Photo/isometric drawing
provided by manufacturer
BalconIE System
Description of Product
This is an assessment of BalconIE system
produced by BalconIE Ltd. The system
comprises of a prefabricated and pre-
engineered composite (steel/polyurethane resin
core/steel plate) sandwich panel stiffened
along the perimeter by HSS frame and steel
fascia plates to which an approved guarding
system may be fixed. The panel is fixed on top
of concrete floor by Halfen channels and bolts
or by mechanical anchors or chemical fixings.
Key Factors Assessed
Mechanical Resistance & Stability
Safety in case of Fire
Health, Hygiene and Environmental
Safety in Use
Durability serviceability and identification
Validity
This certificate was first issued on 16th September 2016 and is valid until 16th September 2019
Issue Dated 31st July 2018
Certificate No: EW691
The registered system is suitable for use in low to high rise buildings of residential and hotel accommodation where the
balcony serves a single unit (please refer to conditions of certificate for more information).
Individual design will be submitted for each balcony type required per project.
Provision of Guarding and handrails are outside of the scope of this registration. The system is designed to accommodate
the standard range of fixings. The balcony system does however cover the shear and overturning calculations for the
guarding fixing plate. Confirmation of acceptability will be forwarded by BalconIE once commissioned.
The system has a maintenance free life of over 25 years. It is protected from the environment by a double coating build up
and a waterproof membrane. It can be installed from within the building using a small crawler crane and can be reused in a
different location.
The system can be used to incorporate a winter garden. This is however, outside of the scope of this Registered Detail and
should be discussed separately with individual building control teams.
If the balcony offers alternate escape to adjoining spaces it will be outside of the scope of this registration and fire protection
will need to be considered.
In line with the amendments to Building Regulation 7 (2) which came into effect on December 21 2018, this system
cannot be used on any relevant building with a storey at least 18m above ground level and which contains one or more
dwellings; an institution; or a room for residential purposes (excluding any room in a hostel, hotel or a boarding house).
This includes student accommodation, care homes, sheltered housing, hospitals and dormitories in boarding schools. For
more information on the changes to Regulation 7 please click here -
https://assets.publishing.service.gov.uk/government/uploads/system/uploads/attachment_data/file/760341/AD_7_v2_amend_2.pdf
This registration is for the tray and components only and design will be provided for:
1. Location plan and the design of the floor intended to accommodate the registered detail.
2. BalconIE design and fixing details for the types proposed
3. Details of guarding and handrails proposed
4. Details of connections and specification if enclosed winter garden proposed to determine appropriate fire resistances
can be achieved
LABC consider that, BalconIE System will meet the functional requirements of the Building Regulations
(listed below) if the criteria detailed in this certificate are met;
The Building Regulations 2010 (as amended) England & Wales
Regulation 7 Materials and Workmanship
Note: The system is acceptable.
AD A Structure
Note: The system is acceptable subject to site specific design.
AD B Fire Safety
Note: Subject to limitations detailed in Conditions section.
AD C Resistance to Moisture
Note: The system is acceptable subject to site specific design.
AD K Protection from falling collision & impact
Note: Subject to limitations detailed in Conditions section.
AD L1B, 2A/B Conservation of Fuel and Power
Note: The system is acceptable in relation to thermal break provisions
The Building Regulations 2010 (as amended) England
AD L1A Conservation of Fuel and Power
Note: The system is acceptable in relation to thermal break provisions
The Building Regulations 2010 (as amended) Wales
AD L1A Conservation of Fuel and Power
Note: The system is acceptable in relation to thermal break provisions
The Building (Scotland) Regulations 2004 (as amended)
If you would like to discuss a specific use of the product in Scotland it will require an additional
assessment under the Scottish Building Regulations and accordingly you should contact the LABSS
STAS Administrator at www.labss.org
LABC Warranty
The use of the BalconIE System has not been assessed to meet the requirements of the LABC Warranty
Technical Manual. If you would like to discuss a specific use please make an enquiry to
technical.services@labcwarranty.co.uk
IE-15-1131-P1.1, P1.2, P1.3 and P1.4
IE-15-1131- P0.1, P0.2 and P0.3
0001-01-02 Rev A
BalconIE brochure
IE-2016-04-04 SPS Balconies - Design Report
SSD Peer Review Balcony system Peer Review Job: 01020 Issue Dated 10th April 2016 Revision A
BRE Report No: P104699-1007 Issue 1
BalconIE Ltd
Allen House
1 Westmead Road
Sutton
Surrey
SM1 4LA
Tel: 020 861 40775
Email: sales@balconie.co.uk
Web: www.balconie.co.uk