Motorised centrifugal impeller
Complete built-up centrifugal fan
To ensure a ventilation system functions in the built environment as it was intended in the design stages, it is crucial to know that the fan’s actual performance matches the catalogue data published by the manufacturer. The only true way to measure the performance of a fan is by using a specially designed air flow test rig which is compliant to an international standard, such as ISO5801:2007; Industrial fans - performance testing using standardised airways.
Australian fan manufacturers purchase their motorised external rotor centrifugal fans from the major suppliers in Europe and increasingly cheaper product from Asia. To derive the fan’s performance, these suppliers test the fan in the very basic configuration where the setup consists of a motorised impeller, inlet cone and a simple motor mount. This allows the fan to perform without restrictions which produces the optimum values for air flow, noise and efficiency.
However, when this motorised impeller is fitted into a housing, which could consist of a cowl, casing or plenum, the fan’s performance characteristics change significantly. It is important to remember that motorised impellers will be used in many fan types, including roof mounted in downflow and vertical discharge configurations, wall mounted and duct mounted.
These components all have an effect on the way the air leaves the impeller and the overall performance of the fan. For example, with an in-line duct mounted centrifugal fan, the air is forced to change direction once it hits the wall of the casing. This together with the air flow losses associated with surface friction, dramatically affects the pressure development capabilities of the fan. In addition to these reductions, the noise level increases and the overall efficiency of the fan decreases. Furthermore, if these components are poorly designed, the performance loss is amplified.
Fantech’s in-house capability allows it to perform air flow testing using their purpose-built air flow rigs which have been specifically designed to test to ISO5801:2007.
In addition, Fantech’s sister company Elta Fans UK, has the capability to perform noise testing to BS848:Part 2 1985.
Fantech recently undertook testing to determine the actual differences in performance between a motorised centrifugal impeller-only assembly and a built up centrifugal fan in a housing. At a given duty point the results are as follows:
• 15% reduction in air flow• 37% reduction in pressure development• 14% reduction in efficiency• 8% reduction in peak efficiency• 1.2dB noise increase
It should also be noted that the tests performed by the motorised impeller manufacturers are completed using their purposely-designed inlet cones and are set to have an ideal overlap between impeller and inlet cone. To reduce production costs many of the local fan manufacturers use their own inlet cones which suit a variety of their fan ranges. These inlet cones often do not follow the supplier’s overlap recommendations, thereby further reducing performance.
When ordering fans it is important to question whether the performance data comes from a complete built-up centrifugal fan with housing, brackets etc, or is it from the motorised impeller only. The majority of imported motorised centrifugal impellers are sourced from Germany and these are tested to a German DIN standard such as DIN24163. So if the data of a locally assembled complete built-up fan is published to the German DIN standard rather than the ISO standard, it would be prudent to question the fan supplier as to how their catalogued performance data is derived.
Every fan range engineered and sold by Fantech is thoroughly tested as a fully assembled fan during the development process to determine its true performance. The fan tested is exactly the same as the unit purchased and installed by the contractor. As a result Fantech has comprehensive data on each fan model and therefore has the ability to publish accurate and reputable technical catalogue data. This information is beneficial to the end user as they can be confident that the fan will perform as intended.
For more information contact Fantech on 03 9554 7870.
0
100
200
300
400
500
600
700
800
0.000 0.500 1.000 1.500 2.000 2.500 3.000qv , Air Flow (m3/s)
Ps F,
Pre
ssu
re (
Pa)
ISO5801 Type A Test Results Comparison
Fan Assembly
Impeller Only
Di�erence in air �ow
Di�erence in pressure
Sta
tic
Eff
icie
ncy
(%
)
ISO5801 Type A Test Results Static Efficiency(Input Power) Fan Assembly
Impeller Only45%40%
35%
30%
25%
20%
15%
10%
5%
0%0.000 0.500 1.000 1.500 2.000 2.500 3.000
qv , Air Flow (m3/s)
Di�erence in Peak E�ciency
Di�erence in e�ciency
Fantech Pty. Ltd.Victoria: (+61 3) 9554 7845New South Wales: (02) 8811 0400South Australia: (08) 8294 0530Northern Territory: (08) 8947 0447
Queensland: (07) 3299 9888Western Australia: (08) 9209 4999A.C.T. (02) 6280 5511New Zealand: (09) 444 6266South East Asia: (+603) 5121 4453
DIN and ISO Fan Performance