Cutler-HammerJanuary 2001Vol. 1, Ref. No. [04871
Molded Case Circuit Breakers10-225 Amperes 12-21
F-Frame
Product SelectionTable 12-33. Types ED, EDH, and EDC Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units Suitable for Reverse Feed
MaximumContinuousAmpereRating@40°C
100125150175200225
240V AC Maximum, 125V DC (Includes Terminals on Load End Only)
65 kAIC @ 240V ACType ED2-PoleCatalogNumber
ED2100ED2125ED2150ED2175ED2200ED2225
PriceU.S. $
357.357.357.357.357.357.
3-Pole
CatalogNumber
ED3100ED3125ED3150ED3175ED3200ED3225
PriceU.S. $
885.885.885.885.885.885.
1 00 kAIC @ 240V ACType EDH2-Pole
CatalogNumber
EDH2100EDH2125EDH2150EDH2175EDH2200EDH2225
PriceU.S. $
850.850.850.850.850.850.
3-Pole
CatalogNumber
EDH3100EDH3125EDH3150EDH3175EDH3200EDH3225
PriceU.S. S
1,280.1,280.1,280.1,280.1,280.1,280.
200 kAIC @ 240V ACType EDC Current Limiting2-PoleCatalogNumber
EDC2100EDC2125EDC2150EDC2175EDC2200EDC2225
PriceU.S. S
1,200.1,200.1,200.1,200.1,200.1,200.
3-PoleCatalogNumber
EDC3100EDC3125EDC3150EDC3175EDC3200EDC3225
PriceU.S. S
1,655.1,655.1,655.1,655.1,655.1,655.
Note: Instruction Leaflet/FRED Number 29C101
Table 12-34. Type EHD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units
MaximumContinuous
@40°C
10©1520253035 - -40455060708090
100
277V AC Maximum, 125V DC14 kAIC @ 277V AC
480V AC Maximum, 250V DC14 kAIC @ 480V AC
Type EHD (Includes Terminals on Load End Only)1-Pole
CatalogNumber
EHD1010EHD1015®EHD1020©EHD1025EHD1030EHD1035EHD1040EHD1045EHD1050EHD1060EHD1070EHD1080EHD1090EHD1100
PriceU.S.S
123.123.123.123.123.123.123.123.123.123.238.239.238.238.
2-PoleCatalogNumber
EHD2010EHD2015EHD2020EHD2025EHD2030EHD2035EHD2040EHD2045EHD2050EHD2060EHD2070EHD2080EHD2090EHD2100
PriceU.S.S
387.387.387.387.387.387.387.387.387.387.505.505.505.505.
3-PoleCatalogNumber
EHD3010EHD3015EHD3020EHD3025EHD3030EHD3035EHD3040EHD3045EHD3050EHD3060EHD3070EHD3080EHD3090EHD3100
PriceU.S.S
498.498.498.498.498.498.498.498.498.498.600.600.600.600.
© Not UL listed. 5 kAIC interrupting rating.® UL listed for SWD applications, see NEC Article 240-83 (d).
Note: Instruction Leaflet/FRED Number 29C101
Discount Symbol. CB-2
CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog F.T*N
12-2
For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E
January 2001
12
Product Line OverviewVol. 1, Ref. No. [0468]
Product Line DescriptionCutler-Hammer Molded Case Circuit Breakers are designed to provide circuit protection for low voltage distribution systems. They are described by NEMA as, “. . . a device for closing and inter-rupting a circuit between separable contacts under both normal and abnormal conditions,” and furthermore as, “. . . a breaker assembled as an integral unit in a supporting and enclosing housing of insulating material.” The NEC describes them as, “A device designed to open and close a circuit by non-automatic means, and to open the circuit automatically on a predetermined overload of current, without injury to itself when properly applied within its rating.”
So designed, Cutler-Hammer circuit breakers protect conductors against overloads and conductors and con-nected apparatus, such as motors and motor starters, against short circuits.
In low voltage distribution systems, there are many varied applications of molded case circuit breakers. Cutler-Hammer offers the most comprehensive family of molded case circuit breakers in the industry.
This family of circuit breakers includes:
■ Thermal Magnetic Trip Breakers■ Electronic rms Trip Breakers■ Molded Case Switches■ Motor Circuit Protectors■ Current Limiting Breakers■ Special Application Breakers■ World Breakers
Special CalibrationSpecial non-UL-listed calibrations are available for certain ambient temperatures other than 40°C and for frequencies other than 50/60 Hz or DC. Reduced interrupting ratings will apply for 400 Hz applications. Maximum thermal calibration is limited to 135A at 400 Hz.
50°C CalibrationAdd suffix V to Catalog Number for complete breaker, listed above, when ordering listed ampere ratings for breakers to be used in 50°C ambients.
Moisture-Fungus TreatmentAll circuit breaker cases are molded from glass-polyester which does not support the growth of fungus. Any parts which are susceptible to the growth of fungus will require special treatment.
Freeze-Tested Circuit BreakersThe circuit breakers may be ordered with freeze testing. This option uses special lubrication and mechanical operation is verified at -40°C.
Marine ApplicationsF-Frame circuit breakers can be sup-plied to meet the following marine specifications:
■ U.S. Coast Guard CFR 46 ABS — American Bureau of Shipping IEEE 45
These specifications generally require molded case circuit breakers to be supplied with 50°C ambient calibration, special nameplating, and plug-in adapter kits. When plug-in adapter kits are used, no terminals need be supplied.
Circuit breakers can also be supplied to meet UL489 Supplement SA (Marine Use) and UL489 Supplement SB (Naval Use).
UL489 Supplement SA applies to vessels over 65 feet in length. Requirements include 40°C ambient calibration, spe-cial labeling, and no use of aluminum conductors or terminals.
UL 489 Supplement SB requires 50°C ambient calibration, vibration testings, special nameplating and no use of aluminum conductors or terminals.
Standards and CertificationsMolded case circuit breakers are designed to conform with the follow-ing standards:
■ Underwriters Laboratories, Inc., Standard UL489, Molded Case Circuit Breakers and Circuit Breaker Enclosures
■ National Electrical Manufacturers Association Standards Publication No. AB1-1993, Molded Case Circuit Breakers
■ Australian Standard AS 2184, Molded Case Circuit Breakers
■ British Standards Institution Standard BS 4752: Part 1, Switchgear and Control Gear Part 1: Circuit Breakers
■ Canadian Standards Association Standard C22.2 No. 5, Service Entrance and Branch Circuit Breakers
■ International Electrotechnical Commission Recommendations IEC 157-1, Circuit Breakers
■ Japanese T-Mark Standard Molded Case Circuit Breakers
■ South African Bureau of Standards, Standard SABS 156, Standard Specification for Molded Case Circuit Breakers
■ Swiss Electro-Technical Association Standard SEV 157-1, Safety Regula-tions for Circuit Breakers
■ Union Technique de l’Electricite Standard NF C 63-120, Low Voltage Switchgear and Control Gear Circuit Breaker Requirements
■ Verband Deutscher Elektrotechniker (Association of German Electrical Engineers) Standard VDE 0660, Low Voltage Switchgear and Control Gear, Circuit Breakers
Conformance with these standards satisfies most local and international codes, assuming user acceptability and simplified application.
Molded case circuit breakers equal or exceed Federal Specification Classifi-cation W-C-375b requirements for the particular class associated with the cir-cuit breaker frame being considered.
Note: For further information, see Circuit Breaker, CD-ROM SA.74A.01.T.E.
Suffix H01 400 Hz 20% Adder
Suffix J01 Fungus Treated $325. + 20% Adder
Suffix F01 Freeze Tested 20% Adder
Suffix H08 “Marine” 10% Adder
Suffix H09 “Naval” 10% Adder
CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog
12January 2001 Product Line OverviewVol. 1, Ref. No. [0469]
Quick ReferenceTable 12-1. Industrial Circuit Breakers
� N.I.T. is non-interchangeable trip unit and I.T. is interchangeable trip unit.� Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250V DC.� Not defined in W-C-375b.
CircuitBreakerType
Cont.Amp.Rating@ 40°C
No.Poles
Volts Type of Trip �
Federal Spec.W-C-375b
UL Listed Interrupting Ratings rms Symmetrical Amperes PageNumberAC DC AC Ratings Volts DC �
120 120/240 240 277 480 600 125 250 125/250
G-FrameGBGB
15 – 10015 – 100
12, 3
120240
125125/250
N.I.T. 11a10b, 11b, 12b, 14b, 15b
65,000 —
——
—65,000
——
——
——
14,000—
——
—14,000
12-912-9
GHBGHBGHBGHBHGHBGQ
15 – 10015 – 10015 – 10015 – 10015 – 3015 – 20
12, 312, 311
120240277277/480277277
125125/250125125/250125—
N.I.T. 11a10b, 11b, 12b, 14b, 15b12c, 13a, 13b
65,000 ———65,00065,000
——————
—65,000————
——14,00014,000 25,00014,000
———14,000——
——————
14,000—14,000—14,000—
——————
—14,000 —14,000——
12-912-912-912-912-912-9
GHBSGBHS
15 – 3015 – 20
1, 21, 2
277/480347/600
——
—N.I.T.
——
65,000—
65,000—
——
14,000—
——
—10,000
——
——
——
11-1411-14
GCGC
15 – 10015 – 100
12, 3
120240
125125/250
N.I.T. 11a10b, 11b, 12b, 14b, 15b
65,000 —
——
—65,000
——
——
——
14,000—
——
—14,000
12-1112-11
GDGD
15 – 5015 – 100
23
480480
125/250250
N.I.T.N.I.T.
13b13b
——
——
65,00065,000
——
14,00022,000
——
——
—10,000
10,000—
12-812-8
GHCGHCGHCGHCHGHC
15 – 10015 – 10015 – 10015 – 10015 – 30
12, 312, 31
120240277277/480277
125125/250125125/250125
N.I.T. 12c, 13a13b12c, 13a13b
65,000 ———65,000
—————
—65,000———
——14,00014,000 25,000
———14,000—
—————
14,000—14,000—14,000
—————
—14,000—14,000—
12-1112-1112-1112-1112-11
New E125 FrameE125B 15 – 125 1
2, 3, 4277480
250 N.I.T. ——
35,000—
——
25,00025,000
18,000—
—18,000
——
10,000—
—10,000
——
12-16
E125E 15 – 125 2, 3, 4 600Y/347 250 N.I.T. — — — 35,000 — 25,000 18,000 10,000 10,000 — 12-16
E125S 15 – 125 12, 3, 4
347600Y/347
250 N.I.T.N.I.T.
——
100,000—
——
85,00085,000
35,000—
—35,000
—22,000
35,000—
—35,000
——
12-16
E125H 15 – 125 12, 3, 4
347600Y/347
250 N.I.T. ——
200,000—
——
100,000100,000
65,000—
—65,000
—25,000
42,000—
—42,000
——
12-17
F-FrameEDEDHEDC
100 – 225100 – 225100 – 225
2, 32, 32, 3
240240240
125125125
N.I.T. 12b14b1
———
———
65,000100,000200,000
———
———
———
10,00010,00010,000
———
———
12-2112-2112-21
EHDEHD
15 – 10015 – 100
12, 3
277480
125250
N.I.T. 13a13b
——
——
—18,000
14,000—
—14,000
——
10,000—
—10,000
——
12-2112-21
FDBFDB
15 – 15015 – 150
2, 34
600600
250250
N.I.T. 18a�
— —
——
18,00018,000
——
14,00014,000
14,00014,000
——
10,00010,000
——
12-2212-22
FDFDFD
15 – 22515 – 22515 – 225
12, 34
277600600
125250250
N.I.T. 13a22a�
— ——
— ——
—65,00065,000
25,000——
—25,00025,000
—18,00018,000
10,000——
—10,00010,000
— ——
12-2212-2212-22
HFDHFDHFD
15 – 22515 – 22515 – 225
12,3 4
277600600
125250250
N.I.T. 13a22a�
— ——
— ——
—100,000100,000
65,000——
—65,00065,000
—25,00025,000
10,000——
—22,00022,000
— ——
12-2212-2212-22
FDCFDC
15 – 22515 – 225
2, 3 4
600600
250250
N.I.T. 24a�
— —
— —
200,000200,000
— —
100,000100,000
35,00035,000
— —
22,00022,000
— —
12-2212-22
New J250 FrameJ250EJ250SJ250H
63 – 25063 – 25063 – 250
2, 3, 42, 3, 42, 3, 4
600600600
250250250
I.TI.TI.T
———
— ——
— ——
65,00085,000
100,000
———
25,00035,00065,000
18,00018,00025,000
———
10,00022,00022,000
— ——
12-2812-2812-28
Cutler-HammerJanuary 2001Vol. 1, Ref. No. [0485]
Molded Case Circuit Breakers10-225 AmperesF-Frame
12-19
ContentsDescription
Product Description
Technical Dataand Specifications
Dimension/Weights
Product Selection ..
F-FramePage
12-19
12-1912-2012-20
Product Description• All F-Frame Circuit Breakers are
HACR rated.• All circuit breakers 10 through
50 amperes are suitable for HID(high intensity discharge) use.
• All F-Frame circuit breakers aresuitable for reverse feed use.
Typical F-Frame Breaker
Technical Data and SpecificationsTable 12-28. UL489 Interrupting Capacity RatingsCircuitBreakerType
EDEDHEDCEHD
FOBFD
HFD
FDC
Numberof Poles
2,32,32,312,32,3,412,3,412,3,42,3,4
Interrupting Capacity (Symmetrical Amperes) (kA)Volts AC (50/60 Hz)240
65100200
1818
65
100200
277
—
14
—25
65
—
480
—
1414
25
65100
600
—
_
14
18
2535
Volts DC &125
10101 01 0
—10
10
—
250 @®
—
1 010
1 0
2222
© DC ratings apply to substantially non-inductive circuits.® 2-pole circuit breaker, or two poles of 3-pole circuit breaker.® Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.
Table 12-29. IEC 157-1 (PI) Interrupting Capacity Ratings (P1)
CircuitBreakerType
EDEDHEDCFOBFD
HFD
FDC
Number ofPoles
2,32,32,32,3,4
12,3,412,3,4
2,3,4
Interrupting Capacity (Symmetrical Amperes) (kA)Volts AC (50/60 Hz)220, 240
65100200
18
2565
65100
200
380,415
—
14
35
65
100
440
—
14
35
65
100
500
—
14
18
25
35
Volts DC A125
101010
—10
10
—
250 @®
—
10
10
22
22
® DC ratings apply to substantially non-inductive circuits.® 2-pole circuit breaker, or two poles of 3-pole circuit breaker.© Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.
CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog F.T.N
12-20 Molded Case Circuit Breakers10-225 AmperesF-Frame .. f-i -i
Cutler-HammerJanuary 2001
Vol. 1, Ref. No. [0486J
Dimensions/WeightsTable 12-30. Dimensions in Inches (mm)Numberof Poles
12
34
Width
1.375(35)2.75 (70)
4.125(105)5.5(140)
Height
6(152)6(152)
6(152)6(152)
Depth
3.375 (86)3.375 (86)
3.375 (86)3.375 (86)
Table 12-31. Approximate Shipping Weight, Lbs. (Kg)Breaker Type
ED, EDH, EDC
EHD, FOB, FD, HFD, FDC
Number of Poles1
—2 (.907)
2 3
3(1.361)
3(1.361)
4.5(2.041)
4.5(2.041)
4
—
6(2.721)
Product SelectionThis information is presented only as an aid to understanding Catalog Numbers. It is not to be used to build Catalog Numbersfor circuit breakers or trip units.
Table 12-32. Circuit Breaker Catalog Numbering System
FDC 3 100 L
Circuit BreakerType
EHDFOBFDHFDFDC
Numberof Poles
1 = 1 Pole2 = 2 Poles3 = 3 Poles4 = 4 Poles
Trip Ar
010015020025030035
J
0450500600700800901001 1 0125150175 (FD,200 (FD,225 (FD,
HFD, FDC, 2-, 3-, 4-Pole Only)HFD, FDC, 2-, 3-, 4-Pole Only)HFD, FDC, 2-, 3-, 4-Pole Only)
Circuit BreakerType
EDEDHEDC
Numberof Poles
2 = 2-Pole3 = 3-Pole
200
SuffixE = 100% Protected (4-Pole only) Neutral PoleEH = 50% Protected (4-Pole only)K = High Magnetic Molded Case SwitchL = Line and Load TerminalsS = Stainless Steel TerminalsV = 50°C CalibrationW = Without TerminalsY = Line Terminals OnlyZ = Aluminum Terminals (< 100 Amperes)
SuffixL = Line and Load TerminalsW = Without TerminalsY = Line Terminals OnlyZ = Aluminum Terminals (100 Amperes)
X
E:T*M For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E
Cutler-HammerJanuary 2001Vol. 1, Ref. No. I0489]
Molded Case Circuit Breakers10-225 AmperesF-Frame
12-23
Molded Case SwitchesMolded Case Switches are used ascompact switches in applicationsrequiring high current switchingcapabilities. Molded case switchesare constructed of circuit breakercomponents and are of the highinstantaneous automatic type. Moldedcase switches are listed in accordancewith Underwriters Laboratories, Inc.,Standard UL 1087.
Line and Load TerminalsLine and Load Terminals provide wireconnecting capabilities for specificranges of continuous current ratingsand wire types. Except as noted,terminals comply with UnderwritersLaboratories, Inc., Standards UL486Aand UL486B. Unless otherwisespecified, F-Frame circuit breakersare factory equipped with loadterminals only.
Ordering InformationF-Frame circuit breakers and moldedcase switches have load terminalsonly as standard equipment. Whenstandard line-end terminals (same asstandard load-end terminals) arerequired, add Suffix L to the circuitbreaker Catalog Number. When non-standard or optional line and/or loadterminals are required, order by stylenumber. Specify if factory installationis required.
Table 12-37. Molded Case SwitchesMaximumContinuousAmpere Rating@40°C
480V AC Maximum,250V DCComplete Circuit Breakerwith Load Side Terminals OnlyCatalogNumber
PriceU.S. S
600V AC Maximum,250V DCComplete Circuit Breakerwith Load Side Terminals OnlyCatalogNumber
PriceU.S. $
2-Pole100150225
EHD2100K 476. FD2100KFD2150KFD2225K
535.001,135.001,135.00
3-Pole100150225
EHD3100K 570. FD3100KFD3150KFD3225K
665.001,240.001,190.00
4-Pole100150225 E —
FD4100KFD4150KFD4225K
930.001,735.001,665.00
Note: Molded Case Switches may open above 1800 amperes.Note: Instruction Leaflet/FRED Number 29C101
Table 12-38. Line and Load TerminalsMaximumBreakerAmperes
Terminal BodyMaterial
Wire Type AWG WireRange
Metric WireRange mm2
Package of 3 TerminalsCatalogNumber
PriceU.S. $
Standard Pressure Type Terminals20 (END)
100225
SteelSteelAluminum
Cu/AICu/AICu/AI
14-1014-1/014-4/0
2.5- 42.5- 50
25 - 95
3T20FB ©3T100FB3TA225FD
6.106.10
89.00Optional Pressure Terminals
50100200225
AluminumAluminumStainless SteelAluminum
Cu/AICu/AICuCu/AI
14-414-1/04-4/06 - 300 kcmil
2.5- 252.5- 50
25 - 9516 -150
3TA50FB ®3TA100FD3T150FB3TA225FDK i
6.106.106.10
89.00® Not for use with ED, EDH, EDC breakers.® Includes terminal shield kit. Adds approximately 3 inches (76.2) to breaker height. Available for
use on 3-pole breaker only.
Discount Symbol. CB-2
CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog E:t>N