Circuit Breakers and Busbars. Circuit Breakers Altech’s Circuit Breaker Line UL1077 (R-Series)...

Post on 15-Dec-2015

217 views 2 download

Transcript of Circuit Breakers and Busbars. Circuit Breakers Altech’s Circuit Breaker Line UL1077 (R-Series)...

Circuit Breakersand

Busbars

Circuit Breakers

Altech’s Circuit Breaker Line

• UL1077 (R-Series)

• UL508 (V-EA Series)

• UL489 (L-Series, AB-Series)

Circuit Breakers

R-Series(UL1077 Recognized Supplementary Protector)

• Short Circuit Withstand Rating 10kA@480Y/277VAC (48VDC rating self-certified)

• B, C, D Trip Curve (0.5-63A)• 1,2,3,4 pole• Accessories: Add-on Neutral Pole, Shunt Trip, Undervoltage Trip,

Auxiliary Contact • UL listed Busbars

Circuit Breakers

V-EA Series(UL508 listed Manual Motor Controller)

• Short Circuit Withstand Rating 10kA@480Y/277VAC, 50/60Hz

• B (1-63A), C (0.3-63A), D (0.3-63A)), E (0.3-63A), G (0.3-63A), Z (0.3-50A) Trip Curve

• 1,2,3,4 pole

• 1 pole plus Neutral

• Accessories: Add-on Shunt Trip, Undervoltage Trip, Auxiliary Contact

• UL listed Busbars

Circuit Breakers

L-Series(UL489 listed Miniature Molded Case Circuit Breaker)

• Voltage Rating 240VAC (0.2-63A), 480Y/277VAC (0.2-32A), 125VDC (1 pole)/ 250VDC (2 pole) (0.2-63A)

• 10kA Short Circuit Interrupt Capacity

• AC and DC

• C, D Trip Curve

• 1,2,3,4 pole

• Accessories: Add-on Neutral Pole, Shunt Trip, Undervoltage Trip, Auxiliary Contact

• UL listed Busbars

Circuit Breakers

AB-Series(UL489 listed Molded Case Circuit Breaker)

• Interrupting Capacity up to 100kA (240VAC)

• Thermal Magnetic

• Door Interlock Handle

• 3 pole

• Accessories: Auxiliary Switch, Alarm Switch, Shunt/ Undervoltage Trip

Circuit Breakers

UL Standards and its Functions

Standard Function

Circuit Breakers

UL Standards and its Functions

Standard Function

UL1077 Supplementary Protector

Overload Protection

Circuit Breakers

UL Standards and its Functions

Standard Function

UL1077 Supplementary Protector

UL508 Manual Motor Controller

Overload Protection

Overload Protection Switching Function Disconnect Function* *when suitable for disconnect means

Circuit Breakers

UL Standards and its Functions

Standard Function

UL1077 Supplementary Protector

UL508 Manual Motor Controller

UL489 (Miniature) Molded Case Circuit Breaker

Overload Protection

Overload Protection Switching Function Disconnect Function* *when suitable for disconnect means

Overload Protection Switching Function Disconnect Function Short Circuit Protection

Application Example

Circuit Breakers

Typical UL508A Panel

Circuit Breakers

Typical UL508A Panel

Circuit Breakers

Typical UL508A Panel

Circuit Breakers

Typical UL508A Panel

Busbars

Altech’s Busbar Line

• UL508 listed Busbars

• UL489 listed Busbars

Busbars

Distribution Block Busbare.g. #38049 (80A, 1xInput, 6xOutput)

Busbars

Distribution Block Busbar

Input Phase 1

80A

Input Phase 2

80A

Input Phase 3

80A

80A Outputs Phase 1

80A Outputs Phase 1

80A Outputs Phase 1

e.g. #38049 (80A, 1xInput, 6xOutput)

Busbars

Distribution Block Busbar

80A Outputs Phase 1

80A Outputs Phase 1

80A Outputs Phase 1

Input Phase 1

80A

Input Phase 2

80A

Input Phase 3

80A

e.g. #38049 (80A, 1xInput, 6xOutput) e.g. #P50UT + #3P18U318

Busbars

Distribution Block Busbar

Inputs 80A per Phase

Outputs

80A per

Phase

1 2 3

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

80A

80A Outputs Phase 1

80A Outputs Phase 1

80A Outputs Phase 1

Input Phase 1

80A

Input Phase 2

80A

Input Phase 3

80A

e.g. #38049 (80A, 1xInput, 6xOutput) e.g. #P50UT + #3P18U318

80A

Busbars

Distribution Block Busbar

Inputs 80A per Phase

Outputs

80A per

Phase

1 2 3

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

80A80A

80A Outputs Phase 1

80A Outputs Phase 1

80A Outputs Phase 1

Input Phase 1

80A

Input Phase 2

80A

Input Phase 3

80A

e.g. #38049 (80A, 1xInput, 6xOutput) e.g. #P50UT + #3P18U318

80A

Busbars

Distribution Block Busbar

Inputs 80A per Phase

Outputs

80A per

Phase

1 2 3

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

80A80A80A

80A Outputs Phase 1

80A Outputs Phase 1

80A Outputs Phase 1

Input Phase 1

80A

Input Phase 2

80A

Input Phase 3

80A

e.g. #38049 (80A, 1xInput, 6xOutput) e.g. #P50UT + #3P18U318

80A 80A 80A

Busbars

Distribution Block Busbar

Inputs 80A per Phase

Outputs

80A per

Phase

Busbar:

-no wiring between distribution and control device

-Installation-time saving

1 2 3

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

80A80A80A

80A Outputs Phase 1

80A Outputs Phase 1

80A Outputs Phase 1

Input Phase 1

80A

Input Phase 2

80A

Input Phase 3

80A

e.g. #38049 (80A, 1xInput, 6xOutput) e.g. #P50UT + #3P18U318

80A 80A 80A

Busbars

Power Feed (Power Input) Methods (1)

1 2 3

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

80A80A80A

80A 80A 80A

1)Start/End Feed-Method (e.g. with Power Feed Lug P50UT and 18mm² Busbar)

3P18U3/18

Busbars

Power Feed (Power Input) Methods (2)

1 1 1 1 1 1

80A

1 2 3115A

2)Center/Middle Feed-Method (e.g. with Power Feed Lug P50UT and 18mm² Busbar)

35A

3P18U3/18

Busbars

Power Feed (Power Input) Methods (3)

1 2 1 2 1 2 1 2 1 2 1 2

80A80A

1 2 3115A 115A

2)Center/Middle Feed-Method (e.g. with Power Feed Lug P50UT and 18mm² Busbar)

35A35A

3P18U3/18

Busbars

Power Feed (Power Input) Methods (4)

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

80A80A80A

1 2 3115A 115A115A

2)Center/Middle Feed-Method (e.g. with Power Feed Lug P50UT and 18mm² Busbar)

35A35A35A

3P18U3/18

Busbars

Power Feed (Power Input) Methods (5)

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

80A80A80A

1 2 3115A 115A115A

2)Center/Middle Feed-Method (e.g. with Power Feed Lug P50UT and 18mm² Busbar)

35A35A35A

35A + 80A = 115A

3P18U3/18

Busbars

Power Feed (Power Input) Methods (6)

2)Center/Middle Feed-Method (e.g. with Power Feed Block P95UB and 25mm² Busbar)

P95UB

Ph

ase

3

Ph

ase

2

Ph

ase

1

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2

3P25U3/18

BRS5

Busbars

Power Feed (Power Input) Methods (6)

1 1 1 1

100A

2)Center/Middle Feed-Method (e.g. with Power Feed Block P95UB and 25mm² Busbar)

100A

200A Input Phase 1

P95UB

3P25U3/18

Busbars

Power Feed (Power Input) Methods (6)

1 2 1 2 1 2 1 2

100A100A

2)Center/Middle Feed-Method (e.g. with Power Feed Block P95UB and 25mm² Busbar)

100A100A

200A Input Phase 1

200A Input Phase 2

P95UB

3P25U3/18

Busbars

Power Feed (Power Input) Methods (7)

1 2 3 1 2 3 1 2 3 1 2 3

100A100A100A

2)Center/Middle Feed-Method (e.g. with Power Feed Block P95UB and 25mm² Busbar)

100A100A100A

200A Input Phase 1

200A Input Phase 3

200A Input Phase 2

P95UB

3P25U3/18

Busbars

UL1077/508 Busbar System (1)

• Electrical Rating: 80A@480VAC (18mm² Pins), 100A@480VAC (25mm² Pins)

• 1,2,3 Phase

• Any possible Pin configuration (1-57Pins)

• ½ pole spacing (auxiliary switch) available

• Power feeding: Power Feed Lugs (115A), Direct Power Feed (80A), Power Feed Block (200A)

• UL508 listed

Busbars

UL1077/508 Busbar System (2)

• Busbars can be cut to customers needs without loosing UL-approval

• UL recognized and listed for Altech’s R-Series, V-EA Series and MA Series of Manual Motor Controllers and Supplementary Protectors

• UL recognized and listed for use with most competitor’s UL1077 supplementary protectors and UL508 Manual Motor Controllers

Busbars

UL489 Busbar System (1)

• Electrical Rating: 80A@480VAC (16mm² Pins)

• 1,2,3 Phase

• 6, 12, 18 Pin configuration

• Power feeding: Power Feed Lugs (115A), Direct Power Feed (80A)

• UL489 listed

Busbars

UL489 Busbar System (2)

• Every Pin configuration possible by combination of existing 6, 12 and 18 Pin Busbars

• UL listed for Altech’s L-Series of Miniature Molded Case Circuit Breaker

• UL listed for use with most competitor’s UL489 Miniature Molded Case Circuit Breaker

Busbars

Configuration of UL489 Busbars (1)

• UL489 Busbars are available in 3 different Pin Configurations per Phase (6, 12 and 18 Pins)

• They can’t be cut, since the creapage and clearance distance requirements from UL are too stringent.

• Therefore to obtain the desired No. of Pins, Busbars can and must be overlapped

Busbars

Configuration of UL489 Busbars (2)1) Busbars are overlapped backwards to each other

Configuration Examples:

1 Phase Busbars 3 Phase Busbars

Busbars

Configuration of UL489 Busbars (3)1) Busbars are overlapped backwards to each other

2) The Number of overlapping Pins of 2 Busbar must be a multiplier of the Number of Phases to keep existing Phase sequence. (Can be overlapped by more than the number of phases)

Configuration Examples:

1 Phase Busbars 3 Phase Busbars

Busbars

Configuration of UL489 Busbars (4)1) Busbars are overlapped backwards to each other

2) The Number of overlapping Pins of 2 Busbar must be a multiplier of the Number of Phases to keep existing Phase sequence. (Can be overlapped by more than the number of phases)

3) Any available combination of the 3 different Pin configurations is possible

Configuration Examples:

1 Phase Busbars 3 Phase Busbars

Thank You!!