.6 5.9
90
6.0 0.8 1.8 1150 42.7 27.8 3.60 56.2 11.9 5.4 1150 69.0 4.37 55.5 125.6 4.6 6.46.0 0.8 1.8 1600 46.2 32.7 3.79 59.1 12.2 5.7 1600 72.1 3.89 58.9 111.7 5.4 5.79.0 1.7 4.0 1150 44.8 28.7 3.38 57.5 13.3 4.7 1150 72.6 4.46 58.7 128.4 4.8 6.79.0 1.7 4.0 1600 48.4 33.8 3.55 60.5 13.6 4.9 1600 75.8 3.97 62.3 113.9 5.6 6.0
12.0 3.0 6.9 1150 45.8 29.2 3.26 58.2 14.0 4.4 1150 74.4 4.51 60.4 129.9 4.8 7.012.0 3.0 6.9 1600 49.5 34.3 3.43 61.2 14.4 4.6 1600 77.8 4.01 64.1 115.0 5.7 6.2
100
6.0 0.8 1.8 1150 39.6 26.3 3.98 54.2 10.0 6.6 1150
Operation not recommended
6.0 0.8 1.8 1600 42.8 31.0 4.18 57.1 10.2 6.9 16009.0 1.7 4.0 1150 41.6 27.3 3.73 55.5 11.2 5.8 11509.0 1.7 4.0 1600 45.0 32.1 3.92 58.4 11.5 6.1 1600
12.0 3.0 6.8 1150 42.7 27.8 3.60 56.1 11.8 5.4 115012.0 3.0 6.8 1600 46.1 32.7 3.79 59.1 12.2 5.7 1600
110
6.0 0.7 1.7 1150 36.6 25.0 4.40 52.5 8.3 8.0 11506.0 0.7 1.7 1600 39.5 29.4 4.63 55.3 8.5 8.4 16009.0 1.7 3.9 1150 38.4 25.8 4.13 53.5 9.3 7.1 11509.0 1.7 3.9 1600 41.5 30.4 4.34 56.3 9.6 7.5 1600
12.0 2.9 6.7 1150 39.4 26.3 3.99 54.1 9.9 6.7 115012.0 2.9 6.7 1600 42.6 30.9 4.20 57.0 10.1 7.0 1600
120
6.0 0.7 1.5 1150 33.9 24.0 4.90 51.5 6.9 9.5 11506.0 0.7 1.5 1600 36.6 28.2 5.15 54.2 7.1 10.0 16009.0 1.6 3.7 1150 35.4 24.5 4.58 52.0 7.7 8.6 11509.0 1.6 3.7 1600 38.3 28.9 4.82 54.8 8.0 9.0 1600
12.0 2.8 6.5 1150 36.3 24.9 4.44 52.4 8.2 8.1 115012.0 2.8 6.5 1600 39.3 29.3 4.67 55.2 8.4 8.5 1600
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
60 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Performance Data — Tranquility® 20 Model 048 - ECM Blower
Performance capacities shown in thousands of Btuh1,550 CFM Nominal (Rated) Airfl ow Cooling, 1,650 CFM Nominal (Rated) Airfl ow Heating
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
2012.0 4.2 9.6 1100
Operation not recommended1200 31.7 3.45 21.3 94.5 2.7 3.7
12.0 4.2 9.6 1550 1650 33.1 3.07 22.7 88.6 3.2 3.3
30
6.0 1.1 2.6 1100 47.7 26.3 1.71 54.8 27.9 1.7 1200 34.4 3.45 24.0 96.6 2.9 3.96.0 1.1 2.6 1550 51.5 30.9 1.80 57.7 28.6 1.8 1650 36.0 3.07 25.5 90.2 3.4 3.59.0 2.3 5.3 1100 44.3 23.4 1.57 50.8 28.2 1.8 1200 35.8 3.46 25.4 97.6 3.0 3.99.0 2.3 5.3 1550 47.9 27.6 1.65 53.5 29.0 1.9 1650 37.4 3.08 26.9 91.0 3.6 3.5
12.0 3.8 8.7 1100 42.3 21.9 1.50 48.6 28.2 1.8 1200 36.6 3.46 26.1 98.2 3.1 4.012.0 3.8 8.7 1550 45.7 25.8 1.58 51.1 28.9 1.9 1650 38.2 3.08 27.7 91.4 3.6 3.6
40
6.0 0.9 2.1 1100 50.6 29.2 1.95 58.6 26.0 1.9 1200 39.1 3.50 28.5 100.2 3.3 4.26.0 0.9 2.1 1550 54.7 34.4 2.05 61.7 26.7 2.0 1650 40.9 3.11 30.3 92.9 3.9 3.79.0 2.1 4.8 1100 49.0 27.5 1.80 56.5 27.3 1.7 1200 40.8 3.52 30.2 101.5 3.4 4.39.0 2.1 4.8 1550 53.0 32.3 1.89 59.4 28.0 1.8 1650 42.7 3.13 32.0 94.0 4.0 3.8
12.0 3.5 8.0 1100 47.8 26.4 1.72 55.0 27.8 1.7 1200 41.8 3.53 31.1 102.3 3.5 4.412.0 3.5 8.0 1550 51.7 31.0 1.81 57.9 28.6 1.8 1650 43.7 3.14 33.0 94.5 4.1 3.9
50
6.0 0.8 1.9 1100 51.3 30.6 2.18 60.1 23.5 2.3 1200 44.1 3.56 33.2 104.0 3.6 4.56.0 0.8 1.9 1550 55.4 36.0 2.29 63.2 24.2 2.4 1650 46.0 3.17 35.2 95.8 4.3 4.09.0 1.9 4.4 1100 51.0 29.8 2.02 59.3 25.3 2.0 1200 46.2 3.61 35.1 105.6 3.7 4.69.0 1.9 4.4 1550 55.2 35.1 2.12 62.4 26.0 2.1 1650 48.2 3.21 37.3 97.1 4.4 4.1
12.0 3.3 7.6 1100 50.6 29.2 1.94 58.6 26.1 1.9 1200 47.3 3.63 36.2 106.5 3.8 4.712.0 3.3 7.6 1550 54.7 34.3 2.04 61.6 26.8 2.0 1650 49.4 3.23 38.4 97.7 4.5 4.2
60
6.0 0.8 1.8 1100 50.4 30.8 2.43 60.0 20.8 2.8 1200 49.2 3.68 37.9 107.9 3.9 4.86.0 0.8 1.8 1550 54.5 36.3 2.55 63.2 21.4 2.9 1650 51.4 3.27 40.2 98.8 4.6 4.39.0 1.8 4.2 1100 51.1 30.8 2.25 60.2 22.7 2.4 1200 51.6 3.73 40.1 109.8 4.1 5.19.0 1.8 4.2 1550 55.3 36.2 2.37 63.4 23.3 2.5 1650 53.9 3.32 42.6 100.3 4.8 4.5
12.0 3.1 7.3 1100 51.3 30.6 2.17 60.0 23.6 2.2 1200 52.9 3.77 41.4 110.9 4.1 5.212.0 3.1 7.3 1550 55.4 36.0 2.28 63.2 24.3 2.3 1650 55.3 3.35 43.9 101.0 4.8 4.6
70
6.0 0.8 1.7 1100 48.4 30.3 2.69 58.9 18.0 3.5 1200 54.3 3.80 42.6 111.9 4.2 5.36.0 0.8 1.7 1550 52.4 35.6 2.83 62.0 18.5 3.7 1650 56.8 3.38 45.3 101.9 4.9 4.79.0 1.8 4.1 1100 49.9 30.7 2.50 59.8 19.9 2.9 1200 57.1 3.87 45.1 114.1 4.3 5.69.0 1.8 4.1 1550 53.9 36.1 2.63 62.9 20.5 3.1 1650 59.7 3.44 47.9 103.5 5.1 5.0
12.0 3.1 7.1 1100 50.4 30.8 2.41 60.0 21.0 2.8 1200 58.6 3.90 46.5 115.2 4.4 5.712.0 3.1 7.1 1550 54.5 36.3 2.53 63.2 21.6 2.9 1650 61.2 3.47 49.4 104.4 5.2 5.1
80
6.0 0.8 1.7 1100 45.8 29.2 2.98 57.2 15.4 4.4 1200 59.5 3.92 47.3 115.9 4.4 5.86.0 0.8 1.7 1550 49.6 34.3 3.13 60.2 15.8 4.6 1650 62.2 3.49 50.2 104.9 5.2 5.29.0 1.7 4.0 1100 47.7 30.0 2.78 58.4 17.2 3.7 1200 62.5 4.00 50.1 118.2 4.6 6.29.0 1.7 4.0 1550 51.5 35.3 2.92 61.5 17.7 3.9 1650 65.3 3.56 53.1 106.6 5.4 5.5
12.0 3.0 7.0 1100 48.5 30.3 2.68 59.0 18.1 3.4 1200 64.1 4.05 51.5 119.5 4.6 6.312.0 3.0 7.0 1550 52.5 35.6 2.82 62.1 18.6 3.6 1650 67.0 3.60 54.7 107.6 5.5 5.6
85
6.0 0.8 1.7 1100 44.3 28.5 3.1 56.3 14.2 4.9 1200 62.0 3.99 49.6 117.9 4.6 6.16.0 0.8 1.7 1550 47.9 33.5 3.31 59.2 14.6 5.2 1650 64.8 3.6 52.7 106.4 5.3 5.59.0 1.7 4.0 1100 46.3 29.4 2.93 57.5 15.8 4.2 1200 65.1 4.1 52.4 120.2 4.7 6.59.0 1.7 4.0 1550 50.0 34.5 3.09 60.5 16.3 4.4 1650 68.0 3.6 55.6 108.2 5.5 5.8
12.0 3.0 6.9 1100 47.2 29.7 2.83 58.1 16.7 3.9 1200 66.7 4.1 53.9 121.5 4.8 6.612.0 3.0 6.9 1550 51.0 35.0 2.98 61.2 17.2 4.1 1650 69.7 3.7 57.2 109.1 5.6 5.9
90
6.0 0.8 1.8 1100 42.8 27.8 3.31 55.3 12.9 5.4 1200 64.5 4.06 51.9 119.8 4.7 6.46.0 0.8 1.8 1550 46.3 32.8 3.48 58.2 13.3 5.7 1650 67.4 3.61 55.1 107.8 5.5 5.79.0 1.7 4.0 1100 44.9 28.8 3.09 56.6 14.5 4.7 1200 67.7 4.15 54.8 122.2 4.8 6.79.0 1.7 4.0 1550 48.5 33.8 3.25 59.6 14.9 4.9 1650 70.7 3.69 58.2 109.7 5.6 6.0
12.0 3.0 6.9 1100 45.8 29.2 2.98 57.2 15.4 4.4 1200 69.3 4.18 56.3 123.5 4.9 7.012.0 3.0 6.9 1550 49.6 34.4 3.13 60.3 15.8 4.6 1650 72.5 3.72 59.8 110.7 5.7 6.2
100
6.0 0.8 1.8 1100 39.7 26.4 3.68 53.3 10.8 6.6 1200
Operation not recommended
6.0 0.8 1.8 1550 42.9 31.0 3.87 56.1 11.1 6.9 16509.0 1.7 4.0 1100 41.7 27.3 3.43 54.5 12.1 5.8 12009.0 1.7 4.0 1550 45.1 32.1 3.61 57.4 12.5 6.1 1650
12.0 3.0 6.8 1100 42.7 27.8 3.32 55.2 12.9 5.4 120012.0 3.0 6.8 1550 46.2 32.7 3.49 58.1 13.2 5.7 1650
110
6.0 0.7 1.7 1100 36.6 25.0 4.11 51.6 8.9 8.0 12006.0 0.7 1.7 1550 39.6 29.4 4.32 54.4 9.2 8.4 16509.0 1.7 3.9 1100 38.5 25.8 3.83 52.6 10.0 7.1 12009.0 1.7 3.9 1550 41.6 30.4 4.03 55.4 10.3 7.5 1650
12.0 2.9 6.7 1100 39.5 26.3 3.71 53.2 10.6 6.7 120012.0 2.9 6.7 1550 42.7 30.9 3.90 56.0 10.9 7.0 1650
120
6.0 0.7 1.5 1100 34.0 24.0 4.60 50.6 7.4 9.5 12006.0 0.7 1.5 1550 36.7 28.2 4.84 53.2 7.6 10.0 16509.0 1.6 3.7 1100 35.5 24.6 4.30 51.1 8.3 8.6 12009.0 1.6 3.7 1550 38.4 28.9 4.52 53.8 8.5 9.0 1650
12.0 2.8 6.5 1100 36.4 24.9 4.15 51.5 8.8 8.1 120012.0 2.8 6.5 1550 39.3 29.3 4.36 54.2 9.0 8.5 1650
61
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Performance Data — Tranquility® 20 Model 060 - PSC Blower
Performance capacities shown in thousands of Btuh1,950 CFM Nominal (Rated) Airfl ow Cooling, 1,950 CFM Nominal (Rated) Airfl ow Heating
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
2015.0 7.2 16.6 1400
Operation not recommended1400 39.4 4.45 26.1 96.1 2.6 4.3
15.0 7.2 16.6 1950 1950 41.2 3.96 27.7 89.6 3.0 3.8
30
7.5 1.3 3.0 1400 68.4 43.6 2.41 78.5 28.4 1.9 1400 43.0 4.55 29.3 98.4 2.8 4.57.5 1.3 3.0 1950 74.0 51.3 2.53 82.6 29.2 2.0 1950 44.9 4.05 31.1 91.3 3.3 4.011.3 3.5 8.1 1400 66.0 41.7 2.26 75.5 29.2 1.7 1400 44.8 4.60 30.9 99.6 2.9 4.611.3 3.5 8.1 1950 71.4 49.0 2.38 79.5 30.0 1.8 1950 46.8 4.09 32.8 92.2 3.4 4.115.0 6.1 14.1 1400 64.2 40.4 2.20 73.5 29.2 1.7 1400 45.8 4.62 31.8 100.3 2.9 4.615.0 6.1 14.1 1950 69.5 47.6 2.31 77.4 30.1 1.8 1950 47.8 4.11 33.8 92.7 3.4 4.1
40
7.5 0.9 2.0 1400 69.5 44.8 2.63 80.3 26.4 2.2 1400 49.3 4.71 35.1 102.6 3.1 4.87.5 0.9 2.0 1950 75.1 52.8 2.77 84.6 27.1 2.3 1950 51.5 4.19 37.3 94.5 3.6 4.311.3 2.9 6.7 1400 68.9 44.0 2.46 79.2 28.0 1.9 1400 51.7 4.75 37.3 104.2 3.2 4.911.3 2.9 6.7 1950 74.5 51.8 2.59 83.4 28.8 2.0 1950 54.0 4.23 39.6 95.6 3.7 4.415.0 5.3 12.2 1400 68.2 43.4 2.39 78.2 28.6 1.8 1400 53.0 4.79 38.5 105.0 3.2 5.115.0 5.3 12.2 1950 73.7 51.0 2.51 82.3 29.4 1.9 1950 55.4 4.26 40.9 96.3 3.8 4.5
50
7.5 0.6 1.4 1400 68.6 45.0 2.89 80.3 23.7 2.8 1400 56.2 4.84 41.4 107.1 3.4 5.27.5 0.6 1.4 1950 74.1 52.9 3.04 84.5 24.4 2.9 1950 58.7 4.31 44.0 97.9 4.0 4.611.3 2.5 5.7 1400 69.4 45.0 2.69 80.5 25.8 2.3 1400 59.1 4.91 44.2 109.1 3.5 5.411.3 2.5 5.7 1950 75.0 52.9 2.83 84.7 26.5 2.4 1950 61.8 4.37 46.9 99.3 4.1 4.815.0 4.7 10.9 1400 69.5 44.8 2.61 80.2 26.7 2.2 1400 60.8 4.93 45.7 110.2 3.6 5.515.0 4.7 10.9 1950 75.1 52.7 2.74 84.4 27.4 2.3 1950 63.5 4.39 48.5 100.2 4.2 4.9
60
7.5 0.5 1.1 1400 66.3 44.3 3.18 78.9 20.9 3.4 1400 63.3 4.99 48.1 111.9 3.7 5.67.5 0.5 1.1 1950 71.7 52.2 3.34 83.1 21.5 3.6 1950 66.2 4.44 51.0 101.4 4.4 5.011.3 2.2 5.1 1400 68.1 44.9 2.96 80.0 23.0 2.9 1400 66.9 5.06 51.4 114.2 3.9 5.811.3 2.2 5.1 1950 73.6 52.8 3.11 84.2 23.7 3.1 1950 69.9 4.50 54.5 103.2 4.6 5.215.0 4.3 10.0 1400 68.8 45.0 2.85 80.3 24.1 2.7 1400 68.8 5.10 53.2 115.5 4.0 6.015.0 4.3 10.0 1950 74.3 53.0 3.00 84.6 24.8 2.8 1950 71.9 4.54 56.4 104.2 4.6 5.3
70
7.5 0.5 1.1 1400 63.2 43.2 3.52 76.9 18.0 4.3 1400 70.7 5.14 54.9 116.7 4.0 6.17.5 0.5 1.1 1950 68.3 50.8 3.70 80.9 18.5 4.5 1950 73.8 4.57 58.2 105.1 4.7 5.411.3 2.1 4.8 1400 65.5 44.1 3.26 78.4 20.1 3.6 1400 74.7 5.23 58.6 119.4 4.2 6.411.3 2.1 4.8 1950 70.9 51.9 3.43 82.6 20.7 3.8 1950 78.1 4.65 62.2 107.1 4.9 5.715.0 4.1 9.5 1400 66.6 44.4 3.15 79.1 21.2 3.3 1400 76.9 5.27 60.7 120.9 4.3 6.615.0 4.1 9.5 1950 72.0 52.3 3.31 83.3 21.8 3.5 1950 80.4 4.69 64.4 108.2 5.0 5.9
80
7.5 0.5 1.1 1400 59.5 41.8 3.90 74.4 15.3 5.3 1400 78.0 5.31 61.6 121.6 4.3 6.67.5 0.5 1.1 1950 64.4 49.1 4.10 78.3 15.7 5.6 1950 81.5 4.72 65.4 108.7 5.1 5.911.3 2.0 4.6 1400 62.2 42.8 3.62 76.2 17.2 4.6 1400 82.4 5.41 65.7 124.5 4.5 7.111.3 2.0 4.6 1950 67.2 50.4 3.81 80.2 17.6 4.8 1950 86.1 4.81 69.7 110.9 5.2 6.315.0 4.0 9.2 1400 63.5 43.3 3.49 77.1 18.2 4.2 1400 84.8 5.47 67.9 126.1 4.5 7.315.0 4.0 9.2 1950 68.6 51.0 3.67 81.1 18.7 4.4 1950 88.7 4.87 72.0 112.1 5.3 6.5
85
7.5 0.5 1.1 1400 57.6 41.0 4.1 73.2 14.1 5.9 1400 81.5 5.40 64.9 123.9 4.4 7.07.5 0.5 1.1 1950 62.3 48.2 4.33 77.1 14.4 6.2 1950 85.2 4.8 68.8 110.5 5.2 6.211.3 2.0 4.6 1400 60.3 42.0 3.83 74.9 15.8 5.1 1400 86.1 5.5 69.0 127.0 4.6 7.411.3 2.0 4.6 1950 65.1 49.5 4.03 78.9 16.3 5.4 1950 90.0 4.9 73.2 112.7 5.4 6.615.0 4.0 9.1 1400 61.6 42.6 3.69 75.8 16.8 4.7 1400 88.6 5.6 71.2 128.6 4.6 7.615.0 4.0 9.1 1950 66.6 50.1 3.88 79.8 17.3 5.0 1950 92.5 5.0 75.6 113.9 5.5 6.8
90
7.5 0.5 1.2 1400 55.7 40.2 4.34 72.0 12.8 6.5 1400 85.1 5.49 68.1 126.3 4.5 7.37.5 0.5 1.2 1950 60.2 47.3 4.56 75.8 13.2 6.8 1950 88.9 4.88 72.3 112.2 5.3 6.511.3 2.0 4.5 1400 58.3 41.3 4.03 73.7 14.5 5.7 1400 89.8 5.62 72.3 129.4 4.7 7.811.3 2.0 4.5 1950 63.1 48.6 4.24 77.5 14.9 6.0 1950 93.8 5.00 76.8 114.6 5.5 6.915.0 3.9 9.1 1400 59.7 41.8 3.88 74.5 15.4 5.2 1400 92.3 5.71 74.5 131.0 4.7 8.015.0 3.9 9.1 1950 64.5 49.2 4.08 78.5 15.8 5.5 1950 96.4 5.08 79.1 115.8 5.6 7.1
100
7.5 0.5 1.1 1400 51.9 38.7 4.85 69.9 10.7 7.9 1400
Operation not recommended
7.5 0.5 1.1 1950 56.1 45.5 5.10 73.5 11.0 8.3 195011.3 1.9 4.5 1400 54.4 39.7 4.51 71.2 12.1 6.9 140011.3 1.9 4.5 1950 58.8 46.7 4.74 75.0 12.4 7.3 195015.0 3.9 9.0 1400 55.7 40.2 4.34 72.0 12.8 6.5 140015.0 3.9 9.0 1950 60.2 47.3 4.56 75.8 13.2 6.8 1950
110
7.5 0.4 0.8 1400 48.6 37.6 5.45 68.5 8.9 9.4 14007.5 0.4 0.8 1950 52.5 44.2 5.73 72.1 9.2 9.9 195011.3 1.8 4.2 1400 50.7 38.3 5.05 69.3 10.0 8.4 140011.3 1.8 4.2 1950 54.8 45.0 5.31 72.9 10.3 8.8 195015.0 3.8 8.8 1400 51.8 38.7 4.86 69.8 10.7 7.9 140015.0 3.8 8.8 1950 56.1 45.5 5.11 73.5 11.0 8.3 1950
120
7.5 0.1 0.3 1400 46.1 37.2 6.15 68.3 7.5 11.3 14007.5 0.1 0.3 1950 49.8 43.7 6.47 71.9 7.7 11.9 195011.3 1.6 3.8 1400 47.6 37.3 5.69 68.2 8.4 10.1 140011.3 1.6 3.8 1950 51.4 43.9 5.98 71.8 8.6 10.6 195015.0 3.7 8.5 1400 48.5 37.6 5.48 68.4 8.8 9.5 140015.0 3.7 8.5 1950 52.4 44.2 5.76 72.0 9.1 10.0 1950
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
62 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Performance Data — Tranquility® 20 Model 060 - ECM Blower
Performance capacities shown in thousands of Btuh1,950 CFM Nominal (Rated) Airfl ow Cooling, 2,050 CFM Nominal (Rated) Airfl ow Heating
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
2015.0 7.2 16.6 1400
Operation not recommended1475 38.5 4.07 26.2 94.2 2.8 4.3
15.0 7.2 16.6 1950 2050 40.2 3.62 27.8 88.2 3.3 3.8
30
7.5 1.3 3.0 1400 68.4 43.6 2.41 78.5 28.4 1.9 1475 42.0 4.14 29.5 96.3 3.0 4.57.5 1.3 3.0 1950 74.0 51.3 2.53 82.6 29.2 2.0 2050 43.9 3.68 31.3 89.8 3.5 4.011.3 3.5 8.1 1400 66.0 41.7 2.26 75.5 29.2 1.7 1475 43.7 4.17 31.1 97.5 3.1 4.611.3 3.5 8.1 1950 71.4 49.0 2.38 79.5 30.0 1.8 2050 45.7 3.71 33.0 90.6 3.6 4.115.0 6.1 14.1 1400 64.2 40.4 2.20 73.5 29.2 1.7 1475 44.7 4.19 32.0 98.1 3.1 4.615.0 6.1 14.1 1950 69.5 47.6 2.31 77.4 30.1 1.8 2050 46.7 3.73 34.0 91.1 3.7 4.1
40
7.5 0.9 2.0 1400 69.5 44.8 2.63 80.3 26.4 2.2 1475 48.2 4.25 35.3 100.3 3.3 4.87.5 0.9 2.0 1950 75.1 52.8 2.77 84.6 27.1 2.3 2050 50.4 3.78 37.5 92.8 3.9 4.311.3 2.9 6.7 1400 68.9 44.0 2.46 79.2 28.0 1.9 1475 50.6 4.29 37.5 101.8 3.5 4.911.3 2.9 6.7 1950 74.5 51.8 2.59 83.4 28.8 2.0 2050 52.9 3.82 39.8 93.9 4.1 4.415.0 5.3 12.2 1400 68.2 43.4 2.39 78.2 28.6 1.8 1475 51.9 4.33 38.7 102.6 3.5 5.115.0 5.3 12.2 1950 73.7 51.0 2.51 82.3 29.4 1.9 2050 54.2 3.85 41.1 94.5 4.1 4.5
50
7.5 0.6 1.4 1400 68.6 45.0 2.89 80.3 23.7 2.8 1475 55.1 4.38 41.7 104.6 3.7 5.27.5 0.6 1.4 1950 74.1 52.9 3.04 84.5 24.4 2.9 2050 57.5 3.90 44.2 96.0 4.3 4.611.3 2.5 5.7 1400 69.4 45.0 2.69 80.5 25.8 2.3 1475 58.0 4.44 44.4 106.4 3.8 5.411.3 2.5 5.7 1950 75.0 52.9 2.83 84.7 26.5 2.4 2050 60.6 3.95 47.2 97.4 4.5 4.815.0 4.7 10.9 1400 69.5 44.8 2.61 80.2 26.7 2.2 1475 59.7 4.47 46.0 107.5 3.9 5.515.0 4.7 10.9 1950 75.1 52.7 2.74 84.4 27.4 2.3 2050 62.4 3.98 48.8 98.2 4.6 4.9
60
7.5 0.5 1.1 1400 66.3 44.3 3.18 78.9 20.9 3.4 1475 62.2 4.52 48.3 109.1 4.0 5.67.5 0.5 1.1 1950 71.7 52.2 3.34 83.1 21.5 3.6 2050 65.0 4.02 51.3 99.4 4.7 5.011.3 2.2 5.1 1400 68.1 44.9 2.96 80.0 23.0 2.9 1475 65.8 4.60 51.6 111.3 4.2 5.811.3 2.2 5.1 1950 73.6 52.8 3.11 84.2 23.7 3.1 2050 68.7 4.09 54.8 101.1 4.9 5.215.0 4.3 10.0 1400 68.8 45.0 2.85 80.3 24.1 2.7 1475 67.8 4.63 53.4 112.5 4.3 6.015.0 4.3 10.0 1950 74.3 53.0 3.00 84.6 24.8 2.8 2050 70.8 4.12 56.7 102.0 5.0 5.3
70
7.5 0.5 1.1 1400 63.2 43.2 3.52 76.9 18.0 4.3 1475 69.5 4.68 55.1 113.7 4.4 6.17.5 0.5 1.1 1950 68.3 50.8 3.70 80.9 18.5 4.5 2050 72.7 4.16 58.5 102.8 5.1 5.411.3 2.1 4.8 1400 65.5 44.1 3.26 78.4 20.1 3.6 1475 73.6 4.77 58.8 116.2 4.5 6.411.3 2.1 4.8 1950 70.9 51.9 3.43 82.6 20.7 3.8 2050 76.9 4.24 62.4 104.7 5.3 5.715.0 4.1 9.5 1400 66.6 44.4 3.15 79.1 21.2 3.3 1475 75.8 4.81 60.8 117.6 4.6 6.615.0 4.1 9.5 1950 72.0 52.3 3.31 83.3 21.8 3.5 2050 79.2 4.28 64.6 105.8 5.4 5.9
80
7.5 0.5 1.1 1400 59.5 41.8 3.90 74.4 15.3 5.3 1475 76.8 4.83 61.7 118.2 4.7 6.67.5 0.5 1.1 1950 64.4 49.1 4.10 78.3 15.7 5.6 2050 80.2 4.30 65.5 106.2 5.5 5.911.3 2.0 4.6 1400 62.2 42.8 3.62 76.2 17.2 4.6 1475 81.1 4.95 65.7 120.9 4.8 7.111.3 2.0 4.6 1950 67.2 50.4 3.81 80.2 17.6 4.8 2050 84.7 4.40 69.7 108.3 5.6 6.315.0 4.0 9.2 1400 63.5 43.3 3.49 77.1 18.2 4.2 1475 83.4 5.01 67.8 122.4 4.9 7.315.0 4.0 9.2 1950 68.6 51.0 3.67 81.1 18.7 4.4 2050 87.2 4.46 72.0 109.4 5.7 6.5
85
7.5 0.5 1.1 1400 57.6 41.0 4.1 73.2 14.1 5.9 1475 80.2 4.92 64.9 120.4 4.8 7.07.5 0.5 1.1 1950 62.3 48.2 4.33 77.1 14.4 6.2 2050 83.8 4.4 68.9 107.9 5.6 6.211.3 2.0 4.6 1400 60.3 42.0 3.83 74.9 15.8 5.1 1475 84.6 5.0 68.8 123.1 4.9 7.411.3 2.0 4.6 1950 65.1 49.5 4.03 78.9 16.3 5.4 2050 88.4 4.5 73.1 109.9 5.8 6.615.0 4.0 9.1 1400 61.6 42.6 3.69 75.8 16.8 4.7 1475 86.9 5.1 70.9 124.5 5.0 7.615.0 4.0 9.1 1950 66.6 50.1 3.88 79.8 17.3 5.0 2050 90.8 4.6 75.3 111.0 5.8 6.8
90
7.5 0.5 1.2 1400 55.7 40.2 4.34 72.0 12.8 6.5 1475 83.7 5.01 68.0 122.5 4.9 7.37.5 0.5 1.2 1950 60.2 47.3 4.56 75.8 13.2 6.8 2050 87.4 4.46 72.2 109.5 5.7 6.511.3 2.0 4.5 1400 58.3 41.3 4.03 73.7 14.5 5.7 1475 88.1 5.15 72.0 125.3 5.0 7.811.3 2.0 4.5 1950 63.1 48.6 4.24 77.5 14.9 6.0 2050 92.1 4.58 76.4 111.6 5.9 6.915.0 3.9 9.1 1400 59.7 41.8 3.88 74.5 15.4 5.2 1475 90.4 5.22 74.0 126.7 5.1 8.015.0 3.9 9.1 1950 64.5 49.2 4.08 78.5 15.8 5.5 2050 94.4 4.64 78.6 112.6 6.0 7.1
100
7.5 0.5 1.1 1400 51.9 38.7 4.85 69.9 10.7 7.9 1475
Operation not recommended
7.5 0.5 1.1 1950 56.1 45.5 5.10 73.5 11.0 8.3 205011.3 1.9 4.5 1400 54.4 39.7 4.51 71.2 12.1 6.9 147511.3 1.9 4.5 1950 58.8 46.7 4.74 75.0 12.4 7.3 205015.0 3.9 9.0 1400 55.7 40.2 4.34 72.0 12.8 6.5 147515.0 3.9 9.0 1950 60.2 47.3 4.56 75.8 13.2 6.8 2050
110
7.5 0.4 0.8 1400 48.6 37.6 5.45 68.5 8.9 9.4 14757.5 0.4 0.8 1950 52.5 44.2 5.73 72.1 9.2 9.9 205011.3 1.8 4.2 1400 50.7 38.3 5.05 69.3 10.0 8.4 147511.3 1.8 4.2 1950 54.8 45.0 5.31 72.9 10.3 8.8 205015.0 3.8 8.8 1400 51.8 38.7 4.86 69.8 10.7 7.9 147515.0 3.8 8.8 1950 56.1 45.5 5.11 73.5 11.0 8.3 2050
120
7.5 0.1 0.3 1400 46.1 37.2 6.15 68.3 7.5 11.3 14757.5 0.1 0.3 1950 49.8 43.7 6.47 71.9 7.7 11.9 205011.3 1.6 3.8 1400 47.6 37.3 5.69 68.2 8.4 10.1 147511.3 1.6 3.8 1950 51.4 43.9 5.98 71.8 8.6 10.6 205015.0 3.7 8.5 1400 48.5 37.6 5.48 68.4 8.8 9.5 147515.0 3.7 8.5 1950 52.4 44.2 5.76 72.0 9.1 10.0 2050
63
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Performance Data — Tranquility® 20 Model 070 - ECM Blower
Performance capacities shown in thousands of Btuh1,950 CFM Nominal (Rated) Airfl ow Cooling, 2,100 CFM Nominal (Rated) Airfl ow Heating
Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.All performance is based upon the lower voltage of dual voltage rated units.Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.Operation below 40°F EWT is based upon a 15% methanol antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.See performance correction tables for operating conditions other than those listed above.See Performance Data Selection Notes for operation in the shaded areas.
EWT °F
GPMWPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FTAirfl ow
CFMTC SC kW HR EER HWC
Airfl ow CFM
HC kW HE LAT COP HWC
2018.0 9.5 22.0 1400
Operation not recommended1475 44.7 4.97 29.8 98.1 2.6 5.6
18.0 9.5 22.0 1950 2050 46.7 4.42 31.6 91.1 3.1 5.0
30
9.0 2.7 6.3 1400 77.0 44.8 2.86 88.8 26.9 3.5 1475 48.7 5.06 33.4 100.5 2.8 6.09.0 2.7 6.3 1950 83.2 52.7 3.01 93.5 27.7 3.7 2050 50.9 4.50 35.5 93.0 3.3 5.3
13.5 5.2 12.0 1400 75.9 43.6 2.67 87.1 28.4 3.5 1475 50.5 5.10 35.1 101.7 2.9 6.113.5 5.2 12.0 1950 82.1 51.3 2.81 91.6 29.2 3.7 2050 52.7 4.54 37.3 93.8 3.4 5.418.0 8.1 18.8 1400 75.0 42.8 2.58 85.8 29.1 3.5 1475 51.5 5.13 36.0 102.3 2.9 6.218.0 8.1 18.8 1950 81.1 50.3 2.71 90.4 29.9 3.7 2050 53.8 4.56 38.2 94.3 3.5 5.5
40
9.0 2.1 4.9 1400 77.1 45.6 3.16 90.0 24.4 3.7 1475 55.5 5.23 39.7 104.8 3.1 6.59.0 2.1 4.9 1950 83.4 53.6 3.32 94.7 25.1 3.9 2050 58.0 4.65 42.2 96.2 3.7 5.8
13.5 4.4 10.1 1400 77.2 45.2 2.95 89.3 26.2 3.5 1475 57.9 5.28 41.9 106.4 3.2 6.713.5 4.4 10.1 1950 83.5 53.1 3.10 94.0 26.9 3.7 2050 60.5 4.70 44.5 97.3 3.8 6.018.0 7.1 16.4 1400 77.0 44.8 2.85 88.8 27.0 3.5 1475 59.2 5.32 43.1 107.2 3.3 6.918.0 7.1 16.4 1950 83.2 52.7 3.00 93.4 27.7 3.7 2050 61.9 4.73 45.8 98.0 3.8 6.1
50
9.0 1.7 4.0 1400 75.8 45.4 3.47 89.7 21.8 4.3 1475 62.9 5.41 46.5 109.5 3.4 7.29.0 1.7 4.0 1950 82.0 53.5 3.65 94.5 22.5 4.5 2050 65.8 4.81 49.4 99.7 4.0 6.4
13.5 3.8 8.8 1400 76.9 45.6 3.25 90.0 23.6 3.9 1475 65.9 5.49 49.2 111.4 3.5 7.513.5 3.8 8.8 1950 83.1 53.7 3.42 94.8 24.3 4.1 2050 68.9 4.88 52.2 101.1 4.1 6.718.0 6.4 14.8 1400 77.1 45.6 3.15 89.9 24.5 3.7 1475 67.5 5.52 50.7 112.4 3.6 7.618.0 6.4 14.8 1950 83.4 53.6 3.31 94.7 25.2 3.9 2050 70.6 4.91 53.8 101.9 4.2 6.8
60
9.0 1.6 3.6 1400 73.5 44.6 3.82 88.6 19.2 5.2 1475 70.6 5.61 53.5 114.3 3.7 8.09.0 1.6 3.6 1950 79.5 52.5 4.02 93.2 19.8 5.5 2050 73.8 4.99 56.8 103.3 4.3 7.1
13.5 3.5 8.1 1400 75.2 45.2 3.58 89.5 21.0 4.6 1475 74.1 5.70 56.6 116.5 3.8 8.413.5 3.5 8.1 1950 81.3 53.2 3.76 94.2 21.6 4.8 2050 77.4 5.07 60.1 105.0 4.5 7.518.0 5.9 13.7 1400 75.9 45.5 3.46 89.8 21.9 4.3 1475 75.9 5.75 58.3 117.7 3.9 8.718.0 5.9 13.7 1950 82.1 53.5 3.64 94.5 22.6 4.5 2050 79.3 5.12 61.9 105.8 4.5 7.7
70
9.0 1.5 3.5 1400 70.5 43.4 4.21 86.7 16.7 6.4 1475 78.3 5.82 60.4 119.2 3.9 9.09.0 1.5 3.5 1950 76.2 51.0 4.43 91.3 17.2 6.7 2050 81.8 5.18 64.1 107.0 4.6 8.0
13.5 3.3 7.6 1400 72.6 44.3 3.94 88.0 18.5 5.5 1475 82.0 5.93 63.8 121.5 4.1 9.613.5 3.3 7.6 1950 78.5 52.1 4.14 92.7 19.0 5.8 2050 85.7 5.28 67.7 108.7 4.8 8.518.0 5.7 13.1 1400 73.6 44.7 3.81 88.6 19.3 5.1 1475 84.0 6.00 65.6 122.7 4.1 9.818.0 5.7 13.1 1950 79.6 52.5 4.01 93.3 19.9 5.4 2050 87.8 5.34 69.6 109.7 4.8 8.7
80
9.0 1.5 3.5 1400 66.9 41.8 4.66 84.5 14.3 7.9 1475 85.6 6.06 67.0 123.8 4.1 10.19.0 1.5 3.5 1950 72.3 49.2 4.90 89.0 14.8 8.3 2050 89.5 5.39 71.1 110.4 4.9 9.0
13.5 3.2 7.5 1400 69.3 42.9 4.36 86.0 15.9 6.8 1475 89.5 6.18 70.4 126.2 4.2 10.813.5 3.2 7.5 1950 74.9 50.4 4.58 90.6 16.4 7.2 2050 93.5 5.50 74.7 112.2 5.0 9.618.0 5.5 12.8 1400 70.5 43.4 4.21 86.8 16.7 6.4 1475 91.4 6.26 72.1 127.4 4.3 11.118.0 5.5 12.8 1950 76.2 51.0 4.43 91.3 17.2 6.7 2050 95.5 5.57 76.5 113.1 5.0 9.9
85
9.0 1.5 3.6 1400 64.9 41.0 4.9 83.4 13.3 8.8 1475 89.0 6.18 69.9 125.9 4.2 10.79.0 1.5 3.6 1950 70.1 48.2 5.17 87.8 13.6 9.3 2050 93.0 5.5 74.3 112.0 5.0 9.6
13.5 3.2 7.5 1400 67.4 42.1 4.59 84.9 14.7 7.6 1475 92.7 6.3 73.2 128.2 4.3 11.513.5 3.2 7.5 1950 72.9 49.5 4.83 89.4 15.2 8.1 2050 96.8 5.6 77.7 113.7 5.1 10.218.0 5.5 12.7 1400 68.7 42.6 4.44 85.6 15.5 7.1 1475 94.5 6.4 74.7 129.3 4.3 11.918.0 5.5 12.7 1950 74.2 50.1 4.67 90.1 16.0 7.5 2050 98.7 5.7 79.3 114.6 5.1 10.6
90
9.0 1.6 3.6 1400 62.9 40.2 5.17 82.2 12.2 9.7 1475 92.3 6.29 72.9 128.0 4.3 11.49.0 1.6 3.6 1950 68.0 47.3 5.44 86.6 12.5 10.2 2050 96.5 5.60 77.4 113.6 5.1 10.1
13.5 3.2 7.4 1400 65.5 41.3 4.83 83.7 13.6 8.5 1475 95.9 6.45 75.9 130.2 4.4 12.113.5 3.2 7.4 1950 70.8 48.5 5.08 88.2 13.9 8.9 2050 100.2 5.74 80.6 115.3 5.1 10.818.0 5.5 12.6 1400 66.8 41.8 4.67 84.5 14.3 7.9 1475 97.6 6.53 77.4 131.3 4.4 12.718.0 5.5 12.6 1950 72.2 49.2 4.91 89.0 14.7 8.3 2050 102.0 5.81 82.1 116.1 5.1 11.3
100
9.0 1.6 3.6 1400 58.8 38.5 5.76 80.1 10.2 11.8 1475
Operation not recommended
9.0 1.6 3.6 1950 63.6 45.3 6.06 84.3 10.5 12.4 205013.5 3.2 7.4 1400 61.4 39.6 5.37 81.4 11.4 10.4 147513.5 3.2 7.4 1950 66.4 46.5 5.65 85.7 11.8 10.9 205018.0 5.4 12.5 1400 62.8 40.1 5.19 82.1 12.1 9.7 147518.0 5.4 12.5 1950 67.8 47.2 5.46 86.5 12.4 10.2 2050
110
9.0 1.4 3.3 1400 54.8 37.0 6.44 78.2 8.5 14.2 14759.0 1.4 3.3 1950 59.2 43.6 6.77 82.4 8.8 14.9 2050
13.5 3.1 7.1 1400 57.3 37.9 6.01 79.3 9.5 12.6 147513.5 3.1 7.1 1950 61.9 44.6 6.32 83.5 9.8 13.3 205018.0 5.3 12.3 1400 58.6 38.4 5.80 79.9 10.1 11.9 147518.0 5.3 12.3 1950 63.3 45.2 6.10 84.1 10.4 12.5 2050
120
9.0 1.2 2.7 1400 51.0 35.9 7.24 77.1 7.1 16.9 14759.0 1.2 2.7 1950 55.2 42.2 7.61 81.1 7.3 17.8 2050
13.5 2.9 6.6 1400 53.3 36.5 6.74 77.7 7.9 15.2 147513.5 2.9 6.6 1950 57.6 43.0 7.09 81.8 8.1 16.0 205018.0 5.2 11.9 1400 54.5 36.9 6.50 78.1 8.4 14.3 147518.0 5.2 11.9 1950 58.9 43.4 6.84 82.2 8.6 15.1 2050
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
64 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Preventive Maintenance
Water Coil Maintenance(Direct ground water applications only) - If the system is installed in an area with a known high mineral content (125 P.P.M. or greater) in the water, it is best to establish a periodic maintenance schedule with the owner so the coil can be checked regularly. Consult the well water applications section of this manual for a more detailed water coil material selection. Should periodic coil cleaning be necessary, use standard coil cleaning procedures, which are compatible with the heat exchanger material and copper water lines. Generally, the more water fl owing through the unit, the less chance for scaling. Therefore, 1.5 gpm per ton [2.0 l/m per kW] is recommended as a minimum fl ow. Minimum fl ow rate for entering water temperatures below 50°F [10°C] is 2.0 gpm per ton [2.6 l/m per kW].
Water Coil Maintenance(All other water loop applications) Generally water coil maintenance is not needed for closed loop systems. However, if the piping is known to have high dirt or debris content, it is best to establish a periodic maintenance schedule with the owner so the water coil can be checked regularly. Dirty installations are typically the result of deterioration of iron or galvanized piping or components in the system. Open cooling towers requiring heavy chemical treatment and mineral buildup through water use can also contribute to higher maintenance. Should periodic coil cleaning be necessary, use standard coil cleaning procedures, which are compatible with both the heat exchanger material and copper water lines. Generally, the more water fl owing through the unit, the less chance for scaling. However, fl ow rates over 3 gpm per ton (3.9 l/m per kW) can produce water (or debris) velocities that can erode the heat exchanger wall and ultimately produce leaks.
Hot Water Generator CoilsSee water coil maintenance for ground water units. If the potable water is hard or not chemically softened, the high temperatures of the desuperheater will tend to scale even quicker than the water coil and may need more frequent inspections. In areas with extremely hard water, a HWG is not recommended.
FiltersFilters must be clean to obtain maximum performance. Filters should be inspected every month under normal operating conditions and be replaced when necessary. Units should never be operated without a fi lter.
Washable, high effi ciency, electrostatic fi lters, when dirty, can exhibit a very high pressure drop for the fan motor and reduce air fl ow, resulting in poor performance. It is especially important to provide consistent washing of these fi lters (in the opposite direction of the normal air fl ow) once per month using a high pressure wash similar to those found at self-serve car washes.
Condensate DrainIn areas where airborne bacteria may produce a “slimy” substance in the drain pan, it may be necessary to treat the drain pan chemically with an algaecide approximately every three months to minimize the problem. The condensate pan may also need to be cleaned periodically to insure indoor air quality. The condensate drain can pick up lint and dirt, especially with dirty fi lters. Inspect the drain twice a year to avoid the possibility of plugging and eventual overfl ow.
CompressorConduct annual amperage checks to insure that amp draw is no more than 10% greater than indicated on the serial plate data.
Fan MotorsAll units have lubricated fan motors. Fan motors should never be lubricated unless obvious, dry operation is suspected. Periodic maintenance oiling is not recommended, as it will result in dirt accumulating in the excess oil and cause eventual motor failure. Conduct annual dry operation check and amperage check to insure amp draw is no more than 10% greater than indicated on serial plate data.
Air CoilThe air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum clean. Care must be taken not to damage the aluminum fi ns while cleaning. CAUTION: Fin edges are sharp.
CabinetDo not allow water to stay in contact with the cabinet for long periods of time to prevent corrosion of the cabinet sheet metal. Generally, vertical cabinets are set up from the fl oor a few inches [7 - 8 cm] to prevent water from entering the cabinet. The cabinet can be cleaned using a mild detergent.
Refrigerant SystemTo maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Reference the operating charts for pressures and temperatures. Verify that air and water fl ow rates are at proper levels before servicing the refrigerant circuit.
65
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
GeneralIf operational diffi culties are encountered, perform the preliminary checks below before referring to the troubleshooting charts.• Verify that the unit is receiving electrical supply power.• Make sure the fuses in the fused disconnect switches
are intact.After completing the preliminary checks described above, inspect for other obvious problems such as leaking connections, broken or disconnected wires, etc. If everything appears to be in order, but the unit still fails to operate properly, refer to the “CXM Troubleshooting Process Flowchart” or “Functional Troubleshooting Chart.”
CXM BoardCXM board troubleshooting in general is best summarized as simply verifying inputs and outputs. After inputs and outputs have been verifi ed, board operation is confi rmed and the problem must be elsewhere. Below are some general guidelines for troubleshooting the CXM control.
Field InputsAll inputs are 24VAC from the thermostat and can be verifi ed using a volt meter between C and Y, G, O, W. 24VAC will be present at the terminal (for example, between “Y” and “C”) if the thermostat is sending an input to the CXM board.
Sensor InputsAll sensor inputs are ‘paired wires’ connecting each component to the board. Therefore, continuity on pressure switches, for example can be checked at the board connector.
The thermistor resistance should be measured with the connector removed so that only the impedance of the thermistor is measured. If desired, this reading can be compared to the thermistor resistance chart shown in the CXM AOM manual. An ice bath can be used to check calibration of the thermistor.
OutputsThe compressor relay is 24VAC and can be verifi ed using a voltmeter. The fan signal is passed through the board to the external fan relay (units with PSC motors only). The alarm relay can either be 24VAC as shipped or dry contacts for use with DDC controls by clipping the JW1 jumper. Electric heat outputs are 24VDC “ground sinking” and require a volt meter set for DC to verify operation. The terminal marked “24VDC” is the 24VDC supply to the electric heat board; terminal “EH1” is stage 1 electric heat; terminal “EH2” is stage 2 electric heat. When electric heat is energized (thermostat is sending a “W” input to the CXM controller), there will be 24VDC between terminal “24VDC” and “EH1” (stage 1 electric heat) and/or “EH2” (stage 2 electric heat). A reading of 0VDC between “24VDC” and “EH1” or “EH2” will indicate that the CXM board is NOT sending an output signal to the electric heat board.
Test ModeTest mode can be entered for 20 minutes by shorting the test pins. The CXM board will automatically exit test mode after 20 minutes.
CXM Troubleshooting Process Flowchart/Functional Troubleshooting ChartThe “CXM Functional Troubleshooting Process Flowchart” is a quick overview of how to start diagnosing a suspected problem, using the fault recognition features of the CXM board. The “Functional Troubleshooting Chart” on the following page is a more comprehensive method for identifying a number of malfunctions that may occur, and is not limited to just the CXM controls. Within the chart are fi ve columns:• The “Fault” column describes the symptoms. • Columns 2 and 3 identify in which mode the fault is likey to
occur, heating or cooling.• The “Possible Cause column” identifi es the most likely
sources of the problem.• The “Solution” column describes what should be done to
correct the problem.
WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING.Failure to disconnect power before servicing can cause severe personal injury or death.
Troubleshooting
WARNING!
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
66 G e o t h e r m a l H e a t i n g a n d C o o l i n g
See “Does not Operate
in Clg”
See “Only Comp Runs”
Start
Did Unit Attempt to
Start?
Did Unit Lockout at Start-up?
Unit Short Cycles?
Only Fan Runs?
Only Compressor
Runs?
Did unit lockout after a period of
operation?
Does unit operate in cooling?
Unit is OK!‘See Performance
Troubleshooting’ for further help
Check Main power (see power
problems)
Check fault LED code on control board
Yes
No
No
No
No
No
Yes
No
Yes
See HP Fault
See LP/LOC
Fault
See FP1 Fault
See FP2 Fault
See Condensate
Fault
See Over/ Under
Voltage
No fault shown
Replace CXM
See “Unit short
cycles”
See “Only Fan Runs”
No
Yes
Yes
Yes
Yes
CXM Functional Troubleshooting Flow Chart
CXM Process Flow Chart
WARNING! WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING.Failure to disconnect power before servicing can cause severe personal injury or death.
67
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Functional Troubleshooting
Fault Htg Clg Possible Cause Solution
Main power problems X X Green Status LED Off
Check line voltage circuit breaker and disconnect.
Check for line voltage between L1 and L2 on the contactor.
Check for 24VAC between R and C on DXM2
Check primary/secondary voltage on transformer.
HP/HPWS Fault Code 2
High Pressure
X Reduced or no water fl ow in coolingCheck pump operation or valve operation/setting.
Check water fl ow adjust to proper fl ow rate.
X Water Temperature out of range in cooling Bring water temp within design parameters.
X Reduced or no air fl ow in heating
Check for dirty air fi lter and clean or replace.
Check fan motor operation and airfl ow restrictions.
Dirty Air Coil- construction dust etc.
Too high of external static. Check static vs blower table.
X Air temperature out of range in heating Bring return air temp within design parameters.
X X Overcharged with refrigerant Check superheat/subcooling vs typical operating condition table.
X X Bad HP Switch Check switch continuity and operation. Replace.
X X Water pressure too high Reduce water pressure to below 300 psig
X X Bad high pressure water switch Replace HPWS
LP/LOC FaultCode 3
Low Pressure / Loss of Charge
X X Insuffi cient charge Check for refrigerant leaks
X Compressor pump down at start-up Check charge and start-up water fl ow.
LT1 FaultCode 4
Water coil low temperature limit
X Reduced or no water fl ow in heating
Check pump operation or water valve operation/setting.
Plugged strainer or fi lter. Clean or replace..
Check water fl ow adjust to proper fl ow rate.
X Inadequate antifreeze level Check antifreeze density with hydrometer.
XImproper temperature limit setting (30°F vs 10°F [-1°C vs -2°C])
Clip JW3 jumper for antifreeze (10°F [-12°C]) use.
X Water Temperature out of range Bring water temp within design parameters.
X X Bad thermistor Check temp and impedance correlation per chart
LT2 FaultCode 5
Air coil low temperature limit
X Reduced or no air fl ow in cooling
Check for dirty air fi lter and clean or replace.
Check fan motor operation and airfl ow restrictions.
Too high of external static. Check static vs blower table.
X Air Temperature out of range Too much cold vent air? Bring entering air temp within design parameters.
XImproper temperature limit setting (30°F vs 10°F [-1°C vs -12°C])
Normal airside applications will require 30°F [-1°C] only.
X X Bad thermistor Check temp and impedance correlation per chart.
Condensate Fault Code 6
X X Blocked drain Check for blockage and clean drain.
X X Improper trap Check trap dimensions and location ahead of vent.
X Poor drainage
Check for piping slope away from unit.
Check slope of unit toward outlet.
Poor venting. Check vent location.
X Moisture on sensor Check for moisture shorting to air coil.
X X Plugged air fi lter Replace air fi lter.
x X Restricted Return Air Flow Find and eliminate restriction. Increase return duct and/or grille size.
Over/Under Voltage Code 7
(Auto resetting)
X X Under Voltage
Check power supply and 24VAC voltage before and during operation.
Check power supply wire size.
Check compressor starting. Need hard start kit?
Check 24VAC and unit transformer tap for correct power supply voltage.
X X Over VoltageCheck power supply voltage and 24VAC before and during operation.
Check 24VAC and unit transformer tap for correct power supply voltage.
Unit Performance SentinelCode 8
X Heating mode LT2>125°F [52°C] Check for poor air fl ow or overcharged unit.
XCooling Mode LT1>125°F [52°C] OR LT2< 40ºF [4ºC])
Check for poor water fl ow, or air fl ow.
No Fault Code Shown
X X No compressor operation See "Only Fan Operates".
X X Compressor overload Check and replace if necessary.
X X Control board Reset power and check operation.
Unit Short Cycles
X X Dirty air fi lter Check and clean air fi lter.
X X Unit in "test mode" Reset power or wait 20 minutes for auto exit.
X X Unit selection Unit may be oversized for space. Check sizing for actual load of space.
X X Compressor overload Check and replace if necessary
Only Fan Runs
X X Thermostat position Ensure thermostat set for heating or cooling operation.
X X Unit locked out Check for lockout codes. Reset power.
X X Compressor Overload Check compressor overload. Replace if necessary.
X X Thermostat wiringCheck thermostat wiring at heat pump. Jumper Y1 and R for compressor operation in test mode.
Only Compressor Runs
X X Thermostat wiring Check G wiring at heat pump. Jumper G and R for fan operation
X XFan motor relay
Jumper G and R for fan operation. Check for voltage at blower relay.
X X Check fan power enable relay operation (if present).
X X Fan motor Check for line voltage at motor. Check capacitor.
X X Thermostat wiringCheck thermostat wiring at heat pump. Jumper Y1 and R for compressor operation in test mode
Unit Doesn’t Operate
in Cooling
X Reversing valve
Set for cooling demand and check 24VAC on RV coil and at DXM2 board.
If RV is stuck, run high pressure up by reducing water fl ow and while operating engage and disengage RV coil voltage to push valve.
X Thermostat setup Check for ‘O’ RV setup not ‘B’.
X Thermostat wiringCheck O wiring at heat pump. Jumper O and R for RV coil ‘click’ when compressor starts.
X Thermostat wiring
Put thermostat in cooling mode. Check 24 VAC on O (check between C and O); check for 24 VAC on W (check between W and C). There should be voltage on O, but not on W. If voltage is present on W, thermostat may be bad or wired incorrectly.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
68 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Performance Troubleshooting
Performance Troubleshooting Htg Clg Possible Cause Solution
Insuffi cient capacity/ Not
cooling or heating
X X Dirty fi lter Replace or clean.
X Reduced or no air fl ow in heating
Check for dirty air fi lter and clean or replace.
Check fan motor operation and airfl ow restrictions.
Too high of external static. Check static vs. blower table.
X Reduced or no air fl ow in cooling
Check for dirty air fi lter and clean or replace.
Check fan motor operation and airfl ow restrictions.
Too high of external static. Check static vs. blower table.
X X Leaky duct workCheck supply and return air temperatures at the unit and at distant duct registers if signifi cantly different, duct leaks are present.
X X Low refrigerant charge Check superheat and subcooling per chart.
X X Restricted metering device Check superheat and subcooling per chart. Replace.
X Defective reversing valve Perform RV touch test.
X X Thermostat improperly located Check location and for air drafts behind stat.
X X Unit undersized Recheck loads & sizing. Check sensible clg. load and heat pump capacity.
X X Scaling in water heat exchanger Perform scaling check and clean if necessary.
X X Inlet water too hot or too cold Check load, loop sizing, loop backfi ll, ground moisture.
High Head Pressure
X Reduced or no air fl ow in heating
Check for dirty air fi lter and clean or replace.
Check fan motor operation and air fl ow restrictions.
Too high of external static. Check static vs. blower table.
X Reduced or no water fl ow in coolingCheck pump operation or valve operation/setting.
Check water fl ow. Adjust to proper fl ow rate.
X Inlet water too hot Check load, loop sizing, loop backfi ll, ground moisture.
X Air temperature out of range in heating Bring return air temperature within design parameters.
X Scaling in water heat exchanger Perform scaling check and clean if necessary.
X X Unit overcharged Check superheat and subcooling. Re-weigh in charge.
X X Non-condensables in system Vacuum system and re-weigh in charge.
X X Restricted metering device. Check superheat and subcooling per chart. Replace.
Low Suction Pressure
X Reduced water fl ow in heating.
Check pump operation or water valve operation/setting.
Plugged strainer or fi lter. Clean or replace.
Check water fl ow. Adjust to proper fl ow rate.
X Water temperature out of range. Bring water temperature within design parameters.
X Reduced air fl ow in cooling.
Check for dirty air fi lter and clean or replace.
Check fan motor operation and air fl ow restrictions.
Too high of external static. Check static vs. blower table.
X Air temperature out of range Too much cold vent air? Bring entering air temperature within design parameters.
X X Insuffi cient charge Check for refrigerant leaks.
Low Discharge Air Temperature in Heating
X Too high of air fl ow Check fan motor speed selection and air fl ow chart.
X Poor performance See ‘Insuffi cient Capacity’
High humidityX Too high of air fl ow Check fan motor speed selection and airfl ow chart.
X Unit oversized Recheck loads & sizing. Check sensible clg load and heat pump capacity.
69
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Troubleshooting Form
Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis using P/T ports to determine water fl ow and temperature diff erence. If water-side analysis shows poor performance, refrigerant troubleshooting may be required. Connect refrigerant gauges as a last resort.
Packaged Water-to-Air RP929
Troubleshooting Form
Customer: Loop Type: Startup Date:
Model #: Serial #: Antifreeze Type & %:
Complaint:
Description Heating Cooling Notes
Water Side Analysis
1 Water In Temp.
2 Water Out Temp. Temp. Diff. =
3 Water In Pressure
4 Water Out Pressure
4a Pressure Drop
4b GPM
Heat of Extraction (Absorption) or Heat of Rejection:
HE or HR (Btuh) = Enter HE or HR:
Flow Rate (GPM) x Temp. Diff (deg F) x Fluid Factor
Refrigerant Analysis
5 Suction Temp.
6 Suction Pressure
6a Saturation Temp.
6b Superheat
7 Discharge Temp.
8 Discharge Pressure
8a Saturation Temp.
8b Subcooling
9 Liquid Line Temp
10 Return Air Temp.
11 Supply Air Temp. Temp. Diff. =
Voltage
Compress Amps
COMPRESSOR
DISCHARGE
SUCTION
HWG**
AIRCOIL
EXPANSIONVALVE FILTER
DRIER*
REVERSINGVALVE
HEATING POSITION
5
COAX
11
42
31
8
7
6
9 LT2:HEATINGLIQUIDLINE
CONDENSER (HEATING)EVAPORATOR (COOLING) CONDENSER (COOLING)
EVAPORATOR (HEATING)
* Filter drier not used for some R-22 units.
** Turn off HWG before troubleshooting.
REFRIG FLOW - HEATING REFRIG FLOW - COOLING
Source
COOLING POSITION
9 LT1:COOLINGLIQUIDLINE
10
REFRIGERANT: R-22 R-410AOPERATING MODE: HEATING COOLING
Fluid Factor:500 (Water); 485 (Antifreeze)
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
70 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Warranty
71
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 AR e v : J a n u a r y 3 0 , 2 0 1 7
c l i m a t e m a s t e r. c o m
Notes
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A :R e v : J a n u a r y 3 0 , 2 0 1 7
72 G e o t h e r m a l H e a t i n g a n d C o o l i n g
Revision History
97B0113N01
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warran-ties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.
Engineered and assembled in the USA
© ClimateMaster, Inc. 2006
*97B0113N01*
7300 S.W. 44th StreetOklahoma City, OK 73179
Phone: 405-745-6000Fax: 405-745-6058climatemaster.com
Rev.:January 30,2017
Date Page # Description30 Jan., 17 20 Add Caution
10 October 16 5 Text Update6 October 16 69 Troubleshooting Form
6 Feb, 16 72 updated certifi cation logos22 July, 15 49, 50 Updated HWC Data6 Oct., 14 69 Updated Troubleshooting Form
18 Aug., 14 All GWHP Loop Piping Desc., Water Quality Notes, TT LWT Data Edited31 March, 14 All TS 024-070 Rev. C Updates, TS 070 PSC Removed
7 June, 13 19 Updated Electrical Data - Ext Pump FLA7 June, 13 5, 33 Edit Cabinet Pitch Text, Update EAT Limits10 Jan., 13 13 Antifreeze Percentage Table Updated7 Jan., 13 47-62 TS Performance Data Added
19 Nov., 12 All First Published