Consult + Engineer + Commission Creating Exceptional Environments © All Rights Reserved January...

Post on 27-Mar-2015

216 views 3 download

Tags:

Transcript of Consult + Engineer + Commission Creating Exceptional Environments © All Rights Reserved January...

Consult + Engineer + Commission

Creating Exceptional EnvironmentsCreating Exceptional Environments

www.syska.com© All Rights Reserved

January 18, 2011

“UNINTERRUPTIBLE POWER SYSTEM (UPS) TECHNOLOGY

UPDATE”

IEEE Industry Applications Society Atlanta Chapter

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

2

TYPES OF UPS TECHNOLOGIES

•STATIC, DOUBLE CONVERSION

•STATIC, LINE INTERACTIVE

•FLYWHEEL-BASED

•ROTARY

•OFF-LINE

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

3

STATIC, DOUBLE CONVERSION UPS TOPOLOGY

•NORMAL POWER PATH: INPUT-RECTIFIER-DC BUS- INVERTER-OUTPUT

•BYPASS POWER PATH: INPUT-STATIC SWITCH-OUTPUT

•STORED POWER PATH: BATTERY/FLYWHEEL-DC BUS- INVERTER-OUTPUT

•MAJOR MANUFACTURERS: GE, LIEBERT, MGE, MITSUBISHI, POWERWARE, TOSHIBA

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

4

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

5

STATIC, DOUBLE CONVERSION UPS CHANGES FOR INCREASED OPERATING EFFICIENCY

•PWM IGBT RECTIFIERS INSTEAD OF SCRS•PWM IGBT INVERTERS•ELIMINATE INPUT AND OUTPUT TRANSFORMERS•USER-SELECTABLE OFFLINE OPERATION•USER-SELECTABLE CAPACITY CONTROL•DISTRIBUTED OR SYSTEM STATIC BYPASS SWITCH

Consult + Engineer + Commission

© All Rights Reserved 6

STATIC, DOUBLE CONVERSION UPS OPERATING EFFICIENCY

•TYPICALLY 91%-96% AT FULL LOAD AND 90%- 94% AT HALF LOAD

•USER-SELECTABLE OFFLINE 98%

•USER-SELECTABLE CAPACITY CONTROL CAN IMPROVE % AT LOW LOADS

UPS TECHNOLOGY UPDATE

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

7

THE FLEAS THAT COME WITH THE DOG, PART 1

•ELIMINATING TRANSFORMERS REDUCES DC BUS SAFETY•INDUSTRY TREND IS TO ELIMINATE TRANSFORMERS•ELIMINATING THE OUTPUT TRANSFORMER MAY ELIMINATE A WYE-CONNECTED OUTPUT•INDUSTRY TREND IS TO PROVIDE DISTRIBUTED STATIC BYPASS SWITCHES•IN USER-SELECTABLE OFFLINE MODE, SOME TRANSIENTS COULD GET THROUGH BEFORE THE UPS CAN REACT

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

8

STATIC, LINE-INTERACTIVE UPS TOPOLOGY

•NORMAL POWER PATH: INPUT-MAIN STATIC SWITCH-OUTPUT

•BYPASS POWER PATH: INPUT-ALTERNATE STATIC SWITCH-OUTPUT

•STORED POWER PATH: BATTERY-DC BUS-INVERTER- OUTPUT

•MANUFACTURER: APC (SYMMETRA MW)

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

9

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

10

STATIC, LINE INTERACTIVE UPS CHANGES FOR INCREASED OPERATING EFFICIENCY

•IMPROVED FIRMWARE CONTROL

STATIC, LINE INTERACTIVE UPS OPERATING EFFICIENCY

•TYPICALLY 97% AT FULL LOAD, 96% AT HALF LOAD AND 94% AT QUARTER LOAD

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

11

THE FLEAS THAT COME WITH THE DOG, PART 2

•REDUCED DC BUS SAFETY

•SOME TRANSIENTS COULD GET THROUGH BEFORE THE UPS CAN REACT

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

12

FLYWHEEL-BASED UPS TOPOLOGY

•NORMAL POWER PATH: INPUT-MAIN STATIC SWITCH-INDUCTOR-OUTPUT

•BYPASS POWER PATH: INPUT-ALTERNATE STATIC SWITCH-OUTPUT

•STORED POWER PATH: FLYWHEEL-CONVERTER- INDUCTOR-OUTPUT

•MANUFACTURER: ACTIVE POWER

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

13

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

14

FLYWHEEL-BASED UPS CHANGES FOR INCREASED OPERATING EFFICIENCY

•IMPROVED FIRMWARE CONTROL

STATIC, LINE INTERACTIVE UPS OPERATING EFFICIENCY

•TYPICALLY 98% AT FULL LOAD AND 96% AT HALF LOAD

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

15

THE FLEAS THAT COME WITH THE DOG, PART 3

•LIMITED ENERGY STORAGE – 14 SECONDS

•SYSTEM CAPACITY LIMITED BY THE CAPACITY OF ONE STANDBY GENERATOR

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

16

BASIC ROTARY UPS TOPOLOGY

•NORMAL POWER PATH: INPUT-RECTIFIER-INVERTER-SYNCHRONOUS MACHINE-OUTPUT

•BYPASS POWER PATH: INPUT-STATIC SWITCH - SYNCHRONOUS MACHINE –OUTPUT

•STORED POWER PATH: BATTERY-DC BUS-INVERTER- SYNCHRONOUS MACHINE-OUTPUT

•MANUFACTURER: PILLER

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

17

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

18

VARIATION ON ROTARY UPS TECHNOLOGY, AKA DYNAMIC ROTARY UPS (DRUPS)

•NORMAL POWER PATH: INPUT-RECTIFIER-COUPLING CHOKE-OUTPUT•BYPASS POWER PATH: INPUT-BYPASS SWITCH - OUTPUT•STORED POWER PATH: ENGINE-COUPLING-ENERGY ACCUMULATOR-SYNCHRONOUS MACHINE- COUPLING CHOKE-OUTPUT•CAN OPERATE AT LOW VOLTAGE OR MEDIUM VOLTAGE •MANUFACTURERS: EURO-DIESEL, HITEC, PILLER

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

19

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

20

ROTARY UPS CHANGES FOR INCREASED OPERATING EFFICIENCY

•IMPROVED FIRMWARE CONTROL•USER-SELECTABLE OFFLINE OPERATION

ROTARY UPS OPERATING EFFICIENCY

•TYPICALLY 92% AT FULL LOAD AND 88% AT HALF LOAD (BASIC)•TYPICALLY 96% AT FULL LOAD AND 48% AT HALF LOAD (VARIATION)

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

21

THE FLEAS THAT COME WITH THE DOG, PART 4

•VARIATION IS THE MOST UPS CAPACITY/SQUARE FOOT OF BUILDING AREA

•VARIATION HAS CONSTANT LOSSES, REGARDLESS OF LOAD

•VARIATION CAN SUPPLY LARGE MEDIUM VOLTAGE SYSTEMS (VOLTAGE VARIES

BY MANUFACTURER)

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

22

OFFLINE UPS TOPOLOGY

•NORMAL POWER PATH: INPUT-STATIC SWITCH- OUTPUT•BYPASS POWER PATH: INPUT-BYPASS SWITCH- OUTPUT•STORED POWER PATH: BATTERY-INVERTER-STEPUP TRANSFORMER-OUTPUT•CAN OPERATE AT LOW OR MEDIUM VOLTAGE (UP TO 25KV)•MANUFACTURER: S&C

Consult + Engineer + Commission

© All Rights Reserved 23

Consult + Engineer + Commission

© All Rights Reserved

UPS TECHNOLOGY UPDATE

24

OFFLINE UPS CHANGES FOR INCREASED OPERATING EFFICIENCY

•CAPACITY UP TO 16MW PER SYSTEM•IMPROVED FIRMWARE•CAN ACCOMMODATE WET CELL OR VRLA BATTERIES•CAN ACCOMMODATE UP TO 20 MINUTES BATTERY OPERATION AT FULL LOAD•CAN BE INSTALLED INDOORS OR OUT DOORS•CAN UTILIZE METAL-ENCLOSED OR METAL-CLAD SWITCHGEAR•DISTRIBUTED OR SYSTEM STATIC BYPASS SWITCH

Consult + Engineer + Commission

© All Rights Reserved 25

OFFLINE UPS OPERATING EFFICIENCY

•TYPICALLY 98%-99% AT ALL LOADS

THE FLEAS THAT COME WITH THE DOG, PART 5

•SOME TRANSIENTS COULD GET THROUGH BEFORE THE UPS CAN REACT

Consult + Engineer + Commission

Creating Exceptional EnvironmentsCreating Exceptional Environments

www.syska.com© All Rights Reserved

Thank You!Comments and Questions?