Demonstration Thermography report
Company
Device
Customer
E-Mail: info@testo.co.uk
Phone: 01420 544433
Andy McGrath - Testo
Tester:
32 degree, Wide AngleLens
Lens:
1434423, 01729604 &01710401
Serial No.:Testo 880-3, 875-2 & 881-3
Demo Report
Testo Thermal ImagingCameras
Testo Ltd
VariousMeasuring Date:
Various Applications for Testo ThermalImaging cameras in HVAC.
Demonstration Thermography Report
Measuring Site:
Demonstration Thermography Report to highlight the capabilities of theTesto Thermal Imaging cameras for various applications associated toHVAC.
Task
Alton, GU34 2QJ
Newman Lane
Testo Ltd
1/15Page
Demonstration Thermography report
File:
IV_00518.BMT 14/01/2009
Measuring Time:
12:57:02
20.0Refl. temp. [°C]:
0.95Emissivity:
Picture parameters:
Date:
Picture markings:
RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects
Spot Temp 1 to indicatetemperature variation across thefloor
20.00.9520.7Measure point 1
Spot Temp 2 to indicatetemperature variation across thefloor
20.00.9530.0Measure point 2
Spot Temp 3 to indicatetemperature variation across thefloor
20.00.9530.9Measure point 3
Spot Temp 4 to indicatetemperature variation across thefloor
20.00.9523.3Measure point 4
Profile line:
Thermal Survey, specifically in a Utility Room for Trace and Access application.Thermal and Digital imagesof Floor area taken as part of an investigation for possible leaks. Thermal image highlights temperaturevariation across the floor, this is therefore an indication of the location of the heating pipework under thefloor.
Remarks:
2/15Page
Demonstration Thermography report
File:
IV_00662.BMT 09/04/2009
Measuring Time:
08:27:40
20.0Refl. temp. [°C]:
0.95Emissivity:
Picture parameters:
Date:
Picture markings:
RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects
-20.00.9519.7Measure point 1
-20.00.9522.5Measure point 2
-20.00.9519.2Measure point 3
Profile line:
Thermal Survey at a Domestic Property.Thermal and Digital images of Floor area taken as part of aninvestigation for possible leaks. Thermal image highlights temperature variation across the floor, this istherefore an indication of the location of the heating pipework under the floor.Spot temperature markershighlight temperature difference across floor where heating pipework is located.
Remarks:
3/15Page
Demonstration Thermography report
File:
IV_00663.BMT 09/04/2009
Measuring Time:
08:28:15
20.0Refl. temp. [°C]:
0.95Emissivity:
Picture parameters:
Date:
Picture markings:
RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects
-20.00.9520.9Measure point 1
-20.00.9523.5Measure point 2
-20.00.9520.6Measure point 3
Profile line:
Thermal Survey at a Domestic Property.Thermal and Digital images of Floor area taken as part of aninvestigation for possible leaks. Thermal image highlights temperature variation across the floor, this istherefore an indication of the location of the heating pipework under the floor.Spot temperature markershighlight temperature difference across floor where heating pipework is located.
Remarks:
4/15Page
Demonstration Thermography report
File:
IV_00383.BMT 08/12/2008
Measuring Time:
13:26:37
20.0Refl. temp. [°C]:
0.95Emissivity:
Picture parameters:
Date:
Picture markings:
RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects
Spot Temp 1 on Tiled Flooradjacent to radiator
20.00.9517.6Measure point 1
Spot Temp 2 on Tiled Flooradjacent to end of Skirting board
20.00.9516.9Measure point 2
Spot Temp 3 on Tiled Floor nextto glazed section
20.00.9516.6Measure point 3
Spot Temp 4 on Tiled floor areaaway from where the hot waterpipes are located
20.00.9514.3Measure point 4
Spot Temp 5 on Tiled floor areaaway from where the hot waterpipes are located
20.00.9514.2Measure point 5
Profile line:
Demonstration Thermal survey conducted with Testo 880 series Thermal Imaging camera. Conducted inGlazed walkway between Lounge and Kitchen extension.The homeowner is complaining of possible water leak under the tiled floor. At the time that this Thermal andDigital image were taken, the heat pattern effect from the hot water pipes under the floor were able to beseen in the the Thermal image, travelling the length of the walkway but no anomaly is apparent at this stage.Spot Temperatures have been added to the image to indicate the temperatures along the path of the pipes.A temperature profile line graph has been added to the thermal image, to highlight the temperature variationacross the tiled floor.
Remarks:
5/15Page
Demonstration Thermography report
File:
IV_00386.BMT 08/12/2008
Measuring Time:
13:32:32
20.0Refl. temp. [°C]:
0.95Emissivity:
Picture parameters:
Date:
Picture markings:
RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects
Spot Temp 1 to indicatetemperature variation across thefloor
20.00.9518.1Measure point 1
Spot Temp 2 to indicatetemperature variation across thefloor
20.00.9518.4Measure point 2
Spot Temp 3 to indicatetemperature variation across thefloor
20.00.9515.7Measure point 3
Spot Temp 4 to indicatetemperature variation across thefloor
20.00.9514.9Measure point 4
HS1 Hottest point on ThermalImage
20.00.9521.0Hot spot 1
Profile line:
Thermal survey conducted with Testo 880 series Thermal Imaging camera for Trace and Access application.In Glazed walkway between Lounge and Kitchen extension. The homeowner is complaining of possiblewater leak under the tiled floor. The Thermal image shows the heat pattern effect from the heating pipesunder the floor, travelling the length of the walkway and now a hot spot can be seen clearly. This is anindication of an anomaly, a possible leak from the central Heating system. The temperature in this area hasincreased and is indicating an anomaly that requires investigation.
Remarks:
6/15Page
Demonstration Thermography report
File:
IV_00585.BMT 10/03/2009
Measuring Time:
16:15:17
20.0Refl. temp. [°C]:
0.95Emissivity:
Picture parameters:
Date:
Picture markings:
RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects
Spot Temp 1 for temperaturecomparison.
20.00.9522.8Measure point 1
Spot Temp 2 for temperaturecomparison.
20.00.9515.5Measure point 2
Spot Temp 3 for temperaturecomparison.
20.00.9515.0Measure point 3
Spot Temp 4 for temperaturecomparison.
20.00.9523.4Measure point 4
Spot Temp 5 for temperaturecomparison.
20.00.9526.2Measure point 5
Profile line:
Thermal and Digital images of a domestic radiator.Taken with Testo 880 series Thermal imaging camera to demonstrate the capabilities of the camera and theTesto IR software.Spot temperature markers have been added to show the temperature variation across the radiator. Atemperature profile line graph has also been added to visually show the temperature profile across the raditorvertically.
Remarks:
7/15Page
Demonstration Thermography report
File:
IV_00596.BMT 10/03/2009
Measuring Time:
16:21:02
20.0Refl. temp. [°C]:
0.95Emissivity:
Picture parameters:
Date:
Picture markings:
RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects
Spot Temp 1 for temperaturecomparison.
20.00.9529.7Measure point 1
Spot Temp 2 for temperaturecomparison.
20.00.9526.0Measure point 2
Spot Temp 3 for temperaturecomparison.
20.00.9520.5Measure point 3
Profile line:
Thermal and Digital images of a domestic radiator.Taken with Testo 880 series Thermal imaging camera to demonstrate the capabilities of the camera and theTesto IR software.Spot temperature markers have been added to show the temperature variation across the radiator. Atemperature profile line graph has also been added to visually show the temperature profile across the raditordiagonally. The palette has been changed to Hot/Cold.
Remarks:
8/15Page
Demonstration Thermography report
File:
IV_00601.BMT 10/03/2009
Measuring Time:
16:24:10
20.0Refl. temp. [°C]:
0.95Emissivity:
Picture parameters:
Date:
Picture markings:
RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects
-20.00.9531.2Measure point 1
-20.00.9527.6Measure point 2
-20.00.9522.0Measure point 3
-20.00.9539.0Measure point 4
Histogram:
Profile line:
Thermal and Digital images of a domestic radiator.Taken with Testo 880 series Thermal imaging camera to demonstrate the capabilities of the camera and theTesto IR software.Additional spot temperature markers have been added to show the temperature variation across the radiator.A temperature profile line graph has also been added to visually show the temperature profile across theraditor diagonally. A Histogram has also been applied to the thermal image which defines the number oftemperature points at specific temperatures within a defined area.
Remarks:
9/15Page
Demonstration Thermography report
File:
IV_00537.BMT 29/01/2009
Measuring Time:
10:58:15
20.0Refl. temp. [°C]:
0.95Emissivity:
Picture parameters:
Date:
Picture markings:
RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects
Spot Temp 1 indicates Floortemperature above the coil
20.00.9529.5Measure point 1
Spot Temp 2 indicates Floortemperature above the coil
20.00.9529.4Measure point 2
Spot Temp 3, indicates the floortemperature at section wherethere is no heating coil
20.00.9522.7Measure point 3
Spot Temp 4 indicates Floortemperature above the coil
20.00.9528.9Measure point 4
Spot Temp 5 indicates Floortemperature above the coil
20.00.9529.1Measure point 5
Spot Temp 6, indicates the floortemperature at section wherethere is no heating coil
20.00.9524.8Measure point 6
Spot Temp 7 indicates Floortemperature above the coil
20.00.9530.0Measure point 7
Spot Temp 8 indicates Floortemperature above the coil
20.00.9529.1Measure point 8
Spot Temp 9, indicates the floortemperature at section wherethere is no heating coil
20.00.9524.5Measure point 9
Auto Hot spot indicator20.00.9533.9Hot spot 1
10/15Page
Demonstration Thermography report
Profile line:
Thermal and Digital Images of Office Floor, taken with the Testo 880 series Thermal Imaging camera.The Thermal image highlights the location of the underfloor heating coils.A temperature Profile Line graph has been applied to the Thermal image to verify the temperatures acrossthe underfloor heating coils.Spot temperature markers have been added to indicate the temperatures of the system at the floor surface.The thermal image is shown in "Iron" palette.
Remarks:
11/15Page
Demonstration Thermography report
File:
IV_00538.BMT 29/01/2009
Measuring Time:
10:58:30
20.0Refl. temp. [°C]:
0.95Emissivity:
Picture parameters:
Date:
Picture markings:
RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects
-20.00.9534.8Measure point 1
-20.00.9531.7Measure point 2
-20.00.9535.0Measure point 3
-20.00.9539.1Hot spot 1
Profile line:
Thermal and Digital Images of Office Floor, taken with the Testo 880 series Thermal Imaging camera.The Thermal image highlights the underfloor heating coils.The thermal image also has the auto Hot spot indicator applied to indicate automatically, the hottest point"HS1" in the designated area.A temperature Profile Line graph has been applied to the Thermal image to verify the temperatures acrossthe underfloor heating coils.Spot temperature markers have been added to indicate the temperatures of the system at the floor surface.The Thermal image is shown in "Iron" Palette.
Remarks:
12/15Page
Demonstration Thermography report
File:
IV_01244.BMT 04/09/2009
Measuring Time:
17:37:00
20.0Refl. temp. [°C]:
0.96Emissivity:
Picture parameters:
Date:
Picture markings:
RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects
-20.00.9624.9Measure point 1
-20.00.9644.4Measure point 2
-20.00.9651.0Measure point 3
-20.00.9643.4Measure point 4
Demonstration Thermal Survey, at a Domestic Property.Thermal and Digital images of Hot Water system,Dual Pump for shower. Thermal image highlights temperature variation across the equipment and pipework,Spot temperature markers highlight temperature difference in respect of the pipework and pump and indicatewhich sections are operational.
Remarks:
13/15Page
Demonstration Thermography Report to highlight the capabilities of the Testo Thermal Imaging cameraS and the Testo IR software.
This is an example report for Demonstration purposes only. The format is the "Standard" report template from the selection of Report Templates available in the software.
There are various subjects for the Thermal images and this report is compiled to indicate the capability of the cameras and the software for a number of applications in the HVAC Industry.
Some of the features of the camera and software have been applied to the Thermal images.
Spot Temperature markers have been added to the thermal images to indicate temperatures.
Auto Hot / Cold Spot Indicator has been applied, which automatically highlights the Hottest or Coldest point
Demonstration Thermography report
File:
IV_01224.BMT 04/09/2009
Measuring Time:
16:45:34
20.0Refl. temp. [°C]:
0.96Emissivity:
Picture parameters:
Date:
Picture markings:
RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects
-20.00.9644.7Measure point 1
-20.00.9647.8Hot spot 1
Profile line:
Demonstration Thermal Survey, at a Domestic Property.Thermal and Digital images of Hot Water Pump.Thermal image highlights temperature variation across the equipment and pipework, Spot temperaturemarkers highlight temperature difference in respect of the pipework and pump and indicate which sectionsare operational.
Remarks:
Review:
14/15Page
Demonstration Thermography report
Auto Hot / Cold Spot Indicator has been applied, which automatically highlights the Hottest or Coldest point in the defined area.
Temperature Profile Line Graph shows the temperature variation in graph form across the subject.
Palettes Various palettes (from the range available) have been used.
The images are automatically Time and Date Stamped to verify the time and date when the images were taken.
The report also details the Emissivity value relating to the image taken.
Andy McGrath - Testo