ES2™
Gas Fired, Chimney Vented,Cast Iron Water Boiler
• ConsistsoftheIntelligentHydronicControland IQOptionPanel
Intelligent Hydronic Control• Providesfastandeasy“outofthebox”installation.
• Simplecodesconveyboilerstatusandeliminateguesswork
• Combinesaquastat,relay,andignitionfunctionsintoasinglemodule
• Twocustomizableintegratedswitchingrelaysforeasyadditionofadditionalheatingzoneorindirectwaterheater
IQ Option Panel• Enablestheeasyplug&playinstallationofoptionalfeaturessuchasoutdoorreset,LWCO,andhighlimit
Optional Touchscreen• LCDdisplaysallboilersettings,diagnostics,andtroubleshootinginsentences,notcodes
boilercontrol
optionpanel
optioncard
controlsystem
85% Efficient!
ANYWHEREUNMATCHED
ANYWHEREUNMATCHED
ANYWHEREUNMATCHED
ANYWHEREUNMATCHED
ANYWHEREUNMATCHED
• 85%AFUE
• Electronicignition
• Easy,intelligentIQControlSystem™
• Outdoorresetavailable–increasesefficiency by15-20%
• 70–280MBH(7sizes)
• Industrystandardtappinglocationsfitthousands ofexistingboilerinstallations
• Reliable,American-madecastironheat exchangeracceptsreturnwateraslowas110°F
• Lifetimelimitedwarranty
©2015U.S.BoilerCompany,Inc.-Lancaster,PAPhone:1-888-432-8887PrintedintheU.S.A.
FormNo.HYDL09081-2/1510mswww.usboiler.net
ES2 Dimensions & Connections
Model
Dimensions (inches) Connections (inches) WaterContent (gal.)Width Height Depth Supply Return
Gas Valve
Relief Valve
ES23 12-3/4 41 33 1-1/4 1-1/4 1/2 3/4 2ES24 15-1/2 41 33 1-1/4 1-1/4 1/2 3/4 3ES25 18-1/2 41 33 1-1/4 1-1/4 1/2 3/4 4ES26 21-1/2 41 33 1-1/4 1-1/4 1/2 3/4 5ES27 24-3/4 41 33 1-1/4 1-1/4 3/4 3/4 6ES28 27-3/4 41 33 1-1/4 1-1/4 3/4 3/4 7ES29 30-3/4 41 33 1-1/4 1-1/4 3/4 3/4 8
Available for natural or LP gasRatings shown are based on certification to 2,000 ft. For elevations above 2,000 ft, use industry standard derating (4% per 1,000 ft.)All ES2s are shipped with 30 psi relief valves, MAWP is 50 psi.Net AHRI Water Ratings shown based on a piping and pickup allowance of 1.15. Consult manufacturer before selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
64”
FLOORLINE
23”**
41”
4” “W” 1”
40”FLUE
34”ELECTRICAL
27”SUPPLY
18”GAS
15”RETURN
FLOORLINE0”
0” 13” 24”29”31”
4”
43”
6”
VENTILATION AIR INLET OPENINGS***
12” MAX
12” MAX
6” MIN*
NOTES:Caution: chimney, liner, and vent connector must meet requirements specified by manufacturer’s installation instructions* Minimalradialdistancearoundventpipeandbreeching** Addheightrequiredtomaintain6”clearancefromallbreechingcomponents*** Areaofeachopening1sq.inchforeach1,000BTUHinput-withminimumof100sq.inches.Heightofopeningshouldbehalfthewidth.
ES2: Technical InformationES2 Ratings & Specifications
Model AFUE%Input
(MBH)
DOE HeatingCapacity(MBH)
Net AHRI (MBH)
Vent Size(Inches)
Approx. Shipping Weight. (lbs.)
ES23 85 70 59 51 4 254ES24 85 105 89 77 5 301ES25 85 140 119 103 6 353ES26 85 175 149 130 6 405ES27 85 210 178 155 7 464ES28 85 245 208 181 7 514ES29 85 280 238 207 8 564
Standard Equipment • Insulatedsleek,modernjacket• Integrateddraftdiverter,damperandconnectorincluded• Heavygauge1”and1-1/2”baseinsulation• IntelligentHydronicControl–Simpleself-diagnostic controlsystemwith3-digitreadoutforstatussettings anderrors• IQOptionPanel,acceptsplug&playIQOptionCardsfor –OutdoorresetwithDHWpriority –Autoormanualresetlowwatercutoff –Autoormanualauxilliaryhighlimit• Step-openingredundantgasvalve• Stainlesssteelfluebaffles• 110°Fminimumreturntemperaturerating• Sparkignitionwithretry• User-friendlywiringwith120VJ-box• Circulator• Castironsectionassembly• Resettableblockedventswitch• Boilerdrainvalve• Castironsupplymanifoldwithsafetyreliefvalvetapping
ASM