Post on 30-Jul-2020
Freedom Express Home Inspections LLC Residential, Commercial, InfraredImaging, Mold Inspections 5400 Hwy 177 Marland Ok. 74644 580-268-3340 Mobile 580-761-8477
Freedom Express Home InspectionsProperty Inspection Report
Cover Page
, Ponca City OK, 74601Inspection prepared for:
Inspection Date: 1/4/2008 Time: 10:30 AM Weather: Clear 45 degrees
Inspector: Charley Bottger5400 Hwy 177
Marland OK, 74644Phone: 580-268-3340
Fax: 580-268-3328Email: freedomexpress495@att.net
freedomexpressinspections.com
Freedom Express Home Inspections , Ponca City
Page 1 of 13
Freedom Express Home Inspections LLC Addendum 1-1
1. A. The dryer vent within the attic appears to be stopped up with lint, does not properlyextend beyond the roof decking and has improper flex corregiated duct installed. Flex duct cannotextend beyond the dryer connection at the wall. B. The main bathroom just off of the hall tub faucetis leaking at the stem. C. The drain valve for the hot water heater is dripping water. D. The hotwaterheater relief valve downspout has a rubber hose traveling to a PVC plastic drain that is not rated forhot water. Recommend a metal downspout be installed within 6 inches of the floor for safety. E. Thedishwasher drain hose does not have a high loop to prevent waste from backing into the dishwasherin the event of sewer line blockage. F. The furnace flue vent does not have the required 1 inchclearance to combustiables at the roof pentration. Estimated cost of labor and material $400.00 G. There is a small gas leak on the top side of the shut off valve to the gas meter, which is theresponsibility of the gas company, recommend they be notified.
2. A. The electrical outlet in the cabinet for the microwave has reverse polarity. B. The frontentry exterior light and the exterior light from the walk through door of the garage does not operaterecommend it be determined bulb or fixture. C. The electrical supply wiring from the wall to the gasfired furnace does not meet requirements. Estimated cost of labor and material $200.00
3. The wood type cricket installed on the surface of the shingles to deter water away from thechimney is improperly installed and constructed of the improper type of material. Crickets arenormally constructed of metal and are installed under the shingles not on the surface. When woodcrickets are used they normally are covered with shingles the same as the roof covering.Recommend a roofing contractor be consulted for a price estimate of repairs.
4.The S.E. and the S.W bedroom closet doorknobs do not catch on their striker plate.Estimated cost of labor and material $50.00
Freedom Express Home Inspections , Ponca City
Page 2 of 13
Structural Systems
The topography of the landscape in the front yard with reference to the home facing east isbasically flat with little to no drainage in any direction. The west 1/2 of the back yard drains awayfrom the foundation toward the west. Water does appear to pool along the foundation S.W. cornerwest side due to a lack of guttering in this area. The brick veneer type exterior wall siding has a hairline mortar joint crack below the window S.W. corner west side that can be contributed to the lack ofguttering and pooling of water near the foundation.The concrete grade on slab type foundationshould be considered as having normal settling for its age located on clay base type of soil. It is recommended for long-term foundation stability that no water be allowed to pool within 3feet of the foundation. This can normally be accomplished with 100% guttering; properly placeddownspouts with extensions and or splashguards. Creative landscaping such as raised flowerbedsor concrete sidewalks along the foundation can also be used to deter water.
The structural supports for the roof as viewed from within the attic has no visible evidence ofstructural stress. The roughly 8 inches of blown type insulation within the attic should be consideredas exceptable for this area of Oklahoma.
The one layer of asphalt type shingles over solid wood decking has no visible evidence ofpast hail damage. It should not be unreasonable to expect life expectancy of the shingles to be inthe area of 12 years of remaining life. This is just an opinion and not meant to imply a warranty or aguarantee of the life of the shingles.
The wood type cricket installed on the roof surface to deflect water away from the chimneywas improperly installed with wood and should be constructed of metal and be installed under theshingles instead of on the top of the shingles as indicated in the pictures. When wood crickets areinstalled they are required to be surfaced with shingles the same as the roof covering. The dry wallceiling to the north of the fireplace in the living room is indicating a past leak. This dry wall ceilingwas check with a moisture meter and an infrared camera that detects moisture. Both moisturedetecting devices indicated no moisture present at the time of inspection.
Additional pages may be attached to this report. Read them very carefully. This report maynot be complete without the attachments. If an item is present in the property but is not inspected,the "NI" column will be checked and an explanation is necessary. Comments may be provided bythe inspector whether or not an item is deemed in need of repair
I=Inspected NI=Not Inspected NP=Not Present R=Not Functioning or in Need of Repair
I NI NP R
X 1. Landscaping drainageMaterials: It is recommended for long term foundation stability that no water beallowed to pool within 3 feet of the foundation. This can normally be accomplishedwith 100% installed guttering properly placed downspouts with extensions and orsplashguards. Concrete type sidewalks or raised flowerbeds along the foundationcan be used to deter water as long as the downspouts do not drain into the raisedflowerbeds., Water appers to pool along the west foundation, The patio doors areabove grade levelObservations: Signs of poor drainage
Freedom Express Home Inspections , Ponca City
Page 3 of 13
X 2. Foundations (If all crawl space areas are not inspected, provide anexplanation.)Observations: Interior Slab not visible due to floor coverings. Concrete slab ongrade type foundation. Foundation settling should be considered as normalsettling for the age of the home
X X 3. Roof Covering (If the roof is inaccessible, report the method used to inspect.)Roof Material: Asphalt shingles. The ___1_____layer of asphalt type shingles oversolid wood decking as viewed from on the roof has no visible evidence of past haildings. It should not be unreasonable to expect a life expectancy of these shinglesto be in the area of _12______ years of remaining life. This is just an opinion andnot meant to imply a warranty or a guarantee of the life of the shingles.Comments: Exposed plywood. Irregular flashing materials used. Improperlyinstalled cricket
Shingles No hail Past hail dings to vent cover
Improper roof cricket
Freedom Express Home Inspections , Ponca City
Page 4 of 13
X 4. Roof Structure and Attic (If the attic is inaccessible, report the method used toinspect.)Insulation Materials: Blown in insulation. Insulation is 8 inches deep. No visibleevidence of structrual stress for the roof support system as viewed from within theatticComments: Evidence of past leaking. Stains in areas. Truss type roofing present
X 5. Walls (Interior and Exterior)Wall Materials: Exterior siding brick veneer. Interior walls are covered withDrywall. Hairline mortar joint cracks visible in the brick veneer siding should beconsidered as normal settlingComments:
Hair line mortar joint crack below window west side S.W. corner
X 6. Ceilings and FloorsCeiling Materials: Ceiling is made of drywallComments: Small stains visible
Ceiling just north of fireplace Infrared image of ceiling north of fireplaceindicating no moisture
Freedom Express Home Inspections , Ponca City
Page 5 of 13
X X 7. Doors (Interior and Exterior)Comments: Folding door present. S.E. & S.W. bedroom closet doors do not latchat the striker plate
X 8. WindowsWindow Materials: Windows are made of vinylComments: All windows are functional. Windows updated in like new condition
Infrared image indicating air intrusion at the corner of the windows dining room
X 9. Fireplace/ChimneyMaterials: Fireplace is located in the living roomMaterials: Fireplace flue minor buildupComments: Cosmetic brick spalling on the chimney brick, Gas Log only Metalinsert, Damper operational
Cosmetic brick spalling exterior chimney as the result of no guttering
X 10. Porches, Decks, Carports (Attached)Comments: Patio is functional
Freedom Express Home Inspections , Ponca City
Page 6 of 13
Electrical Systems
11. OtherMaterials:Comments:
I=Inspected NI=Not Inspected NP=Not Present R=Not Functioning or in Need of Repair
I NI NP R
X 1. Service Entrance and PanelsMaterials: The electrical panel is located within the bedroom closetMaterials: 150 AMPObservations: Electrical panel is fully functional, Main feed from meter to panel iscopper, Service entrance is overhead, FPE Stab-loc panel present
X X 2. Branch Circuits - Connected Devices and Fixtures (Report as in need of repairthe lack of ground fault circuit protection where required.)Materials: 150 Amp service panelComments: 220 volt electrical outlet available in laundry area, Main bathroom justoff of the hall has no GFCI type of electrical outlets installed for safety, Due to theage of the home GFCI type of electrical outlets are not a requirement but arehighly recommended near sources of water for safety, Due to the age of thehome AFCI type safety electrical outlets are not a requirement for bedrooms, Thegarage has no GFCI type of electrical outlets installed., No GFCI type of electricalsafety outlets on the exterior of the home, The electrical outlet in the cabinet forthe microwave has reverse polarity, The walk through garage exterior door lightfixture did not operate, The front entry exterior light fixture did not operate, Theelectrical service cord to the gas furnace does not meet requirements
Improper electrical supply to furnace
Freedom Express Home Inspections , Ponca City
Page 7 of 13
Heating, Ventilation and Air Conditioning Systems
The gas-fired furnace appears to be the same age as the home 1979. The up flow furnacelocated in the garage closet was operated from its thermostat through a normal cycle. The dischargeair from the furnace heat exchanger into the living area was tested for carbon monoxide with anegative results The average life expectancy of a gas fired furnace heat exchanger is 20 to 25years.
.This furnace was operating normal but should be considered as having exceeded a normallife expectancy and recommend budgeting for replacement.
The 220-volt split system A/C unit MFG in 1979 was operated with a deltaT of 20 degrees thisbeing the difference between supply and return air temperature and should be considered asnormal. It is highly recommended to have the heating and cooling system serviced by a qualifiedheat and air contractor at the beginning of each cooling and heating season. The average lifeexpectancy of an A/C unit compressor is 15 to 18 years. This unit has exceeded an average lifeexpectancy by many years recommend you budget for its replacement
I=Inspected NI=Not Inspected NP=Not Present R=Not Functioning or in Need of Repair
I=Inspected NI=Not Inspected NP=Not Present R=Not Functioning or in Need of Repair
I NI NP R
X X 1. Heating EquipmentMaterials: AC is located adjacent North exterior wall. Split System. Furnace Dateof MFG __1979__. The average life expectancy of a standard gas fired furnaceheat exchanger is 20 to 25 years. Gas fired upflow furnaceObservations: The furnace was preforming as intended. Recommend having thefurnace serviced at the beginning of each heating season. The furnace should beconsidered as having exceeded a normal life expectancy for this type ofequipment. The average life expectancy of the heat exchanger on a standard gasfired furnace is 20 to 25 years. The furnace flue vent does not have properclearance to combustiables
X 2. Cooling EquipmentType and Energy Source: AC is located adjacent North exterior wall, ACcompressor is electric powered, Split System, Date of MFG exterior A/Ccondensing unit____1979_________, The average life expectancy of a standardA/C compressor is 15 to 18 yearsObservations: Thermostat is functional, A/C unit performing as intended
X 3. Ducts and VentsComments: Filter is located below heater. Ridgid Metal duct installed within theattic. Flex duct installed within the attic
Freedom Express Home Inspections , Ponca City
Page 8 of 13
Plumbing Systems
Air distribution ducts in the attic with the furnaceoperating Infrared Picture
A/C ducts in the attic same as Infrared Picture
Furnace flue vent improper clearance at the roof
The domestic water supply piping that is visible above the slab on grade foundation is copperpipe. This piping was providing proper pressure to the appliances and fixtures at the time ofinspection. The wastewater drainage and vent piping that is visible is plastic PVC schedule 40.Water was discharged down the various outlets for a period in excess of one hour with no visibleevidence of blockage at any fixture or outlet.
The gas fired water heater installed in the garage closet is raised in height to meetrequirements and has combustion air for its burner provided from the attic. This tank was MFG in June of 1998. The average life expectancy of a standard water heateris 10 years give or take depending on water quality and usage. Recommend you budget for itsreplacement.
I NI NP R
Freedom Express Home Inspections , Ponca City
Page 9 of 13
Appliances
X X 1. PlumbingMaterials: The wastewater drainage and vent piping that is visible above thefoundation and within the attic is schedule 40 plastic PVC piping, The main gasshut off valve is located at the meter, The main water shut of valve is visible at thewater meter, There is an addition water shut off valve locate within the bedroomcloset, Copper water supply piping in useObservations: Copper water supply piping in use, Main bathroom just off of thehall lavatory faucet leaks at the stem and or is dripping
X X 2. Water Heating Equipment (Report as in need of repair those conditionsspecifically listed as recognized hazards by TREC rules.)Enerty Source: Water heater is gas powered. Water heater is located in thegarage closet. Unit is 40 gallons. Number of hot water heaters 1. The average lifeexpectancy of a standard hot water heater depending on water quality and usageis 10 years give or takeComments: The gas fired water heater installed within the garage closet is raisedin height to meet requirements. The gas fired water heater installed within thegarage closet has combustion air for its burner provided from the attic. Leakingfrom the drain. The hot water heater relief valve does not have a downspout towithin 6 inches of the floor for safety
Improper Relief valve downspout hot water heater
I NI NP R
X 1. Cooktop/OvenMaterials: Electric Oven # 1 Settings_350_______ Temp_340_____, ElectricOven # 2 Settings_350______ Temp_340______, Self CleaningObservations: Unit operated normal, Unit is electric
X 2. Range HoodRange Vent Type: Non-ventedComments: Unit operated normally
Freedom Express Home Inspections , Ponca City
Page 10 of 13
X 3. DishwasherObservations: Dishwasher operated normally
No High loop on dishwasher drain line Dishwasher door prevents drawer from opening
X 4. Food Waste DisposerComments: Garbage disposal operated normal
X 5. RefrigeratorObservations: Refrigerator Not Present
X 6. Microwave Cooking EquipmentComments: Unit operated normal
X 7. Trash CompactorComments: No trash compactor present
X 8. Bathroom Exhaust Fans and/or HeatersComments: Bath fan operated normally
X 9. Whole House Vacuum SystemsComments: No vacuum system is present
X 10. Garage Door OpenersDoor Type: Roll-up doorComments: Garage door operated normally
X 11. Door Bell and ChimesComments: Door bell operated normally
X X 12. Dryer VentsComments: 220-volt electrical outlet and gas service available for the dryer, Ventterminates into attic, Vent does not extend to the exterior of the structure asrequired, Flex duct not allowed beyond 5 feet of the dryer, Vent is clogged with lint
Freedom Express Home Inspections , Ponca City
Page 11 of 13
Optional Systems
Improper dryer vent not exiting the interior of attic Dryer vent appears to be stopped up from arrowdownward
X 13. Ice maker free standingObservations: No Freestanding Ice Maker Present
I=Inspected NI=Not Inspected NP=Not Present R=Not Functioning or in Need of Repair
I NI NP R
1. OutbuildingsMaterials:Comments:
X 2. Lawn SprinklersObservations:
X 3. Swimming Pools and EquipmentComments:
X 4. Water Wells (A coliform analysis is recommended.)Type of Pump:Type of Storage Equipment:Comments:
X 5. Septic SystemsType:Comments:
X 6. Security SystemsComments:
Freedom Express Home Inspections , Ponca City
Page 12 of 13
detached garage
X 7. Fire Protection EquipmentComments: All smoke detectors operated noramlly
I NI NP R
Freedom Express Home Inspections , Ponca City
Page 13 of 13
Report Summary
Report Summary
Structural SystemsPage 3 Item: 3 Roof Covering (If
the roof isinaccessible, reportthe method used toinspect.)
Exposed plywood. Irregular flashing materials used.Improperly installed cricket
Page 5 Item: 7 Doors (Interior andExterior)
S.E. & S.W. bedroom closet doors do not latch at the strikerplate
Electrical SystemsPage 6 Item: 2 Branch Circuits -
ConnectedDevices andFixtures (Report asin need of repairthe lack of groundfault circuitprotection whererequired.)
The electrical outlet in the cabinet for the microwave hasreverse polarity, The walk through garage exterior door lightfixture did not operate, The front entry exterior light fixture didnot operate, The electrical service cord to the gas furnacedoes not meet requirements
Heating, Ventilation and Air Conditioning SystemsPage 7 Item: 1 Heating Equipment The furnace flue vent does not have proper clearance to
combustiablesPlumbing SystemsPage 9 Item: 1 Plumbing Main bathroom just off of the hall lavatory faucet leaks at the
stem and or is drippingPage 9 Item: 2 Water Heating
Equipment (Reportas in need of repairthose conditionsspecifically listedas recognizedhazards by TRECrules.)
Leaking from the drain. The hot water heater relief valve doesnot have a downspout to within 6 inches of the floor for safety
AppliancesPage 11 Item: 12 Dryer Vents Vent terminates into attic, Vent does not extend to the exterior
of the structure as required, Flex duct not allowed beyond 5feet of the dryer, Vent is clogged with lint