Masterpact Schneider Electric28
+
+
CCM modbus
+
CE
CD
CT
3
OFSDEPFCH
MXXF
CECT
CD 5
CCCC
CC
4
2
1
communicationBus
The COM option is required for integrationof the circuit breaker or switch-disconnectorin a supervision system.Masterpact uses the Digipact or Modbuscommunications protocol for fullcompatibility with the SMS PowerLogicelectrical-installation management systems.An external gateway is available forcommunication on other networks:c Profibusc Ethernet…
Digipact «device»communication module.
Digipact «craddle»communication module
0564
3105
6401
For fixed devices, the COM option is made up of:c a "device" communication module, installed behind the Micrologic control unitand supplied with its set of sensors (OF, SDE ,PF and CH micro-contacts) and itskit for connection to XF and MX communicating voltage releases.For drawout devices, the COM option is made up of:c a "device" communication module, installed behind the Micrologic control unitand supplied with its set of sensors (OF, SDE, PF and CH micro-contacts) and itskit for connection to XF and MX communicating voltage releasesc a "craddle" communication module supplied separately with its set of sensors(CE, CD and CT contacts).Status indication by the COM option is independent of the device indicationcontacts. These contacts remain available for conventional uses.Digipact or Modbus «Device» communication moduleThis module is independent of the control unit. It receives and transmits informationon the communication network. An infra-red link transmits data between the controlunit and the communication module.Consumption: 30 mA, 24 V.Digipact or Modbus «craddle» communication moduleThis module is independent of the control unit. With Modbus "craddle"communication module, this module makes it possible to address the craddle andto maintain the address when the circuit breaker is in the disconnected position.Consumption: 30 mA, 24 V.XF and MX communicating voltage releasesThe XF and MX communicating voltage releases are equipped for connection tothe "device" communication module.The remote-tripping function (second MX or MN) are independent of thecommunication option. They are not equipped for connection to the "device"communication module.
1 «Device» communication module2 «Craddle» communication module3 OF, SDE, PF and CH «device» sensors4 CE, CD and CT «craddle» sensors5 MX and XF release
E47
073
Modbus «craddle»communication module : hard wire
: communication bus
Modbus «device»communication module
Note: eco COMThe eco COM Modbus is intended to fit the circuit breaker with module display(DMB300, DMC300…).
CommunicationCOM option in Masterpact
Functionsand characteristics
E45
183
0564
31
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5428
Masterpact Schneider Electric29
The Masterpact switch-disconnectors are compatible only with the Digipact COMoption.
The Masterpact circuit breakers are compatible with the Digipact or Modbus COMoption.The COM option may be used with all types of control units to:c identify the devicec indicate status conditionsc control the device.Depending on the different types of Micrologic (A, P, H) control units, the COMoption also offers:c setting of the protection and alarms functionsc analysis of the AC-power parameters for operating-assistance and maintenancepurposes
E47
071
ModuleEventTime
POWERLOGIC System Manager Demo
Ready
File Edit View Setup ToolsControl Display Reports Window Help
ONLINE: DEMO 9:30No working system
5 secondsSampling Mode : MANUAL
0,00
0,20
0,40
0,60
0,80
1,00
1,20
H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12
% F
unda
men
tal
Harmonics
Phase A-N Voltage - Harmonics Analysis
Phase 1-N
Harmonics(RMS)
H2: 0.01H3: 0.45H4: 0.03H5: 0.45H6: 0.04H7: 1.27H8: 0.05H9: 0.42H10: 0.01H11: 1.03H12: 0.07
H1: 118.09
OK
Fundamental:
RMS:
RMS-H:
Peak:
CF:
THD:
Overview of functions
switch-disconnector with circuit breaker withcommunication bus communication busDigipact Modbus Digipact Modbus
device identificationaddress c - A P H A P H
calibre - - A P H A P H
type of device - - P H
type of control unit - - A P H A P H
type of long-time rating plug - - A P H A P H
status indicationsON/OFF OF c - A P H A P H
spring charged CH c - A P H A P H
ready to close PF c - A P H A P H
fault-trip SDE - - A P H A P H
connected/disconnected/test c - A P H A P Hposition CE/CD/CT
commandesopening / closing MX/XF c - A P H A P H
spring charging - -reset of the mechanical - -indicator
protections and alarms settingsreading of protections settings A P H A P H
writing of fine settings in the range P Himposed by the adjustment dialsreading/writing of alarms (délestage, relestage, M2C… ) P H
reading/writing of alarms personnalisables H
operating and maintenance aidsmeasurement
current A P H A P H
voltages, frequency, power, etc. P H P H
power quality: fundamental, harmonics H
programming of demand metering P H
fault readingstype of fault A P H
interrupted current P H
waveform captureon faults H
on demand or programmed H
histories and logstrip history P H
alarm history P H
event logs P H
indicatorscounter operation A P H A P H
contact wear P H
maintenance register P H
Note.See the description of the Micrologic control units for further details on protection andalarms, measurements, waveform capture, histories, logs and maintenance indicators.
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5429
Masterpact Schneider Electric30
CommunicationMasterpact in a communicationnetwork
Functionsand characteristics
E67
968
MasterpactMasterpact
pulsar SV
� � � � � � �� � � �
N°1N°1
1 3
OK
error
com
24V
com
error
JBus
BBus
resetAp
IgI ∆nIsd
I iIr
Micrologic 70
Reset
O OFF
discharged
0 1 2 5 3
push OFF
push ON
Ics = 100% Icu
220/440
525
690
100
100
85
Icw 85kA/1s
NX 32 H 2
cat.B
IEC 947-2
UTE VDE BS CEI UNE AS NEMA
EN 60947-2
50/60Hz
UeIcu
(V)
(kA)
volets
shutters
Test
CD3 CD2 CD1
CE6 CE5 CE4
Com UC1 UC2 UC3 UC4 M2C UC2 SDE2 CE3 CE2 CE1MN MX1 XF PF MCH
OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11
OC24 OC23 OC22 OC21 OC14 OC13 OC12
OF24244
242241
OF23234
232231
OF22224
222221
OF21214
212211
OF14144
142141
OF13134
132131
OF12124
122121
OF11114
112111
OF444
4241
3231
OF334
OF224
2221
OF114
1211
CT3934
932931
CT2924
922921
CT1914
912911
MN/MX2D2/ C12
/ C13D1/ C11
MX1C2
C3C1
XFA2
A3A1
PF254
252251
MCHB2
B3B1
334 324 314CE3
332331
CE2
322321
CE1
312311
Com UC1 UC2 UC3 UC4SDE1
E5E3
E1
E6E4
E2
Z5Z3
Z1
M1Z4
Z2
M2T3
T1
M3T4
T2
F2 +VN
F1 -
V3V2
V1
484/ Q3474/ Q2
471/ Q1
184/ K2182
181/ K1
8482
81M2C/M6C
CD3834
832831
CD2824
822821
CD1814
812811
resetAp
IgI ∆nIsd
I iIr
Micrologic 70
Reset
O OFF
discharged
0 1 2 5 3
push OFF
push ON
Ics = 100% Icu
220/440
525
690
100
100
85
Icw 85kA/1s
NX 32 H 2
cat.B
IEC 947-2
UTE VDE BS CEI UNE AS NEMA
EN 60947-2
50/60Hz
UeIcu
(V)
(kA)
volets
shutters
Test
CD3 CD2 CD1
CE6 CE5 CE4
Com UC1 UC2 UC3 UC4 M2C UC2 SDE2 CE3 CE2 CE1MN MX1 XF PF MCH
OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11
OC24 OC23 OC22 OC21 OC14 OC13 OC12
OF24244
242241
OF23234
232231
OF22224
222221
OF21214
212211
OF14144
142141
OF13134
132131
OF12124
122121
OF11114
112111
OF444
4241
3231
OF334
OF224
2221
OF114
1211
CT3934
932931
CT2924
922921
CT1914
912911
MN/MX2D2/ C12
/ C13D1/ C11
MX1C2
C3C1
XFA2
A3A1
PF254
252251
MCHB2
B3B1
334 324 314CE3
332331
CE2
322321
CE1
312311
Com UC1 UC2 UC3 UC4SDE1
E5E3
E1
E6E4
E2
Z5Z3
Z1
M1Z4
Z2
M2T3
T1
M3T4
T2
F2 +VN
F1 -
V3V2
V1
484/ Q3474/ Q2
471/ Q1
184/ K2182
181/ K1
8482
81M2C/M6C
CD3834
832831
CD2824
822821
CD1814
812811
RS 485
RS 232C,Ethernet
Data concentratorDC150
Digipact Bus ModBUS Bus
Device
CommunicationBus
Communicationinterface
Software
DevicesCircuit breakers equipped with Micrologic control units may be connected to eithera Digipact or Modbus communication bus. The information made availabledepends on the type of Micrologic control unit (A, P or H) and on the type ofcommunication bus (Digipact or Modbus).Switch-disconnectors may be connected exclusively to the Digipact communicationbus.
Communication bus
DigipactThe Digipact bus is the internal bus of the low-voltage switchboard in which theDigipact communicating devices are installed (Masterpact with Digipact COM,PM150, SC150, UA150, etc.). This bus must be equipped with a DC150 dataconcentrator (see the Powerlogic System catalogue).AddressesAddressing is carried out by the DC150 data concentrator.Number of devicesThe maximum number of devices that may be connected to the Digipact bus iscalculated in terms of “communication points”. These points correspond to theamount of traffic the bus can handle. The total number of points for the variousdevices connected to a single bus must not exceed 100.If the required devices represent more than 100 points, add a second Digipactinternal bus.
Communicating device Number of pointsDC150 data concentrator 4Micrologic + Digipact COM 4PM150 4SC150 4UA150 4
Length of busThe maximum recommended length for the Digipact internal bus is 200 meters.Bus power sourcePower is supplied by the DC150 data concentrator (24 V)..
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5430
Masterpact Schneider Electric31
ModbusThe Modbus RS485 (JBus) system is an open bus on which communicatingModbus devices (Masterpact with Modbus COM, PM300, Sepam, Vigilohm, etc.)are installed. All types of PLCs and microcomputers may be connected to the bus.AddressesThe software layer of the Modbus protocol can manage up to 255 addresses (1 to 255).The “device” communication module comprises three addresses linked to:b circuit-breaker manager;b measurement manager;b protection manager.The “craddle” communication module comprises one address linked to:b the craddle manager.The division of the system into four managers secures data exchange with thesupervision system and the circuit-breaker actuators.The manager addresses are automatically derived from the circuit-breaker address@xx entered via the Micrologic control unit (the default address is 47).
logic addresses@xx Circuit-breaker manager (1 to 47)@xx + 50 Craddle manager (51 to 97)@xx + 200 Measurement managers (201 to 247)@xx + 100 Protection manager (101 to 147)
Number of devicesThe maximum number of devices that may be connected to the Modbus busdepends on the type of device (Masterpact with Modbus COM, PM300, Sepam,Vigilohm, etc.), the baud rate (19200 is recommended), the volume of dataexchanged and the desired response time. The RS485 physical layer offers up to32 connection points on the bus (1 master, 31 slaves).A fixed device requires only one connection point (communication module on thedevice).A drawout device uses two connection points (communication modules on thedevice and on the craddle).The number must never exceed 31 fixed devices or 15 drawout devices.Length of busThe maximum recommended length for the Modbus bus is 1200 meters.Bus power sourceA 24 V DC power supply is required (less than 20% ripple, insulation class II).
Communication interfaceThe Modbus bus may be connected to the central processing device in any ofthree manners:b direct link to a PLC. The communication interface is not required if the PLC isequipped with a Modbus port;b direct link to a computer. The Modbus (RS485) / Serial port (RS232)communication interface is required;b connection to a TCP/IP (Ethernet) network. The Modbus (RS485) / TCP/IP(Ethernet) communication interface is required.
SoftwareTo make use of the information provided by the communicating devices, softwarewith a Modbus driver must be used.
Micrologic utilitiesThis is a set of Modbus drivers that may be used with a PC to:b display the variables (I, U, P, E, etc.) with the DDS (Data Display Software)application;b read/write the settings with the RSS (Remote Setting Software) application;b remotely control (ON / OFF) the device with the CSS (Control CommandSoftware) application.These softwares are available upon request.
SMS (System Manager Software)SMS is a software to monitor LV and/or MV electrical energy.The SMS family includes a software range depending on the application andfunction, from single product monitoring to the management of a multiple building:cPower Meter and Circuit Monitor unitscLV devicescSepam units.
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5431
Masterpact Schneider Electric32
Rear connectionhorizontal vertical
Simply turn a horizontal rear connector 90° to make it a vertical connector.
Front connection
Mixed connection
Note.Masterpact circuit breakers can be connected indifferently with bare-copper, tinned-copper and tinned-aluminium conductors, requiring no particular treatment.
Three types of connection are available:c vertical or horizontal rear connectionc front connectionc mixed connection.The solutions presented are similar inprinciple for all Masterpact NT and NWfixed and drawout devices..
ConnectionsOverview of solutions
Functionsand characteristics
0564
32
0564
33
0564
3405
6435
0564
36
0564
37
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5532
Masterpact Schneider Electric33
Type of accessory Masterpact NT06 to NT16 Masterpact NW08 to NW63
fixed drawout fixed drawoutfront rear front rear front rear front rearconnection connection connection connection connection connection connection connection
Optional accessories
E47
064
E46
889
E46
431
E46
431
E46
428
E46
426
E79
058
E46
428
E46
428
Cable lugadapters
Vertical connectionadapters
Bare-cable connectorsand connector shield
E47
067
E47
068
E47
066
Safety shutterswith padlocking
Spreaders
Disconnectablefront-connectionadapter
Shutter positionindication and locking
Masterpact M replacement kitA set of connection parts is available to allow replacement of a Masterpact M08 toM32 circuit breaker by a Masterpact NW without modifying the busbars (pleaseconsult us).
Mounting on a switchboard backplate using special bracketsMasterpact NT and NW fixed front-connected circuit breakers can be installedon a backplate without any additional accessories.Masterpact NW circuit breakers require a set of special brackets.
E46
426
E46
427
E46
427
E70
745Arc chute screen
max. 4000 A
Interphasebarriers
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5633
Masterpact Schneider Electric34
ConnectionsOptional accessories
Functionsand characteristics
Bare-cable connectors and connector shieldThe connectors can be mounted on fixed front-connected devices to allowconnection using bare cables. They are supplied with a connector shield.They are designed to connect four 240 mm2 cables each.
Vertical-connection adaptersMounted on front-connected devices or craddle, the adapters facilitate connectionto a set of vertical busbars.
Cable-lug adaptersCable-lug adapters are used in conjunction with vertical rear connectors or withvertical-connection adapters.They can be used to connect a number of cables fitted with lugs.To ensure adequate mechanical strength, the connectors must be secured togethervia spacers.
Interphase barriersThese barriers are flexible insulated partitions used to reinforce isolation ofconnection points in installations with busbars, whether insulated or not.For Masterpact NT/NW devices, they are installed vertically between rearconnection terminals.
SpreadersMounted on the front or rear connectors, spreaders are used to increase thedistance between bars in certain installation configurations.
Arc chute screenFor Masterpact NT fixed, front connected and using vertical-connection adaptersfront oriented, it is mandatory to install arc chute screen in order to comply with thesafety perimeter.
0564
3805
6440
0564
4105
6415
0564
42
Ipush ON
O OFF
discharged
Opush OFF
E70
746
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5634
Masterpact Schneider Electric35
0564
43 Disconnectable front-connection adapterMounted on a fixed front-connected device, the adapter simplifies replacement of afixed device by enabling fast disconnection from the front.
Safety shuttersMounted on the craddle, the safety shutters automatically block access to thedisconnecting contact cluster when the device is in the disconnected or testpositions (degree of protection IP 20) When the device is removed from its craddle,no live parts are accessible.The shutter-locking system is made up of a moving block that can be padlocked(padlock not supplied). The block:* prevents connection of the device* locks the shutters in the closed positionFor Masterpact NW08 to NW63A support at the back of the craddle is used to store the blocks when they are notused.* 2 blocks for NW08 to NW40* 4 blocks for NW40b to NW63.
Shutter position indication and locking on front faceThis option located on the craddle front plate indicates that the shutters are closed.It is possible to independently or separately padlock the two shutters using one tothree padlocks (not supplied).
0564
45E
4747
6
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5635
Masterpact Schneider Electric36
resetAp
IgI ∆nIsd
I iIr
Micrologic 70
Opush OFF
Ipush ON
O OFF
discharged
0 1 2 5 3
Ics = 100% Icu
IEC 947-2� � � � � � � � � � �
NW 1250 H1
Ui 1000V Uimp 12kV
Ue(V)220/240
480/690
Icu(kA)
10085
Uimp 8kV1
2
9
8
7
654
3
LockingOn the device
Functionsand characteristics
1 reset button for mechanicaltrip indication
2 OFF pushbutton3 OFF position lock4 electrical closing
pushbutton5 ON pushbutton6 springs charged indication7 pushbutton locking8 contact position indication9 operation counter
E47
062
Pushbutton lockingThe transparent cover blocks access to the pushbuttons used to open and closethe device.It is possible to independently lock the opening button and the closing button. Thelocking device is often combined with a remote operating mechanism.The pushbuttons may be locked using either:c three padlocks (not supplied)c lead sealc two screws.
Device locking in the OFF positionThe circuit breaker is locked in the OFF position by physically maintaining theopening pushbutton pressed down:c using padlocks (one to three padlocks, not supplied)c using keylocks (one or two different keylocks, supplied).Keys may be removed only when locking is effective (Profalux or Ronis type locks).The keylocks are available in any of the following configurations:c one keylockc one keylock mounted on the device + one identical keylock supplied separatelyfor interlocking with another devicec two different key locks for double locking.Profalux and Ronis keylocks are compatible with each other.A locking kit (without locks) is available for installation of one or two keylocks(Ronis, Profalux, Kirk or Castell).Accessory-compatibilityFor Masterpact NT: 3 padlocks or 1 keylockFor Masterpact NW: 3 padlocks and/or 2 keylocks
Cable-type door interlockThis option prevents door opening when the circuit breaker is closed and preventscircuit breaker closing when the door is open.For this, a special plate associated with a lock and a cable is mounted on the rightside of the circuit breaker.With this interlock installed, the source changeover function cannot beimplemented.
Pushbutton locking using apadlock
Access to pushbuttonsprotected by transparentcover
OFF position locking using apadlock
OFF position locking using akeylock
0564
4605
6447
0564
4805
6449
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5636
Masterpact Schneider Electric37
1
2
8
10
9
7
5
6
4
305
6451
1 mismatch protection2 door interlock3 racking interlock4 keylock locking5 padlock locking6 position indicator7 craddle front plate
(accessible with cubicledoor closed)
8 racking-handle entry9 reset button10 racking-handle storage
On the craddle
E47
063
« Disconnected» positionlocking by padlocks
« Disconnected» positionlocking by keylocks
Door interlock
Racking interlock
0564
5005
6417
0564
5205
6453 Mismatch protection
« Disconnected» position lockingMounted on the craddle and accessible with the door closed, these devices lockthe circuit breaker in the « disconnected» position in two manners:c using padlocks (standard), up to three padlocks (not supplied)c using keylocks (optional), one or two different keylocks are available.Profalux and Ronis keylocks are available in different options:c one keylockc two different keylocks for double lockingc one (or two) keylocks mounted on the device + one (or two) identical keylockssupplied separately for interlocking with another device.A locking kit (without locks) is available for installation of one or two keylocks(Ronis, Profalux, Kirk or Castell).
« Connected» , « disconnected» and « test» position lockingThe « connected» , « disconnected» and « test» positions are shown by an indicator.The exact position is obtained when the racking handle blocks. A release button isused to free it.On request, the « disconnected» position locking system may be modified to lockthe circuit breaker in any of the three positions, « connected» , « disconnected» and« test» .
Door interlock catchMounted on the right or left-hand side of the craddle, this device inhibits opening ofthe cubicle door when the circuit breaker is in « connected» or « test» position. It thebreaker is put in the « connected» position with the door open, the door may beclosed without having to disconnect the circuit breaker.
Racking interlockThis device prevents insertion of the racking handle when the cubicle door is open.
Cable-type door interlockThis option is identical for fixed and drawout versions.
Racking interlock between crank and OFF pushbuttonThis option makes it necessary to press the OFF pushbutton in order to insert theracking handle and holds the device open until the handle is removed.
Automatic spring discharge before breaker removalThis option discharges the springs before the breaker is removed from the craddle.
Mismatch protectionMismatch protection ensures that a circuit breaker is installed only in a craddle withcompatible characteristics. It is made up of two parts (one on the craddle and oneon the circuit breaker) offering twenty different combinations that the user mayselect.
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5737
Masterpact Schneider Electric38
Indication contacts
Indication contacts are available:c in the standard version for relayapplicationsc in a low-level version for control of PLCsand electronic circuits.M2C and M6C contacts may beprogrammed via the Micrologic P and Hcontrol units.
Functionsand characteristics
ON/OFF indication contacts (OF)Two types of contacts indicate the ON or OFF position of the circuit breaker:c microswitch type changeover contacts for Masterpact NTc rotary type changeover contacts directly driven by the mechanism for MasterpactNW. These contacts trip when the minimum isolation distance between the maincircuit-breaker contacts is reached.OF NT NW
supplied as standard 4 4maximum number 4 12breaking capacity (A) standard minimum load: 100mA/24Vp.f.: 0.3 V AC 240/380 6 10/6*AC12/DC12 480 6 10/6*
690 6 6V DC 24/48 2.5 10/6*
125 0.5 10/6*250 0.3 3
low-level minimum load: 2mA/15V DCV AC 24/48 5 6
240 5 6380 5 3
V DC 24/48 5/2.5 6125 0.5 6250 0.3 3
* standard contacts: 10 A; optional contacts: 6 A.
« Fault-trip» indication contacts (SDE)Circuit-breaker tripping due to a fault is signalled by:c a red mechanical fault indicator (reset)c one changeover contact (SDE).Following tripping, the mechanical indicator must be reset before the circuit breakermay be closed.SDE NT/NW
supplied as standard 1maximum number 2breaking capacity (A) standard minimum load: 100mA/24Vp.f.: 0.3 V AC 240/380 5AC12/DC12 480 5
690 3V DC 24/48 3
125 0.3250 0.15
low-level minimum load: 2mA/15V DCV AC 24/48 3
240 3380 3
V DC 24/48 3125 0.3250 0.15
Combined « connected/closed» contacts (EF)The contact combines the « device connected» and the « device closed»information to produce the « circuit closed» information.Supplied as an option for Masterpact NW, it is mounted in place of the connector ofan additional OF contact.EF NW
maximum number 8breaking capacity (A) standard minimum load: 100mA/24Vp.f.: 0.3 V AC 240/380 6AC12/DC12 480 6
690 6V DC 24/48 2.5
125 0.8250 0.3
low-level minimum load: 2mA/15V DCV AC 24/48 5
240 5380 5
V DC 24/48 2.5125 0.8250 0.3
ON/OFF indication contacts(OF) (microswitch type)
ON/OFF indication contacts(OF) (rotary type)
Combined contacts
Additional « fault-trip»indication contacts (SDE)
0564
1805
6419
0564
6205
6455
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5838
Masterpact Schneider Electric39
CE, CD and CT « connected/disconnected/test» positioncarriage switches
M2C programmablecontacts: circuit-breakerinternal relay with twocontacts
M6C programmablecontacts: circuit-breakerexternal relay with sixindependent changeovercontacts controlled from thecircuit breaker via a three-wire connection.
0564
5605
6413
0564
30
« Connected» , « disconnected» and « test» position carriageswitchesThree series of optional auxiliary contacts are available for the craddle:c changeover contacts to indicate the « connected» position (CE)c changeover contacts to indicate the « disconnected» position (CD). This positionis indicated when the required clearance for isolation of the power and auxiliarycircuits is reached.c changeover contacts to indicate the « test» position (CT). In this position, thepower circuits are disconnected and the auxiliary circuits are connected.Additional actuatorsA set of additional actuators may be installed on the craddle to change thefunctions of the carriage switches.
NT NWcontacts CE/CD/CT CE/CD/CT
maximum number standard 3 2 1 3 3 3with additional actuators 9 0 0
6 3 06 0 3
breaking capacity (A) standard minimum load: 100mA/24Vp.f.: 0.3 V AC 240 8 8AC12/DC12 380 8 8
480 8 8690 6 6
V DC 24/48 2.5 2.5125 0.8 0.8250 0.3 0.3
low-level minimum load: 2mA/15V DCV AC 24/48 5 5
240 5 5380 5 5
V DC 24/48 2.5 2.5125 0.8 0.8250 0.3 0.3
M2C / M6C programmable contactsThese contacts, used with the Micrologic P and H control units, may beprogrammed via the control unit keypad or via a supervisory station with the COMcommunication option. They require an external power supply module.They indicate:c the type of faultc instantaneous or delayed threshold overruns.They may be programmed:c with instantaneous return to the initial statec without return to the initial statec with return to the initial state following a delay.characteristics M2C/M6C
minimum load 100mA/24Vbreaking V AC 240 5capacity (A) 380 3p.f.: 0.7 V DC 24 1.8
48 1.5125 0.4250 0.15
471
S1
474
484
S2
20
S6
24 22
5
S1
1 3
11
S2
7 9
2
S3
6 4
8
S4
12 10
14
S5
18 16
M2C: 24 V DCpower suppliedby control unit(consumption100 mA).
M6C: external 24 V DC power supply required (consumption100 mA).
E59
469
E59
470
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5839
Masterpact Schneider Electric40
The remote ON / OFF function is used to remotely open and close the circuitbreaker. It is made up of:c an electric motor (MCH) equipped with a « springs charged» limit switch contact(CH)c two voltage releases:v a closing release (XF)v an opening release (MX).Optionally, other functions may be added:c a « ready to close» contact (PF)c an electrical closing pushbutton (BPFE)c remote reset following a fault.A remote-operation function is generally combined with:c device ON / OFF indication (OF)c « fault-trip» indication (SDE).
Wiring diagram of a point-to-point remote ON / OFF function
Wiring diagram of a bus-type remote ON / OFF function
A2 A3
A1
XFcom
C1
C2 C3
OF
MXcom
B1
B3 B2
CH
MCH
COM
PF
SDE
CH
closingorder
openingorder
springcharged
supervisor
12 14
11
OF1
82 84
81
SDE
252 254
251
PF
A2
A1
XF
C2
C1
MX
B3 B2
B1
CH
MCH
closedopenfaultreadyto close
closingorder
openingorder
springcharged
Remote operationRemote ON / OFF
Functionsand characteristics
Two solutions are available for remoteoperation of Masterpact devices:c a point-to-point solutionc a bus solution with the COMcommunication option.
0564
07
E46
041
E46
042
Note:An opening order always takes priority over a closingorder.If opening and closing orders occur simultaneously, themechanism discharges without any movement of themain contacts. The circuit breaker remains in the openposition (OFF).In the event of maintained opening and closing orders,the standard mechanism provides an anti-pumpingfunction by blocking the main contacts in open position.Anti-pumping function. After fault tripping or intentionalopening using the manual or electrical controls, theclosing order must first be discontinued, then reactivatedto close the circuit breaker.When the automatic reset after fault trip (RAR) option isinstalled, to avoid pumping following a fault trip, theautomatic control system must take into account theinformation supplied by the circuit breaker before issuinga new closing order or blocking the circuit breaker in theopen position (information on the type of fault, e.g.overload, short-time fault, earth fault, earth leakage,short-circuit, etc.).
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5840
Masterpact Schneider Electric41
Electric motor (MCH) forMasterpact NT
XF and MX voltage releases
“Ready to close” contacts(PF)
0564
20
0564
2105
6457
Electric motor (MCH)The electric motor automatically charges and recharges the spring mechanismwhen the circuit breaker is closed. Instantaneous reclosing of the breaker is thuspossible following opening. The spring-mechanism charging handle is used only asa backup if auxiliary power is absent.The electric motor (MCH) is equipped as standard with a limit switch contact (CH)that signals the “charged” position of the mechanism (springs charged).characteristics
power supplyV AC 50/60 Hz 48/60 - 100/130 - 200/240 - 277- 380/415 - 400/440 - 480V DC 24/30 - 48/60 - 100/125 - 200/250
operating threshold 0.85 to 1.1 Unconsumption (VA or W) 180motor overcurrent 2 to 3 In for 0.1 secondcharging time maximum 3 seconds for Masterpact NT
maximum 4 seconds for Masterpact NWoperating frequency maximum 3 cycles per minuteCH contact 10 A at 240 V
Voltage releases (XF and MX)Closing release (XF)The XF release remotely closes the circuit breaker if the spring mechanism ischarged.Opening release (MX)The MX release instantaneously opens the circuit breaker when energised. Thesupply can be maintained or automatically disconnected.characteristics XF MX
power supplyV AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480V DC 12 - 24/30 - 48/60 - 100/130 - 200/250
operating threshold 0.85 to 1.1 Un 0.7 to 1.1 Unconsumption (VA or W) hold: 4.5 hold: 4.5
pick-up: 200 pick-up: 200circuit-breaker response 55 ms ± 10 (Masterpact NT) 50 ms ± 10time at Un 70 ms ± 10 (NW i 4000A)
80 ms ± 10 (NW > 4000A)
“Ready to close” contact (PF)The “ready to close” position of the circuit breaker is indicated by a mechanicalindicator and a PF changeover contact. This signal indicates that all the followingare valid:c the circuit breaker is in the OFF positionc the spring mechanism is chargedc a maintained opening order is not present:v MX energisedv fault tripv remote tripping (second MX or MN)v device not completely racked inv device locked in OFF positionv device interlocked with a second device.characteristics NT/NW
maximum number 1breaking capacity standard minimum load: 100mA/24Vp.f.: 0.3 V AC 240/380 5AC12/DC12 480 5
690 3V DC 24/48 3
125 0.3250 0.15
low-level minimum load: 2mA/15V DCV AC 24/48 3
240 3380 3
V DC 24/48 3125 0.3250 0.15
Electric motor (MCH) forMasterpact NW
0564
68
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5941
Masterpact Schneider Electric42
Electrical closing pushbutton (BPFE)Located on the front panel, this pushbutton carries out electrical closing of thecircuit breaker. It is generally associated with the transparent cover that protectsaccess to the closing pushbutton.Electrical closing via the BPFE pushbutton takes into account all the safetyfunctions that are part of the control/monitoring system of the installation.The BPFE connects to the closing release (XF) in place of the COM module.
Remote reset after fault tripElectrical reset after fault trip (Res)Following tripping, this function resets the “fault trip” indication contacts (SDE) andthe mechanical indicator and enables circuit breaker closing.Power supply: 110 / 130 V AC and 200 / 240 V AC
Automatic reset after fault trip (RAR)Following tripping, a reset of the mechanical indicator (reset button) is no longerrequired to enable circuit-breaker closing. The mechanical (reset button) andelectrical (SDE) indications remain in fault position until the reset button is pressed.
Remote operationRemote ON / OFF (cont.)
Functionsand characteristics
Electrical closing pushbutton (BPFE).
0564
69
E46
044
SDE2
K2
K1
resetorder
E46
045
A2 A3
A1
BPFE
XF com
remoteclosingorder
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5942
Masterpact Schneider Electric43
This function opens the circuit breaker via an electrical order. It is made up of:c a shunt release (second MX)c or an undervoltage release (MN)c or a delayed undervoltage release (MN + delay unit).The delay unit, installed outside the circuit breaker, may be disabled by anemergency OFF button to obtain instantaneous opening of the circuit breaker.
Wiring diagram for the remote-tripping function
Voltage releases (second MX)When energised, the MX voltage release instantaneously opens the circuit breaker.A continuous supply of power to the second MX locks the circuit breaker in the OFFposition.characteristics
power supplyV AC 50/60Hz 24 - 48 - 100/130 - 200/250 - 277- 380/480V DC 12 - 24/30 - 48/60 - 100/130 - 200/250
operating threshold 0.7 to 1.1 Unpermanent locking function 0.85 to 1.1 Unconsumption (VA or W) pick-up: 200
hold: 4.5circuit-breaker response 50 ms ± 10time at Un
Instantaneous voltage releases (MN)The MN release instantaneously opens the circuit breaker when its supply voltagedrops to a value between 35% and 70% of its rated voltage. If there is no supply onthe release, it is impossible to close the circuit breaker, either manually orelectrically. Any attempt to close the circuit breaker has no effect on the maincontacts. Circuit-breaker closing is enabled again when the supply voltage of therelease returns to 85% of its rated value.characteristics
power supplyV AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 380/480V DC 24/30 - 48/60 - 100/130 - 200/250
operating opening 0.35 to 0.7 Unthreshold closing 0.85 Unconsumption (VA or W) pick-up: 200 hold: 4.5circuit-breaker response 40 ms ± 5 pour NTtime at Un 90 ms ± 5 pour NW
MN delay unitsTo eliminate circuit-breaker nuisance tripping during short voltage dips, operation ofthe MN release can be delayed. This function is achieved by adding an externaldelay unit in the MN voltage-release circuit. Two versions are available, adjustableand non-adjustable.characteristics
power supply non-adjustable 100/130 - 200/250V AC 50-60 Hz /DC adjustable 48/60 - 100/130 - 200/250 - 380/480operating threshold opening 0.35 to 0.7 Un
closing 0.85 Unconsumption (VA or W) pick-up: 200 hold: 4.5circuit-breaker response non-adjustable 0.25 stime at Un adjustable 0.5 s - 0.9 s - 1.5 s - 3 s
openingorder
D2
D1
MN
delayedopeningorder
instantaneousopeningorder
time delayunit
MN
D2
D1
10 12
3 6
openingorder
C12
C11
MX2
E46
043
MX or MN voltage release
0564
58
Remote tripping
E46
553
E46
554
0564
21
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5943
Masterpact Schneider Electric44
0564
6305
6464
E47
535
0168
19
Auxiliary terminal shield (CB)Optional equipment mounted on the craddle, the shield prevents access to theterminal block of the electrical auxiliaries.
Operation counter (CDM)The operation counter sums the number of operating cycles and is visible on thefront panel. It is compatible with manual and electrical control functions.
Escutcheon (CDP)Optional equipment mounted on the door of the cubicle, the escutcheon increasesthe degree of protection to IP 40 (circuit breaker installed free standing: IP30) .It is available in fixed and drawout versions.
Blanking plate (OP) for escutcheonUsed with the escutcheon, this option closes off the door cut-out of a cubicle notyet equipped with a device. It may be used with the escutcheon for both fixed anddrawout devices.
Transparent cover (CP) for escutcheonOptional equipment mounted on the escutcheon, the cover is hinged and securedby a screw. It increases the degree of protection to IP 54, IK10. It adapts to bothfixed and drawout devices.
AccessoriesFunctionsand characteristics
Transparent cover (CP) forEscutcheon
Escutcheon (CDP) with blanking plate
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5944
Masterpact Schneider Electric45
BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5945